1
TRANSFORMADORES FECHA ÚLTIMA PRUEBA REPORTE No. MET-TE-089/06 DIVISIÓN ZONA SUBESTACIÓN: FECHA: 31-Mar-07 EQUIPO (CLAVE): MARCA: VOLTRAN NÚMERO DE SERIE: 13236 CAPACIDAD: 3500 KVA VOLTAJE (kv): A.T.: 4.16 B.T.: 0.480/0.277 TIPO: ONAN/FUT ONAF IMPEDANCIA: 7.87 % TEMPERATURA AMB.: 26 °C TEMP. ACEITE: °C TEMP. DEV: °C H.R.: 65 % CONDICIONES ATMOSFÉRICAS: CIELO NUBLADO T A P DEVANADO DE ALTA TENSIÓN EN DELTA (Δ) CONEXIÓN MULTIPLICADOR 1 H 1 - H 3 63.1 -- 63.1 H 2 - H 1 63.2 -- 63.2 H 3 - H 2 63.1 -- 63.1 2 H 1 - H 3 61.6 -- 61.6 H 2 - H 1 61.5 -- 61.5 H 3 - H 2 61.5 -- 61.5 3 H 1 - H 3 60.2 -- 60.2 H 2 - H 1 60.2 -- 60.2 H 3 - H 2 60.2 -- 60.2 4 H 1 - H 3 59.4 -- 59.4 H 2 - H 1 59.2 -- 59.2 H 3 - H 2 59.1 -- 59.1 5 H 1 - H 3 58.6 -- 58.6 H 2 - H 1 58.8 -- 58.8 H 3 - H 2 58.1 -- 58.1 X 1 - X 0 17.5 -- 17.5 X 2 - X 0 17.5 -- 17.5 X 3 - X 0 17.5 -- 17.5 EQUIPO DE PRUEBA: DUCTER AVO MARCA: BIDDLE MODELO: 247001 SERIE: 47448 OBSERVACIONES FIRMAS AMERICA ENERGY SERVICE PROPIETARIO SUPERVISION DE AREA CONTROL DE CALIDAD SUPERVISION FECHA FECHA FECHA ING. JAVIER LOPEZ PACHECO PREPARO VERIFICO TESTIFICO AES ACTION ENERGY PRUEBA DE RESISTENCIA OHMICA DE DEVANADOS (¬ ) LECTURA VALOR

MET-Te-089-06

Embed Size (px)

DESCRIPTION

FORMATO DE VERIFICACION DE PRUEBAS DE COLLAR CALIENTE A TRANSFORMADORES

Citation preview

Page 1: MET-Te-089-06

TRANSFORMADORESFECHA ÚLTIMA PRUEBA

REPORTE No. MET-TE-089/06

DIVISIÓN

ZONA

SUBESTACIÓN: FECHA: 31-Mar-07

EQUIPO (CLAVE): MARCA: VOLTRAN

NÚMERO DE SERIE: 13236 CAPACIDAD: 3500 KVA

VOLTAJE (kv): A.T.: 4.16 B.T.: 0.480/0.277 TIPO: ONAN/FUT ONAF IMPEDANCIA: 7.87 %

TEMPERATURA AMB.: 26 °C TEMP. ACEITE: °C TEMP. DEV: °C

H.R.: 65 % CONDICIONES ATMOSFÉRICAS: CIELO NUBLADO

T A

P

DEVANADO DE ALTA TENSIÓN EN DELTA (Δ)

CONEXIÓN MULTIPLICADOR

1H 1 - H 3 63.1 -- 63.1

H 2 - H 1 63.2 -- 63.2

H 3 - H 2 63.1 -- 63.1

2H 1 - H 3 61.6 -- 61.6

H 2 - H 1 61.5 -- 61.5

H 3 - H 2 61.5 -- 61.5

3H 1 - H 3 60.2 -- 60.2

H 2 - H 1 60.2 -- 60.2

H 3 - H 2 60.2 -- 60.2

4H 1 - H 3 59.4 -- 59.4

H 2 - H 1 59.2 -- 59.2

H 3 - H 2 59.1 -- 59.1

5H 1 - H 3 58.6 -- 58.6

H 2 - H 1 58.8 -- 58.8

H 3 - H 2 58.1 -- 58.1

X 1 - X 0 17.5 -- 17.5

X 2 - X 0 17.5 -- 17.5

X 3 - X 0 17.5 -- 17.5

EQUIPO DE PRUEBA: DUCTER AVO MARCA: BIDDLE MODELO: 247001 SERIE: 47448

OBSERVACIONES

FIRMAS

AMERICA ENERGY SERVICE PROPIETARIO

SUPERVISION DE AREA CONTROL DE CALIDAD SUPERVISION

FECHA FECHA FECHA

ING. JAVIER LOPEZ PACHECOPREPARO VERIFICO TESTIFICO

AES

ACTION ENERGY

PRUEBA DE RESISTENCIA OHMICA DE DEVANADOS (¬ )

LECTURAmΩ

VALOR mΩ