Medium Voltage Distribution WI up to 52 kV Gas-Insulated Switchgear with Vacuum Circuit-Breaker 1, 2 or 3-phase System configuration

Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

Embed Size (px)

Citation preview

Page 1: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

Medium Voltage Distribution

WIup to 52 kVGas-Insulated Switchgear with Vacuum Circuit-Breaker 1, 2 or 3-phase

System configuration

Page 2: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

Conditions of DeliveryThe General Conditions of Delivery as amended shall apply.

IllustrationsThe illustrations are not binding

Page 3: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

3WI EN

WI Contents

■ Overview .............................................................................................................. 4

□ Features ......................................................................................................... 4

■ Product description ............................................................................................ 5

□ Technical description ...................................................................................... 5

□ Components of the switching unit .................................................................. 6

□ Modular design ............................................................................................... 7• Single busbar WIA up to 36 kV ..................................................................... 7• Double busbar WIB up to 36 kV ................................................................... 7• Single busbar WIA 52 kV, 250 kV BIL .......................................................... 8• Double busbar WIB 52 kV, 250 kV BILL ....................................................... 8

□ Operator interfaces ........................................................................................ 9

□ Switchgear panels ........................................................................................ 10

□ Current/voltage transformers ....................................................................... 11

□ Busbar modules ........................................................................................... 13

□ Modules ........................................................................................................ 15

□ Interlocks ...................................................................................................... 16

□ Gas compartment monitoring WIA, WIB ...................................................... 17

□ Gas-filled compartments of the WIA/ WIB ................................................... 18

■ Standards, regulations, provisions and standards....................................... 19

□ Type designation .......................................................................................... 20

□ Applied norms .............................................................................................. 21

■ Selection tables ................................................................................................ 22

□ WIA/WIB 12 kV ............................................................................................ 22

□ WIA/WIB 17 kV ............................................................................................ 24

□ WIA/WIB 24 kV ............................................................................................ 26

□ WIA/WIB 36 kV ............................................................................................ 28

□ WIA/WIB 38 kV ............................................................................................ 30

□ WIA/WIB 40.5 up to 52 kV ........................................................................... 32

□ WIA/WIB 1 and 2-pole, for stationary railway traction power supply 50/60 hz......34

■ Range of products ............................................................................................ 36

□ Single busbar panels WIA ............................................................................ 36

□ Double busar panels WIB ............................................................................ 37

□ Disconnector panel ...................................................................................... 38

□ Bus section coupler / riser panel .................................................................. 38

□ Bus section coupler, Bus coupler, metering panel ....................................... 39

■ Cable connections ............................................................................................ 40

■ Ecological considerations ............................................................................... 43

■ Design data ....................................................................................................... 44

□ Space requirements - dimensions and weights ........................................... 44

□ Busbar connection with fully insulated conductor bars ................................ 48

■ Shipping instructions ....................................................................................... 50

□ Delievery, packaging .................................................................................... 50

Page 4: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

4 WI EN

WI

FeaturesThe gas-insulated and metal-enclosed switchgear WI has been designed for operation in power plants, transformer substations and industrial networks.The WI switchgear with vacuum circuit-breaker features maximum availability, optimum operator safety and clear design using SF6 gas as insulating medium. The switchgear units are insensitive to environmental influences,suchashumidity,dustandaggressivegases,andoffercomplete operator safety. Their clear design facilitates operation.

Essential features ■Parts under medium voltage in SF6 atmosphere

□ insensitive to air humidity, air pollution and foreign matter ■High degree of operator safety

□ complete metal enclosure for all system components under medium voltage ■Compact and clear design ■No mechanically moved parts in the busbar section ■No problems with SF6 decomposition products

□ currents are switched in the vacuum interrupter chamber ■ Inert insulating gas SF6protectstheswitchgearagainstfire ■Three-pole enclosure of the functional compartments

□ negligible sheath currents □ small number of static and dynamic seals □ few gas compartments, pressure relief devices and gas monitoring

devices □ easy access □ moderate pressure increase in case of internal arcs □ straightforward kinematics between drive and circuit-breaker or

three-position switch ■Steel used as enclosure material

□ high pressure proofness □ good screening effect against X rays

■Optimum security of operation □ complete interlocking system □ separate actuators for isolation and earthing □ automatic circuit-breaker ON or OFF operation in case of earthing at

the outgoing feeder ■High capacity current and voltage transformer ■Delivery of prefabricated switchgear panels to the construction site ■Fully shrouded terminals

□ pluggable, fully insulated cable end boxes ■Switchgear extension possible

□ on both sides □ from single to double busbar system.

Overview

Single busbar WIA up to 36 kV

Page 5: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

5WI EN

WI Product description

Technical descriptionWIpanelsaresuitableforconfiguringsingleordoublebusbarswitchgearinconjunction with indoor installation.

WI switchgear units are completely metal-enclosed. The busbar compartmentwhichaccommodatesfixedpartsonlyissegregatedgas-tightfromtheflange-mountedswitchingunit.Theswitchingunitcomprisesthethree-position switch with isolating and earthing functions and the vacuum circuitbreaker; in case of double busbar systems, there are two three-position switches with isolating and earthing functions and the vacuum circuit-breaker.

The busbar compartment and the switching unit feature three-pole enclosure. Single-pole enclosure is provided in the area of the toroidalcore current transformers which are located in an easily accessible position outside of the SF6 atmosphere. The compact design results in a very clear switchgear arrangement with low space requirement; it has the advantage that a switching unit can be mounted or removed very quickly without the busbar requiring isolation from the power supply.

The panels are equipped with a low-voltage cabinet for the required measuring and protection relays or the terminal strips. The high performance of the instrument transformers installed means that not only electronic but also conventional protection relays can be deployed.

Thanks to its design, this panel series permits straightforward extension of an existing switchgear on both sides, and extension from single to double busbar models.

Gas-insulated double busbar switchgear WIBRated voltage up to 36 kV; rated peak withstand current up to 100 kA; rated current up to 2500 A

Page 6: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

6 WI EN

WI Product description (contd.)

Components of the switching unitThe circuit-breaker in question is a vacuum circuit-breaker. The switching unit has been equipped, for its isolating and earthing functions, with a three-position switch featuring the positions:

EarthingThe metal-enclosed WI series switchgear is equipped with a separate earthing line running along the length of the switchgear.

WiringWiringiseffectedwithflexiblecables(HO7V-K)inthetechnicallyrequiredcross-sections.

Corrosion protectionIf desired, the indoor panels WIA and WIB can be provided optionally with enhanced corrosion protection. To ensure optimum switchgear protection, the environmental installation conditions, such as wind-borne sand, aggressivedust(tobedefinedassaltdust,cokedust,cementdustetc.),vermin(termites),increasedhumiditylevels,aggressiveatmosphere(typeofchemicalsandtheirconcentrationtobedefined)mustbespecified.

Installation locationsThe switchgear has been designed for installation in closed electrical operating facilities.

Connection of cables and barsThe cables are connected by means of metal-enclosed connectors. Switchgear units equipped with multiple connection tanks enable connectionofuptofive300mm2 cables or two 1250 mm2 cables per phase, depending on the insulation rating.Alternatively, fully insulated busbar systems or SF6-insulated conductor bars can be used.

Low voltage cabinetThe secondary devices for protection relay, control, measurement, billing metering and other systems are installed in the low-voltage cabinet. The low-voltage cabinet is separated systematically from the primary part, is shock-proof and arc-resistant. It is an independent, closed low-voltage compartment with mechanical and electrical interfaces to the vertical section(screw-fastenedplug-and-socketconnector).The clear separation between the rack and the low-voltage cabinet is a particularadvantageforthecompanyoperatingtheswitchgear.Retrofittingspare panels and conversion or replacement of complete low-voltage cabinets(e.g.duetoprocesschanges)atalaterdateisalsostraightforward. The panel remains completely enclosed even if the low-voltage cabinet is not attached.Optional inspection ports can be integrated in the torsion-resistant door of the low-voltage cabinet, the door also being able to accommodate measuring instruments, control elements and protection relays.

Disconnector ON(CLOSE)Disconnector earthing switch OFF(TRIP)Earthing switch ON(CLOSE)

Page 7: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

7WI EN

WI Product description (contd.)

Modular design

Single busbar WIA up to 36 kV Tank with vacuum circuit-breaker and disconnector / earthing switch Drive with control panel and pressure gauge for gas monitoring Tank with busbar Supporting structure with cable connection area Low voltage cabinet

Double busbar WIB up to 36 kV Tank with vacuum circuit-breaker and disconnector / earthing switch Drive with control panel and pressure gauge for gas monitoring Tank with busbar 1 Tank with busbar 2 Supporting structure with cable connection area Low voltage cabinet

A

BC

D

E

A

B

C2

C1

D

E

AB

DE

C1C2

AB

E

CD

Page 8: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

8 WI EN

WI Product description (contd.)

Single busbar WIA 52 kV, 250 kV BIL Tank with vacuum circuit-breaker and disconnector / earthing switch Drive with control panel and pressure gauge for gas monitoring Tank with busbar Supporting structure with cable connection area Low voltage cabinet

Double busbar WIB 52 kV, 250 kV BILL Tank with vacuum circuit-breaker and disconnector / earthing switch Drive with control panel and pressure gauge for gas monitoring Tank with busbar 1 Tank with busbar 2 Supporting structure with cable connection area Low voltage cabinet

A

B

C

D

E

A

B

C2

C1

D

E

AB

E

CD

AB

DE

C1C2

Page 9: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

9WI EN

WI Product description (contd.)

Operator interface, double busbar WIB

1

21

2

3

18

45

16

17

6

SS278

9

101112SS1

1314

15

Operator interface, double busbar WIB

Operator interface, single busbar WIA

1

2

3

18

45

16

17

9

1011

12SS1

13

14

Operator interface, single busbar WIA

Operator interfaces for WIA (single busbar) and WIB (double busbar)1 Button „circuit-breaker ON“2 Button „circuit-breaker OFF“3 Opening for charging the energy- storing device by means of a slide4 PositionindicatorEnergy-storingdevice(charged/released)5 Circuit-breaker position indicator 6 Switchpositionindicator,disconnector(SS2)7 Openingforoperationofthedisconnector(SS2)8 Interrogating lever, disconnector9 Earthing switch position indicator10 Opening for operation of the earthing switch11 Interrogating lever “earthing switch”12 Switchpositionindicator,disconnector(SS1)13 Openingforoperationofthedisconnector(SS1)14 Interrogating lever, disconnector15 Mechanical lock-out with cylinder lock16 Rating plate17 Insulating gas monitoring device18 Operations counter

SS1:busbar1(correspondstothelowerbusbartank)SS2:busbar2(correspondstotheupperbusbartank)

Page 10: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

10 WI EN

WI Product description (contd.)

6

8

7

5

4

2

1

3

8

7

9 10

10

6

5

4

2

1

3

8

1

3

2

7

6

5

4

10

10

9

8

7

6

5

4

1

2

3

Switchgear panelsSingle busbarSwitchgear panel WIA up to 36 kV

Double busbarSwitchgear panel WIB up to 36 kV

1 Drive mechanism2 Vacuum circuit-breaker3 Low voltage cabinet4 Cable end boxes5 Current transformers6 Busbar7 Disconnector /earthing switch8 Pressure relief device

1 Drive mechanism2 Vacuum circuit-breaker3 Low voltage cabinet4 Cable end boxes5 Current transformers6 Busbar I7 Disconnector /earthing switch SSI8 Busbar II9 Disconnector /earthing switch SSII10 Pressure relief device

Switchgear panel WIA up to 52 kV Switchgear panel WIB up to 52 kV

1 Drive mechanism2 Vacuum circuit-breaker3 Low voltage cabinet4 Cable end boxes5 Current transformers6 Busbar7 Disconnector /earthing switch8 Pressure relief device

1 Drive mechanism2 Vacuum circuit-breaker3 Low voltage cabinet4 Cable end boxes5 Current transformers6 Busbar I7 Disconnector /earthing switch SSI8 Busbar II9 Disconnector /earthing switch SSII10 Pressure relief device

Page 11: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

11WI EN

WI Product description (contd.)

Current/voltage transformersCurrent transformersThe current transformers are designed as toroidal-core transformers and are put onto the cable outgoing feeder areas with single-pole enclosure. The current transformers in line with the busbar consist of identical units. There, they are slipped onto the busbar areas which also feature singlepole enclosure. The capacity of the current transformers is designed in such a way that supply of conventional protective devices is also possible.

Upto3transformers(3cores)canbeaccommodatedperphaseandoutgoing feeder. The transformers can also be exchanged subsequently. Threecurrenttransformers(3cores)perphasecanalsobeinstalledinlinewith the busbar, in order to measure its currents.

A special current transformer arrangement is the „bus coupler panel within one panel width“. In the double busbar top attachment tank, one core of max.80mmheightwithanIDof≤135mmandanODof≥195mmcanbeinstalled for each phase. The low voltage is led out via a max. 7-pole line which is SF6 proof.

DimensionsOutgoing feeder: Transformer ID 185 mm

Transformer OD 275 mm

Max. stacking height 160 mm

In line with busbar:Minimum ID 185 mm

Maximum OD 250 mm

Maximum stacking height for allcores incl. intermediate layer 225 mm

Measurement Protection/dyn (kA) 100

Ith(3sec) (kA) 40

Class 0.5 M 5 10 P 40 10 P 10

Corerating(VA) (VA) up to 15 up to 5 up to 30

Primary rated current (A) 150 up to 2500

Secondary rated current (A) 1 or 5

Current transformer in linewith the busbar

Page 12: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

12 WI EN

WI Product description (contd.)

■on the busbar A separate metering panel with a set of inductive voltage transformers is provided to this effect. Taking account of the high priority of the busbar, a disconnector enables isolation of the transformer section. Both disconnector and transformer are located in separate compartments. Thus, any damage which might occur in the vicinity of the transformer does not affect the isolating area or the busbar.

Performance characteristic

1

2

Ratings: up to 50 VA Class: 0.5

1 Multi-tank2 Test cable connector

Voltage transformer in outgoing feeder cable (connectionviamulti-tank)

Voltage transformer on busbar

Voltage transformerThe conventional solution for the inductive voltage transformer is a separate single-phase metalenclosed module which can be connected via cable connectors almost anywhere in the busbar area and on the outgoing feeder cable, and thus arranged in practically any location as required.

■ in the outgoing feeder area Another design comprises metal-enclosed inductive voltage transformers directlyflangemountedtotheoutgoingfeederblock,withtheisolating/earthing device mounted upstream. An externally operated isolating feature prevents the voltage transformer from being endangered/ put at risk during DC tests on the cable.

Page 13: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

13WI EN

WI Product description (contd.)

Busbar modules ■Gas tank incl. installation parts ■Busbar ■Coverattachmentonmountingflangewithorwithoutpressurerelief.

Allfivebusbarcompartmentsrequireonepressurereliefdevice.Ifitisnot possible to mount the device to the ends of the busbar tanks, e.g. if a tank for voltage transformer connection or a busbar earthing switch is located on the busbar end, or if the switchgear consists of over 10 panels, every fifthpanelisequippedwithapressurereliefdeviceonthemountingflange

■Coverattachmentonthestopflangeoftheleft-handandright-handendpanel, with or without pressure relief, to connect metalenclosed voltage transformers with cable connection to the front. ■Gas lines incl. pressure gauges; preferably attached to the end panel. (Onlyonceforeachgascompartment.) ■Desiccantfor4busbartankseach,orforeachgascompartment.(Cannotbemountedonswitchgearpanelsequippedwithpressurereliefdevice.) ■Compensation element for busbar tanks. Required after 20 single busbar panels, and after 10 double busbar panels. □ Disconnector for bus sectionalizer □ Earthing switch for bus sectionalizer to the left and right of the

disconnector

Page 14: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

14 WI EN

WI Product description (contd.)

Accessories (for overall system) ■SF6 gas for on-site assembly of the busbar sections

□ Special paint □ Corrosion protection in case of extreme environmental conditions □ Panellabelingaccordingtospecification

■Operating elements, operating crank for vacuum circuit-breaker, disconnector, earthing switch; for the busbar section’s movable segregating cover. □ Star handle spanner □ Hex. spanner

■Castors ■Transportcoverforthebusbartanks(canbereturned) ■ Jack rings

□ Integrated Voltage Detection System IVIS □ Earthing and short-circuit device, 3-phase incl. operating rod □ Cable dummy plug □ Cable test socket on cable connector for cable measurement □ Blanking caps for live cable connectors which have been withdrawn

■ always required □ optional

Auxiliary equipment for transport onlyPossible arrangement of the castors Castors to be used for movements in longitudinal direction for transverse movements

1

2

3

123

Page 15: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

15WI EN

WI Product description (contd.)

ModulesThe modules and attachments shown on this page apply to

■ outgoing feeder panels ■ incoming feeder panels ■ panels with circuit-breaker in case of coupler panels and bus sectionalizers.

Switching device module ■Gas tank incl. pressure relief device, gas lines and pressure gauge ■Switching devices with three-position switch and vacuum circuit-breaker, desiccant

Drive section module ■Drive casing with drive mechanisms incl. interlocks ■Attachment of drive casing on switching device module incl. connecting parts

Attachments for the vacuum circuit-breaker ■Motor drive mechanism to charge the energy-storing device ■Auxiliary switch, 8, 12 or 16 contacts; 8 contact elements are required for thebasiccircuitry(material:silver[normal],gold,silver-palladium) ■Passingcontactforpulsecontacttimestretching(contactsnormalorgold-plated) ■Pushswitchactuatedbyenergystoringdevice.(Pushswitchesforbasiccircuitryincludedinbasicdesign) ■Pushswitch,actuatedby“ON-OFF“pushbutton.(Thebasicdesignincludes1pushswitchforeach) ■Shunt closing release, 1 ea. ■Shunt opening release, 1 or 2 ea. with or without auxiliary spring energy store ■Secondary release, 1 or 2 ea., or in case of design without undervoltage release: 3 ea. ■Undervoltage release, with or without time delay ■Blocking coil on „ON“ pushbutton. Always required on coupler switch in case of bus section coupler and bus coupler, consisting of 2 panels (switchgearpanel+busriserpanel) ■Blocking coil on „OFF“ pushbutton. Always required on coupler switch in caseofbussectioncouplerandbuscoupler,consistingof1or2panel(s)(switchgearpanel+busriserpanel) ■Mechanicallock-outwithlock(forvacuumcircuit-breakerandthree-positionswitch) ■Counter

Attachments for three-position switch ■Motor-drive mechanism. In case of single busbar: 1 motor-drive mechanism each for isolating and earthing movements. In case of double busbar: 1 motor-drive mechanism for the isolating movement of busbar 1, busbar2andearthingmovementofbusbars1+2.Thevacuumcircuitbreaker‘ s ON button features a mechanical lock-out. ■An auxiliary switch, 2-20 contact elements each, for disconnecting and earthingmovement.(Material:silver(normal),gold,silverpalladium) ■ Interlocking solenoid. Single busbar: only in circuit-breaker panel of coupler and in bus riser panel of bus sectionalizer. Generally required in case of double busbar. If the interlocking solenoids are not installed in caseofremotecontrol(motor-drivemechanism)ofthethree-positionswitch, the local actuation is not locked. In this case, mechanical lock-outs(locks)arerequiredonthe„ON“buttonofthevacuumircuit-breakerand on the threeposition switch. ■ always required

□ optional

Page 16: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

16 WI EN

WI Product description (contd.)

InterlocksActuation of the three-position switch and the continuous mechanical interlock between circuitbreaker and three-position switch are designed in such a way that the operator can proceed as usual. This means separate, completely interlocked actuation for the switching procedures ”Establishing isolating distance” and “Earthing”. For the earthing procedure, which is only possible with the three-position switch in isolated position, the circuit-breaker switched off and the circuit-breaker energy-storing device pre-charged, the circuitbreaker is connected positively after the contact blades have beeninserted into the earthing contacts, and protected against immediate mechanical or electrical switching OFF. Vice versa, on de-earthing, the circuit-breakerisfirstswitchedoffpositivelybeforetheisolatingdistancetothe earthing contacts established. The interlocks ensure that each switching operation is always performed completely. Thus, once the switching operation has commenced, the motion cannot be reversed, if applicable, and the operating lever cannot be removed before it reaches its end position.

The description only refers to the single busbar. In the case of double busbars, some of the internal interlocking functions of the panel, as well as all inter-panel interlocking functions are performed by electro-mechanical interlocks(blockingcoil).

The following interlocking functions are provided: ■Disconnector does not switch ON while the circuit-breaker or the earthing switch are ON ■None of the disconnectors switches OFF while the circuit-breaker or the earthing switch are ON ■Circuit-breaker only switches ON with the disconnector in its end position ■No earthing with disconnector engaged ■No earthing with circuit-breaker ON ■No earthing without circuit-breaker being in ready-to-operate condition ■Automatic connection of circuitbreaker during earthing ■Automatic disconnection of circuit- breaker during de-earthing

The following has been ensured: ■The operating crank cannot be removed from the disconnector or earthing switch before it has reached its end positions completely ■The circuit-breaker cannot be actuated while a switching operation is being performed on the disconnector or earthing switch ■The circuit-breaker cannot be switched off with the three-position switch in earthing position ■All interlocks act partly mechanically and partly electrically ■An operating crank can only be inserted on the disconnector or earthing switch once the insertion opening has been released via a manual interrogation system. ■All interlocks also effective when the three-position switch is motor-actuated.

Page 17: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

17WI EN

WI Product description (contd.)

Gas compartment monitoring

Single busbar WIA with bus section coupler

Gas compartment monitoring

Double busbar WIB with bus coupler

Gas connector socket (disposal valve)Pressure gauge

Gas-tight electricalbushing

Check valve

1

2

1 Gas-filled busbar compartments2 Gas-filled circuit-br eaker compartments

Gas connector socket (disposal valve)Pressure gauge

Gas-tight electricalbushing

Double check valve

1

2

3

1 Gas-filled busbar2 compartments2 Gas-filled busbar1 compartments3 Gas-filled circuit-br eaker compartments

Page 18: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

18 WI EN

WI Product description (contd.)

Gas-filled compartments of the WIA/B series panels

WIA up to 40.5 kV,single busbar

WIB up to 40.5 kV,double busbar

WIA up to 52 kV,single busbar

WIB up to 52 kV,double busbar

WIA up to 36 kV,single busbar

WIB up to 36 kV,double busbar

Gas-filledcircuit-breaker compartment

busbar 1 compartment

busbar 2 compartment

Page 19: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

19WI EN

WI

WI series switchgear units are ■metal enclosed ■SF6 insulated ■ prefabricated and type-tested ■ tested for internal faults

Ambient and operating conditionsWI switchgear units are to be operated under normal operating conditions accordingtothespecificationsEN60694ortheIECpublication60694(new:IEC62271-1).

Operation under conditions other than these is only admissible upon consultation with and with the consent of the manufacturer.

Degrees of protection against foreign objects and accidental contact

Other ambient temperaturesTherated(normal)currentsINspecifiedintheselectiontablesrefertoamaximum ambient switchgear temperature of 40 °C.

In case of different maximum ambient temperatures T of the switchgear, between+25°Cand+55°C,theappropriatenormalcurrentINT can be determined from the following formula:

1) Optional: “minus 25 indoors”2) Optional up to 55 °C in case of reduction of normal currents3) Optional up to 40 °C in case of reduction of normal currents4) Higher installation altitudes possible on request

Main electric circuits IP 65Drives IP 2X, IP 5X1)

Low-voltage cabinets and cable connection compartments(operator’ssidewithcablecompartmentcoverandsidepanels)

IP 3X, IP 5X1)

1) Optional

105 - T65

At 25 0C ≤ T < 40 0C INT = IN

At 40 0C < T ≤ 55 0C INT = IN105 - T

650.7

Ambient conditionsTemperature class "Minus 25 indoors” 1)

Min./max. ambient temperature °C -51) / 40 2)

Averagevalueover24hours(max.) °C 353)

Maximum installation altitude above sea level

m 1000 4)

Insulating gasType Sulphurhexafluoride(SF6)

Design pressure pre at 20 °C MPa 0.03 - 0.05

Standards Regulations, provisions and standards

Page 20: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

20 WI EN

WI

Type designationThe type designation of the type-tested, prefabricated panels contains information about their design, rated voltage, insulation level, panel width and panel height. Example:Prefabricated, type-tested WIseries panel with single busbar, for indoor installation, version ARated peak withstand current 100 kARated voltage 12 kV; insulation level acc. to list 2Panel width: 600 mm, panel height: 2100 mmType designation: WI A 10 / 12-2 / 621

Type designationSeries

Version

WI . . .

A

/ . . - .ExplanationFully insulated (SF6) switchgear panels, primarily for distributionsubstations, for very stringent requirements

Single busbar, indoors

B

8

10

Double busbar, indoors

Rated peak withstand current 80

100

kA

kA

Rated voltage

Dimension code WI A

/ 12-2

/ 17-2

/ 24-2

/ 36-2

/ 38-2

/ 40.5-2

/ 52-2

up to 40.5 kV / 621

upper rated voltage 12

17.5

kV

kV

24

36

kV

kV

Panel width

38

40.5

kV

kV

52

600

kV

mm Panel height 2100 mm

WI

WI

A

B

WI B

up to 52

up to 40.5

up to 52

kV

kV

/ 626

/ 627

kV / 633

600

600

mm

mm

600 mm

2664

2750

3314

mm

mm

mm

Standards Regulations, provisions and standards (contd.)

Page 21: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

21WI EN

WI

Designation IEC standard IEC classes EN standardSwitchgear IEC 62271-200

IEC 60694(new IEC 62271-1)

Category for operating availability:LSC 2APartition class(compartmentalization class): PM

EN 62271-200EN 60694(new EN 62271-1)

Behaviour in case of internal faults IEC 60298 EN 60298Circuit-breaker IEC 62271-100 M2, E1, C1 EN 62271-100Earthing switch IEC 62271-102 E2 EN 62271-102Three position disconnector IEC 62271-102 M1 EN 62271-102Current transformers IEC 60044-1 EN 60044-1Inductive voltage transformers IEC 60044-2 EN 60044-2Voltage detection systems IEC 61243-5Protection against accidental contact, foreign objects and water

IEC 60529 EN 60529

Erection HD 637 S1Operation of electrical equipment EN 50110

Applied normsWI switchgear units meet the following standards and regulations:

Standards Regulations, provisions and standards (contd.)

Page 22: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

22 WI EN

WI

Type

WIA

Pan

el w

idth

8/12-2/621mm

Rated insulation levelR

ated

vol

tage

Rat

ed li

ghtn

ing

impu

lse

with

stan

d vo

ltage

kV kV

Rat

ed p

ower

freq

uenc

yw

ithst

and

volta

ge

Rat

ings

of i

sola

ting

dist

ance

kV kV/kV

Des

ign

pres

sure

P r a

t 20

0 C

5)

Rat

ed fr

eque

ncy

bar0.8

Hz

Rat

ed (n

orm

al) c

urre

nt3)

Rat

ed p

eak

with

stan

d cu

rren

teq

ual t

o ra

ted

shor

t-circ

uit

mak

ing

curr

ent

A630

kA80

Rat

ed s

hort-

time

curr

ent

1s 3skA31.5

kA20

Rat

ed s

hort-

circ

uit b

reak

ing

curr

ent

Per

cent

age

valu

e of

the

DC

com

pone

nt

kA31.5

%

WIA

WIA

WIA

WIA

8/12-2/621

8/12-2/621 600

8/12-2/621

8/12-2/621

WIB

WIB

WIB

WIB

8/12-2/627

8/12-2/627

8/12-2/627

8/12-2/627

600

12 75 28 85/32

12 75 28 85/32

0.8

0.8 50/60

1.3

1.3

1250

1600

80

80

2000

2500 1)

80

80

0.8

0.8

0.8

1.3

50/60

630

1250

80

80

1600

2000

80

80

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5 38

31.5

31.5

31.5

31.5

20

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

38

WIB

WIA

WIA

WIA

8/12-2/627

10/12-2/621

60010/12-2/621

10/12-2/621

WIA

WIB

WIB

WIB

10/12-2/621

10/12-2/627

60010/12-2/627

10/12-2/627

12 75 28 85/32

12 75 28 85/32

WIB 10/12-2/627

1.3

0.8

50/600.8

1.3

2500 2)

1250

80

100

1600

2000

100

100

1.3

0.8

50/600.8

1.3

2500 1)

1250

100

100

1600

2000

100

100

31.5

40

31.5

40

40

40

40

40

31.5

40

3840

40

40

40

40

40

40

40

40

40

40

40

3840

40

1.3 2500 2) 100 40 40 40

Rated operatingsequence

O -

3 m

in -

CO

- 3

min

- C

O

O -

0.3

s - C

O -

3 m

in -

CO

CO

- 15

s -

CO

O -

0.3

s - C

O -

15 s

- C

O

Cab

le b

reak

ing

curr

ent

A

Sm

all i

ndire

ct c

urre

nts

Rat

ed b

reak

ing

curr

ent

unde

r out

-of-p

hase

con

ditio

ns

A kA8

Number of operatingcycles without

overhaulmecha-nical

electrical

Operating timeswith release

25 W

LS,TS,E w

ith ra

ted

(nor

mal

) cur

rent

10000

with

rate

d sh

ort-c

ircui

tbr

eaki

ng c

urre

nt

Ope

ning

tim

e4)

ms

160 W 160 W

Command timeswith release

25 W

Ope

ning

tim

e4)

Clo

sing

tim

e4)

ms ms

Arc

dur

atio

n (m

ax.)

Off

ms ms

160 W 160 W

Off

On

On

Offms ms

Cha

rgin

g tim

e fo

r mot

or d

rive

mec

hani

smO

pera

ting

time

for d

isco

nnec

tor

and

earth

ing

switc

h w

ith m

otor

driv

em

echa

nism

, 160

W

s s

25 10

8

25

8

8

10 –

1000

1000 10000 100 45-65

10000

1000

1000 10000 100 45-65

33-50 40-70 12 50

33-50 40-70 12 50

20 20 ≤ 12 ≤ 18

20 20 ≤ 12 ≤ 18

25 10

10

10

10

25 10

10

10

10

10

10

10000

100001000

1000100 45-65

10000

100001000

1000100 45-65

33-50 40-70 12 50

33-50 40-70 12 50

20 20 ≤ 12 ≤ 18

20 20 ≤ 12 ≤ 18

Selection tables

WIA/WIB 12 kV

LS = Circuit-breakerTS = Three-position switch, disconnector I/OES = Three-position switch, earthing switch I/O

1) with cooling gas tank, panel height 2750 mm2) with motor-actuated fan3) possiblelimitsandcomponentsfitted,refertoprojectplanningdocumentsWIno.495424) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report5) minimumservicepressure0.3baratafillingpressureof0.8bar;0.7baratafillingpressureof1.3bar

Page 23: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

23WI EN

WI Selection tables (contd.)

Type

WIA

Pan

el w

idth

8/12-2/621mm

Rated insulation level

Rat

ed v

olta

ge

Rat

ed li

ghtn

ing

impu

lse

with

stan

d vo

ltage

kV kV

Rat

ed p

ower

freq

uenc

yw

ithst

and

volta

ge

Rat

ings

of i

sola

ting

dist

ance

kV kV/kV

Des

ign

pres

sure

P r a

t 20

0 C

5)

Rat

ed fr

eque

ncy

bar0.8

Hz

Rat

ed (n

orm

al) c

urre

nt3)

Rat

ed p

eak

with

stan

d cu

rren

teq

ual t

o ra

ted

shor

t-circ

uit

mak

ing

curr

ent

A630

kA80

Rat

ed s

hort-

time

curr

ent

1s 3skA31.5

kA20

Rat

ed s

hort-

circ

uit b

reak

ing

curr

ent

Per

cent

age

valu

e of

the

DC

com

pone

nt

kA31.5

%

WIA

WIA

WIA

WIA

8/12-2/621

8/12-2/621 600

8/12-2/621

8/12-2/621

WIB

WIB

WIB

WIB

8/12-2/627

8/12-2/627

8/12-2/627

8/12-2/627

600

12 75 28 85/32

12 75 28 85/32

0.8

0.8 50/60

1.3

1.3

1250

1600

80

80

2000

2500 1)

80

80

0.8

0.8

0.8

1.3

50/60

630

1250

80

80

1600

2000

80

80

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5 38

31.5

31.5

31.5

31.5

20

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

38

WIB

WIA

WIA

WIA

8/12-2/627

10/12-2/621

60010/12-2/621

10/12-2/621

WIA

WIB

WIB

WIB

10/12-2/621

10/12-2/627

60010/12-2/627

10/12-2/627

12 75 28 85/32

12 75 28 85/32

WIB 10/12-2/627

1.3

0.8

50/600.8

1.3

2500 2)

1250

80

100

1600

2000

100

100

1.3

0.8

50/600.8

1.3

2500 1)

1250

100

100

1600

2000

100

100

31.5

40

31.5

40

40

40

40

40

31.5

40

3840

40

40

40

40

40

40

40

40

40

40

40

3840

40

1.3 2500 2) 100 40 40 40

Rated operatingsequence

O -

3 m

in -

CO

- 3

min

- C

O

O -

0.3

s - C

O -

3 m

in -

CO

CO

- 15

s -

CO

O -

0.3

s - C

O -

15 s

- C

O

Cab

le b

reak

ing

curr

ent

A

Sm

all i

ndire

ct c

urre

nts

Rat

ed b

reak

ing

curr

ent

unde

r out

-of-p

hase

con

ditio

ns

A kA8

Number of operatingcycles without

overhaulmecha-nical

electrical

Operating timeswith release

25 W

LS,TS,E w

ith ra

ted

(nor

mal

) cur

rent

10000

with

rate

d sh

ort-c

ircui

tbr

eaki

ng c

urre

nt

Ope

ning

tim

e4)

ms

160 W 160 W

Command timeswith release

25 W

Ope

ning

tim

e4)

Clo

sing

tim

e4)

ms ms

Arc

dur

atio

n (m

ax.)

Off

ms ms

160 W 160 W

Off

On

On

Offms ms

Cha

rgin

g tim

e fo

r mot

or d

rive

mec

hani

smO

pera

ting

time

for d

isco

nnec

tor

and

earth

ing

switc

h w

ith m

otor

driv

em

echa

nism

, 160

W

s s

25 10

8

25

8

8

10 –

1000

1000 10000 100 45-65

10000

1000

1000 10000 100 45-65

33-50 40-70 12 50

33-50 40-70 12 50

20 20 ≤ 12 ≤ 18

20 20 ≤ 12 ≤ 18

25 10

10

10

10

25 10

10

10

10

10

10

10000

100001000

1000100 45-65

10000

100001000

1000100 45-65

33-50 40-70 12 50

33-50 40-70 12 50

20 20 ≤ 12 ≤ 18

20 20 ≤ 12 ≤ 18

Page 24: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

24 WI EN

WI

Type

WIA

Pan

el w

idth

8/17-2/621mm

Rated insulation level

Rat

ed v

olta

ge

Rat

ed li

ghtn

ing

impu

lse

with

stan

d vo

ltage

kV kV

Rat

ed p

ower

freq

uenc

y w

ithst

and

volta

ge

Rat

ings

of i

sola

ting

dist

ance

kV kV/kV

Des

ign

pres

sure

P r a

t 20

0C

5)

Rat

ed fr

eque

ncy

bar0.8

Hz

Rat

ed (n

orm

al) c

urre

nt 3)

Rat

ed p

eak

with

stan

d cu

rrent

equa

l to

rate

d sh

ort-c

ircui

t m

akin

g cu

rrent

A630

kA80

Rat

ed s

hort-

time

curre

nt

1s 3skA31.5

kA20

Rat

ed s

hort-

circ

uit b

reak

ing

curr

ent

Per

cent

age

valu

e of

the

DC

co

mpo

nent

kA31.5

%

WIA

WIA

WIA

WIA

8/17-2/621

8/17-2/621 600

8/17-2/621

8/17-2/621

WIB

WIB

WIB

WIB

8/17-2/627

8/17-2/627

8/17-2/627

8/17-2/627

600

17.5 95 38 110/45

17.5 95 38 110/45

0.8

0.8 50/60

1.3

1.3

1250

1600

80

80

2000

2500 1)

80

80

0.8

0.8

0.8

1.3

50/60

630

1250

80

80

1600

2000

80

80

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5 38

31.5

31.5

31.5

31.5

20

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

38

WIB

WIA

WIA

WIA

8/17-2/627

10/17-2/621

60010/17-2/621

10/17-2/621

WIA

WIB

WIB

WIB

10/17-2/621

10/17-2/627

60010/17-2/627

10/17-2/627

17.5 95 38 110/45

17.5 95 38 110/45

WIB 10/17-2/627

1.3

0.8

50/600.8

1.3

2500 2)

1250

80

100

1600

2000

100

100

1.3

0.8

50/600.8

1.3

2500 1)

1250

100

100

1600

2000

100

100

31.5

40

31.5

40

40

40

40

40

31.5

40

3840

40

40

40

40

40

40

40

40

40

40

40

3840

40

1.3 2500 2) 100 40 40 40

Rated operating sequence

O -

3 m

in -

CO

- 3

min

- C

O

O -

0.3

s - C

O -

3 m

in -

CO

CO

- 15

s -

CO

O -

0.3

s - C

O -

15 s

- C

O

Cab

le b

reak

ing

curr

ent

A

Sm

all i

ndire

ct c

urre

nts

Rat

ed b

reak

ing

curr

ent

unde

r out

-of-p

hase

con

ditio

ns

A kA8

Number of operatingcycles without

overhaul

mech. electrical

Operating times

with release25 W

LS,TS,E w

ith ra

ted

(nor

mal

) cur

rent

10000

with

rate

d sh

ort-c

ircui

t

brea

king

cur

rent

Ope

ning

tim

e 4)

ms

160 W 160 W

Command times

with release25 W

Ope

ning

tim

e 4)

Clo

sing

tim

e 4)

ms ms

Arc

dur

atio

n (m

ax.)

Off

ms ms

160 W 160 W

Off

On

On

Offms ms

Cha

rgin

g tim

e fo

r mot

or d

rive

mec

hani

smO

pera

ting

time

for d

isco

nnec

tor

and

earth

ing

switc

h w

ith m

otor

-dr

ive

mec

hani

sm, 1

60 W

s s

25 10

8

8

8

8

25

8

8

10 8

8

1000

1000 10000 100 45-65

10000

1000

1000 10000 100 45-65

33-50 40-70 14 50

33-50 40-70 14 50

20 20 ≤ 12 ≤ 18

20 20 ≤ 12 ≤ 18

25 10

8

10

10

10

25 10

10

10

10

10

10

10000

100001000

1000100 45-65

10000

100001000

1000100 45-65

33-50 40-70 14 50

33-50 40-70 14 50

20 20 ≤ 12 ≤ 18

20 20 ≤ 12 ≤ 18

Selection tables (contd.)

WIA/WIB 17 kV

LS = Circuit-breakerTS = Three-position switch, disconnector I/OES = Three-position switch, earthing switch I/O

1) with cooling gas tank, panel height 2750 mm2) with motor-actuated fan3) possiblelimitsandcomponentsfitted,refertoprojectplanningdocumentsWIno.495424) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report5) minimumservicepressure0.3baratafillingpressureof0.8bar;0.7baratafillingpressureof1.3bar

Page 25: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

25WI EN

WI Selection tables (contd.)

Type

WIA

Pan

el w

idth

8/17-2/621mm

Rated insulation level

Rat

ed v

olta

ge

Rat

ed li

ghtn

ing

impu

lse

with

stan

d vo

ltage

kV kV

Rat

ed p

ower

freq

uenc

y w

ithst

and

volta

ge

Rat

ings

of i

sola

ting

dist

ance

kV kV/kV

Des

ign

pres

sure

P r a

t 20

0C

5)

Rat

ed fr

eque

ncy

bar0.8

Hz

Rat

ed (n

orm

al) c

urre

nt 3)

Rat

ed p

eak

with

stan

d cu

rrent

equa

l to

rate

d sh

ort-c

ircui

t m

akin

g cu

rrent

A630

kA80

Rat

ed s

hort-

time

curre

nt

1s 3skA31.5

kA20

Rat

ed s

hort-

circ

uit b

reak

ing

curr

ent

Per

cent

age

valu

e of

the

DC

co

mpo

nent

kA31.5

%

WIA

WIA

WIA

WIA

8/17-2/621

8/17-2/621 600

8/17-2/621

8/17-2/621

WIB

WIB

WIB

WIB

8/17-2/627

8/17-2/627

8/17-2/627

8/17-2/627

600

17.5 95 38 110/45

17.5 95 38 110/45

0.8

0.8 50/60

1.3

1.3

1250

1600

80

80

2000

2500 1)

80

80

0.8

0.8

0.8

1.3

50/60

630

1250

80

80

1600

2000

80

80

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5 38

31.5

31.5

31.5

31.5

20

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

38

WIB

WIA

WIA

WIA

8/17-2/627

10/17-2/621

60010/17-2/621

10/17-2/621

WIA

WIB

WIB

WIB

10/17-2/621

10/17-2/627

60010/17-2/627

10/17-2/627

17.5 95 38 110/45

17.5 95 38 110/45

WIB 10/17-2/627

1.3

0.8

50/600.8

1.3

2500 2)

1250

80

100

1600

2000

100

100

1.3

0.8

50/600.8

1.3

2500 1)

1250

100

100

1600

2000

100

100

31.5

40

31.5

40

40

40

40

40

31.5

40

3840

40

40

40

40

40

40

40

40

40

40

40

3840

40

1.3 2500 2) 100 40 40 40

Rated operating sequence

O -

3 m

in -

CO

- 3

min

- C

O

O -

0.3

s - C

O -

3 m

in -

CO

CO

- 15

s -

CO

O -

0.3

s - C

O -

15 s

- C

O

Cab

le b

reak

ing

curr

ent

A

Sm

all i

ndire

ct c

urre

nts

Rat

ed b

reak

ing

curr

ent

unde

r out

-of-p

hase

con

ditio

ns

A kA8

Number of operatingcycles without

overhaul

mech. electrical

Operating times

with release25 W

LS,TS,E w

ith ra

ted

(nor

mal

) cur

rent

10000

with

rate

d sh

ort-c

ircui

t

brea

king

cur

rent

Ope

ning

tim

e 4)

ms

160 W 160 W

Command times

with release25 W

Ope

ning

tim

e 4)

Clo

sing

tim

e 4)

ms ms

Arc

dur

atio

n (m

ax.)

Off

ms ms

160 W 160 W

Off

On

On

Offms ms

Cha

rgin

g tim

e fo

r mot

or d

rive

mec

hani

smO

pera

ting

time

for d

isco

nnec

tor

and

earth

ing

switc

h w

ith m

otor

-dr

ive

mec

hani

sm, 1

60 W

s s

25 10

8

8

8

8

25

8

8

10 8

8

1000

1000 10000 100 45-65

10000

1000

1000 10000 100 45-65

33-50 40-70 14 50

33-50 40-70 14 50

20 20 ≤ 12 ≤ 18

20 20 ≤ 12 ≤ 18

25 10

8

10

10

10

25 10

10

10

10

10

10

10000

100001000

1000100 45-65

10000

100001000

1000100 45-65

33-50 40-70 14 50

33-50 40-70 14 50

20 20 ≤ 12 ≤ 18

20 20 ≤ 12 ≤ 18

Page 26: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

26 WI EN

WI

Type

WIA

Pan

el w

idth

8/24-2/621mm

Rated insulation levelR

ated

vol

tage

Rat

ed li

ghtn

ing

impu

lse

with

stan

d vo

ltage

kV kV

Rat

ed p

ower

freq

uenc

y w

ithst

and

volta

ge

Rat

ings

of i

sola

ting

dist

ance

kV kV/kV

Des

ign

pres

sure

P r a

t 20

0 C 5)

Rat

ed fr

eque

ncy

bar0.8

Hz

Rat

ed (n

orm

al) c

urre

nt 3)

Rat

ed p

eak

with

stan

d cu

rrent

equa

l to

rate

d sh

ort-c

ircui

t m

akin

g cu

rrent

A630

kA80

Rat

ed s

hort-

time

curre

nt

1s 3skA31.5

kA20

Rat

ed s

hort-

circ

uit b

reak

ing

curr

ent

Per

cent

age

valu

e of

the

DC

co

mpo

nent

kA31.5

%

WIA

WIA

WIA

WIA

8/24-2/621

8/24-2/621 600

8/24-2/621

8/24-2/621

WIB

WIB

WIB

WIB

8/24-2/627

8/24-2/627

8/24-2/627

8/24-2/627

600

24 125 50 145/60

24 125 50 145/60

0.8

0.8 50/60

1.3

1.3

1250

1600

80

80

2000

2500 1)

80

80

0.8

0.8

0.8

1.3

50/60

630

1250

80

80

1600

2000

80

80

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5 38

31.5

31.5

31.5

31.5

20

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

38

WIB

WIA

WIA

WIA

8/24-2/627

10/24-2/621

60010/24-2/621

10/24-2/621

WIA

WIB

WIB

WIB

10/24-2/621

10/24-2/627

60010/24-2/627

10/24-2/627

24 125 50 145/60

24 125 50 145/60

WIB 10/24-2/627

1.3

0.8

50/600.8

1.3

2500 2)

1250

80

100

1600

2000

100

100

1.3

0.8

50/600.8

1.3

2500 1)

1250

100

100

1600

2000

100

100

31.5

40

31.5

40

40

40

40

40

31.5

40

3840

40

40

40

40

40

40

40

40

40

40

40

3840

40

1.3 2500 2) 100 40 40 40

Rated operating sequence

O -

3 m

in -

CO

- 3

min

- C

O

O -

0.3

s - C

O -

3 m

in -

CO

CO

- 15

s -

CO

O -

0.3

s - C

O -

15 s

- C

O

Cab

le b

reak

ing

curre

nt

A

Sm

all i

ndire

ct c

urre

nts

Rat

ed b

reak

ing

curre

ntun

der o

ut-o

f-pha

se c

ondi

tions

A kA8

Number of operatingcycles without

overhaul

mech. electrical

Operating times

with release25 W

LS,TS,E w

ith ra

ted

(nor

mal

) cur

rent

10000

with

rate

d sh

ort-c

ircui

t

brea

king

cur

rent

Ope

ning

tim

e 4)

ms

160 W 160 W

Command times

with release25 W

Ope

ning

tim

e 4)

Clo

sing

tim

e 4)

ms ms

Arc

dur

atio

n (m

ax.)

Off

ms ms

160 W 160 W

Off

On

On

Offms ms

Cha

rgin

g tim

e fo

r mot

or d

rive

mec

hani

sm

Ope

ratin

g tim

e fo

r dis

conn

ecto

ran

d ea

rthin

g sw

itch

with

mot

or-

driv

e m

echa

nism

, 160

W

s s

31.5 10

8

8

8

8

31.5

8

8

10 8

8

1000

1000 10000 100 45-65

10000

1000

1000 10000 100 45-65

33-50 40-70 14 50

33-50 40-70 14 50

20 20 ≤ 12 ≤ 18

20 20 ≤ 12 ≤ 18

31.5 10

8

31.5 10

-

10000

100001000

1000100 45-65

10000

100001000

1000100 45-65

33-50 40-70 14 50

33-50 40-70 14 50

20 20 ≤ 12 ≤ 18

20 20 ≤ 12 ≤ 18

Selection tables (contd.)

WIA/WIB 24 kV

LS = Circuit-breakerTS = Three-position switch, disconnector I/OES = Three-position switch, earthing switch I/O

1) with cooling gas tank, panel height 2750 mm2) with motor-actuated fan3) possiblelimitsandcomponentsfitted,refertoprojectplanningdocumentsWIno.495424) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report5) minimumservicepressure0.3baratafillingpressureof0.8bar;0.7baratafillingpressureof1.3bar

Page 27: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

27WI EN

WI Selection tables (contd.)

Type

WIA

Pan

el w

idth

8/24-2/621mm

Rated insulation level

Rat

ed v

olta

ge

Rat

ed li

ghtn

ing

impu

lse

with

stan

d vo

ltage

kV kV

Rat

ed p

ower

freq

uenc

y w

ithst

and

volta

ge

Rat

ings

of i

sola

ting

dist

ance

kV kV/kV

Des

ign

pres

sure

P r a

t 20

0 C 5)

Rat

ed fr

eque

ncy

bar0.8

Hz

Rat

ed (n

orm

al) c

urre

nt 3)

Rat

ed p

eak

with

stan

d cu

rrent

equa

l to

rate

d sh

ort-c

ircui

t m

akin

g cu

rrent

A630

kA80

Rat

ed s

hort-

time

curre

nt

1s 3skA31.5

kA20

Rat

ed s

hort-

circ

uit b

reak

ing

curr

ent

Per

cent

age

valu

e of

the

DC

co

mpo

nent

kA31.5

%

WIA

WIA

WIA

WIA

8/24-2/621

8/24-2/621 600

8/24-2/621

8/24-2/621

WIB

WIB

WIB

WIB

8/24-2/627

8/24-2/627

8/24-2/627

8/24-2/627

600

24 125 50 145/60

24 125 50 145/60

0.8

0.8 50/60

1.3

1.3

1250

1600

80

80

2000

2500 1)

80

80

0.8

0.8

0.8

1.3

50/60

630

1250

80

80

1600

2000

80

80

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5 38

31.5

31.5

31.5

31.5

20

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

38

WIB

WIA

WIA

WIA

8/24-2/627

10/24-2/621

60010/24-2/621

10/24-2/621

WIA

WIB

WIB

WIB

10/24-2/621

10/24-2/627

60010/24-2/627

10/24-2/627

24 125 50 145/60

24 125 50 145/60

WIB 10/24-2/627

1.3

0.8

50/600.8

1.3

2500 2)

1250

80

100

1600

2000

100

100

1.3

0.8

50/600.8

1.3

2500 1)

1250

100

100

1600

2000

100

100

31.5

40

31.5

40

40

40

40

40

31.5

40

3840

40

40

40

40

40

40

40

40

40

40

40

3840

40

1.3 2500 2) 100 40 40 40

Rated operating sequence

O -

3 m

in -

CO

- 3

min

- C

O

O -

0.3

s - C

O -

3 m

in -

CO

CO

- 15

s -

CO

O -

0.3

s - C

O -

15 s

- C

O

Cab

le b

reak

ing

curre

nt

A

Sm

all i

ndire

ct c

urre

nts

Rat

ed b

reak

ing

curre

ntun

der o

ut-o

f-pha

se c

ondi

tions

A kA8

Number of operatingcycles without

overhaul

mech. electrical

Operating times

with release25 W

LS,TS,E w

ith ra

ted

(nor

mal

) cur

rent

10000

with

rate

d sh

ort-c

ircui

t

brea

king

cur

rent

Ope

ning

tim

e 4)

ms

160 W 160 W

Command times

with release25 W

Ope

ning

tim

e 4)

Clo

sing

tim

e 4)

ms ms

Arc

dur

atio

n (m

ax.)

Off

ms ms

160 W 160 W

Off

On

On

Offms ms

Cha

rgin

g tim

e fo

r mot

or d

rive

mec

hani

sm

Ope

ratin

g tim

e fo

r dis

conn

ecto

ran

d ea

rthin

g sw

itch

with

mot

or-

driv

e m

echa

nism

, 160

W

s s

31.5 10

8

8

8

8

31.5

8

8

10 8

8

1000

1000 10000 100 45-65

10000

1000

1000 10000 100 45-65

33-50 40-70 14 50

33-50 40-70 14 50

20 20 ≤ 12 ≤ 18

20 20 ≤ 12 ≤ 18

31.5 10

8

31.5 10

-

10000

100001000

1000100 45-65

10000

100001000

1000100 45-65

33-50 40-70 14 50

33-50 40-70 14 50

20 20 ≤ 12 ≤ 18

20 20 ≤ 12 ≤ 18

Page 28: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

28 WI EN

WI

Rated operating sequence

O -

3 m

in -

CO

- 3

min

- C

O

O -

0.3

s - C

O -

3 m

in -

CO

CO

- 15

s -

CO

O -

0.3

s - C

O -

15 s

- C

O

Cab

le b

reak

ing

curre

nt

A

Sm

all i

ndire

ct c

urre

nts

Rat

ed b

reak

ing

curre

ntun

der o

ut-o

f-pha

se c

ondi

tions

A kA6.3

Number of operatingcycles without

overhaul

mech. electrical

Operating times

with release25 W

LS,TS,E w

ith ra

ted

(nor

mal

) cur

rent

10000

with

rate

d sh

ort-c

ircui

t

brea

king

cur

rent

Ope

ning

tim

e 4)

ms

160 W 160 W

Command times

with release25 W

Ope

ning

tim

e 4)

Clo

sing

tim

e 4)

ms ms

Arc

dur

atio

n (m

ax.)

Off

ms ms

160 W 160 W

Off

On

On

Offms ms

Cha

rgin

g tim

e fo

r mot

or d

rive

mec

hani

smO

pera

ting

time

for d

isco

nnec

tor

and

earth

ing

switc

h w

ith m

otor

-dr

ive

mec

hani

sm, 1

60 W

s s

50 10

6.3

6.3

6.3

6.3

50

6.3

6.3

10 6.3

6.3

1000

1000 10000 100 43-65

10000

1000

1000 10000 100 43-65

29-50 40-65 14 50

29-50 40-65 14 50

20 20 ≤ 12 ≤ 18

20 20 ≤ 12 ≤ 18

50 10

6.3

6.3

6.3

6.3

50 10

6.3

6.3

6.3

6.3

6.3

10000

100001000

1000100 43-65

10000

100001000

1000100 43-65

– 40-65 14 50

– 40-65 14 50

– ≤ 1220

20

≤ 18

– ≤ 12 ≤ 18

Type

WIA

Pan

el w

idth

6/36-2/621mm

Rated insulation level

Rat

ed v

olta

ge

Rat

ed li

ghtn

ing

impu

lse

with

stan

d vo

ltage

kV kV

Rat

ed p

ower

freq

uenc

y w

ithst

and

volta

ge

Rat

ings

of i

sola

ting

dist

ance

kV kV/kV

Des

ign

pres

sure

P r a

t 20

0 C 5)

Rat

ed fr

eque

ncy

bar1.3

Hz

Rat

ed (n

orm

al) c

urre

nt 3)

Rat

ed p

eak

with

stan

d cu

rrent

equa

l to

rate

d sh

ort-c

ircui

t m

akin

g cu

rrent

A630

kA63

Rat

ed s

hort-

time

curre

nt

1s 3skA25

kA20

Rat

ed s

hort-

circ

uit b

reak

ing

curr

ent

Per

cent

age

valu

e of

the

DC

co

mpo

nent

kA25

%42

WIA

WIA

WIA

WIA

6/36-2/621

6/36-2/621 600

6/36-2/621

6/36-2/621

WIB

WIB

WIB

WIB

6/36-2/627

6/36-2/627

6/36-2/627

6/36-2/627

600

36 170 70 195/80

36 170 70 195/80

1.3

1.3 50

1.3

1.3

1250

1600

63

63

2000

2500 1)

63

63

1.3

1.3

1.3

1.3

50

630

1250

63

63

1600

2000

63

63

25

25

25

25

25

25

25

25

25

25

42

42

25

25

42

42

25

25

20

25

25

25

25

25

25

25

42

42

25

25

42

42

WIB

WIA

WIA

WIA

6/36-2/627

10/36-2/621

60010/36-2/621

10/36-2/621

WIA

WIB

WIB

WIB

10/36-2/621

10/36-2/627

60010/36-2/627

10/36-2/627

36 170 70 195/80

36 170 70 195/80

WIB 10/36-2/627

1.3

1.3

50/601.3

1.3

2500 2)

1250

63

100

1600

2000

100

100

1.3

1.3

50/601.3

1.3

2500 1)

1250

100

100

1600

2000

100

100

25

40

25

40

40

40

40

40

25

40

42

31

40

40

31

31

40

40

40

40

40

40

40

40

40

40

31

31

40

40

31

31

1.3 2500 2) 100 40 40 40 31

Selection tables (contd.)

WIA/WIB 36 kV

LS = Circuit-breakerTS = Three-position switch, disconnector I/OES = Three-position switch, earthing switch I/O

1) with cooling gas tank, panel height 2750 mm2) with motor-actuated fan3) possiblelimitsandcomponentsfitted,refertoprojectplanningdocumentsWIno.495424) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report5) minimum service pressure 0.7 bar

Page 29: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

29WI EN

WI Selection tables (contd.)

Rated operating sequence

O -

3 m

in -

CO

- 3

min

- C

O

O -

0.3

s - C

O -

3 m

in -

CO

CO

- 15

s -

CO

O -

0.3

s - C

O -

15 s

- C

O

Cab

le b

reak

ing

curre

nt

A

Sm

all i

ndire

ct c

urre

nts

Rat

ed b

reak

ing

curre

ntun

der o

ut-o

f-pha

se c

ondi

tions

A kA6.3

Number of operatingcycles without

overhaul

mech. electrical

Operating times

with release25 W

LS,TS,E w

ith ra

ted

(nor

mal

) cur

rent

10000

with

rate

d sh

ort-c

ircui

t

brea

king

cur

rent

Ope

ning

tim

e 4)

ms

160 W 160 W

Command times

with release25 W

Ope

ning

tim

e 4)

Clo

sing

tim

e 4)

ms ms

Arc

dur

atio

n (m

ax.)

Off

ms ms

160 W 160 W

Off

On

On

Offms ms

Cha

rgin

g tim

e fo

r mot

or d

rive

mec

hani

smO

pera

ting

time

for d

isco

nnec

tor

and

earth

ing

switc

h w

ith m

otor

-dr

ive

mec

hani

sm, 1

60 W

s s

50 10

6.3

6.3

6.3

6.3

50

6.3

6.3

10 6.3

6.3

1000

1000 10000 100 43-65

10000

1000

1000 10000 100 43-65

29-50 40-65 14 50

29-50 40-65 14 50

20 20 ≤ 12 ≤ 18

20 20 ≤ 12 ≤ 18

50 10

6.3

6.3

6.3

6.3

50 10

6.3

6.3

6.3

6.3

6.3

10000

100001000

1000100 43-65

10000

100001000

1000100 43-65

– 40-65 14 50

– 40-65 14 50

– ≤ 1220

20

≤ 18

– ≤ 12 ≤ 18

Type

WIA

Pan

el w

idth

6/36-2/621mm

Rated insulation level

Rat

ed v

olta

ge

Rat

ed li

ghtn

ing

impu

lse

with

stan

d vo

ltage

kV kV

Rat

ed p

ower

freq

uenc

y w

ithst

and

volta

ge

Rat

ings

of i

sola

ting

dist

ance

kV kV/kV

Des

ign

pres

sure

P r a

t 20

0 C 5)

Rat

ed fr

eque

ncy

bar1.3

Hz

Rat

ed (n

orm

al) c

urre

nt 3)

Rat

ed p

eak

with

stan

d cu

rrent

equa

l to

rate

d sh

ort-c

ircui

t m

akin

g cu

rrent

A630

kA63

Rat

ed s

hort-

time

curre

nt

1s 3skA25

kA20

Rat

ed s

hort-

circ

uit b

reak

ing

curr

ent

Per

cent

age

valu

e of

the

DC

co

mpo

nent

kA25

%42

WIA

WIA

WIA

WIA

6/36-2/621

6/36-2/621 600

6/36-2/621

6/36-2/621

WIB

WIB

WIB

WIB

6/36-2/627

6/36-2/627

6/36-2/627

6/36-2/627

600

36 170 70 195/80

36 170 70 195/80

1.3

1.3 50

1.3

1.3

1250

1600

63

63

2000

2500 1)

63

63

1.3

1.3

1.3

1.3

50

630

1250

63

63

1600

2000

63

63

25

25

25

25

25

25

25

25

25

25

42

42

25

25

42

42

25

25

20

25

25

25

25

25

25

25

42

42

25

25

42

42

WIB

WIA

WIA

WIA

6/36-2/627

10/36-2/621

60010/36-2/621

10/36-2/621

WIA

WIB

WIB

WIB

10/36-2/621

10/36-2/627

60010/36-2/627

10/36-2/627

36 170 70 195/80

36 170 70 195/80

WIB 10/36-2/627

1.3

1.3

50/601.3

1.3

2500 2)

1250

63

100

1600

2000

100

100

1.3

1.3

50/601.3

1.3

2500 1)

1250

100

100

1600

2000

100

100

25

40

25

40

40

40

40

40

25

40

42

31

40

40

31

31

40

40

40

40

40

40

40

40

40

40

31

31

40

40

31

31

1.3 2500 2) 100 40 40 40 31

Page 30: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

30 WI EN

WI

Type

WIA

Pan

el w

idth

8/38-2/621mm

Rated insulation levelR

ated

vol

tage

Rat

ed li

ghtn

ing

impu

lse

with

stan

d vo

ltage

kV kV

Rat

ed p

ower

freq

uenc

y w

ithst

and

volta

ge

Rat

ings

of i

sola

ting

dist

ance

kV kV/kV

Des

ign

pres

sure

P r a

t 20

0C

5)

Rat

ed fr

eque

ncy

bar1.45

Hz

Rat

ed (n

orm

al) c

urre

nt 3)

Rat

ed p

eak

with

stan

d cu

rrent

equa

l to

rate

d sh

ort-c

ircui

t m

akin

g cu

rrent

A630

kA80

Rat

ed s

hort-

time

curre

nt

1s 3skA31.5

kA20

Rat

ed s

hort-

circ

uit b

reak

ing

curr

ent

Per

cent

age

valu

e of

the

DC

co

mpo

nent

kA31.5

%31

WIA

WIA

WIA

WIA

8/38-2/621

8/38-2/621 600

8/38-2/621

8/38-2/621

WIB

WIB

WIB

WIB

8/38-2/627

8/38-2/627

8/38-2/627

8/38-2/627

600

38 200 80 220/90

38 200 80 220/90

1.45

1.45 50/60

1.45

1.45

1250

1600

80

80

2000

2500 1)

80

80

1.45

1.45

1.45

1.45

50/60

630

1250

80

80

1600

2000

80

80

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31

31

31.5

31.5

31

31

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31

31

31.5

31.5

31

31

WIB

WIA

WIA

WIA

8/38-2/627

8/40.5-2/621

6008/40.5-2/621

8/40.5-2/621

WIA

WIB

WIB

WIB

8/40.5-2/621

8/40.5-2/627

6008/40.5-2/627

8/40.5-2/627

40.5 185(200) 85 215/90

(220/90)

40.5 185(200) 85 215/90

(220/90)

WIB 8/40.5-2/627

1.45

1.45

501.45

1.45

2500 2)

1250

80

80

1600

2000

80

80

1.45

1.45

501.45

1.45

2500 1)

1250

80

80

1600

2000

80

80

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31

31

31.5

31.5

31

31

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31

31

31.5

31.5

31

31

1.45 2500 2) 80 31.5 31.5 31.5 31

Rated operating sequence

O -

3 m

in -

CO

- 3

min

- C

O

O -

0.3

s - C

O -

3 m

in -

CO

CO

- 15

s -

CO

O -

0.3

s - C

O -

15 s

- C

O

Cab

le b

reak

ing

curre

nt

A

Sm

all i

ndire

ct c

urre

nts

Rat

ed b

reak

ing

curre

ntun

der o

ut-o

f-pha

se c

ondi

tions

A kA–

Number of operatingcycles without

overhaul

mech. electrical

Operating times

with release25 W

LS,TS,E w

ith ra

ted

(nor

mal

) cur

rent

10000

with

rate

d sh

ort-c

ircui

t

brea

king

cur

rent

Ope

ning

tim

e 4)

ms

160 W160 W

Command times

with release25 W

Ope

ning

tim

e 4)

Clo

sing

tim

e 4)

ms ms

Arc

dur

atio

n (m

ax.)

Off

ms ms

160 W160 W

Off

On

On

Offms ms

Cha

rgin

g tim

e fo

r mot

or d

rive

mec

hani

smO

pera

ting

time

for d

isco

nnec

tor

and

earth

ing

switc

h w

ith m

otor

-dr

ive

mec

hani

sm, 1

60 W

s s

50 10

50

10 –

1000

1000 10000 100 43-65

10000

1000

1000 10000 100 43-65

– 40-65 14 50

– 40-65 14 50

– 20 ≤ 12 ≤ 18

– 20 ≤ 12 ≤ 18

50 10

50 10

10000

100001000

1000100 43-65

10000

100001000

1000100 43-65

– 40-65 14 50

– 40-65 14 50

– 20 ≤ 12 ≤ 18

– 20 ≤ 12 ≤ 18

Selection tables (contd.)

WIA/WIB 38 kV

LS = Circuit-breakerTS = Three-position switch, disconnector I/OES = Three-position switch, earthing switch I/O

1) with cooling gas tank, panel height 2750 mm2) with motor-actuated fan3) forpossiblelimitvaluesandcomponentsfitted,refertotheprojectplanningdocumentsWIno.495424) adm. tolerance range, is not a manufacturing tolerance, for the current value of a specimen, refer to the routine test report5) minimumservicepressureat20°C=1.0bar(overpressure)

Page 31: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

31WI EN

WI Selection tables (contd.)

Type

WIA

Pan

el w

idth

8/38-2/621mm

Rated insulation level

Rat

ed v

olta

ge

Rat

ed li

ghtn

ing

impu

lse

with

stan

d vo

ltage

kV kV

Rat

ed p

ower

freq

uenc

y w

ithst

and

volta

ge

Rat

ings

of i

sola

ting

dist

ance

kV kV/kV

Des

ign

pres

sure

P r a

t 20

0C

5)

Rat

ed fr

eque

ncy

bar1.45

Hz

Rat

ed (n

orm

al) c

urre

nt 3)

Rat

ed p

eak

with

stan

d cu

rrent

equa

l to

rate

d sh

ort-c

ircui

t m

akin

g cu

rrent

A630

kA80

Rat

ed s

hort-

time

curre

nt

1s 3skA31.5

kA20

Rat

ed s

hort-

circ

uit b

reak

ing

curr

ent

Per

cent

age

valu

e of

the

DC

co

mpo

nent

kA31.5

%31

WIA

WIA

WIA

WIA

8/38-2/621

8/38-2/621 600

8/38-2/621

8/38-2/621

WIB

WIB

WIB

WIB

8/38-2/627

8/38-2/627

8/38-2/627

8/38-2/627

600

38 200 80 220/90

38 200 80 220/90

1.45

1.45 50/60

1.45

1.45

1250

1600

80

80

2000

2500 1)

80

80

1.45

1.45

1.45

1.45

50/60

630

1250

80

80

1600

2000

80

80

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31

31

31.5

31.5

31

31

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31

31

31.5

31.5

31

31

WIB

WIA

WIA

WIA

8/38-2/627

8/40.5-2/621

6008/40.5-2/621

8/40.5-2/621

WIA

WIB

WIB

WIB

8/40.5-2/621

8/40.5-2/627

6008/40.5-2/627

8/40.5-2/627

40.5 185(200) 85 215/90

(220/90)

40.5 185(200) 85 215/90

(220/90)

WIB 8/40.5-2/627

1.45

1.45

501.45

1.45

2500 2)

1250

80

80

1600

2000

80

80

1.45

1.45

501.45

1.45

2500 1)

1250

80

80

1600

2000

80

80

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31

31

31.5

31.5

31

31

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31

31

31.5

31.5

31

31

1.45 2500 2) 80 31.5 31.5 31.5 31

Rated operating sequence

O -

3 m

in -

CO

- 3

min

- C

O

O -

0.3

s - C

O -

3 m

in -

CO

CO

- 15

s -

CO

O -

0.3

s - C

O -

15 s

- C

O

Cab

le b

reak

ing

curre

nt

A

Sm

all i

ndire

ct c

urre

nts

Rat

ed b

reak

ing

curre

ntun

der o

ut-o

f-pha

se c

ondi

tions

A kA–

Number of operatingcycles without

overhaul

mech. electrical

Operating times

with release25 W

LS,TS,E w

ith ra

ted

(nor

mal

) cur

rent

10000

with

rate

d sh

ort-c

ircui

t

brea

king

cur

rent

Ope

ning

tim

e 4)

ms

160 W160 W

Command times

with release25 W

Ope

ning

tim

e 4)

Clo

sing

tim

e 4)

ms ms

Arc

dur

atio

n (m

ax.)

Off

ms ms

160 W160 W

Off

On

On

Offms ms

Cha

rgin

g tim

e fo

r mot

or d

rive

mec

hani

smO

pera

ting

time

for d

isco

nnec

tor

and

earth

ing

switc

h w

ith m

otor

-dr

ive

mec

hani

sm, 1

60 W

s s

50 10

50

10 –

1000

1000 10000 100 43-65

10000

1000

1000 10000 100 43-65

– 40-65 14 50

– 40-65 14 50

– 20 ≤ 12 ≤ 18

– 20 ≤ 12 ≤ 18

50 10

50 10

10000

100001000

1000100 43-65

10000

100001000

1000100 43-65

– 40-65 14 50

– 40-65 14 50

– 20 ≤ 12 ≤ 18

– 20 ≤ 12 ≤ 18

Page 32: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

32 WI EN

WI Selection tables (contd.)

WIA/WIB 40.5 up to 52 kV

2 vacuum interrupter chambers per conductor

LS = Circuit-breakerTS = Three-position switch, disconnector I/OES = Three-position switch, earthing switch I/O

1) with cooling gas tank, panel height 3314 mm and with motor-actuated fans2) with motor-actuated fan3) possiblelimitsandcomponentsfitted,refertoprojectplanningdocumentsWIno.495424) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report5) minimumservicepressureat20°C:0.1baratafillingpressureof1.45bar;1.8baratafillingpressureof2.2bar

Type

WIA

Pan

el w

idth

10/40.5-2/626mm

600

Rated insulation levelR

ated

vol

tage

Rat

ed li

ghtn

ing

impu

lse

with

stan

d vo

ltage

kV

40.5

kV

200

Rat

ed p

ower

freq

uenc

y w

ithst

and

volta

ge

Rat

ings

of i

sola

ting

dist

ance

kV

80

kV/kV

220/90

Des

ign

pres

sure

P r a

t 20

0 C 5)

Rat

ed fr

eque

ncy

bar1.45

Hz

50R

ated

(nor

mal

) cur

rent

3)

Rat

ed p

eak

with

stan

d cu

rren

teq

ual t

o ra

ted

shor

t-circ

uit

mak

ing

curre

nt

A1250

kA100

Rat

ed s

hort-

time

curre

nt

1s 3skA40

kA40

Rat

ed s

hort-

circ

uit b

reak

ing

curr

ent

Per

cent

age

valu

e of

the

DC

co

mpo

nent

kA40

%

26WIA

WIB

WIB

10/40.5-2/626

10/40.5-2/633

10/40.5-2/633600

WIA

WIA

8/52-2/626600

8/52-2/626

40.5 200 80220/90

52(60)

250(110) 95

290/110

1.45

1.45

1.4550

2500 1) 100

1250

2500 2)

100

100

2.250/60

2.2

1250 82

2500 1) 82

40 40

40

40

40

40

40

40

4026

31.5 31.5

31.5 31.5

31.526

31.5

WIB

WIB

8/52-2/633

8/52-2/633600 52

(60)250(110) 95

290/110 2.2

2.250/60

1250

2500 2)

82

82

31.5

31.5

31.5

31.5

31.5

31.526

Rated operating sequence

O -

3 m

in -

CO

- 3

min

- C

O

O -

0.3

s - C

O -

3 m

in -

CO

CO

- 15

s -

CO

O -

0.3

s - C

O -

15 s

- C

O

Cab

le b

reak

ing

curre

nt

A

50

Sm

all i

ndire

ct c

urre

nts

Rat

ed b

reak

ing

curre

ntun

der o

ut-o

f-pha

se c

ondi

tions

A kA

Number of operatingcycles without

overhaul

mech. electrical

Operating times

with release25 W

LS,TS,E w

ith ra

ted

(nor

mal

) cur

rent

1000010000

with

rate

d sh

ort-c

ircui

t

brea

king

cur

rent

Ope

ning

tim

e 4)

100

ms

50-80

160 W 160 W

Command times

with release25 W

Ope

ning

tim

e 4)

Clo

sing

tim

e 4)

ms

ms

40-65

Arc

dur

atio

n (m

ax.)

Off

ms

14

ms

50

160 W 160 W

Off

On

On

Offms

ms

20

Cha

rgin

g tim

e fo

r mot

or d

rive

mec

hani

smO

pera

ting

time

for d

isco

nnec

tor

and

earth

ing

switc

h w

ith m

otor

-dr

ive

mec

hani

sm, 1

60 W

s

≤ 12

s

≤ 18

50

50

1000

1000

10000

100010000 100 50-80

1000

1000010000

1000

1000

100 50-80

– 40-65 14 50

– 40-65 14 50

– 20 ≤ 12 ≤ 18

– 20 ≤ 12 ≤ 18

5010000

100010000

1000

100 50-80 – 40-65 14 ≤ 12 ≤ 18

■50 – 20

Page 33: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

33WI EN

WI Selection tables (contd.)

Type

WIA

Pan

el w

idth

10/40.5-2/626mm

600

Rated insulation level

Rat

ed v

olta

ge

Rat

ed li

ghtn

ing

impu

lse

with

stan

d vo

ltage

kV

40.5

kV

200

Rat

ed p

ower

freq

uenc

y w

ithst

and

volta

ge

Rat

ings

of i

sola

ting

dist

ance

kV

80

kV/kV

220/90

Des

ign

pres

sure

P r a

t 20

0 C 5)

Rat

ed fr

eque

ncy

bar1.45

Hz

50

Rat

ed (n

orm

al) c

urre

nt 3)

Rat

ed p

eak

with

stan

d cu

rren

teq

ual t

o ra

ted

shor

t-circ

uit

mak

ing

curre

nt

A1250

kA100

Rat

ed s

hort-

time

curre

nt

1s 3skA40

kA40

Rat

ed s

hort-

circ

uit b

reak

ing

curr

ent

Per

cent

age

valu

e of

the

DC

co

mpo

nent

kA40

%

26WIA

WIB

WIB

10/40.5-2/626

10/40.5-2/633

10/40.5-2/633600

WIA

WIA

8/52-2/626600

8/52-2/626

40.5 200 80220/90

52(60)

250(110) 95

290/110

1.45

1.45

1.4550

2500 1) 100

1250

2500 2)

100

100

2.250/60

2.2

1250 82

2500 1) 82

40 40

40

40

40

40

40

40

4026

31.5 31.5

31.5 31.5

31.526

31.5

WIB

WIB

8/52-2/633

8/52-2/633600 52

(60)250(110) 95

290/110 2.2

2.250/60

1250

2500 2)

82

82

31.5

31.5

31.5

31.5

31.5

31.526

Rated operating sequence

O -

3 m

in -

CO

- 3

min

- C

O

O -

0.3

s - C

O -

3 m

in -

CO

CO

- 15

s -

CO

O -

0.3

s - C

O -

15 s

- C

O

Cab

le b

reak

ing

curre

nt

A

50

Sm

all i

ndire

ct c

urre

nts

Rat

ed b

reak

ing

curre

ntun

der o

ut-o

f-pha

se c

ondi

tions

A kA

Number of operatingcycles without

overhaul

mech. electrical

Operating times

with release25 W

LS,TS,E w

ith ra

ted

(nor

mal

) cur

rent

1000010000

with

rate

d sh

ort-c

ircui

t

brea

king

cur

rent

Ope

ning

tim

e 4)

100

ms

50-80

160 W 160 W

Command times

with release25 W

Ope

ning

tim

e 4)

Clo

sing

tim

e 4)

ms

ms

40-65

Arc

dur

atio

n (m

ax.)

Off

ms

14

ms

50

160 W 160 W

Off

On

On

Offms

ms

20

Cha

rgin

g tim

e fo

r mot

or d

rive

mec

hani

smO

pera

ting

time

for d

isco

nnec

tor

and

earth

ing

switc

h w

ith m

otor

-dr

ive

mec

hani

sm, 1

60 W

s

≤ 12

s

≤ 18

50

50

1000

1000

10000

100010000 100 50-80

1000

1000010000

1000

1000

100 50-80

– 40-65 14 50

– 40-65 14 50

– 20 ≤ 12 ≤ 18

– 20 ≤ 12 ≤ 18

5010000

100010000

1000

100 50-80 – 40-65 14 ≤ 12 ≤ 18

■50 – 20

Page 34: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

34 WI EN

WI Selection tables (contd.)

WIA/WIB 1 and 2-POLE, for stationary railway traction power supply 50/60 Hz

with 2 vacuum interrupter chambers per conductor

LS = Circuit-breakerTS = Three-position switch, disconnector I/OES = Three-position switch, earthing switch I/OS = 1-poleT = 2-pole

3) without cooling gas tank and heat sink4) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report5) minimum service pressure at 20 °C 1.8 bar

Type

WIA

Pan

el w

idth

6/55-S/626mm

600

Rated insulation level

Rat

ed v

olta

ge U

NM

acc

. to

EN

50

124

Rat

ed v

olta

ge U

acc

. to

EN

60

694

kV

27.5

kV

52

Rat

ed li

ghtn

ing

impu

lse

with

stan

d vo

ltage

Rat

ed p

ower

freq

uenc

y w

ithst

and

volta

ge

kV

250

kV

95

Rat

ings

of i

sola

ting

dist

ance

Des

ign

pres

sure

P r b

ei 2

0 0 C

5)

kV/kV

290/110

bar

2.2

Rat

ed fr

eque

ncy

Rat

ed (n

orm

al) c

urre

n 3)

Hz

50/60

A1250

Rat

ed p

eak

with

stan

d cu

rrent

equa

l to

rate

d sh

ort-c

ircui

t ma-

king

cur

rent

Rat

ed s

hort-

time

curr

ent

1skA65

kA25

3s

Rat

ed s

hort-

circ

uit b

reak

ing

curr

ent

kA kA25

Per

cent

age

valu

e of

the

DC

co

mpo

nent

%

26WIA

WIA

WIA

6/55-S/626

6/55-T/626

6/55-T/626600

WIA-Z 600

27.5 52 250 95

17.5 36 170 70

290/110 2.2

2000

50/601250

2000

195/110 2.2 16 2/3 1250

65 25

65

65

25

25

25

25

25

80 31.5 31.5

26

46

Rated operating sequence

O -

3 m

in -

CO

- 3

min

- C

O

O -

0.3

s - C

O -

3 m

in -

CO

CO

- 15

s -

CO

O -

0.3

s - C

O -

15 s

- C

O

Cab

le b

reak

ing

curre

nt

A

50

Sm

all i

ndire

ct c

urre

nts

Rat

ed b

reak

ing

curre

ntun

der o

ut-o

f-pha

se c

ondi

tions

A kA

12.5

Number of operatingcycles without over -

haul

mech. electrical

Operating times

with release25 W

LS,TS,E w

ith ra

ted

(nor

mal

) cur

rent

1000010000

with

rate

d sh

ort-c

ircui

t

brea

king

cur

rent

Ope

ning

tim

e 4)

100

ms

50-80

160 W 160 W

Command time

with release25 W

Ope

ning

tim

e 4)

Clo

sing

tim

e 4)

ms

ms

40-50

Arc

dur

atio

n (m

ax.)

Off

ms

14

ms

50

160 W 160 W

Off

On

On

Offms

ms

20

Cha

rgin

g tim

e fo

r mot

or d

rive

mec

hani

smO

pera

ting

time

for d

isco

nnec

tor

and

earth

ing

switc

h w

ith m

otor

-dr

ive

mec

hani

sm, 1

60 W

s

≤ 12

s

≤ 18

50 12.5

50

1000

1000

10000

100010000 100 50-80

1000

10000 10000

1000

1000

100

– 40-50 14 50

25-35 40-50 6-68

– ≤ 12 ≤ 18

20 20

20

≤ 12 ≤ 18

■ ■ ■

Page 35: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

35WI EN

WI Selection tables (contd.)

Type

WIA

Pan

el w

idth

6/55-S/626mm

600

Rated insulation level

Rat

ed v

olta

ge U

NM

acc

. to

EN

50

124

Rat

ed v

olta

ge U

acc

. to

EN

60

694

kV

27.5

kV

52

Rat

ed li

ghtn

ing

impu

lse

with

stan

d vo

ltage

Rat

ed p

ower

freq

uenc

y w

ithst

and

volta

ge

kV

250

kV

95

Rat

ings

of i

sola

ting

dist

ance

Des

ign

pres

sure

P r b

ei 2

0 0 C

5)

kV/kV

290/110

bar

2.2

Rat

ed fr

eque

ncy

Rat

ed (n

orm

al) c

urre

n 3)

Hz

50/60

A1250

Rat

ed p

eak

with

stan

d cu

rrent

equa

l to

rate

d sh

ort-c

ircui

t ma-

king

cur

rent

Rat

ed s

hort-

time

curr

ent

1skA65

kA25

3s

Rat

ed s

hort-

circ

uit b

reak

ing

curr

ent

kA kA25

Per

cent

age

valu

e of

the

DC

co

mpo

nent

%

26WIA

WIA

WIA

6/55-S/626

6/55-T/626

6/55-T/626600

WIA-Z 600

27.5 52 250 95

17.5 36 170 70

290/110 2.2

2000

50/601250

2000

195/110 2.2 16 2/3 1250

65 25

65

65

25

25

25

25

25

80 31.5 31.5

26

46

Rated operating sequence

O -

3 m

in -

CO

- 3

min

- C

O

O -

0.3

s - C

O -

3 m

in -

CO

CO

- 15

s -

CO

O -

0.3

s - C

O -

15 s

- C

O

Cab

le b

reak

ing

curre

nt

A

50

Sm

all i

ndire

ct c

urre

nts

Rat

ed b

reak

ing

curre

ntun

der o

ut-o

f-pha

se c

ondi

tions

A kA

12.5

Number of operatingcycles without over -

haul

mech. electrical

Operating times

with release25 W

LS,TS,E w

ith ra

ted

(nor

mal

) cur

rent

1000010000

with

rate

d sh

ort-c

ircui

t

brea

king

cur

rent

Ope

ning

tim

e 4)

100

ms

50-80

160 W 160 W

Command time

with release25 W

Ope

ning

tim

e 4)

Clo

sing

tim

e 4)

ms

ms

40-50

Arc

dur

atio

n (m

ax.)

Off

ms

14

ms

50

160 W 160 W

Off

On

On

Offms

ms

20

Cha

rgin

g tim

e fo

r mot

or d

rive

mec

hani

smO

pera

ting

time

for d

isco

nnec

tor

and

earth

ing

switc

h w

ith m

otor

-dr

ive

mec

hani

sm, 1

60 W

s

≤ 12

s

≤ 18

50 12.5

50

1000

1000

10000

100010000 100 50-80

1000

10000 10000

1000

1000

100

– 40-50 14 50

25-35 40-50 6-68

– ≤ 12 ≤ 18

20 20

20

≤ 12 ≤ 18

■ ■ ■

Page 36: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

36 WI EN

WI Range of products

Single busbar panelsCircuit-breaker panel

■With inner cone-type cable connection for □ rated voltage up to 52 kV □ rated short-circuit breaking current up to 40 kA □ ratedbusbarandoutgoingfeeder(normal)currentsupto2500A

Disconnector panel ■With inner cone-type cable connection for

□ rated voltage up to 52 kV □ rated short-time current up to 40 kA □ ratedbusbarandoutgoingfeeder(normal)currentsupto2500A

Bus section coupler for

□ rated voltage up to 52 kV □ rated short-circuit breaking current up to 40 kA □ ratedbusbar(normal)currentsupto2500A

connection

Panel connection

or

or

or

and Busbarcurrenttransformer

Surgearrester,pluggable

Voltagetransformer,pluggable

Plug-in cablesingle,Terminal type 3

or

or

or

or Busbarwith solidinsulation

Panel

variants

Surgearrester,

pluggable

Currenttransformer

Voltagetransformer,

pluggable

Busbar attachments

attachment

Currenttransformer

Plug-in cablequadruple

Plug-in cabletriple

Plug-in cabledouble

Plug-in cablesingle

1)

1)

1)

1) if a surge arrester is used,the number of cables isreduced by one

1)

1)

Circuit-breaker panel(Innercone-typecableconnection)

Bus section coupler

1) not possible in case of 52 kV

Page 37: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

37WI EN

WI Range of products (contd.)

Double busar panelsCircuit-breaker panel

■With inner cone-type cable connection for □ rated voltage up to 52 kV □ rated short-circuit breaking current up to 40 kA □ ratedbusbarandoutgoingfeeder(normal)currentsupto2500A

Bus section coupler(Circuit-breakerpanelandbusriserpanel)

■With inner cone-type cable connection for □ rated voltage up to 52 kV □ rated short-circuit breaking current up to 40 kA □ ratedbusbarandoutgoingfeeder(normal)currentupto2500A

Bus section coupler for

■ rated voltage up to 52 kV ■ rated short-circuit breaking current up to 40 kA ■ ratedbusbar(normal)currentupto2500A

Bus coupler (transverse) for

■ rated voltage up to 52 kV ■ rated short-circuit breaking current up to 40 kA ■ ratedbusbar(normal)currentupto2500A

Metering panel for

■ rated voltage up to 36 kV ■ ratedbusbar(normal)currentupto2500A

Circuit-breaker panel(Innercone-typecableconnection)

or

or

or

and Busbarcurrenttransformer

Surgearrester,pluggable

Voltagetransformer,pluggable

Plug-in cablesingle,Terminal type 3

or

or

or

or Busbarwith solidinsulation

variants

Surgearrester,

pluggable

Currenttransformer

Busbar attachments

Panel connectionattachment

Plug-in cablequadruple

Plug-in cabletriple

Plug-in cabledouble

Plug-in cablesingle

1)

1)

1)

1) if a surge arrester is used,the number of cables isreduced by one

Voltagetransformer,

pluggable

1)

1)

SS2SS1

1) not possible in case of 52 kV

Page 38: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

38 WI EN

WI Range of products (contd.)

1) not possible in case of 52 kV

SS2SS1

Panelconnection

variants

or

or

or

or Busbarwith solidinsulation

Surgearrester,

pluggable

Plug-in cablequadruple

Plug-in cabletriple

Plug-in cabledouble

Plug-in cablesingle

Panelconnectionattachment

SS2SS1

Panelconnection

variants

or

or

or

or Busbarwith solidinsulation

Surgearrester,

pluggable

Panel connectionattachment

Currenttransformer

1)

1)

1)

1) if a surge arrester is used,the number of cables isreduced by one

Voltagetransformer,

pluggable

1)

1)

1)

1) if a surge arrester is used,the number of cables isreduced by one

Voltagetransformer,

pluggable

Plug-in cablequadruple

Plug-in cabletriple

Plug-in cabledouble

Plug-in cablesingle

1) 1)

Disconnector panel(Innercone-typecableconnection)

Bus section coupler / riser panel

Page 39: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

39WI EN

WI Range of products (contd.)

1) only up to 40.5 kVAbbreviationsSS1 = Busbar 1SS2 = Busbar 2

SS2SS1

Currenttransformer

SS2SS1

Currenttransformer

SS2SS1

Bus coupler up to 2000 A (1 panel width) 1)

SS2SS1

Currenttransformer

Bus section coupler Bus coupler up to 2500 A 1) Disconnector/earthing switch in line with busbar

Page 40: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

40 WI EN

WI Cable connections

Cable connections in outgoing feeder blockThe medium-voltage cables are connected to the switchgear panels via metal-enclosed inner cone-type plug-in terminations. The panels are equipped with inner cone-type appliance couplers according to EN 50 181.

Themanufacturer’sspecificationsoftheregardingselectionandassemblyof the plug-in terminations must be adhered to. This does not only apply to the selection of size, but also to all electrical rated data, in line with the switchgear’s data.

It is essential that all appliance couplers which are not equipped with plug-in terminations are terminated correctly using voltage-proof and fully shrouded insulating terminals/ dummy plugs.

To this effect, the inner cone-type cable plug-in terminations for attachment to WI require capacitive decoupling. The coupling electrodes for the capacitive voltage detection system are an integral part of the appliance couplers installed in the switchgear panel.

Cable connections in outgoing feeder

3 phase switchgear panels

1 phase switchgear panels

2 phase switchgear panels

Inner cone acc. to EN 50181Terminal types:

size 1 630 A

size 2 800 A

size3(upto40.5kV) 1250 A

size3(>40.5upto52kV) 1250 A

size 4 2500 A

Single / double busbar Single cable, 3-phase, without outgoing voltage transformer

12-36 kV 38-40.5 kV

1x size 1 ■

1x size 2 ■ ■

1x size 3 ■ ■

1x size 4 ■ ■

Size 4 with supporting structure increased in height

Single busbar Railway traction power supply with 2 vacuum interrupter chambers per phase

1-pole L1 2-pole L1, L3

1x size 3/S ■ ■Single cable connection

Page 41: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

41WI EN

WI Cable connections (contd.)

Single / double busbar with 1 vacuum interrupter chamber per conductor/phaseMulti-cable, 3-phase, without outgoingvoltage transformer

12 kV - 36 kV 38 kV - 40.5 kV

2 x size 1 ■

3 x size 1 ■

2 x size 2 ■ ■

3 x size 2 ■ ■

4 x size 2 ■ ■

2 x size 3 ■ ■

3 x size 3 ■ ■

4 x size 3 ■ ■

1xsize1+2xsize3 ■ ■

1xsize2+2xsize3 ■ ■

Single / double busbar with 2 vacuum interrupter chambers per conductor/phaseSingle- and multi-cable, 3-phase, without outgoing voltage transformer

40.5 kV BIL 200 kV

52 kVBIL 250 kV

1 x size 3 ■

1 x size 3/S ■

2 x size 3 ■

2 x size 3/S ■

3 x size 3 ■

3 x size 3/S ■

Single busbar for stationary railway traction power supply with 2 vacuum interrupter chambers per conductor/phaseMultiple cable without voltage transformer

1-phase L1 2-phase L1 + L3

2 x size 3/S ■ ■

3 x size 3/S ■ ■

4 x size 3/S ■

5 x size 3/S ■

Multi-cable connection

Page 42: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

42 WI EN

WI Cable connections (contd.)

Single / double busbar with 1 vacuum interrupter chamber per conductor/phaseMulti-cable, 3-phase with 3 outgoingvoltage transformers

12 kV - 36 kV 38 kV - 40.5 kV

1 x size 2 ■ ■

3 x size 2 ■ ■

4 x size 2 ■ ■

1 x size 3 ■ ■

2 x size 3 ■ ■

3 x size 3 ■ ■

4 x size 3 ■ ■

1xsize2+1xsize3 ■

1xsize2+2xsize3 ■

1xsize2+3xsize3 ■

1xsize2+4xsize3 ■

1xsize1+3xsize3 ■

Single / double busbar with 2 vacuum interrupter chambers per conductor/phaseMulti-cable, 3-phase, with 1 outgoing voltage transformer (1-phase in L2)

40.5 kV BIL 200 kV

52 kVBIL 250 kV

1 x size 3 ■

1 x size 3/S ■

2 x size 3 ■

3 x size 3/S ■

possibleuptorated(normal)currentinoutgoingfeederofmax.1600A

Single busbar for stationary railway traction power supply with 2 vacuum interrupter chambers per conductor/phaseMulti-cable with 1 or 2 voltage transformers

1-phaseL1

2-phase L1 + L3Voltage

transformersL3

Voltage transformersL1 + L3

1 x size 3/S ■ ■ ■

2 x size 3/S ■ ■

3 x size 3/S ■ ■

4 x size 3/S ■

Multi-cable connection with voltagetransformer in outgoing feeder

Page 43: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

43WI EN

WI Ecological considerations

A WI switchgearsatisfiestoahighdegreeecologicalrequirementsinviewof environmental protection thanks to

■ optimization of material and energy consumption during manufacture ■ compliance with all ecological requirements during its service life ■ theuseofrecyclablematerialsforefficientdisposalattheendofitsservice life.

Our design directives regarding environmentally compatible design specify the use of materials which are easily recyclable and can be disassembled. The metals which make up approx. 90 % of the switchgear are easily recyclable. At the end of their service life, they are recycled 100 % in the form of homogenous materials.Plastics can also be recycled. Thermosetting – i.e. non-melting – plastics canbecomminutedandreusedasfillersinotherplasticcomponents;thermoplastic - i.e. melting - materials can be recycled in the form of homogenous material. This means that the material is conserved, melted down and used for the construction of new durable parts. Toensureefficientandenvironmentallycompatibledisassemblyandassignment of materials by the responsible disposal experts, the switchgear’splasticcomponentshavebeenidentifiedaccordingly.Moreover, material and utilization data sheets are available to provide the customer with an over- view about the materials used. Equally, the disposal company is provided with important information regarding the recycling process.Thus, the materials used for our products can be reused 100 %.This represents a major contribution towards saving primary energy and material resources. Allmaterialswereselectedanddevelopedsothate.g.incaseoffirewithinbuildings,affectedswitchgearonlyhaveaminorinfluenceonthefireload(heatdevelopment,pollutantsintheemissions).Anotherimportantecologicalaspectisthelongevityofourproducts(min.30to40years),whichisanextremelylongservicelifecomparedtoothercapital goods. Furthermore, the switchgear units have been designed so as to require little maintenance which would in turn use up energy and material, and so as to enable straightforward replacement of part components, e.g. if newcontrollershavebeendevelopedonthemarket(upgrading).In our gas-insulated switchgear WI, the majority of the switchgear panel hasbeensealedhermeticallyinaninsulatinginertgas(sulphurhexafluorideSF6whichisneitherreactivenortoxic).Thus,allenvironmentalinfluencesreducingtheservicelifeareshutout.Thespecialcharacteristics of the insulating gas also enable an overall size reduction by approx. 50 percent versus switchgear designed without insulating gas with comparable technical properties. This again saves a lot of material and energy required for material production. The portion of insulating gas used for WI switchgear amounts to approx. 0.5 percent by weight. Once the switchgear’s service life has elapsed, the gas is extracted completely via thedisposalvalveprovidedseriallyineachgas-filled,claddedcompartment, and then recycled. The gas suppliers have developed an efficientrecyclingconcepttothiseffect.During normal operation, the gas need not be replenished during the entire service life of the switchgear. The switchgear is a hermetically sealed pressuresystemacc.toIEC60694(IEC62271-1).

Average material distribution in gas-insulated switchgear units

Materials Wt. %Metals Steel 7

Copper 6.5

Aluminium, brass 2

Plastics Thermosetting plastics 7

Thermo-plastics 2

Elastomers 0.5

Electronics Plastics 0.5

Metals 1

Insulating gas Sulphurhexafluoride 0.5

Page 44: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

44 WI EN

WI Design dataSpace requirements - dimensions and weights

>500

>500

>100

0 >1500 1)

2400

WIA up to 40.5 kV

View

>500

>500

>500

>1500 1)

Top view

>500

>500

>1500 1)

>100

0

WIA up to 52 kV

2964

1) smaller gap on request

Weights: WIA up to 40.5 kV approx. 1000 kg

WIA 52 kV approx. 1350 kg

280673

1692

600

460

70

70Spacer bars

7070

Flooring ductsFlooring ducts

Top view

view

Page 45: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

45WI EN

WI Design data Space requirements - dimensions and weights (contd.)

WIA up to 52 kV

>500

>500 >500

>100

0 >1500 1)

2400

WIA up to 40.5 kV

View

>500

>500

>500

>1500 1) >500

280673

1692

600

460

70

70Spacer bars

7070

>500

>500

>1500 1)

>100

0

2964

WIA up to 52 kV

1) smaller gap on request

Weights: WIA up to 40.5 kV max. 1000 kg

WIA 52 kV approx. 1350 kg

Flooring ducts

Top view

view

Page 46: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

46 WI EN

WI

WIB up to 40.5 kV

>500

>500

>500 >1500 1) >500

280673

1692

600

460

70

70Spacer bars

70

70

>500

>500 >500

>100

0 >1500 1)

3050

WIB bis 40,5 kV

View

>500

>500

>1500 1)

>100

0

3614

WIB bis 52 kV

1) smaller gap on request

Weights: WIB up to 40.5 kV approx. 1300 kg

WIB 52 kV approx. 1700 kg

Flooring ducts

Top view

view

Design data Space requirements - dimensions and weights (contd.)

Page 47: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

47WI EN

WI

WIB up to 52 kV

>500

>500

>100

0 >1500 1)

3050

WIB up to 40.5 kV

View

>500

>500

>500

>1500 1)

Top view

280673

1692

600

460

70

7070

70

Spacer bars

Flooring ducts

>500

>500

>1500 1)

>100

0

3614

WIB up to 52 kV

1) smaller gap on request

Weights: WIB up to 40.5 kV approx. 900 - 1000 kg

WIB 52 kV approx. 1100-1500Kg

Flooring ducts

Top view

view

Design data Space requirements - dimensions and weights (contd.)

Page 48: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

48 WI EN

WI

Busbar connection with fully insulated conductor bars

Direct transfer line. Phase exchange in terminal tankDirect transfer line. Phase exchange in terminal tank

Design data Space requirements - dimensions and weights (contd.)

Page 49: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

49WI EN

WI

Direct transfer line. Phase exchange in terminal tank

Transfer line at the bottom. Phase exchange required in transfer line

Transfer line top and bottom by means of supplementary gas tank

Direct transfer line. Phase exchange in terminal tank

Transfer line top and bottom by means of supplementary gas tank

Transfer line at the bottom. Phase exchange required in transfer line

Design data Space requirements - dimensions and weights (contd.)

Page 50: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

50 WI EN

WI Shipping instructions

Transporting the switchgear unitWhen transporting the switchgear unit, it is important to ensure that the transportunitsdonotsliportilt(ifnecessary,nailtransportpalletdowntotheloadingsurface).Reusetheoriginalpackagingtostorepartswhichhave been unpacked for inspection.

Packaging of the switchgear ■ If packed for truck transport, the switchgear unit is delivered on a pallet withPEprotectivefilm. ■Forsea-worthytransport,theunitsarepackedinsealedaluminiumfilmwith desiccant and in a closed case with tightly closed wooden base. ■ In case of air transport, the switchgear unit is packed in a wooden crate withclosedwoodenbaseandwithablisterIPEfilmasdustprotectionorin a wooden case, also with closed wooden base.

Transport to the site of installationStore under conditions admissible for switchgear operation. Avoid condensation.

During transport to the site of installation, remember that the main weight is located in the top area of the switchgear – “top-heavy”.

Transport using a forklift truck: Only transport the switchgear on a pallet. Attention – “top-heavy“!

Transport without pallet: The crane mounting harness must be hooked into the jack rings of the switchgear.

Page 51: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

Notes

51WI EN

Appendices

Page 52: Medium Voltage Distribution WI - Schneider Electricmt.schneider-electric.be/Main/WI/configuration/WI_configuration_en.pdf · Medium Voltage Distribution WI ... enhanced corrosion

WI EN 02-2011

© 2

011

Sch

neid

er E

lect

ric -

All

right

s re

serv

ed

Asstandards,specificationsanddesignschangefromtimetotime,pleaseaskforconfirmationoftheinformationgiveninthispublication.

Publishing: Schneider ElectricDesign: Schneider ElectricPrinting:

This document has been printed on ecological paper

Schneider Electric35, rue Joseph Monier CS 30323 92506 Rueil-Malmaison Cedex, France

RCS Nanterre 954 503 439 Capital social 896 313 776 €www.schneider-electric.com