Potential of Achieving Comfort Conditions in a Typical Housing Project in the Composite Climate of North India using Passive and Low Energy Ideas London Metropolitan University MSc Integration of Renewable Energies in Buildings MODULE CODE ADP034N Hitanshu Jishtu 07031328 September 2008 A thesis submitted in partial fulfilment for requirement for the degree of Master of Science.

Masters Dissertation

Embed Size (px)

DESCRIPTION

Masters Thesis, Potential for Passive design strategies in Architecture, Housing

Citation preview

Page 1: Masters Dissertation

Potential of Achieving Comfort Conditions in a Typical Housing Project

in the Composite Climate of North India using Passive and Low Energy Ideas

London Metropolitan UniversityMSc Integration of Renewable Energies in Buildings

MODULE CODE ADP034N

Hitanshu Jishtu07031328September 2008

A thesis submitted in partial fulfilment for requirement for the degree of Master of Science.

Page 2: Masters Dissertation

CONTENTsABsTRACT 4CHAPTER 11.0 INTRODUCTION 61.1 A INTRODUCTION OF THE CONTEMPORARY HOUsING IN DELHI, THE CHOsEN sITE. 81.11 Traditional Housing 8

CHAPTER 2 PROJECT BRIEF- TIVOLI 112.1 Introduction of the Project Tivoli 122.2 site 132.3 site planning 132.4 Typology of Units 142.5 Climatic Comfort 16

CHAPTER 3 CLIMaTE anaLySIS 173.1 Composite Climate 183.3 sEAsONs 193.31 sUMMER sEAsON 203.32 MONsOON sEAsON 203.33 WINTER sEAsON 223.34 MILD sEAsON 223.4 Prevailing Winds 233.5 solar Altitudes 243.6 WEATHER DATA 253.7 THERMAL COMFORT 263.71 THERMAL COMFORT sTUDIEs 263.72 ADAPTIVE COMFORT 273.73 ADAPTIVE COMFORT RANGE INDIAN CODEs (NBC) 283.8 GENERAL ENVIRONMENTAL sTRATEGIEs 29 3rd of June (summer season) 30 6Th of August (Monsoon season) 31 7Th of January (Winter season) 32

CHAPTER 4 anaLySIS 334.1 Methodology 344.2 EFFECT OF CLIMATE ON DEsIGN 364.21 ORIENTATION 364.22 EFFECT OF sOLAR RADIATION 374.23 DAYLIGHTING ANALYsIs 394.24 EFFECT OF WIND 414.25 EFFECT OF TEMPERATURE 424.3 TAs Dynamic thermal modelling TAs 424.31 ANNUAL sPACE TERMPERATURE DIsTRIBUTION 444.32 TEMPERATURE PROFILE N-FLAT 454.33 ANNUAL TEMPERATURE PROFILE 47

Page 3: Masters Dissertation

CHAPTER 5 PAssIVE DEsIGN RECOMENDATIONs 5.2 THE BUILDING ENVELOPE 505.1 Climatic design for Composite Climates 505.3 IMPACT OF CHANGE IN THERMAL MAss LAYERs 525.4 sTRATEGIEs FOR VARIOUs sEAsONs 585.41 sUMMER sEAsON 585.42 Winter season 595.43 MONsOON sEAsON 605.44 MILD sEAsON 60

CHAPTER 6 ANALYsIs OF RECOMMENDATIONs 616.1 Comparison of Base case Annual energy demand with proposed recommendations 626.11 Comparing the temperature and cooling loads against base case in North Flat 636.12 Comparing the temperature and cooling loads against base case in south Flat 646.13 Effect of mixed mode ventialtion on Cooling load 656.12 Annual space Temperature Disribution. 66

CONCLUsIONs 69

BIBLIOGRAPHY 70

Page 4: Masters Dissertation

ABsTRACT

north India has extremities of climate. a composite climate where the summers tend to be hot with temperatures reaching up to 45deg C and in winters dropping down to 0deg C. It is a challenge designing for comfort within these parameters as the systems need to be flexible to change course in dealing with the climate. The traditional houses in these climates had through all the years been adapted to offered the flexibility in being suited to the climate.

Today’s mass produced housing schemes rely heavily on mechanical means for creating comfortable thermal conditions and are more in tuned for the ease of construction, convenience, profitibility and housing density figures. Climatic comfort as such is as an afterthought to be consigned to mechanical means. Given the high costs and unavailability of energy air-conditioning or heating system is a burden in most of the houses without which the spaces tend to be uncomfortable for a large part of the year.

The thesis attempts to suggest strategies by simulating a typical real world housing project in the national Capital Region of Delhi to put it within the comfort zone by using passive systems and low energy consumption technologies which are viable in the situation there.

Simulation tools today offer the possibilities to render the conditions and to fine-tune the design to suit the conditions. Right from selecting the right orientation to the area of glazing and shadings can have a great effect on the indoor climate and the strategies can be successfully refined by these simulation tools. This thesis exploits the possibilities offered by the simulation tools of Radiance, Ecotect, TaS and Esp-r to arrive at the conclusions for the suggestions.

The existing design prototypes as mentioned are postulated to be out of the comfort band for a large part of the year. The objective ways to find a prototype housing project and study if it meets the parameters of comfort conditions using the adaptive thermal comfort indices. The intent was to find the period it is out of the comfort zone and to suggest solutions using firstly passive design strategies and where unsuitable to reduce the heating or cooling load as appropriate.

By incorporating the design interventions it is proved that the buildings can be within the comfort zone for a longer duration of time with passive solutions like orientation, appropriate sunshades and insulation in the building fabric. Where it is not feasible to get the building within the comfort zone entirely the aim is to reduces the heating and cooling load saving energy as compared to the conventional design.

Page 5: Masters Dissertation

CHAPTER 1InTRODUCTIOn

Page 6: Masters Dissertation

Introduction �

1.0 INTRODUCTION

The relation between the building and its surroundings is an important criteria which defines the design and the positioning of the building. The thesis will attempt to explore ways to make the contemporary housing design in the composite climate of north India more energy efficient and comfortable to inhabit using passive design strategies to a large extent. at the same time explore ways to reduce the heating and cooling load of a typical model of housing project being built today in that particular mentioned climate.

The guidelines to be determined for the energy efficient design include:

1) The impact of solar gains on the heating and cooling load of a building2) The impact of passive design strategies like shading devices and orientation on the heating and cooling loads.3) The impact of the insulation and glazing ratio on the heat gain/loss in the building. 4) The optimisation of the daylight levels in the interiors.

The current standards for the energy efficiency in Indian buildings is defined by the Energy Conservation Building Code (ECBC)- 2007. This code specifies the guidelines to be followed to make the buildings energy efficient in the climatic zones of India by specifying the energy conservation measures which should be incorporated to achieve the standard. The thesis will adhere to them and where possible exceed the set standard by taking up a case of a typical housing project in the composite climate of Delhi.

The thesis will rely on building simulation tools to explore the hypothesis and verify the strategies to be adopted based on the study of the existing housing design. In the first part a typical housing design is chosen as a prototype. This existing design is modelled and simulated using computer software’s for

- thermal analysis,- daylight and sunlight shading - Facade performance and optimisation- Building aerodynamics and ventilation

The data derived is analysed to formulate methods for energy efficient design by reducing the heating and cooling loads and passive design. a detailed study of the climate is also undertaken with which derivation is got as to the strategies to be adopted to deal with it and use it in a positive manner in the incorporation of the design.

Page 7: Masters Dissertation

Introduction 7

From the analysis of the data from the simulation and the outcome of the climatic study the suggestions are incorporated in the existing design and verified by the computer simulation for their effectiveness.

The study is done as a prototypical study for the housing design and although it is site specific and also relies on the particular chosen design, it can considered as a study of climate specific design for housing in composite climates as it emphasises on basic strategies to be followed in achieving the comfort parameters and energy efficiency targets for buildings.

Page 8: Masters Dissertation

Introduction 8

1.1 A INTRODUCTION OF THE CONTEMPORARY HOUsING IN DELHI, THE CHOsEN sITE LOCATION.

The contemporary housing is a far contrast from the traditional housing in India. The progressing economic situation has changed the dynamics of housing and the more demanding people have become. Gone are the small low rise individual houses and the new trend is are housing estates being put forward by developers which have all amenities within the estate. The houses have all modern functional requirements with regard to modern lifestyles and rely on mechanical means to cool and heat the interiors.

1.11 Traditional Housing

The traditional houses of the region had been adapted to be functional in the climatic and site specific context. The house planning followed the courtyard type of houses which ensured the house was shaded and in sun at the same time throughout the day. This made the space multi functional throughout the year as the same space could be used according to the season. The shaded spaces in the summers and the sun lit spaces in the winter. The design was most appropriate for the climate and most low rise houses in the older towns and cities follow this pattern.

They had specific characteristics like thick stone walls and roof which provided a thermal mass to balance the temperature and the insulate from the outside vagaries of the temperature. The climatic aspects of this house design have been well documented and studied and were appropriate for the lifestyle of the people in those times.

fig. 1 courtyard house in Delhi: Source : author

Page 9: Masters Dissertation

Introduction �

The forts of the region are a classic example of the way the climate was overpowered to make the conditions comfortable to inhabit. The kings and the other noblemen would live in the forts which were usually a series of courts which had connected rooms. These courtyards had landscaped gardens and water pools which effectively altered the micro climate to make it comfortable.

Changing lifestyles which have followed the globalised world have changed the pattern of housing as well. The courtyard houses have now been replaced down the years with multi-storeyed houses. as the pressures on the land have increased the land prices getting way beyond reach the obvious answer has been to go higher up and towering housing blocks are now becoming more and more common. With most developers trying to economise they seem to be the way forward now.

The growing metropolis has altered the surroundings and encompassed them within. Today Delhi itself is a city with a population of over 15 million inhabitants (2001 Census data, Survey of India). The trend which had started from the major metropolis in India has started to trickle down to the small towns as well which have felt the pressures on the scarce land and it has become difficult to see any regional features in the architecture of different places. The same block design, material palette and design feature gets replicated everywhere. The comfort conditions to be provided gets relied on air-conditioning which helps to moderate the climate within the interiors.

Fig. 2: Courtyards in Palaces:2a. Oberoi Palace Hotel, Udaipur. 2.b. Oberoi Jai Mahal, agrawww.oberiohotels.com

Page 10: Masters Dissertation

Introduction 10

The reliance on mechanical systems for climate control has inevitably been putting a huge pressure on the energy demand situation and it is in this context the government introduced the ECBC-200� code which has the guidelines for energy consumption to be specified for particular building types. This forces a rethink on the current thinking which delinks the environmental design and performance from the buildings and makes it imperative to use technologies to utilise passive climate control systems and renewable systems to make the buildings comfortable to inhabit.

figure 3. Typical housing estate in Delhi:source:

Page 11: Masters Dissertation

CHAPTER 2PROJECT BRIEF- TIVOLI

Chapter Overview

In the context of this thesis study a typical example of contemporary housing project has been selected for analysis and to see how it could be adapted to utilise passive systems to achieve comfort conditions and to reduce the heating and cooling loads. The Tivoli Holiday village at Daruhera is within the national Capital Region of Delhi has been chosen for this purpose. The detail of this project is described in this chapter.

Page 12: Masters Dissertation

Project Brief_Tivoli 12

2.1 Introduction of the Project Tivoli

The city of Delhi encompasses the surrounding areas and a vast area known as the National Capital Region (NCR) is what comprises of the extended city. Daruhera is one of the up coming regions of Delhi which till a few years ago was on the absolute outskirts of the place but is now seeing a lot of development as the city expands outwards. a number of developers have proposed projects there and the ‘Tivoli Holiday Village is being undertaken by T.G. Buildwell Pvt. Limited.

The project proposes 1-3 bedroom apartments and some villas on the site. The whole project is a self contained township and includes a health club and business centre incorporated within the estate. The housing is arranged in 5 towers with each having a different cluster layout.

Fig. 5: artists representation of Tivoli Holiday Village at Daruhera.aCPL Consutants, Delhi

Page 13: Masters Dissertation

Project Brief_Tivoli 13

2.2 site

The site is located at Daruhera, in the satellite town of Gurgaon. The area has been developed by dividing the land into different sectors and each being developed by a different development company. The distance from the international airport is almost 20 Kms and to the centre of Delhi is almost 50 Kms.

2.3 site planning

The zoning has been done by keeping the residential blocks in the back and the club house and the business centre as the focus. The residential blocks are oriented on a manner to create a parkland in the centre. The whole campus has underground parking as well as parking under each of the tower blocks on the ground floor. The whole structure is thus raised up on stilts.

Figure 7: Site PlanaCPL Consutants, Delhi

figure 6: Site LocationaCPL Consutants, Delhi

Page 14: Masters Dissertation

Project Brief_Tivoli 14

2.4 Typology of Units

The residential units are arranged in 14 storeyerd tower blocks with each block having a different arrangement of housing cluster combination. The residential units comprise of studio flats and 1-3 bedroom units with the top floor having a duplex pent houses on each block.

figure 8: Cluster plan 2 bedroom apartment

figure 9:Cluster plansingle bedroom apartment

Page 15: Masters Dissertation

Project Brief_Tivoli 15

Figure 11: Cluster planStudio apartment

Figure 10:artistic impression of Tivoli Holiday VillageaCPL Consultants, Delhi

Page 16: Masters Dissertation

Project Brief_Tivoli 1�

2.5 Climatic Comfort

The housing project is a high spec one and relies on air-conditioning for the living areas to create comfort conditions. Split aC units in each of the living areas and bedrooms linked to the outside units are proposed to provide comfort cooling. For ventilation the air infiltration through the windows is supposed to provide for the necessary required air changes.

no separate heating system is proposed and the same air conditioning units can be used in the reverse cycle to provide for the heating in the winter season.

Figure 12:cluster Plan 2 Bedroom apartment

Page 17: Masters Dissertation

CHAPTER 3CLIMaTE anaLySIS

Chapter Overview

The climate of the site was analysed to determine the strategies which could be adopted for passive climatic design. The chapter details out the climatic analysis and the outcomes for determining these strategies.

To see how the housing project interacts with the surrounding and the spaces between the buildings can interact will form the character of the project. Optimising the landscape and the architecture to harmonise the passive design of the building keeping in consideration the sunlight, daylight and wind factor is essential to study the climate of the place.

Page 18: Masters Dissertation

Climate Analysis 18

India has different climate zones and it ranges from the cold climate of north to the hot and humid of south India. In between is the composite climate which has the huge seasonal variation to be easily categorised into any one part.

3.1 Composite Climate

The composite climate is characterised by extremities of climate. There is no clear defined climate like hot or cold which is prevalent through the year. Rather the conditions vary to quite the extremities, being hot in summers and cold in winters.

Designing for climatic comfort using passive technologies thus becomes a challenge because both heating and cooling needs are required to be met. Doing this with passive systems is at the same time more challenging. For the purpose of evaluation of the climate to come up with strategies to define comfort conditions the weather data has been obtained from the ISHRAE (Indian Society for Refrigeration and air-conditioning engineers).

Figure 13: Climatic Zones of India:ECBC-200�.

Page 19: Masters Dissertation

Climate Analysis 1�

3.2 DELHI28̊N,78̊E

Delhi enjoys a composite climate and has a hot summers and cold winters. The famed Indian summer when it becomes unbearably hot lasts from april to June and is unbearably hot. The rainfall occurs in the months of July- September and it is consistent in these months with the sky overcast. after a transition month the weather again changes to be the opposite of summer with cold nights through to March.

3.3 sEAsONs

The climate of Delhi can be divided into 4 distinct zones based on the weather profile:

summer Hot & Dry

summer (Monsoon) Hot & Humid

Winter Winter Mild Mild

figure 14: Location map Delhiwww.

figure 15: weather profile of Delhi:generated using ecotect wether tool

Page 20: Masters Dissertation

Climate Analysis 20

3.31 sUMMER sEAsON

Lasts from april to the end to JuneThis season is characterised with a hot and dry weather. The day time temperature stays in the high 30’s degree Celsius mark and very often above 40̊ C . The maximum temperature does reach upto 45˚ C during some of the hottest days. The night time temperature generally is within the comfort zone or just a little above it. The mean outdoor temperature for the season is 7˚ C above the comfort level. A hot and dry wind from the Thar desert flows during the day time which is known as ‘loo’. The percentage of direct radiation is very high in the season and has up to 10 hours of sunshine.

3.32 MONsOON sEAsON

This season starts with the onset of the rains in the beginning of July. The rain brings relief to the high temperature but brings along the high humidity level. The temperature during the day hovers around the 30-35˚C mark and drops to a min. of around 25˚C during the night times. The low diurnal range of temperature is attributed to the high cloud cover which is there in the season.

••

figure 16: weather profile June 3:generated using ecotect weather tool

Page 21: Masters Dissertation

Climate Analysis 21

The percentage of direct radiation is very low compared to the summer season with the sky remaining cloudy through the season.The main characteristic is the very high humidity which remains generally above 80% throughout the season.Higher wind speed though does bring in some relief and is generally considered comforting.

N O R T H1 5 °

3 0 °

4 5 °

6 0 °

7 5 °

E A S T

1 0 5 °

1 2 0 °

1 3 5 °

1 5 0 °

1 6 5 °S O U T H

1 9 5 °

2 1 0 °

2 2 5 °

2 4 0 °

2 5 5 °

W E S T

2 8 5 °

3 0 0 °

3 1 5 °

3 3 0 °

3 4 5 °

1 0 k m/ h

2 0 k m/ h

3 0 k m/ h

4 0 k m/ h

5 0 k m/ h h rs

5 6 +

5 0

4 4

3 9

3 3

2 8

2 2

1 6

1 1

<5

Prevailing WindsW ind Fre q ue nc y (H rs )L o c a tio n : N E W D E L H I , I N D (2 8 .6 ° , 7 7 .2 ° )D a te : 1 st Ju ly - 3 1 st Ju lyT ime : 0 0 :0 0 - 2 4 :0 0© W e a t h e r T o o l

figure 17: weather profile August 15:generated using ecotect weather tool

figure 18: wind rose diag, Julygenerated using Ecotect Weather tool

Page 22: Masters Dissertation

Climate Analysis 22

3.33 WINTER sEAsON

The winter season is characterised with low night time temperature which falls down up to 4˚C. Generally the temperature in the nights is way below the comfort zone. However in the day time does manage to reach just up to the lower level of the comfort band.

3.34 MILD sEAsON

The 2 transition months of March and October are the only times when the temperatures are throughout the time within the extended comfort band. The temperatures are moderated both during the day and night times and the humidity level is also at a very acceptable level throughout.

figure 19: weather profile Oct 11:generated using ecotect weather tool

figure 18: weather profile Dec 22:generated using ecotect weather tool

Page 23: Masters Dissertation

Climate Analysis 23

3.4 Prevailing Winds

Fig 21:Wind Wose patterns of Delhi generated using Ecotect Weather tool

Page 24: Masters Dissertation

Climate Analysis 24

fig 23:

3.5 solar Altitudes

fig 24:

Page 25: Masters Dissertation

Climate Analysis 25

3.6 WEATHER DATA

The weather data for Delhi used in the simulations and for analysis has been sourced from the International Weather for Energy Calculation (IWEC). The summary of the weather data has been included in appendix XX

The IWEC data is the result of aSHRaE Research Project 1015 by numerical Logics and Bodycote Materials Testing Canada for aSHRaE Technical Committee 4.2 Weather Information. The IWEC data files are ‘typical’ weather files suitable for use with building energy simulation programs for 227 locations outside the USa and Canada.

Site Plan of Tivoli Hodiay Village at Daruhera:architect: aCPL Consultants , new Delhi

The files are derived from up to 18 years of DATSAV3 hourly weather data originally archived at the U. S. national Climatic Data Center. The weather data is supplemented by solar radiation estimated on an hourly basis from earth-sun geometry and hourly weather elements, particularly cloud amount information.

fig 25:

Page 26: Masters Dissertation

Climate Analysis 2�

3.7 THERMAL COMFORT

According to Givoni ‘Thermal comfort can be defined operationally as the range of climatic conditions considered comfortable and acceptable inside building’.

Thermal comfort depends on a number of factors. The dry bulb temperature, humidity, wind speed are some of the factors which define the comfort parameters. It however varies according to the place from the work being performed, requirement of people and location. Thermal comfort is in terms of sensations of the body how it perceives the sensations of hot, warm, slightly warmer, slightly cooler, cool or cold. It has a more relevant psychological perspective where the thermal comfort is the equilibrium between the heat exchange between the environment and the body.

Changing the weather conditions to make them suitable for human inhabitation has been one of the foremost needs for building. The traditional buildings of any place usually reflect the way they modify the parameters of weather inside even though the outside weather conditions are inhospitable. The desert houses of Jaisalmer in India evolved to keep the interiors comfortable even when the outside temperature goes above 45 ˚C,( Sofaee, F, 2004). The same effect is seen through the world wherever people live in difficult climates, the buildings they inhabit modify the climate to make the conditions for achieving thermal comfort. The seasonal variation in thermal conditions changes everywhere on the planet and it is obvious that the houses try to balance and moderate this effect.

3.71 THERMAL COMFORT sTUDIEs

Some of the earliest studies in thermal comfort have been done by ASHARAE since the 1920’s. At that time it focused on finding the most comfortable temperature at which the human body feels comfortable. These were later modified to include other parameters of humidity, and wind effect. The significant studies are the Comfort charts (ASHRAE 1967, 1981b, 1985, 1992, 1997). Other significant research was conducted by Fanger who proposed the Predicted Mean Vote (Fanger, 1972). Later these were modified and improved upon by Givoni with the Bio-Climatic Chart (Givoni, 1976)

Page 27: Masters Dissertation

Climate Analysis 27

3.72 ADAPTIVE COMFORT

The way the human body perceives the comfort in a particular climate is not depended only on the parameters of air temperature, humidity and wind speed at the particular space. We perceive the comfort in terms of the external weather factors as well, this is the theory of adaptive comfort’. The theory was put forward in the 1�70’s by nicol and Humphreys.

The adaptive model understands that the human responses vary with context and to preserve comfort people adapt to their surrounding conditions. The field studies led to the adaptive modelling approach (Humphreys & Nicol,1998) which aimed at testing an existing comfort index and finding an optimum comfort zone.

Humphrey’s and Auliciems (Auliciems and Szokolay 1997) expressed the comfort zone in terms of the notion of thermal neutrality. auliciems derived the following expression for free-running buildings:

Tn = 17.� + 0.31 To Where, Tn, neutral temperature deg.C To, mean monthly outdoor air temperature deg.C

A comfort zone can be then defined with the value of Tn at its center extended by 2K on either side thus giving a lower limit equal of Tn-2 and upper limit of Tn+2. The neutral comfort zone given by auliciems’ equation is 19-30 deg.C, which suggests that adaptive measures that will be taken by people will make this range of temperatures acceptable for the city of Delhi. ta tn tn-2 tn+2Jan 13.1 21.7 1�.7 23.7Feb 1�.7 22.8 20.8 24.8Mar 21.4 24.2 22.2 2�.2april 28.4 2�.4 24.4 28.4May 32.4 27.� 25.� 2�.�June 33.2 27.� 25.� 2�.�July 30.3 27.0 25.0 2�.0august 2�.7 2�.8 24.8 28.8September 2�.2 2�.7 24.7 28.7October 25.0 25.4 23.4 27.4november 1�.4 23.� 21.� 25.�December 14.� 22.1 20.1 24.1

Page 28: Masters Dissertation

Climate Analysis 28

3.73 ADAPTIVE COMFORT RANGE ACCORDING TO INDIAN CODEs (NBC)

The Indian National Building codes (NBC) define the comfort parameters according to the prevalent weather conditions there. They have been formulated after extensive testing to ascertain the temperature, humidity and wind speed combination in which a person can feel comfortable and productive.

according to them a person can be comfortable in a temperature of upto 35˚C provided sufficient wind speed is there and the humidity level is low enough.

Page 29: Masters Dissertation

Climate Analysis 2�

3.8 GENERAL ENVIRONMENTAL sTRATEGIEs

To formulate strategies for the climate different typical days are analysed which can give an overview of the methodology to follow. From the 3 distinct seasons Summer, Monsoon and winter which have been defined for the climate one typical day is selected and analysed.

fig 26:

fig 27

Page 30: Masters Dissertation

Climate Analysis 30

3rd of June (summer season)The summer season as mentioned before is characterised with high ambient temperature which is above the comfort zone most of the time.

The ambient temperature is above the comfort band for all the hours in the day and suitable strategies need to be incorporated to cool the place. High insulation from the outside climate would be required to maintain comfortable conditions indoors.The Relative humidity is very low during the day time and it mite be a good idea to incorporate a system of evaporative cooling.The direct solar radiation is very high and requires appropriate shading at least on the glazed portions. It would also be wise to reduce the glazing ratio on the facades receiving direct solar radiation. at the same time this direct solar radiation could be suggested for passive solar applications.

fig 28

Page 31: Masters Dissertation

Climate Analysis 31

6Th of August (Monsoon season)

The monsoon season is characterised by the high humidity levels although the temperature levels are much moderate in comparison to the summer season.

The humidity levels are extremely high and require a ventilation strategy to be adopted.The temperature is fairly constant and remains just above the comfort band, which suggests the utilisation of alternative cooling technologies to be adopted.

fig 29

Page 32: Masters Dissertation

Climate Analysis 32

7Th of January (Winter season)

The winter season is characterised by low temperature in the night time but high level of solar radiation is also there because of generally clear skies.

The high solar radiation could be adopted to heat the building during the daytime by using it for solar gainsHigh thermal mass could be utilised to stabilise the temperature

fig 30

Page 33: Masters Dissertation

The chosen site is simulated using the simulation tools and the results analysed to arrive at the possible areas for intervention to make the spaces comfortable to inhabit.

CHAPTER 4anaLySIS

Chapter Overview

Page 34: Masters Dissertation

Analysis of Current Design 34

4.1 Methodology

The relationship between the building physics and building behaviour is the link which determines the building performance. The building behaviour depends on the natural forces which couple the weather and surrounding conditions to react with the building fabric and mass. the natural forces like gravity, heat transfer and light are in turn affected by variations in local climate. To provide an insight into the building performance requires an indepth analysis of these complex forces which are predicted by the modelling and simulation softwares which are described as follows.The simulation softwares that have been used are:

- ecotect for site layout- TaS for one typical unit- Radiance

fig 31: Model in Ecotectfig 32: Model in TAS

Page 35: Masters Dissertation

Analysis of Current Design 35

The whole site plan has also been analysed to see the effect of overshadowing of blocks due to the location. The surroundings at the moment have no built up structures at the moment which could be of concern for overshadowing or wind path blocking in any way.For the purpose of the study one of the block has been chosen and 2 flats earmarked out which have been analysed in detail to fine-tune the suggested strategies for improvement. The two residential units are on the opposite side one facing due north and the other facing south which should contrast with the heating and cooling load requirement within the cluster plan. The same strategy can be replicated for all the different tower blocks but for reasons of duplicity of the same job only one prototype has been studies which can be a ground work for the way the units can be analysed.

fig 33: site plan Tivoli holiday Village

fig 34

Page 36: Masters Dissertation

Analysis of Current Design 3�

The 2 blocks chosen are in the current design oriented in the north and the South side, this will evidently put them in contrasting situation as to how they react to the climate. They can thus be assumed to be function as either very good or the opposite and thus analysing these two houses should give a general idea to be adopted with all the other houses in the project.

4.2 EFFECT OF CLIMATE ON DEsIGN

4.21 ORIENTATION

For passive cooling utilising the sun is paramount. The basic approach is to allow the winter sun in and the summer sun out. On the southern faces it becomes relatively easy by using shading devices to exclude the high angle summer sun and admit the low angle winter sun. The size of the shading though needs to be optimised.

fig: 35

Page 37: Masters Dissertation

Analysis of Current Design 37

4.22 EFFECT OF sOLAR RADIATION

The sunshine hours in Delhi are about 10 per day, barring the monsoon season which has a high cloud cover the rest of the time the sky is generally clear. In the hot season the high solar altitude and the exposed site makes it vulnerable for the SE, SW and the nW facades for high solar gain. Balcony or solar shading devices need to be incorporated and optimised to allow the solar radiation in the winter and keep it out in the summer season.

This gain though in the brief winter period would be desirable and a compromise would need to be established to the amount of heat gain and the undesirable one in summer. In winters the clear sky allows for a high deal of incident solar radiation and it will be desirable to utilise it by orienting the facade to it.

June 3rd

-9am June 3rd

-12 pm June 3rd

- 4pm

Aug 15th-9am Aug 15th -12 pm Aug 15th -4pm

Dec 22nd-9am Dec 22nd-12pm Dec 22-4pm

fig 36

Page 38: Masters Dissertation

Analysis of Current Design 38

fig: 37

Summer Solstice-9am Summer Solstice-12pm Summer Solstice-4pm

Winter Solstice-9am Winter Solstice-12pm Winter Solstice-4pm

Conclusions

The analysis of the solar shading onsite suggests that the blocks can receive sunlight for some pat of the day atleast. The chosen block for the study can be tilted to align it to be in line with the n-S axis and this will ensure that ll houses on the floor can receive the uniform amount of solar radiation.

Page 39: Masters Dissertation

Analysis of Current Design 3�

4.23 DAYLIGHTING ANALYsIs

This section presents the results of the day lighting analysis for a worst case scenario dwelling for this development to evaluate whether it allows for sufficient daylight within the interiors.

RADIANCE

Radiance is a tool which has been developed by the Lawrence Berkley Laboratories. With this it is possible to accurately determine the lighting levels in the building. The day lighting strategy can be fine tuned by the aid of simulation is Radiance. It is possible to invoke radiance through Ecotect. although this reduces the flexibility of the software it does make things simple to use.

South Flat:

June 3rd

-9am June 3rd

-12 pm June 3rd

- 4pm

Aug 15th-9am Aug 15th -12 pm Aug 15th -4pm

South Flat:

Dec 22nd-9am Dec 22nd-12pm Dec 22-4pm

Page 40: Masters Dissertation

Analysis of Current Design 40

North Flat:

June 3rd

-9am June 3rd

-12 pm June 3rd

- 4pm

Aug 15th-9am Aug 15th -12 pm Aug 15th -4pm

North Flat:

Dec 22nd-9am Dec 22nd-12pm Dec 22-4pm

Conclusions

The analysis of the illumination levels on the working plane suggests that the daylight levels in the south flat are very high and will lead to glare. This leaves suffinet scope to reduce the window to floor ratio which at 28% is quite high. This can easily be reduced to less than 20% and anlysed again to have the daylight levels to be in the region of 300-500 Lux. The distribution of light in the north flat is almost unifrom though the areas at the back have less than 100Lux which should be optimised by increasing the number of windows.

fig 38

Page 41: Masters Dissertation

Analysis of Current Design 41

Fig: 3�

4.24 EFFECT OF WINDThe wind will have an important role to maintain the comfort conditions in naturally ventilated mode particularly in the monsoon season when the humidity is very high. The position of the apertures will need to be optimised with the inlets in the high pressure zones SE in Monsoon season. The outlets will be better located in the low pressure zones in the nW. During the peak summer season the wind known as loo has a very high temperature. To provide comfort it would need to be pre-cooled before it enters the building. Evaporative cooling will be effective in that climate as the humidity is very low then.

Page 42: Masters Dissertation

Analysis of Current Design 42

4.25 EFFECT OF TEMPERATUREThe composite climate has the extremities of the weather and in summers it is extremely hot with average temperatures above 35 ˚C and will require some form of cooling system. The aim will be to reduce the cooling load in this case.In winters although the night temperatures are quite cool the day time is still comfortable and by storing the heat during the day in a thermal mass and radiating in the night time it would be possible to create comfortable conditions.

Fig: 40

4.3 TAs Dynamic thermal modelling TAs

Tas is a thermal simulation tool which can predict the internal micro climatic conditions based on the input building design parameters and the occupancy patterns. With this analysis it can be useful to determine the strategies to follow for insulation and glazing areas.

TAS Dynamic Modelling (DTM) has been used to investigate the potential of the building in achieving the required comfort conditions.DTM software tracks the thermal state of the building on an hour by hour basis using real weather data, resulting in a detailed picture of the buildings performance. DTM combines several mechanisms to calculate the building response:• Conduction• Convection• Long wave radiation• Short wave radiation- absorbed, reflected and transmitted• Internal Condition- gains from lights, equipment and occupants along with the plant operating hours and natural infiltration rates• Ventilation and air movements from internal natural convection.

Page 43: Masters Dissertation

Analysis of Current Design 43

The 2 apartments on the opposite sides have been modelled in TaS and each space is converted into a thermal zone and the interactions of the space with each other and the outside is computed in the simu-lation.

fig 40

fig 41

fig 42

Page 44: Masters Dissertation

Analysis of Current Design 44

0

1000

2000

3000

4000

5000

6000

<20 20> 21> 22> 23> 24> 25> 26> 27> 28> 29> 30>

No

.of

ho

urs

External - IND_New.Delhi_IWEC.epw SF-BBedroom 1 NF- BBedroom1

24.79

29.79

75.95

87.13

0.00

10.00

20.00

30.00

40.00

50.00

60.00

70.00

80.00

90.00

100.00

North bedroom South bedroom North bedroom South bedroom

base case- with no internal gains base case- with internal gains

An

nu

al

De

ma

nd

(k

Wh

/m2

)

heating loads cooling loads

4.31 ANNUAL sPACE TERMPERATURE DIsTRIBUTION

The annual temperature distribution profile suggests that the spaces are above the comfort zone for over 5000 hours in an year and the annual cooling load is as high as 87 KWH/m2 in the south bedroom. One of the bedrooms in each flat will also require a minimum amount of heating though which is minimal at less than 10KWh/m2.

fig 43

fig44

Page 45: Masters Dissertation

Analysis of Current Design 45

north Flat- June 3rd- Summer

north Flat- august 15th- Monsoon

The analysis of the temperature profile in the north flat in a typical day suggests that the space is abovethe comfort zone established for all of sum-mer and monsoon. The internal temperature remains above the ambient temperture all through and sug-gests the need for natural ventialtion in monsoon whn the night time temperature fall.

4.32 TEMPERATURE PROFILE N-FLAT

fig 45

fig 46

Page 46: Masters Dissertation

Analysis of Current Design 4�

north Flat- December 22nd - Winter

The annual space temperature distribution shows that the spaces with-out airconditioning will be out of the comfort zone for almost 2/3 of the time in an year. Intervention is required for heating as well as cooling.

Annual Space Temperature Distribution- North flat

1286

177 394929

2481

29152766

2524

4993

5668 56005307

0

1000

2000

3000

4000

5000

6000

7000

8000

Kitchen Living Bedroom1 Bedroom 2

No

.of

ho

urs

Below comfort In comfort Above comfort

The winter temperature profile suggests that the spaces are almost within the comfort zone. By proper orientation the solar radiation alone could be used to bring the temperatures within the comfort zone.

fig 47

fig 48

Page 47: Masters Dissertation

Analysis of Current Design 47

South Flat- June 3rd- Summer

South Flat- august 15th- Monsoon

The analysi of typical days in the south flat tells us that the space is above the cmfort zone and the ambi-ent temperature throughout the day in peak summer.The same is evident in the monsoon season as well and requires airconditioning to create comfort condi-tions.

4.33 ANNUAL TEMPERATURE PROFILE sOUTH FLAT

fig 50

fig 51

Page 48: Masters Dissertation

Analysis of Current Design 48

South Flat- December 22-winter

Annual Space Temperature Distribution- South flat

701

0 0 6

2829

2856 2815 2932

5230

5904 5945 5822

0

1000

2000

3000

4000

5000

6000

7000

8000

Kitchen Living Bedroom1 Bedroom 2

No

.of

ho

urs

Below comfort In comfort Above comfort

The above figures show that the houses are within the comfort zone without airconditioning for a very short duration of hours. They require no heating except for the kitchen but are above the comfort zone for more than half the time.

The typical winter day has the spaces in the south flat heated up to the upper range of the comfort zone and the high thermal mass of the brick wall en-sures the paces remain comfortable throughout.

fig 52

fig 53

Page 49: Masters Dissertation

Based on the Climatic analysis and the base case simulation analysis the recommendations are made for passivc design suited to the climate and site

CHAPTER 5PaSSIVE DESIGn RECOMEnDaTIOnS

Chapter Overview

Page 50: Masters Dissertation

Recommendations 50

5.1 Climatic design for Composite Climates

The climate of Delhi is a composite climate and thus requires consideration of strategies for both heating the space and cooling the space depending on the season. With just 2 brief periods in an year in October and March when the temperature is within the comfort band for most part, the rest of the year will require some strategies to counter the effect the adversities of the weather.Based on the climatic analysis and the analysis of the simulation results the strategies which could be adopted for making passive climatic design interventions.

5.2 THE BUILDING ENVELOPE

The role of the building envelope is to act as a moderator of the climate, to provide the balance between the heat gain and the heat losses required to maintain a comfortable interior. This calls for using effective shading, high performance glazing systems, good insulation access to thermal mass and the use of natural ventilation in the respective season where feasible.

In the context of Delhi the facades are most vulnerable to solar radiation as the 14 storeyed tower blocks are exposed out without any shading from the surrounding. The only shading is provided by the overshadowing of the different blocks. Excessive glazing should therefore be avoided on the facades. Effective shading though can easily be done by optimising the depth of the balconies and putting vertical shading devices to counter the effect of low morning and

fig 54

Page 51: Masters Dissertation

Recommendations 51

evening sun in the west facade without loss of light.

The environmental performance of a building depends on a number of different factors. The environmental performance of the facade system on a building is one of the influential characteristics determining overall building performance.

The protective shell of the building is the facade and the better this works the less work is required internally from the mechanical systems to maintain good occupant comfort levels. This has a direct influence on the energy consumption of the building.

The ideal insulation strategy to follow for composite climates needs to be optimised again depending on the desing and the site conditions. This needs to counter the effect of the variations in the temperatures through the day and the year and the amount of solar radiation falling on the facades.

Choosing the glazing type will have an impact on both the illuminance levels in the building and the solar heat gains. By choosing a glazing with an emissivity of 0.1 the heat gains can be reduced when the sun is high and the incident solar radiation to the surface glazing causes increase in indoor temperature and cooling load.

For the south east and south west vertical shading devices are recommended in order to reduce the heat gains when the sun is low.

For morning performance optimised east facing glazing with both horizontal and vertical shading devices is a preferred approach.For afternoon performance, a double glazed unit should be installed comprising of solar control glass for the outer pane and low emissivity(Low-e) glass for the inner pane. The solar control glass prevents unwanted solar radiation entering the summer months and the low emissivity glass reduces the heat loss from inside during the winter months. The low- e glass also blocks heat radiated from the outer pane of glass when it heats up.

Page 52: Masters Dissertation

Recommendations 52

5.3 IMPACT OF CHANGE IN THERMAL MAss AND LOCATION OF INsULATION LAYERs

To provide an acceptable internal environment in hot climates, one of the traditional methods that were used was heavy weight construction (low u-value construction). The thick walls of stone or brick gave a huge time lag and the heat transfer co-efficients thus offer good U-values. They are able to absorb a large amount of heat without a marked increase in the temperature of the interior space. However they take a long time to heat up or cool down and as a result the advantage of solar radiation falling directly on them cannot be taken instantaneouly. On the other hand the light weight consturction offers the flexibility to heat up the space faster during the day which is very useful in the cold winter months.

However, during night-time when the out-side air temperature is low heat loss by a lightweight structure is higher than a heavyweight structure, as proven by Victor Olgyay of Princeton University. He made a graphical comparison of a lightweight structure having a 2-hour time lag with a �-inch brick structure with a time lag of 10 hours. Each structure had the same u-value of 0.2�8 btu/ft2. However, in the lightweight structure insulation was placed inside whereas in case of heavy weight structure insulation was placed outside the building envelope.

fig 55

Page 53: Masters Dissertation

Recommendations 53

Interpreting the graph it comes across that though the total daily heat transmission is same for both in amplitude, the period of transmission is different. The heavyweight is better off during daytime whereas the lightweight performs better during night-time. It can thus be inferred that for the rooms to be occupied during day-time, heavyweight construction would be required to reduce heat gain and rise in internal temperatures; whereas night-time active areas construction should be lightweight so that they may cool off quickly at night to prevent need of air-conditioning.

5.31 EXTERNAL INsULATION AND INTERNAL THERMAL MAss

The grouping of the external insulation and internal mass-produces both a high thermal time constant and a high diurnal heat capacity. It helps in stabilising the fluctuating internal temperature when the windows are kept closed for the whole day and night. In Delhi’s climate the summershave a diurnal temperature range which is quite high at

fig 56: Comparing thermal behaviour of heavy and light construction:source: Building Environment , Balwant Singh Sainai

Page 54: Masters Dissertation

Recommendations 54

12-15 deg.C. When the building is ventilated during the night-time and kept closed during the day-time it can effectively cool down the mass and absorb, the solar energy transmitted through windows along with heat generated within interior spaces of the building during day-time, with relatively small rise of the indoor temperature.

5.32 EXTERNAL THERMAL MAss AND INTERNAL INsULATION

Such construction has comparatively low thermal time constant and negligible diurnal heat capacity as the internal insulation separates the mass from the interior space. Thus, it will act as a lightweight building and will follow the external air temperature when ventilated. The reduction in day-time temperature is mainly determined by the thickness of the construction if the windows are kept closed. This combination is of great advantage for space to be used during nighttimes and during the monsoon season as the heavy mass provides protection from the strong winds and the internal insulation can enhance the cooling rate at night.

5.33 PARAMETRIC sTUDY TO DETERMINE WALL TYPE AND CONsTRUCTION

To study the affect of thermal mass and insulation in the climate of Delhi a parametric study was done by testing the effect of different combination of wall material and insulation on the same room in esp-r. The study was conducted by by creating a room 5M X 5M x 5 M with 20% window to floor ratio. Keeping all conditions identical 6 different combinations of wall types as explained below were tested.

a) Brick Wall with insulation in between Conductivity Density Specific Heat Thickness1 Brick 0.�� 2000 50 1002 Insulation .10 100 750 1003 Brick 0.�� 2000 850 100 U-Value 1.15

a) Brick Wall with no additional insulation Conductivity Density Specific Heat Thickness1 Brick 0.�� 2000 850 200 U-Value 2.1

Page 55: Masters Dissertation

Recommendations 55

b) Brick wall with insulation on the outside Conductivity Density Specific Heat Thickness2 Insulation .10 100 750 1003 Brick 0.�� 2000 850 200 U-Value 1.04

c) Brick wall with insulation on the inside Conductivity Density Specific Heat Thickness1 Brick 0.�� 2000 850 1002 Insulation .10 100 750 100 U-Value 1.04

d) Sandwich of Aerated Autoclaved Concrete (AAC) Block wall with insulation in between. Conductivity Density Specific Heat Thickness1 aaC block 0.45 850 �50 1002 Insulation .10 100 750 1003 aaC block 0.45 850 �50 100U-Value 0.85

e) aaC Block wall with insulation on the outside Conductivity Density Specific Heat Thickness1 Insulation .10 100 750 1002 aaC block 0.45 850 �50 100U-Value 1.08

f) aaC Block wall with insulation on the inside Conductivity Density Specific Heat Thickness1 aaC block 0.45 850 �50 1002 Insulation .10 100 750 100U-Value 1.08

The room was simulated for all the 4 typical days selected for study and the results are summarised:

sUMMER sEAsON – (APRIL – JUNE)

On a typical day the resultant temperatures are higher than the comfort zone. Whereas during the day time the light weight aaC block wall with insulation on the outside is showing the best possible reduction in temperature. The heavy thermal mass of brick wall with insulation on outside or a sandwich layer stabilises the temperature through the day and it remains more or less constant.

Page 56: Masters Dissertation

Recommendations 5�

For an air-conditioned building this may be the best option but for a naturally ventilated building the night time cooling in this climate demands the building to cool down for the night time. The aaC blocks with insulation on the inside cools down the fastest and is able to loose heat almost instantaneously.

MONsOON sEAsON – (JULY – sEPTEMBER)

During the monsoon the diurnal range of temperature is less and the direct solar radiation is also very less. Because of this the direct gain as a result is not too much and almost all cases follow a similar profile. Here again the low thermal mass of aaC blocks and external insulation helped keep the temperatures lowest. The high thermal mass without the insulation (case a) has a fluctuation in the temperature whereas the thermal with insulation on the outside ot a sandwich has a very stable profile. The AAC blocks with insulation on the inside shows the high fluctuation in the daily temperature and is able to cool down very rapidly but remains way above the comfort zone in the day time.

fig 57: parametric studygenerated using esp-r

Page 57: Masters Dissertation

Recommendations 57

WINTER sEAsON (Nov-Feb)

The cold climate has a utility for thermal mass in stabilising the temperature. This is infact helped due to the high solar radiation which gets trapped as heat and keeps the night time temperature stable.

The aaC blocks with external insulation which perform well for summer conditions are not suitable in this climate as the temperature remains way below the comfort zone.

fig 58: parametric study august 15generated using esp-r

fig 59: parametric study Dec 22generated using esp-r

Page 58: Masters Dissertation

Recommendations 58

5.4 sTRATEGIEs FOR VARIOUs sEAsONs

5.41 sUMMER sEAsONThe summer season will require strategies to

1) Reduce heat gains from the building fabricThis can be done by:

Orienting the building to reduce the footprint of the solar radiation received. By reducing the exposed area to the direct sun the heat gains should get reduced which will reduce the cooling loadImprove the insulation level of the building fabric. Using insulation on the external face of the building which can reduce the external influence of hot weather can vastly improve the cooling load requirements. Insulating materials can range from simple air gaps in the walls to advanced materials specifically tailored for the effect.Optimise the glazing ratio. The Glazing is the most vulnerable area for heat gains in summers if it is in an exposed area which receives direct sunlight. Optimising the glazing ratio will needs to be balanced to achieve the desired illumination levels in the spaces and the heat gains it will cause. Use insulated glazing system like double glazing which has a marked improvement on the insulating property as compared to the single glazing. This will reduce the heat gains from the surroundings.

2) Reduce Internal gains

Internal sources contribute the heat gains in a space and the strategy for summer needs to be to reduce them to avoid this heat gainThe heat gains from the lighting fixtures can be significant. Using firstly energy efficient lights can reduce this gain. Secondly the control system needs to be defined which can switch on and off the lights according to the usage pattern.

3) Reduce temperatures by apppropriate Ventilation strategies

Ventilation requirements are crucial for health reasons and they need to be optimised in the building heat flow dynamics to reduce the heat indoors.The summer temperatures although quite high, have a low humidity level and can benefit from evaporative cooling.The rate of air changes need to kept at a minimum if the outside temperature is way above the comfort level. The minimum standard to be followed can be the ones from aSHRaE standards for residential buildings.

Page 59: Masters Dissertation

Recommendations 5�

5.42 WINTER sEAsON

The average temperature in the composite climate of Delhi in winters is much below the comfort band. The strategy to be adopted is to keep the interior temperature above the ambient ones.

1) Reduce heat Losses from the Building Fabric

The temperature variation in the interior and the exterior suggests use of insulation to reduce the heat loss from the interiors. This is the same as for the summer seasonOrient the building to gain more direct solar radiation. Since this contrasts with the strategy for summers an optimisation needs to be made on this respect. Optimise the Glazing ratio of the building fabric: The heat gains that can be made from the glazed areas need to be optimised to check the vulnerability of the glazed surfaces to aid in heat loss due to the low U value.Utilise insulated glazing which can reduce the heat loss from the interior

2) VENTILATION

The ventilation rate has to be optimised to fulfil the requirements of comfort and health while at the same time to reduce the outflow of heat from the interiors.

Page 60: Masters Dissertation

Recommendations �0

5.43 MONsOON sEAsON

The High humidity and temperature requires a different strategy from the hot summer season for the monsoons.

1) Reduce heat gains from the building fabric

The temperature generally hovers around the low 30’s and it is essential to provide a insulating fabric from this high temperature.The temperature in the night time though does go down and is in the high 20’s which could essentially be used for free cooling in the night time.The incident solar radiation is quite low and as such the effect of shading would not be apparent,

2) Ventilation strategy

The high humidity makes wind flow very essential, but it renders evaporative cooling as useless in this weathernight time cooling could be utilised as the wind speeds are generally quite high.

5.44 MILD sEAsON

With the weather conditions favouring human comfort it would be an advisable strategy to bring the outdoor climate indoors as much as possible.The heat gains from the interiors and the atmosphere could be channelled to the outside to create comforting conditions.

Page 61: Masters Dissertation

The recommendations put forward in the previous chapter have been incoporated in the base case design and simulated again to quantify their effectiveness. The chapter analyses the two scenarios and discusses the impact of passive strategies in reducing the energy demand and creating comfort conditions.

CHAPTER 6anaLySIS OF RECOMMEnDaTIOnS

Chapter Overview

Page 62: Masters Dissertation

Analysis of Recommendations �2

6.1 Comparison of Base case Annual energy demand with proposed recommendations

List of assumptions of both the baseline and the current design buildings made for the thermal modeling simulation program

Base case building Proposed

Recommendation

1.0 Building Design

1.1 Window to gross wall ratio

28% 20%

1.2 Facade treatment Bedroom, living room windows shaded by a horizontal overhang on all facades on all orientations

Fixed shading devices, same as the current design and additionally vertical shading on east and west

windows

2.0 Construction properties

2.1 U-Values of Transparent Constructions-Glazing

Single glazing 5.71

Double glazing with 12mm air gap 1.8

2.2 U-Values of Opaque constructions

2.21 External Walls (bedrooms) 2.4 1.1

2.22 External Walls (Living) 2.4 0.8

2.32 Internal Walls 2.53 2.53

2.33 Slab 2.65 2.65

2.34 Opaque Doors 2.6 2.6

2.35 Door/ Window Frames 5.88 5.88

3.0 Internal Conditions – Internal Gains- Living Rooms and Bedrooms

a. Infiltration 0.5 ach 0.5 ach

b. Ventilation 0 ach 0 ach

c. Lighting Gain 12 W/m2 6 W/m

2

d. Occupancy Sensible 2.5 W/m2 2.5 W/m

2

e. Occupancy Latent 1.3 W/m2

1.3 W/m2

f. Equipment Sensible 7 W/m2

4.5 W/m2

g. Equipment Latent - -

h. Thermostat Temperature Settings

Air conditioned (25°C) Air conditioned (25°C)

4.0 Occupancy Schedule

4.1 Day-time occupancy 8am-7pm 8am-7pm

4.2 Evening occupancy 6pm-9am 6pm-9am

4.3 Lighting Schedule 6pm-11pm 6pm-11pm

5.0 Apertures for Natural Ventilation

5.1 Apertures (none) On all windows

5.2 Aperture Function (none)

Opens when the zone’s dry bulb temperature is between

20 °C and 29 °C

Page 63: Masters Dissertation

Analysis of Recommendations �3

75.95

69.23

45.74

42.34

39.02

26.13

0.00

10.00

20.00

30.00

40.00

50.00

60.00

70.00

80.00

90.00

100.00

base case w/f ratio optimised Mixed-mode ventilation U-values

(opaque)optimised

U-values (glazing)

double glazing

internal gains-

optimised as per NBC

standads

Annual heating and cooling loads- Bedroom 1- North flat

An

nu

al D

em

an

d (

kW

h/m

2)

6.11 Comparing the temperature and cooling loads against base case in North Flat

Chart1

Page 1

Comparison of Temperatures and Cooling Loads in the North flat on June 3rd (Summer)

15.00

20.00

25.00

30.00

35.00

40.00

45.00

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Dry

Bu

lb T

em

pera

ture

(d

eg

.C)

0.00

100.00

200.00

300.00

400.00

500.00

600.00

Co

oli

ng

Lo

ad

(W

)

External Temperature (deg.C) Base Case-Bedroom1 Dry Bulb (deg.C)

Proposed Design-Bedroom1 Dry Bulb (deg.C) Base Case-Bedroom1 Cooling Load (W)

Proposed Design-Bedroom1 Cooling Load (W)

The above figures show how the energy demand to keep the space at the comfort conditions decreases with the application of each recommendation. With just the application of mixed mode of ventilation and window to floor ratio optimised the the energy demand per annum when the demand falls from base case scenario of 75KHh/M2 to 45KWH/m2. after all the recommendations in place the energy demand can be as low as 25KWH/m2 per day.The cooling load on a typical summer day reduces from a peak of 500W to 300W only.

fig 60:

fig 61

Page 64: Masters Dissertation

Analysis of Recommendations �4

87.13

77.57

46.73

42.03

37.43

25.13

0.00

10.00

20.00

30.00

40.00

50.00

60.00

70.00

80.00

90.00

100.00

base case w/f ratio optimised Mixed-mode ventilation U-values

(opaque)optimised

U-values (glazing)

double glazing

internal gains-

optimised as per NBC

standads

Annual heating and cooling loads- Bedroom 1- South flat

An

nu

al D

em

an

d (

kW

h/m

2)

Chart1 (2)

Page 1

Comparison of Temperatures and Cooling Loads in the South flat on June 3rd (Summer)

15.00

20.00

25.00

30.00

35.00

40.00

45.00

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Dry

Bu

lb T

em

pera

ture

(d

eg

.C)

0.00

100.00

200.00

300.00

400.00

500.00

600.00

Co

oli

ng

Lo

ad

(W

)

External Temperature (deg.C) Base Case-Bedroom1 Dry Bulb (deg.C)

Proposed Design-Bedroom1 Dry Bulb (deg.C) Base Case-Bedroom1 Cooling Load (W)

Proposed Design-Bedroom1 Cooling Load (W)

In the south flat too the energy demand falls from a peak of 87KWH/m2 on a typical summer day to just 25KWH/m2 after the application of all recommendations. Infact due to the change in orientation of the flat it has a zero cooling load can drop to zero in the early moring hours.

6.12 Comparing the temperature and cooling loads against base case in south Flat

fig 62

fig 63

Page 65: Masters Dissertation

Analysis of Recommendations �5

6.13 Effect of mixed mode ventialtion on Cooling load

The base case has airconditioned interiors all through the time, yet it is interpreted from the above figure that the cooling load can be shut off in the monsoon with the application of night time cooling by opening the windows and increasing natural flow of air.

fig 64

Page 66: Masters Dissertation

Analysis of Recommendations ��

0

500

1000

1500

2000

2500

3000

3500

4000

4500

<20 20> 21> 22> 23> 24> 25> 26> 27> 28> 29> 30>

No

.of

ho

urs

External - IND_New.Delhi_IWEC.epw NF- BBedroom1 SF-BBedroom 1

27662815

3521

3738

0

500

1000

1500

2000

2500

3000

3500

4000

North bedrooms South bedrooms

No

.of

ho

urs

Base case Proposed design

6.12 Annual space Temperature Disribution.

With the application of the recommendations for passive design ideas in comparison to the base case scenario the spaces can be made to be in comfort conditions for a longer duration of time. The north bedroom can fuction without any airconditioning for more than 3500 hours in an year as compared to 2750 in the base case. The south facing flats can have he same increased by 1000 hours annually.

fig 65

fig66

Page 67: Masters Dissertation

Analysis of Recommendations �7

75.9

5

87.1

3

69.2

3

77.5

7

45.7

446.7

3

42.3

442.0

339.0

237.4

3

26.1

325.1

3

0.0

0

10.0

0

20.0

0

30.0

0

40.0

0

50.0

0

60.0

0

70.0

0

80.0

0

90.0

0

100.0

0

Nort

h

bedro

om

South

bedro

om

Nort

h

bedro

om

South

bedro

om

Nort

h

bedro

om

South

bedro

om

Nort

h

bedro

om

South

bedro

om

Nort

h

bedro

om

South

bedro

om

Nort

h

bedro

om

South

bedro

om

base c

ase-

with

inte

rnal gain

s

w/f

ratio o

ptim

ised

Mix

ed-m

ode v

entila

tion

U-v

alu

es

(opaque)o

ptim

ised

U-v

alu

es (

gla

zin

g)

double

gla

zin

g

inte

rnal gain

s-

reduced

Com

parison o

f coolin

g loads b

etw

een n

ort

h a

nd s

outh

fla

ts

Annual Demand (kWh/m2)

fig 67

Page 68: Masters Dissertation

Analysis of Recommendations �8

The graph on the previous page shows how the annual cooling load decreases with the application of each recommendation in the spaces. The fact that is elaborated is that the cooling load can be decreased the maximum is by the use of outside weather conditions to cool the interiors. By using a mixed mode of ventialtion the energy demand falls by a third and is the biggest contributor in thepasive design strategy. Each strategy has a marked improvement on the energy consumption load and by the application of these simple techniques the use of energy can be reduced to a third of what the projected energy consuption figures are.

Page 69: Masters Dissertation

Analysis of Recommendations ��

CONCLUsIONs

The quest to make the modern buildings comfrotable has had a drawback of heavy reliance on energy to keep them in that state. However senitivity in design which takes into account the environmental conditions of the site can result to lower this energy consumption. Simple passive design strategies can be effective to make the reliance on mechanical means lower. The thesis proves with simple methods and adherence to the tightening norms for building construction can lower the dependence to achieve the comfrot standard.

The passive design strategeis are vast and in this thesis the basic ones were explored to see how the building can be comfortable and not rely on airconditioning through the year quite easily. However there were many factors which have been assumed and actual site conditions can vary and change the dynacmics of the projected energy consumption figures. the occupancy pattern and the usage of systems has been assumed to be in one strict manner and it will invaribly differ depending ont eh occupants.

Basic attempts at harmonising the building to the enviroment does result in lower energy consumtpion and further research may be done to make even the mass produced housing estates like these ones to be totally not dependent on energy needs at all. The norms at the moment in develpoing countries are still in infacny for these and the aspirations of people have driven the need for fully climatically conrrtolled atmospheres to become common. But it is questionable in the approach as the higher energy de-mand and the reliance on it has pushed the use of such houses in the fore-front. With increasing awareness about global warming and environment consciouness the approach towards environmentally suitable buildings is a step in the right direction.

Page 70: Masters Dissertation

BIBLIOGRAPHY

1) Sofaee, F, 2004, ″ Sustainability of Climatic-Sensitive El-ements in the Iranian Traditional architecture of Hot – arid Regions″, ICHH 2004, India.2) Szokolay, S.V, (1997). Thermal Insulation. PLEA Internatinal/ University of Queensland, Brisbane. 3) Cook, J., (1989). Passive Cooling. The MIT Press Cambridge, London.4) Givoni, B., (1998). Climate Considerations in Building and Urban Design. Van nostrand Reinhold, new york.6) Krishnan, A., (2001). Climate Responsive Architecture. Tata McGraw Hill, new Delhi. 7) Yannas, S., (2000). Designing for Summer Comfort. European Commission, Energy altener Programme.8) Saini, B.S., (1973). Building Environment.9) Auliciems, A.& S. Szokolay., (1997). Thermal Comfort). PLEA Note3, PLEa International/ University of Queensland.10) Energy Conservation building Code 200�, Bureau of Energy Efficiency, (BEE)11) National Building Code of India (NBC)-2005, www. bis.org.in

Softwares used – Eco-tect TaS esp-r

Page 71: Masters Dissertation

Analysis of Recommendations 71