Matz 5

Embed Size (px)

DESCRIPTION

transformer

Citation preview

  • 1

    Dynamic testing of on-load tap changer switching

  • 2

    On-load Tap Changer Designs

    A typical diverter switch type OLTC showing both tap selector switch and diverter switch (MR)

    A typical OLTC with selector switch (17 taps linear) (ABB)

  • 3

    WRM/tap, diverter design Old/aged condition

  • 4

    WRM/tap , selector type OLTC As new

  • 5

    Dynamic measurements during tap switching

    Continuity/break-before-make testing Shut-off if current path is interrupted

    Current change detection

    Dynamic measurements (DRM) Dynamic current/ripple

    Dynamic voltage

    Dynamic resistance

  • 6

    Considerations/issues when performing dynamic testing

    Transformer winding inductance is not constant Low or high test current (saturation or not)

    Open or shorted secondary (assuming LTC on primary)

    Measurement data is pending power source Constant current source

    Constant voltage source

    Source impedance

  • 7

    Dynamic current measurements at different test curr ent30 MVA, YNyn0, open LV

    20A, 38% current drop 10A, 27% current drop

    5A, 14% current drop 1A, 4% current drop

    AM Forum workshop, Madrid 2011

  • 8

    Dynamic current measurements at different test curr ent30 MVA, YNyn0, shorted LV

    20A, 64% current drop 10A, 67% current drop

    5A, 67% current drop 1A, 50% current drop

    AM Forum workshop, Madrid 2011

  • 9

    Dynamic Resistance Measurements on a load tap-changer (direct method)

    TM1800/1700/1600/EGIL(CBA)

    LTC135 (PS)

    DC test current

    DC test currentLV windings shorted

    Computer for detailed

    analysis and reporting

    Measure test current and voltage over the winding

    Calculate R (source impedance >> resistor value)

  • 10

    Tap transition Selector + diverter typ LTC

    Typical LTC sequence of events when tap is switched from one position to next.

  • 11

    Tap transition - Selector switch LTC

  • 12

    OLTC DRM measurements, Uppsala

    Transformer data: 20 MVA, 20/10 kV, YNyn, (spare unit in good condition) OLTC on HV with 17 taps (selector switch type LTC)

    Test equipment: TM1800 CB-DRM analyzer

    Multi-channel voltage and current measurements OLTC control Static and dynamic resistance measurements

    LTC135 DC source for load-tap changer testing 48 V compliance voltage 1 x 5A (10 output impedance) 3 x 1A (48 output impedance) 3 x 0.1A (480 output impedance) Safe discharge of windings after measurement

  • 13

    DRM with LV shorted

    DRM with constant current source

    Blue Voltage/Resistance, Red Test current.

    H1 1-2 tap change with LV shorted.

    Transition times and resistor values easily recognized

    Resistance

    Time

  • 14

    Transition time measurements

    H1 OLTC transition times. 1-2 to 16-17 tap change (ms)

  • 15

    Resistor values, H1

    R1 and R2 transition resistance values per tap (value/10). All within spec ( 10%)

  • 16

    Static and Dynamic Resistance Measurements on a load tap-changer in one operation (patent pending)

    TM1800/1700/1600/EGIL(CBA)

    LTC135 (PS)

    DC test current

    DC test current

    LV windings NOT shorted!

    Computer for detailed

    analysis and reporting

  • 17

    Dynamic measurements, current (5A) + HV and LV voltage - 20 MVA, YNyn0, open LV

    R1 and R2 transition resistor values per tap (value/10). All within spec ( 10%)

    Current

    HV voltage

    LV voltage

  • 18

    Dynamic analysis, utilizing new method (patent pending) for calculating resistance

    LV voltage

    HV voltage

    Resistance

    Test current

    T1 70 msT1//2 8 msT2 56 msTswitch 134 msRwinding 0.52 R1 2.94 R// 1.42 R2 2.83

  • 19

    OLTC DRM measurements, Stockholm

    Transformer data: ASEA-Lepper 6 MVA, 21/11 kV, Dyn11, 1973 OLTC ASEA ASEA UZEDT , 17 taps

    Test equipment: TM1700 CB-DRM analyzer

    Multi-channel voltage and current measurements OLTC control Static and dynamic resistance measurements

    LTC135 DC source for load-tap changer testing 48 V compliance voltage 1 x 5A (10 output impedance) 3 x 1A (48 output impedance) 3 x 0.1A (480 output impedance) Safe discharge of windings after measurement

  • 20

    Dynamic analysis, ASEA Lepper 6 MVA with LTC ASEA UZEDT, start time

  • 21

    Dynamic analysis, ASEA Lepper 6 MVA with LTC ASEA UZEDT, switch time

  • 22

    Dynamic analysis, ASEA Lepper 6 MVA with LTC ASEA UZEDT, start time

    0

    500

    1000

    1500

    2000

    2500

    3000

    Start time, ms

    Start time, ms

  • 23

    Dynamic analysis, ASEA Lepper 6 MVA with LTC ASEA UZEDT, switch time

    0

    10

    20

    30

    40

    50

    60

    R1 time, ms

    R// time, ms

    R2 time, ms

    Total swithc time, ms

  • 24

    OLTC DRM measurements, Belgrade

    Transformer data: ELTA 16 MVA, 110/36.75/10.5 kV, YNynd5, 1973 OLTC ELIN on HV with 27 taps (23 effective)

    Test equipment: TM1700 CB-DRM analyzer

    Multi-channel voltage and current measurements OLTC control Static and dynamic resistance measurements

    LTC135 DC source for load-tap changer testing 48 V compliance voltage 1 x 5A (10 output impedance) 3 x 1A (48 output impedance) 3 x 0.1A (480 output impedance) Safe discharge of windings after measurement

  • 25

    ELTA, tap 1-7, up

  • 26

    ELTA, tap 4-5 transition, 1A

  • 27

    ELTA, tap 2-3 transition, 1A

  • 28

    Summary and conclusions A CB analyzer/signal recorder with analog inputs together with suitable power supply is a

    good tool for performing various DRM measurements e.g. on load tap-changers To measure dynamic properties in a tap changer (HV), several methods are possible:

    Measure dynamic current/ripple on primary with a const ant voltage source and secondary open Current drop value is strongly pending test current/winding inductance and can only be used as fingerprint Contact switching/timing may be measured (difficult) Diverter resistor values cannot be measured

    Measure dynamic current/ripple on primary with a const ant voltage source and secondary short-circuited

    Current drop value is slightly pending test current/winding inductance Contact switching/timing can be measured Diverter resistor values cannot be measured

    Measure dynamic resistance on primary with a constant current source and secondary short-circuited

    Contact switching/timing can be measured Actual diverter resistor values can be measured (high impedance source)

    Measure dynamic voltage on secondary Contact switching/timing can be measured Actual diverter resistor values cannot be measured

    Measure dynamic resistance by measuring dynamic voltage on primary and secondary windings Contact switching/timing can be measured Actual diverter resistor values can be measured (patent pending)

  • 29

    The doctor is in...