Mechanical Shop Drawing Review Form Integral Group | Suite 180 - 200 Granville Street, Vancouver, BC V6C 1S4 +1.604.687.1800 | Integralgroup.com DATE: June 13, 2017 PROJECT: SFU Student Union Building PROJECT NO: 155501.000 Architect: Perkins + Will Submission No: SD-073-1 General Contractor: Pro-Can Construction Group Date Received By Integral: June 7, 2017 Mechanical Contractor: Keith Plumbing and Heating Co. Date Returned By Integral: June 13, 2017 Re: Pumps Mechanical Shop Drawing Review Comments: General Comments: 1. Various pumps voltage and or HP have been altered from IFC drawings due to alternate equipment. If any panels or wire sizes are required to increase the contractor shall revise at no cost to the owner 2. Mounting style of pumps have been altered due to pump types. Required mounting accessories to be complete with pumps Primary Heating Loop Pumps P-1&2: Reject Revise and resubmit 1. Further coordination between supplier and IG has occurred to ensure correct HP and flowrates have been selected AHU Heating Coils Pumps P-3&4: Reviewed Heating Terminals and Fan coils Pumps P-5&6: Reject Revise and resubmit 1. Further coordination between supplier and IG has occurred to ensure correct HP and flowrates have been selected Chiller Loop Pump P-7: Reviewed Primary Chilled Water Loop Pump P-8: Reviewed AHU and Fan Coil Cooling coils Pump P-9: Reviewed Chilled Water to Terminal Units Pump P-10: Reviewed Domestic Hot Water Return Pump P-11: Reviewed as noted 1. Supplier has noted they are to supply a flow switch with pump to be wired to the VFD and DDC for controllability and status Flowtrex Valve: Not Reviewed, reviewed under previous package Suction Guide: Not Reviewed, reviewed under previous package INTEGRAL GROUP Reviewed for general design and compliance with contract documents. Dimensions and suitability for site conditions are the responsibility of the contractor. This review of the drawing shall not relieve the contractor from complying with the conditions of the contract documents. Mechanical contractor shall coordinate the electrical characteristics and requirements with the Electrical contractor. Reviewed Reviewed as noted Reject-Revise and resubmit Per: Ryan Chora, AScT, LEED Green Associate

Mechanical Shop Drawing Review Form - Pro Can …€¦ · Mechanical Shop Drawing Review Form Page 2 of 2 ... Design envelope close coupled vertical in-line pump ... ANSI/HI 14.6.3.4.1

  • Upload
    lytruc

  • View
    245

  • Download
    1

Embed Size (px)

Citation preview

Mechanical Shop Drawing Review Form

Integral Group | Suite 180 - 200 Granville Street, Vancouver, BC V6C 1S4

+1.604.687.1800 | Integralgroup.com

DATE: June 13, 2017 PROJECT: SFU Student Union Building PROJECT NO: 155501.000

Architect: Perkins + Will Submission No: SD-073-1 General Contractor: Pro-Can Construction Group Date Received By Integral: June 7, 2017 Mechanical Contractor: Keith Plumbing and Heating Co. Date Returned By Integral: June 13, 2017

Re: Pumps – Mechanical Shop Drawing Review

Comments:

General Comments:

1. Various pumps voltage and or HP have been altered from IFC drawings due to alternate equipment. If any panels or wire sizes are required to increase the contractor shall revise at no cost to the owner

2. Mounting style of pumps have been altered due to pump types. Required mounting accessories to be complete with pumps

Primary Heating Loop Pumps P-1&2: Reject – Revise and

resubmit 1. Further coordination between supplier and IG has

occurred to ensure correct HP and flowrates have been selected

AHU Heating Coils Pumps P-3&4: Reviewed

Heating Terminals and Fan coils Pumps P-5&6: Reject – Revise and resubmit

1. Further coordination between supplier and IG has occurred to ensure correct HP and flowrates have been selected Chiller Loop Pump P-7: Reviewed

Primary Chilled Water Loop Pump P-8: Reviewed

AHU and Fan Coil Cooling coils Pump P-9: Reviewed

Chilled Water to Terminal Units Pump P-10: Reviewed

Domestic Hot Water Return Pump P-11: Reviewed as noted

1. Supplier has noted they are to supply a flow switch with pump to be wired to the VFD and DDC for controllability and status

Flowtrex Valve: Not Reviewed, reviewed under previous package Suction Guide: Not Reviewed, reviewed under previous package

INTEGRAL GROUP

Reviewed for general design and compliance with contract

documents. Dimensions and suitability for site conditions are

the responsibility of the contractor. This review of the drawing

shall not relieve the contractor from complying with the

conditions of the contract documents. Mechanical contractor

shall coordinate the electrical characteristics and requirements

with the Electrical contractor.

Reviewed

Reviewed as noted

Reject-Revise and resubmit

Per: Ryan Chora, AScT, LEED Green Associate

Mechanical Shop Drawing Review Form Page 2 of 2

Should you have any concerns, please contact the undersigned.

Regards,

INTEGRAL GROUP

Ryan Chora, AScT, LEED Green Associate Senior Mechanical Designer RYAC/jesb

hsuf
PW-Canada-BC

Submittal Transmittal

Perkins+Will Canada, Inc. | 1220 Homer St. Vancouver BC V6B 2Y5 Canada

Page 1 of 2

PROJECT: DATE SENT: 6/7/2017SFU: Student Union Building411314.000

RETURN BY: 6/14/2017

SUBJECT: SFU SUB- Pump Shop Drawings-Revised

SUBMITTAL ID: SD-073.1

TYPE: Submittal TRANSMITTAL ID: 01081

PURPOSE: For Review VIA: Info Exchange

SPEC SECTION: 22 00 00

FROM

NAME COMPANY EMAIL PHONE

Anna Atkinson Perkins+Will Canada, Inc.

[email protected] 604.484.1067

TO

NAME COMPANY EMAIL PHONE

Chris Doel Integral Group [email protected] 604.484.8575

Harold Kroeker MMM Group [email protected]

604 685 9381 - 4117

REMARKS: Hello, From Pro-Can:Please find attached revised pump shop drawings.

Please review and return by Wednesday, June 14th, 2017. Regards, Anna AtkinsonProject Coordinator 1220 Homer St., Vancouver, BC V6B 2Y5t 604.484.1067 [email protected]

DESCRIPTION OF CONTENTS

Submittal TransmittalDATE: 6/7/2017

ID: 01081

Page 2 of 2

QTY DATED TITLE NUMBER NOTES

1 6/7/2017 SD-073.1-220000-KPH-Pumps.pdf

COPIES:

Ryan Chora (Integral Group) Fang-Chun Hsu (Perkins+Will Canada, Inc.) Elena Kaganova (MMM Group)

Submittal Ref. #: 456329.3 rev3

Design envelope close coupled vertical in-line pump

Model: Series Design Envelope Sensorless 4380 0306-002.0

Project name: CC-14147 SFU Student Union Building

Location: Burnaby, BC Representative: Con-Cur West Marketing Inc.

Date submitted: 4/24/2017 11:31:44 PM Phone number: 604-312-9062

Engineer: Integral Group e-mail: [email protected]

Contractor: Keith Plumbing & Heating Submitted by: Rocco Logozzo

Application design data

Tag number: P-1,2 Pipe orientation: SingleSuction pressure: 0 ftService: Primary Heating Loop

Location: Mechanical Room Fluid: Non-Potable Fluid - Water

Quantity: 2 Operating temperature: 75 CViscosity: 31 SSUDuty flow per pump: 9.09 L/s

Specific gravity: 1.0000Duty head: 67.5 kPa

Safety factor % head: 0 %Environment: Indoors

Total dissolved solids: 0 ppm

Materials of construction

Construction: BF Impeller: Bronze (BS1400 Grade LG1)Rating: ANSI-125 Shaft sleeve: 316 SSConnections: Inlet: 3 in, Outlet: 3 in Casing gasket: Confined Non-Asbestos Fiber

Casing (volute): Cast Iron (BS1452 GR220) Flush line: Braided Stainless Steel

Mechanical seal data

Seal type Inside Single Spring Rotating face: Resin Bonded CarbonManufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon Carbide

Springs: Stainless Steel Secondary seal: EPDM

Rotating hardware: Stainless Steel

Motor electrical data

Factory ChoiceSupplier: Insulation class: Class F InsulationSize: 2 hp Inverter motor type: Inverter DutyFrame number: 145JM Efficiency: NEMA Prem (12.12)Enclosure: TEFC Operating speed @ 100% flow: 1537 rpmMotor Electrics: Operating speed @ 50% flow: 1069 rpm460/3/60

less than

IVS102 controller data

Sensorless control: Yes-Quadratic press control Communication port: RS 485

BMS protocol: BACnet Native Analog inputs: 2 (current or voltage)

UL Type 12Enclosure: Analog outputs: 1 (current)

Fused disconnect switch: No Digital inputs: 4 (programmable)

Control orientation: L1 Digital outputs: 2 (programmable)

Expansion card: None Cooling: Fan cooled through back channelBHP at 50% load/flow and 55% of design head: Ambient temperature: -10C to +45C (up to 1000m elevation)

EMI/RFI control: Integrated filter to meet EN61800-3Min. maintained sys. pressure: Harmonic suppression: Integrated DC link reactor**

*If minimum maintained system pressure is not known, default is 40% of design head.** The IVS 102 control is a low harmonic control with a built-in DC link reactor equivalent in performance to a 5% AC line reactor. This does not guarantee performance to any system wide harmonic specification or the costs to meet a system wide specification. If supplied with the system electrical details, Armstrong will run a computer simulation of the system wide harmonics. If system harmonic levels are exceeded, Armstrong can also recommend additional harmonic mitigation and the cost for such mitigation.

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 1 of 38

Pro-Can
Reviewed
Pro-Can
ProCan Logo

Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 250 F

Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.

Performance curve

--- Admin Data --- Tag Num: P-1,2 Service: Primary Heating Loop Location: Mechanical Room

--- Motor Data --- Motor Size: 2 hp

--- Design Duty Point --- Flow: 9.09 lps Head: 67.5 kpa Impeller: 6.19 in

--- Performance Data --- • NPSHR: 26.4 kpa • Eff. @ Design: 76.41 % • BHP @ Design: 1.08 hp • Mtr Capability @ Rated Spd: 1.69 hp • %Mtr Safety: 57.32% • BEP @ Design Imp.: 76.78 % @ 10.12 lps • %max imp. range: 100.00 % • Outlet Velocity: 6.25 ft/s • VFD Op.Speed: 1537 rpm • VFD Setting: 52.4 Hz

Series 4380Design Envelope: 0306-002.0 @ 52.4 Hz

Integrated Intelligent Variable Speed with Sensorless Control

0 4 8 12 16 200

20

40

60

80

100

Flow (lps)

Head

(kpa)

6.19 in

4.50 in

System

6.19 in

1 hp

2 hp

77

77

74

74

70

70

62

62

52

52%

39

Water, spgr= 1.0000

PT70-4-0 (3.29.0.20)ANSI/HI 14.6.3.4.1

77

--- Admin Data --- Tag Num: P-1,2 Service: Primary Heating Loop Location: Mechanical Room

--- Motor Data --- Motor Size: 2 hp

--- Design Duty Point --- Flow: 9.09 lps Head: 67.5 kpa Impeller: 6.19 in

--- Control Data --- 1. Hmax @ 52.4 Hz: • 9.09 @ 67.5, 1.08 hp 2. Control (QPC) @ 48.1 Hz: • 7.97 @ 58.2, 0.82 hp 3. Control (QPC) @ 44.0 Hz: • 6.86 @ 50.1, 0.61 hp 4. Control (QPC) @ 39.5 Hz: • 5.56 @ 42.2, 0.43 hp 5. Control (QPC) @ 35.5 Hz: • 4.19 @ 35.6, 0.29 hp 6. Index @ 31.2 Hz: • 2.27 @ 29.5, 0.17 hp 7. Hmin: 27 kpa 29.5 Hz: • Setting= 40.00% Hmax

Series 4380Design Envelope: 0306-002.0

Integrated Intelligent Variable Speed with Sensorless Control

0 4 8 12 16 200

20

40

60

80

100

120

140

160

Flow (lps)

Head

(kpa)

62.0 Hz

31.2 Hz

29.5 Hz

18.0 Hz System

Avg.Load (QPC)

52.4 Hz

2 hp

7777

77

74

74

70

70

62

62

52

Index Flow (25.0% Duty Flow)

Water, spgr= 1.0000

PT70-4-0 (3.29.0.20)ANSI/HI 14.6.3.4.1

1

2

3

45

6

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 2 of 38

Design envelope pumping unit capability

Operating point Flow Head Efficiency

9.09 L/sFull capability at 100% design flow 102.3 kpa 74.03 %

Design point 9.09 L/s 67.5 kPa 76.41 %

50% average flow (with default load profile) 4.55 lps 37.1 kpa 70.10 %

Dimensional data (not for construction)

Top viewSide view

Weight: 250 lb• Not to scale • R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports

Connection details

Connection Size Rating OD Bolt quantity* BCD Bolt size

Inlet 3 7.5ANSI-125 4 0.6256

Outlet 3 7.5ANSI-125 4 0.6256

*Equally spaced straddling centreline

Special instructions

The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.

OSHPD Seismic Certification OSP-0422-10UL STD 778 & CSA STD C22.2 no.108 certified

Selected options Environmental Application: Indoors Sensorless Bundle: Sensorless control Constant flow control Constant pressure control Flow readout

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 3 of 38

Submittal Ref. #: 456329.3 rev3

Design envelope close coupled vertical in-line pump

Model: Series Design Envelope Sensorless 4380 0306-002.0

Project name: CC-14147 SFU Student Union Building

Location: Burnaby, BC Representative: Con-Cur West Marketing Inc.

Date submitted: 4/24/2017 11:31:44 PM Phone number: 604-312-9062

Engineer: Integral Group e-mail: [email protected]

Contractor: Keith Plumbing & Heating Submitted by: Rocco Logozzo

Application design data

Tag number: P-3,4 Pipe orientation: SingleSuction pressure: 0 ftService: AHU Heating Coil

Location: Mechanical Room Fluid: Non-Potable Fluid - Water

Quantity: 2 Operating temperature: 75 CViscosity: 31 SSUDuty flow per pump: 7.7 L/s

Specific gravity: 1.0000Duty head: 85 kPa

Safety factor % head: 0 %Environment: Indoors

Total dissolved solids: 0 ppm

Materials of construction

Construction: BF Impeller: Bronze (BS1400 Grade LG1)Rating: ANSI-125 Shaft sleeve: 316 SSConnections: Inlet: 3 in, Outlet: 3 in Casing gasket: Confined Non-Asbestos Fiber

Casing (volute): Cast Iron (BS1452 GR220) Flush line: Braided Stainless Steel

Mechanical seal data

Seal type Inside Single Spring Rotating face: Resin Bonded CarbonManufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon Carbide

Springs: Stainless Steel Secondary seal: EPDM

Rotating hardware: Stainless Steel

Motor electrical data

Factory ChoiceSupplier: Insulation class: Class F InsulationSize: 2 hp Inverter motor type: Inverter DutyFrame number: 145JM Efficiency: NEMA Prem (12.12)Enclosure: TEFC Operating speed @ 100% flow: 1641 rpmMotor Electrics: Operating speed @ 50% flow: 1169 rpm208/3/60

IVS102 controller data

Sensorless control: Yes-Quadratic press control Communication port: RS 485

BMS protocol: BACnet Native Analog inputs: 2 (current or voltage)

UL Type 12Enclosure: Analog outputs: 1 (current)

Fused disconnect switch: No Digital inputs: 4 (programmable)

Control orientation: L1 Digital outputs: 2 (programmable)

Expansion card: None Cooling: Fan cooled through back channelBHP at 50% load/flow and 55% of design head: Ambient temperature: -10C to +45C (up to 1000m elevation)

EMI/RFI control: Integrated filter to meet EN61800-3Min. maintained sys. pressure: Harmonic suppression: Integrated DC link reactor**

*If minimum maintained system pressure is not known, default is 40% of design head.** The IVS 102 control is a low harmonic control with a built-in DC link reactor equivalent in performance to a 5% AC line reactor. This does not guarantee performance to any system wide harmonic specification or the costs to meet a system wide specification. If supplied with the system electrical details, Armstrong will run a computer simulation of the system wide harmonics. If system harmonic levels are exceeded, Armstrong can also recommend additional harmonic mitigation and the cost for such mitigation.

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 5 of 38

Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 250 F

Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.

Performance curve

--- Admin Data --- Tag Num: P-3,4 Service: AHU Heating Coild Location: Mechanical Room

--- Motor Data --- Motor Size: 2 hp

--- Design Duty Point --- Flow: 7.7 lps Head: 85 kpa Impeller: 6.19 in

--- Performance Data --- • NPSHR: 22.6 kpa • Eff. @ Design: 72.67 % • BHP @ Design: 1.21 hp • Mtr Capability @ Rated Spd: 1.78 hp • %Mtr Safety: 47.31% • BEP @ Design Imp.: 76.78 % @ 10.81 lps • %max imp. range: 100.00 % • Outlet Velocity: 5.3 ft/s • VFD Op.Speed: 1641 rpm • VFD Setting: 55.9 Hz

Series 4380Design Envelope: 0306-002.0 @ 55.9 Hz

Integrated Intelligent Variable Speed with Sensorless Control

0 4 8 12 16 200

20

40

60

80

100

120

Flow (lps)

Head

(kpa)

6.19 in

4.50 in

System

6.19 in

1 hp

2 hp

77

77

74

74

70

70

62

62

52

52%

39

Water, spgr= 1.0000

PT70-4-0 (3.29.0.20)ANSI/HI 14.6.3.4.1

77

--- Admin Data --- Tag Num: P-3,4 Service: AHU Heating Coild Location: Mechanical Room

--- Motor Data --- Motor Size: 2 hp

--- Design Duty Point --- Flow: 7.7 lps Head: 85 kpa Impeller: 6.19 in

--- Control Data --- 1. Hmax @ 55.9 Hz: • 7.7 @ 85, 1.21 hp 2. Control (QPC) @ 51.8 Hz: • 6.82 @ 74, 0.95 hp 3. Control (QPC) @ 47.4 Hz: • 5.81 @ 63, 0.71 hp 4. Control (QPC) @ 43.3 Hz: • 4.8 @ 53.8, 0.52 hp 5. Control (QPC) @ 38.9 Hz: • 3.55 @ 44.8, 0.36 hp 6. Index @ 34.7 Hz: • 1.92 @ 37.2, 0.22 hp 7. Hmin: 34 kpa 33.1 Hz: • Setting= 40.00% Hmax

Series 4380Design Envelope: 0306-002.0

Integrated Intelligent Variable Speed with Sensorless Control

0 4 8 12 16 200

20

40

60

80

100

120

140

160

Flow (lps)

Head

(kpa)

62.0 Hz

34.7 Hz

33.1 Hz

18.0 Hz

System

Avg.Load (QPC)

55.9 Hz

2 hp

7777

77

74

74

70

70

62

62

52

Index Flow (25.0% Duty Flow)

Water, spgr= 1.0000

PT70-4-0 (3.29.0.20)ANSI/HI 14.6.3.4.1

1

2

3

4

56

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 6 of 38

Design envelope pumping unit capability

Operating point Flow Head Efficiency

7.7 L/sFull capability at 100% design flow 107.7 kpa 69.96 %

Design point 7.7 L/s 85 kPa 72.67 %

50% average flow (with default load profile) 3.85 lps 46.7 kpa 61.97 %

Dimensional data (not for construction)

Top viewSide view

Weight: 250 lb• Not to scale • R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports

Connection details

Connection Size Rating OD Bolt quantity* BCD Bolt size

Inlet 3 7.5ANSI-125 4 0.6256

Outlet 3 7.5ANSI-125 4 0.6256

*Equally spaced straddling centreline

Special instructions

The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.

OSHPD Seismic Certification OSP-0422-10UL STD 778 & CSA STD C22.2 no.108 certified

Selected options Environmental Application: Indoors Sensorless Bundle: Sensorless control Constant flow control Constant pressure control Flow readout

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 7 of 38

Submittal Ref. #: 456329.3 rev3

Design envelope close coupled vertical in-line pump

Model: Series Design Envelope Sensorless 4380 0208-003.0

Project name: CC-14147 SFU Student Union Building

Location: Burnaby, BC Representative: Con-Cur West Marketing Inc.

Date submitted: 4/24/2017 11:31:44 PM Phone number: 604-312-9062

Engineer: Integral Group e-mail: [email protected]

Contractor: Keith Plumbing & Heating Submitted by: Rocco Logozzo

Application design data

Tag number: P-5,6 Pipe orientation: SingleSuction pressure: 0 ftService: Heating Terminal & Fan Coils

Location: Mechanical Room Fluid: Non-Potable Fluid - Water

Quantity: 2 Operating temperature: 60 CViscosity: 31 SSUDuty flow per pump: 5.82 L/s

Specific gravity: 1.0000Duty head: 165 kPa

Safety factor % head: 0 %Environment: Indoors

Total dissolved solids: 0 ppm

Materials of construction

Construction: BF Impeller: Bronze (BS1400 Grade LG1)Rating: ANSI-125 Shaft sleeve: 316 SSConnections: Inlet: 2 in, Outlet: 2 in Casing gasket: Confined Non-Asbestos Fiber

Casing (volute): Cast Iron (BS1452 GR220) Flush line: Braided Stainless Steel

Mechanical seal data

Seal type Inside Single Spring Rotating face: Resin Bonded CarbonManufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon Carbide

Springs: Stainless Steel Secondary seal: EPDM

Rotating hardware: Stainless Steel

Motor electrical data

Factory ChoiceSupplier: Insulation class: Class F InsulationSize: 3 hp Inverter motor type: Inverter DutyFrame number: 182JM Efficiency: NEMA Prem (12.12)Enclosure: TEFC Operating speed @ 100% flow: 1581 rpmMotor Electrics: Operating speed @ 50% flow: 1147 rpm208/3/60

IVS102 controller data

Sensorless control: Yes-Quadratic press control Communication port: RS 485

BMS protocol: BACnet Native Analog inputs: 2 (current or voltage)

UL Type 12Enclosure: Analog outputs: 1 (current)

Fused disconnect switch: No Digital inputs: 4 (programmable)

Control orientation: L1 Digital outputs: 2 (programmable)

Expansion card: None Cooling: Fan cooled through back channelBHP at 50% load/flow and 55% of design head: Ambient temperature: -10C to +45C (up to 1000m elevation)

EMI/RFI control: Integrated filter to meet EN61800-3Min. maintained sys. pressure: Harmonic suppression: Integrated DC link reactor**

*If minimum maintained system pressure is not known, default is 40% of design head.** The IVS 102 control is a low harmonic control with a built-in DC link reactor equivalent in performance to a 5% AC line reactor. This does not guarantee performance to any system wide harmonic specification or the costs to meet a system wide specification. If supplied with the system electrical details, Armstrong will run a computer simulation of the system wide harmonics. If system harmonic levels are exceeded, Armstrong can also recommend additional harmonic mitigation and the cost for such mitigation.

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 9 of 38

Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 250 F

Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.

Performance curve

--- Admin Data --- Tag Num: P-5,6 Service: Heating Terminal Location: Mechanical Room

--- Motor Data --- Motor Size: 3 hp

--- Design Duty Point --- Flow: 5.82 lps Head: 165 kpa Impeller: 8.19 in

--- Performance Data --- • NPSHR: 12.6 kpa • Eff. @ Design: 62.01 % • BHP @ Design: 2.08 hp • Mtr Capability @ Rated Spd: 2.7 hp • %Mtr Safety: 29.97% • BEP @ Design Imp.: 64.38 % @ 7.96 lps • %max imp. range: 100.00 % • Outlet Velocity: 8.82 ft/s • VFD Op.Speed: 1581 rpm • VFD Setting: 53.7 Hz

Series 4380Design Envelope: 0208-003.0 @ 53.7 Hz

Integrated Intelligent Variable Speed with Sensorless Control

0 2 4 6 8 10 12 14 160

40

80

120

160

200

Flow (lps)

Head

(kpa)

8.19 in

6.00 in

System

8.19 in

1.5 hp

2 hp

3 hp

5 hp

65

65

63

63

59

59

54

54

4534

Water, spgr= 1.0000

PT39-2-0 (3.29.0.20)ANSI/HI 14.6.3.4.1

65

--- Admin Data --- Tag Num: P-5,6 Service: Heating Terminal Location: Mechanical Room

--- Motor Data --- Motor Size: 3 hp

--- Design Duty Point --- Flow: 5.82 lps Head: 165 kpa Impeller: 8.19 in

--- Control Data --- 1. Hmax @ 53.7 Hz: • 5.82 @ 165, 2.08 hp 2. Control (QPC) @ 50.0 Hz: • 5.16 @ 143.8, 1.63 hp 3. Control (QPC) @ 45.9 Hz: • 4.4 @ 122.7, 1.21 hp 4. Control (QPC) @ 42.2 Hz: • 3.65 @ 104.8, 0.89 hp 5. Control (QPC) @ 38.4 Hz: • 2.77 @ 88.4, 0.63 hp 6. Index @ 34.4 Hz: • 1.46 @ 72.2, 0.38 hp 7. Hmin: 66 kpa 32.7 Hz: • Setting= 40.00% Hmax

Series 4380Design Envelope: 0208-003.0

Integrated Intelligent Variable Speed with Sensorless Control

0 2 4 6 8 10 12 14 160

40

80

120

160

200

Flow (lps)

Head

(kpa)

55.6 Hz

34.4 Hz

32.7 Hz

18.0 Hz

System

Avg.Load (QPC)

53.7 Hz

3 hp

6565

65

63

63

59

59

54

54

45 Index Flow (25.0% Duty Flow)

Water, spgr= 1.0000

PT39-2-0 (3.29.0.20)ANSI/HI 14.6.3.4.1

1

2

3

4

5

6

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 10 of 38

Design envelope pumping unit capability

Operating point Flow Head Efficiency

5.82 L/sFull capability at 100% design flow 177.5 kpa 61.44 %

Design point 5.82 L/s 165 kPa 62.01 %

50% average flow (with default load profile) 2.91 lps 90.9 kpa 53.41 %

Dimensional data (not for construction)

Top viewSide view

Weight: 292 lb• Not to scale • R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports

Connection details

Connection Size Rating OD Bolt quantity* BCD Bolt size

Inlet 2 6ANSI-125 4 0.6254.75

Outlet 2 6ANSI-125 4 0.6254.75

*Equally spaced straddling centreline

Special instructions

The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.

OSHPD Seismic Certification OSP-0422-10UL STD 778 & CSA STD C22.2 no.108 certified

Selected options Environmental Application: Indoors Sensorless Bundle: Sensorless control Constant flow control Constant pressure control Flow readout

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 11 of 38

Submittal Ref. #: 456329.3 rev3

Split coupled vertical in line pump

Model: Series 4300-5x5x8-7.5 hp Pump (Motor supplier: Armstrong choice)

Project name: CC-14147 SFU Student Union Building

Location: Burnaby, BC Representative: Con-Cur West Marketing Inc.

Date submitted: 4/24/2017 11:31:44 PM Phone number: 604-312-9062

Engineer: Integral Group e-mail: [email protected]

Contractor: Keith Plumbing & Heating Submitted by: Rocco Logozzo

Application design data

Tag number: P-7 Pipe orientation: SingleSuction pressure: 0 ftService: Dry Cooler Loop

Location: Mechanical Room Fluid: PropyleneGlycol:25

Quantity: 1 Operating temperature: 8 CViscosity: 36.319 SSUDuty flow per pump: 20.4 L/s

Specific gravity: 1.0204Duty head: 175 kPa

Total dissolved solids: 0 ppm

Materials of construction

Construction: BF Impeller: Bronze (B584-844)Rating: ANSI-125 Pump shaft: SS ASTM A276 Type 416Connections: Inlet: 5 in, Outlet: 5 in Flush line: Braided Stainless Steel

Casing (volute): Cast Iron (A48-30) Casing gasket: Confined Non-Asbestos Fiber

Mechanical seal data

Seal type Outside Balanced Rotating face: Resin Bonded CarbonManufacturer code: C-SSC AB2 Stationary seat: Sintered Silicon Carbide

Springs: Stainless Steel Secondary seal: Viton

Rotating hardware: Stainless Steel

Motor electrical data

Factory ChoiceSupplier: Insulation class: Class F InsulationSize: 7.5 hp Inverter motor type: Inverter DutyFrame number: 213TC Efficiency: NEMA Prem (12.12)Enclosure: ODP Speed: 1765 rpmMotor Electrics: 480/3/60

Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 200 F

Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 13 of 38

Performance curve

--- Admin Data --- Tag Num: P-7 Service: Dry Cooler Loop Location: Mechanical Room

--- Motor Data --- Motor Size: 7.5 hp Motor Speed: 1800 rpm

--- Design Duty Point --- Flow: 20.4 lps Head: 175 kpa Impeller: 8.19 in (Optimal)

--- Performance Data --- • NPSHR: 23.2 kpa • Eff. @ Design: 75.09 % • BHP @ Design: 6.38 hp • Mtr Capability @ Rated Spd: 7.5 hp • %Mtr Safety: 17.61% • BEP @ Design Imp.: 76.91 % @ 25.70 lps • Impeller Max BHP @ Flow: 7.24 hp @ 33.58 lps • %Optimization: 43.98 % • Outlet Velocity: 5.19 ft/s • VFD Setting: 60.0 Hz

Series 43005x5x8 (Optimal) @ 1765 rpm

0 8 16 24 32 40 480

50

100

150

200

250

300

Flow (lps)

Head

(kpa)

(Optimal)

6.00 in

System

(Optimal)

2 hp

3 hp

5 hp

7.5 hp

1.5 hp

77

77

75

75

70

70

63

63

5238

PropyleneGlycol:25, spgr= 1.0204

PT95-1-0 (3.29.0.20)ANSI/HI 14.6.3.4.1

77

--- Admin Data --- Tag Num: P-7 Service: Dry Cooler Loop Location: Mechanical Room

--- Motor Data --- Motor Size: 7.5 hp Motor Speed: 1800 rpm

--- Design Duty Point --- Flow: 20.4 lps Head: 175 kpa Impeller: 8.19 in (Optimal)

--- System Intersect Data --- 1. System @ 60.0 Hz: • 20.4 @ 175, 6.38 hp 2. System @ 51.7 Hz: • 17.58 @ 130, 4.08 hp 3. System @ 43.2 Hz: • 14.69 @ 90.8, 2.38 hp 4. System @ 34.7 Hz: • 11.8 @ 58.5, 1.23 hp 5. System @ 26.5 Hz: • 9.02 @ 34.2, 0.55 hp 6. System @ 18.0 Hz: • 6.12 @ 15.8, 0.17 hp

Series 43005x5x8 @ 8.19 in (Optimal)

0 8 16 24 32 40 480

40

80

120

160

200

240

Flow (lps)

Head

(kpa)

1853 rpm

1765 rpm

529 rpm

System

1765 rpm

1.5 hp2 hp3 hp

5 hp

7.5 hp10 hp

77

77

77

75

75

70

70

63

63

52

1520 rpm

1270 rpm

1020 rpm

780 rpm

PropyleneGlycol:25, spgr= 1.0204

PT95-1-0 (3.29.0.20)ANSI/HI 14.6.3.4.1

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 14 of 38

Dimensional data (not for construction)

Top viewSide view

Weight: 453 lb• Not to scale • R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge portsConnection details

Connection Size Rating OD Bolt quantity* BCD Bolt size

Inlet 5 10ANSI-125 8 0.758.5

Outlet 5 10ANSI-125 8 0.758.5

*Equally spaced straddling centreline

Special instructions

Armstrong Motor Specification AES 05007The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.

Selected options Motor Nameplate Voltages (200, 416, 480, 600 volts)

Additional equipment Flotrex: FTV-6FA (570200-480) Suction Guide: SG-65 (516860-025)

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 15 of 38

Submittal Ref. #: 456329.3 rev3

Close coupled vertical in-line pump

Model: Series 4380-4x4x8-5 hp Pump (Motor supplier: Armstrong choice)

Project name: CC-14147 SFU Student Union Building

Location: Burnaby, BC Representative: Con-Cur West Marketing Inc.

Date submitted: 4/24/2017 11:31:44 PM Phone number: 604-312-9062

Engineer: Integral Group e-mail: [email protected]

Contractor: Keith Plumbing & Heating Submitted by: Rocco Logozzo

Application design data

Tag number: P-8 Pipe orientation: SingleSuction pressure: 0 ftService: Primary Chilled Water

Location: Mechanical Room Fluid: Non-Potable Fluid - Water

Quantity: 1 Operating temperature: 10 CViscosity: 31 SSUDuty flow per pump: 18 L/s

Specific gravity: 1.0000Duty head: 110 kPa

Total dissolved solids: 0 ppm

Materials of construction

Construction: BF Impeller: Bronze (B584-844)Rating: ANSI-125 Shaft sleeve: 316 SSConnections: Inlet: 4 in, Outlet: 4 in Casing gasket: Confined Non-Asbestos Fiber

Casing (volute): Cast Iron (A48-30) Flush line: Braided Stainless Steel

Mechanical seal data

Seal type Inside Single Spring Rotating face: Resin Bonded CarbonManufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon Carbide

Springs: Stainless Steel Secondary seal: EPDM

Rotating hardware: Stainless Steel

Motor electrical data

Factory ChoiceSupplier: Insulation class: Class F InsulationSize: 5 hp Inverter motor type: Inverter DutyFrame number: 184JM Efficiency: NEMA Prem (12.12)Enclosure: ODP Speed: 1770 rpmMotor Electrics: 480/3/60

Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 250 F

Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 16 of 38

Performance curve

--- Admin Data --- Tag Num: P-8 Service: Primary Chilled Water Location: Mechanical Room

--- Motor Data --- Motor Size: 5 hp Motor Speed: 1800 rpm

--- Design Duty Point --- Flow: 18 lps Head: 110 kpa Impeller: 6.59 in

--- Performance Data --- • NPSHR: 36.6 kpa • Eff. @ Design: 62.68 % • BHP @ Design: 4.24 hp • Mtr Capability @ Rated Spd: 5 hp • %Mtr Safety: 17.99% • BEP @ Design Imp.: 67.91 % @ 24.22 lps • Impeller Max BHP @ Flow: 5.03 hp @ 35.40 lps • %max imp. range: 26.97 % • Outlet Velocity: 7.19 ft/s • VFD Setting: 60.0 Hz

Series 43804x4x8 @ 1770 rpm

0 10 20 30 40 50 600

40

80

120

160

200

240

Flow (lps)

Head

(kpa)

8.19 in

6.00 in

System

6.59 in

3 hp

5 hp

7.5 hp

10 hp

15 hp

79

79

76

76

72

72

64

64%

53

53%

39

Water, spgr= 1.0000

PT87-3-0 (3.29.0.20)ANSI/HI 14.6.3.4.1

80

--- Admin Data --- Tag Num: P-8 Service: Primary Chilled Water Location: Mechanical Room

--- Motor Data --- Motor Size: 5 hp Motor Speed: 1800 rpm

--- Design Duty Point --- Flow: 18 lps Head: 110 kpa Impeller: 6.59 in

--- System Intersect Data --- 1. System @ 60.0 Hz: • 18 @ 110, 4.24 hp 2. System @ 51.5 Hz: • 15.46 @ 81.2, 2.69 hp 3. System @ 43.4 Hz: • 13.02 @ 57.6, 1.6 hp 4. System @ 34.9 Hz: • 10.48 @ 37.3, 0.84 hp 5. System @ 26.4 Hz: • 7.94 @ 21.4, 0.36 hp 6. System @ 18.0 Hz: • 5.4 @ 9.9124, 0.11 hp

Series 43804x4x8 @ 6.59 in

0 8 16 24 32 40 480

20

40

60

80

100

120

140

160

Flow (lps)

Head

(kpa)

1858 rpm

1770 rpm

531 rpm

System

1770 rpm

1.5 hp2 hp

3 hp

5 hp

7.5 hp

68

67

67

63

63

57

57

49

49

39

1520 rpm

1280 rpm

1030 rpm

780 rpm

Water, spgr= 1.0000

PT87-3-0 (3.29.0.20)ANSI/HI 14.6.3.4.1

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 17 of 38

Dimensional data (not for construction)

Top viewSide view

Weight: 319 lb• Not to scale • R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge portsConnection details

Connection Size Rating OD Bolt quantity* BCD Bolt size

Inlet 4 9ANSI-125 8 0.6257.5

Outlet 4 9ANSI-125 8 0.6257.5

*Equally spaced straddling centreline

Special instructions

The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.

Selected options Motor Nameplate Voltages (200, 416, 480, 600 volts)

Additional equipment Flotrex: FTV-6FA (570200-480) Suction Guide: SG-64 (516860-023)

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 18 of 38

Submittal Ref. #: 456329.3 rev3

Design envelope close coupled vertical in-line pump

Model: Series Design Envelope Sensorless 4380 0306-007.5

Project name: CC-14147 SFU Student Union Building

Location: Burnaby, BC Representative: Con-Cur West Marketing Inc.

Date submitted: 4/24/2017 11:31:44 PM Phone number: 604-312-9062

Engineer: Integral Group e-mail: [email protected]

Contractor: Keith Plumbing & Heating Submitted by: Rocco Logozzo

Application design data

Tag number: P-9 Pipe orientation: SingleSuction pressure: 0 ftService: AHU & FC Cooling

Location: Mechanical Room Fluid: Non-Potable Fluid - Water

Quantity: 1 Operating temperature: 59 FViscosity: 31 SSUDuty flow per pump: 17.5 L/s

Specific gravity: 1.0000Duty head: 165 kPa

Safety factor % head: 0 %Environment: Indoors

Total dissolved solids: 0 ppm

Materials of construction

Construction: BF Impeller: Bronze (BS1400 Grade LG1)Rating: ANSI-125 Shaft sleeve: 316 SSConnections: Inlet: 3 in, Outlet: 3 in Casing gasket: Confined Non-Asbestos Fiber

Casing (volute): Cast Iron (BS1452 GR220) Flush line: Braided Stainless Steel

Mechanical seal data

Seal type Inside Single Spring Rotating face: Resin Bonded CarbonManufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon Carbide

Springs: Stainless Steel Secondary seal: EPDM

Rotating hardware: Stainless Steel

Motor electrical data

Factory ChoiceSupplier: Insulation class: Class F InsulationSize: 7.5 hp Inverter motor type: Inverter DutyFrame number: 213JM Efficiency: NEMA Prem (12.12)Enclosure: TEFC Operating speed @ 100% flow: 3283 rpmMotor Electrics: Operating speed @ 50% flow: 2211 rpm480/3/60

less than

IVS102 controller data

Sensorless control: Yes-Quadratic press control Communication port: RS 485

BMS protocol: BACnet Native Analog inputs: 2 (current or voltage)

UL Type 12Enclosure: Analog outputs: 1 (current)

Fused disconnect switch: No Digital inputs: 4 (programmable)

Control orientation: L1 Digital outputs: 2 (programmable)

Expansion card: None Cooling: Fan cooled through back channelBHP at 50% load/flow and 55% of design head: Ambient temperature: 14F to 113F (up to 3280ft elevation)

EMI/RFI control: Integrated filter to meet EN61800-3Min. maintained sys. pressure: Harmonic suppression: Integrated DC link reactor**

*If minimum maintained system pressure is not known, default is 40% of design head.** The IVS 102 control is a low harmonic control with a built-in DC link reactor equivalent in performance to a 5% AC line reactor. This does not guarantee performance to any system wide harmonic specification or the costs to meet a system wide specification. If supplied with the system electrical details, Armstrong will run a computer simulation of the system wide harmonics. If system harmonic levels are exceeded, Armstrong can also recommend additional harmonic mitigation and the cost for such mitigation.

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 19 of 38

Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 250 F

Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.

Performance curve

--- Admin Data --- Tag Num: P-9 Service: AHU & FC Cooling Location: Mechanical Room

--- Motor Data --- Motor Size: 7.5 hp

--- Design Duty Point --- Flow: 17.5 lps Head: 165 kpa Impeller: 5 in

--- Performance Data --- • NPSHR: 47.3 kpa • Eff. @ Design: 72.16 % • BHP @ Design: 5.37 hp • Mtr Capability @ Rated Spd: 6.6 hp • %Mtr Safety: 23.01% • BEP @ Design Imp.: 72.17 % @ 17.81 lps • %max imp. range: 29.86 % • Outlet Velocity: 12.04 ft/s • VFD Op.Speed: 3283 rpm • VFD Setting: 55.6 Hz

Series 4380Design Envelope: 0306-007.5 @ 55.6 Hz

Integrated Intelligent Variable Speed with Sensorless Control

0 8 16 24 32 400

80

160

240

320

400

480

Flow (lps)

Head

(kpa)

6.19 in

4.50 in

System

5.00 in

7.5 hp

77

77

74

74

70

70

62

62

52

52%

39

Water, spgr= 1.0000

PT71-3-0 (3.29.0.20)ANSI/HI 14.6.3.4.1

77

--- Admin Data --- Tag Num: P-9 Service: AHU & FC Cooling Location: Mechanical Room

--- Motor Data --- Motor Size: 7.5 hp

--- Design Duty Point --- Flow: 17.5 lps Head: 165 kpa Impeller: 5 in

--- Control Data --- 1. Hmax @ 55.6 Hz: • 17.5 @ 165, 5.37 hp 2. Control (QPC) @ 50.8 Hz: • 15.39 @ 142.5, 4.08 hp 3. Control (QPC) @ 45.9 Hz: • 13.12 @ 121.6, 2.98 hp 4. Control (QPC) @ 41.0 Hz: • 10.68 @ 102.9, 2.09 hp 5. Control (QPC) @ 36.1 Hz: • 7.94 @ 86.4, 1.37 hp 6. Index @ 31.2 Hz: • 4.38 @ 72.2, 0.8 hp 7. Hmin: 66 kpa 28.7 Hz: • Setting= 40.00% Hmax

Series 4380Design Envelope: 0306-007.5

Integrated Intelligent Variable Speed with Sensorless Control

0 4 8 12 16 20 24 28 320

40

80

120

160

200

240

280

320

Flow (lps)

Head

(kpa)

60.5 Hz

31.2 Hz

28.7 Hz

18.0 Hz System

Avg.Load (QPC)

55.6 Hz

7.5 hp

73

72

72

70

70

65

65

58

58

48

Index Flow (25.0% Duty Flow)

Water, spgr= 1.0000

PT71-3-0 (3.29.0.20)ANSI/HI 14.6.3.4.1

1

2

3

4

56

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 20 of 38

Design envelope pumping unit capability

Operating point Flow Head Efficiency

17.5 L/sFull capability at 100% design flow 209.1 kpa 71.84 %

Design point 17.5 L/s 165 kPa 72.16 %

50% average flow (with default load profile) 8.75 lps 90.8 kpa 68.63 %

Dimensional data (not for construction)

Top viewSide view

Weight: 328 lb• Not to scale • R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports

Connection details

Connection Size Rating OD Bolt quantity* BCD Bolt size

Inlet 3 7.5ANSI-125 4 0.6256

Outlet 3 7.5ANSI-125 4 0.6256

*Equally spaced straddling centreline

Special instructions

The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.

OSHPD Seismic Certification OSP-0422-10UL STD 778 & CSA STD C22.2 no.108 certified

Selected options Motor Nameplate Voltages (200, 416, 480, 600 volts) Environmental Application: Indoors Sensorless Bundle: Sensorless control Constant flow control Constant pressure control Flow readout

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 21 of 38

Submittal Ref. #: 456329.3 rev3

Design envelope close coupled vertical in-line pump

Model: Series Design Envelope Sensorless 4380 0208-003.0

Project name: CC-14147 SFU Student Union Building

Location: Burnaby, BC Representative: Con-Cur West Marketing Inc.

Date submitted: 4/24/2017 11:31:44 PM Phone number: 604-312-9062

Engineer: Integral Group e-mail: [email protected]

Contractor: Keith Plumbing & Heating Submitted by: Rocco Logozzo

Application design data

Tag number: P-10 Pipe orientation: SingleSuction pressure: 0 ftService: CHW to Terminal Units

Location: Mechanical Fluid: Non-Potable Fluid - Water

Quantity: 1 Operating temperature: 15 CViscosity: 31 SSUDuty flow per pump: 6.27 L/s

Specific gravity: 1.0000Duty head: 150 kPa

Safety factor % head: 0 %Environment: Indoors

Total dissolved solids: 0 ppm

Materials of construction

Construction: BF Impeller: Bronze (BS1400 Grade LG1)Rating: ANSI-125 Shaft sleeve: 316 SSConnections: Inlet: 2 in, Outlet: 2 in Casing gasket: Confined Non-Asbestos Fiber

Casing (volute): Cast Iron (BS1452 GR220) Flush line: Braided Stainless Steel

Mechanical seal data

Seal type Inside Single Spring Rotating face: Resin Bonded CarbonManufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon Carbide

Springs: Stainless Steel Secondary seal: EPDM

Rotating hardware: Stainless Steel

Motor electrical data

Factory ChoiceSupplier: Insulation class: Class F InsulationSize: 3 hp Inverter motor type: Inverter DutyFrame number: 182JM Efficiency: NEMA Prem (12.12)Enclosure: TEFC Operating speed @ 100% flow: 1527 rpmMotor Electrics: Operating speed @ 50% flow: 1099 rpm208/3/60

IVS102 controller data

Sensorless control: Yes-Quadratic press control Communication port: RS 485

BMS protocol: BACnet Native Analog inputs: 2 (current or voltage)

UL Type 12Enclosure: Analog outputs: 1 (current)

Fused disconnect switch: No Digital inputs: 4 (programmable)

Control orientation: L1 Digital outputs: 2 (programmable)

Expansion card: None Cooling: Fan cooled through back channelBHP at 50% load/flow and 55% of design head: Ambient temperature: -10C to +45C (up to 1000m elevation)

EMI/RFI control: Integrated filter to meet EN61800-3Min. maintained sys. pressure: Harmonic suppression: Integrated DC link reactor**

*If minimum maintained system pressure is not known, default is 40% of design head.** The IVS 102 control is a low harmonic control with a built-in DC link reactor equivalent in performance to a 5% AC line reactor. This does not guarantee performance to any system wide harmonic specification or the costs to meet a system wide specification. If supplied with the system electrical details, Armstrong will run a computer simulation of the system wide harmonics. If system harmonic levels are exceeded, Armstrong can also recommend additional harmonic mitigation and the cost for such mitigation.

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 23 of 38

Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 250 F

Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.

Performance curve

--- Admin Data --- Tag Num: P-10 Service: CHW to Terminal Units Location: Mechanical

--- Motor Data --- Motor Size: 3 hp

--- Design Duty Point --- Flow: 6.27 lps Head: 150 kpa Impeller: 8.19 in

--- Performance Data --- • NPSHR: 13.2 kpa • Eff. @ Design: 63.46 % • BHP @ Design: 1.99 hp • Mtr Capability @ Rated Spd: 2.63 hp • %Mtr Safety: 32.28% • BEP @ Design Imp.: 64.38 % @ 7.69 lps • %max imp. range: 100.00 % • Outlet Velocity: 9.5 ft/s • VFD Op.Speed: 1527 rpm • VFD Setting: 51.9 Hz

Series 4380Design Envelope: 0208-003.0 @ 51.9 Hz

Integrated Intelligent Variable Speed with Sensorless Control

0 2 4 6 8 10 12 14 160

40

80

120

160

200

Flow (lps)

Head

(kpa)

8.19 in

6.00 in

System

8.19 in

1.5 hp

2 hp

3 hp

5 hp

65

65

63

63

59

59

54

54

4534

Water, spgr= 1.0000

PT39-2-0 (3.29.0.20)ANSI/HI 14.6.3.4.1

65

--- Admin Data --- Tag Num: P-10 Service: CHW to Terminal Units Location: Mechanical

--- Motor Data --- Motor Size: 3 hp

--- Design Duty Point --- Flow: 6.27 lps Head: 150 kpa Impeller: 8.19 in

--- Control Data --- 1. Hmax @ 51.9 Hz: • 6.27 @ 150, 1.99 hp 2. Control (QPC) @ 48.3 Hz: • 5.58 @ 131.3, 1.56 hp 3. Control (QPC) @ 44.2 Hz: • 4.75 @ 111.7, 1.15 hp 4. Control (QPC) @ 40.5 Hz: • 3.92 @ 95.2, 0.84 hp 5. Control (QPC) @ 36.7 Hz: • 2.96 @ 80.1, 0.57 hp 6. Index @ 32.8 Hz: • 1.57 @ 65.6, 0.34 hp 7. Hmin: 60 kpa 31.2 Hz: • Setting= 40.00% Hmax

Series 4380Design Envelope: 0208-003.0

Integrated Intelligent Variable Speed with Sensorless Control

0 2 4 6 8 10 12 14 160

40

80

120

160

200

Flow (lps)

Head

(kpa)

55.6 Hz

32.8 Hz

31.2 Hz

18.0 Hz

System

Avg.Load (QPC)

51.9 Hz

3 hp

6565

65

63

63

59

59

54

54

45 Index Flow (25.0% Duty Flow)

Water, spgr= 1.0000

PT39-2-0 (3.29.0.20)ANSI/HI 14.6.3.4.1

1

2

3

4

5

6

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 24 of 38

Design envelope pumping unit capability

Operating point Flow Head Efficiency

6.27 L/sFull capability at 100% design flow 174.9 kpa 62.63 %

Design point 6.27 L/s 150 kPa 63.46 %

50% average flow (with default load profile) 3.13 lps 82.6 kpa 56.55 %

Dimensional data (not for construction)

Top viewSide view

Weight: 292 lb• Not to scale • R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports

Connection details

Connection Size Rating OD Bolt quantity* BCD Bolt size

Inlet 2 6ANSI-125 4 0.6254.75

Outlet 2 6ANSI-125 4 0.6254.75

*Equally spaced straddling centreline

Special instructions

The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.

OSHPD Seismic Certification OSP-0422-10UL STD 778 & CSA STD C22.2 no.108 certified

Selected options Environmental Application: Indoors Sensorless Bundle: Sensorless control Constant flow control Constant pressure control Flow readout

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 25 of 38

Submittal Ref. #: 456329.3 rev3

Wet rotor circulator

Model: Part number: 110223-321Series ASTRO 280SS FLG

Project name: CC-14147 SFU Student Union Building

Location: Burnaby, BC Representative: Con-Cur West Marketing Inc.

Date submitted: 4/24/2017 11:31:44 PM Phone number: 604-312-9062

Engineer: Integral Group e-mail: [email protected]

Contractor: Keith Plumbing & Heating Submitted by: Rocco Logozzo

Application design data

Tag number: P-11 Pipe orientation: SingleSuction pressure: 0 ftService: DHWR

Location: Mechanical Room Fluid: Water:

Quantity: 1 Operating temperature: 60 F*Viscosity: 31 SSUDuty flow per pump: 1 L/s

Specific gravity: 1.0000Duty head: 35 kPa

Total dissolved solids: 0 ppm

* for open systems, it is recommended that the fluid temperature be less than 150F (66C) to avoid precipitation of calcium.

Materials of construction

Construction: SS150 Impeller: Polyether Imide (PEI)

Connections: Inlet: 1.25 in, Outlet: 1.25 in Bearings: Ceramic

Connection type: NPSM union Certified standard: UL 778 & CSA C22.2 No. 108-01

Companion flange: Bronze 1 1/2" Listing: ETL listed for US and Canada

**certified <0.25 weighted average percent lead and complies with Californai Health and Safety Code section 114875 (commonly known as AB1953)

Motor electrical data

Factory ChoiceSupplier: Insulation class: Not applicableSize: 0.333 hp Inverter motor type: Not applicableFrame number: Not applicable Efficiency: StdEnclosure: ODP Speed: 2900 rpmMotor Electrics: 115/1/60

Operating limits (temperature - pressure)

Maximum pressure: 150 psi

Maximum temperature: 230 F

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 27 of 38

Performance curve

--- Admin Data --- Tag Num: P-11 Service: DHWR Location: Mechanical Room

--- Motor Data --- Motor Size: 0.333 hp Motor Speed: [2] 2900 rpm

--- Design Duty Point --- Flow: 1 lps Head: 35 kpa

--- Pump Data --- Pump Size: Astro 280SS Impeller: 2.95 in Suction Head Req: 0 kpa Projected Flow: 1.04 lps Projected Head: 38 kpa

Series Astro MultiSpeedAstro 280SS @ Discrete Speeds

0 0.4 0.8 1.2 1.6 20

20

40

60

80

100

Flow (lps)

Head

(kpa)

System

Projected

[1] 2300

[2] 2900 [3] 3600

Water:, spgr= 1.0000

PT625-0-231 (3.29.0.20)

Dimensional data (not for construction)

Top viewSide view

Weight: 11 lb• Not to scale• Units of measure : inches [millimeters]• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 28 of 38

Submittal Ref. #: 456329.3 rev3

Flo-trex valveModel: FTV-F (2.5 to 12 inch)

Project name: CC-14147 SFU Student Union Building

Location: Burnaby, BC Representative: Con-Cur West Marketing Inc.

Date submitted: 4/24/2017 11:31:44 PM Phone number: 604-312-9062

Engineer: Integral Group e-mail: [email protected]

Contractor: Keith Plumbing & Heating Submitted by: Rocco Logozzo

Application design data

DesignflowrateTag Qty Model Size Config Flange rating Pressure

Drop* Associated pump

P-8 1 FTV-6FA 6 in Angle Flanged

ANSI-125 17.9 L/s 2.8 ft P-8 4380-4x4x8-5 hp Pump (Factory Choice Motor)

P-9 1 FTV-4FA 4 in Angle Flanged

ANSI-125 17.4 L/s 3.4 ft P-9 Design Envelope Sensorless 4380 0306-007.5

P-1,2 2 FTV-4FA 4 in Angle Flanged

ANSI-125 9.0 L/s 2.8 ft P-1,2 Design Envelope Sensorless 4380 0306-002.0

P-3,4 2 FTV-3FA 3 in Angle Flanged

ANSI-125 7.6 L/s 3.0 ft P-3,4 Design Envelope Sensorless 4380 0306-002.0

P-5,6 2 FTV-3FA 3 in Angle Flanged

ANSI-125 5.8 L/s 3.0 ft P-5,6 Design Envelope Sensorless 4380 0208-003.0

P-7 1 FTV-6FA 6 in Angle Flanged

ANSI-125 20.2 L/s 2.8 ft P-7 4300-5x5x8-7.5 hp Pump (Factory Choice Motor)

P-10 1 FTV-3FA 3 in Angle Flanged

ANSI-125 6.2 L/s 3.0 ft P-10 Design Envelope Sensorless 4380 0208-003.0

*at design flow

Materials of construction

FTV-3FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12

Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302

Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:Seat: EPDM 2 metering ports: Brass Body with EPDM Check and

Gasketed Cap

Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug

FTV-6FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12

Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302

Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:Seat: EPDM 2 metering ports: Brass Body with EPDM Check and

Gasketed Cap

Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug

FTV-6FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12

Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302

Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:Seat: EPDM 2 metering ports: Brass Body with EPDM Check and

Gasketed Cap

Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 30 of 38

FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12

Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302

Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:Seat: EPDM 2 metering ports: Brass Body with EPDM Check and

Gasketed Cap

Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug

FTV-3FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12

Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302

Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:Seat: EPDM 2 metering ports: Brass Body with EPDM Check and

Gasketed Cap

Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug

FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12

Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302

Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:Seat: EPDM 2 metering ports: Brass Body with EPDM Check and

Gasketed Cap

Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug

FTV-3FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12

Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302

Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:Seat: EPDM 2 metering ports: Brass Body with EPDM Check and

Gasketed Cap

Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug

Operating limits (temperature - pressure)

FTV-3FA-Flo-Trex Valve-ANSI-125-Angle Flanged

Maximum pressure: 175 psi

Maximum temperature: 230 F

Dimensional data (not for construction)

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 31 of 38

Model: FTV-3FA-Flo-Trex Valve-ANSI-125-Angle Flanged Weight: 39 lb

Side view Front view

Model: FTV-6FA-Flo-Trex Valve-ANSI-125-Angle Flanged Weight: 167 lb

Side view Front view

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 32 of 38

Model: FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged Weight: 59 lb

Side view Front view

Not to scale Units of measure: inches [millimeters]Tolerance of +/- 0.125 inch (+/- 3 mm) should be used For certified dimensions, please contact your Armstrong representative

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 33 of 38

Submittal Ref. #: 456329.3 rev3

Suction guideModel: SG (2 to 12 inches)

Project name: CC-14147 SFU Student Union Building

Location: Burnaby, BC Representative: Con-Cur West Marketing Inc.

Date submitted: 4/24/2017 11:31:44 PM Phone number: 604-312-9062

Engineer: Integral Group e-mail: [email protected]

Contractor: Keith Plumbing & Heating Submitted by: Rocco Logozzo

Application design data

Design flowrateTag Qty Model System Pump Pressure

Drop* Associated pump

P-3,4 2 SG-33 3 in 3 in 7.6 L/s 0.6 ft P-3,4 Design Envelope Sensorless 4380 0306-002.0

P-5,6 2 SG-32 3 in 2 in 5.8 L/s 0.9 ft P-5,6 Design Envelope Sensorless 4380 0208-003.0

P-7 1 SG-65 6 in 5 in 20.2 L/s 0.7 ft P-7 4300-5x5x8-7.5 hp Pump (Factory Choice Motor)

P-8 1 SG-64 6 in 4 in 17.9 L/s 1.0 ft P-8 4380-4x4x8-5 hp Pump (Factory Choice Motor)

P-9 1 SG-43 4 in 3 in 17.4 L/s 3.2 ft P-9 Design Envelope Sensorless 4380 0306-007.5

P-10 1 SG-32 3 in 2 in 6.2 L/s 1.1 ft P-10 Design Envelope Sensorless 4380 0208-003.0

P-1,2 2 SG-43 4 in 3 in 9.0 L/s 0.9 ft P-1,2 Design Envelope Sensorless 4380 0306-002.0

*at design flow

Materials of construction

SG-33Body: Cast Iron Cover gasket: Synthetic fiber

Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.

Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel

SG-43

Body: Cast Iron Cover gasket: Synthetic fiber

Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.

Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel

SG-32Body: Cast Iron Cover gasket: Synthetic fiber

Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.

Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel

SG-65Body: Cast Iron Cover gasket: Synthetic fiber

Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.

Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel

SG-64Body: Cast Iron Cover gasket: Synthetic fiber

Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.

Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 34 of 38

SG-43Body: Cast Iron Cover gasket: Synthetic fiber

Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.

Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel

SG-32Body: Cast Iron Cover gasket: Synthetic fiber

Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.

Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel

*Remove start up strainer after 24 hours

Operating limits (temperature - pressure)

SG-33-Suction Guide-ANSI-125

Maximum pressure: 175 psi

Maximum temperature: 230 F

Units are hydrostatically tested to 150% of maximum working pressure

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 35 of 38

Dimensional data (not for construction)

SG-33 Weight: 45 lb

Side view Top view

SG-43 Weight: 52 lb

Side view Top view

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 36 of 38

SG-32 Weight: 31 lb

Side view Top view

SG-65 Weight: 103 lb

Side view Top view

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 37 of 38

SG-64 Weight: 85 lb

Side view Top view

Not to scaleUnits of measure: inches [millimeters]Tolerance of +/- 0.125 inch (+/- 3 mm) should be usedFor certified dimensions, please contact your Armstrong representative

www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 38 of 38