Upload
others
View
6
Download
0
Embed Size (px)
Citation preview
Meroblock - Planning and tendering Sanitärtechnik
All toilets compatible with Duravit Sensowash®
Geberit flush-mounted cisterns Compatible with Geberit AquaClean
Meroblock the high-quality all-round system
• Application areas: Front wall, brick/dry construction, Front wall installation
• All common standards are complied with, e.g. DIN 52219 / 4109 • Barrier-free construction
Scope of the tender:
• Always write out final installation parts separately unless specifically included!
• Write out other flooring installations separately!
• Write out other waste water fittings separately!
System accessories:
• Noise protection cages for waste water pipes connected to the down pipe
• Floor connection plates for screed and wet room insulation
• Foot brace for free-standing load
• Flush plates for flush-mounted cistern Burda
... For this, see the tender texts under the item Accessories.
We reserve the right to make technical changes.
General informationfor tendering
Me
rob
lock
2 | 3
The legal basis for the observance of sound levels pertaining to technical building systems (installation noise)
is specified in DIN 4109. Accordingly, a minimum sound insulation of 30 dB (A) is generally applicable for sound-
protected interiors such as living rooms and bedrooms. This value must be adhered to in every case. In addition,
lower sound levels can be contractually agreed upon.
Table (detail) - Values for the permissible sound pressure level of noise from technical building installations in sound-protected rooms
General informationSound insulation - Legal framework
DIN 4109 Amendment A1 dated January 2001
30
27
24
20
30 dB (A) 30 dB (A) 27 dB (A) 24 dB (A)
dB (A)
The statutory standard maximum value for vulnerable rooms in flats (minimum sound insulation)
Civil / Private service contract law (allows additional agreement regarding the increased sound protection) according to DIN 4109 - Part 10 (E):
Multiple family house from 2 flats
In living rooms and bedrooms, max 30 dB (A)
Single family
There is no claim on the structural soundproofing if not contractually agreed upon. DIN 4109
+
Amendment A1
DIN 4109 – Part 10 (E)
Sound Insulation
Class I (SST I)
DIN 4109 – Part 10 (E)
sound insulation
level II (SST II)
Increased sound insulation
Minimum sound insulationGenerally accepted engineering standards (aRdT)
Comfort sound insulation
DIN 4109 – Part 10 (E)
Sound Insulation
Class III (SST III)
Type of vulnerable rooms
Source of noise Living and bedrooms Teaching and working rooms
Characteristics of the sound pressure level dB (A)
Water facilities (water supply and sewage systems together)
≤ 30 dB ≤ 35 dB
General informationSound protection - Implementation in practice
The acoustic outcome of all works in the installation depends on various
factors. Below you will find some valuable tips to check at the construction
site, which are often ignored or are not met. The fitter often has to deal
with inappropriate conditions particularly in terms of the wall quality
which he should examine technically and for legal liability. 220 kg/m2
Wall thickness 17.5 cm
180 kg/m2
Wall thickness 11.5 cm
Metal stud wall only with Certificate of suitability
Install only tested and marked fittings! The individual, installed fittings and appliances must be tested and marked in terms of their fittings noise level and associated fittings noise class.
For a pressures of more than 5 bars, use a pressure reducer!In order to prevent flow noise, the resting pressure from floor distribution must not be more than 5 bars.
Observe dimensioning, Always open shut-off valves in operation! The actual flow must not be higher than the flow based on which the classification is made. Accordingly, the spout devices such as shower heads or jet regulators must not belong to any higher flow group than the fitting itself. Passage fittings must not be used for throttling.
Appropriate suitability certificates must be available for all walls whose mass per unit area is less than 220 kg/mm2 . The mass per unit area of a single-leaf wall, which should be mounted on or in the fittings or water installations including waste water, must be at least 220 kg/m2 according to DIN 4109. For lighter solid and dry walls, an acoustic suitability certificate according to DIN 4109 is always required.
Fittings of the fittings group II should not be mounted on walls that border rooms requiring protection on the same floor or in the floors above or below.
Additionally, note: Installation noise level lowers with high quality pipes. The ground plan, the construction and/or the specified cable routing sometimes necessitate drain pipes with a better sound reduction index than HT pipes.
Suitable expansion strips should be used before placing the screed.No sound bridges should arise between installations or installation walls and floating screed.
Sanitärtechnik
Me
rob
lock
4 | 5
For Burda MEROBLOCK, the test set-ups are aligned to facilities in surgeries consistently and according
to the conditions on the building site. For maximum safety in design and installation.
General informationSound insulation - Test certificates and installation situation on site
To achieve the required noise protection level, it is important for
planners and installers to know the values of the individual com-
ponents of the sanitary systems. For this purpose they use the
acoustic test reports of the manufacturer.
Fundamental to the success of their work is that the test set-up for
the sound level measurement is as close as possible to the set-up of the
later installation. Therefore, they should always ask for the test reports
and compare the test set-up with the proposed installation!
Result: Lowest noise level in practice
Test requirements Riser Down pipe — WC block — WT block — with drinking and waste water pipe
Sound level in the vulnerable room when using Burda MEROBLOCK according to test set-up
Installation wallm´= 180 kg / m2
with front wall installation in brick construction
Installation wallm´= 180 kg / m2
with front wall installation in brick construction
In-wall installationMetal stud wall
Installation wallm´= 220 kg / m2
with front wall installation in brick construction
30
27
24
20
2826
21 20
DIN 4109 and Part 10 (E) (SST Ill)
DIN 4109 and Part 10 (E) (SST Il)
DIN 4109 and Part 10 (E) (SST I)
Background noise level
General informationPreventive fire protection in the L-90 installation shafts
Option of installing Burda MEROBLOCK installation
blocks in space-enclosing walls F 90.
Installation in a bricked L 90 installation shaft
with F 90 shaft cladding according to DIN 4102-4
For this purpose, the required fire safety certificate by a
fire test and a "general building authority approval"
must be produced.
Mounting in a light partition wall F 90 (with suitability
certificate) and cable routing in an L-90 installation
shaft with F-90 shaft cladding according to DIN 4102-4.
Burda MEROBLOCK F 90 M installation in accordance with the general building authority approval of the MPA Braun-schweig P-3083/0738-MPA BS.
Burda MEROBLOCK F 90 L installation in accordance with the general building authority approval of the MPA Braun-schweig P-3083/0738-MPA BS.
Pipe penetrations in accordance with the requirements of preventive fire protection with a fire resistance of 90 minutes, for example, according to the alleviations of MLAR 03/2000.
The installation of the Burda MEROBLOCK F 90 L takes place in an approved F 90 metal stud wall. The pipe in-sertion can be done at each end of the top and bottom of the metal stud wall with a partitioning.
Fire protection mat made of rock wool at least A1 in actuating opening
burda MEROBLOCK Installation Block F 90 M with test certificate
Single-layer F 90 partition/shaft wall d > 115 mm from components acc. DIN 4102-4
Installation shaft as its own L 90 fire compartment
Brandschutzmatteaus Steinwolle mind.A1 inBetätigungsö�nung
Installationsschachtals eigener I 90Brandabschnitt
UPONOR MEROBLOCKInstallationsblock F 90 M mit Prüfzeugnis
Einschalige F 90Trenn -/Schacht -wa nd d > 115 mmaus Bauteilen gem. DIN 4102-4
burda MEROBLOCK fire protection mat in actuating opening (supplied)
Installation shaft as its own L 90 fire compartment
Fire compartment
Tiling
Operation
Fire compartment burda MEROBLOCK F 90 L Mineral fibre
of fire class at least A2
Plasterboard fire protection panels 2 x 12.5 mm
Plasterboard fire protection panels 2 x 12.5 mm
Sanitärtechnik
Me
rob
lock
6 | 7
Performance and technologyThe example of the Burda M block for wall-mounted WC
Note: All installation instructions and other documentation and test certificates can be found in the download area at www.burda-online.com.
Modern water-saving toilet flushing systems
Allows flow, plaster and planking Slot bridge metal surface
Including WC connection fitting and installation accessories for rough installation
Installation space covering (MRA) as an abutment to take the user's weight, i.e.
brick lining is not required!
Sturdy construction, self supporting, corrosion-protected profile frame construction (galvanised)
Structure-borne sound-insulated sanitary engineering (Flushing systems, fittings, pipelines)
Waste water connection either HDPE or cast iron
Infinitely height-adjustable feet from 20 to 200 mm
General informationBarrier-free construction according to DIN 18040, solutions with Burda MEROBLOCK
The Burda MEROBLOCK offers the right connection options in any installation situation, making it a univer-sally applicable choice at the construction site. Whether brick or dry wall construction, the demands on high quality or standard-compliant facilities for barrier-free living can always be met.Examples of the implementations of the requirements according to DIN 18040 with the Burda MEROBLOCK Installation blocks:
The Burda MEROBLOCK range includes not only standard-compliant in-
stallation blocks with dimensional requirements and increased resilience,
but also barrier-free sanitary systems.
Various designs such as the wash-stand flush-mounted siphon, the electrical
and electronic WC actuation and wash-stand fittings engineering meet the
most varied requirements.
The Burda MEROBLOCK mounting plates are particularly designed for
the high load (100 kg) of the folding support handles. In addition to
the original dimensions of the manufacturer's mounting, these parts
include standardised clearance dimensions and a practical design for
brick and dry wall construction.
The high quality standardised sound protection through the structure-
borne sound insulation design can be further improved in bricked front
walls by the use of noise protection cages.
The optical / electrical and contactless Burda WC control allows a toilet
flushing that suitably meets the standard and usage in barrier-free bath-
rooms.
Front wall installation
Front wall installation with brick lining In-wall installation in metal stud wall
WC - Controls and function
??? ?
??
??? ?
??
Automatic flushing when leaving (Can be switched
off) minimumdwell time 15 sec
Optional intermediate flushing by
pressing a button
Optional intermediate flushing by pressing a
button
For detailed information see pages 88/89
Contactless flushing by bringing the hand to the
capacitive sensor
CW
UA
Sanitärtechnik
Me
rob
lock
8 | 9
General informationBarrier-free construction according to DIN 18040
Requirement according to DIN 18040
Movement area in front of the wash-stand. Right, left or cen-
tral arrangement possible. Adequate knee space should be
provided for wheelchair users in the area of the wash-stand.
For this purpose a flat, surface-mounted or a flush-mounted
siphon is provided.
Requirement according to DIN 18040
A movement area 1500 x 1500 mm should be provided in front
of bathtub or in the area of the shower. An appropriate spatial
planning for retrofitting a shower place with a bathtub is recom-
mended.
Barrier-free wash-stand facility Barrier-free bathtub and shower area
Requirement according to DIN 18040
WC seat height 48 cm, including seat.
In the toilet, a movement area is necessary in front and also to
the right and left of the toilet. The toilet flushing must be oper-
able on both sides with the arm or hand, without changing the
seating position. For barrier-free, wheelchair-accessible flats,
only a lateral movement area to the right or left of the toilet is
provided according to DIN 18040.
Movement and spacing areas according to DIN 18040
Movement and spacing areas should be in concordance with
rules and standards in barrier-free construction An important
reference point for this is the manoeuvring space for wheel-
chairs; this is the reason why the movement area according to
DIN 18040 provides 1500 x 1500 mm space for wheelchair users
in public areas and in homes. In other flats, this area is deter-
mined according to DIN 18040 at 1200 x 1200mm. Movement
areas for different installations can overlap.
Movement areas Barrier-free toilet facility