Megger Certificate No: 17 ELECTRICAL INSTALLATION CERTIFICATE (REQUIREMENTS FOR ELECTRICAL INSTALLATIONS BS7671 [IEE WIRING REGULATIONS]) DETAILS OF THE CLIENT Client: Alan Read Address: 36 Arle Gardens Cheltenham INSTALLATION ADDRESS Occupier: Tenants Address: 36 Arle Gardens Cheltenham DESCRIPTION AND EXTENT OF THE INSTALLATION Description of Installation Complete Installation Extent of electrical installation covered by this certificate: As per schedule of tests Gloucestershire GL51 8HR Gloucestershire GL51 8HR Tick boxes as appropriate) New installation |7~ Addition to an existing installation I Alteration to an existing installation I I FOR DESIGN I/We being the person(s) responsible for the design of the electrical installation, (as indicated by my/our signatures below) particulars of which are described above, having exercised reasonable skill and care when carrying out that design hereby CERTIFY that the design work for which I/We have been responsible is to the best of my/our knowledge and belief in accordance with BS7671: 2008 amended to 01/01/2008 except for any departures, if any, detailed as follows. Details of departures from BS7671 as amended (Regulations 120.3 and 120.4): The extent of liability of the signatory or signatories is limited to the work described above as the subject of this Certificate. For the DESIGN of the installation: "(Where there is mutual responsibility for the design) Date: 10/07/2010 Date: Name (IN BLOCK LETTERS) Richard Bryant Name (IN BLOCK LETTERS) Designer No. 1 Designer No. 2* Signature: Signature: FOR CONSTRUCTION I/We being the person(s) responsible for the construction of the electrical installation, (as indicated by my/our signatures below) particulars of which are described above, having exercised reasonable skill and care when carrying out the construction hereby CERTIFY that the construction work for which I/We have been responsible is to the best of my/our knowledge and belief in accordance with BS7671: 2008 amended to except for the departures, if any, detailed as follows. Details of departures from BS7671 as amended (Regulations 120.3 and 120.4): The extent of liability of the signatory or signatories is limited to the work described above as the subject of this Certificate. For the CONSTRUCTION of the installation: Date: 10/07/2010 Name (IN BLOCK LETTERS) Richard Bryant Constructor Signature: FOR INSPECTION AND TESTING I/We being the person(s) responsible for the inspection & testing of the electrical installation, (as indicated by my/our signatures below) particulars of which are described above, having exercised reasonable skill and care when carrying out the inspection and testing hereby CERTIFY that the work for which I/We have been responsible is to the best of my/our knowledge and belief in accordance with BS7671 : 2008 amended to 01/01/2008 except for the departures, if any, detailed as follows. Details of departures from BS7671 as amended (Regulations 120.3 and 120.4): The extent of liability of the signatory or signatories is limited to the work described above as the subject of this Certificate. For INSPECTION AND TEST of the installation: Date: 10/07/2010 Name (IN BLOCK LETTERS) Richard Bryant Signature: NEXT INSPECTION I I/We recommend that this installation is further inspected and tested after an interval of not more than 5 years Inspector Page 1 of 5 This form was developed by Megger Limited and is based on the model shown in Appendix 6 of BS7671 : 2008. © Megger Limited 2008

Megger - Yewtree

  • Upload
    others

  • View
    29

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Megger - Yewtree

MeggerCertificate No: 17

ELECTRICAL INSTALLATION CERTIFICATE

(REQUIREMENTS FOR ELECTRICAL INSTALLATIONS BS7671 [IEE WIRING REGULATIONS])

DETAILS OF THE CLIENT

Client: Alan Read

Address: 36 Arle Gardens

Cheltenham

INSTALLATION ADDRESS

Occupier: Tenants

Address: 36 Arle Gardens

Cheltenham

DESCRIPTION AND EXTENT OF THE INSTALLATIONDescription of Installation

Complete Installation

Extent of electrical installation covered by this certificate:

As per schedule of tests

Gloucestershire

GL51 8HR

Gloucestershire

GL51 8HR

Tick boxes as appropriate)

New installation |7~

Addition to anexisting installation I

Alteration to anexisting installation I I

FOR DESIGNI/We being the person(s) responsible for the design of the electrical installation, (as indicated by my/our signatures below) particulars of whichare described above, having exercised reasonable skill and care when carrying out that design hereby CERTIFY that the design work for whichI/We have been responsible is to the best of my/our knowledge and belief in accordance with BS7671: 2008 amended to 01/01/2008except for any departures, if any, detailed as follows. Details of departures from BS7671 as amended (Regulations 120.3 and 120.4):

The extent of liability of the signatory or signatories is limited to the work described above as the subject of this Certificate.For the DESIGN of the installation: "(Where there is mutual responsibility for the design)

Date: 10/07/2010

Date:

Name (IN BLOCK LETTERS) Richard Bryant

Name (IN BLOCK LETTERS)

Designer No. 1

Designer No. 2*

Signature:

Signature:

FOR CONSTRUCTIONI/We being the person(s) responsible for the construction of the electrical installation, (as indicated by my/our signatures below) particulars ofwhich are described above, having exercised reasonable skill and care when carrying out the construction hereby CERTIFY that theconstruction work for which I/We have been responsible is to the best of my/our knowledge and belief in accordance with BS7671: 2008amended to except for the departures, if any, detailed as follows.Details of departures from BS7671 as amended (Regulations 120.3 and 120.4):

The extent of liability of the signatory or signatories is limited to the work described above as the subject of this Certificate.For the CONSTRUCTION of the installation:

Date: 10/07/2010 Name (IN BLOCK LETTERS) Richard Bryant ConstructorSignature:

FOR INSPECTION AND TESTINGI/We being the person(s) responsible for the inspection & testing of the electrical installation, (as indicated by my/our signatures below) particularsof which are described above, having exercised reasonable skill and care when carrying out the inspection and testing hereby CERTIFY that thework for which I/We have been responsible is to the best of my/our knowledge and belief in accordance with BS7671 : 2008amended to 01/01/2008 except for the departures, if any, detailed as follows.Details of departures from BS7671 as amended (Regulations 120.3 and 120.4):

The extent of liability of the signatory or signatories is limited to the work described above as the subject of this Certificate.For INSPECTION AND TEST of the installation:

Date: 10/07/2010 Name (IN BLOCK LETTERS) Richard BryantSignature:

NEXT INSPECTIONI I/We recommend that this installation is further inspected and tested after an interval of not more than 5 years

Inspector

Page 1 of 5This form was developed by Megger Limited and is based on the model shown

in Appendix 6 of BS7671 : 2008. © Megger Limited 2008

Page 2: Megger - Yewtree

PARTICULARS OF SIGNATORIES TO THE ELECTRICAL INSTALLATION CERTIFICATE

Designer (No. 1) Name: Richard BryantAddress: 64 Hewlett Road

GL52 6AR

Company: Beechwood PropertyCheltenham Tel No:

Designer (No. 2) Name:(if applicable) Address:

Company:Tel No:

Constructor Name: Richard BryantAddress: 64 Hewlett Road

GL52 6AR

Company: Beechwood PropertyCheltenham Tel No:

Inspector Name: Richard BryantAddress: 64 Hewlett Road

GL52 6AR

Company: Beechwood PropertyCheltenham Tel No:

SUPPLY CHARACTERISTICS AND EARTHING ARRANGEMENTS (Tick boxes and enter details as appropriate)

EarthingTN-S

TN-C-S

TN-C

TT

IT

Alternative source ofsupply (to be detailed onattached schedules)

Number and Type of LiveConductorsA.c. Yes D.C. N/A

1 Phase,2 Wire Yes 2-Po!e

2 Phase,3 Wire

3 Phase.3 Wire

3 Phase.4 Wire

3-Pole

Other

Nature of Supply Parameters

Nominal voltage, U/U *1

Nominal frequency, f (1)

Prospective fault current, (2)pf

External loop impedance, Z '2>

Q

(Note: (1) by enquiry. (2) by enquiry or bymeasurement)

V

Hz

kA

Q

SupplyProtective DeviceCharacteristics

BSEN BS1361

Type 2

RatedCurrent 100

PARTICULARS OF INSTALLATION REFERRED TO IN THE CERTIFICATE

Means of EarthingDistributor'sFacility

InstallationEarthElectrode

Details of installation Earth Electrode: (where applicable)Type: (e.g. rod(s). tape etc) Location:

(Tick boxes and enter details as appropriate)

Electrode resistance to earth:

Q

Maximum DemandMaximum demand (load) KVA/AmpS (Delete as appropriate)

Main Protective Conductorsmaterial Copper csa 16Earthing Conductor:

Main protective bonding conductors: material Copper

To incoming water and/or gas service ^ To other elements:

csa 10

connection verified */

connection verified •/

Main Switch or Circuit-breaker

BS, Type and No. of poles: EN60947 3 2 Current rating 100

Location: Hallway

Rated residual operating current I

Fuse rating or setting: ™°

rnA and operating time of

Voltage rating 230

(applicable on|y when an RCD is

suitable and is used as a mainms (at I An ) circuit-breaker)

COMMENTS ON EXISTING INSTALLATION (in the case of an alteration or additions see Section 633)

SCHEDULES

The attached schedules are part of this document and this Certificate is valid only when they are attached to it.1 Schedules of Inspections and 2 Schedules of Test Results are attached.

(Enter quantities of schedules attached)

This form was developed by Megger Limited and is based on the model shownin Appendix 6 of BS7671 : 2008 © Megger Limited 2008 Page 2 of 5

Page 3: Megger - Yewtree

Megger,Certificate No: 17

SCHEDULE OF INSPECTIONS

Methods of protection against electric shock Prevention of mutual detrimental influenceBoth basic and fault protection:

N/A

N/A

N/A

N/A

(i) SELV

(ii) PELV

(iii) Double insulation

(iv) Reinforced insulation

Basic protection:

,/

i S

I N/A

N/A

(i) Insulation of live parts

(ii) Barriers or enclosures

(iii) Obstacles

(iv) Placing out of reach

Fault protection:

S

S

•/

Ident

s

s

s

•/

(a) Proximity of non-electrical services and other influences

(b) Segregation of band I and band II circuits or use ofband II insulation

(c) Segregation of safety circuits

ification

(a) Presence of diagrams, instructions, circuit charts andsimilar information

(b) Presence of danger notices and other warning notices

(c) Labelling of protective devices, switches and terminals

(d) Identification of Conductors

Cables and conductors

^(i) Automatic disconnection of supply:

•/

EH,/s

N/A

N/A

N/A

N/A

ii) N

N/A

(iii) E,

N/A

Presence of earthing conductor

Presence of circuit protective conductors

Presence of protective bonding conductors

Presence of supplementary bonding conductors

Presence of earthing arrangements for combinedprotective and functional purposes

Presence of adequate arrangements foralternative source(s), where applicable

FELV

Choice and setting of protective and monitoringdevices (for fault and/or overcurrent protection)

an-conducting location:

Absence of protective conductors

nth-free equipotential bonding:

Presence of earth-free local equipotential bonding

(iv) Electrical separation

•/

•/

AdditicS

,/

Provided for one item of current-usingequipment

Provided for more than one itemof current-using equipment

anal protection

Presence of supplementary bonding conductors

•/

•/

s

s

s

•/

Selection of conductors for current-carrying capacity andsimilar information

Erection Methods

Routing of cables in prescribed zones

Cables incorporating earthed armour or sheath, or runwithin an earthed wiring system, or otherwise adequatelyprotected against nails, screws and the like

Additional protection provided by 30 mA RCD for cables inconcealed walls (where required in premises not underthe supervision of a skilled or instructed person)

Connection of conductors

Presence of fire barriers, suitable seals and protectionagainst thermal effects

General

•/

s

s

s

•/

N/A

s

s

Presence and correct location of appropriate devices forisolation and switching

Adequacy of access to switchgear and other equipment

Particular protective measures for special installations andlocations

Connection of single-pole devices for protection orswitching in line conductors only

Correct connection of accessories and equipment

Presence of undervoltage protective devices

Selection of equipment and protective measuresappropriate to external influences

Selection of appropriate functional switching devices

Inspected by Richard Bryant Date(s) Inspected 10/07/2010

Notes: V to indicate an inspection has been carried out and the result is satisfactoryx to indicate an inspection has been carried out and the result was unsatisfactory

N/A to indicate the inspection is not applicableLIM to indicate that, exceptionally, a limitation agreed with the person ordering the work prevented the

inspection or test being carried outPage 3 of 5

This form was developed by Megger Limited and is based on the models shownin Appendix 6 of BS 7671 : 2008. © Megger Limited 2008

Page 4: Megger - Yewtree

Megger

Contractor Beechwood Properties And

Test date 10/07/2010

Signature

Schedule of Test Results Certificate No: 17

Address/Location of distribution board Ref

Location Hallway

Address 36 Arle Gardens

Cheltenham

Gloucestershire

GL51 8HR

1 Supply TN-S

TN-C-S

TN-CTT

IT

2 Ze at origin

3PFC

Installation Tester

Instruments

Megger MFT1553 6410-927/070807/4344

0.11

1.84

ohms

kA

Method of fault protection ADOS Equipment vulnerable to testing Emergency Lights

Description of Work New Installation

Ref.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

Circuit Description

Shower

Cooker

Kitchen Ring

Ground Ring

2nd Ring

Immersion

Bath Heater 1st

Bath Heater 2nd

Lights 1st

Fire Alarm

Cooker

Shower

1st Floor Ring

Lights Ground

Lights 2nd

Overcurrent Device

BSEN

EN60898

EN60898

EN60898

EN60898

EN60898

EN60898

EN60898

EN60898

EN60898

EN60898

EN60898

EN60898

EN60898

EN60898

EN60898

RatingIn

A

40

40

32

32

32

20

16

16

6

6

40

40

32

6

6

Short-circuitcap.

kA

6

6

6

6

6

6

6

6

6

6

6

6

6

6

6

Wiring

Inst.Ref.Math.

Conductors

live

mm2

10.0

10.0

2.5

2.5

2.5

2.5

2.5

2.5

1.5

1.5

10.0

10.0

2.5

1.5

1.5

cpc

mm*

4.0

4.0

1.5

1.5

1.5

1.5

1.5

1.5

1.0

1.0

4.0

4.0

1.5

1.0

1.0

Test Results

Continuity

R1+R2*

n0.10

0.06

0.27

0.18

0.21

0.56

0.06

0.05

0.13

0.48

0.72

R2*

a

0.63

0.32

0.73

0.68

Ring

Pass

Pass

Pass

.

Pass

InsulationResistance

Live/Live

MQ

>299

>299

>299

>299

>299

>299

>299

>299

>299

>299

>299

>299

>299

>299

>299

Live/Earth

Mil

>299

>299

>299

>299

>299

>299

>299

>299

>299

>299

>299

>299

>299

>299

>299

Polarity

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

EarthLoopimped-ance

Zs

n0.14

0.10

0.37

0.28

0.41

0.31

0.26

0.27

0.67

0.11

0.19

0.21

0.39

0.55

0.83

FunctionalTesting

RCDtime

ms

42.8

42.8

42.8

42.8

42.8

42.8

42.8

42.8

42.8

42.8

42.8

42.8

42.8

42.8

42.8

Other

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Remarks

x5 RCD Test 18.6

x5 RCD Test 18.6

x5 RCD Test 18.6

x5 RCD Test 18.6

x5 RCD Test 18.6

x5 RCD Test 18.6

x5 RCD Test 18.6

x5 RCD Test 18.6

x5 RCD Test 18.6

x5 RCD Test 18.6

x5 RCD Test 18.6

x5 RCD Test 18.6

x5 RCD Test 18.6

x5 RCD Test 18.6

x5 RCD Test 18.6

Deviations from Wiring Regulations and special notes: ' Complete column R1+R2 or R2

This form was developed by Megger Limited and is based on the model shownin Appendix 6 of BS7671 : 2008. © Megger Limited 2008

Page 4 of 5

Page 5: Megger - Yewtree

Megger.

Contractor Beechwood Properties And

Test date 10/07/2010

Signature

Method of fault protection ADOS

Schedule of Test Results Certificate No: 17

Address/Location of distribution board

Location Hallway

Address 36 Arle Gardens

Cheltenham

Gloucestershire

GL51 8HR

Ref

1 Supply TN-S

TN-C-S

TN-C

Installation Tester

InstrumentsMegger MFT1553 6410-927/070807/4344

IT

2 Ze at origin

3 RFC0.11 ohms

kA

Equipment vulnerable to testing Emergency Lights

Description of Work New Installation On Night Storage Heaters

Ref.

1

2

3

4

5

6

7

8

9

10

11

12

Circuit Description

Room 1

Room 2

Room 3

Room 4

Room 5

Room 6

Room 7

Room 8

Lounge

Lounge

Hallway

Hallway

Overcurrent Device

BSEN

EN60898

EN60898

EN60898

EN60898

EN60898

EN60898

EN60898

EN60898

EN60898

EN60898

EN60898

EN60898

RatingIn

A

20

20

20

20

20

20

20

20

20

20

20

20

Short-circuitcap.

kA

6

6

6

6

6

6

6

6

6

6

6

6

Wiring

Inst.Ref.Meth.

Conductors

live

mm2

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

cpc

mm2

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

Test Results

Continuity

R1+R2*

n0.28

0.30

0.25

0.15

0.36

0.40

0.44

0.45

0.13

0.15

0.17

0.12

R2*

O

Ring

InsulationResistance

Live/Live

MO

>299

>299

>299

>299

>299

>299

>299

>299

>299

>299

>299

>299

Live/Earth

MQ

>299

>299

>299

>299

>299

>299

>299

>299

>299

>299

>299

>299

Polarity

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

EarthLoopimped-ance

Zs

Q

FunctionalTesting

RCDtime

ms

Other

Remarks

. . _ . . .

Deviations from Wiring Regulations and special notes: * Complete column R1+R2 or R2

This form was developed by Megger Limited and is based on the model shownin Appendix 6 of BS7671 : 2008. © Megger Limited 2008

Page 5 of 5