Page 1: Mcs831e-Adx User Manual

SCANNER

MCS831E-ADX

User Manual

Firmware version 3.1

MICRO SYSTEMS & CONTROLS www.mscontrols.com e-mail: [email protected] ISO 9001:2000

Certified Company

DECEMBER 2007 REV 04

Page 2: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 2 of 39

TABLE OF CONTENTS

1.0 INTRODUCTION………………………………………………………………………….. 4

1.1 DESCRIPTION…………………………………………………………………….. 4

1.2 SAFETY CONSIDERATIONS……………………………………………………. 4

2.0 FRONT PANEL SETUP………………………………………………………………….. 5

2.1 DISPLAY…………………………………………………………………………….. 5

2.2 LEDs…………………………………………………………………………………. 5

2.3 KEY SWITCHES………………………………………………………….………… 7

3.0 OPERATION…………………………………………………………………….…………. 8

3.1 INTRODUCTION……………………………………………………………………. 8

3.2 RUN MODE……………………………………………………………….…………. 8

3.3 PROG / MENU CONFIGURATION MODE………………………………………. 10

4.0 INSTALLATION & CONNECTION……………………………………………..………... 23

4.1 INSTALLATION……………………………………………………………………... 23

4.2 POWER CONNECTION…………………………………………………………… 23

4.3 SENSOR CONNECTION………………………………………………………….. 24

4.4 RELAY CONNECTION…………………………………………………………….. 25

4.5 TERMINAL ASSIGNMENT, CONNECTION…………………………………….. 26

5.0 DIMENSION & PANEL CUTOUT……………………………………………………….. 29

6.0 COMMISSIONING. …………………………………………………………….…………. 30

7.0 INPUT ERROR DISPLAY………………………………………………………………… 30

8.0 SELF TEST ERROR CODES……………………………………………………………. 30

9.0 SCANNER SPECIFICATIONS…………………………………………………………… 31

10.0 CALIBRATION……………………………………………………………………………… 32

Appendix A: SYSTEM CONFIGURATIONS (FACTORY SET)

Appendix B: SYSTEM CONFIGURATIONS (USER RECORD)

NOTES

HOW TO CONTACT MICRO SYSTEMS & CONTROLS

Page 3: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 3 of 39

NOTES, CAUTIONS and WARNINGS

NOTE

CAUTION OR IMPORTANT

WARNING

Page 4: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 4 of 39

1. INTRODUCTION

1.1 DESCRIPTION

MCS831E-ADX is the latest series of advanced cost effective temperature and process scanners from Micro Systems & Controls. It incorporates advanced software features and a dual micro controller based design to provide complete user flexibility and can cater to almost all monitoring and data acquisition needs of the user. It can be user programmed to cover different application needs thus reducing time, inventory and spares cost. It accepts direct signals from thermocouples, RTDs and linear voltage and current inputs, either as fixed type or programmable universal input. Each channel is sequentially scanned and active channels are displayed, Individual channels can be locked for monitoring using the HOLD key. Flexible alarm logic and grouping is provided to energize alarm relay outputs as per the process parameter values and programmed set points. All features of the scanner are programmable from the keyboard making it a truly universal scanner. Serial communication options are provided to enable the scanner to be used in DAS front-end applications. Optional windows based MicroDAS software is also available from 8 to 128 channels for monitoring and data logging using multidrop RS485 option. All programmed values are stored permanently in non-volatile memory. Set parameters are protected by password so that they cannot be tampered with. 1.2 SAFETY CONSIDERATIONS

This instrument is a panel mount device for measurement, control and laboratory. Installation of this instrument should be done by qualified personnel. In order to ensure safe operation, the following instructions should be followed.

• Do not exceed voltage rating on the label located on the top of the instrument housing.

• Do not operate this instrument in flammable or explosive atmospheres.

• Do not expose this instrument to rain or moisture.

• Unit mounting should allow for adequate ventilation to ensure instrument does not exceed operating temperature rating.

• Use electrical wires with adequate size to handle mechanical strain and power requirements. Install without exposing bare wire outside the connector to minimize electrical shock hazards.

This instrument has no power-on switch. An external switch or circuit-breaker shall be included in the building installation as a disconnecting device. It shall be marked to indicate this function, and it shall be in close proximity to the equipment within easy reach of the operator.

Furthermore, to provide protection against excessive energy being drawn from the main supply in case of a fault in the equipment, an overcurrent protection device shall be installed.

Page 5: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 5 of 39

EMC Considerations

• Whenever EMC is an issue, always use shielded cables.

• Never run signal and power wires in the same conduit. Use signal wire connections with twisted-pair cables.

Failure to follow all instructions and warnings may result in injury!

2. FRONT PANEL SETUP

2.1 DISPLAY

2 digit LED for Channel Number. 3 digit LED for Multi Function Display 5 digit LED for Process Value.

2.2 LEDs

2.2.1 STATUS LEDs

PROG – On in Program condition.

RUN – On in RUN condition.

HOLD – Flashing in HOLD mode or MANUAL mode.

ER – Not Used

TX – Not Used

RX – Not Used DEG C – On for unit Deg.C.

2.2.2 ALARM STATUS LED

ALARM STATUS LED ‘A1’: Alarm LEDs 16 nos. These are ON when the particular channel has exceeded its set Alarm 1 limit. ALARM STATUS LED ‘A2’: Alarm LEDs 16 nos. These are ON when the particular channel has exceeded its set Alarm 2 limit.

2.2.3 RELAY LEDs RELAY LEDs: 8 Relay LEDs are provided to indicate the relay status.

Page 6: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 6 of 39

1 2 3 4 5 6 7 8

9 10 11 12 13 14 15 16

A2

A1

A2

A1

CHANNEL FN

VALUE

PROG RUN HOLD

ALARM

PROG

RUN

ON

OFF

PRN

NEXT

ACK

ENTER

HOLD

CLEAR

Micro Scanner ADX

MCS831EMICRO SYSTEMS

& CONTROLS

1 2 3 4 5 6 7 8

9 10 11 12 13 14 15 16

RELAY

ER TX RX

CO

MCS831E ADX FRONT PANEL

3 DIGIT FUNCTION DISPLAY

5 DIGIT VALUE DISPLAY

2 DIGIT CHANNEL DISPLAY

STATUS LEDs

ALARM LEDs

KEYBOARD

RELAY STATUS LEDs

Page 7: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 7 of 39

2.3 KEY SWITCHES

Eight key switches are provided on the front panel as follows:-

PROG

RUN

HOLD

CLEAR

ACK

ENTER

PRN

NEXT

ON

OFF

[PROG/RUN] key, this key when pressed simultaneously with [NEXT] key, takes the system from ‘RUN’ mode to ‘PROG’ mode. When [PROG/RUN] key is pressed in ‘PROG’ mode the system goes to ‘RUN’ mode.

[UP ARROW] key, this key is used to increase the channel number in ‘MANUAL SCAN or HOLD’ mode and increase the set parameter in ‘PROG’ mode.

[HOLD/CLEAR] key, this key when pressed in AUTO RUN mode takes system to HOLD, if this key is pressed again HOLD is cleared.

[PRN / NEXT] this key is pressed in programming mode to increase the channel number.

Not used

[DOWN ARROW] key, this key decreased the channel number in ‘MANUAL SCAN or HOLD’ mode and decreases the set parameter in ‘PROG’ mode.

[SCROLL] key, this key is used to select NEXT parameter.

[ENTER/ACK] key, In ‘PROG’ mode this key is used for storing the set parameter in memory.

Page 8: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 8 of 39

3. OPERATION 3.1 INTRODUCTION The Scanner has two different modes of operation, ‘RUN’ mode and ‘PROG’ / MENU CONFIGURATION mode. The first - RUN mode is the normal operating mode of the scanner in this mode the scanner scans the input channels, displays the process values and channel information, and monitors the alarm limits. The other mode ‘PROG’ or Menu configuration mode is used to navigate through the menu options and configure the scanner as per user requirement.

For your instrument to operate properly the user must first program or configure the

system through the configuration menu. 3.2 RUN MODE 3.2.1

On power on a self test is done and all LEDs and displays light up for a few seconds, the scanner then displays the hardware configuration setup sequentially for a few seconds. The ‘Fn’ display shows ‘Su’ (setup). The value window displays the following information: -

1. v xx = Version Number 2. Ch xx = Number of channels 3. rL xx = Number of relays provided. 4. Input type available (First type) 5. Input type available (Last type)

If only one input type is available item 4 and 5 will be the same. If more than one type

is available item 4 will display the first input from the input list and 5 will display the last item from the list , all inputs in between will be available. After the setup display the system is ready and the display indicates: MCS rdy The scanner enters RUN mode and normal scanning operation is performed. If any channel has exceeded its Alarm set points the corresponding channel alarm LED starts flashing and if any relay is assigned to the alarm the corresponding relay is also energized. Alarms can be programmed to be latching ‘TRIP’ or non-latching ‘ALARM only’ types. Refer to section 3.2.3 ALARM OPTIONS for details.

Page 9: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 9 of 39

3.2.2 AUTO / MANUAL SCAN MODE Two display scanning options are provided namely AUTO and MANUAL. In Auto display scanning mode the channel display scanning of the system is automatic and the display shows the channel number and its corresponding values sequentially as per selected rate. Pressing the [HOLD/SCAN] key in auto mode would hold the particular channel value and HOLD LED would keep flashing. Pressing the [HOLD/SCAN] key again would revert to auto sequential display scanning. In Manual display scanning mode HOLD LED is steady on. The system operates in manual mode indicating the current channel number and its value continuously on the display. The channel number could be increased / decreased by using [UP] or [DOWN] keys.

3.2.3 ALARM OPTIONS

Alarms are arranged in two groups A1 and A2, each channel has one alarm from A1 group and one alarm from A2 group. Each groups alarm mode can be configured for non-latching (ALARM only) or latching (TRIP) Mode operation. The sensor break or error condition output for each group can also be set separately. 3.2.3.1 ALARM MODES

ALARM only – Non latching (auto reset) mode, in this mode once a channel crosses its alarm set point the corresponding alarm LED starts flashing and the associated relay if any is energized. If [ENTER / ACK] key is pressed the LED becomes steady and the alarm relay is de-energized. When channel value returns to normal the alarm LED is OFF, if the alarm was not acknowledged earlier both the LED and relay are automatically reset.

TRIP – Latching mode, in this mode once a channel crosses its alarm set point the corresponding alarm LED starts flashing and the associated relay if any is energized. If [ENTER / ACK] key is pressed the LED becomes steady and the alarm relay continues to be ON. When channel value returns to normal if alarm was acknowledged the alarm LED and relay is reset.

In all cases the internal channel scanning and alarm monitoring is always maintained irrespective of the display mode.

In ALARM only mode, alarm relay is automatically reset as soon as channel value return to normal or fault is acknowledged. This mode is normally used where an audio alarm / electronic hooter is connected to the relay output and needs to be disabled as soon as the operator acknowledges the alarm. Or an external alarm annunciator unit is used.

In TRIP mode the alarm is required to be acknowledged by pressing the [ENTER / ACK] key so that the alarm LED and relay is reset when process value returns to normal.

Page 10: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 10 of 39

3.2.3.2 ALARM OUTPUT IN SENSOR BREAK / ERROR CONDITION The alarm output status for each group on sensor break or error condition can be separately set to either enable alarm or disable alarm under such conditions. 3.2.3.3 ALARM TYPE The type of alarm ‘High alarm’ or ‘Low alarm’ or ‘Alarm off’ can be separately programmed for each channel. Four combinations are available for each channel:

TYPE A1 A2 REMARKS

OFF ALARM OFF ALARM OFF -

H-L HIGH ALARM LOW ALARM -

H-VH HIGH ALARM VERY HIGH ALARM Set A2 > A1

L-VL LOW ALARM VERY LOW ALARM Set A1 > A2

3.2.3.4 A1 & A2-ALARM SET POINTS The A1 and A2 alarm set points for each channel can be set independently for all channels.

3.3 PROG MODE / MENU CONFIGURATION MODE This mode is used for programming or configuring the scanner as per user requirement. This mode is protected by two level security code, the first level is the USER LEVEL where access is available to the normal configuration parameters required by the user. The second level is the FULL ACCESS LEVEL, which is normally required only during initial setup of the scanner.

To ensure that the scanner is not left in PROG mode, the scanner automatically returns to RUN mode if no keyboard activity is detected within 30 seconds. 3.3.1 ENTERING PROG MODE

To enter into PROG. mode , keep [PROG/RUN] key pressed at the time of power on. (If scanner is running press [PROG/RUN] key and [PRN/NEXT] keys simultaneously)

To configure alarms as High - Very high or Low - Very Low for each channel appropriate set points A1 and A2 are to be configured as functionally both A1 & A2 are identical.

In PROG mode system does not monitor the inputs and the relays remain in the previous state.

Page 11: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 11 of 39

Display changes to

UPS 101 Enter the security code for the access level required in place of 101 by using the [UP] or [DOWN] keys and press [ENTER] key, if correct security code is entered the first item of the program menu will be displayed. PROGRAM MENU SECURITY CODES:

3.3.2 NAVIGATING THE PROGRAM MENU The program menu can be navigated by using the following keys: [NEXT] (Right arrow) key – Go to the next item in the menu. [UP] key – Increment parameter or move up item sub menu. [DOWN] key – Decrement parameter or move down item sub menu. [ENTER/ACK] key – Save the selection. [PRN/NEXT] key – Go to next channel in the sub menu. [PROG/RUN] Key – Exit the PROG mode or exit from Channel Name sub menu.

3.3.3 PROGRAM MENU FLOWCHART

The Program Menu Flowchart indicates the Program Menu layout. P-XX indicates the parameters displayed in this menu where XX is the parameter number from 01 to 24. By using NEXT key you can navigate through the menu parameters and configure the same.

USER LEVEL SECURITY CODE = 24 FULL ACCESS SECURITY CODE = 135

If the [UP] or [DOWN] key is kept pressed the displayed parameter increases or decreases at a fast rate.

Page 12: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 12 of 39

SELECT

CHANNEL

MODE

SCAN RATE

FUNCTION

CHANNEL SKIP

ALARM 1 LIMIT

ALARM 2 LIMIT

CHANNEL NAME ENTRY

ALARM TYPE SELECTION

ALARM 1 RELAY ASSIGNMENT

ALARM 2 RELAY ASSIGNMENT

CHANNEL INPUT TYPE

CHANNEL UNITS

CHANNEL DECIMAL POINT

LOWER LIMIT FOR

CHANNEL RANGE

HIGHER LIMIT FOR

CHANNEL RANGE

ALARM HYSTERESIS

ALARM 1 MODE

ALARM 2 MODE

ALARM 1 SENSOR BREAK

OR ERROR CONDITION

ALARM 2 SENSOR BREAK

OR ERROR CONDITION

LATCHING ALARM LED's

CHANNEL COPY

STANDARD VALUES

CALIBRATION

C

H

NAME ENTRY

Use Keys:

ACK

ENTE

R

PROG

Use Keys:ACK

ENTE

R

On

entering

PROG

MODE

PROG

RUN

EXIT

MENU

P-24

P-23

P-22

P-21

P-18

P-19

P-20

P-17

P-16

P-15

P-14

P-12

P-11

P-10

P-09

P-08

P-07

P-06

P-05

P-04

P-03

P-02

P-01

PROGRAM MENU FLOWCHART

NOTE:

Available with FULL ACCESS Password

C

H

C

H

C

H

C

H

C

H

C

H

C

H

C

H

C

H

F

O

R

U

S

E

R

M

E

N

U

O

N

L

Y

P-13C

H

Page 13: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 13 of 39

3.3.4 PROGRAM MENU ITEMS

P-01 SCAN MODE

Mod Auto / Man

This is the AUTO/MANUAL Mode selection. If AUTO is selected the display scanning is in AUTO mode on power ON. Other wise it is in MANUAL mode on power ON, (Note: AUTO/MANUAL selection can be changed when scanner is running by pressing the [HOLD/CLEAR] key, however this setting is not saved in memory and scanner reverts to the AUTO/MAN selection as set in program mode on power ON). Use the [UP]/[DOWN] key to change the setting if required and press [ENTER] key to save the setting.

Press the SCROLL [>] key to go to the next parameter in the menu.

P-02 SCAN RATE

Sr XX This is the display scan rate setting (xx), display scan rate can be set from 1 to 99 seconds. Use the [UP]/[DOWN] key to change the setting if required and press [ENTER] key to save the setting.

Press the SCROLL [>] key to go to the next parameter in the menu.

P-03 FUNCTION

Fn < Item to display >

This setting selects the item to display in the Function (Fn) display. Item to display can be selected from list below:

1. ‘nAME’ = Channel name. 2. ‘unit’ = Units. 3. ‘iP’ = Channel input type 4. ‘AL-ty’ = Channel alarm type set HL, HH & LL 5. ‘AL-St’ = Channel alarm status.

Use the [UP]/[DOWN] key to change the setting if required and press [ENTER] key to save the setting.

Page 14: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 14 of 39

Press the SCROLL [>] key to go to the next parameter in the menu.

P-04 CHANNEL SKIP

01 Ch On / oFF

This is the Channel SKIP mode setting, if a channel is set to OFF, that channel will not be scanned or displayed. Use [UP] or [DOWN] key to set the channel ‘on’ or ‘oFF’ and press the [ENTER] key to save the setting. ‘01’ indicates the current channel number being set. Use the [PRN/NEXT] key to go to next channel to set.

Unused or open channels should always be set to Skip.

Press the SCROLL [>] key to go to the next parameter in the menu.

P-05 ALARM 1 LIMIT

01 A1 xxx

This is the Alarm 1 limit programming mode, using [UP] or [DOWN] keys set the desired limit ‘xxx’ and press [ENTER]. The decimal point is automatically adjusted as per the input type and selected dp.

The Limit of alarm setting can be only within the limits set in the range setting (low and

high range set for the channel: P-14, P-15) Use [UP] or [DOWN] key to set the channel Alarm-1 setpoint and press the [ENTER] key to save the setting. ‘01’ indicates the current channel number being set. Use the [PRN/NEXT] key to go to next channel to set.

Page 15: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 15 of 39

P-06 ALARM 2 LIMIT

01 A2 xxx

This is the channel Alarm 2 limit programming mode, using [UP] or [DOWN] keys set the desired limit ‘xxx’ and press [ENTER]. The decimal point is automatically adjusted as per the input type and selected dp.

The Limit of alarm setting can be only within the limits set in the range setting (low and

high range set for the channel: P-14, P-15)

Use [UP] or [DOWN] key to set the channel Alarm-2 setpoint and press the [ENTER] key to save the setting. ‘01’ indicates the current channel number being set Use the [PRN/NEXT] key to go to next channel to set.

Set as required and Press the [>] SCROLL key

P-07 CHANNEL NAME ENTRY

01 Ch nAME

This is the channel name entry menu; press [ENTER] to go to the menu. On pressing [ENTER] the display changes to: -

01 Ch NNN ^

This is the 3 character ‘NNN’ name entry for channel 1, use the SCROLL [>] keys to select the character to be changed, the selected digit will flash. Use [UP] or [DOWN] keys to change the character to the required display. Press the [ENTER] key to save the name, use the [PRN/NEXT] key to go to the next channel. After completion of name entry use the [PROG/RUN] key to exit the menu.

This is the last item in the USER LEVEL menu, pressing the SCROLL [>] key will go back to the 1st item in the menu.

Page 16: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 16 of 39

If Full access password was entered, the next item in the menu will be displayed. Press the SCROLL [>] key, the display changes as follows:

P-08 ALARM TYPE SELECTION

01 ALM OFF/hL/hh/LL

This is the Alarm Type selection for the selected channel. OFF = Alarm is OFF for this channel hL = A1-High Alarm & A2-Low Alarm hh = A1-High Alarm & A2-Very High Alarm LL = A1-Low Alarm & A2-Very Low Alarm Set as required (the channel number can be changed by the [PRN/NEXT] key) and Press the [>] SCROLL key.

P-09 ALARM 1 RELAY ASSIGNMENT

01 A1r oFF / rL-1 /rL-2 ../rL-8 (or max relays provided)

This is the Alarm 1 relay assignment for the selected channel as follows:

OFF = No relay assigned for channel Alarm-1 RL-1 to RL-8 = Relays 1 to Relay 8 (Max).

Set as required and Press the [>] SCROLL key

P-10 ALARM 2 RELAY ASSIGNMENT

01 A2r oFF / rL-1 /rL-2 ../rL-8 (or max relays provided)

This is the Alarm 2 relay assignment for the selected channel as follows:

OFF = No relay assigned for channel Alarm-2 RL-1 to RL-8 = Relays 1 to Relay 8 (Max). Set as required and Press the [>] SCROLL key

Page 17: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 17 of 39

P-11 CHANNEL INPUT TYPE

01 iP Pt0/Pt1/ni/ . . . /05V

This is the channel Input type programming mode, the Input type can be set for each channel as follows.

Only input types between the first and last input types as displayed in the initial power

on hardware setup will be available, other types will not be displayed and are not available. 1) ‘PT0’ – PT 100 (-200 to 600 Deg C) 2) ‘PT1’ – PT 100 (-199.9 to 400.0 Deg C ) 3) ‘P46’ – PT 46 (0 to 200 Deg C) 4) ‘ ni’ – Ni 100 (0 to 200 Deg C) 5) ‘C50’ – Cu50 (0 to 150 Deg C) 6) ‘C53’ – Cu53 (0 to 150 Deg C) 7) ‘TCJ’ – TC-J (0 to 700 Deg C) 8) ‘TCK’ – TC-K (0 to 1200 Deg C) 9) ‘TCT’ – TC-T (-100 to +400 Deg C) 10) ‘TCE’ – TC-E (-100 to +1000 Deg C) 11) ‘TCB’ – TC-B (250 to 1820 Deg C) 12) ‘TCR’ – TC-R (-50 to 1765 Deg C) 13) ‘TCS’ – TC-S (0 to 1766 Deg C) 14) ‘TCN’ – TC-N (0 to 1800 Deg C) 15) ‘15V’ – Voltage 1.0 to 5.0 Volts (-1999 to 9999) * 16) ‘05V’ – Voltage 0.0 to 5.0 Volts (-1999 to 9999) * 17) ‘420’ – Current 4 to 20 mA (-1999 to 9999) 1`8) ‘020’ – Current 0 to 20 mA (-1999 to 9999)

Inputs are factory set and would be available as per the ordering code. If universal

input is selected then all the inputs would be displayed.

For current input use 150 ohm conditioning resistance.

Set as required and Press the [>] SCROLL key

* Voltages greater than 5.6 Volts should not be applied, this may affect accuracy of other channels or damage the input.

Page 18: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 18 of 39

P-12 CHANNEL UNITS

01 unt Units

This is the channel units programming mode, this is only displayed if linear type input is selected.

Select the display units from the list displayed as shown below:

A m p s

m A

M 3 / H r

M 3 / M i n

m m H 2 0

m m H g

V o l t s

m V

B a r

m B a r

P S I

k g / c m 2

1 .

2 .

3 .

4 .

5 .

6 .

7 .

8 .

9 .

1 0 .

1 1 .

1 2 .

1 3 .

N i l

D e g C

D e g F

%

% R H

1 4 .

1 5 .

1 6 .

1 7 .

If RTD or TC type input is selected this item will not be displayed and units will be ‘Deg-C’

Page 19: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 19 of 39

Set as required and Press the [>] SCROLL key.

P-13 CHANNEL DECIMAL POINT

01 dP xx This is the channel decimal point programming mode, this is only displayed if linear type input is selected.

Select the decimal point as required from 0 to 3 decimal points, Set as required.

Set as required and Press the [>] SCROLL key

P-14 LOWER LIMIT FOR CHANNEL RANGE

01 rLo xxx This is the lower limit for the channel range used to:

• Set the lower limit for the alarm setting

• Scale lower limit of linear inputs / process inputs to engineering units The decimal point is automatically adjusted as per the input type and selected dp (decimal point).

Set as required and Press the [>] SCROLL key

P-15 HIGHER LIMIT FOR CHANNEL RANGE

01 rhi xxx This is the higher limit for the channel range used to:

• Set the higher limit for the alarm setting

• Scale the higher limit of linear inputs / process inputs to engineering units The decimal point is automatically adjusted as per the input type and selected dp (decimal point). Set as required and Press the [>] SCROLL key

If RTD or TC type input is selected this item will not be displayed and decimal point will be set as per input type.

Page 20: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 20 of 39

P-16 ALARM HYSTERESIS

Hyt xx This is the Alarm Hysteresis setting, common for all channels. It is set within the range 0 to 20, to produce a hysteresis of +/-0 to +/- 20. It is set in LSD or counts, setting 10 will mean +/- 10 digit if dp is 0, if dp is 1 it will mean +/-1.0, if dp is 2 it will mean +/- 0.10 It is normally set to 1 or higher to prevent relay chatter.

P-17 ALARM 1 MODE

A1M ALARM/TRIP

This is the Alarm-1 mode programming screen. Each alarm 1 and 2 can be set for either ‘ALARM’ type or ‘TRIP’ type operation. For ALARM type operation the alarm LEDs and relay are energized only in fault condition, and is automatically cleared when value returns to normal or the fault is acknowledged. For TRIP type operation the relay and LED is latched, and will be cleared if acknowledged and fault is cleared.

Select the option ALARM or TRIP as required (Normally A1 is set for ALARM and A2 for TRIP).

P-18 ALARM 2 MODE

A2M ALARM/TRIP

This is the Alarm-2 ALARM or TRIP operation programming screen. Operation is similar to that for A1 Alarm. Select as required.

P-19 ALARM 1 SENSOR BREAK OR ERROR CONDITION

A1b A-OFF / A-ON

This is the Alarm-1 sensor break or error condition setting.

Select as required.

If this is set for ‘ALM-OFF’, A1 will be OFF on sensor break or error condition. If this is selected as ‘ALM-ON’, A1 will be ON on sensor break or error condition.

Page 21: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 21 of 39

P-20 ALARM 2 SENSOR BREAK OR ERROR CONDITION

A2b A-OFF / A-ON This is the Alarm-2 sensor break or error condition setting.

Select as required.

P-21 LATCHING ALARM LED’s

LED No Lh / LATCH This is for latching the alarm LEDs, when A1 or A2 is selected as ALARM type, the alarm LEDs only can be latched to indicate that a fault had occurred. The relay operation will not be effected, and will operate as per ALARM or TRIP mode as selected.

Select as required.

P-22 COPYING PARAMETERS FROM ONE CHANNEL TO ANOTHER

Ch Copy

This is used to copy the set parameters from one channel to the next channel or channels. A higher channel cannot be copied to a lower channel. To copy channel press [ENTER], the display will change to as follows:-

Fr= (Copy from Channel Number) 1

Use [UP] or [DOWN] key to select the channel to copy from (default selection is channel 1), when selected press ENTER the display will change to:

If this is set for ‘ALM-OFF’, A2 will be OFF on sensor break or error condition. If this is selected as ‘ALM-ON’, A2 will be ON on sensor break or error condition.

Latched LED’s can be reset by pressing the acknowledge [ACK] key.

Page 22: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 22 of 39

Cn= 1

‘Cn’ is the counts, the number of channels to copy to, starting from the next channel, default value is 1. Use the [UP] or [DOWN] key to select the next number of channels to copy to, when selected press ENTER the selected channel will be copied to the next number of channels as selected.

P-23 STANDARD VALUES

Set Std

Factory set values are as follows: - Scan Mode = AUTO Scan Rate = 2 sec Fn Display = Units CH 01 to 16 is ON Alarm-1 setting for all channels = 70 Deg C Alarm-2 setting for all channels = 80 Deg C Alarm Type = HH Alarm-1 Relay = 1 Alarm-2 Relay = 2 Input Type = PT100 Units = NIL Dp = 0 Range Low = 0 Range High = 400 Hysterisis= +/-1 A1 Type = ALARM A2 Type = TRIP A1 Sensor break = ALARM OFF A2 Sensor break = ALARM OFF Alarm LEDs = NON-LATCH

This entry restores all parameters including Channel names to their default values.

Page 23: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 23 of 39

P-24 CALIBRATION

Set Cal

This is the Calibration mode.

Press the SCROLL key the display changes back to first item of the menu.

MENU END

Press the PROG/RUN key to quit PROG mode.

4. INSTALLATION

Before proceeding with the installation please check the label to verify the rating.

4.1 Install the scanner in the panel cutout and tighten the fixing clamp carefully.

4.2 POWER CONNECTION

Connect the 90VAC - 260VAC, 50/60Hz power supply to the terminals marked ‘L’ Live, ‘N’ Neutral

& ‘E’ Earth. Refer TABLE-3.

Be sure to connect L, N and E as indicated. Failure to wire the power as indicated could result in damage to the scanner.

Do not connect power to your device until you have completed all input and output connections. Failure to do so may result in injury!

Do not enter Calibration Mode unless system is out of calibration and you have fully understood the Calibration Procedure.

Calibration details are given in separate calibration manual

Page 24: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 24 of 39

Also refer to Safety Considerations in section 1.2 4.3 SENSOR CONNECTION

Connect the sensor / inputs to the appropriate terminals - refer TABLE-1. Care should be taken during installation to check polarity of the wires.

4.3.1 THERMOCOUPLE INPUT (Type – J, K, T, E, B, R, S, N)

• This input must be wired by using proper thermocouple compensating or extension cable of the type of input selected.

• Normally un-grounded thermocouples (TC) should be used. If grounded type TC is used then other inputs should be isolated since they will also get grounded.

• Polarity of cables must be maintained.

4.3.2 RTD INPUT (Type – PT 100, Ni 100, Cu 50, Cu 53)

• PT 100 RTD are as per 385 curve (0.385 ohms/deg.C - DIN 43760)

• For two-wire RTD short ‘-‘ & ‘R’ and connect RTD between ‘+’ & ‘-‘ • The two-wire connection is simplest method, but does not provide wire resistance

compensation that may lead to reading error due to connecting cable resistance.

• The three-wire connection provides wire resistance compensation and produces excellent lead-resistance cancellation for balanced measurements. So three-wire connection is recommended.

To prevent shock ensure that the instrument is properly earthed.

Thermocouple Wire Colors are different as per different Standards. Please check your manufacturers specification for the polarity indication.

Signal cables should be routed away from all power cables and cables connected to relay contacts.

Use shielded cable for signal wiring.

Tighten all RTD cable terminals properly, loose junction box terminals or connectors will lead to erratic readings.

Page 25: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 25 of 39

4.3.3 Process / Linear Input – VOLTAGE (0 to 5V or 1 to 5V)

4.3.4 Process / Linear Input – CURRENT (0 to 20mA or 4 to 20mA)

• Connect 150Ω conditioning resistance across ‘+’ & ‘-‘ terminals for current input. • Current loops connected to the system should be isolated or share a common return path

to the negative terminal due to common negative terminal. 4.4 RELAY CONNECTION

Connect the potential free contacts from the ALARM relays as required. Terminal numbers for

relay contacts are given TABLE-2.

• Voltages greater than 5.6 Volts should not be applied; this may affect accuracy of other channels or damage the input.

• If voltage inputs are left open you may get floating values, so the inputs must be either shorted or switched off and not be kept floating.

Relays provided are for alarm annunciation. Switching heavy loads is not recommended. In case of inductive loads use suitable RC snubber network. Recommended values for R & C are R = 470 ohm and C = 0.1 uF/250V, RC value will depend on connected inductive load.

Page 26: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 26 of 39

4.5 TERMINAL ASSIGNMENT, CONNECTIONS

WIRING DIAGRAM FOR TEMPERATURE SCANNER

MODEL No. - MCS831E ADX

MICRO SYSTEMS & CONTROLSPOWER

90-260V AC

1

2

3

+

-

R

4

5

6

+

-

R

7

8

9

+

-

R

10

11

12

+

-

R

13

14

15

+

-

R

16

17

18

+

-

R

19

20

21

+

-

R

22

23

24

+

-

R

CH-1

CH-3

CH-5

CH-7

CH-9

CH-1

1CH-1

3CH-1

5

25

26

27

+

-

R

28

29

30

+

-

R

31

32

33

+

-

R

34

35

36

+

-

R

37

38

39

+

-

R

40

41

42

+

-

R

43

44

45

+

-

R

46

47

48

+

-

R

CH-2

CH-4

CH-6

CH-8

CH-1

0CH-1

2CH-1

4CH-1

6

52

53

54

NO

C

NC

49

50

51

NO

C

NC

58

59

60

NO

C

NC

55

56

57

NO

C

NC

64

65

66

NO

C

NC

61

62

63

NO

C

NC

67

68

69

NO

C

NC

70

71

72

NO

C

NC

73

74

75

L

N

E

Page 27: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 27 of 39

TABLE-1 Input Connection

RTDs / PT 100 TC / Linear CHANNEL # + - R + -

1 1 2 3 1 2

2 25 26 27 25 26

3 4 5 6 4 5

4 28 29 30 28 29

5 7 8 9 7 8

6 31 32 33 31 32

7 10 11 12 10 11

8 34 35 36 34 35

9 13 14 15 13 14

10 37 38 39 37 38

11 16 17 18 16 17

12 40 41 42 40 41

13 19 20 21 19 20

14 43 44 45 43 44

15 22 23 24 22 23

16 46 47 48 46 47

TABLE-2: Relay Connection

TERMINAL # RELAY #

NO C NC

RELAY-1 49 50 51

RELAY-2 52 53 54

RELAY-3 55 56 57

RELAY-4 58 59 60

RELAY-5 61 62 63

RELAY-6 64 65 66

RELAY-7 67 68 69

RELAY-8 70 71 72

TABLE- 3: Power Connection

POWER L N E

TERMINAL # 73 74 75

+ - R PT100/Ni- 100

+ - TC

+ -

0-5V

or

1 –5V

Page 28: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 28 of 39

TABLE- 4: Input Types

INPUT TYPE RANGE RESOLUTION UNITS

TC - J 0 to 700 Deg.C 1

TC - K 0 to 1200 Deg.C 1

TC - R -50 to 1765 Deg.C 1

TC - S 0 to 1766 Deg.C 1

TC - T -100 to 400 Deg.C 1

TC - E -100 to 1000 Deg.C 1

TC - B 250 to1820 Deg.C 1

Thermocouple

TC - N 0 to1800 Deg.C 1

PT100 0 to 600 Deg.C 1

PT100 0.0 to 400.0 Deg.C 0.1

PT46 0 to 200 Deg.C 1

Ni100 0 to 200 Deg.C 1

Cu50 0 to Deg.C 1

RTD

Cu53 0 to 150 Deg.C 1

Deg.C

0 to 5V –1999 to +9999 programmable

1 to 0.001 Process/ Linear Input -DC Volts 1 to 5V

–1999 to +9999 programmable

1 to 0.001

0 to 20mA –1999 to+9999 using 150 ohms conditioning resistance

1 to 0.001 Process/ Linear Input -mA

4 to 20mA –1999 to+9999 using 150 ohms conditioning resistance

1 to 0.001

User Selected

TABLE- 5: Serial Communication Connection

SIGNAL GND Rx / B- Tx / A+

TERMINAL # 76 77 78

For Rs232 - GND ,Rx & Tx For RS485 - GND ,B- & A+

Page 29: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 29 of 39

5. DIMENSIONS & PANEL CUTOUT

minimum

96.0 mm192.0 mm

186.0 mm

10.0mm240.0mm

110.0mm

110.0mm

PANEL CUTOUT: 92.0 X 186.0mm

92.0mm

(-0, +0.5mm)

186.0mm

(-0, +0.5mm)

Page 30: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 30 of 39

6. COMMISSIONING

8.1 Check that there is no physical damage to the scanner during transportation. 8.2 Check that the scanner is properly installed in the panel and mounting clamps are properly

tightened. 8.3 Check the power line voltage to ensure that it is within the specified limits. 8.4 Check that there is a proper ‘Earth’ connection to the scanner. 8.5 Ensure that all sensor terminal screws are properly tightened.

7. INPUT ERROR DISPLAY The following display errors are displayed on the system if there is any input error.

ERROR MEANING REASON

OPEN Open sensor

• RTD/ PT100 wire open

• For 4-20mA if current input is below 3mA

• For 1-5V if voltage is below 1V

SHRT Short RTD / PT100 wire short

– OR – Over Range Reading is over calibrated range

– UR – Under Range Reading is below calibrated range

8. SELF TEST ERROR CODES During power ON and while running, the systems performs certain self tests to ensure that the scanner does not display a false reading due to system hardware fault. In the process if a hardware fault is detected, the scanner stops normal operation and displays an Error Code.

List of error codes and their meaning is given below: -

ERROR CODE TABLE

ERROR CODE MEANING REMEDY

E1 Input type selected not supported

Select Valid Type, CONSULT FACTORY

E2 Calibration error Selected input type is not calibrated, recalibrate the selected input type

E3 CJC (Cold Junction Compensation) error

• Check ambient sensor at back panel

• Recalibrate thermocouple ambient temperature or hardware failure

E4 ADC Error / Fail Hardware failure, contact SUPPORT for repair

E5 ADC auto zero fail Hardware failure, contact SUPPORT for repair

Page 31: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 31 of 39

9. SCANNER SPECIFICATIONS

Electrical

Supply Voltage : Universal 90-260VAC or 110 to 250VDC, 10VA max

Input :

Universal input PT100 / Ni-100 / CU50 / CU53 / TC / 1-5V / 0-5V / 4-20mA / 0-20mA (mA input using 150 ohms conditioning resistance)

Range : Refer Input Range Table – 4

No of channels : 8, 12 or 16 channels

Input Impedance : > 1 Meg Ohm

Noise Rejection : Common mode 120 dB or better, Series mode 60dB or better

Indication & Control

Display :

12.7 mm, 7segment Red LED- 2 digits for channel value, 4 digits for process value. 3 digits user programmable multi function display (Name, Units, Type etc) Status LEDs: Prog, Run, Hold, Error, Tx, Rx & Deg C.

Alarm LEDs : Individual A1 & A2 LEDs per channel, Latching or non Latching

Auto Manual Selection : Programmable from Keyboard

Channel Skipping : Provided from Keyboard

Alarm set points : Two individual alarm settings per channel

Alarm Logic : Programmable High, Low, Very High, Very Low Latching & Non Latching

Display Scan : 1 to 99 seconds programmable, Auto and Manual with HOLD

Internal Scan Rate : 10 channels per second max.

Output

Output : 8 Relays maximum

Relay Grouping : Programmable – Any alarm can be assigned to any relay.

Relay Rating : 1 C/O, 5 Amps / 230VAC resistive max

Performance

Accuracy : +/- 0.1 % FS, +/- 1 count

Resolution : Programmable as per Input table

Calibration : Software based calibration from calibration menu,

Page 32: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 32 of 39

no internal pots

ADC : 20,000 count optically isolated ADC with dedicated microcontroller

Battery Backup Non-volatile EEPROM, Battery not required

Compensations : Automatic - Cold junction for TC, Wire resistance for RTDs

Sensor break / Error : Programmable Enable or Disable Alarm with ‘open’ / ’short’ indication

Protection : Password protection for configuration, Watchdog for system monitoring

Diagnosis : Auto diagnosis facilities with error display

Fail Safe Condition : Alarm relay is not energized in case of power supply failure

Environment : Temp: -10 to + 60 Deg C Max. RH: Up to 95% non condensing

Serial Port (OPTIONAL)

Real Time Clock : Optional real time clock calendar for data printout with time stamp

Communications : Optional RS232 or RS485 for printer log, MSC ASCII or MODBUS RTU

Software : Optional Windows MicroDAS data acquisition package for single or multi scanner

Mechanical

Enclosure : Robust metallic powder coated enclosure with plastic bezel

Protection Class : IP65 Front panel

Mounting : Flush on panel with screw type clamps 2 Nos

Dimensions : External: 96(W) X 192 (H) X 250 (D) mm.

Panel Cutout : 92 X 186 mm, -0 / +0.5mm

Input Connections : Rugged screw terminals suitable for 0.2 to 2.5 mm sq mm cable

Weight : 1.5 Kg Approx

Accessories : 2 Nos Screw clamps for mounting, 150 Ohms conditioning resistances if 4 to 20mA inputs provided

10. CALIBRATION

The Scanner is factory calibrated for the three basic types RTD, Thermocouples and Volts. The calibration is not required to be changed if the input type is changed. However if the scanner is required to be recalibrated in case of error over time, or any component has been changed, the calibration procedure is as follows. The Scanner has auto calibration feature. It gets calibrated automatically when the required input in the acceptable range is given. If its not in acceptable range it is rejected and there is calibration failure.

Page 33: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 33 of 39

EQUIPMENT REQUIRED:

INPUT TYPE EQUIPMENT REQUIRED

RTD –PT100 Decade resistance box 0 to 400.0 Ohms accuracy 0.05% or better.

Thermocouple 1. 0 to 75.00 mV calibrator, accuracy 0.05% or better. 2. Thermometer 0 to 60 Deg C, 0.1 Deg C resolution, accuracy

0.1 Deg C or better.

VOLTS 0 to 5.000 V DC Precision voltage source, accuracy 0.05% or better

Connect the following inputs to the following channel:

CHANNEL INPUT TYPE VALUE

Channel - 1 RTD input 400.0 Ohms

Channel - 2 Thermocouple input 75.00 mV

Channel - 3 Voltage input 5.000 V

(Refer Table – 1 of USER MANUAL for the connections).

CALIBRATION PROCEDURE:

The scanner need not be opened for recalibration and the calibration can be done from the front panel keyboard. There are no internal potentiometers and the entire calibration is done digitally via software.

Before proceeding with calibration ensure that the required equipment is available, and the calibration procedure is fully understood, improper calibration will change the factory calibration and make the scanner unusable or display incorrect reading.

ENTERING CALIBRATION MODE:

Enter the PROG mode and enter password 135, to access the full menu. Press NEXT key till display shows:

Before calibration ensure that the scanner is at room temperature and provide a

warmup period of 15 minutes.

The above-mentioned inputs should not be changed as this will lead to calibration failure.

Before entering calibration mode connect the three calibration inputs to channel 1, 2 and 3.

Page 34: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 34 of 39

Set Cal If you want to continue calibration press the ENTER key else to exit press the [>] NEXT key. On pressing ENTER display shows:

CPS 000 Use the UP key to change 000 to 015 and press ENTER. This will access the calibration menu. The display indicates the following sequentially as follows:

C1 rtd 400.0 C2 tC 75mV C3 Lin 5.00 CJC 00XX Where ‘00XX’ is the previous set ambient temperature (eg 30.0 Deg C). Measure the ambient temperature (back terminal temperature) and set this value using the UP or DOWN key. Press ENTER and display changes to:

CAL busy The Scanner now starts auto calibration based on the input values at terminal 1,2 and 3. This process should take 2 to 3 minutes.

Display then indicates the following one after the other:

rtd Pass tC Pass

Page 35: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 35 of 39

CJC Pass Lin Pass

And then display returns to:

Set CAL The calibration is now complete.

If any of the inputs at channel 1, 2 or 3 are incorrect or Scanner has hardware failure then display would indicate ‘FAIL !!’ instead of ‘PASS !!’.

Press the PROG/RUN key to quit PROG mode or press the NEXT key to return to first item of the Prog menu.

Page 36: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 36 of 39

Appendix – A

SYSTEM CONFIGURATIONS (FACTORY SET):

Customer:

Order No.:

Serial No.:

Ordering Code:

Special Option:

No. of Channels:

Input Type:

ALARM/RELAY SETTING:

ALARM 1 ALARM 2 Channel

Input Type

Range High

Range Low Type Value Relay Type Value Relay

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

REMARKS:

Page 37: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 37 of 39

Appendix – B

SYSTEM CONFIGURATIONS (USER RECORD):

Customer:

Order No.:

Serial No.:

Ordering Code:

Special Option:

No. of Channels:

Input Type:

ALARM/RELAY SETTING:

ALARM 1 ALARM 2 Channel

Input Type

Range High

Range Low Type Value Relay Type Value Relay

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

REMARKS:

Page 38: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 38 of 39

NOTES

Page 39: Mcs831e-Adx User Manual

USER MANUAL FOR SCANNER MCS831E-ADX Rev 04

MICRO SYSTEMS & CONTROLS Page 39 of 39

NOTES

Page 40: Mcs831e-Adx User Manual

How to contact Micro Systems & Controls

• For Technical Support

Call: +91 – 33 – 24163135 / 24168933

Fax: +91 – 33 – 24163135 / 24168933

Email: [email protected]

• For Sales Support or to place an order

Call: +91 – 33 – 24163135 / 24168933

Fax: +91 – 33 – 24163135 / 24168933

Email: [email protected]

• For latest information, please visit www.mscontrols.com

• Postal address:

MICRO SYSTEMS & CONTROLS 140A, SANTOSHPUR AVENUE, KOLKATA - 700 075 WEST BENGAL INDIA

Page 41: Mcs831e-Adx User Manual

OUR OTHER PRODUCTS

INDICATORS MPI-200 1/8 DIN 3 &½ Digit Process Indicator MPI-501U 1/8 DIN 4 Digits Universal Indicator with alarm option BG-102 Dual Channel Bar Graph Indicator CONTROLLERS DC2010 1/8 DIN 4 Digits, Universal ON/OFF, PI controller DC3010 ¼ DIN 4 Digits, Universal Input PID controller SCANNERS MCS831E-ADX Universal or Fixed Input Scanner upto 16 channels, LED display DV 9800 Dual Display LED & LCD advanced Universal Scanner FLOW TOTALISERS FTX55P LCD type Flow Indicator Totaliser FTX55PL LED type Flow Indicator Totaliser DATA LOGGERS Stand alone online hard copy data logging systems

PC Based advanced data logging systems

ALARM ANNUNCIATORS ALM-108 Eight channel modular microprocessor based Annunciator ALM-200 12 to 64 channels microprocessor based Annunciator PC based alarm Annunciators with fault logging TRANSMITTERS TEMPERATURE TxPT2 2 Wire RTD PT100 transmitters TxTC2 2 Wire Thermocouple transmitters PRESSURE 2 Wire Pressure transmitters RELATIVE HUMIDITY TXRH2 2 Wire RH transmitter 0 to 100% CURRENT & VOLTAGE Range of Current and Voltage transmitters SIGNAL ISOLATORS / DISTRIBUTORS ISO-101 / 102 Single output and dual output current loop Isolators ISO-101MP / ISO-102MP Signal Isolator / Distributor – Mains powered WEIGHING

BC1000 Weight indicator controller, Weigh Feeders and Batching BAG FILTER & ESP TIMERS BF-200 Bag Filter Timer RP-200 Rapping Programmer POWER SUPPLY UNITS PS242 24V/2A PANEL PRINTERS AN240 MicroDAS Data Acquisition Software SOFTWARE DEVELOPMENT EMBEDDED SYSTEMS Application specific Controllers & Displays: Design & Manufacture