LIGHTING CONTROLSMANUAL TIME SWITCHES93000, TS-200 SERIES
2004 KELE CATALOG • www.kele.com • USA 888-397-5353 • International 901-382-6084380
DESCRIPTIONThe Marktime 93000 Series Wall-Box Manual Time Switchis a spring-wound, manually set time switch for the control ofelectrical current. Interchangeable with standard toggle switch-es to turn circuits either off or on at the end of a preset timeperiod, the 93000 Series is ideally suited for new installationsor retrofit projects.
FEATURES
• White and ivory plates and knobs included with each time switch
• Time ranges from minutes to 12 hours, all with ±5%accuracy
• Easy-to-install two-wire design to fit into standardsingle-gang wall box
• Heavy motor loads without the need of contactors• Rotary knob operation• Available to turn circuits off or on, with or
without manual hold override feature• UL listed, CUL
DESCRIPTION
The Watt Stopper® InteliSwitch® TS-200 Series is a digitaltime switch that automatically turns the load off after a presetamount of time. The load can be turned off anytime during thetimer's countdown by pushing the on/off button. The TS-200Series has four user-adjustable features:
Time-Out DelayThe timer can be adjusted to hold the load from five minutesto 12 hours. This is adjusted by setting the DIP switch locatedon the left side of the unit.Time ScrollingIn situations where the load needs to be held on for a differentamount of time than the preset time-out period, time scrollingallows the user to manually and temporarily override the time-out period without adjusting the DIP switch.Flash OptionIf this option is on, the load will flash once, one minute beforethe time-out period expires. Set this option on the DIP switch.Beeper OptionIf this option is on, the timer will beep every five seconds dur-ing the last minute of the time-out period. Set this option onthe DIP switch.
ORDERING INFORMATION
93000 SERIESELECTRICAL RATING20A 125 VAC 1 hp10A 277 VAC7A 125 VAC tungsten
MODELNo Hold Previous93501C (90005/90539)93502C (90006/90032)93503C (90008/90024)93504C (90281/90540)93505C (90007/90017)93506C (90001/90015)93507C (90240/90547)
DESCRIPTION
0-15 Min. N.O./N.C.0-30 Min. N.O./N.C.0-60 Min. N.O./N.C.0-120 Min. N.O./N.C.0-6 Hour N.O./N.C.0-12 Hour N.O./N.C.0-4 Hour N.O./N.C.
MODELWith Hold Previous93511C (90012/90543)93512C (90011/90037)93513C (90010/90038) 93515C (90017/90548)93516C (90015/90014)93517C (90542/90546)
DESCRIPTION
0-15 Min. N.O./N.C. (w/hold)0-30 Min. N.O./N.C. (w/hold)0-60 Min. N.O./N.C. (w/hold)
0-6 Hour N.O./N.C. (w/hold)0-12 Hour N.O./N.C. (w/hold)0-4 Hour N.O./N.C. (w/hold)
Weight: 0.4 lb (182g)
ORDERING INFORMATION TS-200 TS-200-24Voltage 120/277 VAC/60 Hz 24 VDC, 24 VAC/60 HzLoad rating 800W tungsten Isolated relay
or ballast @ 120 VAC SPDT, 1A @ 30V1200W ballast @ 277 VAC
Time adjust(both models) 5, 15, 30 min.; 1,3, 6, 9, 12 hr
SPECIFICATIONS
NeutralGroundGround (capped)(black) Hot
Load
(red)
(red)
(black)
+24 VDC or24 VAC 60Hz
Return
Isolated Relay
(green) Normally Closed(orange) Common(yellow) Normally Open
TS-200 TS-200-24
Important!
120 VAC Ground - Green277 VAC Ground - Green/Yellow
WIRING
MODEL DESCRIPTIONTS-400-W Digital Time Switch, 120/277 VACTS-400-24-W Digital Time Switch, 24 VAC/DC