16
Installation Instructions Medical Gas Alarm Assembly Medipoint 125 Central Alarm Part number 2005414 Revision 04 August 15, 2016

Medical Gas Alarm Assembly Medipoint 125 Central Alarm · 8 - Earth Lead Assembly Details 9 - MP125 Power Supply Board Connection Layout 10 - MP125 Example Maximum Of Cable Segments

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Medical Gas Alarm Assembly Medipoint 125 Central Alarm · 8 - Earth Lead Assembly Details 9 - MP125 Power Supply Board Connection Layout 10 - MP125 Example Maximum Of Cable Segments

Installation Instructions

Medical Gas Alarm AssemblyMedipoint 125 Central AlarmPart number 2005414Revision 04August 15, 2016

Page 2: Medical Gas Alarm Assembly Medipoint 125 Central Alarm · 8 - Earth Lead Assembly Details 9 - MP125 Power Supply Board Connection Layout 10 - MP125 Example Maximum Of Cable Segments

Atlas Copco Ltd. trading as Atlas Copco Medical Unit18NuffieldWay,Abingdon,Oxfordshire,UKOX141RL

Personnelmustmakethemselvesfamiliarwiththecontentsofthismanualandthe functionoftheunitbeforeinstalling,operatingormaintaining.

Installation InstructionsMedicalGasAlarmAssembly-MP125CentralAlarm

Thisunitispurchasedfrom:

Datepurchased:

Modelnumber:

Serialnumber:

Option(s)included:

Anyinformation,serviceorsparepartsrequestsshouldincludetheserialnumberandbedirectedto:

BeaconMedæsTelfordCrescent,StaveleyDerbyshireS433PF

Telephone:+44(0)1246474242Email:[email protected]:www.beaconmedaes.com

BeaconMedæsreservestherighttomakechangesandimprovementstoupdateproductssoldpreviouslywithoutnoticeorobligation.

AbbreviationsAbbreviation FullDescription Abbreviation FullDescription

HTM HealthTechnicalMemorandum % Percentage

BS BritishStandard Kg Kilograms

BSP BritishStandardPipe kPa Kilopascals

ISO InternationalStandardOrganisation PSI Poundspersquareinch

EN European Standards NRV Non-returnvalve

ID Identification 1st First

Med Medical 2nd Second

°C Degree Celsius O2 Oxygen

ø Diameter N2O Nitrousoxide

OD OutsideDiameter N2O/O2 O2/N2O50%/50%V/V

m Meter MA Medical Air

mm Millimetres SA Surgical Air

“ Inch VAC MedicalVacuum

Max Maximum CO2 CarbonDioxide

Min Minimum N2 Medical Nitrogen

Page 3: Medical Gas Alarm Assembly Medipoint 125 Central Alarm · 8 - Earth Lead Assembly Details 9 - MP125 Power Supply Board Connection Layout 10 - MP125 Example Maximum Of Cable Segments

3

Medical Gas Alarm Assembly - Medipoint 125 Central Alarm

2005414.04

Table of Contents

0. Safety, Storage and Handling 0.1 Environmental Transport, Storage and

Operating Conditions.

0.2 Cleaning

0.3 Environmental Protection

0.4 Electromagnetic Interference

0.5 Rechargeable Battery

0.6 Electrical Details

0.7 Protection

0.8 Symbols

1.1 Description

1.2 Installation of a first fix panel. 1.2.1 Backbox. Locate

1.2.2 Wall. Fit anchors.

1.2.3 Backbox. Fit

1.3 Installation of a Second Fix Assembly 1.3.1 Backbox. Check.

1.3.2 Fit Legends as required

1.3.3 Alarm panel front cover. Fit

1.3.4 Power supply printed circuit board. Fit

1.3.5 Electrical bonding lead. Fit

1.3.6 Cable Installation - Input Cable

2.0 Programming of the alarm system

3.0 Commissioning (See Document 2005415)

Figures 1 - MP125 Display, Shown In Normal Running

2 - Backbox Details

3 - Bezel Detail

4 - Legend Installation

5 - Examples Of Recommended Display Positions

6 - Door Installation Detail

7 - Power Supply Board Installation Details

8 - Earth Lead Assembly Details

9 - MP125 Power Supply Board Connection Layout

10 - MP125 Example Maximum Of Cable Segments

11 - MP125 Typical Wiring Diagrams

12 - MP125 Programming Switches

13 - Example Of Programming Settings

Table 1 - Recommended Display Positions

2 - Medipoint 125 Programming

Page 4: Medical Gas Alarm Assembly Medipoint 125 Central Alarm · 8 - Earth Lead Assembly Details 9 - MP125 Power Supply Board Connection Layout 10 - MP125 Example Maximum Of Cable Segments

4

Medical Gas Alarm Assembly - Medipoint 125 Central Alarm

2005414.04

0. Safety Precautions

Operator should have carefully read and become familiar with the contents of this manual before maintaining the terminal units.

Operator is expected to use common sense safety precautions, good workmanship practices and follow any related local safety precautions.

Component descriptions and parts lists are available on request.

0.1 Environmental Transport and Storage Conditions

All products are separately packaged and stored in controlled conditions.

0.2 Cleaning

The alarm cover and fascia should be wiped over with a damp cloth frequently to remove any dust or foreign substances.

0.3 Environmental Protection

Discard the unit and/or components in any standard refuse facility. The unit does not contain any hazardous substances.

0.4 Electromagnetic Interference

Ensure any input and data cables are physically separated from other mains and data cables.

0.5 Rechargeable Battery

The rechargeable battery (ref. 1828825) should be replaced every 5 years.

0.6 Electrical Details

WARNING...It is necessary to check the integrity of the power source for safety at regular intervals. These checks should be carried out annually and replacement power supplies used is necessary.

Power source

Mains operated using 115/230V, 50/60Hz, alternating current, from an essential circuit. Please see labelling inside unit for correct voltage.

Current requirements

3.0 amps

0.7 Protection

Type of protection against electric shock

Class 1 (Mains supplied equipment using a protected earth)

Mode of operation

Continuous (equipment may be left switched on indefinitely)

Degree of protection against ingress of liquids

IPX0 (Not protected)

Degree of mobility

Permanently installed (This unit is electrically connected by permanent means)

Degree of protection

Type B (no Applied Part or with and Applied Part not designed to meet F type (floating) requirements)

Degree of protection against flammable anaesthetic mixtures

Not protected (not suitable for use with flammable gases)

0.8 Symbols

The following symbols apply to this product and are used in these instructions and on the product in question. The meanings of these symbols are as specified below: -

Page 5: Medical Gas Alarm Assembly Medipoint 125 Central Alarm · 8 - Earth Lead Assembly Details 9 - MP125 Power Supply Board Connection Layout 10 - MP125 Example Maximum Of Cable Segments

5

Medical Gas Alarm Assembly - Medipoint 125 Central Alarm

2005414.04

Read instructions

Warning - dangerous voltage

Ambient temperature range

Ambient humidity range

Ambient pressure range

Date of manufacture

Caution - system alarm

Power on

Mute switch

Test button

Protective earth

Alternating current

Static sensitive components

Audible warning

Do not dispose of in general waste

1.1 Description

The BeaconMedæs Medipoint 125 medical gas central alarm system is designed to provide full monitoring of a complete medical gas installation. Medipoint 125 alarm systems consist of source panels connected to supply equipment located in plant rooms, and repeater panels in locations as specified by the customer for constant monitoring. Medical gas supply conditions are transmitted throughout the alarm system by means of an advanced data transmission circuit.

The Medipoint 125 can be programmed by the use of switches to provide a fully flexible alarm system. Allowing the panels to be adapted to suit any hospital’s medical gas monitoring requirements (see user manual 2005414 section 1.12 for programming details).

An individual Medipoint 125 panel has 5 columns consisting of ‘normal’ and 4 ‘fault’ conditions. These columns can be setup to monitor either up to 5 medical gas source equipment, or up to 20 individual point alarms, or a combination of the 2.

One Medipoint 125 alarm panel is designated the master panel for control purposes. Any number of panels may be programmed as a ‘central acknowledge panel’ and cause all flashing displays on the system to change to steady when the MUTE switch on the central acknowledge panel is operated. Each Medipoint 125 alarm panel connects directly with the mains electrical power supply and alarm panels are available for use with AC supplies of either 115V±10%, 60Hz or 230V±10%, 50Hz. Electrical power supplies should be from an essential circuit and fused at 3 Amps.

Each Medipoint 125 alarm panel incorporates flashing alarm displays, a POWER ON indication, a SYSTEM ALARM indication, MUTE and TEST switches and an audible warning programmed to operate depending upon the alarm condition displayed (see figure 1 overleaf for display image). Alarm panels are interconnected by data transmission cable. Relay interface units are available to input conditions into existing alarm systems or building management systems.

1.2 Installation of a first fix panel

The alarm panel backbox is suitable for both surface and concealed installation and is annotated 'TOP' inside to ensure correct orientation. With a concealed installation a chase depth of 45mm is required and a bezel is fitted to cover the plaster joint. The procedure to install a first fix alarm panel backbox is as follows: -

1.2.1 Backbox. Locate (see figure 2). Ensure the backbox is the correct way up. Locate the backbox at the correct position and mark out for securing screws.

1.2.2 Wall. Fit anchors. Drill wall and fit anchors in position.

1.2.3 Backbox. Fit (see figure 2). Select cable entry/exit points and remove the desired knock-out segments from the inside. Fit suitable grommets/cable glands as required by the contract specification. Feed cables into the box leaving 400mm to enable connection to printed circuit board. Secure back box to wall with suitable screws.

WARNING... WITH A CONCEALED INSTALLATION, THE PLASTER DEPTH MUST BE FLUSH WITH THE BOX SURFACE, LEAVING THE WATER CHANNEL PROUD OF THE PLASTER.

Page 6: Medical Gas Alarm Assembly Medipoint 125 Central Alarm · 8 - Earth Lead Assembly Details 9 - MP125 Power Supply Board Connection Layout 10 - MP125 Example Maximum Of Cable Segments

6

Medical Gas Alarm Assembly - Medipoint 125 Central Alarm

2005414.04

1.3 Installation of a Second Fix Assembly

WARNING...ENSURE THAT THE ELECTRICAL POWER SUPPLY TO THE ALARM IS OFF AND REMAINS ISOLATED UNTIL REQUIRED DURING THE COMMISSIONING PROCEDURE

1.3.1 Backbox. Check. Ensure that the inside of the backbox is clean and free from debris.

Concealed installation. Fit bezel plate (see figure 3). Fit bezel plate to backbox and retain with securing screw engaged in right hand anchor nut.

FIGURE 1 - MP125 DISPLAY, SHOWN IN NORMAL RUNNING

Audible Warning

Test Switch

System Alarm LED

Power On LED

Mute Switch

Gas ID Row

Normal LED

Warning Fault LED Rows

7 101.50

98

196

5

105

105

200

17

20

46

KNOCKOUT SEGMENTS BACKBOX SURFACE

40 40 40 40

17

20

KNOCKOUT SEGMENTS

FIGURE 2 - BACKBOX DETAILS

FIGURE 3 - BEZEL DETAIL 310

246

4

6

25 (ALL ROUND)

1.2

0

Page 7: Medical Gas Alarm Assembly Medipoint 125 Central Alarm · 8 - Earth Lead Assembly Details 9 - MP125 Power Supply Board Connection Layout 10 - MP125 Example Maximum Of Cable Segments

7

Medical Gas Alarm Assembly - Medipoint 125 Central Alarm

2005414.04

1.3.2 Fit Legends as required (see figures 4, 5 and table 1)

Fit blank and gas/vacuum service legend, through the slots in the rear of the cover, as required. NB. It is necessary to remove the display PCB to access the slots easily.

To provide an aesthetic display and maintain consistency in accordance with recognised and established Medical gas service sequencing, it is recommended that displays are positioned in the following sequence on each alarm panel commencing with the left hand column:-

Medical Oxygen (cryogenic and manifolds)Nitrous oxide (manifolds)Oxygen/Nitrous oxide (manifolds)Medical Air 400 kPa (plant and manifolds)Medical Air 700 kPa (plant and manifolds)Medical Vacuum (plant)AGS (simplex or duplex)Point alarms (as required)

When an alarm panel is required to display less than its maximum of 5 gas services, it is recommended that displays are positioned in accordance with the following (see figure 4 & table 1):

TABLE 1: RECOMMENDED DISPLAY POSITIONS

Displaycolumn 1 2 3 4 5

1 gas Gas 1

2 gas Gas 1 Gas 2

3 gas Gas 1 Gas 2 Gas 3

4 gas Gas 1 Gas 2 Gas 3 Gas 4

5 gas Gas 1 Gas 2 Gas 3 Gas 4 Gas 5

BEZEL

SECURING SCREW(M4 x 12 PAN HEAD)

BACK BOX

310

246

4

6

25 (ALL ROUND)

1.2

0

FIGURE 4 - LEGEND INSTALLATION

Col. 5 Col. 4 Col. 3 Col. 2 Col. 1

GAS LEGEND INSTALLATION SLOTS

FIGURE 5 - EXAMPLES OF RECOMMENDED DISPLAY POSITIONS

TYPI

CAL

1 G

AS

Page 8: Medical Gas Alarm Assembly Medipoint 125 Central Alarm · 8 - Earth Lead Assembly Details 9 - MP125 Power Supply Board Connection Layout 10 - MP125 Example Maximum Of Cable Segments

8

Medical Gas Alarm Assembly - Medipoint 125 Central Alarm

2005414.04

1.3.3 Alarm panel front cover. Fit (SEE FIGURE 6).

Secure the front cover to backbox flange by securing hinge to backbox with screws provided.

TYPI

CAL

4 G

ASTY

PICA

L 5

GAS

TYPI

CAL

3 G

AS

FIGURE 6 - DOOR INSTALLATION DETAIL.

M4 x 12 PAN HEAD x 2

DOOR ASSEMBLY

M4 x WASHER x 2

BACK BOX

FIGURE 7 - POWER SUPPLY BOARD INSTALLATION DETAILS.

1.3.4 Power supply printed circuit board. Fit (see figure 7).

Fit a plastic spacer over each of the four retaining studs in the backbox and locate the board on the studs. Fit the washers and tighten nuts in place just enough to hold the board and not crack it.

CAUTION... Printed circuit boards are susceptible to damage by static electricity and must remain enclosed in their anti-static packaging until immediately required for use. Removed printed circuit boards must be placed in their anti-static packaging immediately on removal. To prevent damage to printed circuit boards, handle with care and do not over torque retaining nuts.

M3 NUT x 4

PLASTIC SPACERS x 49.5 OD x 8mm LONG

POWER SUPPLY BOARDM3 STEEL WASHER x 1

M3 x 18 HEX SPACER

TERMINAL SHIELDM3 x 5 PAN HEAD

M3 NYLON WASHER x 3

TYPI

CAL

2 G

AS

Page 9: Medical Gas Alarm Assembly Medipoint 125 Central Alarm · 8 - Earth Lead Assembly Details 9 - MP125 Power Supply Board Connection Layout 10 - MP125 Example Maximum Of Cable Segments

9

Medical Gas Alarm Assembly - Medipoint 125 Central Alarm

2005414.04

1.3.5 Electrical bonding lead. Fit (see figure 8).

Connect the flying earth lead from the power supply PCB mains terminal ‘E’ to the earthing stud in the alarm panel backbox and alarm panel front cover.

FIGURE 8 - EARTH LEAD ASSEMBLY DETAILS.

EARTH STUD EARTH LEAD EARTH STUD

M3 NUT

M3 WASHER

EARTH LEAD

M3 WASHER

M3 NUT

M3 STUD

M3 NUT

M3 STUD

M3 WASHER

EARTH LEAD

M3 NUT

M3 WASHER

1.3.5 Cable Installation - Data Cable

Details for the cable connections can be seen on figure 9, typical wiring diagrams can be seen on figure 11.

The MP125 uses the EIA/TIA-485 (RS-485) data communications specification. Cable used for the alarm data must be suitable for these signals. BeaconMedæs recommends the following cable types:

Manufacturer / Reference Part Number

Belden 8132 (2 pr, Non-Plenum) 2005421

Belden 82842 (2 pr, Plenum)

Alphawire 6455 (2 pr, Non-Plenum)

If segment lengths longer than 1200 metres, or non-standard network topologies are required, a signal booster / splitter is available. See figure 10 for examples. BeaconMedæs recommend installation of 2 pair cable, such that a spare pair is available, if needed.

1.3.6 Cable Installation - Input Cable

Details for the cable connections can be seen on figure 9, typical wiring diagrams can be seen on figure 11.

The MP125 uses BeaconMedæs Line Contact Monitoring on all input signals. This type of connection is relatively immune to interference. Shielded cable is not a requirement, however, in extremely electrical noise shielding may be necessary. BeaconMedæs recommends the following cable types, and a maximum length of 100 metres.

Manufacturer / Reference Part NumberAlphawire 1175C (Unshielded) 2005422

Alphawire 1175L (Unshielded, LSZH)

Alphawire 1295C (Shielded)

Page 10: Medical Gas Alarm Assembly Medipoint 125 Central Alarm · 8 - Earth Lead Assembly Details 9 - MP125 Power Supply Board Connection Layout 10 - MP125 Example Maximum Of Cable Segments

10

Medical Gas Alarm Assembly - Medipoint 125 Central Alarm

2005414.04

FIGURE 9 - MP125 POWER SUPPLY BOARD CONNECTION LAYOUTMULTI-WAY DATA RIBBON

FROM LIGHT BOARD

INPUTS FOR DISPLAY COLUMNS 1-5[COMMON] [FAULT CONDITIONS 1-4]

NOTE - FAULT CONDITION 1 COINCIDES WITH THE TOP FAULT CONDITION LED, WORKING DOWN IN ORDER

DATA TRANSMISSION CONNECTIONSIN [A] [B], OUT [A] [B] AND [SCREEN]

REMOTE AUDIBLE CONNECTION [+] [-]

OUTPUT RELAY FORTRANSMITTING SINGLE

EVENT ALARM[COMMON] [N/O]

MAIN POWER CONNECTION[BONDING EARTH]

[MAIN EARTH][NEUTRAL] [LIVE]

MEDIPOINT 125

DATA

IN OUT

MEDIPOINT 125

DATA

IN OUT

MEDIPOINT 125

DATA

IN OUT

IN OUT

BOOSTER

IN OUT

MEDIPOINT 125

DATA

IN OUT

LENGTH OF SEGMENT <1200 METRES LENGTH OF SEGMENT <1200 METRES

FIGURE 10 - MP125 EXAMPLE MAXIMUM OF CABLE SEGMENTS

MEDIPOINT 125

DATA

IN OUT

MEDIPOINT 125

DATA

IN OUT

MEDIPOINT 125

DATA

IN OUT

IN OUT

BOOSTER

IN OUT

LENGTH OF SEGMENT <1200 METRES

MEDIPOINT 125

DATA

IN OUT

MEDIPOINT 125

DATA

IN OUT

MEDIPOINT 125

DATA

IN OUT

MEDIPOINT 125

DATA

IN OUT

MEDIPOINT 125

DATA

IN OUT

MEDIPOINT 125

DATA

IN OUT

MEDIPOINT 125

DATA

IN OUT

MEDIPOINT 125

DATA

IN OUT

MEDIPOINT 125

DATA

IN OUT

LENGTH OF SEGMENT <1200 METRES

LENGTH OF SEGMENT <1200 METRES LENGTH OF SEGMENT <1200 METRES

2 segment network with a single, distant panel.

2 segment network arranged as a physical cross.

Page 11: Medical Gas Alarm Assembly Medipoint 125 Central Alarm · 8 - Earth Lead Assembly Details 9 - MP125 Power Supply Board Connection Layout 10 - MP125 Example Maximum Of Cable Segments

11

Medical Gas Alarm Assembly - Medipoint 125 Central Alarm

2005414.04

Medipoint 125 Wiring Diagram Typical Schematic

Medipoint 125 Typical Input Connection

Notes...1. If connected to BeaconMedæs plant, line contact monitors are integral to the plant.2. Unused terminals must be linked out with linking resistors provided.

Notes...1. A maximum of four point alarms may be connected to any channel.2. Unused terminals must be linked out with linking resistors provided.

FIGURE 11 - MP125 TYPICAL WIRING DIAGRAMS

Page 12: Medical Gas Alarm Assembly Medipoint 125 Central Alarm · 8 - Earth Lead Assembly Details 9 - MP125 Power Supply Board Connection Layout 10 - MP125 Example Maximum Of Cable Segments

12

Medical Gas Alarm Assembly - Medipoint 125 Central Alarm

2005414.04

2.0 Programming of the alarm system

The Medipoint 125 central alarm system panels are programmed by setting a series of DIL and rotary switches on the rear of the light display board (see figure 12), as detailed in table 4. Rotary switches SW1 to SW5 assign the display columns to a specified input, or OFF. 1 to F correspond to ‘normal’ medical gas alarms, i.e. Normal + 4 alarm conditions with an audible on all alarm conditions. 8-way DIL switch SW6 sets details specific to each panel. Rotary switch SW7 sets the panel ID. Similar switches are on the rear of the relay board in a Medipoint 125 relay interface panel.

The Medipoint 125 central alarm system works by identifying each individual gas channel or set of point alarm inputs with a unique ID and by identifying each panel with a unique ID. The rotary switches are hexadecimal i.e. A corresponds to 10, B corresponds to 11 etc. for purposes of panel Ids. A channel must be set between 0 and F, 0 being OFF.

SW7 in conjunction with SW6-7 give each individual panel an ID between 0 and 31. The alarm panel with the highest ID must be set as the MASTER panel (SW6-6 ON), all other panels (including Medipoint 125 Relay panels) must be set as slave panels (SW6-6 OFF). Therefore one alarm system may contain up to 32 panels the highest number being set as the MASTER.

SW6-8 enables or disables the central acknowledge facility, ON enabled, OFF disabled. When the mute switch is operated on a central acknowledge panel displaying a fault condition, the flashing light on all panels showing the same fault changes from flashing to steady, and the audible alarm is muted for that particular gas.

NB there may be more than one central acknowledge panel on a system (i.e. two panels in the telephone exchange on a 10 gas system), but there must be only one master panel on the system and it must have the highest panel ID on the system.

SW6-1 to SW6-5 are used to identify where each channel is input onto the system. If these switches are set to ON then this means that a particular gas or set of point alarms is input to this panel. On a complete system there should only be as many of these switches set to ON as there are channels on the complete system. When set to ON the alarm panel will look for a complete set of inputs, i.e. four fault conditions. If less than four inputs are been connected to a particular channel then the linking resistors provided must be used to “link out” the unused conditions. I.e. if a C11 vacuum plant is to be connected, then the input alarm conditions would be connected between Common, 1, 2 and 4. Therefore a linking resistor must be connected between Common and 3.

An alarm system is set up by allocating a number (1 to 9) or letter (A to F) to each set of plant inputs or point alarm inputs. Typically on a 4 gas system with point alarms:-

1 – Oxygen Manifold Alarms2 – Nitrous Oxide Manifold Alarms3 – Air Plant Alarms4 – Vacuum Plant AlarmsA – Ward 1 to 4 Point AlarmsB – Ward 5 to 8 Point Alarms

Therefore on every panel where Oxygen is to be displayed the appropriate gas number switch (SW1 to SW5) is set to 1. Where inputs are connected into the system the appropriate DIL switch (SW6-1 to SW6-5) must be set ON.

For example, if air and vacuum plant are both input into channels 2 and 3 on a two gas panel in the plant room, then SW2 must be set to 3 to display air plant, SW3 must be set to 4 to display vacuum plant. SW1, SW4 and SW5 must be set to 0. Also SW6-2 and SW6-3 must be set to ON to indicate that these alarms are input to this panel.

SW8 selects the voltage range of the power supply, either 230V±10% or 115V±10%.

SW9 selects the termination and fail safe biassing options for the RS-485 port. A network is divided up into segments. Each segment can be up to 1200 metres (see figure 10 for examples), subject to cable type and site conditions.For the two panels at the endpoints of each cable segment on a network, the termination resistor should be switched on with SW9-1 and SW9-2. For all other panels, SW9-1 and SW9-2 should be switched off. If a signal booster is the endpoint of a cable segment, the termination resistor of the booster should be enabled. See the instruction manual enclosed with the signal booster for more details.

For each cable segment on a network the fail safe resistors should be enabled on a single panel, by switching on SW9-3 and SW9-4. For all other panels, SW9-3 and SW9-4 should be switched off.

See figure 13 for example of programming settings for a typical installation. Table 2 shows a summary of the programming switch functions

NOTE:Whenever the programming switches on the light board are changed, it is necessary to reset the alarm by pressing the reset button, or by cycling the power, to read in the new configuration values.

Page 13: Medical Gas Alarm Assembly Medipoint 125 Central Alarm · 8 - Earth Lead Assembly Details 9 - MP125 Power Supply Board Connection Layout 10 - MP125 Example Maximum Of Cable Segments

13

Medical Gas Alarm Assembly - Medipoint 125 Central Alarm

2005414.04

FIGURE 12 - MP125 PROGRAMMING SWITCHES

PROGRAMMING SWITCHES (SEE SECTION 1.12)

AUDIBLE WARNING VOLUME CONTROL

SW1SW2SW3SW4SW5SW6SW7

CONFIGURABLE DIP SWITCHES FOR DATA

TRANSMISSION

NOTE...Jumper JP1 shown on the right hand and middle pin [LCM], sets the Output Relay for line contact monitoring. Move to the left hand and middle pin [N/O] if line contact monitoring is not desired, for example when the Output Relay is communicating with a non BeaconMedæs alarm.

Operate the RESET after changing any setting on the power supply board.

The BOOT switch & Communication Port is only used during manufacture.

JUMPER JP1(SEE NOTE)

TABLE 2: MEDIPOINT 125 PROGRAMMING

Switch Setting/description

SW1 0 Display channel 1 Off, gas display

channel not used

1-F Display channel 1 Normal gas display HTM02-01

SW2 0 Display channel 2 Off, gas display

channel not used

1-F Display channel 2 Normal gas display HTM02-01

SW3 0 Display channel 3 Off, gas display

channel not used

1-F Display channel 3 Normal gas display HTM02-01

SW4 0 Display channel 4 Off, gas display

channel not used

1-F Display channel 4 Normal gas display HTM02-01

SW5 0 Display channel 5 Off, gas display

channel not used

1-F Display channel 5 Normal gas display HTM02-01

SW6

1OFF Channel 1 display not input at this panel

ON Channel 1 display input to this panel

2OFF Channel 2 display not input at this panel

ON Channel 2 display input to this panel

3OFF Channel 3 display not input at this panel

ON Channel 3 display input to this panel

4OFF Channel 4 display not input at this panel

ON Channel 4 display input to this panel

5OFF Channel 5 display not input at this panel

ON Channel 5 display input to this panel

6OFF to designate panel as slave

ON to designate panel as master (must be highest ID on system)

7OFF for panel ID 0 to 15

ON or panel ID 16-31

8OFF to disable central acknowledge facility

ON to enable central acknowledge facility

SW7 0-F Sets panel ID 0 to 15 or 16 to 31 in conjunction with SW6-7

SW8115 Set voltage to 115V±10%

230 Set voltage to 230V±10%

SW9

1-2OFF to disable RS485 termination

ON to enable RS485 termination(on cable segment endpoints only)

3-4OFF to disable RS485 fail safe biassing

ON to enable RS485 fail safe biassing(on one panel per cable segment only)

NOTE:Switches SW8 and SW9 are on the power PCB (see fig-ure 12). All other switches are on the light PCB (see fig-ure 12)

For example of typical installation see figure 13.

Page 14: Medical Gas Alarm Assembly Medipoint 125 Central Alarm · 8 - Earth Lead Assembly Details 9 - MP125 Power Supply Board Connection Layout 10 - MP125 Example Maximum Of Cable Segments

14

Medical Gas Alarm Assembly - Medipoint 125 Central Alarm

2005414.04

FIGURE 13 - EXAMPLE OF PROGRAMMING SWITCH SETTINGS FOR A TYPICAL INSTALLATION INCLUDING MP125 & MP26

Swit

ch s

etti

ngs

for

exam

ple

inst

alla

tion

Pane

l Loc

atio

n

TYPE

SW1

SW2

SW3

SW4

SW5

SW6

SW7

SW9

C1 Gas

1

C2 Gas

2

C3 Gas

3

C4 Gas

4

C5 Gas

5

C1 Inpu

tC2 Inpu

tC3 Inpu

tC4 Inpu

tC5 Inpu

tM

aste

rPa

nel

ID H

igh

Mas

ter

Mut

ePa

nel

IDRS

485

TERM

Vie

I0

01*

00

OFF

OFF

ON

OFF

OFF

OFF

OFF

OFF

0O

NEs

tate

s 1

R1

23

45

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

1O

NEs

tate

s 2

R6

78

9A

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

2O

FFSo

uth

Plan

t Ro

omI

05*

08*

0O

FFO

NO

FFO

NO

FFO

FFO

FFO

FF3

OFF

Day

Sur

gery

R1

35

80

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

4O

FFM

anifo

ld

Room

1I

02*

03*

0O

FFO

NO

FFO

NO

FFO

FFO

FFO

FF5

OFF

Thea

tre

Rece

ptio

n 1

R1

23

67

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

6O

FF

Thea

tre

Rece

ptio

n 2

RI0

90

A*0

OFF

OFF

OFF

ON

OFF

OFF

OFF

OFF

7O

FF

Nor

th P

lant

Ro

omI

06*

7*9*

0O

FFO

NO

NO

NO

FFO

FFO

FFO

FF8

OFF

Mat

erni

ty

Man

ifold

Roo

mI

00

4*0

0O

FFO

FFO

NO

FFO

FFO

FFO

FFO

FF9

OFF

Mat

erni

tyR

14

69

0O

FFO

FFO

FFO

FFO

FFO

FFO

FFO

FFA

OFF

Rela

y In

terf

ace

1RL

12

34

5O

FFO

FFO

FFO

FFO

FFO

FFO

FFO

FFB

ON

Rela

y In

terf

ace

2RL

67

89

AO

FFO

FFO

FFO

FFO

FFO

FFO

FFO

FFC

OFF

Tele

phon

e Ex

chan

ge 1

R1

23

45

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

DO

FF

Tele

phon

e Ex

chan

ge 2

R6

78

9A

OFF

OFF

OFF

OFF

OFF

ON

OFF

OFF

EO

FF

* m

arks

the

chan

nel a

s an

inpu

t, Ty

pe ‘I

’ - In

put p

anel

, Typ

e ‘R

’ - r

epea

ter

pane

l, Ty

pe ‘R

I’ - r

epea

ter/

inpu

t pan

el, T

ype

‘R’ -

rel

ay in

terf

ace

pane

l

Page 15: Medical Gas Alarm Assembly Medipoint 125 Central Alarm · 8 - Earth Lead Assembly Details 9 - MP125 Power Supply Board Connection Layout 10 - MP125 Example Maximum Of Cable Segments

15

Medical Gas Alarm Assembly - Medipoint 125 Central Alarm

2005414.04

3.0 Commissioning procedure. Carry out.All testing and commissioning should be completed in accordance with the installation contract.

See Instructions Manual (2005415) for commissioning details.

MEDIPOINT 125 ID: 0

LOCATION: VIE

COLUMN INPUTS DATA

0 0 1* 0 0 IN OUT

OXYGEN SUPPLY

SIGNAL BOOSTER/SPLITTER

LOCATION: SOUTH PLANT ROOM

DATA

A B

MEDIPOINT 125 ID: 3

LOCATION: SOUTH PLANT ROOM

COLUMN INPUTS DATA

0 5* 0 8* 0 IN OUT

MEDICAL AIR VACUUM SOUTH SOUTH

MEDIPOINT 125 ID: 4

LOCATION: DAY SURGERY

COLUMN INPUTS DATA

1 3 5 8 0 IN OUT

MEDIPOINT 125 ID: 2

LOCATION: ESTATES 2

COLUMN INPUTS DATA

6 7 8 9 A IN OUT

MEDIPOINT 125 ID: 1

LOCATION: ESTATES 1

COLUMN INPUTS DATA

1 2 3 4 5 IN OUT

MEDIPOINT 125 ID: 6

LOCATION: THEATRE 1

COLUMN INPUTS DATA

1 2 3 6 7 IN OUT

MEDIPOINT 125 ID: 5

LOCATION: MANIFOLD ROOM

COLUMN INPUTS DATA

0 2* 0 3* 0 IN OUT

OXYGEN NITROUS MANIFOLD OXIDE

MEDIPOINT 125 ID: 7

LOCATION: MANIFOLD ROOM

COLUMN INPUTS DATA

0 9 0 A* 0 IN OUT

MEDIPOINT 26

LOCATION: THEATRE RECEPTION

COLUMN INPUTS DATA

RELA

Y[C

] [N

/O]

O2

N2O

MA

4

MA

7

VAC 0 IN O

UT

MEDIPOINT 26

LOCATION: THEATRE 1

COLUMN INPUTS DATA

RELA

Y[C

] [N

/O]

O2

N2O

MA

4

MA

7

VAC 0 IN O

UT

MEDIPOINT 26

LOCATION: THEATRE AVSUs

COLUMN INPUTS DATA

RELA

Y[C

] [N

/O]

O2

N2O

MA

4

MA

7

VAC 0 IN O

UT

PRESSURE SWITCH INPUTS

MEDIPOINT 125 ID: 8

LOCATION: NORTH PLANT ROOM

COLUMN INPUTS DATA

0 6* 7* 9* 0 IN OUT

MEDICAL SURGICAL VACUUMAIR NORTH AIR NORTH

MEDIPOINT 125 ID: 9

LOCATION: MATERNITY MANIFOLD ROOM

COLUMN INPUTS DATA

0 0 4* 0 0 IN OUT

ENTONOX

MEDIPOINT 125 ID: A

LOCATION: MATERNITY UNIT

COLUMN INPUTS DATA

1 4 6 9 0 IN OUT

MEDIPOINT 125 (MASTER) ID: E

LOCATION: TELEPHONE EXCHANGE 2

COLUMN INPUTS DATA

6 7 8 9 A IN OUT

MEDIPOINT 125 ID: D

LOCATION: TELEPHONE EXCHANGE 1

COLUMN INPUTS DATA

1 2 3 4 5 IN OUT

MP125 RELAY INTERFACE ID: C

LOCATION: TELEPHONE EXCHANGE R2

COLUMN INPUTS DATA

6 7 8 9 A IN OUT

MP125 RELAY INTERFACE ID: B

LOCATION: TELEPHONE EXCHANGE R1

COLUMN INPUTS DATA

1 2 3 4 5 IN OUT

CABLE TYPESBelden 8729 2 pair RS485Alphawire 117C 5 coreAlphawire B964011 1 pairAlphawire 1173C 3 core

NOTES...Columns marked * indicate that gas service is input at that panelMaximum length of data cable segments is 1200 metresMaximum length of input cable segments is 100 metresMaximum length of remote audible cables is 50 metres

Page 16: Medical Gas Alarm Assembly Medipoint 125 Central Alarm · 8 - Earth Lead Assembly Details 9 - MP125 Power Supply Board Connection Layout 10 - MP125 Example Maximum Of Cable Segments

Unit 18 Nuffield Centrum, Abingdon,Oxfordshire, OX14 1RL, UK

+44 (0) 1235 463 010www.beaconmedaes.com 0088