If you can't read please download the document
Upload
ritesh-jaiswal
View
48
Download
0
Embed Size (px)
DESCRIPTION
transformer
Citation preview
1
Dynamic testing of on-load tap changer switching
2
On-load Tap Changer Designs
A typical diverter switch type OLTC showing both tap selector switch and diverter switch (MR)
A typical OLTC with selector switch (17 taps linear) (ABB)
3
WRM/tap, diverter design Old/aged condition
4
WRM/tap , selector type OLTC As new
5
Dynamic measurements during tap switching
Continuity/break-before-make testing Shut-off if current path is interrupted
Current change detection
Dynamic measurements (DRM) Dynamic current/ripple
Dynamic voltage
Dynamic resistance
6
Considerations/issues when performing dynamic testing
Transformer winding inductance is not constant Low or high test current (saturation or not)
Open or shorted secondary (assuming LTC on primary)
Measurement data is pending power source Constant current source
Constant voltage source
Source impedance
7
Dynamic current measurements at different test curr ent30 MVA, YNyn0, open LV
20A, 38% current drop 10A, 27% current drop
5A, 14% current drop 1A, 4% current drop
AM Forum workshop, Madrid 2011
8
Dynamic current measurements at different test curr ent30 MVA, YNyn0, shorted LV
20A, 64% current drop 10A, 67% current drop
5A, 67% current drop 1A, 50% current drop
AM Forum workshop, Madrid 2011
9
Dynamic Resistance Measurements on a load tap-changer (direct method)
TM1800/1700/1600/EGIL(CBA)
LTC135 (PS)
DC test current
DC test currentLV windings shorted
Computer for detailed
analysis and reporting
Measure test current and voltage over the winding
Calculate R (source impedance >> resistor value)
10
Tap transition Selector + diverter typ LTC
Typical LTC sequence of events when tap is switched from one position to next.
11
Tap transition - Selector switch LTC
12
OLTC DRM measurements, Uppsala
Transformer data: 20 MVA, 20/10 kV, YNyn, (spare unit in good condition) OLTC on HV with 17 taps (selector switch type LTC)
Test equipment: TM1800 CB-DRM analyzer
Multi-channel voltage and current measurements OLTC control Static and dynamic resistance measurements
LTC135 DC source for load-tap changer testing 48 V compliance voltage 1 x 5A (10 output impedance) 3 x 1A (48 output impedance) 3 x 0.1A (480 output impedance) Safe discharge of windings after measurement
13
DRM with LV shorted
DRM with constant current source
Blue Voltage/Resistance, Red Test current.
H1 1-2 tap change with LV shorted.
Transition times and resistor values easily recognized
Resistance
Time
14
Transition time measurements
H1 OLTC transition times. 1-2 to 16-17 tap change (ms)
15
Resistor values, H1
R1 and R2 transition resistance values per tap (value/10). All within spec ( 10%)
16
Static and Dynamic Resistance Measurements on a load tap-changer in one operation (patent pending)
TM1800/1700/1600/EGIL(CBA)
LTC135 (PS)
DC test current
DC test current
LV windings NOT shorted!
Computer for detailed
analysis and reporting
17
Dynamic measurements, current (5A) + HV and LV voltage - 20 MVA, YNyn0, open LV
R1 and R2 transition resistor values per tap (value/10). All within spec ( 10%)
Current
HV voltage
LV voltage
18
Dynamic analysis, utilizing new method (patent pending) for calculating resistance
LV voltage
HV voltage
Resistance
Test current
T1 70 msT1//2 8 msT2 56 msTswitch 134 msRwinding 0.52 R1 2.94 R// 1.42 R2 2.83
19
OLTC DRM measurements, Stockholm
Transformer data: ASEA-Lepper 6 MVA, 21/11 kV, Dyn11, 1973 OLTC ASEA ASEA UZEDT , 17 taps
Test equipment: TM1700 CB-DRM analyzer
Multi-channel voltage and current measurements OLTC control Static and dynamic resistance measurements
LTC135 DC source for load-tap changer testing 48 V compliance voltage 1 x 5A (10 output impedance) 3 x 1A (48 output impedance) 3 x 0.1A (480 output impedance) Safe discharge of windings after measurement
20
Dynamic analysis, ASEA Lepper 6 MVA with LTC ASEA UZEDT, start time
21
Dynamic analysis, ASEA Lepper 6 MVA with LTC ASEA UZEDT, switch time
22
Dynamic analysis, ASEA Lepper 6 MVA with LTC ASEA UZEDT, start time
0
500
1000
1500
2000
2500
3000
Start time, ms
Start time, ms
23
Dynamic analysis, ASEA Lepper 6 MVA with LTC ASEA UZEDT, switch time
0
10
20
30
40
50
60
R1 time, ms
R// time, ms
R2 time, ms
Total swithc time, ms
24
OLTC DRM measurements, Belgrade
Transformer data: ELTA 16 MVA, 110/36.75/10.5 kV, YNynd5, 1973 OLTC ELIN on HV with 27 taps (23 effective)
Test equipment: TM1700 CB-DRM analyzer
Multi-channel voltage and current measurements OLTC control Static and dynamic resistance measurements
LTC135 DC source for load-tap changer testing 48 V compliance voltage 1 x 5A (10 output impedance) 3 x 1A (48 output impedance) 3 x 0.1A (480 output impedance) Safe discharge of windings after measurement
25
ELTA, tap 1-7, up
26
ELTA, tap 4-5 transition, 1A
27
ELTA, tap 2-3 transition, 1A
28
Summary and conclusions A CB analyzer/signal recorder with analog inputs together with suitable power supply is a
good tool for performing various DRM measurements e.g. on load tap-changers To measure dynamic properties in a tap changer (HV), several methods are possible:
Measure dynamic current/ripple on primary with a const ant voltage source and secondary open Current drop value is strongly pending test current/winding inductance and can only be used as fingerprint Contact switching/timing may be measured (difficult) Diverter resistor values cannot be measured
Measure dynamic current/ripple on primary with a const ant voltage source and secondary short-circuited
Current drop value is slightly pending test current/winding inductance Contact switching/timing can be measured Diverter resistor values cannot be measured
Measure dynamic resistance on primary with a constant current source and secondary short-circuited
Contact switching/timing can be measured Actual diverter resistor values can be measured (high impedance source)
Measure dynamic voltage on secondary Contact switching/timing can be measured Actual diverter resistor values cannot be measured
Measure dynamic resistance by measuring dynamic voltage on primary and secondary windings Contact switching/timing can be measured Actual diverter resistor values can be measured (patent pending)
29
The doctor is in...