ADDENDUM MECHANICAL | ELECTRICAL | PLUMBING | FIRE PROTECTION COLUMBUS | INDIANAPOLIS | VIRGINIA BEACH 1405 DUBLIN ROAD, COLUMBUS, OH 43215 PHONE: (614) 486-4778 FAX: (614) 486-4082 WWW.AECMEP.COM Page 1 of 1 ADDENDUM NUMBER: 1 PROJECT NAME: COTA EV CHARGING – NORTHERN LIGHTS AND NORTHLAND (REBID) PROJECT NUMBER: - AEC PROJECT NUMBER: 19-008-03 PROJECT LOCATION: COLUMBUS, OH PREPARED BY: AEC DATE: 11/18/2019 PART 1 - PRE-BID QUESTIONS AND ANSWERS A. Please see attached list of RFI questions and answers in blue. PART 2 - DRAWING REVISIONS A. Northland Transit Center - See attached E-002 and E-003 for revisions. B. Northern Lights – See attached E-002 for revisions. END OF SECTION

MECHANICAL ELECTRICAL PLUMBING FIRE PROTECTION€¦ · (ct4021-gw1-ct4000-pmgmt-ct4001-ccm-cpcld-commerical-5-ct4000-assure5-cpsupport-active) basis of design: myparkingsign.com,

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: MECHANICAL ELECTRICAL PLUMBING FIRE PROTECTION€¦ · (ct4021-gw1-ct4000-pmgmt-ct4001-ccm-cpcld-commerical-5-ct4000-assure5-cpsupport-active) basis of design: myparkingsign.com,

ADDENDUM

MECHANICAL | ELECTRICAL | PLUMBING | FIRE PROTECTION 

COLUMBUS | INDIANAPOLIS | VIRGINIA BEACH

1405 DUBLIN ROAD, COLUMBUS, OH 43215 ∙ PHONE: (614) 486-4778 ∙ FAX: (614) 486-4082 ∙ WWW.AECMEP.COM Page 1 of 1

ADDENDUM NUMBER: 1

PROJECT NAME: COTA EV CHARGING – NORTHERN LIGHTS AND NORTHLAND (REBID)

PROJECT NUMBER: - AEC PROJECT NUMBER: 19-008-03

PROJECT LOCATION: COLUMBUS, OH

PREPARED BY: AEC DATE: 11/18/2019

PART 1 - PRE-BID QUESTIONS AND ANSWERS

A. Please see attached list of RFI questions and answers in blue.

PART 2 - DRAWING REVISIONS

A. Northland Transit Center - See attached E-002 and E-003 for revisions.

B. Northern Lights – See attached E-002 for revisions.

END OF SECTION

Page 2: MECHANICAL ELECTRICAL PLUMBING FIRE PROTECTION€¦ · (ct4021-gw1-ct4000-pmgmt-ct4001-ccm-cpcld-commerical-5-ct4000-assure5-cpsupport-active) basis of design: myparkingsign.com,

Rockwood Builders, Ltd. 11/14/2019

EV Charging Station for the Northland Transit Center

RFI Questions: 1. Are there any existing drawings of the Northland Transit Center Project?

2. On the drawings sheet E-003 and Coded Notes #2: along the trench line locations, there are two

(2) trees and one (1) existing sign in the way. There are no coded notes to remove and/or relocate these trees. Are these trees to be removed and/or relocated? If yes, please provide the location on the drawings. Also, is the existing sign encased in concrete below grade? See pictures below.

3. The new EV Charging Station concrete pad is 46” x 30” as shown on the drawings E-003 and coded notes #6 that is to be located in between the existing concrete curb and metal fence. The distance between the concrete curb inside edge and to the front side of the metal fence is approx. +/- 28”. There’s now indication on the drawing to remove and reinstall for the pad installation or to modify the new pad so that it fits within the +/- 28” gap. See pictures below

EXISTING SIGNAGE

EXISTING TREE

EXISTING TREE

30”

28”

GavinL
Text Box
See attached reference drawing from previous Civil Engineering project
GavinL
Text Box
Northland Drawing E-003 has been revised and attached
GavinL
Text Box
Northland Drawing E-002 has been revised and attached
Page 3: MECHANICAL ELECTRICAL PLUMBING FIRE PROTECTION€¦ · (ct4021-gw1-ct4000-pmgmt-ct4001-ccm-cpcld-commerical-5-ct4000-assure5-cpsupport-active) basis of design: myparkingsign.com,

4. The existing fence will be an obstacle for a trenching machine to maneuver along the parking lot island. Can we remove the fence? Are the fence posts encased in concrete below grade? What is the min. trench width and depth for both direct burial conduit and concrete encased duct bank? See picture below.

5. The trench line shows on the drawing going thru in between two existing bollards by the sidewalk area. Can you provide a detail of the bollard footer? What is the thickness of the existing concrete drive (assuming min. 8 – 10” thick), curb and sidewalk slab? See picture below.

6. Is the permit and inspection fees by the contractor or Advanced Engineer Consultant will provide a blanket permit and inspection fees for this project?

28”

48”

EXISTING BOLLARDS

EXISTING CONCRETE DRIVE

GavinL
Text Box
Please account for hand trenching as necessary. This island area will be direct buried conduits. Conduit depths are shown on E-001
GavinL
Text Box
Northland Drawing E-003 has been revised and attached
GavinL
Text Box
AEC has already filed and received a PLEX permit number from City of Columbus. However, the City may still charge the Contractor inspection fees, this shall be paid by the Contractor.
Page 4: MECHANICAL ELECTRICAL PLUMBING FIRE PROTECTION€¦ · (ct4021-gw1-ct4000-pmgmt-ct4001-ccm-cpcld-commerical-5-ct4000-assure5-cpsupport-active) basis of design: myparkingsign.com,
Page 5: MECHANICAL ELECTRICAL PLUMBING FIRE PROTECTION€¦ · (ct4021-gw1-ct4000-pmgmt-ct4001-ccm-cpcld-commerical-5-ct4000-assure5-cpsupport-active) basis of design: myparkingsign.com,

MN

#11

MN #

12

IP #

10

CLEVELAND AVENUE

NO

RTH

LAN

D P

LAZA

DR

IVE

GavinL
Text Box
COTA NORTHLAND FOR REFERENCE ONLY NOT FOR CONSTRUCTION
Page 6: MECHANICAL ELECTRICAL PLUMBING FIRE PROTECTION€¦ · (ct4021-gw1-ct4000-pmgmt-ct4001-ccm-cpcld-commerical-5-ct4000-assure5-cpsupport-active) basis of design: myparkingsign.com,

DUAL EV CHARGING STATION WITH BOLLARDMOUNTING KIT (CHARGEPOINT). INSTALL PERMANUFACTURER'S WRITTEN INSTRUCTION.PROVIDE FACTORY AUTHORIZED STARTUPAND TRAINING FOR THE OWNER'SREPRESENTATIVE.

GRADE

UTILIZING THE BID ALLOWANCE AS DESCRIBEDON SHEET E-001, PROVIDE CUSTOM AEP ANDCOTA LOGOS ON THE EV CHARGING STATION.COORDINATE EXACT GRAPHICS WITH AEP ANDCOTA AND COORDINATE PRINTING OF THELOGOS WITH THE MANUFACTURER.

46"

28"

9" 3"

36" R

2'-6"

MIN

.

90° BEND

REINFORCE WITH 6x6-W2-9/2-9EPOXY COATED MESH

CLASS "QC1"CONCRETE

4" MIN. COMPACTEDGRANULAR FILL

TO EXISTING PULLBOX

FRONT

PULL SERVICING WIRING UP THROUGH THE CONDUIT,LEAVING APROXIMATELY 6' EXTENDING OUT OF THECONDUIT. MAKE FINAL CONNECTIONS PERMANUFACTURER'S WRITTEN INSTRUCTIONS.

CHARGING STATION,SEE DETAIL 1

BOLLARD, FILL WITHCONCRETESEE DETAIL 2

1" GALVANIZED RIGID STEEL STUB UPCONDUIT

6"4"

12"

6"

8" 8"8" 14" 8"

BOLLARD

EV CHARGING STATION

BOLLARD

PLAN VIEW

SECTION

FRONT OF CONCRETE PAD SHALLBE INSTALLED FLUSH AGAINSTCURB OF PARKING LOT

3'-0"

MIN

.3'-

0"

BOLLARD, FILLWITH CONCRETESEE DETAIL 2

FIELD ADJUST DIMENSION TO FITCONCRETE PAD TIGHT TO FENCELINE

PROVIDE 8" DIAMETERCONCRETE ENCASEMENTAROUND BOLLARD

PROVIDE 8" DIAMETERCONCRETE ENCASEMENTAROUND BOLLARD

PROVIDE GREEN STRIPINGINSIDE EXISTING PARKINGLOT AROUND PERIMETEROF ENTIRE SPACE WHEREEV CHARGING STATION ISPROVIDED

EV CHARGING STATION.REFER TO PLANS FOR LOCATION.

CURBINSTALL SIGN FLUSHED WITH TOP OF POST (POSTSHALL BE INSTALLED 6' TO TOP). SEE DETAIL5/E-002

ELECTRICVEHICLEPARKING

ONLY

PROVIDE GREEN PAINTEDLETTERING WITHINPARKING SPACEELECTRIC

VEHICLEPARKING

ONLY

DATE:DRN:DSN:

SHEET:SCALE:

CHK:

OF 4

NOVEMBER 6, 2019

COTANORTHLAND TRANSIT CENTER

5495 CLEVELAND AVENUEEV CHARGING STATIONS

SUBMITTAL: BID SET

REV NUMBER REV DATEREV DESCRIPTION

A DVANCEDE NGINEERINGC ONSULTANTS

Mechanical | Electrical | Plumbing | Fire Protection1405 Dublin Road Tel: (614) 486-4778Columbus, Ohio 43215 Fax: (614) 486-4082

Date:

11/18

/2019

11:24

AM

File L

ocati

on:Z

:\201

9 pro

j\19-

008-

03 C

OTA

EV C

harg

ing\C

AD\C

AD S

heets

\3 No

rthlan

d Tra

nsit C

enter

\ Las

t Edit

:Gav

inL

E-002NONE 2

S. SMITHG. LIM

DETAILSELECTRICAL

NTS1 DETAIL - EV CHARGING STATION

NTS2 DETAIL - PROTECTION BOLLARD FOR CHARGING STATIONNTS3 DETAIL - BASE PLATE/BOLLARD MOUNTING FOR CHARGING STATION

BASIS OF DESIGN: VESTIL - BOLPP-62-5.5

NTS5 DETAIL - EV CHARGING STATION SIGNAGENTS4

DETAIL - TYPICAL EV CHARGING STATIONPARKING SPACE AND HARDWARE

NTS1 DETAIL - EV CHARGING STATION

NTS2 DETAIL - PROTECTION BOLLARD FOR CHARGING STATION

BASIS OF DESIGN: VESTIL - BOLPP-62-5.5

NTS3 DETAIL - BASE PLATE/BOLLARD MOUNTING FOR CHARGING STATION

BASIS OF DESIGN: CHARGEPOINT(CT4021-GW1-CT4000-PMGMT-CT4001-CCM-CPCLD-COMMERICAL-5-CT4000-ASSURE5-CPSUPPORT-ACTIVE)

BASIS OF DESIGN: myparkingsign.com, ITEM K-5507 (ENGINEER GRADE REFLECTIVE ALUMINUM)AND 8' BAKED ENAMEL POST ITEM K-153-8K.

1

1 ADDENDUM 1 11/18/2019

1

1

1

1

Page 7: MECHANICAL ELECTRICAL PLUMBING FIRE PROTECTION€¦ · (ct4021-gw1-ct4000-pmgmt-ct4001-ccm-cpcld-commerical-5-ct4000-assure5-cpsupport-active) basis of design: myparkingsign.com,

1

33

24

2

5

4

5

4

5

6

6

B-6,8

B-2,4

B-1,3

67 (TYP.)

8

M

B

9

10

11

DATE:DRN:DSN:

SHEET:SCALE:

CHK:

OF 4

NOVEMBER 6, 2019

COTANORTHLAND TRANSIT CENTER

5495 CLEVELAND AVENUEEV CHARGING STATIONS

SUBMITTAL: BID SET

REV NUMBER REV DATEREV DESCRIPTION

A DVANCEDE NGINEERINGC ONSULTANTS

Mechanical | Electrical | Plumbing | Fire Protection1405 Dublin Road Tel: (614) 486-4778Columbus, Ohio 43215 Fax: (614) 486-4082

01"=20'-0" 10' 20' 40'1 ELECTRICAL SITE PLAN

CODED NOTES:

1. APPROXIMATE LOCATION OF EXISTING ELECTRICAL/DATA ROOM.

2. PROVIDE ONE 2" UNDERGROUND CONDUIT FOR POWER TO SERVE PULLBOX. PRIORTO TRENCHING WORK, CONTRACTOR SHALL PROVIDE GROUND PENETRATING RADARSCANNING TO VERIFY THAT THERE ARE NO CONFLICTS WITH OTHER UTILITIES.

3. PROVIDE 17" X 30" X 18" UNDERGROUND PULLBOX (QUAZITE) TO SERVE EV CHARGINGSTATIONS.

4. PROVIDE 12" X 12" X 12" UNDERGROUND PULLBOX (QUAZITE) TO SERVE ELECTRICVEHICLE CHARGER FEEDERS.

5. PROVIDE ONE 2" UNDERGROUND CONDUIT VIA PULLBOXES TO EV CHARGERS.

6. APPROXIMATE LOCATION OF EV CHARGING STATION CONCRETE PAD. REFER TODETAILS ON E-002. VERIFY EXACT LOCATION WITH OWNER PRIOR TO ROUGH-IN.

7. PROVIDE #8AWG CONDUCTORS BETWEEN PULLBOX AND CHARGING STATION(TYPICAL OF 3 LOCATIONS).

8. PROVIDE CONCRETE ENCASEMENT FOR UNDERGROUND CONDUITS BENEATHDRIVEWAY.

9. PROVIDE 150A SUB-FEED (UNDER 10') WITH 2 - #1/0 AWG CONDUCTORS AND #6 AWGGROUND IN 2" RGS CONDUIT FROM EXISTING PANEL "A" IN ELECTRICAL ROOMTHROUGH UTILITY (AEP) METER TO SERVE PANEL "B". PROVIDE WALL MOUNTEDMETER BASE FOR AEP METER. COORDINATE EXACT REQUIREMENTS WITH AEP.METER SHALL BE SUPPLIED BY AEP AND INSTALLED BY THE CONTRACTOR

10. PROVIDE 150A, 240/120V, 1Ø, NEMA 3R PANELBOARD FOR EV CHARGING STATIONS.MOUNT ON WALL BY METER. ATTACH WEATHER-RESISTANT VINYL LABEL ONPANELBOARD STATING "FOR EV CHARGERS ONLY". REFER TO PANEL SCHEDULE ONSHEET E-001.

11. CONTRACTOR SHALL REMOVE AND DISPOSE THE TREE AT THIS LOCATION.

N

Date:

11/18

/2019

11:25

AM

File L

ocati

on:Z

:\201

9 pro

j\19-

008-

03 C

OTA

EV C

harg

ing\C

AD\C

AD S

heets

\3 No

rthlan

d Tra

nsit C

enter

\ Las

t Edit

:Gav

inL

E-0031" = 20'-0" 3

M. CALDWELLG. LIM

SITE PLANELECTRICAL

1 ADDENDUM 1 11/18/2019

1

1

Page 8: MECHANICAL ELECTRICAL PLUMBING FIRE PROTECTION€¦ · (ct4021-gw1-ct4000-pmgmt-ct4001-ccm-cpcld-commerical-5-ct4000-assure5-cpsupport-active) basis of design: myparkingsign.com,

DUAL EV CHARGING STATION WITH BOLLARDMOUNTING KIT (CHARGEPOINT). INSTALL PERMANUFACTURER'S WRITTEN INSTRUCTION.PROVIDE FACTORY AUTHORIZED STARTUPAND TRAINING FOR THE OWNER'SREPRESENTATIVE.

GRADE

UTILIZING THE BID ALLOWANCE AS DESCRIBEDON SHEET E-001, PROVIDE CUSTOM AEP ANDCOTA LOGOS ON THE EV CHARGING STATION.COORDINATE EXACT GRAPHICS WITH AEP ANDCOTA AND COORDINATE PRINTING OF THELOGOS WITH THE MANUFACTURER.

46"

30"

9" 3"

36" R

2'-6"

MIN

.

90° BEND

REINFORCE WITH 6x6-W2-9/2-9EPOXY COATED MESH

CLASS "QC1"CONCRETE

4" MIN. COMPACTEDGRANULAR FILL

TO EXISTING PULLBOX

FRONT

PULL SERVICING WIRING UP THROUGH THE CONDUIT,LEAVING APROXIMATELY 6' EXTENDING OUT OF THECONDUIT. MAKE FINAL CONNECTIONS PERMANUFACTURER'S WRITTEN INSTRUCTIONS.

CHARGING STATION,SEE DETAIL 1

1" GALVANIZED RIGID STEEL STUB UPCONDUIT

8"4"

12"

6"

8" 8"8" 14" 8"

BOLLARD

EV CHARGING STATION

BOLLARD

PLAN VIEW

SECTION

FRONT OF CONCRETE PAD SHALLBE INSTALLED FLUSH AGAINSTCURB OF PARKING LOT

3'-0"

MIN

.3'-

0"

BOLLARD, FILL WITHCONCRETESEE DETAIL 2

BOLLARD, FILLWITH CONCRETESEE DETAIL 2

PROVIDE 8" DIAMETERCONCRETE ENCASEMENTAROUND BOLLARD

PROVIDE 8" DIAMETERCONCRETE ENCASEMENTAROUND BOLLARD

PROVIDE GREEN STRIPINGINSIDE EXISTING PARKINGLOT AROUND PERIMETEROF ENTIRE SPACE WHEREEV CHARGING STATION ISPROVIDED

EV CHARGING STATION.REFER TO PLANS FOR LOCATION.

CURB

INSTALL SIGN FLUSHED WITH TOP OF POST(POST SHALL BE INSTALLED 6' TO TOP). SEEDETAIL 5/E-002

ELECTRICVEHICLEPARKING

ONLY

PROVIDE GREEN PAINTEDLETTERING WITHINPARKING SPACEELECTRIC

VEHICLEPARKING

ONLY

Date:

11/18

/2019

11:29

AM

File L

ocati

on:Z

:\201

9 pro

j\19-

008-

03 C

OTA

EV C

harg

ing\C

AD\C

AD S

heets

\2 No

rther

n Ligh

ts\ L

ast E

dit:G

avinL

E-002NONE 2

S. SMITHG. LIM

DETAILSELECTRICAL

DATE:DRN:DSN:

SHEET:SCALE:

CHK:

OF 4

NOVEMBER 6, 2019

COTANORTHERN LIGHTS PARK AND RIDE

3573 CLEVELAND AVENUEEV CHARGING STATIONS

SUBMITTAL: BID SET

REV NUMBER REV DATEREV DESCRIPTION

A DVANCEDE NGINEERINGC ONSULTANTS

Mechanical | Electrical | Plumbing | Fire Protection1405 Dublin Road Tel: (614) 486-4778Columbus, Ohio 43215 Fax: (614) 486-4082

NTS1 DETAIL - EV CHARGING STATION

NTS2 DETAIL - PROTECTION BOLLARD FOR CHARGING STATIONNTS3 DETAIL - BASE PLATE/BOLLARD MOUNTING FOR CHARGING STATION

BASIS OF DESIGN: VESTIL - BOLPP-62-5.5

NTS5 DETAIL - EV CHARGING STATION SIGNAGE

BASIS OF DESIGN: myparkingsign.com, ITEM K-5507 (ENGINEER GRADE REFLECTIVE ALUMINUM)AND 8' BAKED ENAMEL POST ITEM K-153-8K.

NTS4

DETAIL - TYPICAL EV CHARGING STATIONPARKING SPACE AND HARDWARE

BASIS OF DESIGN: CHARGEPOINT(CT4021-GW1-CT4000-PMGMT-CT4001-CCM-CPCLD-COMMERICAL-5-CT4000-ASSURE5-CPSUPPORT-ACTIVE)

1 ADDENDUM 1 11/18/2019

1

1

1

1