Medium Voltage Product TPO 7x.xx Outdoor current transformers Highest voltage for equipment [kV] 36; 38,5; 40,5 Rated power-frequency withstand voltage (r.m.s.), 1 min. [kV] 70; 80; 90 Rated lightning impulse withstand voltage (peak) [kV] 170; 180; 200 Max. rated primary current [VA/cl] 2500 Rated short - time thermal current, 1 sec. [A] 100 Rated output, classes [kA] 5-30 / 0.2-1 / 5P ; 10P Reconnectible prim. or sec. Description The TPO 7x.xx transformers are cast in epoxy resin, capable of withstanding outdoor environmental conditions, and designed for insu- lation voltages from 36 kV to 40.5 kV. The TPO 7x.xx transformers are designed as single-or-multiple turn transformers, with one transformer ratio, and, if necessary, with the possibility to change over on the primary or secondary side. The number of secondary windings ranges from 1 to 4 (usually 2) depending on parameters (such as the accuracy class, short-circuit current, overcurrent factor…). The secondary windings are used for measurement or protection pur- poses, or for special use (testing windings, “PX” class).One terminal of each secondary winding used, and one terminal of the unused, short- circuited, winding must be earthed during the transformer operation. The transformer can be mounted in any position. The transformer body is fixed by using four screws. For ease of han- dling and assemblythe transformer is supplied with suspension lugs. The secondary winding is led out into a cast secondary terminal board covered with a sealable cover. Highest voltage fo equipment... 36 kV; 38,5 kV; 40,5 kV Rated primary currents 10;15;20;25;30;40;50;60;75;100;150;200;300;400;500;600;750;1000; 1250;1500; 2000;2500 A; primary current changeover range from 600 A to 1200 A. Different primary currents can be supplied to special order. Rated secondary currents...5 A; 1 A ((it is possible to combine different values in one transformer). Rated frequency ... 50 Hz; 60 HzThe transformers are designed and manufactured in conformity with the following standards and recommen- dations: IEC, VDE, ANSI, BS, GOST and CSN.

Medium Voltage Product TPO 7x.xx Outdoor current transformers€¦ · 1 sec. [A] 100 Rated output, classes [kA] 5-30 / 0.2-1 / 5P ; 10P Reconnectible prim. or sec. Description The

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Medium Voltage Product TPO 7x.xx Outdoor current transformers€¦ · 1 sec. [A] 100 Rated output, classes [kA] 5-30 / 0.2-1 / 5P ; 10P Reconnectible prim. or sec. Description The

Medium Voltage Product

TPO 7x.xxOutdoor current transformers

Highest voltage for equipment [kV] 36; 38,5; 40,5

Rated power-frequency withstand

voltage (r.m.s.), 1 min.[kV] 70; 80; 90

Rated lightning impulse withstand

voltage (peak)[kV] 170; 180; 200

Max. rated primary current [VA/cl] 2500

Rated short - time thermal current,

1 sec.[A] 100

Rated output, classes [kA] 5-30 / 0.2-1 / 5P ; 10P

Reconnectible prim. or sec.

Description

The TPO 7x.xx transformers are cast in epoxy resin, capable of withstanding outdoor environmental conditions, and designed for insu-lation voltages from 36 kV to 40.5 kV.

The TPO 7x.xx transformers are designed as single-or-multiple turn transformers, with one transformer ratio, and, if necessary, with the possibility to change over on the primary or secondary side.

The number of secondary windings ranges from 1 to 4 (usually 2) depending on parameters (such as the accuracy class, short-circuit current, overcurrent factor…).

The secondary windings are used for measurement or protection pur-poses, or for special use (testing windings, “PX” class).One terminal of each secondary winding used, and one terminal of the unused, short-circuited, winding must be earthed during the transformer operation.The transformer can be mounted in any position.

The transformer body is fixed by using four screws. For ease of han-dling and assemblythe transformer is supplied with suspension lugs.

The secondary winding is led out into a cast secondary terminal board covered with a sealable cover.

Highest voltage fo equipment... 36 kV; 38,5 kV; 40,5 kV

Rated primary currents 10;15;20;25;30;40;50;60;75;100;150;200;300;400;500;600;750;1000;1250;1500; 2000;2500 A; primary current changeover range from 600 A to 1200 A.Different primary currents can be supplied to special order.

Rated secondary currents...5 A; 1 A ((it is possible to combine different values in one transformer).

Rated frequency ... 50 Hz; 60 HzThe transformers are designed and manufactured in conformity with the following standards and recommen-dations: IEC, VDE, ANSI, BS, GOST and CSN.

Medium Voltage Product

TPO 7x.xx

Outdoor current transformers

Description

The TPO 7x.xx transformers are cast in epoxy resin, capable of withstanding outdoor environmental conditions, and designed for insulation voltages from 36 kV to 40.5 kV.

The TPO 7x.xx transformers are designed as single-or-multiple turn transformers, with one transformer ratio, and, if necessary, with the possibility to change over on the primary or secondary side.

The number of secondary windings ranges from 1 to 4 (usually 2) depending on parameters (such as the accuracy class, short-circuit current, overcurrent factor…).

The secondary windings are used for measurement or protection purposes, or for special use (testing windings, "PX" class).One terminal of each secondary winding used, and one terminal of the unused, short-circuited, winding must be earthed during the transformer operation.

The transformer can be mounted in any position. The transformer body is fixed by using four screws. For ease of handling and assembly the transformer is supplied with suspension lugs.

The secondary winding is led out into a cast secondary terminal board covered with a sealable cover.

Highest voltage fo equipment... 36 kV; 38,5 kV; 40,5 kV

Rated primary currents 10;15;20;25;30;40;50;60;75;100;150;200;300;400;500;600;750;1000;1250;1500; 2000;2500 A; primary current changeover range from 600 A to 1200 A.Different primary currents can be supplied to special order.

Rated secondary currents...5 A; 1 A ((it is possible to combine different values in one transformer).

Rated frequency ... 50 Hz; 60 HzThe transformers are designed and manufactured in conformity with the following standards and recommendations: IEC, VDE, ANSI, BS, GOST and CSN.

170; 180; 200

70; 80; 90

36; 38,5; 40,5

2500

100

[VA] 5-30 / 0.2-1 / 5P ; 10P

Reconnectible prim. or sec.

Highest voltage for equipment [kV]

Rated power-frequency withstand

Rated lightning impulse withstand

[kV]

[A]

[kV]

Rated output, classes

[kA]

Max. rated primary current

voltage (peak)

voltage (r.m.s.), 1 min.

Rated short - time thermal current,

1 sec.

Page 2: Medium Voltage Product TPO 7x.xx Outdoor current transformers€¦ · 1 sec. [A] 100 Rated output, classes [kA] 5-30 / 0.2-1 / 5P ; 10P Reconnectible prim. or sec. Description The

TPO 7x.xx / Technical data 2

Labelling of the voltage transformer outlets

Basic marking

0...up to 600 A multi-turn1...up to 400 A one-turn2...up to 600 A one-turn3...up to 1250 A one-turn4...up to 1500 A one-turn5...up to 2000 A one-turn 6...up to 2500 A one-turn

1...non-reconnectable on primary side2...reconnectable on primary side

... design

TPO 7 x . x x

36 / 70/ 170 kV38,5 / 80 /180 kV40,5 / 95 / 200 kV

a) Single-core design b) Double-core design

c) Three-core design

d) Single-core design, reconnectable on the secondary side

e) Double-core design, reconnectable on the secondary side

f) Double-core design, reconnectable on the primary side

Insulation levels for TPO 7x.xx transformers

TPO 7 x . x x

0...up to 600 A multi-turn1...up to 400 A one-turn2...up to 600 A one-turn3...up to 1250 A one-turn4...up to 1500 A one-turn5...up to 2000 A one-turn 6...up to 2500 A one-turn

1...non-reconnectable on primary side2...reconnectable on primary side

... design

Basic marking

Insulation levels for TPO 7x.xx transformers

Labelling of the voltage transformer outlets

36 / 70/ 170 kV38,5 / 80 /180 kV40,5 / 95 / 200 kV

a) Single-core design

d) Single-core design, recon nectable on the secondary side

b) Double-core design

e) Double-core design, recon nectable on the secondary side

c) Three-core design

f ) Double-core design, recon nectable on the primary side

TPO 7x.xx / Technical data 2

Page 3: Medium Voltage Product TPO 7x.xx Outdoor current transformers€¦ · 1 sec. [A] 100 Rated output, classes [kA] 5-30 / 0.2-1 / 5P ; 10P Reconnectible prim. or sec. Description The

Dimensions

TPO 7x.xx / Technical data 3

Dimensions

Drawing n. 44615810

Drawing n. 44615790 Drawing n. 44615800

WEIGHT: appr. 90kg

CREP. DISTANCE: 1600mm

WEIGHT: appr. 90kg

CREP. DISTANCE: 1600mmWEIGHT: appr. 90kg

CREP. DISTANCE: 1600mm

TPO 71.11-76.11

TPO 7x.xx / Technical data 3

Dimensions

Drawing n. 44615810

Drawing n. 44615790 Drawing n. 44615800

WEIGHT: appr. 90kg

CREP. DISTANCE: 1600mm

WEIGHT: appr. 90kg

CREP. DISTANCE: 1600mmWEIGHT: appr. 90kg

CREP. DISTANCE: 1600mm

TPO 71.11-76.11

TPO 7x.xx / Technical data 3

Dimensions

Drawing n. 44615810

Drawing n. 44615790 Drawing n. 44615800

WEIGHT: appr. 90kg

CREP. DISTANCE: 1600mm

WEIGHT: appr. 90kg

CREP. DISTANCE: 1600mmWEIGHT: appr. 90kg

CREP. DISTANCE: 1600mm

TPO 71.11-76.11

WEIGHT: appr. 90kgCREP. DISTANCE: 1600mm

Drawing n. 44615790 Drawing n. 44615800

Drawing n. 44615800

WEIGHT: appr. 90kgCREP. DISTANCE: 1600mm

WEIGHT: appr. 90kgCREP. DISTANCE: 1600mm

TPO 71.11-76.11

TPO 7x.xx / Technical data 2

Page 4: Medium Voltage Product TPO 7x.xx Outdoor current transformers€¦ · 1 sec. [A] 100 Rated output, classes [kA] 5-30 / 0.2-1 / 5P ; 10P Reconnectible prim. or sec. Description The

1VLC

0005

41 -

Rev.

4, e

n 20

10.1

1.23