Metering the Customer

Embed Size (px)

Citation preview

  • 8/2/2019 Metering the Customer

    1/21

  • 8/2/2019 Metering the Customer

    2/21

    CTs are used in determining the line current. Theprimary winding is connected in series with theconductor leads and the secondary leads are

    connected to the current coil of the meter. The currenttransformers usually have a secondary side ampacity of5A.

    The marked ratio of a CT is the ratio of primary current tosecondary current.

  • 8/2/2019 Metering the Customer

    3/21

    Before the CT and VT ratios can be determined,the following information is needed:

    i. Customers reserve capacityii. Supply voltageiii. Customers transformer configuration if high -voltage

    meter

    =tage xSupplyVol3

    CapacityReserve

  • 8/2/2019 Metering the Customer

    4/21

    ExampleCustomer Reserve Capacity= 365kVA

    Supply Voltage=12000V

    IL =

    = 17.56AThis represents the current in the primary of the CT

    120003

    365000

    x

  • 8/2/2019 Metering the Customer

    5/21

    CT ratios for LVMetering

    200:5

    400:5

    CT ratios for HVMetering

    25:5

    50:5100:5150:5200:5300:5

  • 8/2/2019 Metering the Customer

    6/21

    From the exampleCT with the ratio of 25:5 would be chosen

    The rating factor of CT is also noted.

  • 8/2/2019 Metering the Customer

    7/21

    VT are only used for Metering on the HV.

    If a four-wire metering unit is used, the reference wire

    used is the neutral wire, this would result in phasevoltages being imposed on the voltage transformer.

    For the three-wire metering units, the reference wire

    used is a live phase and as such phase-to-phasevoltages would be imposed on the voltage transformer.

  • 8/2/2019 Metering the Customer

    8/21

    ExampleSupply voltage =12000VPrimary is 4W star

    The phase voltages would be measuredPhase voltage=6900VTherefore, 3VTs would be required.VT with a ratio of 7200:120 would be chosen.

  • 8/2/2019 Metering the Customer

    9/21

    Supply voltagecharacteristic

    VTR used

    6.6 kV (3-wire) 7200:120

    12 kV (4-wire) 7200:12012 kV (3-wire) 12000:12033 kV (3-wire) 33000:11066 kV (3-wire) 66000:110

    132 kV (3-wire) 132000:110

  • 8/2/2019 Metering the Customer

    10/21

    The value of the current to be measured woulddetermine the type of meter to be used.

    Less than 200A- Non transformer type201-500A- Low-Voltage Meter Installation, CTmetering is to be done.Above 500A- Three-phase 115/230V, and 230/400V

    installation requiring over 500A are to be metered athigh-voltage (Metering Units)

  • 8/2/2019 Metering the Customer

    11/21

    Form Wires Circuit Class

    1S 2 115V, 1 200

    2S 3 115/230V1

    200

    16S 4 115/230V230/400

    3

    200

  • 8/2/2019 Metering the Customer

    12/21

    Form Wires Class Circuit CustomerReserve

    Capacity16S 4 200 115/230

    3 Delta50-80kVA

    230/400V3 Star

    50-138kVA

    10A(Used if I L >

    500A)

    4 20 115/2303 Delta

    80-199kVA

    230/400V3 Star

    80-350kVA

  • 8/2/2019 Metering the Customer

    13/21

    Form Wires Class Circuit CustomerReserveCapacity

    10A 4 200 6.6kV/12kV/33kV/66kV

    Exceeding350kVA andless than4000kVA

  • 8/2/2019 Metering the Customer

    14/21

    AvailabilityFor domestic use

    Character of ServiceSingle phase: 2-wires or 3-wires 115/230 voltsBilled on energy consumed ( kWh ).

  • 8/2/2019 Metering the Customer

    15/21

    Maximum demand of 50 kVA.Single phase: 3-wires 115/230 voltsThree phases: 4-wires 115/230 volts or 230/400 volts

    Three phases: 6.6, 12 kilovoltsBilled on energy consumed ( kWh ).

  • 8/2/2019 Metering the Customer

    16/21

    Maximum demand greater than 50 kVA but notexceeding 350 kVA.Single phase: 3-wires 115/230 volts

    Three phases: 4-wires 115/230 volts or 230/400 voltsThree phases: 6.6, 12, 33 kilovoltsBilled on energy consumed ( kWh ).Meter Used: Form 9s, 10A, 16S

  • 8/2/2019 Metering the Customer

    17/21

    Maximum demand greater than 50 kVA but notexceeding 350 kVA.Three phases: 4-wires 115/230 volts or 230/400 volts

    Three phases: 6.6, 12, 33 kilovoltsBilled on energy consumed ( kWh ) and demand ( kVA).Meter Used: Form 9s, 10A, 16S

  • 8/2/2019 Metering the Customer

    18/21

    Maximum demand greater than 350 kVA but notexceeding 4000 kVA.Three phases: 6.6, 12, 33, 66 kilovolts

    Billed on energy consumed (kWh

    ) and demand (kVA).Meter Used: Form 9s, 10A, 16S

  • 8/2/2019 Metering the Customer

    19/21

    Maximum demand greater than 4,000 kVA but notexceeding 25,000 kVA.Three phases: 6.6, 12, 33, 66 kilovolts

    Billed on energy consumed (kWh

    ) and demand (kVA).Meter Used: Form 9s, 10A, 16S

  • 8/2/2019 Metering the Customer

    20/21

    Sixty (60) Hertz Alternating currentMaximum demandexceeding 25,000 kVA.

    Energy Usage less than 25,000,000 kWh per month.Three phases: 66, 132 kilovoltsBilled on energy consumed ( kWh ) and demand ( kVA).

  • 8/2/2019 Metering the Customer

    21/21

    Maximum demand greater than exceeding 25,000 kVA.Energy Usage greater than 100,000,000 kWh per month.Three phases: 66, 132 kilovolts

    Billed on energy consumed (kWh

    ) and demand (kVA).