Measuring Transducers

Embed Size (px)

Citation preview

  • 7/24/2019 Measuring Transducers

    1/8

    M easuring Transducers

    AC, DC POWER SYSTEM MEASUREMENT MICROPROCESSOR CONTROL HOUSING FOR DIN RAIL MOUNTING IN

    COMPLIANCE WITH EN 50022 PROGRAMMABLE VOLTAGE INPUT RANGE PROGRAMMABLE CURRENT INPUT RANGE PROGRAMMABLE ANALOGUE OUTPUT SERIAL COMMUNICATION RS232/RS485 (OPTION) UP TO THREE ELECTRICALLY ISOLATED ANALOGUE OUTPUTS UNIVERSAL AUXILIARY POWER SUPPLY (OPTION) ACCURACY CLASS 0.5 (FREQUENCY TRANSDUCER 0.2) CURRENT INPUTS ELECTRICALLY ISOLATED FROM THE SYSTEM

    OUTPUTS, SERIAL COMMUNICATION, AUXILIARY POWER SUPPLY, CURRENT AND VOLTAGE INPUTS GALVANICALLY SEPARATED (SOME MODELS)

    Features

    Measuring TransducersTransducing electrical quantities Iskra MI d.d.

  • 7/24/2019 Measuring Transducers

    2/8

  • 7/24/2019 Measuring Transducers

    3/8

    TYPE MI400 MI413 MI414 MI421Class 0.5 1Power supply With auxiliary power supply Measuring principle Microprocessor control

    Input q ua nt ity Prog ra mma ble Ac tive power React ive power Power fac tortra nsducer t ra nsduce r tra nsducer measu ring

    Measuring range -Pn...0...Pn -Pn...0...Pn -Qn...0...Qn Cap. 0...1...0 Ind.-Qn...0...Qn 0...Pn 0...Qn -180...0...+180-Sn...0...Sn

    Cap. 0...1...0 Ind.-180...0...+180

    45...65 Hz0...1.2 Un0...1.2 In

    Input voltage Un 0...50 - 500 VNominal voltage Programmable rangeInput current In 0...0.5 - 5 ANominal current Programmable range

    Nominal frequency 50/60 HzConsumption/Input Voltage circuit: U2 /3 M Current circuit: 2 x 0.01 resistanceOverload capability 1.5 Un; 2 InPower supply 57, 100, 110, 230, 400, 500 V AC, 20%, 45...65 Hz 3 VA

    Universal auxiliary power supply 24...300 V DC 40...276 V AC

    Range selection Programmable range over communication, at placing orderNumbers of analogue 0, 1, 2 and 3 1outputsCurrent nominal values -1 mA...0 (0.2)...1 mA

    -5 mA...0 (1)...5 mA-10 mA...0 (2)...10 mA-20 mA...0 (4)...20 mA

    Voltage nom. values -1 V...0... 1 V, -10 V... 0...10 VHarmonic analysis Yes (Optional) -Maximum Demand Yes -Communication RS232 or RS485 RS232, RS485 (optional)Residual ripple < 1 % p.p.on nominal currentResponse time < 300 msBurden max. I output 5 mA 3 k, 10 mA 1.5 k,

    min. U output 20 mA 750, 10 V 500Ref. measuring range 0+50C Working temperature -10+55CStorage temperature -40...+70C

    Climatic class 3 according to EN 60688General technical data Protection system: IP 50, terminals IP20, according to EN 60529, 1989

    Protection class: II, III cat. (300 Vrms), II cat. (500 Vrms)Test voltage: 3.7 kV rms according to EN 61010-1: 1990

    Characteristic curves A, B, C, DDimensions A = 100 mm, B = 75 mm, C = 104.5 mm

    Differences between measuring transducers

    Ou r measu ring t ra nsducers ca n be d ivided i nto two g roups: MI40 0 mu ltifunc tiona l measu ring t ra nsducer a nd allthe others.MI40 0 is t he most power ful mu ltifunct iona l meas uring tra nsducer. It super vises simu lta neously a ny 3 va lues of a ne lectrica l s ystem. It has the capa bil ity of measu ring more t ha n 50 d iffe re nt e lectr ical q ua nt ities such as: TRMSva lues of voltage, c urrent, kW, kvar, kVA, PF, Hz, MD, THD etc i n one inst rument. A ll va lues a re ava ila ble v iacom mu nicat ion port for monitor ing on t he PC. It ca n have up to three con f ig ura ble a na log ue out puts, wh ich a re

    prog ra m ma ble. P rog ram ma ble are a lso CT a nd V T rat ios. All the othe r measu ring t ra nsducers compose group MI4x x (4xx g reate r than 40 0). Each measu ring tra nsduce r i nth is group is ta ilored for measu ring one elect rica l qua nt ity. I n the ta ble below you ca n see wh ich fu nc tional ity iscovered by w hich ins tru ment a nd inst rument's i nput a nd output va lues.

    INPUT

    OUTPUT

  • 7/24/2019 Measuring Transducers

    4/8

    TYPE MI436 MI438 MI420Class 0.5 0.2Power supply With auxiliary power supply Measuring principle Microprocessor control

    Input q ua ntit y 3 x AC - 3 x AC - Freq uency Voltage Cu rrent

    Measuring range 0..50 V to 0..500 V 0..6 A, 1 A, 5 A 40 to 70 HzInput voltage 500 V programmable, 3...500 VNominal voltage 57.74, 63.5, 100, 110,

    230, 250, 400, 500 Vfixed configuration

    Input current 6 A programmableNominal current 1 A, 5 A fixed

    configuration

    Nominal frequency 50/60 Hz

    45...55 Hz48...52 Hz45...65 Hz55...65 Hz

    Consumption / Input U2 / 3 M I2 0.01 < 0.5 VAresistanceOverload capability 1.2 Un 2 In 1.2 UnPower supply Universal auxiliary power supply 57, 100, 110, 230, 400,

    24...300 V DC, 40...276 V AC, 40...70 Hz, < 3 VA 500 V AC,20%,Universal auxiliary

    power supply 24...300 VDC 40...276 V AC

    Range selection Programmable range over communication, at placing orderNumber of analogue 3 1outputsCurrent nominal values 0 (0.2)...1 mA 5 mA, 20 mA

    0 (1)...5 mA programmable10 mA fixed configuration 5 mA, 10 mA, 20 mA,

    0 (4)...20 mA 4...20 mA fixed4...20 mA fixed configuration

    Voltage nom. values 0...1 V to 0...10 V 10 V programmable,fixed

    Harmonic analysis Yes (Optional) -Maximum Demand - Yes (thermal function) -

    Communication RS232, RS485 (optional)Residual ripple on < 1% p.p.nominal currentResponse time < 300 ms

    Burden max. Ioutput 5 mA 3 k, 10 mA 1.5 k, 20 mA 750, 10 V 500min. Uoutput

    Ref. measuring range 0+50C Working temperature -10+55C -10+55CStorage temperature -40 to +70 C -40...+70CClimatic class 3 according to EN 60688 3 according to EN 60688General technical data Protection system: IP 50, terminals IP20, according to EN 60529, 1989

    Protection class: II, III cat. (300 Vrms), II cat. (500 Vrms)Test voltage: 3.7 kV rms according to EN 61010-1: 1990

    Characteristic curves A, B A, B, DDimensions A = 100 mm, B = 75 mm, A = 44.8 mm, B = 75 mm,

    C = 104.5 mm C = 104.5 mm

    INPUT

    OUTPUT

  • 7/24/2019 Measuring Transducers

    5/8

    TYPE MI406 MI408 MI416 MI418Class 0.5Power supply Without auxiliary power supply With auxiliary power supply Measuring principle Rectifier method Microprocessor control

    Input q ua nt ity AC - Voltage AC - Cu rrent RMS RMS AC - Voltage AC - C ur re nt

    Measuring range 0.2...Un 0...In 0...1.2 Un 0...1.2 InInput voltage Un 0...20 to 0...500 V Un 0...50 V to 0...500 V

    programmable rangeNominal voltage 57.74, 63.5, 100, 57.74, 63.5, 100,

    110, 250, 500 V 110, 230, 250, 400, 500 VInput current In 0...1 A to 0...7.5 A In 0..6 A

    programmable rangeNominal current 1 A, 5 A In 1 A, 5 A fixed

    configurationNominal frequency 50/60 HzConsumption / Input < 2 VA < 2 VA < 0.5 VA < 0.5 VAresistanceOverload capability 1.2 Un 2 In 1.2 Un 2 InPower supply

    Power supply from measuring circuit

    57, 100, 110, 230, 400, 500 V AC, 20 %,45...65 Hz 3 VA

    Universal auxiliary power supply24...300 V DC, 40...276 V AC

    Range selection At placing order Programmable range over

    communication, at placing orderNumber of analogue outputs 1Current nominal values 0...5 mA 0 (0.2)...1 mA

    0...10 mA 0 (1)...5 mA0...20 mA 0 (2)...10 mA

    0 (4)...20 mA Voltage nom. values 0...1 V, 0...10 VHarmonic analysis - Yes (Optional)Maximum Demand -Communication - RS232, RS485 (optional)Residual ripple on

    < 1% p.p.nominal currentResponse time < 300 msBurden max. Ioutput 5 mA 3 k, 10 mA 1.5 k, 5 mA 3 k, 10 mA 1.5 k,min. Uoutput 20 mA 750 20 mA 750, 10 V500 Ref. measuring range 0+50C Working temperature -10+55CStorage temperature -40...+70CClimatic class 3 according to EN 60688General technical data Protection system: IP 50, terminals IP20, according to EN 60529, 1989

    Protection class: II, III cat. (300 Vrms), II cat. (500 Vrms)Test voltage: 3.7 kV rms according to EN 61010-1: 1990

    Characteristic curves A A, B, DDimensions A = 44.8 mm, B = 75 mm, C = 104.5 mm

    INPUT

    OUTPUT

  • 7/24/2019 Measuring Transducers

    6/8

    TYPE MI450 MI452 MI454Class 0.5Power supply With auxiliary power supply Measuring principle Microprocessor control

    Input q ua ntit y Te mperat ure Resista nce Pote nciomete r &Pt 100 TAP posit ion

    Measuring range 0..20 to 0..10 k 0...Rn 0..100 to 0..500kUn < 2.2 V R0Rn...R0 Un < 2.2 V

    Input value -200C+850C for Pt Rn 0..10 - 50 k Rn 100 to 500 k-60C+250C for Ni 0..100 - 500 k programmable

    20 to 10 k for programmablepolinom programmable

    Nominal value 0 to 100, 0 to 250, Rn 100, 1 k, 2 k, 5 k, Rn 100, 1 k, 2 k, 5 k, 10 k-100 to 800C for Pt 10 k, 20 k, 50 k fixed 20 k, 50 k, 100 k, 200 k,0 to 100, 0 to 180, Rn 5 k, 10 k, 50 k, 100 k, 500 k 0-linear-50 to 150C for Ni 200 k, 500 k fixed Rn 300, 1 k, 2 k, 5 k, 10 k,

    fixed configuration 20 k, 50 k, 100 k, 200 k,500 k 10 steps

    (both fixed configuartion)Nominal frequency -Consumption / Input < 0.5 VAresistancePower supply 57, 100, 110, 230, 400, 500 V AC, 20 %,

    Universal auxiliary power supply: 24...300 V DC,40... 276 V AC

    Range selection Programmable range over communication, at placing orderNumber of analogue 1outputsCurrent nominal -1...0 (0.2)...1 mA 0 (0.2)...1 mA values -5...0 (1)...5 mA 0 (1)...5 mA

    -20...0 (4)...20 mA 0 (4)...20 mA Voltage nom. values -1...0...1 V, -10...0...10 V 0...1 V, 0...10 VHarmonic analysis -Maximum Demand -

    Communication RS232, RS485 (optional)Residual ripple on < 1 % p.p.nominal currentResponse time Programmable 0.5 s to 60 sBurden max. Ioutput

    min. Uoutput 5 mA 3 k, 10 mA 1.5 k, 20 mA 750, 10 V 500Ref. measuring range 0+50C Working temperature -10+55CStorage temperature -40...+70CClimatic class 2 according to EN 60688General technical Protection system: IP 50, terminals IP20, according to EN 60529, 1989data Protection class: II, III cat. (300 Vrms), II cat. (500 Vrms)

    Test voltage: 3.7 kV rms according to EN 61010-1: 1990Characteristic curves A, B, C, D ADimensions A = 44.8 mm, B = 75 mm, C = 104.5 mm

    INPUT

    OUTPUT

  • 7/24/2019 Measuring Transducers

    7/8

    TYPE MI456 MI458 MI485Class 0.5 -Power supply With auxiliary power supply Measuring principle Microprocessor control -

    Input q ua ntit y DC - DC - RS232 to Voltage Cu rrent RS485

    Measuring range 0...Un 0...In RS485-Un0...Un -In0...In Bit rate to115200 bit/s

    Input value Un 0...50 mV 1 V In 0...1 10 mA -0..1 50 V 0...10 100 mA

    0..50 300 V programmableprogrammable

    Nominal input Un 50, 100, 500 mV, In 1, 1.5, 2, 2.5, 4, 5, 6,1 V fixed 10 mA fixed

    1.5, 2, 2.5, 4, 5, 6, In 15, 20, 25, 40, 50,10, 15, 20, 25, 40, 60, 100 mA fixed

    50 V fixed60, 100, 150,

    200, 250, 400 V fixedNominal frequency DC -Consumption / < 0.5 VA < 0.5 VAInput resistanceOverload capability 1.2 Un 2 In -Power supply 57, 100, 110, 230, 400, 500 V AC, 20 %, 45...65 Hz 3 VA

    Universal auxiliary power supply 24...300 V DC 40...276 V AC

    Range selection Programmable range over communication RS232at placing order Electrically isolated

    Number of analogue 1 Terminals or SUB Doutputs connectorCurrent nominal -1 mA...0 (0.2)...1 mA Indication values -5 mA...0 (1)...5 mA communication with

    -20 mA...0 (4)...20 mA LED Diode Voltage nom. values -1V...0...1V, -10V...0...10VHarmonic analysis -Maximum Demand -Communication RS232, RS485 (optional) -

    Residual ripple on < 1% p.p. -nominal current

    Response time Programmable 0.5s to 3s -Burden max. Ioutput

    min. Uoutput 5 mA 3 k, 10 mA 1.5 k, 20 mA 750, 10 V 500 -Ref. measuring range 0+50C Working temperature -10+55CStorage temperature -40...+70CClimatic class 3 according to EN 60688General technical data Protection system: IP50, terminals IP20, according to EN 60529, 1989

    Protection class: II, III cat. (300 Vrms), II cat. (500 Vrms)Test voltage: 3.7 kV rms according to EN 61010-1: 1990

    Characteristic curves A, B, C, D -Dimensions A = 44.8 mm, B = 75 mm, C = 104.5 mm

    INPUT

    OUTPUT

    Note: Transducers according to EN 606881, EN 610101

  • 7/24/2019 Measuring Transducers

    8/8

    a) linear characteristic

    c) zoom absolute value d) zoom

    b) up to 5 break points

    Case dimensions

    Ordering infoOrdering informations for each transducer are available in technical leaflets.

    Characteristic curves