Mechanical Shop Drawing Review Form
Integral Group | Suite 180 - 200 Granville Street, Vancouver, BC V6C 1S4
+1.604.687.1800 | Integralgroup.com
DATE: June 13, 2017 PROJECT: SFU Student Union Building PROJECT NO: 155501.000
Architect: Perkins + Will Submission No: SD-073-1 General Contractor: Pro-Can Construction Group Date Received By Integral: June 7, 2017 Mechanical Contractor: Keith Plumbing and Heating Co. Date Returned By Integral: June 13, 2017
Re: Pumps – Mechanical Shop Drawing Review
Comments:
General Comments:
1. Various pumps voltage and or HP have been altered from IFC drawings due to alternate equipment. If any panels or wire sizes are required to increase the contractor shall revise at no cost to the owner
2. Mounting style of pumps have been altered due to pump types. Required mounting accessories to be complete with pumps
Primary Heating Loop Pumps P-1&2: Reject – Revise and
resubmit 1. Further coordination between supplier and IG has
occurred to ensure correct HP and flowrates have been selected
AHU Heating Coils Pumps P-3&4: Reviewed
Heating Terminals and Fan coils Pumps P-5&6: Reject – Revise and resubmit
1. Further coordination between supplier and IG has occurred to ensure correct HP and flowrates have been selected Chiller Loop Pump P-7: Reviewed
Primary Chilled Water Loop Pump P-8: Reviewed
AHU and Fan Coil Cooling coils Pump P-9: Reviewed
Chilled Water to Terminal Units Pump P-10: Reviewed
Domestic Hot Water Return Pump P-11: Reviewed as noted
1. Supplier has noted they are to supply a flow switch with pump to be wired to the VFD and DDC for controllability and status
Flowtrex Valve: Not Reviewed, reviewed under previous package Suction Guide: Not Reviewed, reviewed under previous package
INTEGRAL GROUP
Reviewed for general design and compliance with contract
documents. Dimensions and suitability for site conditions are
the responsibility of the contractor. This review of the drawing
shall not relieve the contractor from complying with the
conditions of the contract documents. Mechanical contractor
shall coordinate the electrical characteristics and requirements
with the Electrical contractor.
Reviewed
Reviewed as noted
Reject-Revise and resubmit
Per: Ryan Chora, AScT, LEED Green Associate
Mechanical Shop Drawing Review Form Page 2 of 2
Should you have any concerns, please contact the undersigned.
Regards,
INTEGRAL GROUP
Ryan Chora, AScT, LEED Green Associate Senior Mechanical Designer RYAC/jesb
Submittal Transmittal
Perkins+Will Canada, Inc. | 1220 Homer St. Vancouver BC V6B 2Y5 Canada
Page 1 of 2
PROJECT: DATE SENT: 6/7/2017SFU: Student Union Building411314.000
RETURN BY: 6/14/2017
SUBJECT: SFU SUB- Pump Shop Drawings-Revised
SUBMITTAL ID: SD-073.1
TYPE: Submittal TRANSMITTAL ID: 01081
PURPOSE: For Review VIA: Info Exchange
SPEC SECTION: 22 00 00
FROM
NAME COMPANY EMAIL PHONE
Anna Atkinson Perkins+Will Canada, Inc.
[email protected] 604.484.1067
TO
NAME COMPANY EMAIL PHONE
Chris Doel Integral Group [email protected] 604.484.8575
Harold Kroeker MMM Group [email protected]
604 685 9381 - 4117
REMARKS: Hello, From Pro-Can:Please find attached revised pump shop drawings.
Please review and return by Wednesday, June 14th, 2017. Regards, Anna AtkinsonProject Coordinator 1220 Homer St., Vancouver, BC V6B 2Y5t 604.484.1067 [email protected]
DESCRIPTION OF CONTENTS
Submittal TransmittalDATE: 6/7/2017
ID: 01081
Page 2 of 2
QTY DATED TITLE NUMBER NOTES
1 6/7/2017 SD-073.1-220000-KPH-Pumps.pdf
COPIES:
Ryan Chora (Integral Group) Fang-Chun Hsu (Perkins+Will Canada, Inc.) Elena Kaganova (MMM Group)
Submittal Ref. #: 456329.3 rev3
Design envelope close coupled vertical in-line pump
Model: Series Design Envelope Sensorless 4380 0306-002.0
Project name: CC-14147 SFU Student Union Building
Location: Burnaby, BC Representative: Con-Cur West Marketing Inc.
Date submitted: 4/24/2017 11:31:44 PM Phone number: 604-312-9062
Engineer: Integral Group e-mail: [email protected]
Contractor: Keith Plumbing & Heating Submitted by: Rocco Logozzo
Application design data
Tag number: P-1,2 Pipe orientation: SingleSuction pressure: 0 ftService: Primary Heating Loop
Location: Mechanical Room Fluid: Non-Potable Fluid - Water
Quantity: 2 Operating temperature: 75 CViscosity: 31 SSUDuty flow per pump: 9.09 L/s
Specific gravity: 1.0000Duty head: 67.5 kPa
Safety factor % head: 0 %Environment: Indoors
Total dissolved solids: 0 ppm
Materials of construction
Construction: BF Impeller: Bronze (BS1400 Grade LG1)Rating: ANSI-125 Shaft sleeve: 316 SSConnections: Inlet: 3 in, Outlet: 3 in Casing gasket: Confined Non-Asbestos Fiber
Casing (volute): Cast Iron (BS1452 GR220) Flush line: Braided Stainless Steel
Mechanical seal data
Seal type Inside Single Spring Rotating face: Resin Bonded CarbonManufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon Carbide
Springs: Stainless Steel Secondary seal: EPDM
Rotating hardware: Stainless Steel
Motor electrical data
Factory ChoiceSupplier: Insulation class: Class F InsulationSize: 2 hp Inverter motor type: Inverter DutyFrame number: 145JM Efficiency: NEMA Prem (12.12)Enclosure: TEFC Operating speed @ 100% flow: 1537 rpmMotor Electrics: Operating speed @ 50% flow: 1069 rpm460/3/60
less than
IVS102 controller data
Sensorless control: Yes-Quadratic press control Communication port: RS 485
BMS protocol: BACnet Native Analog inputs: 2 (current or voltage)
UL Type 12Enclosure: Analog outputs: 1 (current)
Fused disconnect switch: No Digital inputs: 4 (programmable)
Control orientation: L1 Digital outputs: 2 (programmable)
Expansion card: None Cooling: Fan cooled through back channelBHP at 50% load/flow and 55% of design head: Ambient temperature: -10C to +45C (up to 1000m elevation)
EMI/RFI control: Integrated filter to meet EN61800-3Min. maintained sys. pressure: Harmonic suppression: Integrated DC link reactor**
*If minimum maintained system pressure is not known, default is 40% of design head.** The IVS 102 control is a low harmonic control with a built-in DC link reactor equivalent in performance to a 5% AC line reactor. This does not guarantee performance to any system wide harmonic specification or the costs to meet a system wide specification. If supplied with the system electrical details, Armstrong will run a computer simulation of the system wide harmonics. If system harmonic levels are exceeded, Armstrong can also recommend additional harmonic mitigation and the cost for such mitigation.
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 1 of 38
Operating limits (temperature - pressure)
Maximum pressure: 175 psi
Maximum temperature: 250 F
Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.
Performance curve
--- Admin Data --- Tag Num: P-1,2 Service: Primary Heating Loop Location: Mechanical Room
--- Motor Data --- Motor Size: 2 hp
--- Design Duty Point --- Flow: 9.09 lps Head: 67.5 kpa Impeller: 6.19 in
--- Performance Data --- • NPSHR: 26.4 kpa • Eff. @ Design: 76.41 % • BHP @ Design: 1.08 hp • Mtr Capability @ Rated Spd: 1.69 hp • %Mtr Safety: 57.32% • BEP @ Design Imp.: 76.78 % @ 10.12 lps • %max imp. range: 100.00 % • Outlet Velocity: 6.25 ft/s • VFD Op.Speed: 1537 rpm • VFD Setting: 52.4 Hz
Series 4380Design Envelope: 0306-002.0 @ 52.4 Hz
Integrated Intelligent Variable Speed with Sensorless Control
0 4 8 12 16 200
20
40
60
80
100
Flow (lps)
Head
(kpa)
6.19 in
4.50 in
System
6.19 in
1 hp
2 hp
77
77
74
74
70
70
62
62
52
52%
39
Water, spgr= 1.0000
PT70-4-0 (3.29.0.20)ANSI/HI 14.6.3.4.1
77
--- Admin Data --- Tag Num: P-1,2 Service: Primary Heating Loop Location: Mechanical Room
--- Motor Data --- Motor Size: 2 hp
--- Design Duty Point --- Flow: 9.09 lps Head: 67.5 kpa Impeller: 6.19 in
--- Control Data --- 1. Hmax @ 52.4 Hz: • 9.09 @ 67.5, 1.08 hp 2. Control (QPC) @ 48.1 Hz: • 7.97 @ 58.2, 0.82 hp 3. Control (QPC) @ 44.0 Hz: • 6.86 @ 50.1, 0.61 hp 4. Control (QPC) @ 39.5 Hz: • 5.56 @ 42.2, 0.43 hp 5. Control (QPC) @ 35.5 Hz: • 4.19 @ 35.6, 0.29 hp 6. Index @ 31.2 Hz: • 2.27 @ 29.5, 0.17 hp 7. Hmin: 27 kpa 29.5 Hz: • Setting= 40.00% Hmax
Series 4380Design Envelope: 0306-002.0
Integrated Intelligent Variable Speed with Sensorless Control
0 4 8 12 16 200
20
40
60
80
100
120
140
160
Flow (lps)
Head
(kpa)
62.0 Hz
31.2 Hz
29.5 Hz
18.0 Hz System
Avg.Load (QPC)
52.4 Hz
2 hp
7777
77
74
74
70
70
62
62
52
Index Flow (25.0% Duty Flow)
Water, spgr= 1.0000
PT70-4-0 (3.29.0.20)ANSI/HI 14.6.3.4.1
1
2
3
45
6
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 2 of 38
Design envelope pumping unit capability
Operating point Flow Head Efficiency
9.09 L/sFull capability at 100% design flow 102.3 kpa 74.03 %
Design point 9.09 L/s 67.5 kPa 76.41 %
50% average flow (with default load profile) 4.55 lps 37.1 kpa 70.10 %
Dimensional data (not for construction)
Top viewSide view
Weight: 250 lb• Not to scale • R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 3 7.5ANSI-125 4 0.6256
Outlet 3 7.5ANSI-125 4 0.6256
*Equally spaced straddling centreline
Special instructions
The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.
OSHPD Seismic Certification OSP-0422-10UL STD 778 & CSA STD C22.2 no.108 certified
Selected options Environmental Application: Indoors Sensorless Bundle: Sensorless control Constant flow control Constant pressure control Flow readout
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 3 of 38
Submittal Ref. #: 456329.3 rev3
Design envelope close coupled vertical in-line pump
Model: Series Design Envelope Sensorless 4380 0306-002.0
Project name: CC-14147 SFU Student Union Building
Location: Burnaby, BC Representative: Con-Cur West Marketing Inc.
Date submitted: 4/24/2017 11:31:44 PM Phone number: 604-312-9062
Engineer: Integral Group e-mail: [email protected]
Contractor: Keith Plumbing & Heating Submitted by: Rocco Logozzo
Application design data
Tag number: P-3,4 Pipe orientation: SingleSuction pressure: 0 ftService: AHU Heating Coil
Location: Mechanical Room Fluid: Non-Potable Fluid - Water
Quantity: 2 Operating temperature: 75 CViscosity: 31 SSUDuty flow per pump: 7.7 L/s
Specific gravity: 1.0000Duty head: 85 kPa
Safety factor % head: 0 %Environment: Indoors
Total dissolved solids: 0 ppm
Materials of construction
Construction: BF Impeller: Bronze (BS1400 Grade LG1)Rating: ANSI-125 Shaft sleeve: 316 SSConnections: Inlet: 3 in, Outlet: 3 in Casing gasket: Confined Non-Asbestos Fiber
Casing (volute): Cast Iron (BS1452 GR220) Flush line: Braided Stainless Steel
Mechanical seal data
Seal type Inside Single Spring Rotating face: Resin Bonded CarbonManufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon Carbide
Springs: Stainless Steel Secondary seal: EPDM
Rotating hardware: Stainless Steel
Motor electrical data
Factory ChoiceSupplier: Insulation class: Class F InsulationSize: 2 hp Inverter motor type: Inverter DutyFrame number: 145JM Efficiency: NEMA Prem (12.12)Enclosure: TEFC Operating speed @ 100% flow: 1641 rpmMotor Electrics: Operating speed @ 50% flow: 1169 rpm208/3/60
IVS102 controller data
Sensorless control: Yes-Quadratic press control Communication port: RS 485
BMS protocol: BACnet Native Analog inputs: 2 (current or voltage)
UL Type 12Enclosure: Analog outputs: 1 (current)
Fused disconnect switch: No Digital inputs: 4 (programmable)
Control orientation: L1 Digital outputs: 2 (programmable)
Expansion card: None Cooling: Fan cooled through back channelBHP at 50% load/flow and 55% of design head: Ambient temperature: -10C to +45C (up to 1000m elevation)
EMI/RFI control: Integrated filter to meet EN61800-3Min. maintained sys. pressure: Harmonic suppression: Integrated DC link reactor**
*If minimum maintained system pressure is not known, default is 40% of design head.** The IVS 102 control is a low harmonic control with a built-in DC link reactor equivalent in performance to a 5% AC line reactor. This does not guarantee performance to any system wide harmonic specification or the costs to meet a system wide specification. If supplied with the system electrical details, Armstrong will run a computer simulation of the system wide harmonics. If system harmonic levels are exceeded, Armstrong can also recommend additional harmonic mitigation and the cost for such mitigation.
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 5 of 38
Operating limits (temperature - pressure)
Maximum pressure: 175 psi
Maximum temperature: 250 F
Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.
Performance curve
--- Admin Data --- Tag Num: P-3,4 Service: AHU Heating Coild Location: Mechanical Room
--- Motor Data --- Motor Size: 2 hp
--- Design Duty Point --- Flow: 7.7 lps Head: 85 kpa Impeller: 6.19 in
--- Performance Data --- • NPSHR: 22.6 kpa • Eff. @ Design: 72.67 % • BHP @ Design: 1.21 hp • Mtr Capability @ Rated Spd: 1.78 hp • %Mtr Safety: 47.31% • BEP @ Design Imp.: 76.78 % @ 10.81 lps • %max imp. range: 100.00 % • Outlet Velocity: 5.3 ft/s • VFD Op.Speed: 1641 rpm • VFD Setting: 55.9 Hz
Series 4380Design Envelope: 0306-002.0 @ 55.9 Hz
Integrated Intelligent Variable Speed with Sensorless Control
0 4 8 12 16 200
20
40
60
80
100
120
Flow (lps)
Head
(kpa)
6.19 in
4.50 in
System
6.19 in
1 hp
2 hp
77
77
74
74
70
70
62
62
52
52%
39
Water, spgr= 1.0000
PT70-4-0 (3.29.0.20)ANSI/HI 14.6.3.4.1
77
--- Admin Data --- Tag Num: P-3,4 Service: AHU Heating Coild Location: Mechanical Room
--- Motor Data --- Motor Size: 2 hp
--- Design Duty Point --- Flow: 7.7 lps Head: 85 kpa Impeller: 6.19 in
--- Control Data --- 1. Hmax @ 55.9 Hz: • 7.7 @ 85, 1.21 hp 2. Control (QPC) @ 51.8 Hz: • 6.82 @ 74, 0.95 hp 3. Control (QPC) @ 47.4 Hz: • 5.81 @ 63, 0.71 hp 4. Control (QPC) @ 43.3 Hz: • 4.8 @ 53.8, 0.52 hp 5. Control (QPC) @ 38.9 Hz: • 3.55 @ 44.8, 0.36 hp 6. Index @ 34.7 Hz: • 1.92 @ 37.2, 0.22 hp 7. Hmin: 34 kpa 33.1 Hz: • Setting= 40.00% Hmax
Series 4380Design Envelope: 0306-002.0
Integrated Intelligent Variable Speed with Sensorless Control
0 4 8 12 16 200
20
40
60
80
100
120
140
160
Flow (lps)
Head
(kpa)
62.0 Hz
34.7 Hz
33.1 Hz
18.0 Hz
System
Avg.Load (QPC)
55.9 Hz
2 hp
7777
77
74
74
70
70
62
62
52
Index Flow (25.0% Duty Flow)
Water, spgr= 1.0000
PT70-4-0 (3.29.0.20)ANSI/HI 14.6.3.4.1
1
2
3
4
56
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 6 of 38
Design envelope pumping unit capability
Operating point Flow Head Efficiency
7.7 L/sFull capability at 100% design flow 107.7 kpa 69.96 %
Design point 7.7 L/s 85 kPa 72.67 %
50% average flow (with default load profile) 3.85 lps 46.7 kpa 61.97 %
Dimensional data (not for construction)
Top viewSide view
Weight: 250 lb• Not to scale • R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 3 7.5ANSI-125 4 0.6256
Outlet 3 7.5ANSI-125 4 0.6256
*Equally spaced straddling centreline
Special instructions
The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.
OSHPD Seismic Certification OSP-0422-10UL STD 778 & CSA STD C22.2 no.108 certified
Selected options Environmental Application: Indoors Sensorless Bundle: Sensorless control Constant flow control Constant pressure control Flow readout
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 7 of 38
Submittal Ref. #: 456329.3 rev3
Design envelope close coupled vertical in-line pump
Model: Series Design Envelope Sensorless 4380 0208-003.0
Project name: CC-14147 SFU Student Union Building
Location: Burnaby, BC Representative: Con-Cur West Marketing Inc.
Date submitted: 4/24/2017 11:31:44 PM Phone number: 604-312-9062
Engineer: Integral Group e-mail: [email protected]
Contractor: Keith Plumbing & Heating Submitted by: Rocco Logozzo
Application design data
Tag number: P-5,6 Pipe orientation: SingleSuction pressure: 0 ftService: Heating Terminal & Fan Coils
Location: Mechanical Room Fluid: Non-Potable Fluid - Water
Quantity: 2 Operating temperature: 60 CViscosity: 31 SSUDuty flow per pump: 5.82 L/s
Specific gravity: 1.0000Duty head: 165 kPa
Safety factor % head: 0 %Environment: Indoors
Total dissolved solids: 0 ppm
Materials of construction
Construction: BF Impeller: Bronze (BS1400 Grade LG1)Rating: ANSI-125 Shaft sleeve: 316 SSConnections: Inlet: 2 in, Outlet: 2 in Casing gasket: Confined Non-Asbestos Fiber
Casing (volute): Cast Iron (BS1452 GR220) Flush line: Braided Stainless Steel
Mechanical seal data
Seal type Inside Single Spring Rotating face: Resin Bonded CarbonManufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon Carbide
Springs: Stainless Steel Secondary seal: EPDM
Rotating hardware: Stainless Steel
Motor electrical data
Factory ChoiceSupplier: Insulation class: Class F InsulationSize: 3 hp Inverter motor type: Inverter DutyFrame number: 182JM Efficiency: NEMA Prem (12.12)Enclosure: TEFC Operating speed @ 100% flow: 1581 rpmMotor Electrics: Operating speed @ 50% flow: 1147 rpm208/3/60
IVS102 controller data
Sensorless control: Yes-Quadratic press control Communication port: RS 485
BMS protocol: BACnet Native Analog inputs: 2 (current or voltage)
UL Type 12Enclosure: Analog outputs: 1 (current)
Fused disconnect switch: No Digital inputs: 4 (programmable)
Control orientation: L1 Digital outputs: 2 (programmable)
Expansion card: None Cooling: Fan cooled through back channelBHP at 50% load/flow and 55% of design head: Ambient temperature: -10C to +45C (up to 1000m elevation)
EMI/RFI control: Integrated filter to meet EN61800-3Min. maintained sys. pressure: Harmonic suppression: Integrated DC link reactor**
*If minimum maintained system pressure is not known, default is 40% of design head.** The IVS 102 control is a low harmonic control with a built-in DC link reactor equivalent in performance to a 5% AC line reactor. This does not guarantee performance to any system wide harmonic specification or the costs to meet a system wide specification. If supplied with the system electrical details, Armstrong will run a computer simulation of the system wide harmonics. If system harmonic levels are exceeded, Armstrong can also recommend additional harmonic mitigation and the cost for such mitigation.
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 9 of 38
Operating limits (temperature - pressure)
Maximum pressure: 175 psi
Maximum temperature: 250 F
Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.
Performance curve
--- Admin Data --- Tag Num: P-5,6 Service: Heating Terminal Location: Mechanical Room
--- Motor Data --- Motor Size: 3 hp
--- Design Duty Point --- Flow: 5.82 lps Head: 165 kpa Impeller: 8.19 in
--- Performance Data --- • NPSHR: 12.6 kpa • Eff. @ Design: 62.01 % • BHP @ Design: 2.08 hp • Mtr Capability @ Rated Spd: 2.7 hp • %Mtr Safety: 29.97% • BEP @ Design Imp.: 64.38 % @ 7.96 lps • %max imp. range: 100.00 % • Outlet Velocity: 8.82 ft/s • VFD Op.Speed: 1581 rpm • VFD Setting: 53.7 Hz
Series 4380Design Envelope: 0208-003.0 @ 53.7 Hz
Integrated Intelligent Variable Speed with Sensorless Control
0 2 4 6 8 10 12 14 160
40
80
120
160
200
Flow (lps)
Head
(kpa)
8.19 in
6.00 in
System
8.19 in
1.5 hp
2 hp
3 hp
5 hp
65
65
63
63
59
59
54
54
4534
Water, spgr= 1.0000
PT39-2-0 (3.29.0.20)ANSI/HI 14.6.3.4.1
65
--- Admin Data --- Tag Num: P-5,6 Service: Heating Terminal Location: Mechanical Room
--- Motor Data --- Motor Size: 3 hp
--- Design Duty Point --- Flow: 5.82 lps Head: 165 kpa Impeller: 8.19 in
--- Control Data --- 1. Hmax @ 53.7 Hz: • 5.82 @ 165, 2.08 hp 2. Control (QPC) @ 50.0 Hz: • 5.16 @ 143.8, 1.63 hp 3. Control (QPC) @ 45.9 Hz: • 4.4 @ 122.7, 1.21 hp 4. Control (QPC) @ 42.2 Hz: • 3.65 @ 104.8, 0.89 hp 5. Control (QPC) @ 38.4 Hz: • 2.77 @ 88.4, 0.63 hp 6. Index @ 34.4 Hz: • 1.46 @ 72.2, 0.38 hp 7. Hmin: 66 kpa 32.7 Hz: • Setting= 40.00% Hmax
Series 4380Design Envelope: 0208-003.0
Integrated Intelligent Variable Speed with Sensorless Control
0 2 4 6 8 10 12 14 160
40
80
120
160
200
Flow (lps)
Head
(kpa)
55.6 Hz
34.4 Hz
32.7 Hz
18.0 Hz
System
Avg.Load (QPC)
53.7 Hz
3 hp
6565
65
63
63
59
59
54
54
45 Index Flow (25.0% Duty Flow)
Water, spgr= 1.0000
PT39-2-0 (3.29.0.20)ANSI/HI 14.6.3.4.1
1
2
3
4
5
6
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 10 of 38
Design envelope pumping unit capability
Operating point Flow Head Efficiency
5.82 L/sFull capability at 100% design flow 177.5 kpa 61.44 %
Design point 5.82 L/s 165 kPa 62.01 %
50% average flow (with default load profile) 2.91 lps 90.9 kpa 53.41 %
Dimensional data (not for construction)
Top viewSide view
Weight: 292 lb• Not to scale • R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 2 6ANSI-125 4 0.6254.75
Outlet 2 6ANSI-125 4 0.6254.75
*Equally spaced straddling centreline
Special instructions
The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.
OSHPD Seismic Certification OSP-0422-10UL STD 778 & CSA STD C22.2 no.108 certified
Selected options Environmental Application: Indoors Sensorless Bundle: Sensorless control Constant flow control Constant pressure control Flow readout
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 11 of 38
Submittal Ref. #: 456329.3 rev3
Split coupled vertical in line pump
Model: Series 4300-5x5x8-7.5 hp Pump (Motor supplier: Armstrong choice)
Project name: CC-14147 SFU Student Union Building
Location: Burnaby, BC Representative: Con-Cur West Marketing Inc.
Date submitted: 4/24/2017 11:31:44 PM Phone number: 604-312-9062
Engineer: Integral Group e-mail: [email protected]
Contractor: Keith Plumbing & Heating Submitted by: Rocco Logozzo
Application design data
Tag number: P-7 Pipe orientation: SingleSuction pressure: 0 ftService: Dry Cooler Loop
Location: Mechanical Room Fluid: PropyleneGlycol:25
Quantity: 1 Operating temperature: 8 CViscosity: 36.319 SSUDuty flow per pump: 20.4 L/s
Specific gravity: 1.0204Duty head: 175 kPa
Total dissolved solids: 0 ppm
Materials of construction
Construction: BF Impeller: Bronze (B584-844)Rating: ANSI-125 Pump shaft: SS ASTM A276 Type 416Connections: Inlet: 5 in, Outlet: 5 in Flush line: Braided Stainless Steel
Casing (volute): Cast Iron (A48-30) Casing gasket: Confined Non-Asbestos Fiber
Mechanical seal data
Seal type Outside Balanced Rotating face: Resin Bonded CarbonManufacturer code: C-SSC AB2 Stationary seat: Sintered Silicon Carbide
Springs: Stainless Steel Secondary seal: Viton
Rotating hardware: Stainless Steel
Motor electrical data
Factory ChoiceSupplier: Insulation class: Class F InsulationSize: 7.5 hp Inverter motor type: Inverter DutyFrame number: 213TC Efficiency: NEMA Prem (12.12)Enclosure: ODP Speed: 1765 rpmMotor Electrics: 480/3/60
Operating limits (temperature - pressure)
Maximum pressure: 175 psi
Maximum temperature: 200 F
Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 13 of 38
Performance curve
--- Admin Data --- Tag Num: P-7 Service: Dry Cooler Loop Location: Mechanical Room
--- Motor Data --- Motor Size: 7.5 hp Motor Speed: 1800 rpm
--- Design Duty Point --- Flow: 20.4 lps Head: 175 kpa Impeller: 8.19 in (Optimal)
--- Performance Data --- • NPSHR: 23.2 kpa • Eff. @ Design: 75.09 % • BHP @ Design: 6.38 hp • Mtr Capability @ Rated Spd: 7.5 hp • %Mtr Safety: 17.61% • BEP @ Design Imp.: 76.91 % @ 25.70 lps • Impeller Max BHP @ Flow: 7.24 hp @ 33.58 lps • %Optimization: 43.98 % • Outlet Velocity: 5.19 ft/s • VFD Setting: 60.0 Hz
Series 43005x5x8 (Optimal) @ 1765 rpm
0 8 16 24 32 40 480
50
100
150
200
250
300
Flow (lps)
Head
(kpa)
(Optimal)
6.00 in
System
(Optimal)
2 hp
3 hp
5 hp
7.5 hp
1.5 hp
77
77
75
75
70
70
63
63
5238
PropyleneGlycol:25, spgr= 1.0204
PT95-1-0 (3.29.0.20)ANSI/HI 14.6.3.4.1
77
--- Admin Data --- Tag Num: P-7 Service: Dry Cooler Loop Location: Mechanical Room
--- Motor Data --- Motor Size: 7.5 hp Motor Speed: 1800 rpm
--- Design Duty Point --- Flow: 20.4 lps Head: 175 kpa Impeller: 8.19 in (Optimal)
--- System Intersect Data --- 1. System @ 60.0 Hz: • 20.4 @ 175, 6.38 hp 2. System @ 51.7 Hz: • 17.58 @ 130, 4.08 hp 3. System @ 43.2 Hz: • 14.69 @ 90.8, 2.38 hp 4. System @ 34.7 Hz: • 11.8 @ 58.5, 1.23 hp 5. System @ 26.5 Hz: • 9.02 @ 34.2, 0.55 hp 6. System @ 18.0 Hz: • 6.12 @ 15.8, 0.17 hp
Series 43005x5x8 @ 8.19 in (Optimal)
0 8 16 24 32 40 480
40
80
120
160
200
240
Flow (lps)
Head
(kpa)
1853 rpm
1765 rpm
529 rpm
System
1765 rpm
1.5 hp2 hp3 hp
5 hp
7.5 hp10 hp
77
77
77
75
75
70
70
63
63
52
1520 rpm
1270 rpm
1020 rpm
780 rpm
PropyleneGlycol:25, spgr= 1.0204
PT95-1-0 (3.29.0.20)ANSI/HI 14.6.3.4.1
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 14 of 38
Dimensional data (not for construction)
Top viewSide view
Weight: 453 lb• Not to scale • R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge portsConnection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 5 10ANSI-125 8 0.758.5
Outlet 5 10ANSI-125 8 0.758.5
*Equally spaced straddling centreline
Special instructions
Armstrong Motor Specification AES 05007The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.
Selected options Motor Nameplate Voltages (200, 416, 480, 600 volts)
Additional equipment Flotrex: FTV-6FA (570200-480) Suction Guide: SG-65 (516860-025)
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 15 of 38
Submittal Ref. #: 456329.3 rev3
Close coupled vertical in-line pump
Model: Series 4380-4x4x8-5 hp Pump (Motor supplier: Armstrong choice)
Project name: CC-14147 SFU Student Union Building
Location: Burnaby, BC Representative: Con-Cur West Marketing Inc.
Date submitted: 4/24/2017 11:31:44 PM Phone number: 604-312-9062
Engineer: Integral Group e-mail: [email protected]
Contractor: Keith Plumbing & Heating Submitted by: Rocco Logozzo
Application design data
Tag number: P-8 Pipe orientation: SingleSuction pressure: 0 ftService: Primary Chilled Water
Location: Mechanical Room Fluid: Non-Potable Fluid - Water
Quantity: 1 Operating temperature: 10 CViscosity: 31 SSUDuty flow per pump: 18 L/s
Specific gravity: 1.0000Duty head: 110 kPa
Total dissolved solids: 0 ppm
Materials of construction
Construction: BF Impeller: Bronze (B584-844)Rating: ANSI-125 Shaft sleeve: 316 SSConnections: Inlet: 4 in, Outlet: 4 in Casing gasket: Confined Non-Asbestos Fiber
Casing (volute): Cast Iron (A48-30) Flush line: Braided Stainless Steel
Mechanical seal data
Seal type Inside Single Spring Rotating face: Resin Bonded CarbonManufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon Carbide
Springs: Stainless Steel Secondary seal: EPDM
Rotating hardware: Stainless Steel
Motor electrical data
Factory ChoiceSupplier: Insulation class: Class F InsulationSize: 5 hp Inverter motor type: Inverter DutyFrame number: 184JM Efficiency: NEMA Prem (12.12)Enclosure: ODP Speed: 1770 rpmMotor Electrics: 480/3/60
Operating limits (temperature - pressure)
Maximum pressure: 175 psi
Maximum temperature: 250 F
Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 16 of 38
Performance curve
--- Admin Data --- Tag Num: P-8 Service: Primary Chilled Water Location: Mechanical Room
--- Motor Data --- Motor Size: 5 hp Motor Speed: 1800 rpm
--- Design Duty Point --- Flow: 18 lps Head: 110 kpa Impeller: 6.59 in
--- Performance Data --- • NPSHR: 36.6 kpa • Eff. @ Design: 62.68 % • BHP @ Design: 4.24 hp • Mtr Capability @ Rated Spd: 5 hp • %Mtr Safety: 17.99% • BEP @ Design Imp.: 67.91 % @ 24.22 lps • Impeller Max BHP @ Flow: 5.03 hp @ 35.40 lps • %max imp. range: 26.97 % • Outlet Velocity: 7.19 ft/s • VFD Setting: 60.0 Hz
Series 43804x4x8 @ 1770 rpm
0 10 20 30 40 50 600
40
80
120
160
200
240
Flow (lps)
Head
(kpa)
8.19 in
6.00 in
System
6.59 in
3 hp
5 hp
7.5 hp
10 hp
15 hp
79
79
76
76
72
72
64
64%
53
53%
39
Water, spgr= 1.0000
PT87-3-0 (3.29.0.20)ANSI/HI 14.6.3.4.1
80
--- Admin Data --- Tag Num: P-8 Service: Primary Chilled Water Location: Mechanical Room
--- Motor Data --- Motor Size: 5 hp Motor Speed: 1800 rpm
--- Design Duty Point --- Flow: 18 lps Head: 110 kpa Impeller: 6.59 in
--- System Intersect Data --- 1. System @ 60.0 Hz: • 18 @ 110, 4.24 hp 2. System @ 51.5 Hz: • 15.46 @ 81.2, 2.69 hp 3. System @ 43.4 Hz: • 13.02 @ 57.6, 1.6 hp 4. System @ 34.9 Hz: • 10.48 @ 37.3, 0.84 hp 5. System @ 26.4 Hz: • 7.94 @ 21.4, 0.36 hp 6. System @ 18.0 Hz: • 5.4 @ 9.9124, 0.11 hp
Series 43804x4x8 @ 6.59 in
0 8 16 24 32 40 480
20
40
60
80
100
120
140
160
Flow (lps)
Head
(kpa)
1858 rpm
1770 rpm
531 rpm
System
1770 rpm
1.5 hp2 hp
3 hp
5 hp
7.5 hp
68
67
67
63
63
57
57
49
49
39
1520 rpm
1280 rpm
1030 rpm
780 rpm
Water, spgr= 1.0000
PT87-3-0 (3.29.0.20)ANSI/HI 14.6.3.4.1
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 17 of 38
Dimensional data (not for construction)
Top viewSide view
Weight: 319 lb• Not to scale • R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge portsConnection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 4 9ANSI-125 8 0.6257.5
Outlet 4 9ANSI-125 8 0.6257.5
*Equally spaced straddling centreline
Special instructions
The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.
Selected options Motor Nameplate Voltages (200, 416, 480, 600 volts)
Additional equipment Flotrex: FTV-6FA (570200-480) Suction Guide: SG-64 (516860-023)
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 18 of 38
Submittal Ref. #: 456329.3 rev3
Design envelope close coupled vertical in-line pump
Model: Series Design Envelope Sensorless 4380 0306-007.5
Project name: CC-14147 SFU Student Union Building
Location: Burnaby, BC Representative: Con-Cur West Marketing Inc.
Date submitted: 4/24/2017 11:31:44 PM Phone number: 604-312-9062
Engineer: Integral Group e-mail: [email protected]
Contractor: Keith Plumbing & Heating Submitted by: Rocco Logozzo
Application design data
Tag number: P-9 Pipe orientation: SingleSuction pressure: 0 ftService: AHU & FC Cooling
Location: Mechanical Room Fluid: Non-Potable Fluid - Water
Quantity: 1 Operating temperature: 59 FViscosity: 31 SSUDuty flow per pump: 17.5 L/s
Specific gravity: 1.0000Duty head: 165 kPa
Safety factor % head: 0 %Environment: Indoors
Total dissolved solids: 0 ppm
Materials of construction
Construction: BF Impeller: Bronze (BS1400 Grade LG1)Rating: ANSI-125 Shaft sleeve: 316 SSConnections: Inlet: 3 in, Outlet: 3 in Casing gasket: Confined Non-Asbestos Fiber
Casing (volute): Cast Iron (BS1452 GR220) Flush line: Braided Stainless Steel
Mechanical seal data
Seal type Inside Single Spring Rotating face: Resin Bonded CarbonManufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon Carbide
Springs: Stainless Steel Secondary seal: EPDM
Rotating hardware: Stainless Steel
Motor electrical data
Factory ChoiceSupplier: Insulation class: Class F InsulationSize: 7.5 hp Inverter motor type: Inverter DutyFrame number: 213JM Efficiency: NEMA Prem (12.12)Enclosure: TEFC Operating speed @ 100% flow: 3283 rpmMotor Electrics: Operating speed @ 50% flow: 2211 rpm480/3/60
less than
IVS102 controller data
Sensorless control: Yes-Quadratic press control Communication port: RS 485
BMS protocol: BACnet Native Analog inputs: 2 (current or voltage)
UL Type 12Enclosure: Analog outputs: 1 (current)
Fused disconnect switch: No Digital inputs: 4 (programmable)
Control orientation: L1 Digital outputs: 2 (programmable)
Expansion card: None Cooling: Fan cooled through back channelBHP at 50% load/flow and 55% of design head: Ambient temperature: 14F to 113F (up to 3280ft elevation)
EMI/RFI control: Integrated filter to meet EN61800-3Min. maintained sys. pressure: Harmonic suppression: Integrated DC link reactor**
*If minimum maintained system pressure is not known, default is 40% of design head.** The IVS 102 control is a low harmonic control with a built-in DC link reactor equivalent in performance to a 5% AC line reactor. This does not guarantee performance to any system wide harmonic specification or the costs to meet a system wide specification. If supplied with the system electrical details, Armstrong will run a computer simulation of the system wide harmonics. If system harmonic levels are exceeded, Armstrong can also recommend additional harmonic mitigation and the cost for such mitigation.
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 19 of 38
Operating limits (temperature - pressure)
Maximum pressure: 175 psi
Maximum temperature: 250 F
Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.
Performance curve
--- Admin Data --- Tag Num: P-9 Service: AHU & FC Cooling Location: Mechanical Room
--- Motor Data --- Motor Size: 7.5 hp
--- Design Duty Point --- Flow: 17.5 lps Head: 165 kpa Impeller: 5 in
--- Performance Data --- • NPSHR: 47.3 kpa • Eff. @ Design: 72.16 % • BHP @ Design: 5.37 hp • Mtr Capability @ Rated Spd: 6.6 hp • %Mtr Safety: 23.01% • BEP @ Design Imp.: 72.17 % @ 17.81 lps • %max imp. range: 29.86 % • Outlet Velocity: 12.04 ft/s • VFD Op.Speed: 3283 rpm • VFD Setting: 55.6 Hz
Series 4380Design Envelope: 0306-007.5 @ 55.6 Hz
Integrated Intelligent Variable Speed with Sensorless Control
0 8 16 24 32 400
80
160
240
320
400
480
Flow (lps)
Head
(kpa)
6.19 in
4.50 in
System
5.00 in
7.5 hp
77
77
74
74
70
70
62
62
52
52%
39
Water, spgr= 1.0000
PT71-3-0 (3.29.0.20)ANSI/HI 14.6.3.4.1
77
--- Admin Data --- Tag Num: P-9 Service: AHU & FC Cooling Location: Mechanical Room
--- Motor Data --- Motor Size: 7.5 hp
--- Design Duty Point --- Flow: 17.5 lps Head: 165 kpa Impeller: 5 in
--- Control Data --- 1. Hmax @ 55.6 Hz: • 17.5 @ 165, 5.37 hp 2. Control (QPC) @ 50.8 Hz: • 15.39 @ 142.5, 4.08 hp 3. Control (QPC) @ 45.9 Hz: • 13.12 @ 121.6, 2.98 hp 4. Control (QPC) @ 41.0 Hz: • 10.68 @ 102.9, 2.09 hp 5. Control (QPC) @ 36.1 Hz: • 7.94 @ 86.4, 1.37 hp 6. Index @ 31.2 Hz: • 4.38 @ 72.2, 0.8 hp 7. Hmin: 66 kpa 28.7 Hz: • Setting= 40.00% Hmax
Series 4380Design Envelope: 0306-007.5
Integrated Intelligent Variable Speed with Sensorless Control
0 4 8 12 16 20 24 28 320
40
80
120
160
200
240
280
320
Flow (lps)
Head
(kpa)
60.5 Hz
31.2 Hz
28.7 Hz
18.0 Hz System
Avg.Load (QPC)
55.6 Hz
7.5 hp
73
72
72
70
70
65
65
58
58
48
Index Flow (25.0% Duty Flow)
Water, spgr= 1.0000
PT71-3-0 (3.29.0.20)ANSI/HI 14.6.3.4.1
1
2
3
4
56
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 20 of 38
Design envelope pumping unit capability
Operating point Flow Head Efficiency
17.5 L/sFull capability at 100% design flow 209.1 kpa 71.84 %
Design point 17.5 L/s 165 kPa 72.16 %
50% average flow (with default load profile) 8.75 lps 90.8 kpa 68.63 %
Dimensional data (not for construction)
Top viewSide view
Weight: 328 lb• Not to scale • R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 3 7.5ANSI-125 4 0.6256
Outlet 3 7.5ANSI-125 4 0.6256
*Equally spaced straddling centreline
Special instructions
The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.
OSHPD Seismic Certification OSP-0422-10UL STD 778 & CSA STD C22.2 no.108 certified
Selected options Motor Nameplate Voltages (200, 416, 480, 600 volts) Environmental Application: Indoors Sensorless Bundle: Sensorless control Constant flow control Constant pressure control Flow readout
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 21 of 38
Submittal Ref. #: 456329.3 rev3
Design envelope close coupled vertical in-line pump
Model: Series Design Envelope Sensorless 4380 0208-003.0
Project name: CC-14147 SFU Student Union Building
Location: Burnaby, BC Representative: Con-Cur West Marketing Inc.
Date submitted: 4/24/2017 11:31:44 PM Phone number: 604-312-9062
Engineer: Integral Group e-mail: [email protected]
Contractor: Keith Plumbing & Heating Submitted by: Rocco Logozzo
Application design data
Tag number: P-10 Pipe orientation: SingleSuction pressure: 0 ftService: CHW to Terminal Units
Location: Mechanical Fluid: Non-Potable Fluid - Water
Quantity: 1 Operating temperature: 15 CViscosity: 31 SSUDuty flow per pump: 6.27 L/s
Specific gravity: 1.0000Duty head: 150 kPa
Safety factor % head: 0 %Environment: Indoors
Total dissolved solids: 0 ppm
Materials of construction
Construction: BF Impeller: Bronze (BS1400 Grade LG1)Rating: ANSI-125 Shaft sleeve: 316 SSConnections: Inlet: 2 in, Outlet: 2 in Casing gasket: Confined Non-Asbestos Fiber
Casing (volute): Cast Iron (BS1452 GR220) Flush line: Braided Stainless Steel
Mechanical seal data
Seal type Inside Single Spring Rotating face: Resin Bonded CarbonManufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon Carbide
Springs: Stainless Steel Secondary seal: EPDM
Rotating hardware: Stainless Steel
Motor electrical data
Factory ChoiceSupplier: Insulation class: Class F InsulationSize: 3 hp Inverter motor type: Inverter DutyFrame number: 182JM Efficiency: NEMA Prem (12.12)Enclosure: TEFC Operating speed @ 100% flow: 1527 rpmMotor Electrics: Operating speed @ 50% flow: 1099 rpm208/3/60
IVS102 controller data
Sensorless control: Yes-Quadratic press control Communication port: RS 485
BMS protocol: BACnet Native Analog inputs: 2 (current or voltage)
UL Type 12Enclosure: Analog outputs: 1 (current)
Fused disconnect switch: No Digital inputs: 4 (programmable)
Control orientation: L1 Digital outputs: 2 (programmable)
Expansion card: None Cooling: Fan cooled through back channelBHP at 50% load/flow and 55% of design head: Ambient temperature: -10C to +45C (up to 1000m elevation)
EMI/RFI control: Integrated filter to meet EN61800-3Min. maintained sys. pressure: Harmonic suppression: Integrated DC link reactor**
*If minimum maintained system pressure is not known, default is 40% of design head.** The IVS 102 control is a low harmonic control with a built-in DC link reactor equivalent in performance to a 5% AC line reactor. This does not guarantee performance to any system wide harmonic specification or the costs to meet a system wide specification. If supplied with the system electrical details, Armstrong will run a computer simulation of the system wide harmonics. If system harmonic levels are exceeded, Armstrong can also recommend additional harmonic mitigation and the cost for such mitigation.
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 23 of 38
Operating limits (temperature - pressure)
Maximum pressure: 175 psi
Maximum temperature: 250 F
Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.
Performance curve
--- Admin Data --- Tag Num: P-10 Service: CHW to Terminal Units Location: Mechanical
--- Motor Data --- Motor Size: 3 hp
--- Design Duty Point --- Flow: 6.27 lps Head: 150 kpa Impeller: 8.19 in
--- Performance Data --- • NPSHR: 13.2 kpa • Eff. @ Design: 63.46 % • BHP @ Design: 1.99 hp • Mtr Capability @ Rated Spd: 2.63 hp • %Mtr Safety: 32.28% • BEP @ Design Imp.: 64.38 % @ 7.69 lps • %max imp. range: 100.00 % • Outlet Velocity: 9.5 ft/s • VFD Op.Speed: 1527 rpm • VFD Setting: 51.9 Hz
Series 4380Design Envelope: 0208-003.0 @ 51.9 Hz
Integrated Intelligent Variable Speed with Sensorless Control
0 2 4 6 8 10 12 14 160
40
80
120
160
200
Flow (lps)
Head
(kpa)
8.19 in
6.00 in
System
8.19 in
1.5 hp
2 hp
3 hp
5 hp
65
65
63
63
59
59
54
54
4534
Water, spgr= 1.0000
PT39-2-0 (3.29.0.20)ANSI/HI 14.6.3.4.1
65
--- Admin Data --- Tag Num: P-10 Service: CHW to Terminal Units Location: Mechanical
--- Motor Data --- Motor Size: 3 hp
--- Design Duty Point --- Flow: 6.27 lps Head: 150 kpa Impeller: 8.19 in
--- Control Data --- 1. Hmax @ 51.9 Hz: • 6.27 @ 150, 1.99 hp 2. Control (QPC) @ 48.3 Hz: • 5.58 @ 131.3, 1.56 hp 3. Control (QPC) @ 44.2 Hz: • 4.75 @ 111.7, 1.15 hp 4. Control (QPC) @ 40.5 Hz: • 3.92 @ 95.2, 0.84 hp 5. Control (QPC) @ 36.7 Hz: • 2.96 @ 80.1, 0.57 hp 6. Index @ 32.8 Hz: • 1.57 @ 65.6, 0.34 hp 7. Hmin: 60 kpa 31.2 Hz: • Setting= 40.00% Hmax
Series 4380Design Envelope: 0208-003.0
Integrated Intelligent Variable Speed with Sensorless Control
0 2 4 6 8 10 12 14 160
40
80
120
160
200
Flow (lps)
Head
(kpa)
55.6 Hz
32.8 Hz
31.2 Hz
18.0 Hz
System
Avg.Load (QPC)
51.9 Hz
3 hp
6565
65
63
63
59
59
54
54
45 Index Flow (25.0% Duty Flow)
Water, spgr= 1.0000
PT39-2-0 (3.29.0.20)ANSI/HI 14.6.3.4.1
1
2
3
4
5
6
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 24 of 38
Design envelope pumping unit capability
Operating point Flow Head Efficiency
6.27 L/sFull capability at 100% design flow 174.9 kpa 62.63 %
Design point 6.27 L/s 150 kPa 63.46 %
50% average flow (with default load profile) 3.13 lps 82.6 kpa 56.55 %
Dimensional data (not for construction)
Top viewSide view
Weight: 292 lb• Not to scale • R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 2 6ANSI-125 4 0.6254.75
Outlet 2 6ANSI-125 4 0.6254.75
*Equally spaced straddling centreline
Special instructions
The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.
OSHPD Seismic Certification OSP-0422-10UL STD 778 & CSA STD C22.2 no.108 certified
Selected options Environmental Application: Indoors Sensorless Bundle: Sensorless control Constant flow control Constant pressure control Flow readout
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 25 of 38
Submittal Ref. #: 456329.3 rev3
Wet rotor circulator
Model: Part number: 110223-321Series ASTRO 280SS FLG
Project name: CC-14147 SFU Student Union Building
Location: Burnaby, BC Representative: Con-Cur West Marketing Inc.
Date submitted: 4/24/2017 11:31:44 PM Phone number: 604-312-9062
Engineer: Integral Group e-mail: [email protected]
Contractor: Keith Plumbing & Heating Submitted by: Rocco Logozzo
Application design data
Tag number: P-11 Pipe orientation: SingleSuction pressure: 0 ftService: DHWR
Location: Mechanical Room Fluid: Water:
Quantity: 1 Operating temperature: 60 F*Viscosity: 31 SSUDuty flow per pump: 1 L/s
Specific gravity: 1.0000Duty head: 35 kPa
Total dissolved solids: 0 ppm
* for open systems, it is recommended that the fluid temperature be less than 150F (66C) to avoid precipitation of calcium.
Materials of construction
Construction: SS150 Impeller: Polyether Imide (PEI)
Connections: Inlet: 1.25 in, Outlet: 1.25 in Bearings: Ceramic
Connection type: NPSM union Certified standard: UL 778 & CSA C22.2 No. 108-01
Companion flange: Bronze 1 1/2" Listing: ETL listed for US and Canada
**certified <0.25 weighted average percent lead and complies with Californai Health and Safety Code section 114875 (commonly known as AB1953)
Motor electrical data
Factory ChoiceSupplier: Insulation class: Not applicableSize: 0.333 hp Inverter motor type: Not applicableFrame number: Not applicable Efficiency: StdEnclosure: ODP Speed: 2900 rpmMotor Electrics: 115/1/60
Operating limits (temperature - pressure)
Maximum pressure: 150 psi
Maximum temperature: 230 F
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 27 of 38
Performance curve
--- Admin Data --- Tag Num: P-11 Service: DHWR Location: Mechanical Room
--- Motor Data --- Motor Size: 0.333 hp Motor Speed: [2] 2900 rpm
--- Design Duty Point --- Flow: 1 lps Head: 35 kpa
--- Pump Data --- Pump Size: Astro 280SS Impeller: 2.95 in Suction Head Req: 0 kpa Projected Flow: 1.04 lps Projected Head: 38 kpa
Series Astro MultiSpeedAstro 280SS @ Discrete Speeds
0 0.4 0.8 1.2 1.6 20
20
40
60
80
100
Flow (lps)
Head
(kpa)
System
Projected
[1] 2300
[2] 2900 [3] 3600
Water:, spgr= 1.0000
PT625-0-231 (3.29.0.20)
Dimensional data (not for construction)
Top viewSide view
Weight: 11 lb• Not to scale• Units of measure : inches [millimeters]• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 28 of 38
Submittal Ref. #: 456329.3 rev3
Flo-trex valveModel: FTV-F (2.5 to 12 inch)
Project name: CC-14147 SFU Student Union Building
Location: Burnaby, BC Representative: Con-Cur West Marketing Inc.
Date submitted: 4/24/2017 11:31:44 PM Phone number: 604-312-9062
Engineer: Integral Group e-mail: [email protected]
Contractor: Keith Plumbing & Heating Submitted by: Rocco Logozzo
Application design data
DesignflowrateTag Qty Model Size Config Flange rating Pressure
Drop* Associated pump
P-8 1 FTV-6FA 6 in Angle Flanged
ANSI-125 17.9 L/s 2.8 ft P-8 4380-4x4x8-5 hp Pump (Factory Choice Motor)
P-9 1 FTV-4FA 4 in Angle Flanged
ANSI-125 17.4 L/s 3.4 ft P-9 Design Envelope Sensorless 4380 0306-007.5
P-1,2 2 FTV-4FA 4 in Angle Flanged
ANSI-125 9.0 L/s 2.8 ft P-1,2 Design Envelope Sensorless 4380 0306-002.0
P-3,4 2 FTV-3FA 3 in Angle Flanged
ANSI-125 7.6 L/s 3.0 ft P-3,4 Design Envelope Sensorless 4380 0306-002.0
P-5,6 2 FTV-3FA 3 in Angle Flanged
ANSI-125 5.8 L/s 3.0 ft P-5,6 Design Envelope Sensorless 4380 0208-003.0
P-7 1 FTV-6FA 6 in Angle Flanged
ANSI-125 20.2 L/s 2.8 ft P-7 4300-5x5x8-7.5 hp Pump (Factory Choice Motor)
P-10 1 FTV-3FA 3 in Angle Flanged
ANSI-125 6.2 L/s 3.0 ft P-10 Design Envelope Sensorless 4380 0208-003.0
*at design flow
Materials of construction
FTV-3FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12
Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302
Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:Seat: EPDM 2 metering ports: Brass Body with EPDM Check and
Gasketed Cap
Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug
FTV-6FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12
Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302
Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:Seat: EPDM 2 metering ports: Brass Body with EPDM Check and
Gasketed Cap
Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug
FTV-6FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12
Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302
Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:Seat: EPDM 2 metering ports: Brass Body with EPDM Check and
Gasketed Cap
Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 30 of 38
FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12
Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302
Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:Seat: EPDM 2 metering ports: Brass Body with EPDM Check and
Gasketed Cap
Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug
FTV-3FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12
Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302
Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:Seat: EPDM 2 metering ports: Brass Body with EPDM Check and
Gasketed Cap
Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug
FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12
Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302
Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:Seat: EPDM 2 metering ports: Brass Body with EPDM Check and
Gasketed Cap
Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug
FTV-3FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12
Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302
Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:Seat: EPDM 2 metering ports: Brass Body with EPDM Check and
Gasketed Cap
Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug
Operating limits (temperature - pressure)
FTV-3FA-Flo-Trex Valve-ANSI-125-Angle Flanged
Maximum pressure: 175 psi
Maximum temperature: 230 F
Dimensional data (not for construction)
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 31 of 38
Model: FTV-3FA-Flo-Trex Valve-ANSI-125-Angle Flanged Weight: 39 lb
Side view Front view
Model: FTV-6FA-Flo-Trex Valve-ANSI-125-Angle Flanged Weight: 167 lb
Side view Front view
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 32 of 38
Model: FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged Weight: 59 lb
Side view Front view
Not to scale Units of measure: inches [millimeters]Tolerance of +/- 0.125 inch (+/- 3 mm) should be used For certified dimensions, please contact your Armstrong representative
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 33 of 38
Submittal Ref. #: 456329.3 rev3
Suction guideModel: SG (2 to 12 inches)
Project name: CC-14147 SFU Student Union Building
Location: Burnaby, BC Representative: Con-Cur West Marketing Inc.
Date submitted: 4/24/2017 11:31:44 PM Phone number: 604-312-9062
Engineer: Integral Group e-mail: [email protected]
Contractor: Keith Plumbing & Heating Submitted by: Rocco Logozzo
Application design data
Design flowrateTag Qty Model System Pump Pressure
Drop* Associated pump
P-3,4 2 SG-33 3 in 3 in 7.6 L/s 0.6 ft P-3,4 Design Envelope Sensorless 4380 0306-002.0
P-5,6 2 SG-32 3 in 2 in 5.8 L/s 0.9 ft P-5,6 Design Envelope Sensorless 4380 0208-003.0
P-7 1 SG-65 6 in 5 in 20.2 L/s 0.7 ft P-7 4300-5x5x8-7.5 hp Pump (Factory Choice Motor)
P-8 1 SG-64 6 in 4 in 17.9 L/s 1.0 ft P-8 4380-4x4x8-5 hp Pump (Factory Choice Motor)
P-9 1 SG-43 4 in 3 in 17.4 L/s 3.2 ft P-9 Design Envelope Sensorless 4380 0306-007.5
P-10 1 SG-32 3 in 2 in 6.2 L/s 1.1 ft P-10 Design Envelope Sensorless 4380 0208-003.0
P-1,2 2 SG-43 4 in 3 in 9.0 L/s 0.9 ft P-1,2 Design Envelope Sensorless 4380 0306-002.0
*at design flow
Materials of construction
SG-33Body: Cast Iron Cover gasket: Synthetic fiber
Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.
Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel
SG-43
Body: Cast Iron Cover gasket: Synthetic fiber
Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.
Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel
SG-32Body: Cast Iron Cover gasket: Synthetic fiber
Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.
Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel
SG-65Body: Cast Iron Cover gasket: Synthetic fiber
Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.
Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel
SG-64Body: Cast Iron Cover gasket: Synthetic fiber
Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.
Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 34 of 38
SG-43Body: Cast Iron Cover gasket: Synthetic fiber
Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.
Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel
SG-32Body: Cast Iron Cover gasket: Synthetic fiber
Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.
Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel
*Remove start up strainer after 24 hours
Operating limits (temperature - pressure)
SG-33-Suction Guide-ANSI-125
Maximum pressure: 175 psi
Maximum temperature: 230 F
Units are hydrostatically tested to 150% of maximum working pressure
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 35 of 38
Dimensional data (not for construction)
SG-33 Weight: 45 lb
Side view Top view
SG-43 Weight: 52 lb
Side view Top view
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 36 of 38
SG-32 Weight: 31 lb
Side view Top view
SG-65 Weight: 103 lb
Side view Top view
www.armstrongfluidtechnology.com 5/13/2017, Ref. # 456329.3 rev3 Page 37 of 38