Upload
trinhtruc
View
254
Download
6
Embed Size (px)
Citation preview
Compact Medium Voltage SwitchgearMASCON S24
IS-VINAhttp://www.lsisvina.biz
Leading Innovation, Creating Tomorrow
Power Transmission & Distribution
COMPACT!
Height 13% reduction
width 52% reduction
Bottom 76% reduction
24kV-630A MESG 4 Panel
LBS MOF PT VCB
Installation space
LBS Measuring PT VCB
1135
MASCON S24
BASIC PANELCLASSIFY MASCON S24
FLOOR AREA
WIDTH
HIGHT
DEPTH
With the 24% reduced compact size of the panels, MASCON S24 can be transported in the apartment elevators and makes light and easy installation possible at site with powerful 25kA.
Class ClassSpecification Specification
LSIS-VINA Co., Ltd.
Rated voltage [kV]Rated current [A]
Rated short time current [kA]Rated frequency [Hz]
Lightning Impulse Withstand [BIL]
25/62.5
Power Frequency Withstand Voltage [kV]Degree of Protection
Operation Invironment Ambient
Humidity
Altitude
Design Concept:
Product Characteristics::- MASCSCONON SS2424 iis an air-insulated Metal Enclosed SwitchGear. - MASCON S24 guarantees safe usage for environment.- MASCON S24 saves space for sub-stations.
24
630
50
50
125
LV DOOR : IP 3X ; OTHER : IP4X
< 1000m Sea Level-5 ~45 Co
95%
(24%)
(48%)
(87%)
(43%)
2.8m
2500
2040
1085
2500
57% reduction in depth
LSIS-VINA Co., Ltd.
With digital know-how, LSIS-VINA provides future technology in electricalequipment field for the customer’s satisfaction.
Application:
Compact Medium Voltage SwitchgearMASCON S24
LSIS-VINA Co., Ltd.
VCB OUTGOING FUSE
MASCON S24 CONTRUCTION:
Insulator Power FuseEarthing switchVCB
BUSBAR LBS
Busbar Compartment:The busbar compartment is located on top of the cubicle. It contains the main busbar that interconnect between cubicles.
Mechanism and Low Voltage Compartment:Mechanism and low voltage compartment is seperated from other compartment for easy maintenance and repair.
Cable Compartment:Power cables are making it possible to use 1-3 phase cables with simple unscreened termination.
Load Break S/W :Brand new epoxy housing is applied. It is 3position(On-Off -Earth) and insulated by SF6 Gas.SF6 Gas Pressure indicator install in front face for visual checking including pressure low alarm contact.
Main Configuration:
Compact Medium Voltage SwitchgearMASCON S24
LSIS-VINA Co., Ltd.
LBS MEASURING PT VCB MAINVCB OUTGOING FUSE OUTGOING
TLS/1
NAME
CUBICLETYPE TME/2 TME/2A TVB/3 TVB/3BTLF/4
2040 2040 2040 204020402040
1085 1085 1085108510851085
500 750 500 750 750500
TLS/1
Compact Medium Voltage SwitchgearMASCON S24
LSIS-VINA Co., Ltd.
CUBICLE TYPE:
Load Break S/W Cubicle (TLS)
(Width 500 Hight 2040)
6
TLS/1
LBS (manual)
OPTION NAME
DESCRIPTION
SINGLE LINE
TLS/1A
LBS (motor)
TLS/1B
LBS (manual)+CT
TLS/1C
LBS main or Section
(W=750mm)
M
Compact Medium Voltage SwitchgearMASCON S24
LSIS-VINA Co., Ltd.
CUBICLE TYPE:
7
TME/2
CT/PT for Measuring
OPTION NAME
DESCRIPTION
SINGLE LINE
TME/2A
PT for Busbar
TME/2B
LBS +PT for Busbar
Measuring with CT & PT Cubicle (TME)
(Width 750 Hight 2040)
TME/2
(Width 750 Hight 2040)
(W=500mm)(W=750mm) (W=500mm)
Compact Medium Voltage SwitchgearMASCON S24
LSIS-VINA Co., Ltd.
CUBICLE TYPE:
Circuit Breaker Cubicle (TVB)
8
(Width 750 Hight 2040)
TVB/3
LBS (motor)+VCB+CT+E/S LBS (motor)+VCB+CT LBS (motor)+VCB+CT
OPTION NAME
DESCRIPTION
SINGLE LINE
TVB/3A TVB/3B
M M
M
TVB/3
M
TLF/4
Compact Medium Voltage SwitchgearMASCON S24
LSIS-VINA Co., Ltd.
CUBICLE TYPE:
(Width 500 Hight 2040)
9
Fuse Combination Load Break Cubicle (TLF)
TLF/4 TLF/4A TLF/4B TLF/4C
LBS (manual)+Fuse+E/S
OPTION NAME
DESCRIPTION
SINGLE LINE
LBS (manual)+CT+Fuse+E/S
LBS (manual)+Fuse LBS (manual)+Fuse
(W=750mm)
Compact Medium Voltage SwitchgearMASCON S24
LSIS-VINA Co., Ltd.
CUBICLE TYPE :
Bus Riser & Connection Cubicle (TLB)
(Width 500 Hight 2040)
10
TLB/5
TLB/5
Busbar+Insulator Busbar+InsulatorBusbar+Insulator+CT
OPTION NAME
DESCRIPTION
SINGLE LINE
TLB/5A TLB/5B
Compact Medium Voltage SwitchgearMASCON S24
LSIS-VINA Co., Ltd.
INSTALLATION CUBICLE DIMENTIONS:
11
This dimention is used in cubicle withoutcircuit breaker and without arc gas channel
TLSApplied Cubicle :
TLFTMETLB
This dimention is used in cubicle withcircuit breaker and without arc gas channel
TVB/3Applied Cubicle :
TVB/3ATVB/3B
Optional forinstalling protection relay
Optional forinstalling protection relay
Compact Medium Voltage SwitchgearMASCON S24
MAIN EQUIPMENTS :Epoxy housing Load Breaker Switch
Side Mounting Circuit BreakerThe vacuum circuit breaker Pro-MEC Side mounting VCB has been specially designed for LS Mascon S24 MVSG.The switching capacity is sufficient for any conditions arising from switching of the equipment as well as from systemcomponents under normal operating and fault conditions.
SM - VCB Specifications:Voltage [kV]Rated current [A]
Rated short time current [kA]Rated frequency [Hz]
Rated Impulse Voltage [BIL]Rated short-Making current [kA]
Power Frequency Withstand Voltage [kV]
Voltage [kV]Ratio (1’ry/2’ry)
Rated short time current [kA]Rated frequency [Hz]
Rated Impulse Voltage [BIL]Rated short-Making current [kA]
Power Frequency Withstand Voltage [kV]
CT Specifications:
Current Transformer
Potential Transformer
LSIS-VINA Co., Ltd.
This current transformer can be used with electronic relays according to the class and burden below. These datas only describe our basic type. Other types are available upon request. It can be installed with capacitive voltage indication device.
This voltage transformer can be use with lectronic relays according to the class and burden below. These datas only describe our basic type. Other types are available upon request.
Load Breaker Switch Specifications:Voltage [kV]Rated current [A]
Rated short time current [kA]Rated frequency [Hz]
Rated Impulse Voltage [BIL]Rated short-Making current [kA]
Power Frequency Withstand Voltage [kV]
The switch-disconnector has 3 positions (On-Off-Earth) is using SF6 as extinguishing arc and insulation.
24630
12550
25kA/1s50
62.5Control Voltage DC110V (Standard)
Control Voltage DC110V (Standard)
SM VCB
CT
PT
24630
12550
25kA/3s50
62.5
24Up to 600A/1 or 5A
12550
25kA/1s50
62.5Class 0.5, 1.0 / 5P10, 5P20Burden 5/10/15/30VA
Voltage [kV]Voltage Factor
Voltage Ratio [V]Rated frequency [Hz]
Rated Impulse Voltage [BIL]
PT Specifications:24
1.2cont 1.5 /30sec or 1.9/8 Hr (Max)
12522/√3/110/√3 (22/√3/190/√3) or as Requirement
50
12
LBS
Class 0.2, 0.5, 1.0 / 3P, 6PBurden 30~200 VA
Compact Medium Voltage SwitchgearMASCON S24
MAIN EQUIPMENTS :
LSIS-VINA Co., Ltd.
Power Fuse (DIN Type Power Fuse)The LS HRC Power Fuses belong to the PRIME MEC series. It interrupts high currents before the first loop of fault currenthas reached its natural peak value and therefore cuts down the required withstand capacity of the associated equipment on the electric system.
Power Fuse Selection Table:
Power Fuse rated current [A] Transformer capacity [kVA]Power Fuse rated Voltage [KV]
Monitoring and Protection Devices (Integrated Protection and Metering Equipment)Instrumentation and protective relaying functions into one converged, complex digital power monitoring device protection.
GIMAC-II
GIPAM 115FL GIPAM 2000
Main Feature Main Function∙ Protective relaying elements: OCR, OCGR, OVR, UVR, SGR, OVGR, POR of the seven kinds of protective factors
∙ Measuring element: 3-phase / seonganjeopap, three-phase current, video-voltage, active / reactive power, active / reactive power, power factor, Frequency measurement, including nine kinds of
∙ Accident records and self-diagnostic capabilities
∙ Control features: Circuit Breaker On / Off Control and Local / Remote switch available
∙ Communication features: I-NET, MODBUS communication available by the high-speed communication
13
DPR
Compact Medium Voltage SwitchgearMASCON S24
LSIS-VINA Co., Ltd.
Order information
14
L0 Without LBSL1 Manual type
L2 Motor typeDC110V
L3 Motor typeDC24V
L4 Motor typeAC220V
LBSCubicle TypeTLS/1TME/2TVB/3
…
R0 Without RelayR1 GIPAM 115R2 GIPAM 2200R3 Other RelayM1 GIMACM2 Other Meter
Protection Relay& Meter
A0 None LAA1 Installation LAS0 None SAS1 Installation SA
LA & SAT0 None LAT1 Installation
CT
Inform us detailspec. of CT asattached sheet
E0 None LAE1 Installation
Earthing switch E/S
C0 NoneC1 Installation
Capacity VoltageIndicator
0 : Basic & Standard specification , ▲ : Optional specification
Main Equipment
Cubicle Type BusbarInsulation Supporter
Motor Type
Manual Type
No Installation
Protection Relay
LV Components
Capacitive Voltage
Indicator
SM VCB
LAMeasuring
CT&PT
DIN Type Fuse
PT CT SAEarthing Switch
TLS/1 0 0 0 0 ▲ ▲ Incoming or Outgoing
TLS/1A 0 0 0 0 ▲ ▲ Incoming or OutgoingTLS/1B 0 ▲ 0 ▲ 0 ▲ ▲ ▲ Outgoing
TLS/1C 0 0 0 ▲ ▲ 0 ▲ ▲ Main or Section
TME/2 0 0 ▲ 0 0 Measuring CT & PT
TME/2A 0 0 ▲ ▲ 0 0 0 Busbar PT
TME/2B 0 ▲ ▲ ▲ 0 0 0 Busbar PT
TVB/3 0 0 0 ▲ ▲ 0 ▲ 0 0 ▲ ▲ Outgoing
TVB/3A 0 0 0 ▲ ▲ 0 ▲ 0 0 ▲ ▲ Outgoing
TVB/3B 0 0 0 ▲ ▲ 0 ▲ 0 ▲ Main or Section
TLF/4 0 0 ▲ 0 0 ▲ 0 ▲ ▲ Outgoing
TLF/4A 0 0 ▲ 0 0 ▲ 0 ▲ ▲ OutgoingTLF/4B 0 0 ▲ 0 ▲ 0 ▲ 0 ▲ ▲ ▲ Outgoing
TLF/4C 0 0 0 ▲ 0 0 Main or Section
TLB/5 0 0 ▲ Bus Riser
TLB/5A 0 0 ▲ ▲ 0 ▲ Bus Riser
TLB/5B 0 0 ▲ ▲ ▲ Cable Connection
LBS Cubicle
Measuring Cubicle
Service
VCB Cubicle
LBS & Fuse Cubicle
Others
Busbar Compartment LBS LV Compartment VCB & Cable Compartment
Compact Medium Voltage SwitchgearMASCON S24
LSIS-VINA Co., Ltd. 15
Leading Innovation, Creating Tomorrow
http://www.lsisvina.biz
MASCON S24 Medium Voltage Switchgear 2011.10(V1) Printed in Viet Nam
“Specification and Dimension in this catalog are subject to change without notice to continuous products development and improvement”
LSIS-VINA Co., Ltd.
■ HEAD OFFICENguyen Khe - Dong Anh - Ha Noi - Viet Nam,Tel. (+84-4) 38820222Fax. (+84-4) 38820220http://www.lsisvina.bizEmail: [email protected]
■ HA NOI OFFICE13th Floor - M3M4 Office Centre91 Nguyen Chi Thanh Str. Dong Da - Ha Noi - Viet Nam,Tel. (+84-4) 62758055 Fax. (+84-4) 62758056Email: [email protected]
■ HO CHI MINH OFFICE7th Floor - Yoco Building41 Nguyen Thi Minh Khai Str. District No.1Ho Chi Minh City - Viet Nam,Tel. (+84-8) 38227941 Fax. (+84-8) 38227942Email: [email protected]
© LSIS-VINA Co., Ltd. All rights reserved
220/110KV SUBSTATION• Consultation• Supply Equipments• Installation• Maintenance
EQUIPMENTS AND BUSWAYS• SF6 Insulated LBS (GLBS)• LS Cast Resin Transformer (M-TR)• Busways system
MEDIUM VOLTAGE SWITCHGEAR • Indoor and Outdoor Kiosks• MCSG 40.5KV, 24KV,12KV, 7.2KV, 3.3KV• MESG 24KV,12KV, 7.2KV, 3.3KV• Outdoor switchgear• Ring Main Unit (RMU)• Mascon S24, Mascon S12
LOW VOLTAGE SWITCHGEAR• LV up to 6300A (indoor or outdoor)• Control & Protection (CP-RP)• Motor Control Center (MCC)• Marine Switchboard (MSB)• DB : Indoor or outdoor• AC-DC
POWER & CONTROL DEVICES • VCB, VCS, ACB, MCCB, ELCB, MCB, CONTACTORS...• Digital Integrated Monitoring & Protection Device (GIPAM, GIMAC, DPR...)• Intelligent Building Management System (IBS)