MCCB

Embed Size (px)

DESCRIPTION

Moulded Case Circuit Breaker

Citation preview

  • 3VL 630 Spec Sheet (A4) 3/24/00 3:46 PM Page 3

    SENTRON VL630Specifications

  • 3VL 630 Spec Sheet (A4) 3/24/00 3:46 PM Page 4

    Catalog Information

    Specifications:Category AIEC 60947-2 EN609473-4 Poles315-630 Amperes, 220/240Vac, 380/415Vac,690Vac50-60hz.Ui 750VacUimp 8kV

    CE MarkedCalibrations for 50C ambient

    Permissible Loadfor various ambient temperatures close to the circuit-breaker, related to the rated current of the circuit-breaker used for line protection.

    @ 40C--100% @ 50C--100% @ 60C--93% @ 70C--86%

    Endurance10,000 operations @ 600 per/hour

    Watts loss (power loss)at maximum rated current In3 phase symmetrical load for line protection----230 watts--T/M

    160 watts--ETU/LCD

    Permissible mounting position

    Breaker shipping weight 3 pole = 18.1 lbs. / 8.4kg. 4 pole = 23.8lbs. / 11kg.

    900300

    Reverse feed--All VL630 frame circuit breakersare suitable for reverse feed applications.

    300900

    Type IN UE ICU ICS ICMVL630N 315-630A 220/240~ 65kA 65kA 143kA

    380/415~ 45kA 45kA 94.5kA690~ 20kA 10kA 42kA

    VL630H 315-630A 220/240~ 100kA 75kA 220kA380/415~ 70kA 70kA 143kA

    690~ 30kA 15kA 63kAVL630L 315-630A 220/240~ 200kA 150kA 440kA

    380/415~ 100kA 75kA 220kA690~ 35kA 17kA 73.5kA

    Adj. thermal overload 80 to 100% x INAdj. short circuit releases Ii IN Short circuit release Ii

    315 1575 - 3150 400 2000 - 4000 500 2500 - 5000 630 3250 - 6500

    All VL630 circuit-breakers are shipped withfactory supplied Nut Keeper Plates for both incomingand outgoing terminals. Customer determines needfor termination devices.

    AmpereRating

    IN Ir

    3 = 3 poles1 = Standard interruption2 = High interruption

    4 = 4 poles w/left pole (N) switching

    E = Non-adjustable circuit-breaker IN = 630A only

    C = Adjustable thermal overload & short-circuit releases (N) pole protected when using with 4 pole

    Thermal/magnetic circuit-breaker

    3 = Very High interruption

    D = Thermal/magnetic

    protection---4 poles

    protection---3 polesE = Thermal/magnetic

    315 250 to 315 3VL5731 - 6 - 0AA0400 315 to 400 3VL5740 - 6 - 0AA0500 400 to 500 3VL5750 - 6 - 0AA0630 500 to 630 3VL5763 - 6 - 0AA0

    (N) pole = 60% protected

    K = Starter protection only -- IJ = 4 pole (N) without protection

    N = 315A, 630A3 pole only

    Product SpecificationsVL630 Frame630 Amperes

    SENTRON VL Series

  • 3VL 630 Spec Sheet (A4) 3/24/00 3:46 PM Page 5

    2HS/2AS2AS4HS4HS (*)

    Catalog Number4HS (2NO +2NC) 3VL9800-2AC002HS (1NO +1NC) + 1AS (1NO)

    Individual Auxiliary switch:3SB3400-0K (NO contact) Rated thermal current Ith ---10Amps3SB3400-0J (NC contact) Rated making capacity-------10Amps

    3VL9800-2AE00

    4HS2AS

    2HS / 2AS

    (*) Do not use N - pole is accessoriesare installed in left pole

    + ++

    +

    +

    ++ +

    rightN - pole

    left

    U