12
CONTENTS TIPS BEFORE BEGINNING INSTALLATION ......... 2 COMMUNICATIONS LOOPS ..................... 3 CONSTANT VOLUME CONTROLLERS ............. 4 CONSTANT VOLUME CONTROLLER ADDRESSING ................................. 6 ZONE SENSORS ............................... 7 COMMLINK II INTERFACE ....................... 8 APPENDIX .................................... 9 INSTALLATION INSTRUCTIONS MERIDIAN CV MERIDIAN C OOL MODE 036-33036-001-A-1101

MERIDIAN CV - UPGNET · 2014-11-18 · 036-33036-001-A-1101 Installation Instruction - Meridian CV 3 COMMUNICATIONS LOOPS The Communications Loop is two wire shielded RS-485. The

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: MERIDIAN CV - UPGNET · 2014-11-18 · 036-33036-001-A-1101 Installation Instruction - Meridian CV 3 COMMUNICATIONS LOOPS The Communications Loop is two wire shielded RS-485. The

CONTENTS

TIPS BEFORE BEGINNING INSTALLATION . . . . . . . . . 2

COMMUNICATIONS LOOPS . . . . . . . . . . . . . . . . . . . . . 3

CONSTANT VOLUME CONTROLLERS . . . . . . . . . . . . . 4

CONSTANT VOLUME CONTROLLERADDRESSING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

ZONE SENSORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

COMMLINK II INTERFACE . . . . . . . . . . . . . . . . . . . . . . . 8

APPENDIX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

INSTALLATIONINSTRUCTIONS

MERIDIAN CV

M ERIDIANC OO L MODE

036-33036-001-A-1101

Page 2: MERIDIAN CV - UPGNET · 2014-11-18 · 036-33036-001-A-1101 Installation Instruction - Meridian CV 3 COMMUNICATIONS LOOPS The Communications Loop is two wire shielded RS-485. The

036-33036-001-A-1101

2 Installation Instruction - Meridian CV

TIPS BEFORE BEGINNING INSTALLATION

Take a few moments to review the following before beginninginstallation of the Meridian CV System.

ï Familiarize yourself with all system components andreview all documentation. Pay special attention to "Cau-tions" and "Warnings" since these may keep you fromexperiencing unnecessary problems.

Before installing controllers, be sure to tag it with itsappropriate location. A set of labels is included with thismanual. It is also best to set the controller addressswitches before mounting. Use the CV Address Work-sheet to list all CV unit locations. This will assist yougreatly when setting up the system.

Be sure and install all wiring according to local, state,and national codes.

Pay close attention to communication wiring since themost common mistakes are made in this area. Polarity isthe most important rule. Make notes on your wiring dia-grams as to which color wire you will be using on eachterminal.

When in doubt - ask! Contact your local Meridian distrib-utor if you have any questions. The only dumb questionsare the ones you don't ask.

Remember - each electronic device contains only onepuff of smoke. If you release it, you have voided the war-ranty! So please be careful and pay attention.

FIGURE 1: SYSTEM OVERVIEW

M E R ID IA NC O O L M O D E

Page 3: MERIDIAN CV - UPGNET · 2014-11-18 · 036-33036-001-A-1101 Installation Instruction - Meridian CV 3 COMMUNICATIONS LOOPS The Communications Loop is two wire shielded RS-485. The

036-33036-001-A-1101

Installation Instruction - Meridian CV 3

COMMUNICATIONS LOOPS

The Communications Loop is two wire shielded RS-485. Theloop is best connected in daisy chain configuration, meaningthe loop is connected from one controller to another. It is notnecessary to sequentially address the CV Controllers in rela-tion to their location on the loop. Cable must be Belden No.82760 or equivalent.

COMMUNICATIONS LOOP WIRING OVERVIEW

The daisy chain is the best method for running a communica-tions loop since there is only one starting point and one end-ing point for each of the communications loops. (Figure 2).

FIGURE 2: COMMUNICATION LOOP WIRING, DAISY-CHAIN CONFIGURATION

TIPIncorrect wiring of the communications loop is themost common mistake made during installation.Before beginning installation, write down the wirecolor used on each terminal connection and consis-tently maintain that color code. It is recommendedthat a continuous wire run be made betweendevices. Anytime a splice is made in the cable youincrease your chance of problems.

Make sure when you are inserting wires into theterminal blocks that strands of wire do not stick outand touch the next terminal. This could cause ashort or erratic operation.

Page 4: MERIDIAN CV - UPGNET · 2014-11-18 · 036-33036-001-A-1101 Installation Instruction - Meridian CV 3 COMMUNICATIONS LOOPS The Communications Loop is two wire shielded RS-485. The

036-33036-001-A-1101

4 Installation Instruction - Meridian CV

Even though the daisy chain configuration is preferred, thestar configuration can also be used. If required, a combina-tion of the two can also be used. Remember, the best commloop wiring is the one which utilizes the minimum number ofends while using the shortest wiring path.

CONSTANT VOLUME CONTROLLERS

The Constant Volume Controller may be installed in anyconvenient protected location. Observe the recommendedenvironmental limitations for the Constant Volume Controller(see the Technical Data section of the product data sheet)when choosing a location.

The Constant Volume Controller may be mounted withoutremoving the controller from the mounting plate. The unit ismounted by four (4) screws in the corners. Select the correctscrews or other fasteners for the type of mounting materialbeing utilized.

FIGURE 3: CONSTANT VOLUME CONTROLLER

NOTEThe loop does not have to follow the controlleraddress sequence.

If the comm loop is not installed in conduit, becareful to position the cable away from high noisedevices like fluorescent lights, transformers,VFD's, etc. Conduit is not required for comm loopwiring unless required by local codes.

Page 5: MERIDIAN CV - UPGNET · 2014-11-18 · 036-33036-001-A-1101 Installation Instruction - Meridian CV 3 COMMUNICATIONS LOOPS The Communications Loop is two wire shielded RS-485. The

036-33036-001-A-1101

Installation Instruction - Meridian CV 5

FIGURE 4: CONSTANT VOLUME CONTROLLER WIRING

Polarity is very important when connecting power tothe controllers! The grounded side of the controltransformer must be connected to the terminallabeled GND on the CV Controller. If a single trans-former is used to power more than one CV Control-ler you must connect GND-to-GND and 24VAC-to-24VAC on each CV controller. Failure to observepolarity will result in damage to one or more compo-nents in your system.

Use extreme care not to damage any of the elec-tronic components while mounting the backplate.Mark the holes then remove the CV Controller fromthe backplate before drilling.

Do not allow metal shavings to fall onto the circuitboards.

TIPAfter making all electrical connections unplug all ter-minal blocks on the CV Controller until you are readyto begin the checkout procedure. This may help toprevent damage if wiring errors occur elsewhere inthe system during installation or start-up .

Page 6: MERIDIAN CV - UPGNET · 2014-11-18 · 036-33036-001-A-1101 Installation Instruction - Meridian CV 3 COMMUNICATIONS LOOPS The Communications Loop is two wire shielded RS-485. The

036-33036-001-A-1101

6 Installation Instruction - Meridian CV

The Constant Volume Controller requires the following electrical connections:

18 Gauge minimum unless otherwise noted.

CONSTANT VOLUME CONTROLLER ADDRESSING

FIGURE 5: CV CONTROLLER ADDRESS SWITCH SETTING

-24VAC Supply Voltage 2 Conductors

-Communications Loop 2 Conductor twisted pair with shield(Belden #82760 or equivalent)

-Supply Air Temperature Sensor (24 ga. Min.) 2 Conductors

-Room Air Temperature Sensor (24 ga. Min.) 2 Conductors for standard sensor3 Conductors for sensors with setpoint adjustment

-Outside Air Temperature Sensor (24 ga. Min.) 2 Conductors

-HVAC Unit Control Wiring R - Common G - FanHeat / Cool Stage 1, 2, 3, & 4

Page 7: MERIDIAN CV - UPGNET · 2014-11-18 · 036-33036-001-A-1101 Installation Instruction - Meridian CV 3 COMMUNICATIONS LOOPS The Communications Loop is two wire shielded RS-485. The

036-33036-001-A-1101

Installation Instruction - Meridian CV 7

ZONE SENSORS

The zone sensor uses a patented flush mount design to iso-late the temperature sensing element from the housing whichmounts flush with the wall surface.

Zone sensors should be located on an inside wall away fromdirect sunlight or heat producing equipment such as comput-ers, copiers, etc. Such devices can adversely affect the accu-racy of the sensor.

Although the sensor eliminates most of the effects of thermalcoupling to the walls, try to avoid walls which retain largeamounts of thermal energy (such as marble or steel). Wallscontaining either cold or warm air currents should also beavoided whenever possible.

Avoid locating the sensor in dead air areas of a room. Thiswill result in slow response to temperature changes in thespace.

Mount the sensor approximately 50-60 inches from the floorfor best results.

The zone sensor is designed to mounted vertically in a stan-dard 2 by 4 inch electrical box. The sensor may be mounteddirectly into the drywall where electrical codes do not requirelow voltage wiring to be enclosed in conduit. A template issupplied with the sensor to facilitate cutting a hole of the cor-rect size.

FIGURE 6: ZONE SENSOR WIRING

Connect the terminal labeled GND on the zone sensor to theterminal labeled GND on the CV Controller Analog Input ter-

minal block. Connect the terminal labeled TMP on the zonesensor to the terminal labeled AIN 1 on the CV ControllerAnalog Input terminal block. If the zone sensor has a setpointadjust slider, then connect the sensor terminal labeled AUXto the CV Controller AIN 2 terminal block.

SUPPLY AIR TEMPERATURE SENSOR

The supply air temperature sensor should be located asclose to the rooftop unit discharge as possible for bestresponse.

Locate the sensor in the center of the widest part of the duct.Use the supplied template and a 5/16" drill to make a hole forthe sensor. Install the gasket over the probe and mountsecurely to the duct using the supplied sheet metal screws.Be sure the gasket is compressed to provide an air tight seal.

For best accuracy, apply insulation on the outside of the duct,over the sensor. This will help prevent thermal gradients fromaffecting the sensor.

OUTSIDE AIR TEMPERATURE SENSOR

The outside air sensor must be located where it will not beaffected by direct sun or heat producing equipment. Mountingunder the eve of a roof is often a good choice.

TIPBe careful when cutting the hole for the sensor orthe plastic bezel of the sensor may not completelycover the opening.

TIPIf sensors must be installed on walls which aresolid and cannot be penetrated, surface mountedboxes and raceway can be purchased from yourlocal electrical distributor.

Complaints of inaccurate outside sensor readingsare very common and can almost always beshown to be the result of poor sensor location.

NOTEAll temperature sensors supplied with the systemutilize the same thermistor type sensing element.Refer to Appendix Table 1 , TEMPERATURESENSOR RESISTANCE CHART, for troubleshoot-ing sensor problems.

Page 8: MERIDIAN CV - UPGNET · 2014-11-18 · 036-33036-001-A-1101 Installation Instruction - Meridian CV 3 COMMUNICATIONS LOOPS The Communications Loop is two wire shielded RS-485. The

036-33036-001-A-1101

8 Installation Instruction - Meridian CV

COMMLINK II INTERFACE

The CommLink II Interface provides on site computer hook-up or modem interface for remote communications. TheCommLink II is wired as shown in Figure 7.

Locate the CommLink II near the computer or modem. Thecable connections between the CommLink II and the com-puter or modem should be kept to less than twenty-five feet.

The CommLink II comes complete with computer and modemcables, and a plug-in power supply.

FIGURE 7: COMMLINK INTERFACE WIRING

M ERIDIAN

Page 9: MERIDIAN CV - UPGNET · 2014-11-18 · 036-33036-001-A-1101 Installation Instruction - Meridian CV 3 COMMUNICATIONS LOOPS The Communications Loop is two wire shielded RS-485. The

036-33036-001-A-1101

Installation Instruction - Meridian CV 9

APPENDIX

*Notes:

1. Use the resistance column to check the thermistor sen-sor while disconnected from the controllers (not pow-ered).

2. Use the voltage column to check sensors while con-nected to powered controllers. Read voltage with meterset on DC volts. Place the "-" (minus) lead on GND termi-nal and the "+" (plus) lead on the sensor input terminalbeing investigated.

If the voltage is above 5.08 VDC, then the sensor or wir-ing is "open". If the voltage is less than 0.05 VDC, thesensor or wiring is shorted.

Table 1:Temperature Sensor Resistance Chart

TEMPERATURE

°FRESISTANCE

Ω*VOLTAGE AT

INPUT*

-10 93,333 4.620

-5 80,531 4.550

0 69,822 4.474

5 60,552 4.390

10 52,500 4.297

15 45,902 4.200

20 40,147 4.095

25 35,165 3.982

30 30,805 3.862

35 27,140 3.737

40 23,874 3.605

45 21,094 3.470

50 18,655 3.330

52 17,799 3.275

54 16,956 3.217

56 16,164 3.160

58 15,385 3.100

60 14,681 3.042

62 14,014 2.985

64 13,382 2.927

66 12,758 2.867

68 12,191 2.810

69 11,906 2.780

70 11,652 2.752

71 11,379 2.722

72 11,136 2.695

73 10,878 2.665

74 10,625 2.635

75 10,398 2.607

76 10,158 2.577

78 9,711 2.520

80 9,302 2.465

82 8,893 2.407

84 8,514 2.352

86 8,153 2.297

88 7,805 2.242

90 7,472 2.187

95 6,716 2.055

100 6,047 1.927

105 5,453 1.805

110 4,923 1.687

115 4,449 1.575

120 4,030 1.469

125 3,656 1.369

130 3,317 1.274

135 3,015 1.185

140 2,743 1.101

145 2,502 1.024

150 2,288 0.952

Table 1:Temperature Sensor Resistance Chart

TEMPERATURE

°FRESISTANCE

Ω*VOLTAGE AT

INPUT*

Page 10: MERIDIAN CV - UPGNET · 2014-11-18 · 036-33036-001-A-1101 Installation Instruction - Meridian CV 3 COMMUNICATIONS LOOPS The Communications Loop is two wire shielded RS-485. The

036-33036-001-A-1101

10 Installation Instruction - Meridian CV

NOTES

Page 11: MERIDIAN CV - UPGNET · 2014-11-18 · 036-33036-001-A-1101 Installation Instruction - Meridian CV 3 COMMUNICATIONS LOOPS The Communications Loop is two wire shielded RS-485. The

036-33036-001-A-1101

Installation Instruction - Meridian CV 11

NOTES

Page 12: MERIDIAN CV - UPGNET · 2014-11-18 · 036-33036-001-A-1101 Installation Instruction - Meridian CV 3 COMMUNICATIONS LOOPS The Communications Loop is two wire shielded RS-485. The

Subject to change without notice. Printed in U.S.A. 036-33036-001-A-1101Copyright © by Unitary Products Group 2001. All rights reserved. Supersedes: Nothing

Unitary 5005 NormanProduct York OKGroup Drive 73069