23
UT Pan Am McDonald Observatory 120V wall outlet 120V wall outlet Funding provided by EPRI Equipment provided by Schweitzer Engineering Labs Start-up funds provided by Governor’s Emerging Technology Fund through CCET 69kV grid monitor provided by Austin Energy Independent. Not affiliated with ERCOT or any utility except Austin Energy Will soon have one or more wind farm members 400 miles 300 miles Wind generation is mostly in West Texas. 7000 MW peak so far this year. Many hours in the spring have 15-20% wind MW, and some have > 20%. Most windy days have wind curtailments. Observations From the Texas Synchrophasor Network Monitoring 120V Wall Outlet Voltages and Communicating Through the Public Internet at 30 Readings per Second Since Spring 2009 Austin Majority of load is in the green rectangles, i.e. “Central ERCOT” Wind Country Presentation prepared by Prof. Mack Grady and Graduate Research Assistant Moses Kai, U.T. Austin, for the “Breaking News” Session at the IEEE-PES Annual Meeting, Minneapolis, Monday afternoon, July 26, 2010. 120V wall outlet at U.T. Austin, and 69kV 3Φ monitor at nearby Austin Energy Harris Sub

McDonald Observatory Austin 400 miles 300 milesewh.ieee.org/cmte/pes/etcc/M_Grady_Texas_Synchrophasor... · 2010-08-04 · Synchrophasor Detective – EVERY day has surprises and

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: McDonald Observatory Austin 400 miles 300 milesewh.ieee.org/cmte/pes/etcc/M_Grady_Texas_Synchrophasor... · 2010-08-04 · Synchrophasor Detective – EVERY day has surprises and

1

UT Pan Am

Austin

McDonald Observatory

120V wall outlet

120V wall outlet

• Funding provided by EPRI

• Equipment provided by Schweitzer Engineering Labs

• Start-up funds provided by Governor’s Emerging Technology Fund through CCET

• 69kV grid monitor provided by Austin Energy

• Independent. Not affiliated with ERCOT or any utility except Austin Energy

• Will soon have one or more wind farm members

400 miles

300 miles

Wind generation is mostly in West Texas. 7000 MW peak so far this year. Many hours in the spring have 15-20% wind MW, and some have > 20%. Most windy days have wind curtailments.

Observations From the Texas Synchrophasor Network

Monitoring 120V Wall Outlet Voltages and Communicating Through the Public Internet at 30 Readings per Second

Since Spring 2009

Austin

Majority of load is in the green rectangles, i.e. “Central ERCOT”Wind Country

Presentation prepared by Prof. Mack Grady and Graduate Research Assistant Moses Kai, U.T. Austin, for the “Breaking News” Session at the IEEE-PES Annual Meeting, Minneapolis, Monday afternoon, July 26, 2010.

120V wall outlet at U.T. Austin, and 69kV 3Φ monitor at nearby Austin Energy Harris Sub

Page 2: McDonald Observatory Austin 400 miles 300 milesewh.ieee.org/cmte/pes/etcc/M_Grady_Texas_Synchrophasor... · 2010-08-04 · Synchrophasor Detective – EVERY day has surprises and

2

Bus 2DFW

Bus 4SA

Bus 5VAL

Bus 6COAL

Bus 7WIND

300 km

250 km

150 km300 km

400 km

500 km400 km

Bus 3UT

Bus 1HOU

Positive-sequence line constants for each 345kV circuit:

• R = 0.06 Ω/km per conductor

• L = 1 µH/m

• C = 12 pF/m

• Rating = 800 A per conductor

• From the L, XL (500 km) = 188.5 Ω

• For 345 kV, 100 MVA base, Zbase = 1190 Ω

• For each 500 km circuit, XL = 0.158 pu

• Thus, four parallel circuits have XL = 0.040pu, and six parallel circuits have XL = 0.026 pu

Relatively small phase angle variation in central ERCOT

McDonald Observatory

PMU

UT Austin PMU

Bus 2DFWBus 2DFW

Bus 4SA

Bus 4SA

Bus 5VAL

Bus 5VAL

Bus 6COALBus 6COAL

Bus 7WINDBus 7WIND

300 km

250 km

150 km300 km

400 km

500 km400 km

Bus 3UT

Bus 3UT

Bus 1HOUBus 1HOU

Positive-sequence line constants for each 345kV circuit:

• R = 0.06 Ω/km per conductor

• L = 1 µH/m

• C = 12 pF/m

• Rating = 800 A per conductor

• From the L, XL (500 km) = 188.5 Ω

• For 345 kV, 100 MVA base, Zbase = 1190 Ω

• For each 500 km circuit, XL = 0.158 pu

• Thus, four parallel circuits have XL = 0.040pu, and six parallel circuits have XL = 0.026 pu

Relatively small phase angle variation in central ERCOT

McDonald Observatory

PMU

UT Austin PMU

U.T. Pan Am

Synchrophasor Homework Network for ERCOT

Page 3: McDonald Observatory Austin 400 miles 300 milesewh.ieee.org/cmte/pes/etcc/M_Grady_Texas_Synchrophasor... · 2010-08-04 · Synchrophasor Detective – EVERY day has surprises and

3

Thur Fri

West Texas voltage phase angle swings nearly 100º and back with respect to U.T. Austin in about 24 hours

Wind generation and West Texas phase angle can go through large daily swings

Synchrophasor Detective –EVERY day has surprises and clues

McDonald Observatory Voltage Phase Angle with respect to U.T. AustinMarch 25, 26, 2010

-60

-40

-20

0

20

40

60

24 36 48 60 7236 Hours Beginning 12am, March 24, 2010

Deg

rees

Wind Generation in ERCOT - MWMarch 25, 26, 2010

0

1000

2000

3000

4000

5000

6000

24 36 48 60 72

MW

48

Page 4: McDonald Observatory Austin 400 miles 300 milesewh.ieee.org/cmte/pes/etcc/M_Grady_Texas_Synchrophasor... · 2010-08-04 · Synchrophasor Detective – EVERY day has surprises and

4

ERCOT Log. June 23, 2010, 15:20 15:49. Deployed 1150 MW of Responsive Reserve Service from actual adjusted responsive reserve of 3281 MW with an obligation of 2300 MW when frequency dropped to 59.716 Hz due to XXXX and XXXX and XXXX tripped with 1213 MW, issued fleet up of 550 MW. ERCOT load 58446 MW.

Event 1. Large Unit Trip. Freq. Drops to 59.71 Hz. Afternoon of June 23, 2010.

GMT

2-Minute Window of All Four Frequency Readings, 1800 Samples per MinuteThe four

frequency plots are practically identical

Page 5: McDonald Observatory Austin 400 miles 300 milesewh.ieee.org/cmte/pes/etcc/M_Grady_Texas_Synchrophasor... · 2010-08-04 · Synchrophasor Detective – EVERY day has surprises and

5

0.52% drop

0.45% drop

1.78% drop

1.07% drop

U.T. Austin120V wall outlet

Austin Energy Harris Sub 69kV 3Φ positive seq.

McDonald Observatory 120V wall outlet

U.T. Pan American 120V wall outlet

Vrms plot

Vrms plot

Vrms plot

Vrms plot

Event 1. Large Unit Trip, June 23, 2010, cont.

2-Minute Windows of All Four VrmsReadings, 1800 Samples per Minute

120V wall outlet voltages are clearly more noisy than 69kV grid, but nevertheless 120V wall outlets together with Schweitzer relays provide reliable phase angle measurements

Page 6: McDonald Observatory Austin 400 miles 300 milesewh.ieee.org/cmte/pes/etcc/M_Grady_Texas_Synchrophasor... · 2010-08-04 · Synchrophasor Detective – EVERY day has surprises and

6

1-Minute Windows of Phase Angle Ringdowns, 1800 Samples per MinuteEvent 1. Large Unit Trip, June 23, 2010, cont.

• The data stream in from 300 and 400 miles away and are then time synchronized.

• Can you see any difference in the ringdowns observed by the 120V wall outlet on campus and the 69kV grid monitor near campus? (The correct answer is NO!)

• Essentially the only difference is the fixed 90º transformer-related offset plus a 0.3ºpower flow shift through the substation transformer.

• What conclusions can be made about the location of the tripped generator?

Ringdowns Observed atU.T. Austin 120V Wall Outlet

Ringdowns Observed at Austin Energy’s Nearby Harris Sub 69kV (3Φ Positive Sequence)

U.T. Pan Am U.T. Pan Am

McDonald Observatory McDonald Observatory

Page 7: McDonald Observatory Austin 400 miles 300 milesewh.ieee.org/cmte/pes/etcc/M_Grady_Texas_Synchrophasor... · 2010-08-04 · Synchrophasor Detective – EVERY day has surprises and

7

Frequency at the Four PMU Locations

U.T. Pan Am Phase Angle w.r.tU.T. Austin

• Insignificant frequency event – too small to be logged.

• But very significant response in South Texas voltage phase angle.

• Illustrates the sensitivity of synchrophasors.

• Shows that South Texas was importing P because the phase angle dropped.

1-Minute Windows

Event 2. Small Unit Trip in South Texas. Morning of July 18, 2010.

Page 8: McDonald Observatory Austin 400 miles 300 milesewh.ieee.org/cmte/pes/etcc/M_Grady_Texas_Synchrophasor... · 2010-08-04 · Synchrophasor Detective – EVERY day has surprises and

8

ERCOT Log. Frequency dropped to 59.920 Hz due to wind generation dropped 1400 MW after off-set was calculated. Issued fleet up of 400 MW due to out of Up Regulation. ERCOT load 35153 MW.

Event 3. Wind MW Backdown Invoked. Early Morning of July 15, 2010. Thevenin Impedance Calculation.

90-Minute WindowsTotal Generation, MW

0

10000

20000

30000

40000

4.0 4.5 5.0 5.5Hour (CDT)

Wind Generation, MW

0

1000

2000

3000

4000

5000

4.0 4.5 5.0 5.5Hour (CDT)

McDonald Voltage Phase Angle wrt U.T. Austin, Degrees

-10

0

10

20

30

4.0 4.5 5.0 5.5Hour (CDT)

Page 9: McDonald Observatory Austin 400 miles 300 milesewh.ieee.org/cmte/pes/etcc/M_Grady_Texas_Synchrophasor... · 2010-08-04 · Synchrophasor Detective – EVERY day has surprises and

9

Bus 7WINDBus 7WIND

500 km

Local conventional Pload,conv − Pgen,conv

Pexport

Thevenin Impedance jXTH

Central ERCOT

Vangle = 0

Vangle = δ

Event 3. Wind MW Backdown. July 15, 2010. Thevenin Impedance Calculation, cont.

Use the Excel Solver with the 90 minutes of readings tominimize least-squared error and determine Xth

Page 10: McDonald Observatory Austin 400 miles 300 milesewh.ieee.org/cmte/pes/etcc/M_Grady_Texas_Synchrophasor... · 2010-08-04 · Synchrophasor Detective – EVERY day has surprises and

10

Event 3. Wind MW Backdown. July 15, 2010. Thevenin Impedance Calculation, cont.

The knowns (all are given in one-minute average): • Wind generation MW • Wind generation phase angle δ with respect to central ERCOT (i.e., U.T. Austin) • ERCOT total generation

The unknowns

• jXTH • Local conventional load minus generation in West Texas wind country • Pexport

The equations

• Ignoring losses, power balance requires that

( ) )sin(,, δTH

ERCOTwindconvgenconvloadwind X

VVPPP

•=−−

Other assumptions • Having access to no other information, assume that local net conventional ( convgenload PP ,− )

varies with ERCOT total generation according to BPAPP GenTotalERCOTconvgenconvload +•=− ,,

Excel Solver Setup

• Define )(

11puXX

VVC

THTH

ERCOTwind •=

•=

• Instruct Excel Solver to vary coefficients A, B, and C to minimize the sum of squared error

( )[ ]∑=

−−−N

nconvgenconvloadwind CPPP

1

2,, )sin(δ ,

n = minutes, for either the entire interval

The balance equation: want left-hand side ≈ right-hand side for all 90 readings

Three unknowns

Page 11: McDonald Observatory Austin 400 miles 300 milesewh.ieee.org/cmte/pes/etcc/M_Grady_Texas_Synchrophasor... · 2010-08-04 · Synchrophasor Detective – EVERY day has surprises and

11

West Texas Power Export Estimates Pexp1 and Pexp2, MW

-1000

0

1000

2000

3000

0 10 20 30 40 50 60 70 80 90

Minute Beginning 0400 CDT, July 15, 2010

90-Minute Window

Event 3. Wind MW Backdown. July 15, 2010. Thevenin Impedance Calculation, cont.

Squared area between the two curves is minimized when

A = -0.0471

B = 356

Xth = 0.0211 pu on 345kV, 100MVA base

Page 12: McDonald Observatory Austin 400 miles 300 milesewh.ieee.org/cmte/pes/etcc/M_Grady_Texas_Synchrophasor... · 2010-08-04 · Synchrophasor Detective – EVERY day has surprises and

12

• A unit trip causes a drop of 0.06 Hz, which was not significant enough to be noted on ERCOT’s Daily Grid Operation Report.

• However, the phase angle ringdown at McDonald Observatory gives a clear indication of the damped resonant frequency and normalized damping coefficient between West Texas wind country and central ERCOT.

Event 4. Small Unit Trip. Early Afternoon of July 16, 2010. Ringdown Analysis.

2-Minute Window

Page 13: McDonald Observatory Austin 400 miles 300 milesewh.ieee.org/cmte/pes/etcc/M_Grady_Texas_Synchrophasor... · 2010-08-04 · Synchrophasor Detective – EVERY day has surprises and

13

2-Minute Window

Event 4. Small Unit Trip. July 16, 2010. Ringdown Analysis, cont.

Page 14: McDonald Observatory Austin 400 miles 300 milesewh.ieee.org/cmte/pes/etcc/M_Grady_Texas_Synchrophasor... · 2010-08-04 · Synchrophasor Detective – EVERY day has surprises and

14

McDonald Observatory Voltage Phase Angle w.r.t U.T. Austin 120V and Harris 69kV

-14

-13

-12

-11

-10

1600 1700 1800 1900 2000 2100 2200

Sample (30 samples per second)

Deg

rees w.r.t U.T. Austin

w.r.t Harris 69kV

10 seconds

Event 4. Small Unit Trip. July 16, 2010. Ringdown Analysis, cont.

• The fixed net multiple of 30 degree phase shift between U.T. Austin 120V and Harris 69kV has been removed. The variable but steady 0.1 degree power flow phase shift through the substation transformer has also been removed.

• Can you see any significant difference between the waveform seen by the 120V wall outlet (in black) and the waveform seen by the 69kV, 3Φ grid monitor (in red)? (The correct answer is NO!)

Voltage Ringdown at McDonald Observatory Observed at the Following Two Locations in Austin: a 120V Wall Outlet on Campus, and the Harris 69kV Substation that Feeds the Campus

Page 15: McDonald Observatory Austin 400 miles 300 milesewh.ieee.org/cmte/pes/etcc/M_Grady_Texas_Synchrophasor... · 2010-08-04 · Synchrophasor Detective – EVERY day has surprises and

15

U.T. Pan Am Voltage Phase Angle w.r.t U.T. Austin 120V and Harris 69kV

-40

-39

-38

-37

-36

-35

-34

-33

-32

1600 1700 1800 1900 2000 2100 2200

Sample (30 samples per second)

Deg

rees w.r.t U.T. Austin

w.r.t Harris 69kV

10 seconds

• The fixed net multiple of 30 degree phase shift between U.T. Austin 120V and Harris 69kV has been removed. The variable but steady 0.1 degree power flow phase shift through the substation transformer has also been removed.

• Can you see any significant difference between the waveform seen by the 120V wall outlet (in black) and the waveform seen by the 69kV, 3Φ grid monitor (in red)? (The correct answer is NO!)

Event 4. Small Unit Trip. July 16, 2010. Ringdown Analysis, cont.

Voltage Ringdown at U.T. Pan Am Observed at the Following Two Locations in Austin: a 120V Wall Outlet on Campus, and the Harris 69kV Substation that Feeds the Campus

Page 16: McDonald Observatory Austin 400 miles 300 milesewh.ieee.org/cmte/pes/etcc/M_Grady_Texas_Synchrophasor... · 2010-08-04 · Synchrophasor Detective – EVERY day has surprises and

16

Estimated Normalized Damping Ratio ξ = 0.088

McDonald Voltage Phase Angle wrt AustinMeasured Response is Dotted Line,

Ideal 2nd-Order Approximation is Solid Line

-14

-13

-12

-11

-10

0 1 2 3 4 5 6 7

Seconds

1.84sec, 0.54 Hz, 3.39 rad/sec

Event 4. Small Unit Trip. July 16, 2010. Ringdown Analysis, cont.

Page 17: McDonald Observatory Austin 400 miles 300 milesewh.ieee.org/cmte/pes/etcc/M_Grady_Texas_Synchrophasor... · 2010-08-04 · Synchrophasor Detective – EVERY day has surprises and

17

Low Wind

High Wind

McDonald Observatory w.r.t. UT Austin Phase Angle Oscillations

Low Wind Generation Period, Feb. 27, 2010, 1- 3 pm

0.0

0.5

1.0

1.5

2.0

2.5

3.0

0.00.10.10.20.20.30.3

Normalized Damping Ratio

Dam

ped

Res

onan

t Fre

quen

cy

McDonald Observatory w.r.t. UT Austin Phase Angle OscillationsHigh Wind Generation Period, Feb. 28, 2010, 1- 3 pm

0.0

0.5

1.0

1.5

2.0

2.5

3.0

00.050.10.150.20.250.3

Normalized Damping RatioD

ampe

d R

eson

ant F

requ

ency

More Observations

From Last Spring: Modal analysis of ambient oscillations show that high wind causes tighter clustering of damped resonant frequency points

unstable

unstable0.3 0.25 0.2 0.15 0.1 0.05

Page 18: McDonald Observatory Austin 400 miles 300 milesewh.ieee.org/cmte/pes/etcc/M_Grady_Texas_Synchrophasor... · 2010-08-04 · Synchrophasor Detective – EVERY day has surprises and

18

Ringing Frequency vs Wind Generation (% of Total), Sep 2009 ‐ Feb 2010

0

0.5

1

1.5

2

2.5

3

0 2 4 6 8 10 12 14 16 18 20

Wind Generation (% of Total)

Freq

uency (Hz)

Ringdown Analysis of More Than 100 Unit Trips Yields No Clear Relationship Between Wind MW and Damped Resonant Frequency

More Observations, cont.

Page 19: McDonald Observatory Austin 400 miles 300 milesewh.ieee.org/cmte/pes/etcc/M_Grady_Texas_Synchrophasor... · 2010-08-04 · Synchrophasor Detective – EVERY day has surprises and

19

Damping Ratio vs Wind Generation (% of Total), Sep 2009 ‐ Feb 2010

0

0.2

0.4

0.6

0.8

1

1.2

0 2 4 6 8 10 12 14 16 18 20

Wind Generation (% of Total)

Normalized

Dam

ping

Ratio

Ringdown Analysis of More Than 100 Unit Trips Yields No Clear Relationship Between Wind MW and Normalized Damping Ratio

More Observations, cont.

Page 20: McDonald Observatory Austin 400 miles 300 milesewh.ieee.org/cmte/pes/etcc/M_Grady_Texas_Synchrophasor... · 2010-08-04 · Synchrophasor Detective – EVERY day has surprises and

20

What Have We Learned Thus Far?1. After knowing “are the lights on everywhere,” voltage phase angles

across a grid (i.e., synchrophasors) are arguably the next most important grid diagnostic measurement.

2. While voltage synchrophasors are valuable in steady-state analysis, they are far more valuable in observing the dynamic performance of a grid, e.g. damped resonant frequencies and normalized damping coefficients that indicate grid stress and stability.

3. Because voltage synchrophasors are very sensitive to grid disturbances, they can be thought of as the “EKG” of power grids. They quickly point out abnormalities not easily seen in conventional voltage, frequency, and power measurements. Grid “stress tests”come frequently, each time a generator trips off line.

4. If Steinmetz had known about GPS time stamping in the early 1900’s, synchrophasors would have been in common use for the past 50-60 years.

Page 21: McDonald Observatory Austin 400 miles 300 milesewh.ieee.org/cmte/pes/etcc/M_Grady_Texas_Synchrophasor... · 2010-08-04 · Synchrophasor Detective – EVERY day has surprises and

21

What Have We Learned Thus Far, continued ?

5. Excluding redundancy requirements, ten or so strategically-placed synchophasor units in a grid the size of ERCOT are adequate.

6. 120V wall outlets on distribution feeders have proven themselves to provide essentially the same results as transmission voltage measurements.

7. The three reasons that 120V wall outlets are suitable for synchrophasor purposes are that

• Grid oscillations are in the 0.5 to 2 Hz range and readily pass through transformers of all sizes,

• Schweitzer relays effectively filter out distribution noise,

• With 30 points streaming in each second from remote monitoring points, occasional dropouts due to deep voltage sags or internettraffic cause no problems.

Page 22: McDonald Observatory Austin 400 miles 300 milesewh.ieee.org/cmte/pes/etcc/M_Grady_Texas_Synchrophasor... · 2010-08-04 · Synchrophasor Detective – EVERY day has surprises and

22

Texas Synchrophasor Network

Thanks to

• Schweitzer Engineering Laboratories – for all the equipment and technical support that we have and will need

• EPRI – for past, present, and future funding of graduate students and faculty summer support

• Startup money in 2008 from the Texas Governor’s Emerging Technology Fund through CCET

• Austin Energy – for installing the 69kV grid monitor, and providing advice on system operating and protection

Dr. Mack Grady, Mr. Moses Kai, IEEE-PES Breaking News, Minneapolis, July 26, 2010

Page 23: McDonald Observatory Austin 400 miles 300 milesewh.ieee.org/cmte/pes/etcc/M_Grady_Texas_Synchrophasor... · 2010-08-04 · Synchrophasor Detective – EVERY day has surprises and

23

Biographies

William Mack Grady is a Professor of Electrical & Computer Engineering at U.T. Austin and a Fellow of IEEE for “Contributions to the Analysis and Control of Power System Harmonics and Power Quality.” He received his BSEE from U.T. Arlington, and MSEE and PhD from Purdue University. His research topics are power quality, grid studies, synchrophasors, and integration of renewable energy into the grid. His research sponsors are EPRI, Schweitzer Engineering Labs, Austin Energy, DOE, and NREL.

Moses Kai is a Graduate Research Assistant at U.T. Austin, working in the area of synchrophasors and impact of large-scale wind generation on ERCOT. He received his BSEE and MSEE from U.T. Austin in 2007 and 2009, respectively, and is now working toward his PhD. He also serves as a Teaching Assistant for the Power Electronics Lab course, which has an enrollment of more than 130 students per year. He is a student member of IEEE and a U.S. citizen.