HORA MC-Series - the new generation of linear actuators
• Microcontroller equipped• intelligent• all-inclusive
MC-Series: Cover
3
Holter Regelarmaturen GmbH & Co. KG ©20.11.2008 MC100
•Haubenfixierung in 4 Positionen, alle 90°
•Kein Verschraubenerforderlich
MC-Series: 3-point control signal (on/off)
5
24 VAC 24 VDC
230 VAC
Holter Regelarmaturen GmbH & Co. KG ©20.11.2008 MC100
MC-Series: Modulated control signal
6
24 VAC 24 VDC
230 VAC
0...10 VDC
2...10 VDC
0...20 mA
4...20 mA
Holter Regelarmaturen GmbH & Co. KG ©20.11.2008 MC100
MC-Series: Calibration
7
Init
Holter Regelarmaturen GmbH & Co. KG ©20.11.2008 MC100
•Self-stroking•Automatic compensation of the
tolerances of the valve•The entire stroke of the valve is
passed by the maximum speed
MC100: DIP-switches
8
S1 X normalX inverted
SwitchONOFF
S30...10V (0...20mA)2...10V (4...20mA)
S2Y normalY inverted
S4hysteresis 0,15Vhysteresis 0,5V
S5Autopause / Autotest onAutopause / Autotest off
S6safety position bottomsafety position top
Holter Regelarmaturen GmbH & Co. KG ©20.11.2008 MC100
MC100: Adjustable actuating time
slow9 s/mm
medium4 s/mm
fast 1,9 s/mm
very slow12 s/mm
10
Holter Regelarmaturen GmbH & Co. KG ©20.11.2008 MC100
MC-Series: Feedback signal
11
Holter Regelarmaturen GmbH & Co. KG ©20.11.2008 MC100
•TRUE output signal 0..10V, real time•optional 0..20mA / 4..20mA
MC-Series: Line break recognition
12
Holter Regelarmaturen GmbH & Co. KG ©20.11.2008 MC100
•Automatic line break recognition in modulated mode (2...10V or 4... 20mA):
When Y-Signal drops below 1V or 2mA, the actuator moves to the limit position set by
coding switch S6•Control LED on board
MC-Series: Error detection
13
Holter Regelarmaturen GmbH & Co. KG ©20.11.2008 MC100
•In case the valve becomes mechanically blocked, e.g. by a particle, the actuator returns briefly and tries up to seven times again to reach the required position. If the
particle is still there then, the actuator stops. A control LED blinks.
MC-Series: Repeat back signal by manual actuation
14
Holter Regelarmaturen GmbH & Co. KG ©20.11.2008 MC100
24 VAC 24 VDC
230 VAC
HORA MC-Series: Advantages
15
MC-Series actuators are...
Holter Regelarmaturen GmbH & Co. KG ©20.11.2008 MC100
HORA MC Series: Advantages
16
MC-Series actuators are...
Flexible:
1 .In series suitable for 3-point signal as well as for continuous control signal.
2 .Possibility to change the speed on site by the simple use of DIP-switches.
3 .DC is possible as well as AC in the 24V version.
Note: The use of smoothed DC is possible with the MC103, MC253 and MC503. For the MC1003, the thrust is reduce by 20%, for the MC1503 by 10% and for the MC163
by 20%. For the MC403, the actuating speed has to be reduced. The use of the MC103-SE with 24V smoothed DC is not recommended.
The use of smoothed DC always has to be stated in the order .