434
MASTER SPECIFICATIONS Division 26 - ELECTRICAL Release 2.0 April 2012 Released by: Cleveland Clinic Facilities and Construction 9500 Euclid Ave. Cleveland OH 44195 All information within this Document is considered CONFIDENTIAL and PROPRIETARY. By receipt and use of this Document, the recipient agrees not to divulge any of the information herein and attached hereto to persons other than those within the recipients’ organization that have specific need to know for the purposes of reviewing and referencing this information. Recipient also agrees not to use this information in any manner detrimental to the interests of Cleveland Clinic.

MASTER SPECIFICATIONS Division 26 - ELECTRICALportals.clevelandclinic.org/Portals/57/2012_Elec Specs.pdf · MASTER SPECIFICATIONS . Division 26 - ELECTRICAL . Release 2.0 . April

Embed Size (px)

Citation preview

  • MASTER SPECIFICATIONS

    Division 26 - ELECTRICAL

    Release 2.0 April 2012 Released by: Cleveland Clinic Facilities and Construction 9500 Euclid Ave. Cleveland OH 44195

    All information within this Document is considered CONFIDENTIAL and PROPRIETARY. By receipt and use of this Document, the recipient agrees not to divulge any of the information herein and attached hereto to persons other than those within the recipients organization that have specific need to know for the purposes of reviewing and referencing this information. Recipient also agrees not to use this information in any manner detrimental to the interests of Cleveland Clinic.

  • Cleveland Clinic Master Specifications

    Copyright 2012 By the Cleveland Clinic

    These Specifications, or parts thereof, may not be reproduced in any form without the permission of the Cleveland Clinic.

  • Cleveland Clinic Master Specifications: Division 26 - Electrical

    This document contains the Master Specifications for the design and construction of new and renovated facilities for all domestic Cleveland Clinic locations. It is be used by A/E firms in the preparation of Construction Documents for all facility types. The general purpose of each Specification is to provide minimum criteria for construction materials at Cleveland Clinic facilities regarding Code and FM Global compliance, warranty, approved products, execution and uniformity. The Specifications are used to prepare specific project Contract Specifications. They are intended to be used to address system design aspects of equipment that Cleveland Clinic desires to standardize among facilities, and identify prohibited materials and construction practices. Use of these Specifications will help A/Es meet the Cleveland Clinics primary goal of providing a safe, reliable, and energy efficient installations and ultimately successful patient outcomes. The use of these Specifications is mandatory for all design or maintenance projects. Deviations are discouraged. If project conditions arise which require a deviation, it should be thoroughly documented by the user and submitted to the Cleveland Clinic for review and approval using the Design Standards Revision Request document. Additionally, all Cleveland Clinic staff, architects, engineers, and contractors are encouraged to participate in the ongoing development of these guidelines by communicating any suggestions by use of the Revision Request document. USER NOTE: throughout the specifications, bracketed, bold text indicates optional requirements which may be deleted if project conditions permit.

    *****

  • MASTER SPECIFICATIONS: DIVISION 26 ELECTRICAL

    SECTION # TITLE ____________________________ 260500 COMMON WORK RESULTS FOR ELECTRICAL 260513 MEDIUM VOLTAGE CABLES 260519 LOW VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260523 CONTROL VOLTAGE ELECTRICAL CABLES 260526 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260529 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260533 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260543 UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS 260544 SLEEVES AND SLEEVE SEALS 260548 VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS 260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS 260573 OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY 260573.1 ELECTRICAL STUDIES 260913 ELECTRICAL POWER MONITORING AND CONTROL 260923 LIGHTING CONTROL DEVICES 260933 CENTRAL DIMMING CONTROLS 260936 MODULAR DIMMING CONTROLS 260943 NETWORK LIGHTING CONTROLS 261116 SECONDARY UNIT SUBSTATIONS 261200 MEDIUM VOLTAGE TRANSFORMERS 261300 MEDIUM VOLTAGE SWITCHGEAR 262011 ISOLATED POWER CENTER 262200 LOW VOLTAGE TRANSFORMERS 262300 LOW VOLTAGE SWITCHGEAR 262313 PARALLELING LOW VOLTAGE SWITCHGEAR 262413 SWITCHBOARDS 262416 PANELBOARDS 262417 ROLL UP GENERATOR TERMINATION CABINET 262419 MOTOR CONTROL CENTERS 262500 ENCLOSED BUS ASSEMBLIES 262600 POWER DISTRIBUTION UNITS 262713 ELECTRICITY METERING 262726 WIRING DEVICES 262813 FUSES 262816 ENCLOSED SWITCHES AND CIRCUIT BREAKERS 262913 ENCLOSED CONTROLLERS 263213 ENGINE GENERATORS 263323 CENTRAL BATTERY SYSTEMS 263353 UNINTERRUPTIBLE POWER SUPPLY 263533 POWER FACTOR CORRECTION 263600 TRANSFER SWITCHES 264113 LIGHTNING PROTECTION 264313 SURGE PROTECTIVE DEVICES 265100 INTERIOR LIGHTING 265600 EXTERIOR LIGHTING

    ** End of List **

  • PROJECT NAME FOR: CLEVELAND CLINIC JOB # ISSUED: 00/00/20XX

    COMMON WORK RESULTS FOR ELECTRICAL 260500 - 1

    SECTION 260500 - COMMON WORK RESULTS FOR ELECTRICAL

    PART 1 - GENERAL

    1.1 SUMMARY

    A. It is intended this facility obtain a minimum LEED Silver rating. LEED criteria will be followed for the installation of building systems. This Contractor shall be responsible for the following items to ensure the Facility achieves LEED certification: 1. SS credit 8 Light Pollution Reduction. 2. EA prerequisite 2 Minimum Energy Performance. 3. EA credit 1 Optimize Energy Performance. 4. MR credit 2 Construction Waste Management. 5. IEQ credit 4.1 Low Emitting Materials: Adhesives and Sealants 6. IEQ credit 4.2 Low Emitting Materials: Paints and Coatings. 7. IEQ credit 6.1 Controllability of Systems: Lighting.

    B. Section Includes: 1. Common electrical installation requirements.

    1.2 SUBMITTALS

    A. N/A.

    PART 2 - PRODUCTS

    2.1 N/A.

    PART 3 - EXECUTION

    3.1 COMMON REQUIREMENTS FOR ELECTRICAL INSTALLATION

    A. Comply with Cleveland Clinic Design Standards.

    B. Comply with NECA, NFPA, and OSHA requirements.

    C. All work shall be installed in a neat, workmanlike manner in accordance with ANSI/NECA 1 [2011].

    D. All materials and equipment provided under this contract shall be new (except where otherwise noted) and shall be listed, labeled or certified by Underwriters Laboratories, Inc.

    E. All equipment of the same type and capacity shall be by the same manufacturer.

  • PROJECT NAME FOR: CLEVELAND CLINIC JOB # ISSUED: 00/00/20XX

    COMMON WORK RESULTS FOR ELECTRICAL 260500 - 2

    F. Where any device or part of equipment is referred to in these specifications in the singular number (e.g., "the switch"), this reference shall be deemed to apply to as many such devices as are required to complete the installation as shown on the drawings.

    G. During construction the contractor shall at all times maintain electrical utilities of the building without interruption. Should it be necessary to interrupt any electrical service or utility, the contractor shall secure permission in writing from the Cleveland Clinic for such interruption at least seven days in advance. Any interruption shall be made with minimum amount of inconvenience to the Cleveland Clinic and any shut-down time shall have to be on a premium time basis and such time to be included in the contractor's bid. Arrange to provide and pay for temporary power source if required by project conditions.

    H. Measure indicated mounting heights to bottom of unit for suspended items and to center of unit for wall-mounted items.

    I. Headroom Maintenance: If mounting heights or other location criteria are not indicated, arrange and install components and equipment to provide maximum possible headroom consistent with these requirements.

    J. Working clearance around equipment shall not be less than that specified in the N.E.C. for all voltages specified.

    K. The locations of switches, receptacles, lights, motors, etc. outlets shown are approximate. The contractor shall use good judgment in placing the preceding items to eliminate all interference with ducts, piping, etc. The contractor shall check all door swings so that light switches are not located behind doors. Relocate switches as required, with approval from the Design Professional.

    L. Equipment: Install to facilitate service, maintenance, and repair or replacement of components of both electrical equipment and other nearby installations. Connect in such a way as to facilitate future disconnecting with minimum interference with other items in the vicinity. Normal maintenance shall not require the removal of protective guards from adjacent equipment. Install equipment as close as practical to the locations shown on the Drawings.

    1. Where the Cleveland Clinic determines that the Contractor has installed equipment not conveniently accessible for operations and maintenance, the equipment shall be removed and reinstalled as directed at no additional cost to the Cleveland Clinic.

    2. Conveniently Accessible is defined as being capable of being reached without use of ladders, or without climbing or crawling over or under obstacles such as motors, pumps, belt guards, transformers, racks, piping, ductwork, raceways or similar.

    M. Right of Way: Give to piping systems installed at a required slope.

    N. Owner furnished equipment: Equipment furnished by the Cleveland Clinic shall be received, stored, uncrated, protected, and installed by the Contractor with all appurtenances required to place the equipment in operation, ready for use. The Contractor shall be responsible for the equipment as if he had purchased the equipment himself.

    END OF SECTION 260500

  • PROJECT NAME FOR: CLEVELAND CLINIC JOB # ISSUED: 00/00/20XX

    MEDIUM-VOLTAGE CABLES 260513 - 1

    SECTION 260513 - MEDIUM-VOLTAGE CABLES

    PART 1 - GENERAL

    1.1 RELATED DOCUMENTS

    A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

    1.2 SUMMARY

    A. This Section includes medium voltage shielded power cables, sizes 1/0 through 2000 kcmil, related splices, terminations, and accessories for medium-voltage electrical distribution systems, 5 kV through 35 kV.

    1.3 DEFINITIONS

    A. NETA ATS: National Electrical Testing Association Acceptance Testing Specification.

    1.4 ACTION SUBMITTALS

    A. Product Data: For each size and type of cable indicated.

    B. Samples: 16-inch (400-mm) lengths of each type of cable indicated.

    C. Include data sheets for the following additional items: 1. Splices and terminations. 2. Separable connectors. 3. Cable accessories. 4. Pulling compounds. 5. Strand dynamometer.

    1.5 INFORMATIONAL SUBMITTALS

    A. Resumes of cable splicer(s).

    B. Material Certificates: For each cable and accessory type, signed by manufacturers.

    C. Cable pulling tension calculations and recorded values.

    D. Source quality-control test reports.

    E. Field quality-control test reports.

  • PROJECT NAME FOR: CLEVELAND CLINIC JOB # ISSUED: 00/00/20XX

    MEDIUM-VOLTAGE CABLES 260513 - 2

    1.6 QUALITY ASSURANCE

    A. Installer: Engage a cable splicer, trained and certified by splice material manufacturer, to install, splice, and terminate medium-voltage cable. Cable splicer shall have a minimum of 2000 hours experience with terminating and installing medium voltage cable. Furnish satisfactory proof of such experience for each employee who splices or terminates the cables. Persons listed by the Contractor may be required to perform a dummy or practice splice and termination in the presence of the Cleveland Clinic representative or Engineer before being approved as a qualified installer of medium-voltage cables.

    B. Source Limitations: Obtain cables and accessories through one source from a single manufacturer.

    C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.

    D. Comply with IEEE C2 and NFPA 70.

    E. Comply with ASTM B3 and B8.

    F. Comply with UL requirements.

    G. Comply with Cleveland Clinic Design Standards.

    1.7 PROJECT CONDITIONS [DELETE IF NOT REQUIRED]

    A. Interruption of Existing Electric Service: Do not interrupt electric service to facilities occupied by the Cleveland Clinic or others unless permitted under the following conditions and then only after arranging to provide temporary electric service according to requirements indicated:

    1. Notify Cleveland Clinic no fewer than seven days in advance of proposed interruption of electric service.

    2. Do not proceed with interruption of electric service without Cleveland Clinics permission.

    3. Cleveland Clinic Lock-out/Tag-out procedures shall be used with Contractor controlled locks and tags.

    4. Comply with NFPA 70E.

    PART 2 - PRODUCTS

    2.1 MANUFACTURERS

    A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

    1. Cables: a. General Cable Technologies Corporation. b. Okonite Company (The).

  • PROJECT NAME FOR: CLEVELAND CLINIC JOB # ISSUED: 00/00/20XX

    MEDIUM-VOLTAGE CABLES 260513 - 3

    c. Southwire Company.

    2. Cable Splicing and Terminating Products and Accessories: a. Raychem Corp.; Tyco International Ltd. b. Thomas & Betts Corporation/Elastimold. c. 3M; Electrical Products Division.

    2.2 CABLES

    A. Cable Type: Single conductor [Three conductor (AIA only)], UL type MV105 approved for N.E.C. applications.

    B. Comply with UL 1072, AEIC CS 8, ICEA S-93-639/NEMA WC74, and ICEA S-97-682.

    C. Conductor: Annealed, soft drawn Copper.

    D. Conductor Stranding: Compact round, concentric lay, Class B.

    E. Conductor Insulation: discharge free, no lead, Ethylene-Propylene Rubber (EPR), color contrasted with strand and insulation shields.

    1. Voltage Rating: [5] [8] [15] [25] [35] kV. 2. Insulation Thickness: 133 percent insulation level.

    F. Strand Shielding: Black extruded semi-conducting thermoset copolymer applied directly over the conductor.

    G. Insulation Shield: Black extruded semiconducting thermoset copolymer applied directly over the insulation.

    H. Shielding: [Copper tape, 5 mils thick, helically applied with 25% overlap, over semiconducting insulation shield,] or [six solid copper corrugated drain wires embedded longitudinally in composite layers of semi conducting thermoset copolymer and CPE].

    I. [Cable Armor: Aluminum Interlocked Armor (AIA) applied over cable with overall PVC jacket] [ FOR CABLE TRAY/TUNNEL INSTALLATIONS ] 1. Listings: cables shall be UL listed For CT Use. 2. Jacket shall be color coded for voltage identification.

    J. Cable Jacket: Chlorinated Polyethylene, CPE per ICEA and UL 1072.

    K. Identification: The following minimum legend shall be printed on the jacket and repeated at not more than two foot intervals. 1. Manufacturer/plant no. 2. Conductor size (awg or kcmil). 3. CU. 4. EPR. 5. SHLD. 6. Voltage (kV). 7. Insulation level (133%). 8. Insulation thickness (mils), MV-105.

  • PROJECT NAME FOR: CLEVELAND CLINIC JOB # ISSUED: 00/00/20XX

    MEDIUM-VOLTAGE CABLES 260513 - 4

    2.3 SPLICE KITS

    A. Connectors and Splice Kits: Comply with IEEE 404; type as recommended by cable or splicing kit manufacturer for the application.

    B. Splicing Products: As recommended, in writing, by splicing kit manufacturer for specific sizes, ratings, and configurations of cable conductors. Include all components required for complete splice, with detailed instructions. 1. Heat-shrink splicing kit of uniform, cross-section, polymeric construction with outer

    heat-shrink jacket. 2. Pre-molded, cold-shrink-rubber, in-line splicing kit.

    2.4 SOLID TERMINATIONS

    A. Multi-conductor Cable Sheath Seals: Type recommended by seal manufacturer for type of cable and installation conditions, including orientation.

    1. Compound-filled, cast-metal body, metal-clad cable terminator for metal-clad cable with external plastic jacket.

    2. Cold-shrink sheath seal kit with preformed sleeve openings sized for cable and insulated conductors.

    3. Heat-shrink sheath seal kit with phase- and ground-conductor re-jacketing tubes, cable-end sealing boot, and sealing plugs for unused ground-wire openings in boot.

    B. Shielded-Cable Terminations: Comply with the following classes of IEEE 48. Insulation class is equivalent to that of cable. Include shield ground strap for shielded cable terminations.

    1. Class 1 Terminations: Modular type, furnished as a kit, with stress-relief tube; multiple, molded-silicone rubber, insulator modules; shield ground strap; and compression-type connector.

    2. Class 1 Terminations: Heat-shrink type with heat-shrink inner stress control and outer non-tracking tubes; multiple, molded, non-tracking skirt modules; and compression-type connector.

    3. Class 2 Terminations, Indoors: Kit with stress-relief tube, non-tracking insulator tube, shield ground strap, and compression-type connector. Include silicone-rubber tape, cold-shrink-rubber sleeve, or heat-shrink plastic-sleeve moisture seal for end of insulation whether or not supplied with kits.

    4. Medium voltage cable terminations and splices: long barrel, 2-hole hydraulic crimp lugs.

    2.5 SEPARABLE INSULATED CONNECTORS

    A. Description: Modular system, complying with IEEE 386, with disconnecting, single-pole, cable terminators and with matching, stationary, plug-in, dead-front terminals designed for cable voltage and for sealing against moisture.

    B. Terminations at Distribution Points: Modular type, consisting of terminators installed on cables and modular, dead-front, terminal junctions for interconnecting cables.

  • PROJECT NAME FOR: CLEVELAND CLINIC JOB # ISSUED: 00/00/20XX

    MEDIUM-VOLTAGE CABLES 260513 - 5

    C. Load-Break Cable Terminators: Elbow-type units with 200-A load make/break and continuous-current rating; coordinated with insulation diameter, conductor size, and material of cable being terminated. Include test point on terminator body that is capacitance coupled.

    D. Dead-Break Cable Terminators: Elbow-type unit with 600-A continuous-current rating; designed for de-energized disconnecting and connecting; coordinated with insulation diameter, conductor size, and material of cable being terminated. Include test point on terminator body that is capacitance coupled.

    E. Dead-Front Terminal Junctions: Modular bracket-mounted groups of dead-front stationary terminals that mate and match with above cable terminators. Two-, three-, or four-terminal units as indicated, with fully rated, insulated, watertight conductor connection between terminals and complete with grounding lug, manufacturer's standard accessory stands, stainless-steel mounting brackets, and attaching hardware.

    1. Protective Cap: Insulating, electrostatic-shielding, water-sealing cap with drain wire. 2. Portable Feed-Through Accessory: Two-terminal, dead-front junction arranged for

    removable mounting on accessory stand of stationary terminal junction. 3. Grounding Kit: Jumpered elbows, portable feed-through accessory units, protective caps,

    test rods suitable for concurrently grounding three phases of feeders, and carrying case. 4. Standoff Insulator: Portable, single dead-front terminal for removable mounting on

    accessory stand of stationary terminal junction. Insulators suitable for fully insulated isolation of energized cable-elbow terminator.

    F. Tool Set: Shotgun hot stick with energized terminal indicator, and carrying case.

    G. Ground Bails: Heavy duty grounding bails shall be provided to accommodate portable grounding equipment.

    2.6 ARC-PROOFING MATERIALS

    A. Tape for First Course on Metal Objects: Scotch 88, 10-mil- (250-micrometer-) thick, corrosion-protective, moisture-resistant, PVC pipe-wrapping tape.

    B. Arc-Proofing Tape: Scotch 77, fireproof tape, flexible, conformable, and intumescent to 0.3 inch (8 mm) thick, compatible with cable jacket.

    C. Self-fusing Silicon Tape: Scotch 70, high temperature, arc and track resistant tape composed of self-fusing, inorganic silicone rubber.

    D. Glass-Cloth Tape: Scotch 69, Pressure-sensitive adhesive type, 1/2 inch (13 mm) wide.

    2.7 SOURCE QUALITY CONTROL

    A. Test and inspect cables according to ICEA S-97-682 before shipping.

    B. Test strand-filled cables for water-penetration resistance according to ICEA T-31-610, using a test pressure of 5 psig (35 kPa).

  • PROJECT NAME FOR: CLEVELAND CLINIC JOB # ISSUED: 00/00/20XX

    MEDIUM-VOLTAGE CABLES 260513 - 6

    PART 3 - EXECUTION

    3.1 INSTALLATION

    A. Minimum cable size shall be #1/0 awg.

    B. Install cables according to IEEE 576.

    C. Pull Conductors: Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values for single or multi-conductor cables. 1. A strand dynamometer/tension meter shall be used during the cable installation, readings

    shall be recorded and a report submitted for each cable pull. 2. Where necessary, use manufacturer-approved pulling compound or lubricant that will not

    deteriorate conductor or insulation. 3. Use pulling means, including fish tape, cable, rope, and basket-weave cable grips that

    will not damage cables and raceways. Do not use rope hitches for pulling attachment to cable.

    4. Provide cable lengths with liberal allowances of slack for terminations. 5. Cable ends shall be moisture proofed at all times until terminations are installed.

    D. Install exposed cables in tunnels in suitable cable trays, cables shall be secured with UL listed tie wrap materials.

    E. Install underground cables in Sch. 40 PVC conduits in concrete encased ductbanks, comply with Section 260543.

    F. In buildings and at road crossings, install cables in Rigid Galvanized Conduit (Heavy-wall).

    G. Provide an insulated, stranded copper ground conductor in each conduit with phase conductors.

    H. Medium voltage cables shall not be direct buried.

    I. Install permanent markers at ends of cable runs, changes in direction, and splices.

    J. Install "buried-cable" detectable, warning tape above ductbanks. Comply with Sections 260543 and 260553.

    K. Outdoor splices and terminations shall be performed in dry conditions only.

    L. In manholes, hand holes, pull boxes, junction boxes, and cable vaults, train cables around walls by the longest route from entry to exit and support cables with suitable UL listed non-metallic racks, located at intervals adequate to prevent sag.

    M. Pull all cables in continuous lengths, splices shall be avoided unless necessitated by the length of the run. Locations of all splices shall be approved by the Facilities Engineering representative in writing.

    N. Install separable insulated-connector components as follows:

    1. Protective Cap: At each terminal junction, with one on each terminal to which no feeder is indicated to be connected.

  • PROJECT NAME FOR: CLEVELAND CLINIC JOB # ISSUED: 00/00/20XX

    MEDIUM-VOLTAGE CABLES 260513 - 7

    2. Portable Feed-Through Accessory: Three. 3. Standoff Insulator: Three.

    O. Arc Proofing: Unless otherwise indicated, arc proof medium-voltage cable at locations not protected by conduit, cable tray, or termination materials such as transformers, switchgear, and manholes. In addition to arc-proofing tape manufacturer's written instructions, apply arc proofing as follows:

    1. Clean cable sheath. 2. Wrap metallic cable components with 10-mil (250-micrometer) pipe-wrapping tape. 3. Smooth surface contours with electrical insulation putty. 4. Apply arc-proofing tape in one half-lapped layer with coated side toward cable. 5. Band arc-proofing tape with 1-inch- (25-mm-) wide bands of half-lapped, adhesive,

    glass-cloth tape 2 inches (50 mm) O.C.

    P. Apply firestopping to electrical penetrations of fire-rated floor and wall assemblies to restore original fire-resistance rating of assembly according to Division 07 Sections and Cleveland Clinic Fire Protection Group. 1. All penetrations shall be under constant visual surveillance until firestopping is applied

    unless an approved ILSM is in place for each location. 2. Products: Specified Technologies, Inc.

    Q. Ground shields of shielded cable at terminations, splices, and separable insulated connectors. Ground metal bodies of terminators, splices, cable and separable insulated-connector fittings, and hardware.

    R. Identify cables according to Division 26 Section 260553 "Identification for Electrical Systems." 1. Identify individual phases at termination points. 2. In manholes, cables shall be identified where cables enter and leave the manhole. Identify

    circuit number and voltage. 3. Use embossed brass tags tie wrapped to cable.

    3.2 FIELD QUALITY CONTROL

    A. Perform the following field tests and inspections and prepare test reports:

    1. Perform each visual and mechanical inspection and electrical test stated in NETA ATS. Certify compliance with test parameters.

    2. After installing medium-voltage cables and terminations but before electrical circuitry has been connected to busses or switchgear and energized, test for compliance with requirements, including but not limited to DC high potential testing according to IEEE 400 and insulation resistance testing.

    B. Remove and replace non-compliant cable or terminations and retest as specified above.

    END OF SECTION 260513

  • PROJECT NAME FOR: CLEVELAND CLINIC JOB # ISSUED: 00/00/20XX

    LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 1

    SECTION 260519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

    PART 1 - GENERAL

    1.1 RELATED DOCUMENTS

    A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

    1.2 SUMMARY

    A. This Section includes the following:

    1. Building wires and cables rated 600 V and less. 2. Connectors, splices, and terminations rated 600 V and less.

    B. Related Sections include the following: 1. Division 27 Sections for cabling used for voice and data circuits.

    1.3 QUALITY ASSURANCE

    A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by UL and marked for intended use.

    B. Comply with ASTM.

    C. Comply with UL 44, 83, and 486.

    D. Comply with NFPA 70.

    E. Comply with NFPA 99.

    F. Comply with FM Global requirements.

    G. Comply with Cleveland Clinic Design Standards.

    1.4 SUBMITTALS

    A. Product Data: For each type of product indicated.

    B. Include data sheets for the following additional items: 1. Splices and terminations. 2. Pulling compounds. 3. Cable accessories.

  • PROJECT NAME FOR: CLEVELAND CLINIC JOB # ISSUED: 00/00/20XX

    LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 2

    C. Field quality-control test reports.

    1.5 PROJECT CONDITIONS [DELETE IF NOT REQUIRED]

    A. Interruption of Existing Electric Service: Do not interrupt electric service to facilities occupied by the Cleveland Clinic or others unless permitted under the following conditions and then only after arranging to provide temporary electric service according to requirements indicated:

    1. Notify Cleveland Clinic no fewer than seven days in advance of proposed interruption of electric service.

    2. Do not proceed with interruption of electric service without Cleveland Clinics permission.

    3. Cleveland Clinic Lock-out/Tag-out procedures shall be used with Contractor controlled locks and tags.

    4. Comply with NFPA 70E.

    PART 2 - PRODUCTS

    2.1 CONDUCTORS AND CABLES

    A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. General Cable Corporation. 2. Okonite. 3. Southwire Company.

    B. Copper Conductors: Comply with NEMA WC 70.

    1. Aluminum conductors shall not be used under any circumstances.

    C. Conductor Insulation: Comply with NEMA WC 70 for Types THHN-THWN, XHHW-2 and SO.

    1. Voltage rating: 600 Volts for 480/277V and 208/120V.

    D. Multi-conductor Cable type MC and AC: Use of MC or medical grade AC cable is not permitted under any circumstances unless specifically approved in writing by the Senior Director of Facilities.

    2.2 CONNECTORS AND SPLICES

    A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Burndy, Thomas & Betts. 2. O-Z/Gedney; EGS Electrical Group LLC. 3. 3M; Electrical Products Division. 4. Ilsco.

  • PROJECT NAME FOR: CLEVELAND CLINIC JOB # ISSUED: 00/00/20XX

    LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 3

    B. Description: Factory-fabricated connectors and splices of size, ampacity rating, material, type, and class for application and service indicated. 1. Aboveground Circuits (No. 10 AWG and smaller):

    a. Connectors: Solderless, screw-on, reusable pressure cable type, rated 600 V, 90 C, with integral insulation, approved for copper conductors.

    b. The integral insulator shall have a skirt to completely cover the stripped wires. c. The number, size, and combination of conductors, as listed on the manufacturer's

    packaging, shall be strictly followed. 2. Aboveground Circuits (No. 8 AWG and larger):

    a. Cable termination lugs shall be made of high conductivity and corrosion-resistant material, electro-tin plated, listed for use with copper conductors only, rated for 600 V. Lugs shall be color coded by size.

    b. Cable termination lugs shall be indent type, long barrel with chamfered entry, 2 hole, compression type for 250 kcmil and above, 1 hole for less than 250 kcmil.

    PART 3 - EXECUTION

    3.1 CONDUCTOR MATERIAL APPLICATIONS

    A. Feeders: Soft annealed Copper stranded, class B compressed.

    B. Branch Circuits: Copper. Solid for No. 16 AWG and smaller; stranded for No. 14 AWG and larger.

    C. Minimum Wire Size: #12 awg for power and lighting circuits, #14 awg for control circuits. In the case of homeruns over 125 feet in length, no conductor smaller than a No. 10 wire shall be used. The tap conductor from the J-box in the ceiling to the receptacle may be No. 12. Each 120-volt phase conductor shall have a neutral conductor of the same size. The sizing of all wire except remote control wire shall be accomplished in the case of both feeder and branch circuits by conforming to the following provisions. Only lighting circuits may share grounding conductors. All lighting circuits with shared grounding conductors shall be #10 AWG minimum.

    3.2 CONDUCTOR INSULATION AND MULTI-CONDUCTOR CABLE APPLICATIONS AND WIRING METHODS

    A. Service Entrance: Type XHHW, or type THHN/THWN up to and including 600 kcmil.

    B. Exposed Feeders: Type XHHW for #2 awg and larger, or type THHN/THWN for all sizes up to and including 600 kcmil, single conductors in raceway.

    C. Feeders Concealed in Ceilings, Walls, Partitions, and Crawlspaces: Type XHHW for #2 awg and larger, or type THHN/THWN for all sizes up to and including 600 kcmil, single conductors in raceway.

  • PROJECT NAME FOR: CLEVELAND CLINIC JOB # ISSUED: 00/00/20XX

    LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 4

    D. Feeders Concealed in Concrete, below Slabs-on-Grade, and underground: Type XHHW for #2 awg and larger, or type THHN/THWN for all sizes up to and including 600 kcmil, single conductors in raceway.

    E. Exposed Branch Circuits, Including in Crawlspaces: Type THHN-THWN, single conductors in raceway.

    F. Branch Circuits Concealed in Ceilings, Walls, and Partitions: Type THHN-THWN, single conductors in raceway.

    G. Branch Circuits Concealed in Ceilings, Walls, and Partitions for Isolated Power Panel (IPP) Systems in Operating Rooms, ICU or CCU: Type XHHW or XHHW-2, low leakage, with a dielectric constant of 3.5 or less, single conductors in raceway.

    H. Branch Circuits Concealed in Concrete, below Slabs-on-Grade, and underground: Type THHN-THWN, single conductors in raceway.

    I. Cord Drops and Portable Appliance Connections: Type SO, hard service cord with stainless-steel, wire-mesh, and strain relief device at terminations to suit application.

    J. Recessed or Semi-recessed Lighting Fixture Whips: Type THHN-THWN (90 deg C), single conductors in FMC in lengths not to exceed six (6) feet.

    3.3 INSTALLATION OF CONDUCTORS AND CABLES

    A. Splices in feeder circuits shall be avoided unless necessitated by the length of the run. Locations of all splices shall be approved by the Office of Facilities.

    B. Conductors may be run parallel from sizes 250 kcmil up to and including 600 kcmil provided all paralleled conductors are of the same size, manufacturer, length and type of insulation.

    C. Use manufacturer-approved pulling compound or lubricant where necessary; compound used must not deteriorate conductor or insulation. Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values.

    D. Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips that will not damage cables or raceway.

    E. Support cables according to Division 26 Section "Hangers and Supports for Electrical Systems."

    F. Identify and color-code conductors and cables according to Division 26 Section "Identification for Electrical Systems" for secondary service, feeders and branch circuits.

    3.4 CONNECTIONS

    A. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A.

  • PROJECT NAME FOR: CLEVELAND CLINIC JOB # ISSUED: 00/00/20XX

    LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 5

    B. Make splices and taps that are compatible with conductor material and that possess equivalent or better mechanical strength and insulation ratings than unspliced conductors.

    C. Wiring at Outlets: Install conductor at each outlet, with at least 6 inches (150 mm) of slack.

    3.5 FIRESTOPPING

    A. Apply firestopping to electrical penetrations of fire-rated floor and wall assemblies to restore original fire-resistance rating of assembly according to Division 07 Sections and Cleveland Clinic Fire Protection Group. 1. All penetrations shall be under constant visual surveillance until firestopping is applied

    unless an approved ILSM is in place for each location. 2. Products: Specified Technologies, Inc.

    3.6 FIELD QUALITY CONTROL

    A. Perform tests and inspections and prepare test reports.

    B. Tests and Inspections:

    1. After installing conductors and cables and before electrical circuitry has been energized, test service entrance and feeder conductors, and conductors feeding the following critical equipment and services for compliance with requirements.

    a. Generator, UPS, Isolated Power Panel, Fire Pump.

    2. Perform each visual and mechanical inspection and electrical test stated in NETA Acceptance Testing Specification. Certify compliance with test parameters.

    C. Test Reports: Prepare a written report to record the following:

    1. Test procedures used. 2. Test results that comply with requirements. 3. Test results that do not comply with requirements and corrective action taken to achieve

    compliance with requirements.

    D. Remove and replace non-compliant cables or wires and retest as specified above.

    END OF SECTION 260519

  • PROJECT NAME CLEVELAND CLINIC JOB #

    FOR: ISSUED: 00/00/20XX

    CONTROL-VOLTAGE ELECTRICAL POWER CABLES 260523 - 1

    SECTION 260523 - CONTROL-VOLTAGE ELECTRICAL POWER CABLES

    PART 1 - GENERAL

    1.1 RELATED DOCUMENTS

    A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

    B. See Cleveland Clinic ITD Standards for Telecommunications Cabling requirements.

    1.2 SUMMARY

    A. Section Includes: 1. Low-voltage control cabling. 2. Control-circuit conductors. 3. Identification products.

    1.3 DEFINITIONS

    A. Low Voltage: As defined in NFPA 70 for circuits and equipment used for remote-control and signaling power-limited circuits.

    1.4 ACTION SUBMITTALS

    A. Product Data: For each type of product indicated.

    1.5 INFORMATIONAL SUBMITTALS

    A. Source quality-control reports.

    B. Field quality-control reports.

    1.6 CLOSEOUT SUBMITTALS

    A. Maintenance Data: For wire and cable to include in maintenance manuals.

    1.7 QUALITY ASSURANCE

    A. Surface-Burning Characteristics: As determined by testing identical products according to ASTM E 84 by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.

  • PROJECT NAME CLEVELAND CLINIC JOB #

    FOR: ISSUED: 00/00/20XX

    CONTROL-VOLTAGE ELECTRICAL POWER CABLES 260523 - 2

    1. Flame-Spread Index: 25 or less. 2. Smoke-Developed Index: 50 or less.

    B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

    PART 2 - PRODUCTS

    2.1 PATHWAYS

    A. Conduit and Boxes: Comply with requirements in Division 26 Section "Raceway and Boxes for Electrical Systems."

    1. Outlet boxes shall be no smaller than 2 inches (50 mm) wide, 3 inches (75 mm) high, and 2-1/2 inches (64 mm) deep.

    2.2 LOW-VOLTAGE CONTROL CABLE

    A. Plenum-Rated, Paired Cable: NFPA 70, Type CMP.

    1. One pair, twisted, No. 16 AWG, stranded (19x29) tinned-copper conductors. 2. PVC insulation. 3. Unshielded. 4. PVC jacket. 5. Flame Resistance: Comply with NFPA 262.

    B. Plenum-Rated, Paired Cable: NFPA 70, Type CMP.

    1. One pair, twisted, No. 18 AWG, stranded (19x30) tinned-copper conductors. 2. Fluorinated ethylene propylene insulation. 3. Unshielded. 4. Plastic jacket. 5. Flame Resistance: NFPA 262, Flame Test.

    2.3 CONTROL-CIRCUIT CONDUCTORS

    A. Class 1 Control Circuits: Stranded copper, Type THHN-THWN, in raceway, complying with UL 83.

    B. Class 2 Control Circuits: Stranded copper, Type THHN-THWN, in raceway, complying with UL 83.

    C. Class 3 Remote-Control and Signal Circuits: Stranded copper, Type TW or Type TF, complying with UL 83.

  • PROJECT NAME CLEVELAND CLINIC JOB #

    FOR: ISSUED: 00/00/20XX

    CONTROL-VOLTAGE ELECTRICAL POWER CABLES 260523 - 3

    2.4 IDENTIFICATION PRODUCTS

    A. Comply with requirements in Division 26 Section "Identification for Electrical Systems."

    PART 3 - EXECUTION

    3.1 INSTALLATION OF PATHWAYS

    A. Comply with requirements in Division 26 Section "Raceway and Boxes for Electrical Systems" for installation of conduits and wireways.

    3.2 INSTALLATION OF CONDUCTORS AND CABLES

    A. Comply with NECA 1.

    B. General Requirements for Cabling: 1. Terminate all conductors; no cable shall contain un-terminated elements. Make

    terminations only at indicated outlets, terminals, and panels. 2. Cables may not be spliced. Secure and support open cables at intervals not exceeding 30

    inches (760 mm) and not more than 6 inches (150 mm) from cabinets, boxes, fittings, and terminals.

    3. Do not install bruised, kinked, scored, deformed, or abraded cable. Do not splice cable between termination, tap, or junction points. Remove and discard cable if damaged during installation and replace it with new cable.

    4. Cold-Weather Installation: Bring cable to room temperature before de-reeling. Heat lamps shall not be used for heating.

    C. Installation of Control-Circuit Conductors:

    1. Install wiring in raceways. Comply with requirements specified in Division 26 Section "Raceway and Boxes for Electrical Systems."

    3.3 REMOVAL OF CONDUCTORS AND CABLES

    A. Remove abandoned conductors and cables.

    3.4 CONTROL-CIRCUIT CONDUCTORS

    A. Minimum Conductor Sizes:

    1. Class 1 remote-control and signal circuits, No. 14 AWG. 2. Class 2 low-energy, remote-control, and signal circuits, No. 16 AWG. 3. Class 3 low-energy, remote-control, alarm, and signal circuits, No. 12 AWG.

  • PROJECT NAME CLEVELAND CLINIC JOB #

    FOR: ISSUED: 00/00/20XX

    CONTROL-VOLTAGE ELECTRICAL POWER CABLES 260523 - 4

    3.5 FIRESTOPPING

    A. Apply firestopping to electrical penetrations of fire-rated floor and wall assemblies to restore original fire-resistance rating of assembly according to Division 07 Sections and Cleveland Clinic Fire Protection Group. 1. All penetrations shall be under constant visual surveillance until firestopping is applied

    unless an approved ILSM is in place for each location. 2. Products: Specified Technologies, Inc.

    3.6 GROUNDING

    A. For low-voltage wiring and cabling, comply with requirements in Division 26 Section "Grounding and Bonding for Electrical Systems."

    3.7 IDENTIFICATION

    A. Comply with requirements for identification specified in Division 26 Section "Identification for Electrical Systems."

    3.8 FIELD QUALITY CONTROL

    A. Perform tests and inspections. 1. Perform each visual and mechanical inspection and electrical test stated in NETA

    Acceptance Testing Specification. Certify compliance with test parameters. 2. Perform continuity tests and checks.

    B. End-to-end cabling will be considered defective if it does not pass tests and inspections.

    C. Prepare test and inspection reports.

    END OF SECTION 260523

  • PROJECT NAME CLEVELAND CLINIC JOB #

    FOR: ISSUED: 00/00/20XX

    GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 1

    SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

    PART 1 - GENERAL

    1.1 RELATED DOCUMENTS

    A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

    B. Cleveland Clinic ITD Standards for Electronic equipment, voice and data systems grounding requirements.

    1.2 SUMMARY

    A. Section Includes: Grounding systems and equipment.

    B. Section includes grounding systems and equipment, plus the following special applications: 1. Underground distribution grounding. 2. Ground bonding common with lightning protection system.

    1.3 ACTION SUBMITTALS

    A. Product Data: For each type of product indicated.

    1.4 INFORMATIONAL SUBMITTALS

    A. Informational Submittals: Plans showing dimensioned as-built locations of grounding features specified in "Field Quality Control" Article, including the following:

    1. Test wells. 2. Ground rods. 3. Ground rings. 4. Grounding arrangements and connections for separately derived systems. 5. Grounding for sensitive electronic equipment.

    B. Field quality-control reports.

    1.5 CLOSEOUT SUBMITTALS

    A. Operation and Maintenance Data: For grounding to include in emergency, operation, and maintenance manuals. In addition to items specified in Division 01 Section "Operation and Maintenance Data," include the following:

  • PROJECT NAME CLEVELAND CLINIC JOB #

    FOR: ISSUED: 00/00/20XX

    GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 2

    1. Instructions for periodic testing and inspection of grounding features at test wells, ground rings, and grounding connections for separately derived systems based on NFPA 70B.

    a. Tests shall determine if ground-resistance or impedance values remain within specified maximums, and instructions shall recommend corrective action if values do not.

    b. Include recommended testing intervals.

    1.6 QUALITY ASSURANCE

    A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

    B. Comply with UL 467 for grounding and bonding materials and equipment.

    C. Comply with NFPA 70.

    D. Comply with NFPA 99.

    E. Comply with FM Global requirements.

    F. Comply with Cleveland Clinic Design Standards.

    PART 2 - PRODUCTS

    2.1 CONDUCTORS

    A. Insulated Conductors: Tinned-copper wire or cable insulated for 600 V with green colored insulation, UL 44 or UL 83 listed, unless otherwise required by applicable Code or authorities having jurisdiction.

    B. Bare Copper Conductors:

    1. Solid Conductors: ASTM B 3. 2. Stranded Conductors: ASTM B 8. 3. Tinned Conductors: ASTM B 33. 4. Bonding Cable: 28 kcmil, 14 strands of No. 17 AWG conductor, 1/4 inch (6 mm) in

    diameter. 5. Bonding Conductor: No. 4 or No. 6 AWG, stranded conductor. 6. Bonding Jumper: Copper tape, braided conductors terminated with copper ferrules; 1-5/8

    inches (41 mm) wide and 1/16 inch (1.6 mm) thick. 7. Tinned Bonding Jumper: Tinned-copper tape, braided conductors terminated with copper

    ferrules; 1-5/8 inches (41 mm) wide and 1/16 inch (1.6 mm) thick.

    C. Grounding Bus: Predrilled rectangular bars of annealed copper, 1/4 by 4 inches (6.3 by 100 mm) in cross section, provided with standard NEMA bolt hole sizing and spacing for the type of connectors to be used. Stand-off insulators for mounting shall comply with UL 891 for use in

  • PROJECT NAME CLEVELAND CLINIC JOB #

    FOR: ISSUED: 00/00/20XX

    GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 3

    switchboards, 600 V, Lexan or PVC, impulse tested at 5000 V. Provide clear Lexan cover over connections.

    2.2 CONNECTORS

    A. Listed and labeled by an NRTL acceptable to authorities having jurisdiction for applications in which used and for specific types, sizes, and combinations of conductors and other items connected.

    B. Bolted Connectors for Conductors and Pipes: Copper or copper alloy, pressure type with at least two bolts.

    1. Pipe Connectors: Clamp type, sized for pipe.

    C. Welded Connectors: Exothermic-welding kits of types recommended by kit manufacturer for materials being joined and installation conditions.

    D. Bus-bar Connectors: Mechanical type, cast silicon bronze, solder-less compression-type wire terminals, and long-barrel, two-bolt connection to ground bus bar.

    2.3 GROUNDING ELECTRODES

    A. Ground Rods: Copper-clad steel; 3/4 inch by 10 feet (19 mm by 3 m) in diameter.

    PART 3 - EXECUTION

    3.1 APPLICATIONS

    A. Conductors: Install solid conductor for No. 8 AWG and smaller, and stranded conductors for No. 6 AWG and larger unless otherwise indicated.

    B. Underground Grounding Conductors: Install bare tinned-copper conductor, No. 2/0 AWG minimum.

    1. Bury at least 24 inches (600 mm) below grade. 2. Duct-Bank Grounding Conductor: Bury 12 inches (300 mm) above duct bank as part of

    duct-bank installation. Bury detectable warning tape approximately 6 inches (150 mm) above grounding conductors. Warning tape shall comply with Section 260553.

    C. Isolated Grounding Conductors: Green-colored insulation with continuous yellow stripe. On feeders with isolated ground, identify grounding conductor where visible to normal inspection, with alternating bands of green and yellow tape, with at least three bands of green and two bands of yellow.

    D. Grounding Bus: Install in electrical rooms, in rooms housing service equipment, and elsewhere as indicated.

  • PROJECT NAME CLEVELAND CLINIC JOB #

    FOR: ISSUED: 00/00/20XX

    GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 4

    1. Install bus on insulated spacers 2 inches (50 mm) minimum from wall, 12 inches (300 mm) above finished floor unless otherwise indicated.

    2. Where indicated on both sides of doorways, route bus up to top of door frame, across top of doorway, and down to specified height above floor; connect to horizontal bus.

    E. Conductor Terminations and Connections:

    1. Pipe and Equipment Grounding Conductor Terminations: Bolted connectors. 2. Underground Connections: Exothermic welded connectors except at test wells and as

    otherwise indicated. 3. Connections to Ground Rods at Test Wells: Bolted connectors. 4. Connections to Structural Steel: Exothermic welded connectors.

    3.2 GROUNDING UNDERGROUND DISTRIBUTION SYSTEM COMPONENTS

    A. Comply with IEEE C2 grounding requirements.

    B. Grounding Manholes and Handholes: Install a driven ground rod through manhole or handhole floor, close to wall, and set rod depth so 4 inches (100 mm) will extend above finished floor. If necessary, install ground rod before manhole is placed and provide No. 1/0 AWG bare, tinned-copper conductor from ground rod into manhole through a waterproof sleeve in manhole wall. Protect ground rods passing through concrete floor with a double wrapping of pressure-sensitive insulating tape or heat-shrunk insulating sleeve from 2 inches (50 mm) above to 6 inches (150 mm) below concrete. Seal floor opening with waterproof, non-shrink grout.

    C. Grounding Connections to Manhole Components: Bond exposed-metal parts such as inserts, cable racks, pulling irons, ladders, and cable shields within each manhole or handhole, to ground rod or grounding conductor. Make connections with No. 4 AWG minimum, stranded, hard-drawn copper bonding conductor. Train conductors level or plumb around corners and fasten to manhole walls. Connect to cable armor and cable shields according to written instructions by manufacturer of splicing and termination kits.

    D. Pad-Mounted Transformers and Switches: Install two ground rods and ground ring around the pad. Ground pad-mounted equipment and noncurrent-carrying metal items associated with substations by connecting them to underground cable and grounding electrodes. Install tinned-copper conductor not less than No. 2/0 for ground ring and for taps to equipment grounding terminals. Bury ground ring not less than 12 inches (300 mm) from the foundation.

    3.3 UTILITY GROUNDING

    A. Provide grounding and bonding at Utility Companys metering equipment in accordance with Utility Companys requirements.

    3.4 EQUIPMENT GROUNDING

    A. Install insulated equipment grounding conductors with all feeders and branch circuits.

  • PROJECT NAME CLEVELAND CLINIC JOB #

    FOR: ISSUED: 00/00/20XX

    GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 5

    1. Conduit shall not be used as the ground conductor. 2. In Healthcare facilities, metallic conduit may be used as the additional means of

    grounding where the raceway system qualifies as a grounding conductor in accordance with NEC 250.118.

    B. Install insulated equipment grounding conductors with the following items, in addition to those required by NFPA 70:

    1. Feeders and branch circuits. 2. Lighting circuits. 3. Receptacle circuits. 4. Single-phase motor and appliance branch circuits. 5. Three-phase motor and appliance branch circuits. 6. Flexible raceway runs. 7. Armored cable runs. 8. Busway Supply Circuits: Install insulated equipment grounding conductor from

    grounding bus in the switchgear, switchboard, or distribution panel to equipment grounding bar terminal on busway.

    9. Computer and Rack-Mounted Electronic Equipment Circuits: Install insulated equipment grounding conductor in branch-circuit runs from equipment-area power panels and power-distribution units.

    10. X-Ray/Imaging Equipment Circuits: Install insulated equipment grounding conductor in circuits supplying x-ray/imaging equipment.

    C. Air-Duct Equipment Circuits: Install insulated equipment grounding conductor to duct-mounted electrical devices operating at 120 V and more, including air cleaners, heaters, dampers, humidifiers, and other duct electrical equipment. Bond conductor to each unit and to air duct and connected metallic piping.

    D. Water Heater, Heat-Tracing, and Anti-frost Heating Cables: Install a separate insulated equipment grounding conductor to each electric water heater and heat-tracing cable. Bond conductor to heater units, piping, connected equipment, and components.

    E. Isolated Grounding Receptacle Circuits: Install an insulated equipment grounding conductor connected to the receptacle grounding terminal. Isolate conductor from raceway and from panelboard grounding terminals. Terminate at equipment grounding conductor terminal of the applicable derived system or service unless otherwise indicated.

    F. Isolated Equipment Enclosure Circuits: For designated equipment supplied by a branch circuit or feeder, isolate equipment enclosure from supply circuit raceway with a nonmetallic raceway fitting listed for the purpose. Install fitting where raceway enters enclosure, and install a separate insulated equipment grounding conductor. Isolate conductor from raceway and from panelboard grounding terminals. Terminate at equipment grounding conductor terminal of the applicable derived system or service unless otherwise indicated.

    G. Special Grounding: For patient care area electrical power system grounding, conform to NFPA 99 and N.E.C.

    H. Panelboard Bonding in Patient Care Areas: The equipment grounding terminal buses of the normal and essential branch circuit panel boards serving the same individual patient vicinity

  • PROJECT NAME CLEVELAND CLINIC JOB #

    FOR: ISSUED: 00/00/20XX

    GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 6

    shall be bonded together with an insulated continuous copper conductor not less than No. 10 AWG installed in rigid metal conduit.

    I. Cable trays shall be grounded and bonded in accordance with N.E.C. requirements and Cleveland Clinic ITD Standards.

    J. Raised floors: Provide bonding of all raised floor components.

    K. Signal, Data, and Communication Equipment: Comply with requirements in Cleveland Clinic ITD Standards.

    L. Metal Poles Supporting Outdoor Lighting Fixtures: Install grounding electrode and a separate insulated equipment grounding conductor in addition to grounding conductor installed with branch-circuit conductors.

    M. Outdoor metallic fences around electrical equipment shall be grounded.

    3.5 INSTALLATION

    A. Grounding Conductors: Route along shortest and straightest paths possible unless otherwise indicated or required by Code. Avoid obstructing access or placing conductors where they may be subjected to strain, impact, or damage.

    1. Where ground conductors are subject to physical damage, install in raceway.

    B. Ground Bonding Common with Lightning Protection System: Comply with NFPA 780 and UL 96 when interconnecting with lightning protection system. Bond electrical power system ground directly to lightning protection system grounding conductor at closest point to electrical service grounding electrode. Use bonding conductor sized same as system grounding electrode conductor, and install in conduit.

    C. Ground Rods: Drive rods until tops are 12 inches (100 mm) below finished floor or final grade unless otherwise indicated.

    1. Interconnect ground rods with grounding electrode conductor below grade and as otherwise indicated. Make connections without exposing steel or damaging coating if any.

    D. Test Wells: Ground rod driven through bottom of handhole. Handholes are specified in Division 26 Section "Underground Ducts and Raceways for Electrical Systems," and shall be at least 12 inches (300 mm) deep, with cover.

    1. Test Wells: Install at least one test well for each service unless otherwise indicated. Install at the ground rod electrically closest to service entrance. Set top of test well flush with finished grade or floor.

    E. Bonding Straps and Jumpers: Install in locations accessible for inspection and maintenance except where routed through short lengths of conduit.

  • PROJECT NAME CLEVELAND CLINIC JOB #

    FOR: ISSUED: 00/00/20XX

    GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 7

    1. Bonding to Structure: Bond straps directly to basic structure, taking care not to penetrate any adjacent parts.

    2. Bonding to Equipment Mounted on Vibration Isolation Hangers and Supports: Install bonding so vibration is not transmitted to rigidly mounted equipment.

    3. Use exothermic-welded connectors for outdoor locations; if a disconnect-type connection is required, use a bolted clamp.

    F. Grounding and Bonding for Piping:

    1. Metal Water Service Pipe: Install insulated copper grounding conductors, in conduit, from building's main service equipment, or grounding bus, to main metal water service entrances to building. Connect grounding conductors to main metal water service pipes; use a bolted clamp connector or bolt a lug-type connector to a pipe flange by using one of the lug bolts of the flange. Where a dielectric main water fitting is installed, connect grounding conductor on street side of fitting. Bond metal grounding conductor conduit or sleeve to conductor at each end.

    2. Water Meter Piping: Use braided-type bonding jumpers to electrically bypass water meters. Connect to pipe with a bolted connector.

    3. Bond each aboveground portion of gas piping system downstream from equipment shutoff valve.

    G. Bonding Interior Metal Ducts: Bond metal air ducts to equipment grounding conductors of associated fans, blowers, electric heaters, and air cleaners. Install tinned bonding jumper to bond across flexible duct connections to achieve continuity.

    H. Grounding for Steel Building Structure: Install a driven ground rod at base of each corner column and at intermediate exterior columns at distances not more than 60 feet (18 m) apart.

    I. Ground Ring: Install a grounding conductor, electrically connected to each building structure ground rod and to each steel column, extending around the perimeter of building.

    1. Install tinned-copper conductor not less than No. 4/0 AWG for ground ring and for taps to building steel.

    2. Bury ground ring not less than 24 inches (600 mm) from building's foundation.

    J. Ufer Ground (Concrete-Encased Grounding Electrode): Fabricate according to NFPA 70; use a minimum of 20 feet (6 m) of bare copper conductor not smaller than No. 4 AWG.

    1. If concrete foundation is less than 20 feet (6 m) long, coil excess conductor within base of foundation.

    2. Bond grounding conductor to reinforcing steel in at least four locations and to anchor bolts. Extend grounding conductor below grade and connect to building's grounding grid or to grounding electrode external to concrete.

    3.6 LABELING

    A. Comply with requirements in Division 26 Section "Identification for Electrical Systems" Article for instruction signs. The label or its text shall be green.

  • PROJECT NAME CLEVELAND CLINIC JOB #

    FOR: ISSUED: 00/00/20XX

    GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 8

    3.7 FIELD QUALITY CONTROL

    A. Perform tests and inspections.

    1. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect components, assemblies, and equipment installations, including connections, and to assist in testing.

    B. Tests and Inspections:

    1. After installing grounding system but before permanent electrical circuits have been energized, test for compliance with requirements.

    2. Inspect physical and mechanical condition. Verify tightness of accessible, bolted, electrical connections with a calibrated torque wrench according to manufacturer's written instructions.

    3. Test completed grounding system at each location where a maximum ground-resistance level is specified, at service disconnect enclosure grounding terminal, at ground test wells, and at individual ground rods. Make tests at ground rods before any conductors are connected.

    a. Measure ground resistance no fewer than two full days after last trace of precipitation and without soil being moistened by any means other than natural drainage or seepage and without chemical treatment or other artificial means of reducing natural ground resistance.

    b. Perform tests by fall-of-potential method according to IEEE 81.

    4. Prepare dimensioned Drawings locating each test well, ground rod and ground-rod assembly, and other grounding electrodes. Identify each by letter in alphabetical order, and key to the record of tests and observations. Include the number of rods driven and their depth at each location, and include observations of weather and other phenomena that may affect test results. Describe measures taken to improve test results.

    C. Grounding system will be considered defective if it does not pass tests and inspections.

    D. Prepare test and inspection reports.

    E. Report measured ground resistances that exceed the following values:

    1. Power and Lighting Equipment or System with Capacity of 500 kVA and less: 10 ohms. 2. Power and Lighting Equipment or System with Capacity of 500 to 1000 kVA: 5 ohms. 3. Power and Lighting Equipment or System with Capacity More Than 1000 kVA: 3 ohms. 4. Power Distribution Units or Panelboards Serving Electronic Equipment: 1 ohm(s). 5. Substations and Pad-Mounted Equipment: 5 ohms. 6. Manhole Grounds: 10 ohms.

    F. Excessive Ground Resistance: If resistance to ground exceeds specified values, notify Engineer promptly and include recommendations to reduce ground resistance.

    END OF SECTION 260526

  • PROJECT NAME CLEVELAND CLINIC JOB #

    FOR: ISSUED: 00/00/20XX

    HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 1

    SECTION 260529 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

    PART 1 - GENERAL

    1.1 RELATED DOCUMENTS

    A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

    1.2 SUMMARY

    A. This Section includes the following:

    1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases.

    B. Related Sections include the following:

    1. Division 26 Section "Vibration and Seismic Controls for Electrical Systems" for products and installation requirements necessary for compliance with seismic criteria.

    1.3 DEFINITIONS

    A. EMT: Electrical metallic tubing.

    B. IMC: Intermediate metal conduit.

    C. RMC: Rigid metal conduit.

    1.4 PERFORMANCE REQUIREMENTS

    A. Design supports for multiple raceways capable of supporting combined weight of supported systems and its contents.

    B. Design equipment supports capable of supporting combined operating weight of supported equipment and connected systems and components.

    C. Rated Strength: Adequate in tension, shear, and pullout force to resist maximum loads calculated or imposed for this Project, with a minimum structural safety factor of five times the applied force.

    1.5 ACTION SUBMITTALS

    A. Product Data: For the following:

  • PROJECT NAME CLEVELAND CLINIC JOB #

    FOR: ISSUED: 00/00/20XX

    HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 2

    1. Steel slotted support systems. 2. Nonmetallic slotted support systems.

    B. Shop Drawings: Show fabrication and installation details and include calculations for the following:

    1. Trapeze hangers. Include Product Data for components. 2. Steel slotted channel systems. Include Product Data for components. 3. Nonmetallic slotted channel systems. Include Product Data for components. 4. Equipment supports.

    1.6 INFORMATIONAL SUBMITTALS

    A. Welding certificates.

    1.7 QUALITY ASSURANCE

    A. Welding: Qualify procedures and personnel according to AWS D1.1/D1.1M, "Structural Welding Code - Steel."

    B. All products shall be UL labeled for their intended use.

    C. Comply with NFPA 70.

    D. Comply with Cleveland Clinic Design Standards.

    1.8 COORDINATION

    A. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases. Concrete, reinforcement, and formwork requirements are specified in Division 03.

    B. Coordinate installation of roof curbs, equipment supports, and roof penetrations. These items are specified in Division 07 Sections.

    PART 2 - PRODUCTS

    2.1 SUPPORT, ANCHORAGE, AND ATTACHMENT COMPONENTS

    A. Steel Slotted Support Systems: Comply with MFMA-4, factory-fabricated components for field assembly. 1. Manufacturers: Subject to compliance with requirements, provide products by one of the

    following:

    a. Allied Tube & Conduit. b. Cooper B-Line, Inc.; a division of Cooper Industries. c. ERICO International Corporation.

  • PROJECT NAME CLEVELAND CLINIC JOB #

    FOR: ISSUED: 00/00/20XX

    HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 3

    d. GS Metals Corp. e. Thomas & Betts Corporation. f. Unistrut; Tyco International, Ltd.

    2. Metallic Coatings: Hot-dip galvanized after fabrication and applied according to MFMA-4.

    3. Nonmetallic Coatings: Manufacturer's standard PVC, polyurethane, or polyester coating applied according to MFMA-4.

    4. Painted Coatings: Manufacturer's standard painted coating applied according to MFMA-4.

    5. Channel Dimensions: Selected for applicable load criteria.

    B. Nonmetallic Slotted Support Systems: Structural-grade, factory-formed, glass-fiber-resin channels and angles with 9/16-inch- (14-mm-) diameter holes at a maximum of 8 inches (200 mm) o.c., in at least 1 surface. 1. Manufacturers: Subject to compliance with requirements, provide products by one of the

    following:

    a. Allied Tube & Conduit. b. Cooper B-Line, Inc.; a division of Cooper Industries.

    2. Fittings and Accessories: Products of channel and angle manufacturer and designed for use with those items.

    3. Fitting and Accessory Materials: Same as channels and angles, except metal items may be stainless steel.

    4. Rated Strength: Selected to suit applicable load criteria.

    C. Raceway and Cable Supports: As described in NECA 1 and NECA 101.

    D. Conduit and Cable Support Devices: Steel and malleable-iron hangers, clamps, and associated fittings, designed for types and sizes of raceway or cable to be supported.

    E. Support for Conductors in Vertical Conduit: Factory-fabricated assembly consisting of threaded body and insulating wedging plug or plugs for non-armored electrical conductors or cables in riser conduits. Plugs shall have number, size, and shape of conductor gripping pieces as required to suit individual conductors or cables supported. Body shall be malleable iron.

    F. Structural Steel for Fabricated Supports and Restraints: ASTM A 36/A 36M, steel plates, shapes, and bars; black and galvanized.

    G. Mounting, Anchoring, and Attachment Components: Items for fastening electrical items or their supports to building surfaces include the following:

    1. Powder-Actuated Fasteners: Threaded-steel stud, for use in hardened Portland cement concrete, steel, or wood, with tension, shear, and pullout capacities appropriate for supported loads and building materials where used. a. Manufacturers: Subject to compliance with requirements, provide products by one

    of the following:

    1) Hilti Inc. 2) ITW Ramset/Red Head; a division of Illinois Tool Works, Inc.

  • PROJECT NAME CLEVELAND CLINIC JOB #

    FOR: ISSUED: 00/00/20XX

    HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 4

    3) MKT Fastening, LLC. 4) Simpson Strong-Tie Co., Inc.; Masterset Fastening Systems Unit.

    2. Mechanical-Expansion Anchors: Insert-wedge-type, stainless steel, for use in hardened Portland cement concrete with tension, shear, and pullout capacities appropriate for supported loads and building materials in which used. a. Manufacturers: Subject to compliance with requirements, provide products by one

    of the following:

    1) Cooper B-Line, Inc.; a division of Cooper Industries. 2) Empire Tool and Manufacturing Co., Inc. 3) Hilti Inc. 4) ITW Ramset/Red Head; a division of Illinois Tool Works, Inc. 5) MKT Fastening, LLC.

    3. Concrete Inserts: Steel or malleable-iron, slotted support system units similar to MSS Type 18; complying with MFMA-4 or MSS SP-58.

    4. Clamps for Attachment to Steel Structural Elements: MSS SP-58, type suitable for attached structural element.

    5. Through Bolts: Structural type, hex head, and high strength. Comply with ASTM A 325.

    6. Toggle Bolts: All-steel springhead type. 7. Hanger Rods: Threaded steel.

    2.2 FABRICATED METAL EQUIPMENT SUPPORT ASSEMBLIES

    A. Description: Welded or bolted, structural-steel shapes, shop or field fabricated to fit dimensions of supported equipment.

    B. Materials: Comply with requirements in Division 05 Sections for steel shapes and plates.

    PART 3 - EXECUTION

    3.1 APPLICATION

    A. Comply with NECA 1 and NECA 101 for application of hangers and supports for electrical equipment and systems except if requirements in this Section are stricter.

    B. Maximum Support Spacing and Minimum Hanger Rod Size for Raceway: Space supports for EMT, IMC, and RMC as required by NFPA 70. Minimum rod size shall be 1/4 inch (6 mm) in diameter.

    C. Multiple Raceways or Cables: Install trapeze-type supports fabricated with steel slotted support system, sized so capacity can be increased by at least 25 percent in future without exceeding specified design load limits.

    1. Secure raceways and cables to these supports with single-bolt conduit clamps or single-bolt conduit clamps using spring friction action for retention in support channel.

  • PROJECT NAME CLEVELAND CLINIC JOB #

    FOR: ISSUED: 00/00/20XX

    HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 5

    D. Spring-steel clamps designed for supporting single conduits without bolts may be used for 1-1/2-inch (38-mm) and smaller raceways serving branch circuits and communication systems above suspended ceilings and for fastening raceways to trapeze supports.

    E. Fire pump feeders that are run exposed shall have conduit supported every five feet from a two hour rated structure with UL listed components.

    3.2 SUPPORT INSTALLATION

    A. Comply with NECA 1 and NECA 101 for installation requirements except as specified in this Article.

    B. Raceway Support Methods: In addition to methods described in NECA 1, EMT, IMC, and RMC may be supported by openings through structure members, as permitted in NFPA 70.

    C. Strength of Support Assemblies: Where not indicated, select sizes of components so strength will be adequate to carry present and future static loads within specified loading limits. Minimum static design load used for strength determination shall be weight of supported components plus 200 lb (90 kg).

    D. Mounting and Anchorage of Surface-Mounted Equipment and Components: Anchor and fasten electrical items and their supports to building structural elements by the following methods unless otherwise indicated by code:

    1. To Wood: Fasten with lag screws or through bolts. 2. To New Concrete: Bolt to concrete inserts. 3. To Masonry: Approved toggle-type bolts on hollow masonry units and expansion anchor

    fasteners on solid masonry units. 4. To Existing Concrete: Expansion anchor fasteners. 5. Instead of expansion anchors, powder-actuated driven threaded studs provided with lock

    washers and nuts may be used in existing standard-weight concrete 4 inches (100 mm) thick or greater. Do not use for anchorage to lightweight-aggregate concrete or for slabs less than 4 inches (100 mm) thick.

    6. To Steel: Beam clamps (MSS Type 19, 21, 23, 25, or 27) complying with MSS SP-69. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow Walls and Nonstructural Building Surfaces: Mount cabinets,

    panelboards, disconnect switches, control enclosures, pull and junction boxes, transformers, and other devices on slotted-channel racks attached to substrate[ by means that meet seismic-restraint strength and anchorage requirements].

    E. Drill holes for expansion anchors in concrete at locations and to depths that avoid reinforcing bars.

    3.3 INSTALLATION OF FABRICATED METAL SUPPORTS

    A. Comply with installation requirements in Division 05 Sections for site-fabricated metal supports.

  • PROJECT NAME CLEVELAND CLINIC JOB #

    FOR: ISSUED: 00/00/20XX

    HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 6

    B. Cut, fit, and place miscellaneous metal supports accurately in location, alignment, and elevation to support and anchor electrical materials and equipment.

    C. Field Welding: Comply with AWS D1.1/D1.1M.

    3.4 CONCRETE BASES

    A. Construct concrete bases of dimensions indicated but not less than 4 inches (100 mm) larger in both directions than supported unit and four inches high, and so anchors will be a minimum of 10 bolt diameters from edge of the base. Edges shall be chamfered.

    B. Use 3000-psi (20.7-MPa) 28-day compressive-strength concrete. Concrete materials, reinforcement, and placement requirements are specified in Division 03 Concrete Sections.

    C. Install dowel rods to connect concrete bases to concrete floor. Unless otherwise indicated, install dowel rods on 18-inch (450-mm) centers around full perimeter of base.

    D. Anchor equipment to concrete base.

    1. Place and secure anchorage devices. Use supported equipment manufacturer's setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded.

    2. Install anchor bolts to elevations required for proper attachment to supported equipment. 3. Install anchor bolts according to anchor-bolt manufacturer's written instructions.

    3.5 PAINTING

    A. Touchup: Clean field welds and abraded areas of shop paint. Paint exposed areas immediately after erecting hangers and supports. Use same materials as used for shop painting. Comply with SSPC-PA 1 requirements for touching up field-painted surfaces.

    1. Apply paint by brush or spray to provide minimum dry film thickness of 2.0 mils (0.05 mm).

    B. Touchup: Comply with requirements in Division 09 Painting Sections for cleaning and touchup painting of field welds, bolted connections, and abraded areas of shop paint on miscellaneous metal.

    C. Galvanized Surfaces: Clean welds, bolted connections, and abraded areas and apply galvanizing-repair paint to comply with ASTM A-780.

    END OF SECTION 260529

  • PROJECT NAME CLEVELAND CLINIC JOB #

    FOR: ISSUED: 00/00/20XX

    RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533 - 1

    SECTION 260533 - RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS

    PART 1 - GENERAL

    1.1 RELATED DOCUMENTS

    A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

    B. Cleveland Clinic ITD Standards for raceways and cable trays for Telecommunications cabling.

    1.2 SUMMARY

    A. Section Includes:

    1. Metal conduits, tubing, and fittings. 2. Nonmetal conduits, tubing, and fittings. 3. Metal wireways and auxiliary gutters. 4. Nonmetal wireways and auxiliary gutters. 5. Surface raceways. 6. Poke Thru Assemblies. 7. Trench Duct. 8. Boxes, floor boxes, enclosures, and cabinets.

    B. Related Requirements:

    1. Division 26 Section "Underground Ducts and Raceways for Electrical Systems" for exterior ductbanks, manholes, and underground utility construction.

    2. Cleveland Clinic ITD Standards for pathways for Electronic Safety, Communications and Security Systems.

    1.3 DEFINITIONS

    A. ARC: Aluminum rigid conduit.

    B. GRC: Galvanized rigid steel conduit.

    C. IMC: Intermediate metal conduit.

    1.4 ACTION SUBMITTALS

    A. Product Data: For surface raceways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets.

    B. LEED Submittals:

  • PROJECT NAME CLEVELAND CLINIC JOB #

    FOR: ISSUED: 00/00/20XX

    RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533 - 2

    1. Product Data for Credit IEQ 4.1: For solvent cements and adhesive primers, documentation including printed statement of VOC content.

    2. Laboratory Test Reports for Credit IEQ 4: For solvent cements and adhesive primers, documentation indicating that products comply with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers."

    C. Shop Drawings: For custom enclosures and cabinets. Include plans, elevations, sections, and attachment details.

    1.5 PERFORMANCE REQUIREMENTS [WHERE REQUIRED BY PROJECT CONDITIONS]

    A. [Seismic Qualification Certificates: For enclosures, cabinets, and conduit racks and their mounting provisions, include those for internal components, from manufacturer.

    1. Basis for Certification: Indicate whether withstand certification is based on actual test of assembled components or on calculation.

    2. Dimensioned Outline Drawings of Equipment Unit: Identify center of gravity and locate and describe mounting and anchorage provisions.

    3. Detailed description of equipment anchorage devices on which the certification is based and their installation requirements.

    4. Detailed description of conduit support devices and interconnections on which the certification is based and their installation requirements.]

    1.6 QUALITY ASSURANCE

    A. All products shall be UL labeled for their intended use.

    B. Comply with NFPA 70.

    C. Comply with NFPA 99.

    D. Comply with Cleveland Clinic Design Standards.

    1.7 INFORMATIONAL SUBMITTALS

    A. Coordination Drawings: Conduit routing plans, drawn to scale, on which the following items are shown and coordinated with each other, using input from installers of items involved:

    1. Structural members in paths of conduit groups with common supports. 2. HVAC and plumbing items and architectural features in paths of conduit groups with

    common supports.

    B. Source quality-control reports.

  • PROJECT NAME CLEVELAND CLINIC JOB #

    FOR: ISSUED: 00/00/20XX

    RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533 - 3

    PART 2 - PRODUCTS

    2.1 METAL CONDUITS, TUBING, AND FITTINGS

    A. Manufacturers: Subject to compliance with requirements, products of all manufacturers are acceptable provided they have a smooth interior, are UL listed and labeled as defined in NFPA 70 for the intended location and application and are electro-galvanized steel (EMT) or hot dipped galvanized steel inside and out (GRC). Conduit and fittings shall be obtained from the same manufacturer:

    B. GRC: Comply with ANSI C80.1 and UL 6.

    C. ARC: Comply with ANSI C80.5 and UL 6A.

    D. IMC: Comply with ANSI C80.6 and UL 1242.

    E. EMT: Comply with ANSI C80.3 and UL 797.

    F. FMC: Comply with UL 1; zinc-coated steel.

    G. LFMC: Flexible steel conduit with PVC jacket and complying with UL 360.

    H. Multi-conductor Cable type MC and AC: Use of MC or medical grade AC cable is not permitted under any circumstances unless specifically approved in writing by the Senior Director of Facilities.

    I. Electrical nonmetallic tubing (ENT or blue tube) and liquid-tight flexible nonmetallic conduit (LFNC) are not acceptable for use on any Project.

    J. Fittings for Metal Conduit: Comply with NEMA FB 1 and UL 514B.

    1. Conduit Fittings for Hazardous (Classified) Locations: Comply with UL 886 and NFPA 70.

    2. Fittings for EMT:

    a. Material: Steel. b. Type: Set Screw indoors; compression - outdoors.

    3. Expansion Fittings: PVC or steel to match conduit type, complying with UL 651, rated for environmental conditions where installed, and including flexible external bonding jumper.

    K. Joint Compound for IMC, ARC, or GRC: Approved, as defined in NFPA 70, by authorities having jurisdiction for use in conduit assemblies, and compounded for use to lubricate and protect threaded conduit joints from corrosion and to enhance their conductivity.

  • PROJECT NAME CLEVELAND CLINIC JOB #

    FOR: ISSUED: 00/00/20XX

    RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533 - 4

    2.2 NONMETALLIC CONDUITS AND FITTINGS

    A. Manufacturers: Subject to compliance with requirements, products of all manufacturers are acceptable provided they are sunlight resistant and UL listed and labeled as defined in NFPA 70 and marked for intended location and application. Conduit and fittings shall be obtained from the same manufacturer.

    B. RNC: Type EPC-40-PVC, complying with NEMA TC 2 and UL 651 unless otherwise indicated.

    C. Fittings for RNC: Comply with NEMA TC 3; match to conduit or tubing type and material.

    D. Solvent cements and adhesive primers shall have a VOC content of 510 and 550 g/L or less, respectively, when calculated according to 40 CFR 59, Subpart D (EPA Method 24).

    E. Solvent cements and adhesive primers shall comply with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers."

    2.3 METAL WIREWAYS AND AUXILIARY GUTTERS

    A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

    1. Cooper B-Line, Inc. 2. Hoffman; a Pentair company. 3. Square D; a brand of Schneider Electric.

    B. Description: Sheet metal, complying with UL 870 and NEMA 250, Type 1 unless otherwise indicated, and sized according to NFPA 70.

    1. Metal wireways installed outdoors shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

    C. Fittings and Accessories: Include covers, couplings, offsets, elbows, expansion joints, adapters, hold-down straps, end caps, and other fittings to match and mate with wireways as required for complete system.

    D. Wireway Covers: Screw-cover type unless otherwise indicated.

    E. Finish: Manufacturer's standard enamel finish.

    2.4 NONMETALLIC WIREWAYS AND AUXILIARY GUTTERS

    A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Hoffman; a Pentair company. 2. Lamson & Sessions; Carlon Electrical Products.

  • PROJECT NAME CLEVELAND CLINIC JOB #

    FOR: ISSUED: 00/00/20XX

    RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533 - 5

    B. Listing and Labeling: Nonmetallic wireways and auxiliary gutters shall be UL listed and labeled as defined in NFPA 70 and marked for intended location and application.

    C. Description: PVC, extruded and fabricated to required size and shape, and having snap-on cover, mechanically coupled connections, and plastic fasteners.

    D. Fittings and Accessories: Couplings, offsets, elbows, expansion joints, adapters, hold-down straps, end caps, and other fittings shall match and mate with wireways as required for complete system.

    E. Solvent cements and adhesive primers shall have a VOC content of 510 and 550 g/L or less, respectively, when calculated according to 40 CFR 59, Subpart D (EPA Method 24).

    F. Solvent cements and adhesive primers shall comply with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers."

    2.5 SURFACE RACEWAYS

    A. Listing and Labeling: Surface raceways shall be UL listed and labeled as defined in NFPA 70 and marked for intended location and application.

    B. Surface Metal Raceways: Galvanized steel with snap-on covers complying with UL 5. Manufacturer's standard enamel finish in color selected by Architect. Provide dividers as required to separate systems of different voltages.

    1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. Panduit Corp. b. Wiremold / Legrand.

    C. Surface Nonmetallic Raceways: Two- or three-piece construction, complying with UL 5A, and manufactured of rigid PVC with texture and color selected by Architect from manufacturer's standard colors. Product shall comply with UL 94 V-0 requirements for self-extinguishing characteristics. Provide dividers as required to separate systems of different voltages.

    1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

    a. Hubbell Incorporated; Wiring Device-Kellems Division. b. Panduit Corp. c. Wiremold / Legrand.

    2.6 MEDICAL GRADE TRENCH DUCT

    A. Trench-type medical grade, under floor raceways used for routing of power, data, and signal cables in CT, X Ray, MRI rooms and similar rooms.

  • PROJECT NAME CLEVELAND CLINIC JOB #

    FOR: ISSUED: 00/00/20XX

    RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533 - 6

    B. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Square D; Schneider Electric. 2. Thomas & Betts Corporation; Steel City Division. 3. Raceway Solutions, Inc. 4. Walker Systems, Inc.; a Wiremold company.

    C. Trench: Include the following features: 1. UL listed. 2. Galvanized steel, 14 gauge factory welded. 3. Non-Ferrous Metal Raceways for use in MRI scan rooms or similar: Aluminum. 4. Slab Depth Adjustment: Minimum of minus 1/8 inch (3 mm) to plus 5/8 inch (16 mm)

    before and during concrete placement. 5. Cover Supports: Height adjustable, with leveling screws to rigidly support cover

    assembly. 6. Screed Strip: Extruded aluminum along both edges at proper elevation without requiring

    shim material. 7. Trim Strip: Select to accommodate floor finish material. 8. Partitions: Arranged to separate channels and isolate wiring of different systems. 9. Grommeted openings in service raceways. 10. Manufacturer's standard corrosion-resistant finish, applied after fabrication.

    D. Cover Plates: Removable, steel plates, 1/4 inch (6 mm) thick, with full gasket attached to side units. Fabricate covers with appropriate depth recess to receive indicated floor finish.

    E. Dimensions: coordinate with Medical Equipment Suppliers approved site installation drawings.

    2.7 POKE THRU ASSEMBLIES

    A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

    1. Hubbell Incorporated; Wiring Device-Kellems. 2. Pass & Seymour/Legrand; Wiring Devices & Accessories. 3. Thomas & Betts Corporation. 4. Wiremold Company (The).

    B. Poke-Thru Assemblies: 1. Factory-fabricated and -wired assembly of below-floor junction box with multi-

    channeled, through-floor raceway/firestop unit and detachable matching floor service outlet assemb