D- Masterpact Electrical diagrams Presentation 3 Functions and characteristics A-1 Installation recommendations B-1 Dimensions and connection C-1 Masterpact NT06 to NT16 0 Fixed and drawout devices D- Masterpact NW08 to NW63 0 Fixed and drawout devices D- Masterpact NT and NW 0 Communications of the V DC External power supply AD module D-6 Communications option 24 V DC external power supply D-8 Earth-fault and earth-leakage protection Neutral protection Zone selective interlocking D-0 Additional characteristics E-1 Catalogue numbers and order form F-1 施耐德電機授權經銷商 普得企業股份有限公司 總公司:台北市內湖區行愛路68號6樓 話:(02)8791-8588 中辦處:(04)2296-9388 真:(02)8791-9588 高辦處:(07)227-2133 E-mail:[email protected] 址:www.toyotech.com.tw

Masterpact Electrical diagrams - TOYO Tech · D- Masterpact Electrical diagrams Presentation 3 Functions and characteristics A-1 Installation recommendations B-1 Dimensions and connection

  • Upload
    ngodieu

  • View
    229

  • Download
    1

Embed Size (px)

Citation preview

  • D-

    Masterpact Electricaldiagrams

    Presentation 3Functionsandcharacteristics A-1Installationrecommendations B-1Dimensionsandconnection C-1

    MasterpactNT06toNT16 0Fixedanddrawoutdevices D-

    MasterpactNW08toNW63 0Fixedanddrawoutdevices D-

    MasterpactNTandNW 0Communications of the V DC ExternalpowersupplyADmodule D-6Communicationsoption24VDCexternalpowersupply D-8Earth-fault and earth-leakage protectionNeutral protectionZone selective interlocking D-0

    Additionalcharacteristics E-1Cataloguenumbersandorderform F-1

    Livre_EN.indb 1 17/04/2008 11:41:03

    :686 :(02)8791-8588 :(04)2296-9388 :(02)8791-9588 :(07)227-2133E-mail:[email protected] :www.toyotech.com.tw

  • D-

    Electricaldiagrams

    Thediagramisshownwithcircuitsde-energised,alldevicesopen,connectedandchargedandrelaysinnormalposition.

    Power Controlunit Remoteoperation

    DB

    0

    0

    Controlunit RemoteoperationTerminalblockmarking

    Com UC1 UC2 UC3 UC4 / M2C / M6C SDE2 / Res SDE1 MN / MX2 MX1 XF PF MCH

    E5 E6 Z5 M M M F+ V / 8 / Q 8 / K 8 D / C C A 5 B

    E E Z Z T T VN V / 7 / Q 8 8 C A 5 B

    E E Z Z T T F V / 7 / Q 8 / K 8 D / C C A 5 B

    A P H Controlunit Remoteoperationb b b Com:E-E6 communication SDE2:fault-trip indication contact

    orRes: remote reset

    SDE1:fault-trip indication contact (supplied as standard)

    MN: undervoltage releaseorMX2:shunt release

    MX1:shunt release (standard or communicating)

    XF: closing release (standard or communicating)

    PF: ready-to-close contact

    MCH:electric motor

    Note: whencommunicatingMXorXFreleasesareused,thethirdwire(C3,A3)mustbeconnectedevenifthecommunicationmoduleisnotinstalled.

    b b b UC1:Z-Z5 zone selective interlockingZ = ZSI OUT SOURCEZ = ZSI OUT ; Z = ZSI IN SOURCEZ = ZSI IN ST (short time)Z5 = ZSI IN GF (earth fault)

    b b b M = Vigi module input (Micrologic 7)b b b UC2:T1,T2,T3,T4=externalneutralb b b M, M = Vigi module input (Micrologic 7)

    b b b UC3:F2+,F1external24VDCpowersupplyb b VNexternalvoltageconnector(mustbe

    connected to the neutral with a P circuit breaker)

    b b UC4:ExternalVoltageConnector(PTEoption)or

    b b M2C:2programmablecontacts(externalrelay) ext.24VDCpowersupplyrequired.or

    b b M6C:6 programmable contacts tobeconnectedtotheexternalmoduleM6C) ext.24VDCpowersupplyrequired.

    A :digitalammeter.P :A+powermeter+additionalprotection.H :P+harmonics.

    MasterpactNT06toNT16 0Fixedanddrawoutdevices

    Livre_EN.indb 2 17/04/2008 11:41:05

  • D-

    Electricaldiagrams

    Indicationcontacts Chassiscontacts

    DB

    0

    06

    DB

    0

    07

    Indicationcontacts ChassiscontactsOF4 OF3 OF2 OF1 CD2 CD1 CE3 CE2 CE1 CT1

    8 8 9

    8 8 9

    8 8 9

    Indicationcontacts ChassiscontactsOF4/OF3/OF2/OF1:ON/OFF indication contacts.

    (*) Spring charging motor 440/480 V AC(380Vmotor+additionalresistor).

    CD2:CD1

    disconnectedposition contacts

    CE3:CE2CE1

    connectedposition contacts

    CT1: testposition contacts

    DB

    70

    Key:

    drawoutdeviceonly.

    XXX SDE1,OF1,OF2,OF3,OF4suppliedasstandard.

    interconnectedconnections (onlyonewireperconnectionpoint).

    MasterpactNT06toNT16 0Fixedanddrawoutdevices

    Livre_EN.indb 3 17/04/2008 11:41:07

  • D-

    Electricaldiagrams

    Thediagramisshownwithcircuitsde-energised,alldevicesopen,connectedandchargedandrelaysinnormalposition.

    Power Controlunit Remoteoperation

    DB

    0

    0

    Controlunit RemoteoperationTerminalblockmarking

    Com UC1 UC2 UC3 UC4 M2C / M6C SDE2 / Res SDE1 MN / MX2 MX1 XF PF MCH

    E5 E6 Z5 M M M F+ V 8 / Q 8 / K 8 D / C C A 5 B

    E E Z Z T T VN V 7 / Q 8 8 C A 5 B

    E E Z Z T T F V 7 / Q 8 / K 8 D / C C A 5 B

    A P H Controlunit Remoteoperationb b b Com:E-E6 communication SDE2:fault-trip indication contact

    orRes: remote reset

    SDE1:fault-trip indication contact (supplied as standard)

    MN: undervoltage releaseorMX2:shunt release

    MX1:shunt release (standard or communicating)

    XF: closing release (standard or communicating)

    PF: ready-to-close contact

    MCH:electric motor

    Note: whencommunicatingMXorXFreleasesareused,thethirdwire(C3,A3)mustbeconnectedevenifthecommunicationmoduleisnotinstalled.

    b b b UC1:Z-Z5 zone selective interlockingZ = ZSI OUT SOURCEZ = ZSI OUT ; Z = ZSI IN SOURCEZ = ZSI IN ST (short time)Z5 = ZSI IN GF (earth fault)

    b b b M = Vigi module input (Micrologic 7)b b b UC2:T1,T2,T3,T4=externalneutralb b b M, M = Vigi module input (Micrologic 7)

    b b b UC3:F2+,F1external24VDCpowersupplyb b VNexternalvoltage

    connector (must be connected to the neutral

    b b UC4:ExternalVoltageConnector(PTEoption)

    b b M2C: programmable contacts (internal relay)ext.24VDCpowersupplyrequired

    orb b M6C: 6 programmable contacts

    (tobeconnectedtotheexternalmoduleM6C)ext.24VDCpowersupplyrequired

    A :digitalammeter.P :A+powermeter+additionalprotection.H :P+harmonics.

    MasterpactNW08toNW63 0Fixedanddrawoutdevices

    Livre_EN.indb 4 17/04/2008 11:41:09

  • D-5

    Electricaldiagrams

    Indicationcontacts Chassiscontacts

    DB

    0

    09

    Indicationcontacts ChassiscontactsOF4 OF3 OF2 OF1 OF24 OF23 OF22 OF21 OF14 OF13 OF12 OF11 CD3 CD2 CD1 CE3 CE2 CE1 CT3 CT2 CT1

    8 8 8 9 9 9

    8 8 8 9 9 9

    8 8 8 9 9 9or or or or or or or or or orEF24 EF23 EF22 EF21 EF14 EF13 EF12 EF11 CE6 CE5 CE4 CE9 CE8 CE7

    8 8 8 8 8 8 8 8 6 5 9 8 7

    6 6 6 6 6 6 6 6 6 5 9 8 7

    5 5 5 5 5 5 5 5 6 5 9 8 7

    Indicationcontacts ChassiscontactsOF4:OF3OF2OF1

    ON/OFF indication contacts OF24orEF24OF23orEF23OF22orEF22OF21orEF21OF14orEF14OF13orEF13OF12orEF12OF11orEF11

    Combined connected-deconnected indication contacts

    CD3CD2CD1

    disconnected position contacts

    CE3CE2CE1

    connected position contacts

    CT3CT2CT1

    test position contacts

    or orCE6CE5CE4

    connected position contacts

    CE9CE8CE7

    connected position contacts

    orCD6CD5CD4

    disconnected position contacts

    Key:

    drawoutdeviceonly.

    XXX SDE1,OF1,OF2,OF3,OF4suppliedasstandard.

    interconnectedconnections (onlyonewireperconnectionpoint).

    MasterpactNW08toNW63 0Fixedanddrawoutdevices