Design Of Meter and
Regulating Stations (MRS)
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 2/59
Introduction
Desain statsiun meter dan pengaturan (mtering and regulatingstation) yang baik diperlukan untuk:
• Sustained Safety
• Accuracy
• Pressure!o" control
#A$%ORS %O &' $OSID'R'D #OR PROP'R D'SII
Many particulars are to be considered and assembled into
speci*cations and dra"ings to accomplis+ for properdesign ob,ecti-es.
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 3/59
#lo" Range $onsiderations
As a *rst step establis+ t+e gas load• Ma/imum #lo" Rate• Minimum #lo" Rate• 0+et+er loads are constant1 +a-e little or "ide -ariations•
2tmost care s+ould be taken "+ile assessing t+e load• In our conditions consumer try to pro-ide lo" loads to sa-e insecurity deposit1 "+ic+ e-entually result in meter under si3ing bad design of metering station
• ormally metering stations are designed for ma/imum !o"rate. 4o"e-er minimum +ourly loads s+ould be considered to
ensure t+at regulators and meters +a-e satisfactoryrangibility regulator to +a-e tig+t s+uto5 • #uture Pro,ections s+ould also be included. It is appropriate to
+a-e it agreed at t+e time of contract.
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 4/59
Pressure $onditions
Inlet pressureInlet
pressure• Does it +a-e "ide -ariation
• 0+et+er it is more t+an normal MAOP of t+e instruments1
good to deli-er outlet pressure e.g. normally MAOP of metersin distribution system is 678psig and t+at of 'mcorrector is699psig. If inlet pressure is more t+an 9psig t+an aregulator at t+e inlet of t+e meter "ould be installed.
• %+e ma/imum pressure "ill determine t+e MAOP of t+einstruments1 particularly of regulator
• %+e minimum -alue of t+e pressure "ill be used for si3ingt+e regulator and metering e;uipment.
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 5/59
<Pressure $onditions
Outlet Pressure• %+is pressure is set by t+e contract operational
re;uirements
• %+e regulator s+ould be designed according to t+e
minimum and ma/imum outlet pressure acceptable to t+ecustomer.
• %+e amount of pressure reduction is a ma,or indication of"+et+er a single stage pressure regulator "ill besatisfactory or if multiple stage reduction is re;uired.
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 6/59
<Pressure $onditions
%ype of =oad• $yclic loads needs critical analysis1 to ascertain t+e e/act
peak load (design load)
• =oads t+at goes to 3ero re;uire regulators capable of tig+t>
s+ut>o5 • #or "ider -ariation of loads1 "e "ould re;uire +ig+errangibility meters.
• Special consideration s+ould be gi-en to select a meter forcontinuous loads1 suc+ as process industries1 city loads etc.In t+ese cases usually inferential meters "+ic+ does not
block are more suitable. Sometimes to ompro-e rangibillitymultiple meter runs are installed "it+ s"itc+ing e;uipments
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 7/59
as $onditions Ambient $onditions
• %+e pipeline ;uality gas s+ould be dry and clean
• If dust or ot+er particles (condensate +ig+er +ydrocarbon)are present1 *ltering e;uipments s+ould be installedupstream of t+e station.
• Dust *lters are e;uipped "it+ suitable mes+ or coalescing*lter elements. It is good practice to install a 69 micron*lter elements. %+e *lters can be selected from t+e tablesaccording to gas loads and pressure.
• If t+ere are larger pressure cuts and ambient temperature
are e/pected to be lo"1 t+e free3ing of measuringe;uipment s+ould be considered. In suc+ cases ade;uateselection of +eating tapes1 indirect>*red gas +eaters1in+ibitors like glycol in,ection etc.
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 8/59
oise
• A metering regulating station s+ould preferably+a-e noise le-el less t+an ?8 db (decibel)
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 9/59
SampleSample
StationStation
SurveySurvey
MeteringStation Survey
Sur-ey of meteringstation s+ould be done-ery carefully because
design of meter andregulating stationdepend on t+is sur-ey.A poor sur-ey canresult in undersi3e oro-ersi3e design.
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 10/59
Selection of Dust #ilter
Dust *lter s+ould be installed at t+e inlet of t+e metering
regulating station to protect regulator pilots main -al-es1
meters etc.• Ma/imum !o" rate at minimum inlet pressure
• Ma/imum di5erential pressure @ psi• Ma/imum 69 microns solids• Design must meet ASM' code and ASI &6B.C code
400
300
200
100
0 25 50 75 100 % a g e o f i n i t i a
l
D i f f e r e n t i a l p r
e s s u r e Pressure Differential Vs Percent Plugged
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 11/59
<Selection of Dust #ilter
• It +as been e/perimentally establis+ed t+at *lters "+enclogged plugged to 89E +ad a 699E increase in di5erentialpressure1 and 78E plugged element +ad a 99E increase ofdi5erential pressure. It is t+erefore assumed t+at "+en t+edi5erential pressure across t+e *lter increases 699E from t+e
original di5erential 1 t+e *lter elements are 89E plugged and"+en t+e di5erential reac+es times t+e original1 t+eelement are 78E plugged.
• It is recommended t+at t+e *lter s+ould be replaced "+en t+edi5erential pressure is F of t+e ma/imum allo"able pressure
drop• %+e 78E plugged condition is normally suggested. So t+e
initial di5erential pressure of t+e *lter "ould be 6 t+ of t+erecommended di5erential pressure for *lter replacement (i.e.F of t+e ma/imum allo"able pressure)
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 12/59
'/ample
Conditions
0orking Pressure @ 699psig1 #lo" Rate @ B91999 ftC+r
Ma/imum Allo"able Pressure Drop @ B psig
Di5erential Pressure for replacement of elements
@F of Ma/imum Allo"able Pressure drop @6GB@ Cpsig
o" C psig is t+e ma/imum pressure di5erential limit for *lter
element replacement. According to 78E plugged rule Cpsig
(?9 in 0.$.) di5erential "ill be e/perienced "+en *lter
elements are 78E plugged. So t+e initial di5erential pressureneeds to be HG?9 @ 9 in 0.$.
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 13/59
<'/ample
In t+e table see t+e capacity at t+e intersection of 699psig inlet pressure and 9 in0.$. di5erential pressure. %+e capacity is BB1999 ftC4r. "+ic+ is good for gi-enconditions.
#A AD #S #I=%'R $APA$I%J %A&='
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 14/59
Remo-al of $ondensate
Remo-al of condensate is accomplis+ed by installing aknock>out -essel at t+e inlet of t+e metering station.ormally t+e direction of gas !uid is c+anged eit+er by
putting an obstruction plate or by employing multiplecyclones in parallel to remo-e li;uid particles. %+e c+angein -elocity enables t+e li;uid particles to drop do"n in t+ebottom of t+e scrubber.
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 15/59
=ine 4eater
%+ese are used to pre-ent :
• 4ydrate condensate "it+in gas stream to clog pilot line andregulator ori*ce
• Ice deposition around outside of regulator and control line
ydrocar!on De"point #oundary
P r e s s u r e $as
%ondensate$as
&ncreasing gas te'perature atconstant pressure "ill !ringt(e gas strea' in t(e rig(t of
t(e De" Point #oundary )i*e*$as P(ase+
,e'perature
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 16/59
<=ine 4eater
=ine 4eater Selection is based on :
• ormal inlet station pressure
• Minimum outlet station pressure
• Design !o" rate
• Inlet gas temperature
• Outlet gas temperature re;uired
• Ma/imum pressure drop across 4eater $oil at design !o"
(less t+an 69 psi)
%+e amount of +eat re;uired to raise t+e temperature of gi-en
;uality of gas to desired temperature is calculated from t+e
ent+alpy cur-e.
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 17/59
<=ine 4eater
At 899psig and 9K# inlet temperature 'nt+alpy@?.8 &tuftC
At 899psig and 78K# desired outlet temperature 'nt+alpy@?. &tuftC
Di5erence @ 9. &tuftC1 If t+e !o" rate @ MM$#D @ 6BB1BBB ftC4r %+en amount of 4eat Re;uired @ 6BB1BBB G9. @ BB1BBB &tu 4r&y using t+is +eating -alue t+e suitable si3e of 4eater can be selected from t+emanufacturerLs catalog
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 18/59
Regulator Selection
• Regulators are re;uired to control t+e do"nstreampressure in t+e metering station at one or more points
• Regulators are si3ed for ma/imum anticipated !o"re;uirement "it+ t+e minimum inlet pressure
• Alt+oug+ many regulators can operate o-er a "ide !o"and pressure ranges1 often it is necessary to considerparallel runs to +a-e better control1 redundancy andcapacity increase
• Regulators re;uired to operate nearly closed position o-erlong periods of time "ill tend to +a-e more -al-e and seat
damage1 t+an a unit t+at is si3ed to +a-e -al-e open atleast 69E
• A small regulator can be installed in one line and t+elarger regulator in t+e parallel line to +andle larger !o"sup to t+e re;uired capacity
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 19/59
<Regulator Selection
• Ade;uate "orking space s+ould be a-ailable for regulator1plug -al-es maintenance
• Regulators "it+ an e/ternal control line s+ould +a-esensing point 8 69 pipe diameters. $ontrol line may be
H16 or N depending upon t+e types of regulator anddistance from t+e pressure sensing point to t+e regulator
• 'ac+ regulator s+ould +a-e a separate sensing tap andcontrol line.
• Sensing tap s+ould not be installed on t+e *ttings suc+ ase/panders1 %ees1 'lbo"s etc.
• $ontinuity of operation is t+e most essential consideration.In case of fail to close regulators1 free3ing possibilities1 it isa good practice to +a-e parallel regulator runs.
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 20/59
<Regulator Selection
• Pilots re;uire clean and dry operating supply1 +eating taps1small *lters can be installed on t+e pilot lines
• #or safety of regulator operation normally1 regulators "it+relief -al-e or monitoring regulators are used. #ordistribution system monitoring operation is preferred"+ereas relief -al-e is used for remote locations in general
• Regulator by>pass and parallel legs are good for performingroutine maintenance
• #or */ed factor applications t+e droop s+ould be in 6E
(accuracy). 4o"e-er1 for *eld tapping up to 69E droop isa-ailable.
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 21/59
Regulator Si3ing
Most control -al-es are rated "it+ a capacity term called $-1
"+ic+ is de*ned as t+e number of gallons of "ater per
Minute t+at "ill !o" t+roug+ t+e -al-e "it+ 6 psi pressure
drop across t+e -al-e.
$- @ Q(P B.B)0+ere @ ;uality of "ater in gpm
P@ Pressure drop in psi
ormally $- or -alues of t+e regulators are gi-en by t+e
manufacturers and formulae for calculating t+e regulator
capacity at critical and non>critical !o"s are gi-en. %+ecapacity tables can also be used.
According to AALs recommendation
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 22/59
<Regulator Si3ingIf P is less t+an ?E of (P6) inlet pressure t+an use formula:
+ @ 7B.G$-Q(P(P6)) MS$#4r < formula > 6
Ot+er"ise use formula
+ @ 8.8 G$- Q(P(P6TP)) <formula >
$apacity #ormula as gi-en by di5erent manufacturers
ROCKWELL (Now SENSUS) @ Q(P9(P6>P9)) for P6P9 U 6.?
@ P6 for P6P9 V 6.?
factor for -arious ori*ces
Or i f i c e
Single Port Double Port
1/8” ¼” 3/8” ½” 3/4” 1” 1” 1 ½” 1 ¾” 2 1/8” 3”
K 33 132 292 52 85 13 2 42! 545 888 1!!4
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 23/59
<Regulator Si3ing
• '/ample:
P6 @ Minimum inlet pressure @ 699psia
P9 @ outlet pressure @ B9 psia
$apacity @ 991999 S$#4r
P6P9 @ 699B> @ 6.BB U6.? use formula 6
991999 @ Q(B9(699 B9))
@ 9?61 so from t+e abo-e table "e can select t+e ori*cesi3e of 6 F +a-ing @79
for monitoring total capacity of bot+ regulators is normallytaken as 79E of t+e capacity of a single regulator. So diaregulator "it+ an ori*ce si3e of 6 F "ill be selected
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 24/59
<Regulator Si3ing
#ind for @9?6
@79Q(B9(699>B9)) @ 91C9 S$#4r
If monitoring is re;uired1
calculated @9?6 "ill become @ 8?C9
0+ic+ means no" "e need an ori*ce si3e of 6? dia.
0+ic+ is a-ailable in C dia as R0>6>87S regulator. Its
MAOP is 678 psig "+ic+ can +andle inlet pressure of 699 psig
FISER RE!UL"#ORS
• $apacities can be calculated regulator selected from t+e
soft"are de-eloped by t+em• $apacity tables can be consulted
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 25/59
<Regulator Si3ing (FISER
RE!UL"#ORS)
• #ormulas
(i) @ P6(abs) ($g) (6.) "+en P9P6 W 9.8
(ii) @ Q(89%) $g Sin (C67$6 QpP6) D' 0+en
P9P6 V9.8
"+ere
P6 @ Inlet Pressure
P9 @ Outlet Pressure
$6 @ $g $- 1 $g @ as Si3ing $o>eXcient1 See tables
from #is+er catalog for C regulators
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 26/59
Important $onsiderations
A regulator is usually capable of +a-ing more t+an one ori*cesi3e. MAOP of t+e regulator de*nes t+e ma/imum operatingpressure of t+e regulator body1 but pressure rating for di5erentori*ces may be less t+an MAOP. So great care s+ould be taken
for t+e selection of ori*ce for a particular ori*ce si3e1 ot+er"iseregulator "ould not pro-ide tig+t lock>up.
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 27/59
S+uto5 Yal-e Selection
%"o types are generally used
• Plug Yal-es
• &all Yal-es
$LU! %"L%ES
• Reduced port
• =ubricated
• Recommended to be used do"nstream of regulator or meter
&"LL %"L%ES
• #ull opening (lesser pressure drop)• on>lubricated
• Recommended to be used upstream of t+e meter regulator
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 28/59
<S+uto5 Yal-e Selection
%+e capacities of t+e -al-e can be calculated from t+e AA
formulas for regulators if $- is gi-en. 4o"e-er as a t+umb
rule one step lo"er t+an pipe si3e can be used for -al-e si3e
(i.e. for pipe -al-e is normally O. Some designers
prefer to use same si3e -al-es for symmetry and to a-oid
*ttings like reducers e/panders.
• &lock -al-es are installed on t+e inlet outlet of t+emetering and regulating stations1 ot+er locations could be.
• Isolations of di5erent sections suc+ as *lters1 regulators1meter stations1 by>pass legs1 blo" do"ns1 relief -al-es1scrubbers etc.
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 29/59
Yal-e Zoint Selection
• 0eld neck !anges are used for abo-e ground applicationsfor ease of disassembly
• 0elded -al-es eliminate potential for leaks1 t+ese are moresuitable for underground applications
• %+read -al-e ,oints +a-e +ig+ potential for leakage1 t+eses+ould be a-oided as far as possible. $an be used for smallinstrument -al-es
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 30/59
Pipe Si3ing $on*guration
• AA recommend -elocities in piping system from 89 ftsec to99 ftsec. Di5erent companies use t+eir o"n limits onpipelines -elocities. =o"er -elocities are used to +a-e a;uieter system and to +a-e lo" "ear and tear ofinstruments
• SP= may use t+e -alue of pipeline -elocity of ?9ftsec fordesigning purposes
formula for calculation of -elocity:
Y @ 9.78 +DPf
Y@-elocity (ftsec)1 +@-olumetric !o" rate (S$#4r)
D@ inside diameter (inc+)1 Pf @!o"ing pressure (psia)
• #rom t+is formula "e can calculate t+e diameter of piping in-arious sections of t+e metering regulating stations
D@ Q(9.78+YPf )
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 31/59
Measurement
• #irst of all determine t+e type of meter t+at "ill be bestsuited for t+e load applications
• In SP= follo"ing types of meters are generally used
'omesti Low Capaity Commerial *eterin+ Station
• %+ese consumers +a-e -ery large -ariations in load "+ic+re;uire -ery +ig+ rangibility as suc+ diap+ragm meters+a-ing rangibility of 6:699 are used
!eneral Industry i+, $ressure Lar+e Capaity
Commerial *eterin+ Stations
• $omparati-ely lo"er !uctuations in load. ormally largecapacity diap+ragm or positi-e displacement rotary metersare used "+ic+ +a-e rangibility of 6:9
• In case of process industry "+ere it is not desirable to +a-egas supply s+uto51 turbine meters are more suitable
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 32/59
<Measurement
Lar+e Capaity *eter Stations su, as -ertili.ers
Cement and $ower
• ormally inferential meters1 ori*ce or turbine meters areused for suc+ applications
• Ori*ce meters +a-e a rangibility of 6:C.8 and turbine meters+a-e rangibility of 6:6? (at 9) and 6: at a pressure of78psig
• #or diap+ragm and rotary meters t+ere is no speci*cre;uirement of straig+t upstream and do"nstream piping
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 33/59
<Measurement
Seletion o- 'iap,ra+m and Rotary *eters
• =oad in S$# 4r (ma/imum and minimum)
• Metering Pressure (Minimum)
• In diap+ragm meters t+e capacity does not increase
corresponding to t+e pressure factor1 as suc+ consult tableagainst t+e ma/imum load and minimum metering pressureto *nd select t+e ade;uately si3ed meters
• $ompany is presently s"itc+ing o-er to rotary meters dueto t+eir sustained accuracy1 smaller si3e and non>ad,usting
accuracy features
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 34/59
<Measurement
Rotary *eter Seletion
• $alculate t+e pressure factor against t+e meteringpressure1 suppose metering pressure @ 9psig (min.)
P.#. @ (9T6.B8) 6.B8 @ C.7C
• Ma/imum load @ 61999 $uft4r• $alculate uncorrected -olume i.e. compressed -olume of
t+e gas to be passed t+roug+ t+e meter at meteringpressure @ 61999 C.7C @ C67 ftC4r
• Di-ide t+is -olume by 9.?8 as a facor of safety @ C7?8
• $apacities of rotary meters in company used are: >
R$CM678 @ C999 ftC4r 1 R$8M678 @ 8999 ftC4r
R$7M678 @ 7999 ftC4r 1 R$66M678 @ 66999 ftC4r
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 35/59
<Measurement
In t+is e/ample t+e uncorrected !o" rate is more t+an C999ftC4r and less t+an 8999 ftC4r1 so "e "ill select meterR$8M6781 t+e suX/ 678 depicts its MAOP
• $ompany +as decided to go for t+e automatic 'lectronicYolume $orrection by use of 'lectronic Yolume $orrectors.
So meter R$8M678 "it+ 'Y$ "ill be selected• Similar principle s+all be applied for t+e selection of %urbine
meters. 4o"e-er1 great care s+ould be taken to +a-estraig+t run piping upstream and do"nstream of t+e meteras recommended in AA>7
• ormally 69 pipe dia upstream of t+e turbine meters and 8
pipe dia. Do"nstream are to be used• A H dia by>pass line across t+e inlet -al-e of t+e turbine
meter leg is -ery essential "+ic+ is needed forcommissioning of t+e meter
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 36/59
<Measurement
Ori/e *eter Si.in+for si3ing ori*ce meters formula
@ $ Q(+"Pf ) is used
&eta Ratio @ [ @dD @Ori*ce Dia pipe dia @ 9.8
may be used for design purposes
As a t+umb rule $ @ #b (AA>C) G6.6minimum -alue of +" may be taken as @ ? in 4O
pf @ Absolute Static Pressure @ 899 psia
@ #b G6.6 Q(? G 899)
-. /ine Valve
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 37/59
<Measurement
@ 6B71999
#b@ 6B71999 (6.6 G66?) @ 6979 (gi-en -alue of about 7 ori*ce dia.)
• o" *nd t+e -alue of ori*ce dia from t+e tables of AA>Creport
• Meter run dia can be found by using [ ratio@[email protected] +enceD@ d9.81 [email protected] @6 pipe dia for meter tube
• %+e meter run can also be si3ed by using a computer soft"areprogramme de-eloped by manufacturers
• ormally 699 di5erential pressure recorder is used for
recording +" in t+e company
• Pro-ide ma/imum possible straig+t pipe upstream anddo"nstream of t+e ori*ce *ttings as recommended in AA>Cot+er pertinent instructions of AA>C s+ould be follo"ed
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 38/59
ormal Piping Arrangement of Distribution MeteringStations
"egul#tor$
"egul#tor$
Di#%&r#g' /"ot#r(
)eter$
O*/O++ ,-.,
O*/O++ ,-.,
Pre$$ure
0#uge
ilter
$as lo"
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 39/59
<ormal Piping Arrangement ofDistribution Metering Stations
"egul#tor$
O*/O++ ,-.,
ilter
"egul#tor$
$as lo"
Meter
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 40/59
<ormal Piping Arrangement ofDistribution Metering Stations
" e g u l #
t o r $
" e g u l #
t o r $
O * / O + +
, - . ,
1 i l t e
r
M e t
e r
$ a s 1 l o "
= $ i M i
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 41/59
=arge $apacity MeteringStation
%+ese stations normally +a-e four blocks
6. #iltration
. Regulation for t+e Meter
C. Meters
. Regulation for t+e deli-ery pressure if re;uired. %ypicalsketc+es of piping of large capacity meters in t+ecompany
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 42/59
<=arge $apacity Metering Station
$as lo"
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 43/59
<=arge $apacity Metering Station
$as lo"
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 44/59
'/ample
• Load and $ressure Re0uirements
=oad @ 9 M$#4r ma/imum
@ M$#4r Minimum
Inlet Pressure @ 9 psig ma/imum
@ 9 psig minimumOutlet Pressure @ ? psig
• Ot,er In-ormation
%ype of Industry @ eneral Industry in Pri-ate SectorMonitoring Re;uired @ Jes1 by "ay of Data =ogging
Deli-ery Pressure Re;uired @ $onstant
as uality @ Probability of Presence of Dust
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 45/59
<'/ample
• $roposal
%ype of Measurement @ Meter "it+ 'Y$ "ill be suitable
#ilters @ #ilters "ill be re;uired for t+e remo-al of dust
Regulation @ Pilot Operated "it+ minimum droop
• Filter
Pressure (minimum) @ 9 T 68 @ 88 psia
(ma/) @ 9 M$#4r
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 46/59
#A AD #S #I=%'R $APA$I%J %A&='
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 47/59
<'/ample
• Re+ulatorsP6P9 @ 88C @ .C V6.?9so1 "e "ill use @ G P6 or @ C?6
for @C?61 ori*ce si3e of F is suitable
for monitoring @C?69.7 @ 8 implied ori*ce si3e of N$onsult Regulator catalog of -arious regulator manufacturersand select regulator si3e "it+ ori*ce N or e;uilentP9P6 @ C88 @9.6use formula @ Pabs G $g G 6.
$g @ 91999 6. G 88 @ ?6#is+er 6 C at B9E +as $g @C8#is+er F +as $g@99 and N +as $g@C9
So #is+er "ill be selected for monitoring
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 48/59
<'/ample
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 49/59
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 50/59
<'/ample
• *eterRangibility @ :9 i.e 6:69
Diap+ragm or Rotary Meters can be selected.since Rotary meters are more rugged and 'Y$ is re;uired1 "e"ill go for Rotary Meter "it+ 'Y$
Minimum Metering Pressure @ 9 psigPressure #actor @ 9T6.B8 6.B8 @C.7C2ncorrected Yolume @ 9 C.7C @ 8.CB M$#4rma/imum !o" t+roug+ t+e meter s+ould be 9.?8 of t+e
ma/imum rated capacity of t+e meter.
so uncorrected -olume for design purpose @ [email protected]$#R$ 8M @ 8 M$# and R$ 7M @ 7 M$#So meter R$ 7M678 "it+ 'Y$ or e;ui-alent "ill be selected "+ic+
+as connection si3e of C
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 51/59
<'/ample
• $ipin+Inlet Piping:Inlet Pressure (Minimum) @ 88ma/ @ 9 M$#4rD @ Q(9.78G91999)(B8G88) @ .99
Outlet Piping:Outlet Pressure @ Cma/ @ 9 M$#4rD @ Q(9.78G91999)(CG89) @ C.6B\
%o c+eck if relati-e dia section of pipe can be used againstcalculated dia pipe1 assume pipe section @ 6ft
Darcy ';uation:dp@("6)/f/(=D)/(Yg) [email protected].?8G6G(89G89)(GC.67)
[email protected] psig\ 9.6?
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 52/59
<'/ample
"egul#tor$
Di#%&r#g' /"ot#r(
)eter$
O*/O++ ,-., 2”
O*/O++
P/,-.,
Pre$$ure
0#uge
ilter
$as lo"
CG
CG
Pipe
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 53/59
<'/ample
O*/O++ ,-., 1”
ilter
2.2.
"egul#tor$
2” i#
$asir lo"
Meter12.
. .
3.
12. .
Pipe Dia* 2.
eig(tfro'
1loor42.
12. 6eedle Valve
)0 100psig+
3.
12. 6eedle Valve
)0 100psig+
O*/O++,-.,
1”
,ee to !e connected"it( ir %o'pressor
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 54/59
Selection of s+uto5 -al-e
6. #or pressure drop in psig (sub,ect to P@CE of Pinlet)
dp @ 9.66BG#PpsiaG](A) in MS$#
. #or pressure drop in inc+es of "ater column
dp(inc+es of 4O) @ C.G#PpsiaG]G(A)
"+ere dp @ pressure drop
Ppsia @ Absolute Static Pressure in upstream pipe
(S$#4)@as #lo" in S$#4r
A @ Pipe #lo" Area in inc+es] @ compressibility #actor
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 55/59
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 56/59
<Selection of s+uto5 -al-e
• $alculations
Inlet -al-e
since pipe si3ing @ so "e "ill *rst analy3e dia -al-e
#@9.C (from table)
Assume @ dp@6psi 1 @9MS$#4r1 Pressure@88psia]@9.?
2se [email protected]#Pabs G]G(scf+A)
[email protected].?(9A)
A
@9.C88 or [email protected]#rom table for [email protected] 6 dia -al-e is suXcient. 4o"e-er for
symmetry dia -al-e can also be recommended1 "+ic+"ill pro-ide lo"er di5erential pressure.
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 57/59
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 58/59
7/23/2019 Meter and Regulating Stations (MRS) Design
http://slidepdf.com/reader/full/meter-and-regulating-stations-mrs-design 59/59
<Selection of s+uto5 -al-e
Do"nstream Outlet Yal-e
dp@69 inc+es of 4O (as do"nstream pressure is -ery lo""e +a-e to keep pressure loss to be minimum)
]@9. from grap+
Since pipe si3e is "e "ill initially calculate A for use formula #@9.7
dp (inc+es of 4O)@C.G#Pabs G](A)
69@C. G9.7C G9.(9A)
[email protected] from table again [email protected] -al-e si3e b" 6 H to
6 6 is good1 so "e "ill select -al-e.