Hardware and Engineering
CM4-505-GV1CM4-505-GV2AS-i/PROFIBUS-Gateways
Think future. Switch to green.
SystemsIndustrial AutomationBuilding Automation
AWB2700-1409GB 04/01
7/28/2019 Maquina_119_rob
2/78
7/28/2019 Maquina_119_rob
3/78
AS-i/PROFIBUS Gateway Table of Contents
Table of Contents
1 The Used Symbols ................................................
2 Safety .....................................................................2.1 Intended Use ...................................................................
2.2 General Safety Information ............................................
3 General Information ..............................................
4 Connections, Displays and Operating Keys .......4.1 Power Supply Concepts and AS-i Connection Techniq
4.1.1 Single Masters in IP65 ......................................................
4.1.2 Single Masters in IP20 with Power Supply A ....................
4.2 The PROFIBUS Interface ................................................
4.2.1 Devices in IP20 .................................................................
4.2.2 Devices in IP65 .................................................................
4.3 Display and Operating Elements ...................................
4.3.1 LEDs of the Single Masters ..............................................
5 Operating the AS-i/PROFIBUS Gateway .............
5.1 Master Start-Up ...............................................................5.2 Configuration Mode ........................................................
5.3 Protected Operating Mode .............................................
5.3.1 Switching to Protected Operating Mode ...........................
5.3.2 Configuration Errors in Protected Operating Mode ...........
5.4 Assigning an AS-i Address in Configuration Mode ....
5.4.1 Assigning a Slave Address ...............................................
5.4.2 Erasing the Slave Address ...............................................5.5 Programming the Address in Case of Configuration E
5.5.1 Automatic Address Assignment ........................................
5.5.2 Manual Address Assignment ............................................
5.6 Setting of the PROFIBUS Station Address ...................
5.6.1 PROFIBUS Station Address .............................................
7/28/2019 Maquina_119_rob
4/78
AS-i/PROFIBUS Gateway Table of Contents
7.3 Mailbox ............................................................................................
7.3.1 Construction .....................................................................................7.3.2 Mailbox commands ..........................................................................
7.3.3 Mailbox example ..............................................................................
8 Commissioning Tools and Accessories ...........................8.1 Windows Software AS-i Control Tools ........................................
8.2 PROFIBUS-DP master simulator ..................................................
8.3 Serial PROFIBUS Master ...............................................................
9 Appendix: Displays of the Figure Display ........................
10 Appendix: The First Commissioning of AS-i ...................
11 Appendix: Putting PROFIBUS into Operation with a Siem11.1 Putting into Operation in Easy Mode ...........................................
7/28/2019 Maquina_119_rob
5/78
AS-i/PROFIBUS Gateway The Used Symbols
1 The Used Symbols
This symbol warns the user of possible dang
warning can lead to personal injury or death a
ment.
This symbol warns the user of a possible failu
warning can lead to total failure of the equipm
nected equipment.
This symbol gives the user important hints.
7/28/2019 Maquina_119_rob
6/78
AS-i/PROFIBUS Gateway The Used Symbols
7/28/2019 Maquina_119_rob
7/78
AS-i/PROFIBUS Gateway Safety
2 Safety
2.1 Intended Use
2.2 General Safety Information
The protection of operating personnel and the
danger is not guaranteed if the control interfa
accordance with its intended use.
The device may only be operated by appropr
in accordance with this operating manual.
Safety and correct functioning of the device ca
operation other than that described in this op
formed.
The connecting of the equipment and any ma
ried out with voltage applied to the equipmen
by appropriately qualified electrotechnical pe
In the case that a failure cannot be repaired,
out of operation and kept from inadvertently p
Repair work is to be carried out by the manuf
modifications to the equipment are not allowe
The operator is responsible for the observanc
dards.
7/28/2019 Maquina_119_rob
8/78
AS-i/PROFIBUS Gateway Safety
7/28/2019 Maquina_119_rob
9/78
AS-i/PROFIBUS Gateway General Information
3 General Information
This operating instruction is for use with the following devi
AS-i/PROFIBUS-DP gateway power supply A
AS-i/PROFIBUS-DP gateway IP65 power supply A
The AS-i/PROFIBUS-Gateways serve to connect AS-Inter
PROFIBUS. They act as a Master for the AS-Interface andPROFIBUS.
New AS-i Specification 2.1
The AS-i/PROFIBUS-DP Gateways already fulfil the new A
means:
Up to 62 AS-Interface slaves can be connected per 1 A
The transfer of analog signals via AS-i is integrated in t
All further functions of the new specification as e.g. the
ripheral fault are implemented.
All AS-i functions are provided cyclically via PROFIBUS-D
PROFIBUS-DP V1.
In the cyclic data transfer optionally up to 32 bytes I/O dat
nary data of 1 AS-i network. Furthermore analog signals a
the new AS-i specification can be transferred in the managPROFIBUS.
The AS-i Control Tools can be used for the monitoring of t
PROFIBUS-DP V1.
Advanced Diagnostics
Diagnostics, which go far beyond the standard diagnostics
tion of the occassionally occuring configuration errors and
the AS-i communication. So in case of an error the down t
minimized or you can initiate preventive maintenance.
Two Sorts of Housing
The AS-i PROFIBUS Gateways with one Master can be d
bi t ti i fi ld h i i IP65 Th h dli
7/28/2019 Maquina_119_rob
10/78
AS-i/PROFIBUS Gateway General Information
Commissioning, debugging and setting up of the AS-i parameters w
ware can only be accomplished with the use of two push-buttons, theLEDs directly on the system.
Accessories
Software "AS-i Control Tools"
PROFIBUS-DP Master Simulator DP V1
D-Sub data transmission cord for AS-i masters in IP65
7/28/2019 Maquina_119_rob
11/78
AS-i/PROFIBUS Gateway Connections, Displays and Operating Keys
4 Connections, Displays and Operating Keys
Devices in IP20:
On the front panel of the AS-i/PROFIBUS gateways in IP2
terminals to connect the power supply and the AS-i circ
a 9-pin SUB-D connector as PROFIBUS interface
7 LEDs
a two-digit seven-segment display
2 push-buttons to configure the gateway
Devices in IP65:
7/28/2019 Maquina_119_rob
12/78
7/28/2019 Maquina_119_rob
13/78
AS-i/PROFIBUS Gateway Connections, Displays and Operating Keys
4.2 The PROFIBUS Interface
4.2.1 Devices in IP20
The PROFIBUS interface is realized as a 9-pin SUB-D co
the standard for PROFIBUS DIN 19245. It is placed on the
panel.
Connection samples for the AS-i power supp
In the w i r ing schemes above the cu rrent t
must n ot exceed 5 A.
-+
AS--+
-+
AS-i Master
max. 8 APELV according to EN 60950(Protective extra low voltage)
-power
supply
-
+
AS-i Slave-+
AS-i Slave-+
GND
54321
9876
RxD/TxD-P
(data line B)
RxD/TxD-N(data line A)
PROFIBUS
7/28/2019 Maquina_119_rob
14/78
AS-i/PROFIBUS Gateway Connections, Displays and Operating Keys
4.2.2 Devices in IP65
The AS-i/PROFIBUS gateway in IP65 can be connected to PROFIBclamp terminals inside of the device. For that purpose the top of the
be screwed off.
You can use a SUB-D data cable as an accessory part for AS-i maste
is led through the heavy gauge terminals and is connected after the
scheme:
3 - green, 4 - yellow, 5 - blue, 10 - red
The device in IP65 is powered out of the AS-i line to which it is conne
tromechanical interface (penetration technique as it is used with ASBus Termination
If the AS-i/PROFIBUS gateway is at the end of the PROFIBUS line, b
have to be switched on to terminate the bus with the built-in termina
If the gateway is not at the end of the line, swith off both DIP switch
4.3 Display and Operating Elements
On the front panel of the AS-i/PROFIBUS gateway are seven light-e
two-digit display and two push buttons.
With the devices in IP65 the push buttons are situated inside of the
liquids from entering. The top of the housing has to be screwed off t
Connection of PROFI-
BUS
interface on cage clamp
terminal block and
arrangement on circuit
board:
1 RxD/TxD-N (data line A)
2 RxD/TxD-P (data line B)
3 RxD/TxD-N (data line A)
4 RxD/TxD-P (data line B)
5 0 V
6 Shield7 FG function ground
8 FG function ground
9 Shield
10 +5 V
6
1
clam
but
7/28/2019 Maquina_119_rob
15/78
AS-i/PROFIBUS Gateway Connections, Displays and Operating Keys
This LED blinks if there is at least one
slave in the AS-i network. If there are cas periphery faults, only configuration
U ASI The AS-i circuit is sufficiently powere
ASI active Normal operation active.
(Blinks, if an B slave is displayed)
prg enable Automatic address programming ena
Exactly one slave is missing in protecslave can be replaced by another slav
dress zero. The master addresses the
dress and thus eliminates the configu
prj mode The AS-i master is in configuration m
7/28/2019 Maquina_119_rob
16/78
AS-i/PROFIBUS Gateway Connections, Displays and Operating Keys
7/28/2019 Maquina_119_rob
17/78
AS-i/PROFIBUS Gateway Operating the AS-i/PROFIBUS Gateway
5 Operating the AS-i/PROFIBUS Gateway
5.1 Master Start-Up
After powering on, all segments of the figure display and a
imately one second (self-test). Afterwards, the LEDs displ
spective flags. The figure display shows the condition of th
40 Off-line Phase
The AS-i master initializes - there is no data co
In configuration mode or when an AS-i Controlmatically the device can leave the off-line phas
In protected mode, if the PROFIBUS communi
AS-i master switches to the off-line phase after
PROFIBUS has expired unless an AS-i Contro
was started automatically.
41 Detection Phase
Start of the start-up phase, where the system lthe AS-i. The master remains in the detection p
one slave.
42 Activation Phase
Condition at the end of the start-up operation w
transmitted to all connected and recognized sla
to the AS-i slaves data connections.
431 Start of Normal Operation
In normal operation the AS-i master can excha
slaves. It transmits management messages an
newly connected slaves. During normal operat
maximum cycle time of 5 milliseconds.
I f the AS-i ci rcui t is in suf f ic ient
does not l ight up)or there is no
ship between the PROFIBUS ma
BUS gateway, the master remai
7/28/2019 Maquina_119_rob
18/78
AS-i/PROFIBUS Gateway Operating the AS-i/PROFIBUS Gateway
Pressing the mode button for at least five seconds switches the m
ration mode. While in configuration mode, the yellow prj mode LEDThe system then displays one after the other all detected slaves at a
second. First all "A" slaves and afterwards all "B" slaves. If the displ
slaves were detached on the AS-i circuit.
In configuration mode, all recognized slaves are activated except of
AS-i master is in normal operation. There is data exchange between
and all AS-i slaves detected by the master regardless of whether th
slaves were projected before.
5.3 Protected Operating Mode
5.3.1 Switching to Protected Operating Mode
The configuration mode can be left by pressing the mode button.
Pressing the button shortly:
Exits the configuration mode without projecting the current AS
Pressing the button for more than five seconds:
Exits the configuration mode and projects the actual AS-i con
taneously the actual AS-i configuration is stored as nominal coEEPROM.
When delivered the device is in configuration mode.
In contrast with the configuration mode in the protected
only data exchange between the AS-i master and the p
slaves.
If the system detects an AS-i slave with address zero o
not leave the configuration mode.
7/28/2019 Maquina_119_rob
19/78
AS-i/PROFIBUS Gateway Operating the AS-i/PROFIBUS Gateway
Shortly appearing configuration errors are stored in the de
nosis). The last error that occurred can be displayed by prshort AS-i power failure is responsible for the configuration
39.
5.4 Assigning an AS-i Address in Configuration Mode
AS-i can be put into operation in a very comfortable mann
software AS-i Control Tools (see chapter 8.1)(addressing d
dress assistant).
Furthermore you can use a hand held addressing device.
If you dont have neither a PC nor a hand held addressing
of the AS-i slaves is also possible with the AS-i/PROFIBU
buttons. How it works is described as follows.
5.4.1 Assigning a Slave Address
(assigning an available address to a slave with address zeIn configuration mode, the addresses of all detected slave
the other. To display the next higher available operating ad
ton shortly. Each time you press the set button, the next
played.
Choose the displayed address as your target address by pr
than five seconds. The address display blinks. The master
pressing the set button again addresses the connected sthe target (blinking address).
Any errors will be displayed by their error codes according
the detected slaves are displayed again as described in c
Only slaves with address 0 can get a new ad
There must not be two AS-i slaves with the s
circuit.
7/28/2019 Maquina_119_rob
20/78
AS-i/PROFIBUS Gateway Operating the AS-i/PROFIBUS Gateway
5.5 Programming the Address in Case of Configuration Errors
5.5.1 Automatic Address Assignment
For automatic programming to work, some requirements must be m
1.The AS-i master must be in the protected operating mode
2.The Auto_Address_Assign release flag must be set.
3.Only one of the projected slaves may not be detected.
If these requirements are met, the AS-i masters prg enable LED
slave with address zero will be automatically assigned to the operatin
missing slave. The "Automatic Address Assignment" can be activate
ed via the software "AS-i Control Tools".
5.5.2 Manual Address Assignment
In protected operating mode, wrong assignments are displayed as er
5.3). By pressing the set button, you can display all faulty assignme
other. By pressing the set button for more than five seconds, you c
rently displayed address as a potential target address, and the displ
One of AS-is great advantages is the automatic addres
a slave fails, it can be replaced by one of the same typ
zero. The master will detect the replacement and autom
addresses the new slave with the address of the faulty
If the two slaves have different configuration data, i.e. a
same type as far as AS-i is concerned, the automatic a
ment will not be carried out.
If several slaves fail, they cannot be replaced automati
master. Then these addresses have to be set manually
not be done via the host interface(using the AS-i Contro
hand held addressing device, the slave addresses can
with the help of the push buttons and the figure display
7/28/2019 Maquina_119_rob
21/78
AS-i/PROFIBUS Gateway Operating the AS-i/PROFIBUS Gateway
5.6 Setting of the PROFIBUS Station Address
5.6.1 PROFIBUS Station Address
Station addresses from 1 to 99 can be set, when delivered
For the relocation, both the set button and the mode bu
multaneously for at least 5 seconds until the current bus ad
display. With every pushing of the set button, the station
creased by 1.
Once the desired PROFIBUS station address is shown on t
non-volatile in the EEPROM by pushing the mode buttonMastersimulator DP V1 can be used to chage the AS-i/PR
address via PROFIBUS.
5.7 Error Messages
The addressing of the AS-i/PROFIBUS gatew
can be done locally at the gateway or via PR
PROFIBUS standard.
The system displays error codes for error mes
faulty assignments on the AS-i circuit. The co
than 50 and are therefore outside the slave acodes are described in the appendix, chapter
7/28/2019 Maquina_119_rob
22/78
AS-i/PROFIBUS Gateway Operating the AS-i/PROFIBUS Gateway
7/28/2019 Maquina_119_rob
23/78
AS-i/PROFIBUS Gateway Advanced Diagnostics for AS-i Masters
6 Advanced Diagnostics for AS-i Masters
The advanced AS-i diagnostics serve to locate occasiona
judge the quality of data transmission on AS-i without add
The "AS-i Control Tools" (software for the comfortable com
face and the programming of AS-i Control) support the op
agnostics (LCS, error counters and LOS).
6.1 List of Corrupted AS-i Slaves (LCS)
To locate occasionally occurring short-time configuration e
advanced diagnostics manage beside the list of projected
tected slaves (LDS) and the list of activated slaves (LAS)
rupted slaves (LCS). This list contains entries of all AS-i
responsible for at least one configuration error since powe
reading the list. Short-time AS-i power failures are represe
sition of AS-i slave with address 0.
6.2 Error Counters: Counters of corrupted data telegrams
The AS-i master with advanced diagnostics has an error co
which is increased every time there is a corrupted AS-i tel
sible to judge the quality of the AS i network even if only a
With every read access the LCS will be delet
The last short-time configuration error can alsMaster:
Pressing the set button of the AS-i master s
was responsible for the last short-time configu
short-time AS-i power failure the display show
set button.
This function is only available if device is in th
of the protected mode (display empty) or in th
7/28/2019 Maquina_119_rob
24/78
AS-i/PROFIBUS Gateway Advanced Diagnostics for AS-i Masters
6.3 Off-line Phase on Configuration Errors (LOS)
The AS-i masters with advanced diagnostics offer the possibility to
into the off-line Phase when a configuration error on the AS-Interfac
way the security of the application can be ensured. The reaction to a
ror is very fast and the host can be relieved from this task. If there a
on the AS-i network, the AS-interface can be switched to a secure s
There are two different ways to parameterize the AS-i master for thi
Every configuration error during normal operation in protected mooff-line phase.
For each slave address can be chosen whether a configuration e
dress will release the off-line phase or not. This information is sto
Off-line Slaves (LOS).
The user himself can decide how the system reacts to a configura
AS-Interface. The AS-i master can release the off-line phase in c
i.e. only with certain slave addresses, while in less critical situatioother AS-i slaves have a configuration error) only the error messa
error is sent to the host, but AS-i is still running.
The parameterization of off-line phase on configuration error is also
"AS-i Control Tools".
7/28/2019 Maquina_119_rob
25/78
AS-i/PROFIBUS Gateway PROFIBUS-DP
7 PROFIBUS-DP
This chapter contains all the necessary information to ope
gateway in a PROFIBUS-DP network.
7.1 DP Telegrams
7.1.1 Diagnosis
DP Diagnosis
PDU byte user byte DP
1 station_status 1
2 station_status 2
3 station_status 3
4 master address
5 ident high
6 ident low
7 1 header
8 2 type
9 3 slot
10 4 spec
11 5 ec-flags (high)
12 6 ec-flags (low)
13 7 delta (07)
14 8 delta (815)
20 14 delta (5663)
21 15 LPF (07)
28 22 LPF (5663)
29 23 LCS (07)
36 30 LCS (56 63)
7/28/2019 Maquina_119_rob
26/78
AS-i/PROFIBUS Gateway PROFIBUS-DP
Delta List: List of AS-i slaves with configuration error:
1: ConfigError0: no ConfigError
LPF:List of AS-i slaves with peripery fault:
1: periphery fault
0: no periphery fault
LCS: List of Corrupted slaves (see chapter 6).
Each element of the user diagnosis (ec-flags and slave lists) can besetting the appropriate bit in the parameter telegram.
Each element that is not used will be filled up with zeros. This way th
in the diagnosis telegram will keep its designated position (and clea
fits to the data furthermore).
Only if an element at the end of the user diagnosis is not used, the le
nosis will be shortened.
Extdiag will be set if at least one of the following conditions is fulfille
ConfigError 1
APF 1
PeripheryFault 1
LCS is not empty
The conditions when to set the ExtDiag bit can be chosen using the
or the mailbox commands.
The GSD file includes the following presettings:
The PROFIBUS diagnosis displayes: EC-flags, delta list and LPF
displayed.
ExtDiag will be set if ConfigError =1 and APF = 1. ExtDiag will not
periphery fault or if there is a entry in the LCS.
If an AS-i/PROFIBUS-DP Gateway with 2 AS-i masters is used, theBytes 5 to 30 represent AS-i network 1 and the User-diagnosis byte
sent AS-i network 2.
User Parameters
With the User Paramters can be selected which slave liste will be di
7/28/2019 Maquina_119_rob
27/78
AS-i/PROFIBUS Gateway PROFIBUS-DP
The bits in "slave lists" and "ExtDiag" have following mean
LCS: 1: LCS will be displayed in PROFIBUS diagnosis
0: LCS will not be displayed
LPF: 1: LPF will be displayed in PROFIBUS diagnosis
0: LPF will not be displayed
D: 1: Delta list will be displayed in PROFIBUS diagno
0: Delta list will not be displayed
F: 1: EC flags will be displayed in PROFIBUS diagno
0: EC flags will not be displayed
CS: 1: ExtDiag will be set, if there is an entry in the LCS
0: ExtDiag will not be set, if there is an entry in the
7 group_ident
8 1 DPV status 1
9 2 DPV status 2
10 3 DPV status 3
11 4 slave lists
12 5 ExtDiag
Slave lists
27 26 25 24 23 2
LCS LPF
default 0 0 0 0 1 0
ExtDiag
27 26 25 24 23 2
CS PF AP
default 0 0 0 0 0 1
DP Parameters
PDU byte user byte DP DP
7/28/2019 Maquina_119_rob
28/78
AS-i/PROFIBUS Gateway PROFIBUS-DP
7.1.2 Configuration DP V0 (cyclic data)
AS-i V2.04 easy mode
The PROFIBUS diagnosis is dilayed as described in chapter 7.1.1.
Even if the PROFIBUS-DP gateway V2.1 shall be used in this V2.04
GSD file which comes together with the gateway has to be used. Th
V2.04 gateway can not be used.
AS-i V2.1 mode
In AS-i V2.1 mode the input and output data field can be used with vIDs".
The advantages of special input and output IDs are: They can includ
ments (bytes or words) and the length of input and output data can
thermore "manufacturer specific" data bytes are possible. These "m
specific" data bytes describe the which type ID is.
The following types are possible:
The AS-i/PROFIBUS-DP Gateway V2.1 can be used th
Bihl+Wiedemann's AS-i/PROFIBUS-DP Gateway acco
specification 2.04 which has been commisioned in eas
mode the AS-i I/O data are shown in the PROFIBUS pro
bytes I/O data with or without consistency.
Areas of the I/O-data fields
type input data
length (bytes)
0016 empty 0128
0116 digital process data out of AS-i circuit 1 032
0216
digital process data out of AS-i circuit 2 032
0316 mailbox 236
1016 analog input data circuit 1, slave 31 2128
1116 analog input data circuit 1, slave 15 2120
12 l t t d t i it 1 l 31 0
7/28/2019 Maquina_119_rob
29/78
AS-i/PROFIBUS Gateway PROFIBUS-DP
The IDs can be used in different sequences. But in the I/O
area with each type.7.1.3 I/O-Data
AS-i V2.04 easy mode
AS-i V2.1 mode
Process data
byte 27 26 25 24 23
0 slave 1/1A
D3 D2 D1 D0 F3
1 slave 3/3A
2 slave 5/5A
3 slave 7/7A
4 slave 9/9A
5 slave 11/11A
6 slave 13/13A
7 slave 15/15A
8 slave 17/17A
9 slave 19/19A
10 slave 21/21A
11 slave 23/23A
12 slave 25/25A
13 slave 27/27A14 slave 29/29A
15 slave 31/31A
In V2.1 mode the AS-i I/O data are mapped i
data as known from the Siemens and AS-i/In
means the lower nibble describes the data of
higher slave address. The EC flags resp. HI-f
d t th ibbl f AS i l 0
7/28/2019 Maquina_119_rob
30/78
AS-i/PROFIBUS Gateway PROFIBUS-DP
7 slave 14/14A slave 15/
8 slave 16/16A slave 17/
9 slave 18/18A slave 19/
10 slave 20/20A slave 21/
11 slave 22/22A slave 23/
12 slave 24/24A slave 25/
13 slave 26/26A slave 27/
14 slave 28/28A slave 29
15 slave 30/30A slave 31/
16 reserved slave 1
17 slave 2B slave 3
18 slave 4B slave 5
19 slave 6B slave 720 slave 8B slave 9
21 slave 10B slave 1
22 slave 12B slave 1
23 slave 14B slave 1
24 slave 16B slave 1
25 slave 18B slave 126 slave 20B slave 2
27 slave 22B slave 2
28 slave 24B slave 2
29 slave 26B slave 2
30 slave 28B slave 2
31 slave 30B slave 3
Flags
input data output data
F0 ConfigError Off-line
byte 27 26 25 24 23 22
7/28/2019 Maquina_119_rob
31/78
AS-i/PROFIBUS Gateway PROFIBUS-DP
A rising edge of the "LOS master bit" effects that all bits in
edge effects that all bits are reset.
Analog data
The 16 bit values of AS-i slaves according to the profile 7.3
each PROFIBUS cycle or via the mailbox.
If analog values are written cyclic and acyclic via the mailbo
time, the values transmitted cyclically will overwrite the ac
Mailbox
Only using the IDs of the process data field the AS-i/PROFI
as M0 AS-i master. Using the mailbox (see chapter 7.1) th
are avaiable.
Analog data
byte 27 26 25 24 23
1 slave 31-n/8, channel 1, high
2 slave 31-n/8, channel 1, low
3 slave 31-n/8, channel 2, high
4 slave 31-n/8, channel 2, low
n-1 slave 31, channel 4, high b
n slave 31, channel 4, low by
Request
byte 27 26 25 24 23
1 command
2 T circuit
3 request parameter byte 1
36 request parameter byte 3
7/28/2019 Maquina_119_rob
32/78
AS-i/PROFIBUS Gateway PROFIBUS-DP
The mailbox commands can also be activated with PROFIBUS-DP V
cess data exchange is possible via the mailbox. In that way the config
"AS-i Control Tools" can run the whole communication via DP V1.
7.2 DP V1
To exchange data between the PROFIBUS master and the AS-i/PRO
via PROFIBUS-DP V1 only one data block is used - slot 1, index 16
block a mailbox is installed like the one used in the DP telegram.
The DP V1-mailboxes are processed every time they are called. Thsible, to execute the same command several times without changin
"circuit".
7.3 Mailbox
7.3.1 Construction
If an AS-i slave is addressed in a command or in a response, the addras shown below:
Request
byte 27 26 25 24 23 22
1 command
2 T circuit
3 request parameter byte 1
36 request parameter byte 34
Response
byte 27 26 25 24 23 22
1 command
2 T result
3 response parameter byte 1
34 response parameter byte 32
7/28/2019 Maquina_119_rob
33/78
AS-i/PROFIBUS Gateway PROFIBUS-DP
Circuit = 1 If AS-i gateway with 2 masters and the maste
Values for command
Values for command
value meaning
IDLE 0016 No order
READ_IDI 4116 Read IDI
WRITE_ODI 4216 Write_ODI
SET_PP 4316 Set_Permanent_Parameter
GET_PP 0116 Get_Permanent_Parameter
WRITE_P 0216 Write_Parameter
READ_PI 0316 Read_Parameter
STORE_PI 0416 Store_Actual_ParameterSET_PCD 2516 Set_Permanent_Config
GET_PCD 2616 Get_Permanent_Config
STORE_CDI 0716 Store_Actual_Configuration
READ_CDI 2816 Read_Actual_Configuration
SET_LPS 2916 SET_LPS
GET_LPS 4416 Get_LPS
GET_LAS 4516 Get_LAS
GET_LDS 4616 Get_LDS
GET_FLAGS 4716 Get_Flags
SET_OP_MODE 0C16 Set_Operation_Mode
SET_OFFLINE 0A16 Set_Offline_ModeSET_DATA_EX 4816 Set_Data_Exchange_Active
SLAVE_ADDR 0D16 Change_Slave_Address
SET_AAE 0B16 Set_Auto_Adress_Enable
7/28/2019 Maquina_119_rob
34/78
AS-i/PROFIBUS Gateway PROFIBUS-DP
Values for results
READ_ODI 5616 Read ODI 2
GET_LISTS 3016 Get LDS, LAS, LPS, Flags 2
GET_LCS 6016 Get LCS 2
GET_LOS 6116 GET_LOS 2
SET_LOS 6216 SET_LOS 10
GET_TECA 6316 Get transm.err.counters 2
GET_TECB 6416 Get transm.err.counters 2
GET_TECX 6616 Get transm.err.counters 4
EXT_DIAG 7116 ExtDiag generation 6
OPTIONS 7416
Software options 2
BUTTONS 7516 Disable pushbuttons 3
RD_EXT_DIAG 7B16 Read ExtDiag Settings 2
INVERTER 7C16 Configure Inverter Slaves 12
Values for result
value place meaning
OK 0016 execution without fault
HI_NG 1116 HI general fault
HI_OPCODE 1216 HI illegal value in command
HI_LENGTH 1316 HI length of the mailbox in the I/O-datatively the length of the DPV1-Reque
HI_ACCESS 1416 HI no access right
EC_NG 2116 EC general fault
Values for command
value meaning ReqLen
7/28/2019 Maquina_119_rob
35/78
AS-i/PROFIBUS Gateway PROFIBUS-DP
7.3.2 Mailbox commands
IDLE:
READ_IDI:
With this call the input data values of all AS-i slaves are re
AS-i/PROFIBUS Gateway in addition to the cyclic data ex
box command READ_IDI transmits all Execution-Control-F
Request
byte 27 26 25 24 23
1 0016
2 T circuit
Responsebyte 27 26 25 24 23
1 0016
2 T result
Request
byte 27 26 25 24 23
1 41162 T circuit
Response
byte 27 26 25 24 23
1 4116
2 T result
3
4 OR APF NA CA AAv
5
6 slave 2A
AS i/PROFIBUS G t PROFIBUS DP
7/28/2019 Maquina_119_rob
36/78
AS-i/PROFIBUS Gateway PROFIBUS-DP
WRITE_ODI:
With this call the output data values of all AS-i slaves are written in aclic data exchange.
Set_Permanent_Parameter (SET_PP):
With this call, a parameter value for the specified AS-i slave is config
PROFIBUS Gateway. The value is stored permanently in the EEPRway.
The configured parameter is not transferred immediately by the AS-
Gateway to the AS-i slave. The configured parameter value is only t
the AS-i slave is activated after turning on the power supply on the
Gateway.
Request
byte 27 26 25 24 23 22
1 4216
2 T circuit
3 slave 1
4 slave 2A slave 3
34 slave 30B slave 3
Response
byte2
7
2
6
2
5
2
4
2
3
2
2
1 4216
2 T result
Requestbyte 27 26 25 24 23 22
1 4316
2 T circuit
AS i/PROFIBUS Gateway PROFIBUS DP
7/28/2019 Maquina_119_rob
37/78
AS-i/PROFIBUS Gateway PROFIBUS-DP
Get_Permanent_Parameter (GET_PP):
With this call, a slave-specific parameter value stored on tPROFIBUS Gateway is read.
Write Parameter (WRITE_P):
The AS-i slave parameter value transferred with the comm
dressed AS-i slave.
The parameter is stored on the AS-i/PROFIBUS Gateway
entered as a configured parameter in the EEPROM!
The AS-i slave transfers its current parameter value in the
echo). This can deviate from the value that has just been w
master specification. The AS-i slave response is returned a
response data.
Request
byte 27 26 25 24 23
1 0116
2 T circuit
3 B slave
Response
byte 27 26 25 24 23
1 0116
2 T result
3
Request
byte 27 26 25 24 23
1 0216
2 T circuit
3 B slave
AS-i/PROFIBUS Gateway PROFIBUS-DP
7/28/2019 Maquina_119_rob
38/78
AS-i/PROFIBUS Gateway PROFIBUS-DP
Read Parameter (READ_PI):
This call returns the current parameter value (actual parameter) of aby the AS-i/PROFIBUS Gateway.
This value must not be confused with the parameter echo that is sup
slave as a response to the write_parameter job.
Meaning of bit B:
B = 0 Single AS-i slave or A-slave
B = 1 B-slave
Store Actual Parameters (STORE_PI):
With this call, the configured parameters stored on the EEPROM are
the current, permanently stored (actual) parameters; in other words
of all the AS-i slaves are configured.
Request
byte 27 26 25 24 23 22
1 0316
2 T circuit
3 B slave address
Response
byte 27 26 25 24 23 22
1 0316
2 T result
3 PI
Requestbyte 27 26 25 24 23 22
1 0416
2 T circuit
AS-i/PROFIBUS Gateway PROFIBUS-DP
7/28/2019 Maquina_119_rob
39/78
AS i/PROFIBUS Gateway PROFIBUS DP
Set Permanent Configuration (SET_PCD):
This call sets the following configuration data for the addre I/O configuration
ID code
Extended ID1 code
Extended ID2 code
The configuration data are stored permanently on the EEP
PROFIBUS Gateway and are used as the expected configin the protected mode. The configuration data are specifie
the AS-i slave.
If the addressed AS-i slave does not support an extended I
must be specified.
When this command is executed, the AS-i master change
then changes back to the normal mode (warm restart on t
This command can only be executed in the configuration m
Meaning of bit B:
B = 0 Single AS-i slave or A-slave
Request
byte 27 26 25 24 23
1 2516
2 T circuit
3 B slave4 xID2
5 ID
Response
byte 27 26 25 24 23
1 2516
2 T result
AS-i/PROFIBUS Gateway PROFIBUS-DP
7/28/2019 Maquina_119_rob
40/78
y
The configuration data are specified by the manufacturer of the AS-
Meaning of bit B:
B = 0 Single AS-i slave or A-slave
B = 1 B-slave
Store Actual Configuration (STORE_CDI):
With this call, the (actual) configuration data (I/O configuration, ID codcode and extended ID2 code) of all AS-i slaves are stored permane
EEPROM as the (expected) configuration data. The list of activated A
is adopted in the list of permanent AS-i slaves (LPS).
When this command is executed, the AS-i master changes to the of
then changes back to the normal mode (warm restart on the AS-i m
This command can only be executed in the configuration mode.
Request
byte 27 26 25 24 23 22
1 2616
2 T circuit
3 B slave address
Responsebyte 27 26 25 24 23 22
1 2616
2 T result
3 xID2 xID1
4 ID I0
Request
byte 27 26 25 24 23 22
1 0716
AS-i/PROFIBUS Gateway PROFIBUS-DP
7/28/2019 Maquina_119_rob
41/78
Read Actual Configuration (READ_CDI):
With this call, the following configuration data of an addresthe AS-i master on the AS-Interface are read.
I/O configuration
ID code
Extended ID1 code
Extended ID2 code
The configuration data are specified by the manufacturer o
Meaning of bit B:
B = 0 Single AS-i slave or A-slave
B = 1 B-slave
SET_LPS:
With this call, the list of configured AS-i slaves is transferre
the EEPROM of the master.
When this command is executed, the AS-i master change
th h b k t th l d ( t t t
Request
byte 27 26 25 24 23
1 2816
2 T circuit
3 B slave
Response
byte 27 26 25 24 23
1 2816
2 T result
3 xID2
4 ID
AS-i/PROFIBUS Gateway PROFIBUS-DP
7/28/2019 Maquina_119_rob
42/78
GET_LPS:
With this call, the following entry is read out of the AS-i/PROFIBUS G
of projected AS-i slaves (LPS).
GET_LAS:
With this call, the following entry is read out of the AS-i/PROFIBUS G
of activated slaves (LAS).
Response
byte 27 26 25 24 23 22
1 2916
2 T result
Request
byte 27 26 25 24 23 22
1 4416
2 T circuit
Response
byte 27 26 25 24 23 22
1 4416
2 T result
3 7A &A 5A 4A 3A 2A
10 31B 30B 29B 28B 27B 26B
Request
byte 27 26 25 24 23 22
1 4516
2 T circuit
AS-i/PROFIBUS Gateway PROFIBUS-DP
7/28/2019 Maquina_119_rob
43/78
GET_LDS:
With this call, the following entry is read out of the AS-i/PRof detected AS-i slaves (LDS).
GET_FLAGS:
With this call, the following entry is read out of the AS-i/PR
flags according to the AS-i slave specification.
Request
byte 27 26 25 24 23
1 4616
2 T circuit
Response
byte 27 26 25 24 23
1 4616
2 T result
3 7A &A 5A 4A 3A
10 31B 30B 29B 28B 27B
Request
byte 27 26 25 24 23
1 4716
2 T circuit
Response
byte 27 26 25 24 23
1 4716
2 T response
3
AS-i/PROFIBUS Gateway PROFIBUS-DP
7/28/2019 Maquina_119_rob
44/78
AAs Auto_Address_Assign
This flag is set when the automatic address programming is
words, AUTO_ADDR_ENABLE = 1 and there is no incorrect
to the AS-i Interface).
AAv Auto_Address_Available
This flag is set when the automatic address programming ca
(in other words, exactly one AS-i slave is currently out of ope
CA Configuration_Active
The flag is set in the configuration mode and reset in the pro
NA Normal_Operation_Active
This flag is set when the AS-i master is in normal operation.
APF APF
This flag is set when the voltage on the AS-i cable is too low
OR Offline_Ready
The flag is set when the offline phase is active.
Cok Config_Ok
This flag is set when the desired (configured) and actual con
AAe Auto_Address_Enable
This flag indicates whether the automatic address programm
(bit = 1) or disabled (bit = 0) by the user.
OL Off-lineThis flag is set when the mode is to changed to OFFLINE or
already been adopted.
DX Data_Exchange_Active
If the "Data_Exchnge_Active" flag is set, the the data exchag
master and slaves is available in the dataexchange phase. If
the data exchange is not available. The read ID telgegrams a
the slave.
The bit is set if the AS-i master entries the offline phase.
SET OP MODE:
7/28/2019 Maquina_119_rob
45/78
AS-i/PROFIBUS Gateway PROFIBUS-DP
7/28/2019 Maquina_119_rob
46/78
The master changes to the Offline phase, if there is a 1 written in by
The master will change to online mode if there is a 0 written in byte
SET_DATA_EX:
Change Slave Address (SLAVE_ADDR):
With this call, the AS-i address of an AS-i slave can be modified.
This call is mainly used to add a new AS-i slave with the default add
AS-Interface. In this case, the address is changed from "AS-i slave
to "AS-i slave address new.
This change can only be made when the following conditions are fu
1. An AS-i slave with AS-i slave address old exists.
2. If the old AS-i slave address is not equal to 0, then an AS-i slave
cannot be connected at the same time.
Response
byte 27 26 25 24 23 22
1 0A16
2 T result
Request
byte 27 26 25 24 23 22
1 4816
2 T circuit
3 Data_Exchange_Active
Response
byte 27 26 25 24 23 22
1 4816
2 T result
AS-i/PROFIBUS Gateway PROFIBUS-DP
7/28/2019 Maquina_119_rob
47/78
Meaning of bit B:
B = 0 Single AS-i slave or A-slave
B = 1 B-slave
Set Auto Address Enable (SET_AAE):
This call can enable or disable the "automatic address pro
The AUTO_ADDR_ENABLE bit is stored permanently; in
after a warm/hot restart on the AS-i master.
Request
byte 27 26 25 24 23
1 0D16
2 T circuit
3 B sourc
4 B targe
Response
byte 27 26 25 24 23
1 0D16
2 T result
Request
byte 27 26 25 24 23
1 0B16
2 T circuit
3 Auto_Address_Enable
Response
byte 27 26 25 24 23
1 0B16
2 T lt
AS-i/PROFIBUS Gateway PROFIBUS-DP
7/28/2019 Maquina_119_rob
48/78
EXEC_CMD:
With this call the master gets a message from the host that a messa
transmitted to the AS-i slaves.
Meaning of bit B:
B = 0 Single AS-i slave or A-slave
B = 1 B-slave
GET_LPF:
With this call, the list of peripheral faults (LPF) signaled by the AS-i s
from the AS-i master. The LPF is updated cyclically by the AS-i mas
when an AS-i slave signals faults of the attached peripherals (for exa
can be found in the description of the AS-i slave.
Request
byte 27 26 25 24 23 22
1 4916
2 T circuit
3 B slave address4 info5
Response
byte 27 26 25 24 23 22
1 4916
2 T result3 info4
Request
byte 27 26 25 24 23 22
1 3E16
2 T circuit
AS-i/PROFIBUS Gateway PROFIBUS-DP
7/28/2019 Maquina_119_rob
49/78
Write AS-i Slave Extended ID1 (WRITE_XID1):
With this call, the extended ID1 code of an AS-i slave with
directly over the AS-i cable. The call is intended for diagno
required in the normal master mode.
The AS-i master passes on the extended ID1 code to the A
sibility check.
RD_7X_IN:
With this command the four 16 bit channels of an AS-i inp
slave profil 7.3 can be read.
Request
byte 27 26 25 24 23
1 3F16
2 T circuit
3
Response
Byte 27 26 25 24 23
1 3F16
2 T result
Request
byte 27 26 25 24 23
1 5016
2 T circuit
3 0 slave
Response
byte 27 26 25 24 23
1 5016
AS-i/PROFIBUS Gateway PROFIBUS-DP
7/28/2019 Maquina_119_rob
50/78
WR_7X_OUT:
With this command the four 16 bit channels of an AS-i output slave
slave profil 7.3 can be written.
RD_7X_OUT:
With this command the four 16 bit channels of an AS-i output slave
slave profil 7.3 can be read out of the AS-i/PROFIBUS Gateway.
Request
byte 27 26 25 24 23 22
1 5116
2 T circuit
3 0 slave address4 channel 1, high byte
11 channel 4, low byte
Response
byte 27 26 25 24 23 22
1 5116
2 T result
Request
byte 27 26 25 24 23 22
1 5216
2 T circuit
3 0 slave address
Response
byte 27 26 25 24 23 22
1 5216
AS-i/PROFIBUS Gateway PROFIBUS-DP
7/28/2019 Maquina_119_rob
51/78
RD_7X_IN_X:
With this command the four 16 bit channels of 4 AS-i inpu
dresses according to the slave profil 7.3 can be read.
WR_7X_OUT_X:
With this command the four 16 bit channels of 4 AS-i outpu
dresses according to the slave profil 7.3 can be written.
Request
byte 27 26 25 24 23
1 5316
2 T circuit
3 0 1st sla
Response
byte 27 26 25 24 23
1 5316
2 T result
3 1st slave, channell 1, high b
34 4th slave, channel 4, low b
Request
byte 27 26 25 24 23
1 5416
2 T circuit
3 0 1st sla
4 1st slave, channel 1, high b
35 4th slave, channel 4, low b
AS-i/PROFIBUS Gateway PROFIBUS-DP
7/28/2019 Maquina_119_rob
52/78
RD_7X_OUT_X:
With this command the four 16 bit channels of 4 AS-i output slaves w
dresses according to the slave profil 7.3 can be read.
READ_ODI:
With this call the output data values of all AS-i slaves is read out of
PROFIBUS Gateway.
Request
byte 27 26 25 24 23 22
1 5516
2 T circuit
3 0 1st slave addres
Response
byte 27 26 25 24 23 22
1 5516
2 T result
3 1st slave, channel 1, high byte
34 4th slave, channel 4, low byte
Request
byte 27 26 25 24 23 22
1 5616
2 T circuit
Responsebyte 27 26 25 24 23 22
1 5616
2 T result
AS-i/PROFIBUS Gateway PROFIBUS-DP
7/28/2019 Maquina_119_rob
53/78
Get_LPS, Get_LAS, Get_LDS, Get_Flags (GET_LISTS):
With this call, the following entries are read out of the AS-
The list of active AS-i slaves (LAS)
The list of detected AS-i slaves (LDS)
The list of projected AS-i slaves (LPS)
The flags according to the AS-i slave specification
Pok Periphery_Ok
S0 LDS.0
Request
byte 27 26 25 24 23
1 3016
2 T circuit
Response
byte 27 26 25 24 23
1 3016
2 T result
3 7A 6A 5A 4A 3A
LAS
10 31B 30B 29B 28B 27B
11 7A 6As 5A 4A 3A
LDS19 31B 30B 29B 28B 27B
20 7A 6As 5A 4A 3A
LPS
26 31B 30B 29B 28B 27B
27
28 OR APF NA CA AAv29
AS-i/PROFIBUS Gateway PROFIBUS-DP
7/28/2019 Maquina_119_rob
54/78
GET_LCS:
With this call, the List of Corrupted Slaves (LCS) is read out of the A
Gateway.
GET_LOS:
With this call, the List of Offline Slaves (LOS) is read out of the AS-i/P
way (see chapter 6).
Request
byte 27 26 25 24 23 22
1 6016
2 T circuit
Response
byte 27 26 25 24 23 22
1 6016
2 T result
3 7A 6A 5A 4A 3A 2A
10 31B 30B 29B 28B 27B 26B
Request
byte 27 26 25 24 23 22
1 6116
2 T circuit
Response
byte 27 26 25 24 23 22
1 6116
2 T result
3 7A 6A 5A 4A 3A 2A
AS-i/PROFIBUS Gateway PROFIBUS-DP
7/28/2019 Maquina_119_rob
55/78
SET_LOS:
With this call, the List of Offline Slaves is written to the AS-i/
chapter 6).
GET_TECA:
With this call the error counters of all single slaves / A-slav
ter 6).
Request
byte 27 26 25 24 23
1 6216
2 T circuit
3 7A 6A 5A 4A 3A
10 31B 30B 29B 28B 27B
Response
byte 27 26 25 24 23
1 6216
2 T result
Request
byte 27 26 25 24 23
1 6316
2 T circuit
Response
byte 27 26 25 24 23
1 6316
2 T result
3 APF
AS-i/PROFIBUS Gateway PROFIBUS-DP
7/28/2019 Maquina_119_rob
56/78
GET_TECB:
With this call the counts of the error counters for B-slaves are read ou
With every read out of the counts the error counters are restarted.
The counts are read out via the correspondending host interface an
with every read access. The counter value is limited to 254. 255 mea
flow.
GET_TEC_X:
With this call beginning by a definite slave address the counts of the
are read out (see chapter 6).
With every read out of the counts the error counters are restarted.
The counts are read out via the correspondending host interface an
with every read access. The counter value is limited to 254. 255 meaflow.
Request
byte2
7
26
25
24
23
22
1 6416
2 T circuit
Response
byte 27 26 25 24 23 22
1 6416
2 T result
3 APF
4 slave 1B
34 slave 31B
Anfrage
Byte 27 26 25 24 23 22
AS-i/PROFIBUS Gateway PROFIBUS-DP
7/28/2019 Maquina_119_rob
57/78
EXT_DIAG:
With this call, the conditions when to set the ExtDiag bit ca
CF ExtDiag is set, if ConfigError 1
APF ExtDiag is set, if APF 1
PF ExtDiag is set, if PeripheryFault 1
CS ExtDiag is set, if LCS is not empty
OPTIONS
Antwort
Byte2
7
26
25
24
23
1 6616
2 T Ergebnis
3 Zhler 1
n Zhler n - 2
Request
byte 27 26 25 24 23
1 71162 T circuit
3 CF
4 APF
5 PF
6 CS
Response
byte 27 26 25 24 23
1 7116
2 T result
AS-i/PROFIBUS Gateway PROFIBUS-DP
7/28/2019 Maquina_119_rob
58/78
BUTTONS:
With this call, the use of the buttons can be enabled/disabled.
RD_EXT_DIAG:
With this call, the conditions when the ExtDiag bit is set can be read
Response
byte2
7
26
25
24
23
22
1 7416
2 T result
3 character 1
18 character 16
Request
byte 27 26 25 24 23 22
1 7516
2 T circuit
3 ButtonsDisabled
Response
byte 27 26 25 24 23 22
1 7516
2 T result
Request
byte 27 26 25 24 23 22
1 7B16
2 T circuit
AS-i/PROFIBUS Gateway PROFIBUS-DP
7/28/2019 Maquina_119_rob
59/78
CF ExtDiag is set by ConfigError 1
APF ExtDiag is set by APF 1
PF ExtDiag is set by PeripheryFault 1CS ExtDiag is set, if LCS is not empty
FD Diagnosis will updated still only then, if this is dictated
Diagnosis data are doubtful not actual
INVERTER:
With that call an AS-i slave for frequency inverters is switch16 bit values via the AS-i analog profile 7.3 and afterwards
stination parameter.
Request
byte 27 26 25 24 23
1 7C16
2 T circuit
3 slave address
4 destination parameter
5 value 1, high byte
6 value 1, low byte
7 value 2, high byte
8 value 2, low byte9 value 3, high byte
10 value 3, low byte
11 value 4, high byte
12 value 4, low byte
Response
byte 27 26 25 24 23
1 7C16
2 T result
AS-i/PROFIBUS Gateway PROFIBUS-DP
3 3 M ilb l
7/28/2019 Maquina_119_rob
60/78
7.3.3 Mailbox example
Command RD_7X_IN: Reading of analog input values
PROFIBUS-DP V0: cyclic data exchange
Used ID/module in the GSD file: 12 bytes management
Meaning of the bytes:
The mailbox call has not been anwsered with the valid values, beau
has not been set.
Set of Toggle bit:
Request: RD_7X_IN
Byte 1 50hex (RD_7X_IN)
Byte 2 00hex (master 1, single master)
Byte 3 1Dhex (slave address 29)
Byte 4 00hex
Byte 12 00hex
ResponseByte 1 00hex
Byte 2 00hex
Byte 3 00hex
Byte 4 00hex
Byte 12 00hex
Request
Byte 1 50hex
Byte 2 80hex (Toggle bit, master 1, single master)
Byte 3 1Dhex (slave address 29)
Byte 4 00h
AS-i/PROFIBUS Gateway PROFIBUS-DP
7/28/2019 Maquina_119_rob
61/78
To get the input data again, the T-bit has to be reset aso.
If a mailbox command is used via PROFIBUS-DP V1, it is
toggle bit.
Response
Byte 1 50hex
Byte 2 80hex (Toggle bit, master1)
Byte 3 analog channel 1 high bytehex
Byte 4 analog channel 1 low bytehex
Byte 5 analog channel 2 high bytehex
Byte 6 analog channel 2 low bytehex
Byte 7 analog channel 3 high bytehex
Byte 8 analog channel 3 low bytehex
Byte 9 analog channel 4 high bytehex
Byte 10 analog channel 4 low bytehex
Byte 11 00hex not usedt
Byte 12 00hex
not usedt
AS-i/PROFIBUS Gateway PROFIBUS-DP
7/28/2019 Maquina_119_rob
62/78
AS-i/PROFIBUS Gateway Commissioning Tools and Accessories
8 Commissioning Tools and Accessories
7/28/2019 Maquina_119_rob
63/78
8 Commissioning Tools and Accessories
The AS-i circuit on the AS-i/PROFIBUS Gateway can be pcomfortable Windows software "AS-i Control" Tools.
This software communicates with the AS-i/PROFIBUS gat
PROFIBUS DP Mastersimulator DP V1 of Bihl+Wiedeman
no. 1257) or Serial PROFIBUS Master of Bihl+Wiedeman
no 1258), which converts the RS 232-signals of the PC to
The AS-i master in IP65 needs an additional D-Sub data t
AS-i masters in IP65 of Bihl+Wiedemann GmbH, Mannhe
8.1 Windows Software AS-i Control Tools
The Windows software AS-i Control Tools enables you to c
a very comfortable manner.
1. For that purpose plug in the PROFIBUS-DP Ma
Bihl+Wiedemann GmbH, Mannheim, (art. no. 1257) to thAS-i/PROFIBUS gateway. Connect the device with encl
sion cord to the AS-i/PROFIBUS gateway in IP20.
For the connection of the AS-i/PROFIBUS gateway in I
Sub data transmission cord of Bihl+Wiedemann GmbH,
2. Start the AS-i Control Tools.
3. Call the command Master | New.
AS-i/PROFIBUS Gateway Commissioning Tools and Accessories
5 Do the appropriate settings (e g serial interface COM 2 station
7/28/2019 Maquina_119_rob
64/78
5. Do the appropriate settings. (e.g. serial interface COM 2, station
AS-i circuit 1)
6. Call the command Master | AS-i configuration.
The AS-i configuration editor will be started. All detected and proje
are displayed in this window.
AS-i/PROFIBUS Gateway Commissioning Tools and Accessories
7. Click on a slave entry to open the dialogbox slave confi
7/28/2019 Maquina_119_rob
65/78
7. Click on a slave entry to open the dialogbox slave confi
This dialog box is for changing a slave address, settinconfiguration data. Additionally you can test inputs and
A very easy approach to configure the AS-i circuit is connec
line and setting the AS-i slave address one after the other.
Store configuration to adopt the detected AS-i circuit to th
data.
Moreover you can use the AS-i Address Assistant. This t
the address of an AS-i slave to the desired address after pluline. The desired AS-i configuration can be created off-line
When you build up the plant you only have to plug the AS-i
after the other.
AS-i/PROFIBUS Gateway Commissioning Tools and Accessories
8.2 PROFIBUS-DP master simulator
7/28/2019 Maquina_119_rob
66/78
The PROFIBUS-DP Master Simulator is an easy to use software fo
with PROFIBUS slaves of many suppliers via PROFIBUS-DP. The
Master Simulator can exchange data with many PROFIBUS slaves GSD-file or type-file. The PROFIBUS slaves can be put into operatio
I/O window. Input data can be read and output data can be written.
PROFIBUS-DP Master Simulator also processes GSD-files. User pa
edited and the configuration can be modified and stored. The PROF
dress can be changed as well with the PROFIBUS-DP Master Simula
for PROFIBUS I/O modules in protection class IP67 without address
The PROFIBUS-DP Master Simulator offers the possibility to scan awork for connected slaves and display them in a graphical way. In th
PROFIBUS UART has to be connected directly to a PROFIBUS slav
and the PROFIBUS user diagnosis can be displayed binary, hexdecim
as ASCII code. The PROFIBUS output data can be transmitted con
PROFIBUS slave. In type mode it is possible to set an output as lon
button is pressed.
The new version of the PROFIBUS-DP Master Simulator supports PV1. PROFIBUS slaves can be operated in the acyclic mode DP V1. T
pecially for the commissioning of complex field devices like drives, m
tems etc.
AS-i/PROFIBUS Gateway Commissioning Tools and Accessories
8.3 Serial PROFIBUS Master
7/28/2019 Maquina_119_rob
67/78
The Serial PROFIBUS Master fulfills all tasks of the PROF
Futhermore it can run the PROFIBUS with up to 1,5 MBau
The Serial PROFIBUS Master can also be used as class 2
in a PROFIBUS network. In that way the software AS-i Con
permanent diagnosis while the PROFIBUS is running.
AS-i/PROFIBUS Gateway Commissioning Tools and Accessories
7/28/2019 Maquina_119_rob
68/78
AS-i/PROFIBUS Gateway Appendix: Displays of the Figure Display
9 Appendix: Displays of the Figure Display
7/28/2019 Maquina_119_rob
69/78
In the basic state of the configuration mode, the display shaddresses of all detected slaves at a rate of two per secon
that the LDS is empty, i.e. no slaves were detected.
In the basic state of the protected operating mode, the dis
plays the address of a faulty assignment (see chapter 5.3.
During manual address programming, the slave address d
meaning (see chapter 5.4 and 5.5).
All displayed numbers that are bigger than 31 and therefor
a slave address are status or error messages of the maste
meanings:
39 Advanced AS-i diagnostics: If a 39 appears on the d
set-button a short-time AS-i power failure occured.
40 The AS-i master is in off-line phase.
41 The AS-i master is in detection phase.42 The AS-i master is in activation phase.
43 The AS-i master starts the normal operating mode.
70 Hardware error: The AS-i masters EEPROM canno
72 Hardware error: The PIC processor does not respon
73 Hardware error: The PIC processor does not respon
74 Checksum error in the EEPROM.75 Error in the external RAM.
76 Error in the external RAM.
77 AS-i control software error: Stack overflow (AS-i con
78 AS-i control software error: Checksum error in the c
80 Error while attempting to exit the configuration mode
zero exists.
81 General error while changing a slave address.
82 The front panel operation is blocked. Until the next p
ter the accessing to the device only from the host via
83 P t f th AS i C t l Th A
AS-i/PROFIBUS Gateway Appendix: Displays of the Figure Display
95 Error while changing slave address in protected operating mo
7/28/2019 Maquina_119_rob
70/78
ration error was caused by one slave too many (instead of one
AS-i/PROFIBUS Gateway Appendix: The First Commissioning of AS-i
10 Appendix: The First Commissioning of AS-i
7/28/2019 Maquina_119_rob
71/78
In this chapter an example is given of how to
operation quickly and easily and without the n
The addressing of the components connecte
be performed directly on the AS-i master. It is
able to do the addressing with a hand-held pr
the Windows software AS-i Control Tools. Ho
figure even complex networks using only the
What to do ? How to go abo
See to it that the AS-i master is properly
supplied with power.
Connect the A
the terminals A
master, connec
Turn on the po
After the self-test: the LEDs power, config err, U ASI
The figure display shows 40: the AS-i master is in the of
that a 41 will be displayed: the AS-i master stays in the
Switch the device to the projecting
mode, if the yellow LED does not light
up.
Press the mod
approx. five se
The yellow LED prj mode lights up. The device is now i
Add a slave with the address 0 to the
AS-i line.
Connect the sl
terminals AS-i
The green LED ASI active lights up. The figure display s
AS-i master has detected the slave.
Change the slave address to address 1. Select address
button shortly,
When a 1 appthe set button
until the displa
shortly the set
address to the
AS-i/PROFIBUS Gateway Appendix: The First Commissioning of AS-i
What to do ? How to go about it?
7/28/2019 Maquina_119_rob
72/78
The configuration of the AS-i master is now finished.Now the hierarchically higher fieldbus system can be put into opera
The gateway stays in the off-line phase (Display dark, the LED
out), until the hierarchically higher fieldbus system operates p
AS-i/PROFIBUS Gateway Appendix: Putting PROFIBUS into Operation with a Siemens S5
11 Appendix: Putting PROFIBUS into Operation wit
7/28/2019 Maquina_119_rob
73/78
This chapter shows exemplarily the putting into operation oway on PROFIBUS for the PLC Simatic S5 135 of Siemens
ter card IM 308 C. The configuration software used is the S
3.0 (German version).
11.1 Putting into Operation in Easy Mode
1. Copy the GSD-file "B_W_1745.GSD" (by Gateway CM4
GSD-file "B_W_61745.GSD (by Gateway CM4-50AS-i/PROFIBUS Gateway IBM PC Software from the
rectory \GSD of the software COM PROFIBUS 3.0.
2. Start the configuration software COM PROFIBUS 3.0
3. Execute the command File | Scan GSD-Files.
4. Execute the command File | New.
The dialog box Master & Host Selection appears.
Select your PROFIBUS master.
5. With the command Configure | Master Parameters... y
and other bus parameters.
AS-i/PROFIBUS Gateway Appendix: Putting PROFIBUS into Operation with a Siemens S5
6. In the window DP Master System there is a ledge with several PR
Click on AS-i and drag the icon to the PROFIBUS in the window
7/28/2019 Maquina_119_rob
74/78
Click on AS i and drag the icon to the PROFIBUS in the window
7. After a second mouse click the dialogbox for the selection of the P
address appears. Setting of the AS-i/PROFIBUS gateway's sta
chapter 5.6:
AS-i/PROFIBUS Gateway Appendix: Putting PROFIBUS into Operation with a Siemens S5
8. and afterwards the dialogbox for the selection of the de
ters):
7/28/2019 Maquina_119_rob
75/78
)
Choose AS-i/DP as station type. This name stands fotings for the easy mode.
9. Afterwards, your PROFIBUS system looks as follows:
AS-i/PROFIBUS Gateway Appendix: Putting PROFIBUS into Operation with a Siemens S5
10.Select the PROFIBUS slave. With the command Configure | Sla
| Configure... you get to the dialogbox Configure.
7/28/2019 Maquina_119_rob
76/78
| g y g g g
The fields I Addr. and O Addr. hold the start addresses for th
easiest way to set the addresses is with Auto Addr.. From the
bytes of AS-i data each are mapped to the address space of yo
This AS-i data can be processed with your user program by m
transfer operations.
11.After closing this dialogbox save your project with the command 12.The last step is exporting the data to a memory card with the com
port | Memory Card...
7/28/2019 Maquina_119_rob
77/78
Moeller GmbHIndustrial AutomationHein Moeller Str 7 11
7/28/2019 Maquina_119_rob
78/78
Hein-Moeller-Str. 711
D-53115 Bonn
E-Mail: [email protected]: www.moeller.net
2001 by Moeller GmbH
Subject to alteration
AWB2700-1409GB DMD/MDS/B+W 04/01
Printed in the Federal Republic of Germany (04/01)
Article No.: 231344