Manual panouri solare UVR61_V2_5_engl

Embed Size (px)

Citation preview

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    1/116

    single and triple-loop universal controller

    The UVR61-3 unit has various functions for use in solar power systems and heating systems:thermostat, differential temperature, and speed control. The desired control function is the result ofthe program number that is input.

    Overview of functions:

    6 sensor inputs

    1 output, speed controlled 2 other outputs optional (with additional relay module)

    1 analogue output 0-10 volts

    Each with 3 functions for differential, minimum and maximum

    Tank and corrosion protection (potentiostat) integrated

    Heat counter integrated

    Freely programmable timer

    Easy-to-read display with various icons

    Time, date

    Data line (to analyse the temperature with a PC via D-LOGGUSB or BL-USB)

    System function control

    Solar start function, collector temperature delimiter, frost protection

    Overvoltage protection on all inputs

    Technische Alternativeelektronische Steuerungsgertegesellschaft mbH.A-3872 Amaliendorf, Langestr. 124, Fax 02862 53635/7

    UVR61-3Vers. 2.5

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    2/116

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    3/116

    This instruction manual is also available in English at www.ta.co.at

    Diese Anleitung ist im Internet auch in anderen Sprachen unter www.ta.co.atverfgbar.

    Ce manuel dinstructions est disponible en langue franaise sur le site Internetwww.ta.co.at

    Questo manuale distruzioni disponibile in italiano sul sito Internetwww.ta.co.at

    Estas instrucciones de funcionamiento estn disponibles en espaol, en

    Internet www.ta.co.at.

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    4/116

    4

    Table of contents

    Generally applicable rules, Stagnation 6Hydraulic diagrams 7

    0 Simple solar power system 816 Tank load by boiler 9

    32 Burner requirement via two tank sensors 1048 Solar power system with 2 consumers 1164 Solar power system with 2 collector panels 1280 Single solar power system and tank load via boiler 1396 Buffer and tank load via boiler fired with solid fuel 15112 2 independent differential circuits 16128 Burner requirement and solar power system (or feed pump) 17144 Solar power system with layered storage 18160 Inserting two boilers into the heating system 19176 Solar power system with 2 consumers and feed pump function 20192 Solar power system with 2 consumers and feed pump (heating boiler) 21208 Solar power system with 2 consumers and burner requirement 23224 Solar power system with 3 consumers 24240 Solar power system with 2 collector panels and 2 consumers 26256 Solar power system with 2 collector panels (1 pump, 2 stop valves) 28272 Solar power system with 2 collector panels and feed pump function 29288 Solar power system with 2 collector panels and burner requirement 30304 Solar power system with 2 coll. panels and feed pump (heating boiler) 31320 Layered storage tank and 1 independent feed pump 32336 Layered storage tank and feed pump (heating boiler) 33352 Layered storage tank and burner requirement 34

    368 Layered storage tank and feed pump function 36384 Layered storage tank with bypass function 37400 Solar power system with 1 consumer and 2 feed pump functions 38416 1 consumer, 2 feed pump functions, and burner requirement 39432 Solar power system, burner requirement, and 1 feed pump function 41448 Burner requirement and 2 feed pump functions 43464 Solar power system with 2 consumers and bypass function 45480 2 consumers and 3 feed pump functions 47496 1 consumers and 3 feed pump functions 48512 3 consumers and 3 feed pumps (3 independent differential loops) 49528 2 independent differential loops and independent burner requirement 50

    544 Cascade: S1 S2 S3 S4 51560 Cascade: S1 S2, S3 S4 S5 52576 Cascade: S4 S1 S2 + burner requirement 53592 2 generators on 2 consumers + independent differential loop 54608 2 generators on 2 consumers + burner requirement 55624 Solar power system with one consumer and a swimming pool 57640 Preparation of hot water including circulation and solar power system 58656 Preparation of hot water including circulation and burner requirement 59

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    5/116

    5

    Installation instructions 61Installing the sensor(s) 61Installing the unit - Electrical connection 63Special connections (inputs and outputs) 64

    Operation 65The main level 66

    Changing a value (parameter) 68

    The parameter menu Par 69Brief description 70Code CODE, Version VER, Program PR, Linking of outputs LO 71Priority assignment PA 72Thresholds and differential values max, min, diff 72Example with program 0 73Time 74Date DATE 74Time window TIME W 75Automatic / manual mode of outputs O AUTO 76

    The menu Men 77Brief description 78Language ENGL 79Code CODE 79Sensor menu SENSOR 79

    Sensor settings 80Sensor type, Creating a mean (average)AV, 81Assigning iconsAIC 82

    System protection function SYS PF 83Collector excess temperature CET 84Frost protection function FROST 85

    Start function STARTF 86Priority PRIOR 88After-running timeART 90Pump speed control PSC 91

    Absolute value control 93Differential control 94Event control 95Waveform 96Stability problems 97Pump standstill, Control commands 98

    Analogue output 0-10V 99

    Function check F CHECK 100Heat quantity counterHQC 102Potentiostat P STAT 105

    Status display Stat 106Troubleshooting 108Table of settings 109Maintenance, Safety requirements, Certificate of warranty 112Free for notices ex 113

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    6/116

    6

    Generally applicable rulesfor the proper use of this unit:

    The manufacturers warranty does not cover any indirect damage to the unit if themechanic installing the unit does not equip it with any additional electromagnetic devices(thermostat, possibly in combination with a one-way valve) to protect the unit from damagefrom malfunction under the following conditions:

    u Swimming pool system: If used with a high-performance collector and heat-sensitivecomponents (such as plastic lines), the supply line must have a excess temperaturethermostat with all of the necessary self-closing valves (closed when current less). Thecontrollers pump output can provide this as well. Hence, all heat-sensitive parts would beprotected from overheating if the system were not running, even if steam were created inthe unit due to stagnation. This technique is mandatory, especially in systems with heatexchangers, as a failure of the secondary pump might cause great damage to the plastictubes.

    u Conventional solar power systems with an external heat exchanger: in such systems, thesecondary heat transfer medium is usually pure water. If the pump runs at temperaturesbelow freezing because the controller fails, the heat exchanger and other components maybe damaged due to freezing. In this case, a thermostat must be installed on the supply lineof the secondary side after the heat exchanger to stop the primary pump automaticallywhen the temperature falls below 5C, regardless of the output of the controller.

    uWhen used for floor and wall heaters: here, a safety thermostat must be used just aswith conventional heater controllers. It has to switch off the heating loop pump if there isoverheating regardless of the output from the controller to prevent indirect damage fromexcess temperatures.

    Solar power systems - tips on system standstill (stagnation):

    Generally, stagnation is not a problem and cannot be ruled out if there is a power outage,for instance. In the summer, the controllers storage limit may switch off the systemrepeatedly. Every system must thus be intrinsically safe. If the expansion container isproperly designed, this is ensured. Tests have shown that the heat transfer medium(antifreeze) is under less stress during stagnation than when it is just below the steamphase.

    All of the data sheets of the collector manufacturers list standstill temperatures above200C. However, these temperatures generally only occur during operation with dry steam,

    i.e. when the heat exchange medium has completely turned to steam in the collector or thecollector has been completely emptied due to steam. The damp steam then dries quicklyand is no longer able to conduct heat. Hence, it can be assumed that these hightemperature cannot occur at the measuring point of the collector sensor (when installed inthe collector tube as usual) as the remaining thermal line would cool down the temperaturevia the metal connections between the absorber and the sensor.

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    7/116

    7

    Hydraulic diagrams

    Additional functions:

    w The following functions can also be used for every program diagram:

    Pump after-running time

    Pump speed control

    0 10V output

    System function control

    Heat counter

    Potentiostat

    w The following functions only make sense when program diagrams are used with solarpower systems:

    Collector excess temperature delimiter

    Frost protection function

    Start function

    Solar priority

    w For diagrams that do not need the outputs A2 and/orA3 for technical purposes:

    They can be set to always on with complimentary programs. Time windows can be set sothat A2 and/orA3 are used as separate timer outputs. The following information indicatesthis possibility:

    The output A3 is available as a timer output (without time window always ON).

    w In diagrams with a holding circuit (= burner requirement with a sensor, shut-down functionwith another one), the shut-down transducer is dominant. In other words, if improper

    parameters or sensor installation leads to the fulfilment of both the shut-on and shut-offconditions, the shut-off condition has priority.

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    8/116

    8

    Single solar power system - program 0 = factory settings

    Program 0: Pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1

    All programs +1:

    In addition, ifS3 exceeds the threshold max2,pump A1 is switched off.

    All programs +2: (only with relay module)

    The output A2 is available as a timer output (without time window always ON).

    All programs +4: (only with relay module)

    The output A3 is available as a timer output (without time window always ON).

    S1

    S2A1

    S3

    S1min1

    S2max1

    diff1A1

    Required settings :

    diff1 coll. S1 TK S2 A1min1 switch-on temp.burner . S1 A1max1 limit TK S2 A1max2 see all programs +1

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    9/116

    9

    Loading the tank from the boiler - program 16

    Program 16: Pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1

    All programs +1:

    In addition, ifS3 exceeds the threshold max2,pump A1 is switched off.

    All programs +2: (only with relay module)

    The output A2 is available as a timer output (without time window always ON).

    All programs +4: (only with relay module)

    The output A3 is available as a timer output (without time window always ON).

    A1 S2S1

    S3

    S1min1

    S2max1

    diff1A1

    requred settings :

    diff1 burnerS1 TK S2 A1min1 switch-on temp.burnerS1 A1max1 limit TK S2 A1

    max2 see all programs +1

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    10/116

    10

    Burner requirement via two tank sensors - program 32

    Program 32: Output A1 switches on when S2 falls below threshold min1.

    Output A1 switches off (dominant) when S1 exceeds max1.

    A1 (on) = S2 < min1 A1 (off) = S1 > max1

    All programs +1:The burner requirement (A1) only occurs via sensorS2.

    Output A1 switches on when S2 falls below threshold min1.

    Output A1 switches off (dominant) when S2 exceeds max1. A1 (on) = S2 < min1 A1 (off) = S2 > max1

    All programs +2: (only with relay module)

    The output A2 is available as a timer output (without time window always ON).

    All programs +4: (only with relay module)

    The output A3 is available as a timer output (without time window always ON).

    required settings:

    min1 burner req. on TK S2 A1max1 burner req. off TK S1 A1

    burnerA1

    S2 min1S1 max1

    S2

    A1 S1

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    11/116

    11

    Solar power system with 2 consumers - program 48

    Program 48: Pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    Pump A2 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S3 by the difference diff2w and S3 has not exceeded the threshold max2.

    A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1A2 = S1 > (S3 + diff2) & S1 > min1 & S3 < max2

    All programs +1:Instead of the two pumps, one pump and a three-way valve are used (pump-valve system).The speed control (if activated) only affects loop 1.

    A1 ... common pump A2 ... valve (A2/S has power when loading tank TK2)

    All programs +2:

    In addition, ifS4 exceeds the threshold max3,pump A1 is switched off.

    All programs +4:

    The output A3 is available as a timer output (without time window always ON).

    All programs +8: Both solar loops have separate switch-on thresholds at S1:

    output A1 retains min1, and A2 switches at min2.

    The priorities forTK1 and TK2 can be set in the parameter menu underPA. In addition, a

    solar priority function can be set for this diagram in the menu PRIOR (see solar priorities onpage 88 for more details).

    TK2 TK1

    A1A2S2S3

    S1

    S4

    S1min1

    S2 S3max1 max2

    diff2

    A2diff1

    A1

    required settings:

    diff1 coll. S1 TK1 S2 A1diff2 coll. S1 TK2 S3 A2min1 switch-on temp. coll. S1 A1, A2

    min2 see all programs +8max1 limit TK1 S2 A1max2 limit TK2 S3 A2max3 see all programs +2

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    12/116

    12

    Solar power system with 2 collector panels - program 64

    Program 64: Pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S3 by the difference diff1

    w and S3 has not exceeded the threshold max1.

    Pump A2 runs when:

    wS2 is greater than the threshold min2w and S2 is greater than S3 by the difference diff1

    w and S3 has not exceeded the threshold max1.

    A1 = S1> (S3 + diff1) & S1 > min1 & S3 < max1A2 = S2> (S3 + diff1) & S2 > min2 & S3 < max1

    All programs +1:

    If the difference between collector sensors S1 and S2 exceeds the difference diff3, thecolder collector is switched off. This prevents heat from being lost in the colder collector

    when temperatures are mixed.

    All programs +2:

    In addition, ifS4 exceeds the threshold max2,pumps A1 and A2 are switched off.

    All programs +4:

    The output A3 is available as a timer output (without time window always ON).

    S1 S2min1 min2

    S3

    max1

    diff1A2

    diff1A1

    required settings:

    diff1 coll.1 S1 TK S3 A1 coll.2 S2 TK S3 A2

    diff3 see all programs +1min1 switch-on temp. coll.1 S1 A1min2 switch-on temp. coll.2 S2 A2max1 limit TK S3 A1, A2max2 see all programs +2

    A1 A2

    S1 S2

    S3

    S4

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    13/116

    13

    Single solar power system and tank load from boiler - program 80

    Program 80: Pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    The feed pump A2 runs when:

    wS3 is greater than the threshold min2w and S3 is greater than S4 by the difference diff2

    w and S4 has not exceeded the threshold max2.

    A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1A2 = S3 > (S4 + diff2) & S3 > min2 & S4 < max2

    S1 S3min1 min2

    S2 S4

    max1 max2

    diff2A2diff1A1

    required settings:

    diff1 coll. S1 TK S2 A1diff2 boilerS3 TK S4 A2

    min1 switch-on temp. coll. S1 A1min2 switch-on temp. boilerS3 A2max1 limit TK S2 A1max2 limit TK S4 A2max3 see all programs +4

    S1

    S2S3 S4

    A1A2

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    14/116

    14

    Program 81 (all programs +1):

    Pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    The feed pump A2 runs when:wS3 is greater than the threshold min2w and S3 is greater than S2 by the difference diff2

    w and S2 has not exceeded the threshold max2.

    A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1A2 = S3 > (S2 + diff2) & S3 > min2 & S2 < max2

    All programs +2:

    If sensor S2 has reached max1 (or if S4 has reached threshold max3 along with allprograms +4), pump A2 is switched on, and pump A1 keeps running. This provides acooling function for the boiler / heater without causing standstill temperatures in the

    collector.

    All programs +4:

    In addition, ifS4 exceeds the threshold max3,pump A1 is switched off.

    All programs +8:

    The output A3 is available as a timer output (without time window always ON).

    S1 S3min1 min2

    S2max1max2

    diff2

    A2diff1

    A1

    required settings:

    diff1 coll. S1 TK S2 A1diff2 boilerS3 TK S2 A2min1 switch-on temp. coll. S1 A1

    min2 switch-on temp. boilerS3 A2max1 limit TK S2 A1max2 limit TK S2 A2max3 see all programs +4

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    15/116

    15

    Buffer and space-heating tank load via boiler fired with solid fuel - program 96

    Program 96: Pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    Feed pump A2 runs when:

    wS3 is greater than the threshold min2w and S3 is greater than S4 by the difference diff2

    w and S4 has not exceeded the threshold max2.

    A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1A2 = S3 > (S4 + diff2) & S3 > min2 & S4 < max2

    All programs +1:

    In additional, space-heating tank load pump A2 also switches on via the heater boiler

    temperature S1.

    Pump A2 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S4 by the difference diff3

    w and S4 has not exceeded the threshold max2

    w orS3 is greater than threshold min2w and S3 is greater than S4 by the difference diff

    w and S4 has not exceeded max2.

    A2 = (S1 > (S4 + diff3) & S1 > min1 & S4 < max2)or S3 > (S4 + diff2) & S3 > min2 & S4 < max2

    All programs +2:The output A3 is available as a timer output (without time window always ON).

    S1 S3min1 min2

    S2 S4

    max1 max2

    diff2

    A2

    diff1

    A1

    required settings:

    diff1 boilerS1 TK1 S2 A1

    diff2 TK1 S3 TK2 S4 A2diff3 see all programs +1min1 switch-on temp. boilerS1 A1min2 switch-on temp TK1. S3 A2max1 limit TK1 S2 A1max2 limit TK2 S4 A2

    A1 A2

    S1S2

    S3

    S4

    TK2TK1

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    16/116

    16

    Two independent differential loops - program 112

    Program 112: Pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    Feed pump A2 runs when:

    wS3 is greater than the threshold min2w and S3 is greater than S4 by the difference diff2

    w and S4 has not exceeded the threshold max2.

    A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1A2 = S3 > (S4 + diff2) & S3 > min2 & S4 < max2

    All programs +1:

    Output A3 is available as a timer output (without time window always ON).

    S3

    S4A2

    S1

    S2A1

    TK1 TK2

    S1 S3min1 min2

    S2 S4max1 max2

    diff2A2

    diff1A1

    required settings:

    diff1 coll. S1 TK1 S2 A1diff2 coll. S3 TK2 S4 A2min1 switch-on temp. coll.1 S1 A1min2 switch-on temp. coll.2 S3 A2max1 limit TK1 S2 A1max2 limit TK2 S4 A2max3 see all programs +4

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    17/116

    17

    Burner requirement and solar power system (or feed pump) - program 128

    Program 128: Pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    Output A3 switches on when S4 falls below threshold min2.

    Output A3 switches off (dominant) when S3 exceeds max2.

    A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1 A3 (on) = S4 < min2 A3 (off) = S3 > max2

    All programs +1:The burner requirement (A3) only occurs via sensorS4.

    Output A3 switches on when S4 falls below threshold min2.

    Output A3 switches off (dominant) when S4 exceeds max2.

    A3 (on) = S4 < min2 A3 (off) = S4 > max2

    All programs +2:

    In addition, pump A1 switches between sensors S4 and S2 (such as oil boiler - buffer - tanksystem) when difference diff2is reached.

    Pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1,

    w orS4 is greater than threshold min3 w and S4 is greater than S2 by the difference diff2

    w and S2 has not exceeded max2.

    A1 = (S1 > (S2 + diff1) & S1 > min1 & S2 < max1)or (S4 > (S2 + diff2) & S4 > min3 & S2 < max1)

    All programs +4:

    Output A2 is available as a timer output (without time window always ON).

    required settings:

    diff1 collectorS1 TK S2 A1diff2 see all programs +2min1 switch-on temp. coll. S1 A1min2 burner req. on TK S4 A3max1 limit TK S2 A1max2 burner req. off TK S3 A3

    S1min1

    S2max1

    diff1A1

    burnerA3

    S4 min2S3 max2

    A1A3

    S1

    S2

    S4

    S3

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    18/116

    18

    Solar power system with layered storage tank loading - program 144

    A layered system only makes sense if the speed control is activated!

    Program 144: Solar pumps A1 run when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    The three-way valve A2 switches up when:

    wS3 is greater than the threshold min2w orS3 is greater than S4 by the difference diff2

    w and S4 has not exceeded the threshold max2.

    A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1A2 = (S3 > min2 or S3 > (S4 + diff2)) & S4 < max2

    Program 145:

    IfS4 has reached max2, the quick warm-up phase has been completed, and the speed

    control is thus blocked optimal efficiency.

    Program 146:

    The speed control is generally blocked if the three-way valve is switched down ( A2 = off).In this case, the priority control is active to allow the upper layer of the storage tank to beaccessed when irradiation is great enough.

    All programs +4:

    The output A3 is available as a timer output (without time window always ON).

    S1 S3min1 min2

    S2 S4max1 max2

    diff2A2

    diff1A1

    required settings:

    diff1 collectorS1 TK S2 A1diff2 supply line S3 TK S4 A2min1 switch-on temp. coll. S1 A1min2 switch-on temp. supply l. S3 A2max1 limit TK S2 A1max2 limit TK S4 A2

    S2S4

    A1

    S3 A2

    A1

    S1

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    19/116

    19

    Inserting two boilers into the heating system - program 160

    Program 160: Feed pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    Feed pump A2 runs when:

    wS5 is greater than the threshold min2w and S5 is greater than S3 by the difference diff2

    w and S3 has not exceeded the threshold max2.

    Output A3 switches on when S4 falls below threshold min3.

    Output A3 switches off (dominant) when S3 exceeds max3.

    A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1A2 = S5 > (S3 + diff2) & S5 > min2 & S3 < max2

    A3 (on) = S4 < min3 A3 (off) = S3 > max3

    All programs +1:The burner requirement (A3) only occurs via sensorS4.

    Output A3 switches on when S4 falls below threshold min3.

    Output A3 switches off (dominant) when S4 exceeds max3.

    A3 (on) = S4 < min3 A3 (off) = S4 > max3

    All programs +2:

    The burner requirement (A3) is only admissible if pump A1 is switched off.

    required settings:

    diff1 boilerS1 TK S2 A1diff2 boilerS5 TK S3 A2

    min1 switch-on temp. boilerS1 A1min2 switch-on temp. boilerS5 A2min3 burner req. on TK S4 A3max1 limit TK S2 A1max2 limit TK S3 A2max3 burner req. off TK S3 A3

    S1 S5min1 min2

    S2 S3max1 max2

    burnerA3

    S4 min3

    S3 max3diff2A2

    diff1A1

    A1 A2S1

    S2S3S5

    A3

    S4

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    20/116

    20

    All programs +4 (only makes sense together with all programs +2):

    Feed pump A2 runs when:

    wS5 is greater than the threshold min2w and S5 is greater than S4 by the difference diff2

    w and S4 has not exceeded the threshold max2.

    All programs +8 (Additional used SensorS6!):

    If S6 exceeds the threshold max1 (and not used with A1!), burner requirement A3 isswitched off. A flue gas thermostat can replace sensorS6, or the sensor can be installed onthe pipe using a metal strip so that the maximum temperature does not exceed 120C (dueto heat conduction as well as cooling through the metal strip).

    Solar power system with 2 consumers and feed pump function - program 176

    Program 176: Pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    Pump A2 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S3 by the difference diff2

    w and S3 has not exceeded the threshold max2.

    S1 S5min1 min2

    S2 S3 S4

    max1 max2 max3

    diff2A2

    diff1A1

    diff3A3

    required settings:

    diff1 coll. S1 TK1 S2 A1diff2 coll. S1 TK2 S3 A2diff3 TK2 S5 TK1 S4 A3min1 switch-on temp. coll. S1 A1, A2min2 switch-on temp. TK2 S5 A3min3 see all programs +4max1 limit TK1 S2 A1max2 limit TK2 S3 A2max3 limit TK1 S4 A3

    A1A2 S2S3

    S4S5A3

    S1

    TK2 TK1

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    21/116

    21

    The feed pump A3 runs when:

    wS5 is greater than the threshold min2w and S5 is greater than S4 by the difference diff3

    w and S4 has not exceeded the threshold max3.

    A1 = S1 > (S2 + diff1) & S2 < max1 & S1 > min1A2 = S1 > (S3 + diff2) & S3 < max2 & S1 > min1A3 = S5 > (S4 + diff3) & S4 < max3 & S5 > min2

    All programs +1:

    Instead of the two pumps, one pump and a three-way valve are used (pump-valve system).The speed control (if activated) only affects loop 1.

    A1 ... common pump A2 ... valve (A2/S has power when loading tank TK2)

    All programs +2:

    If both tanks have reached their maximum temperature due to the solar power system,pumps A1 and A3 are switched on (reverse cooling function).

    All programs +4:

    Both solar loops have separate switch-on thresholds at S1:

    Output A1 retains min1, and A2 switches at min3.

    The priorities forTK1 and TK2 can be set in the parameter menu underPA. In addition, asolar priority function can be set for this diagram in the menu PRIOR (see solar priorities onpage 88 for more details).

    Solar power system with 2 consumers and feed pump (heating boiler) - program 192

    S1 S4min1 min2

    S2 S3max1 max2max3

    diff2

    A2diff1

    A1

    diff3A3

    required settings:

    diff1 ... coll. S1 TK1 S2 A1diff2 ... coll. S1 TK2 S3 A2diff3 ... boilerS4 TK2 S3 A3min1 ... switch-on temp. Coll. S1 A1, A2min2 ... switch-on temp. boilerS4 A3min3 ... see all programs +4

    max1 ... limit TK1 S2 A1max2 ... limit TK2 S3 A2max3 ... limit TK2 S3 A3

    S1

    S2S3S4 A3

    TK1TK2

    A1A2

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    22/116

    22

    Program 192: Pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    Pump A2 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S3 by the difference diff2

    w and S3 has not exceeded the threshold max2.

    The feed pump A3 runs when:

    wS4 is greater than the threshold min2w and S4 is greater than S3 by the difference diff3

    w and S3 has not exceeded the threshold max3.

    A1 = S1 > (S2 + diff1) & S2 < max1 & S1 > min1A2 = S1 > (S3 + diff2) & S3 < max2 & S1 > min1A3 = S4 > (S3 + diff3) & S3 < max3 & S4 > min2

    All programs +1:

    Instead of the two pumps, one pump and a three-way valve are used (pump-valve system).The speed control (if activated) only affects loop 1.

    A1 ... common pump A2 ... valve (A2/S has power when loading tank TK2)

    All programs +2:

    If both tanks have reached their maximum temperature due to the solar power system,pumps A2 and A3 are switched on (reverse cooling function).

    All programs +4:

    Both solar loops have separate switch-on thresholds at S1:output A1 retains min1, and A2 switches at min3.

    The priorities forTK1 and TK2 can be set in the parameter menu underPA. In addition, asolar priority function can be set for this diagram in the menu PRIOR (see solar priorities onpage 88 for more details).

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    23/116

    23

    Solar power system with 2 consumers and burner requirement - program 208

    Program 208: Pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    Pump A2 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S3 by the difference diff2

    w and S3 has not exceeded the threshold max2.

    Output A3 switches on when S5 falls below threshold min2.

    Output A3 switches off (dominant) when S4 exceeds max3.

    A1 = S1 > (S2 + diff1) & S2 < max1 & S1 > min1A2 = S1 > (S3 + diff2) & S3 < max2 & S1 > min1

    A3 (on) = S5 < min2 A3 (off) = S4 > max3

    All programs +1:

    Instead of the two pumps, one pump and a three-way valve are used (pump-valve system).The speed control (if activated) only affects loop 1.

    A1 ... common pump A2 ... valve (A2/S has power when loading tank TK2)

    All programs +2:The burner requirement (A3) only occurs via sensorS5.

    Output A3 switches on when: w S5 falls short of threshold min2.

    Output A3 switches off (dominant) when: w S5 falls short of threshold max3.

    A3 (on) = S5 < min2 A3 (off) = S5 > max3

    required settings:

    diff1 coll. S1 TK1 S2 A1diff2 coll. S1 TK2 S3 A2min1 switch-on temp. coll. S1 A1, A2min2 burner req. on TK2 S5 A3min3 see all programs +4max1 limit TK1 S2 A1max2 limit TK2 S3 A2max3 burner req. off TK2 S4 A3

    S1min1

    S2 S3max1 max2

    diff2A2

    diff1A1

    burnerA3

    S5 min2

    S4 max3

    S4

    A3

    S5TK2 TK1

    S1

    S2S3 A1A2

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    24/116

    24

    All programs +4:

    Both solar loops have separate switch-on thresholds at S1:

    Output A1 retains min1, and A2 switches at min3.

    The priorities forTK1 and TK2 can be set in the parameter menu underPA. In addition, a

    solar priority function can be set for this diagram in the menu PRIOR (see solar priorities onpage 88 for more details).

    Solar power system with 3 consumers - program 224

    Program 224: Pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    Pump A2 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S3 by the difference diff2

    w and S3 has not exceeded the threshold max2.

    S1min1

    S2 S3 S4max1 max2 max3

    diff2

    A2

    diff1A1

    diff3A3

    required settings:

    diff1 coll. S1 TK1 S2 A1diff2 coll. S1 TK2 S3 A2diff3 coll. S1 TK3 S4 A3min1 switch-on temp. coll. S1A1, A2, A3min2 see all programs +8min3 see all programs +8max1 limit TK1 S2 A1max2 limit TK2 S3 A2max3 limit TK3 S4 A3

    A3

    S1

    S4

    A3TK3A1

    A2

    S2 S3

    TK2

    TK1

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    25/116

    25

    Pump A3 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S4 by the difference diff3

    w and S4 has not exceeded the threshold max3.

    A1 = S1 > (S2 + diff1) & S2 < max1 & S1 > min1A2 = S1 > (S3 + diff2) & S3 < max2 & S1 > min1A3 = S1 > (S4 + diff3) & S4 < max3 & S1 > min1

    Program 225:

    Instead of the two pumps A1 and A2, one pump and a three-way valve are used (pump-valve system). The speed control (if activated) only affects loop 1.

    A1 ... common pump A2 ... valve (A2/S has power when loading tank TK2)

    Program 226:

    Instead of the two pumps A1 and A2, one pump and a three-way valve are used (pump-valve system between TK1 and TK3). The speed control (if activated) only affects loop 1.

    A1 ... common pump A3 ... valve (A3/S has power when loading tank TK3)

    Program 227:

    All three tanks are fed via one pump (A1) and two serially connected three-way valves (A2and A3). When both valves have no power, TK1 is fed. The speed control (if activated) onlyaffects loop 1.

    A1 ... common pump

    A2 ... valve (A2/S has power when loading TK2)

    A3 ... valve (A3/S has power when loading TK3)

    All programs +4:

    If all of the tanks have reached their maximum temperature, loading to TK2 continuesregardless ofmax2.

    All programs +8:

    All solar loops have separate switch-on thresholds at S1:

    Output A1 retains min1, but A2 switches at min2 and A3 at min3.

    The priorities forTK1 and TK2 can be set in the parameter menu underPA. In addition, asolar priority function can be set for this diagram in the menu PRIOR (see solar priorities onpage 88 for more details).

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    26/116

    26

    Solar power system with 2 collector panels and 2 consumers - program 240

    A1, A2... pumps A3. switch-over valve (A3/S has power when loading TK2)

    Program 240: Pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S3 by the difference diff1

    wand S3 has not exceeded max1wand valve A3 is switched off

    or

    wS1 is greater than the threshold min1w and S1 is greater than S4 by the difference diff2

    wand S4 has not exceeded max2wand valve A3 is switched on.

    Pump A2 runs when:

    wS2 is greater than the threshold min2w and S2 is greater than S3 by the difference diff1

    wand S3 has not exceeded max1wand valve A3 is switched offor

    wS2 is greater than the threshold min2w and S2 is greater than S4 by the difference diff2

    wand S4 has not exceeded max2wand valve A3 is switched on.

    Valve A3 switches relative to the set priority (solar priority)

    A1 = S1 > (S3 + diff1) & S3 < max1 & S1 > min1 & (A3 = off)or S1 > (S4 + diff1) & S4 < max2 & S1 > min1 & (A3 = on)

    A2 = S2 > (S3 + diff2) & S3 < max1 & S2 > min2 & (A3 = off)

    or S2 > (S4 + diff2) & S4 < max2 & S2 > min2 & (A3 = on)

    A3 = relative to the set priority

    A1 A2

    S1 S2

    S3 S4A3

    TK2TK1

    S1 S2min1 min2

    S3 S4max1 max2

    diff2A2, A3diff1

    A1

    diff1A2

    diff2A1, A3

    required settings:

    diff1 coll.1 S1 TK1 S3 A1 coll.2 S2 TK1 S3 A2

    diff2 coll.1 S1 TK2 S4 A1, A3 coll.2 S2 TK2 S4 A2, A3

    diff3 see all programs +1min1 switch-on temp. coll.1 S1 A1min2 switch-on temp. coll.2 S2 A2max1 limit TK1 S3 A1, A2max2 limit TK2 S4 A1, A2, A3

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    27/116

    27

    All programs +1:

    If the difference between collector sensors S1 and S2 exceeds the difference diff3, thecolder collector is switched off. This prevents heat from being lost in the colder collectorwhen temperatures are mixed.

    WARNING:

    In this diagram, priority does not refer to the pumps, but rather to the tanks. The prioritiesforTK1, TK2 and TK3 can be set in the parameter menu under PA. In addition, a solarpriority function can be set for this diagram in the menu PRIOR (see solar priorities on page88 for more details).

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    28/116

    28

    Solar power system with 2 collector panels (1 pump, 2 stop valves) - program 256

    Program 256: Pump A1 runs when:

    wValve A2 is switched on wor valve A3 is switched on.

    Valve A2 switches on when:

    wS1 is greater than the threshold min1w and S1 is greater than S3 by the difference diff1

    w and S3 has not exceeded the threshold max1.

    Valve A3 switches on when:

    wS2 is greater than the threshold min2w and S2 is greater than S3 by the difference diff1

    w and S3 has not exceeded the threshold max1.

    A1 = (A2 = on) or (A3 = on)A2 = S1> (S3 + diff1) & S1 > min1 & S3 < max1

    A3 = S2> (S3 + diff1) & S2 > min2 & S3 < max1

    All programs +1:

    If the difference between collector sensors S1 and S2 exceeds the difference diff3, thecolder collector is switched off. This prevents heat from being lost in the colder collectorwhen temperatures are mixed.

    S1 S2min1 min2

    S3

    max1

    diff1A1, A3

    diff1A1, A2

    required settings:

    diff1 coll.1 S1 TK S3 A1, A2 coll.2 S2 TK S3 A1, A3

    diff3 see all programs +1min1 switch-on temp. coll.1 S1 A1, A2min2 switch-on temp. coll.2 S2 A1, A3max1 limit TK S3 A1, A2, A3

    S1 S2

    S3A1

    A2 A3

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    29/116

    29

    Solar power system with 2 collector panels and feed pump function - program 272

    Program 272: Pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S3 by the difference diff1

    w and S3 has not exceeded the threshold max1.

    Pump A2 runs when:

    wS2 is greater than the threshold min2w and S2 is greater than S3 by the difference diff1

    w and S3 has not exceeded the threshold max1.

    The feed pump A3 runs when:

    wS5 is greater than the threshold min3w and S5 is greater than S4 by the difference diff2

    w and S4 has not exceeded the threshold max2.

    A1 = S1 > (S3 + diff1) & S3 < max1 & S1 > min1A2 = S2 > (S3 + diff1) & S3 < max1 & S2 > min2A3 = S5 > (S4 + diff2) & S4 < max3 & S5 > min3

    All programs +1:

    If the difference between collector sensors S1 and S2 exceeds the difference diff3, thecolder collector is switched off. This prevents heat from being lost in the colder collectorwhen temperatures are mixed.

    required settings:

    diff1 coll.1 S1 TK1 S3 A1 coll.2 S2 TK1 S3 A2

    diff2 TK1 S5 TK2 S4 A3diff3 see all programs +1min1 switch-on temp. coll.1 S1A1min2 switch-on temp. coll.2 S2A2min3 switch-on temp. TK1 S5 A3max1 limit TK1 S3 A1, A2max2 limit TK2 S4 A3

    S1 S2 S5min1 min2 min3

    S3 S4max1 max2

    diff1

    A2

    diff1

    A1

    diff2

    A3

    A1 A2

    S1 S2

    S3

    A3

    TK2TK1

    S5

    S4

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    30/116

    30

    Solar power system with 2 collector panels and burner requirement - program 288

    Program 288: Pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S3 by the difference diff1

    w and S3 has not exceeded the threshold max1.

    Pump A2 runs when:

    wS2 is greater than the threshold min2w and S2 is greater than S3 by the difference diff1

    w and S3 has not exceeded the threshold max1.

    Output A3 switches on when: S5 falls short of threshold min3.

    Output A3 switches off (dominant) when S4 exceeds max2.

    A1 = S1 > (S3 + diff1) & S3 < max1 & S1 > min1A2 = S2 > (S3 + diff1) & S3 < max1 & S2 > min2

    A3 (on) = S5 < min3 A3 (off) = S4 > max2

    All programs +1:

    If the difference between collector sensors S1 and S2 exceeds the difference diff3, thecolder collector is switched off. This prevents heat from being lost in the colder collectorwhen temperatures are mixed.

    All programs +2:

    The burner requirement (A3) only occurs via sensorS5.

    Output A3 switches on when S5 falls below threshold min3.

    Output A3 switches off (dominant) when S5 exceeds max2.

    A3 (on) = S5 < min3 A3 (off) = S5 > max2

    S1 S2min1 min2

    S3

    max1

    diff1A2

    burnerA3

    S5 min3

    S4 max2

    required settings:

    diff1 coll.1 S1 TK S3 A1 coll.2 S2 TK S3 A2

    diff3 see all programs +1min1 switch-on temp. coll.1 S1 A1min2 switch-on temp. coll.2 S2 A2min3 burner req. on TK S5 A3max1 limit TK S3 A1, A2max2 burner re . off TK S4 A3

    diff1A1

    S1 S2

    S3A1 A2

    S5

    A3

    S4

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    31/116

    31

    Solar power system with 2 collector panels and feed pump (heating boiler) pr. 304

    Program 304: Pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S3 by the difference diff1w and S3 has not exceeded the threshold max1.

    Pump A2 runs when:

    wS2 is greater than the threshold min2w and S2 is greater than S3 by the difference diff1

    w and S3 has not exceeded the threshold max1.

    The feed pump A3 runs when:

    wS4 is greater than the threshold min3w and S4 is greater than S3 by the difference diff2

    w and S3 has not exceeded the threshold max2.

    A1 = S1 > (S3 + diff1) & S3 < max1 & S1 > min1A2 = S2 > (S3 + diff1) & S3 < max1 & S2 > min2A3 = S4 > (S3 + diff2) & S3 < max2 & S4 > min3

    All programs +1:

    If the difference between collector sensors S1 and S2 exceeds the difference diff3, thecolder collector is switched off. This prevents heat from being lost in the colder collectorwhen temperatures are mixed.

    required settings:

    diff1 coll.1 S1 TK S3 A1

    coll.2 S2 TK S3 A2diff2 boilerS4 TK S3 A3diff3 see all programs +1min1 switch-on temp. coll.1 S1 A1min2 switch-on temp. coll.2 S2 A2min3 switch-on temp. boilerS4 A3max1 limit TK S3 A1, A2max2 limit TK S3 A3

    S1 S2 S4min1 min2 min3

    S3max1

    max2

    diff1A2diff1

    A1

    diff2

    A3

    S1 S2

    S3A1 A2

    A3 S4

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    32/116

    32

    Layered storage tank and one independent feed pump - program 320

    A layered system only makes sense if the speed control is activated!

    Program 320: Solar pumps A1 run when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1w and S2 has not exceeded the threshold max1.

    The three-way valve A2 switches up when:

    wS5 is greater than the threshold min2w and S5 is greater than S4 by the difference diff2

    w and S4 has not exceeded the threshold max2.

    The feed pump A3 runs when:

    wS6 is greater than the threshold min3w and S6 is greater than S3 by the difference diff3

    w and S3 has not exceeded the threshold max3.

    A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1A2 = (S5 > min2 or S5 > (S4 + diff2)) & S4 < max2A3 = S6 > (S3 + diff3) & S6 > min3 & S3 < max3

    Program 321:

    IfS4 has reached max2, the quick warm-up phase has been completed, and the speed

    control is thus blocked optimal efficiency.

    Program 322:

    The speed control is generally blocked if the three-way valve is switched down ( A2 = off).

    In this case, the priority control is active to allow the upper layer of the storage tank to beaccessed when irradiation is great enough.

    S1 S5 S6min1 min2 min3

    S2 S4 S3

    max1 max2 max3

    diff3A3

    diff1A1

    diff2A2

    required settings:

    diff1 coll. S1 TK S2 A1diff2 supply l. S5 TK S4 A2diff3 boilerS6 TK S3 A3min1 switch-on temp. coll. S1 A1min2 switch-on temp.ssl. S5 A2min3 switch-on temp. boilerS6 A3max1 limit TK S2 A1max2 limit TK S4 A2max3 limit TK S3 A3

    S2

    A3S6

    S4

    A1

    S5 A2

    A1

    S1

    S3

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    33/116

    33

    Layered storage tank and feed pump (heating boiler) - program 336

    A layered system only makes sense if the speed control is activated!

    Program 336: Solar pumps A1 run when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    The three-way valve A2 switches up when:

    wS5 is greater than the threshold min2w and S5 is greater than S4 by the difference diff2

    w and S4 has not exceeded the threshold max2.

    The feed pump A3 runs when:

    wS3 is greater than the threshold min3w and S3 is greater than S2 by the difference diff3

    w and S2 has not exceeded the threshold max3.

    A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1A2 = (S5 > min2 or S5 > (S4 + diff2)) & S4 < max2A3 = S3 > (S2 + diff3) & S3 > min3 & S2 < max3

    Program 337:

    IfS4 has reached max2, the quick warm-up phase has been completed, and the speed

    control is thus blocked optimal efficiency.

    Program 338:

    The speed control is generally blocked if the three-way valve is switched down ( A2 = off).

    In this case, the priority control is active to allow the upper layer of the storage tank to beaccessed when irradiation is great enough.

    S1 S3 S5min1 min3 min2

    S2 S4max1 max2max3

    diff3

    A3

    diff1

    A1

    diff2A2

    required settings:

    diff1 coll. S1 TK S2 A1diff2 supply l. S5 TK S4 A2diff3 boilerS3 TK S2 A3min1 switch-on temp. coll. S1 A1min2 switch-on temp.ssl. S5 A2min3 switch-on temp. boilerS3 A3max1 limit TK S2 A1max2 limit TK S4 A2max3 limit TK S2 A3

    S3A3S4

    S2A1

    S5 A2

    A1

    S1

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    34/116

    34

    Layered tank and burner requirement - program 352

    A layered system only makes sense if the speed control is activated!

    Program 352: Solar pumps A1 run when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    The three-way valve A2 switches up when:

    wS5 is greater than the threshold min2w and S5 is greater than S4 by the difference diff2

    w and S4 has not exceeded the threshold max2.

    Output A3 switches on when S4 falls below min3.

    Output A3 switches off (dominant) when S3 exceeds max3.

    A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1A2 = (S5 > min2 or S5 > (S4 + diff2)) & S4 < max2

    A3 (on) = S4 < min3 A3 (off) = S3 > max3

    Program 353:

    IfS4 has reached max2, the quick warm-up phase has been completed, and the speed

    control is thus blocked optimal efficiency.

    Program 354:

    The speed control is generally blocked if the three-way valve is switched down ( A2 = off).In this case, the priority control is active to allow the upper layer of the storage tank to beaccessed when irradiation is great enough.

    required settings:

    diff1 coll. S1 TK S2 A1diff2 supply l. S5 TK S4 A2min1 switch-on temp. coll. S1 A1min2 switch-on temp.ssl. S5 A2min3 burner req. on TK S4 A3max1 limit TK S2 A1max2 limit TK S4 A2max3 burner re . off TK S3 A3

    S1 S5min1 min2

    S2 S4

    max1 max2

    diff2A2

    diff1A1

    burnerA3

    S4 min3

    S3 max3

    S2

    S4S3

    A3A1

    S5 A2A1

    S1

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    35/116

    35

    All programs +4:

    The burner requirement (A3) only occurs via sensorS4.

    Output A3 switches on when: w S4 falls short of threshold min3.

    Output A3 switches off (dominant) when: w S4 falls short of threshold max3.

    A3 (on) = S4 < min3 A3 (off) = S4 > max2

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    36/116

    36

    Layered tank and feed pump function - program 368

    A layered system only makes sense if the speed control is activated!

    Program 368: Solar pumps A1 run when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    The three-way valve A2 switches up when:

    wS5 is greater than the threshold min2w and S5 is greater than S4 by the difference diff2

    w and S4 has not exceeded the threshold max2.

    The feed pump A3 runs when:

    wS4 is greater than the threshold min3w and S4 is greater than S3 by the difference diff3

    w and S3 has not exceeded the threshold max3.

    A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1A2 = (S5 > min2 or S5 > (S4 + diff2)) & S4 < max2A3 = S4 > (S3 + diff3) & S4 > min3 & S3 < max3

    Program 369:

    IfS4 has reached max2, the quick warm-up phase has been completed, and the speed

    control is thus blocked optimal efficiency.

    Program 370:

    The speed control is generally blocked if the three-way valve is switched down ( A2 = off).In this case, the priority control is active to allow the upper layer of the storage tank to beaccessed when irradiation is great enough.

    S1 S5min1 min2

    S2 S4max1 max2

    min3

    S3max3

    required settings:

    diff1 coll. S1 TK1 S2 A1diff2 supply l. S5 TK1 S4 A2diff3 TK1 S4 TK2 S3 A3min1 switch-on temp. coll. S1 A1min2 switch-on temp.ssl. S5 A2min3 switch-on temp. TK1 S4 A3max1 limit TK1 S2 A1max2 limit TK1 S4 A2max3 limit TK2 S3 A3diff3

    A3

    diff1A1

    diff2A2

    TK1

    S2

    S4S3A3

    TK2

    A1

    S5 A2

    A1

    S1

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    37/116

    37

    Layered storage with bypass function - program 384

    A layered system only makes sense if the speed control is activated!

    Program 384: Pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    The three-way valve A2 switches up when:

    wS5 is greater than the threshold min2w and S5 is greater than S4 by the difference diff2

    w and S4 has not exceeded the threshold max2.

    The feed pump A3 runs when:

    w S3 is greater than S2 by diff3wand pump A1 is running.

    A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1

    A2 = (S5 > min2 or S5 > (S4 + diff2)) & S4 < max2A3 = S3 > (S2 + diff3) & (A1 = on)

    Program 385:

    IfS4 has reached max2, the quick warm-up phase has been completed, and the speed

    control is thus blocked optimal efficiency.

    Program 386:

    The speed control is generally blocked if the three-way valve is switched down ( A2 = off).In this case, the priority control is active to allow the upper layer of the storage tank to beaccessed when irradiation is great enough.

    S1 S3 S5min1 min3 min2

    S2 S4max1 max2max3

    diff3A3

    diff1A1

    diff2A2

    required settings:

    diff1 coll. S1 TK S2 A1diff2 supply l.1 S5 TK S4 A2

    diff3 supply l.2 S3 TK S2 A3min1 switch-on temp. coll. S1 A1min2 switch-on temp.ssl. 1 S5 A2min3 switch-on temp.ssl. 2 S3 A3max1 limit TK S2 A1max2 limit TK S4 A2max3 limit TK S2 A3

    S2

    S4S3

    A3A1

    S5 A2

    S1

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    38/116

    38

    Solar power system with 1 consumer and 2 feed pump functions - program 400

    Program 400: Pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    The feed pump A2 runs when:

    wS3 is greater than the threshold min2w and S3 is greater than S4 by the difference diff2

    w and S4 has not exceeded the threshold max2.

    The feed pump A3 runs when:

    wS3 is greater than the threshold min2w and S3 is greater than S5 by the difference diff3w and S5 has not exceeded the threshold max3.

    A1 = S1 > (S2 + diff1) & S2 < max1 & S1 > min1A2 = S3 > (S4 + diff2) & S4 < max2 & S3 > min2A3 = S3 > (S5 + diff3) & S5 < max3 & S4 > min2

    All programs +1:Instead of the two pumps A2 and A3, one pump and a three-way valve are used (pump-valve system).

    A2 ... common pump A3 ... valve (A2/S has power when loading tank TK3)

    S1 S3min1 min2

    S2 S4 S5max1 max2 max3

    diff2A2

    diff1A1

    diff3A3

    required settings:

    diff1 coll. S1 TK1 S2 A1diff2 TK1 S3 TK2 S4 A2diff3 TK1 S3 TK3 S5 A3min1 switch-on temp. coll. S1 A1min2 switch-on temp. TK1 S3 A2, A3min3 see all programs +2max1 limit TK1 S2 A1max2 limit TK2 S4 A2max3 limit TK3 S5 A3

    S1

    S2A1

    S3

    A2A3

    S5S4

    TK1TK2

    TK3

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    39/116

    39

    All programs +2:

    Both feed pump loops have separate switch-on thresholds at S3:

    output A2 retains min2, and A3 switches at min3.

    The priorities forTK1 and TK2 can be set in the parameter menu underPA. In addition, asolar priority function can be set for this diagram in the menu PRIOR (see solar priorities on

    page 88 for more details).

    1 consumer, 2 feed pump functions, and burner requirement - program 416

    Program 416: Feed pump A1 runs when:

    wS4 is greater than the threshold min1w and S4 is greater than S1 by the difference diff1

    w and S1 has not exceeded the threshold max1.

    The feed pump A2 runs when:

    wS4 is greater than the threshold min1w and S4 is greater than S2 by the difference diff2

    w and S2 has not exceeded the threshold max2.

    Output A3 switches on when S4 falls below threshold min2.

    Output A3 switches off (dominant) when S3 exceeds max3.

    A1 = S4 > (S1 + diff1) & S1 < max1 & S4 > min1A2 = S4 > (S2 + diff1) & S2 < max2 & S4 > min1

    A3 (on) = S4 < min2 A3 (off) = S3 > max3

    required settings:

    diff1 TK3 S4 TK1 S1 A1

    diff2 TK3 S4 TK2 S2 A2diff3 see all programs +2min1 switch-on temp. TK3. S4 A1, A2min2 burner req. on TK3 S4 A3min3 see all programs +8max1 limit TK1 S1 A1max2 limit TK2 S2 A2max3 burner req. off TK3 S3 A3

    S4min1

    S1 S2max1 max2

    diff2A2

    diff1A1

    burnerA3

    S4 min2S3 max3

    S3

    A2A3

    S5

    S4

    S1S2

    A1S3

    TK1TK3 TK2

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    40/116

    40

    All programs +1:Instead of the two pumps A1 and A2, one pump and a three-way valve are used (pump-valve system).

    A2 ... common pump A3 ... valve (A2/S has power when loading tank TK2)

    All programs +2:

    In addition, the feed pump A1 switches on when the temperature of the tank S1 (TK1)varies by diff3 from the temperature of the burner.

    In addition, the feed pump A2 switches on when the temperature of the tank S2 (TK2)varies by diff3 from the temperature of the burner.

    Pump A1 runs when:

    wS4 is greater than the threshold min1w and S4 is greater than S1 by the difference diff1

    w and S1 has not exceeded the threshold max1.

    or

    wS5 is greater than the threshold min3w and S5 is greater than S1 by the difference diff3

    w and S1 has not exceeded the threshold max1.

    Feed pump A2 runs when:

    wS4 is greater than the threshold min1w and S4 is greater than S2 by the difference diff2

    w and S2 has not exceeded the threshold max2.

    or

    wS5 is greater than the threshold min3w and S5 is greater than S2 by the difference diff3

    w and S2 has not exceeded the threshold max2.

    A1 = (S4 > (S1 + diff1) & S4 > min1 & S1 < max1)

    or (S5 > (S1 + diff3) & S5 > min3 & S1 < max1)

    A2 = (S4 > (S2 + diff2) & S4 > min1 & S2 < max2)

    or (S5 > (S2 + diff3) & S5 > min3 & S2 < max2)

    All programs +4:

    The burner requirement (A3) only occurs via sensorS4.

    Output A3 switches on when: ? S4 falls short of threshold min2.

    Output A3 switches off (dominant) when: ? S4 falls short of threshold max3.

    A3 (on) = S4 < min2 A3 (off) = S4 > max3

    All programs +8: (Cannot be used with +2!)

    Both feed pump loops have separate switch-on thresholds at S4:

    output A1 retains min1, and A2 switches at min3.

    WARNING:

    The priorities between TK1 and TK2 can be set in the parameter menu underPA.

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    41/116

    41

    Solar power system, burner requirement, and one feed pump - program 432

    Program 432: Pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    The feed pump A2 runs when:wS3 is greater than the threshold min2w and S3 is greater than S4 by the difference diff2

    w and S4 has not exceeded the threshold max2.

    Output A3 switches on when S5 falls below threshold min3.

    Output A3 switches off (dominant) when S4 exceeds max3.

    A1 = S1 > (S2 + diff1) & S2 < max1 & S1 > min1A2 = S3 > (S4 + diff2) & S4 < max2 & S3 > min2

    A3 (on) = S5 < min3 A3 (off) = S4 > max3

    required settings:

    diff1 coll. S1 TK S2 A1diff2 boilerS3 TK S4 A2min1 switch-on temp. coll. S1 A1

    min2 switch-on temp. boilerS3 A2min3 burner req. on TK S5 A3max1 limit TK S2 A1max2 limit TK S4 A2max3 burner re . off TK S4 A3

    S1 S3min1 min2

    S2 S4max1 max2

    diff2

    A2

    diff1

    A1

    burnerA3

    S5 min3

    S4 max3

    A1A2

    S1

    S2S3 S4

    S5

    A3

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    42/116

    42

    Program 433:

    Pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    The feed pump A2 runs when:

    wS3 is greater than the threshold min2w and S3 is greater than S2 by the difference diff2

    w and S2 has not exceeded the threshold max2.

    Output A3 switches on when S5 falls below threshold min3.

    Output A3 switches off (dominant) when S4 exceeds max3.

    A1 = S1 > (S2 + diff1) & S2 < max1 & S1 > min1A2 = S3 > (S2 + diff2) & S2 < max2 & S3 > min2

    A3 (on) = S5 < min3 A3 (off) = S4 > max3

    All programs +2:

    The burner requirement (A3) only occurs via sensorS5.

    Output A3 switches on when S5 falls below threshold min3.

    Output A3 switches off (dominant) when S5 exceeds max3.

    A3 (on) = S5 < min3 A3 (off) = S5 > max3

    S1 S3min1 min2

    S2max1max2

    diff2

    A2diff1

    A1

    burnerA3

    S5 min3S4 max3

    required settings:

    diff1 coll. S1 TK S2 A1diff2 boilerS3 TK S2 A2min1 switch-on temp. coll.1 S1 A1min2 switch-on temp. boiler 2 S3 A2min3 burner req. on TK S5 A3max1 limit TK S2 A1max2 limit TK S2 A2max3 burner req. off TK S4 A3

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    43/116

    43

    Burner requirement and 2 feed pump functions - program 448

    Program 448: Feed pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    The feed pump A2 runs when:

    wS5 is greater than the threshold min2w and S5 is greater than S3 by the difference diff2

    w and S3 has not exceeded the threshold max2.

    Output A3 switches on when S5 falls below threshold min3.

    Output A3 switches off (dominant) when S4 exceeds max3.

    A1 = S1 > (S2 + diff1) & S2 < max1 & S1 > min1A2 = S5 > (S3 + diff2) & S3 < max2 & S5 > min2

    A3 (on) = S5 < min3 A3 (off) = S4 > max3

    required settings:

    diff1 boilerS1 TK1 S2 A1diff2 TK1 S5 TK2 S3 A2diff3 see all programs +2

    min1 switch-on temp. boilerS1 A1min2 switch-on temp. TK1 S5 A2min3 burner req. on TK1 S5 A3max1 limit TK1 S2 A1max2 limit TK2 S3 A2max3 burner req. off TK1 S4 A3

    S1 S5min1 min2

    S2 S3

    max1 max2

    diff2

    A2

    diff1

    A1

    burnerA3

    S5 min3S4 max3

    A2S1

    A3S3

    S2S4S5

    TK2TK1

    A1

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    44/116

    44

    Program 449:

    Feed pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S4 by the difference diff1

    w and S4 has not exceeded the threshold max1.

    Feed pump A2 runs when:

    wS5 is greater than the threshold min2w and S5 is greater than S3 by the difference diff2

    w and S3 has not exceeded the threshold max2.

    Output A3 switches on when S5 falls below threshold min3.

    Output A3 switches off (dominant) when S4 exceeds max3.

    A1 = S1 > (S4 + diff1) & S2 < max1 & S4 > min1A2 = S5 > (S3 + diff2) & S3 < max2 & S5 > min2 A3 (on) = S5 < min3 A3 (off) = S4 > max3

    All programs +2:

    In addition, the feed pump A2 switches on when the temperature of the tank S3 (TK2)varies by diff3 from the temperature of the burner.

    Feed pump A2 runs when:

    wS5 is greater than the threshold min2w and S5 is greater than S3 by the difference diff2

    w and S3 has not exceeded the threshold max2.

    or

    wS1 is greater than the threshold min1w and S1 is greater than S3 by the difference diff3

    w and S3 has not exceeded the threshold max2.

    A2 = (S5 > (S3 + diff2) & S5 > min2 & S3 < max2)or (S1 > (S3 + diff3) & S1 > min1 & S3 < max2)

    All programs +4:

    The burner requirement (A3) only occurs via sensorS5.

    Output A3 switches on when S5 falls below threshold min3.

    Output A3 switches off (dominant) when S5 exceeds max3.

    A3 (on) = S5 < min3 A3 (off) = S5 > max3

    required settings:

    diff1 boilerS1 TK1 S4 A1diff2 TK1 S5 TK2 S3 A2diff3 see all programs +2

    min1 switch-on temp. boilerS1 A1min2 switch-on temp. TK1 S5 A2min3 burner req. on TK1 S5 A3max1 limit TK1 S4 A1max2 limit TK2 S3 A2max3 burner req. off TK1 S4 A3

    S1 S5min1 min2

    S4 S3max1 max2

    diff2

    A2

    diff1

    A1

    burnerA3

    S5 min3

    S4 max3

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    45/116

    45

    Solar power system with 2 consumers and bypass function - program 464

    Program 464: Pump A1 runs when:wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    worS1 is greater than S3 by diff1

    wboth temperature delimiters (S2 > max1 and S3 > max2) have not been exceeded.

    Feed pump A2 runs when:

    wS4 is greater than the threshold min2w and S4 is greater than S2 by the difference diff2

    w and S2 has not exceeded the threshold max1.

    The feed pump A3 runs when:

    wS4 is greater than the threshold min2w and S4 is greater than S3 by the difference diff3w and S3 has not exceeded the threshold max2.

    A1 = (S1 > (S2 + diff1) or S1 > (S3 + diff1)) & S1 > min1

    & (S2 < max1 or S3 < max2)

    A2 = S4 > (S2 + diff2) & S4 > min1 & S2 < max1

    A3 = S4 > (S3 + diff3) & S4 > min1 & S3 < max2

    required settings:

    diff1 coll. S1 TK1 S2 A1 coll. S1 TK2 S3 A1diff2 supply l. S4 TK1 S2 A2diff3 supply l. S4 TK2 S3 A3min1 switch-on temp. coll. S1 A1min2 switch-on temp. ssl. S4 A2, A3min3 see all programs +8max1 limit TK1 S2 A1, A2max2 limit TK2 S3 A1, A3

    S1 S4

    min1 min2

    S2 S3

    max1 max2

    diff1

    A1diff2A2

    diff1A1

    diff3

    A3

    A2A1

    S1

    S3A3

    S2S4

    TK1 TK2

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    46/116

    46

    All programs +1:

    Instead of the two feed pumps A2 and A3, one pump and a three-way valve are used(pump-valve system).

    A2 ... common pump A3 ... valve (A2/S has power when loading tank TK2)

    All programs +2:

    Both secondary solar loops have separate switch-on thresholds at S4:

    output A2 retains min2, and A3 switches at min3.

    All programs +4:

    The two secondary pumps A2 and A3 are only released when primary pump A1 is runningin automatic mode.

    The priorities forTK1 and TK2 can be set in the parameter menu underPA. In addition, asolar priority function can be set for this diagram in the menu PRIOR (see solar priorities onpage 88 for more details).

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    47/116

    47

    2 consumers and 3 feed pump functions - program 480

    Program 480: Feed pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    The feed pump A2 runs when:

    wS3 is greater than the threshold min2w and S3 is greater than S2 by the difference diff2

    w and S2 has not exceeded the threshold max2.

    The feed pump A3 runs when:

    wS5 is greater than the threshold min3w and S5 is greater than S4 by the difference diff3w and S4 has not exceeded the threshold max3.

    A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1

    A2 = S3 > (S2 + diff2) & S3 > min2 & S2 < max2

    A3 = S5 > (S4 + diff3) & S5 > min3 & S4 < max3

    S1 S3 S5min1 min2 min3

    S2 S4max1 max3max2

    diff2

    A2

    diff1

    A1

    diff3

    A3

    required settings:

    diff1 heat source S1 TK1 S2 A1diff2 boilerS3 TK1 S2 A2diff3 TK1 S5 TK2 S4 A3min1 switch-on t. heat source S1 A1min2 switch-on temp. boilerS3 A2min3 switch-on temp. TK1 S5 A3max1 limit TK1 S2 A1max2 limit TK1 S2 A2max3 limit TK2 S4 A3

    S1 A1

    A2A3

    S3S5

    S2S4

    TK1 TK2

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    48/116

    48

    1 consumer and 3 feed pump functions - program 496

    Program 496: Solar pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    The feed pump A2 runs when:

    wS3 is greater than the threshold min2w and S3 is greater than S2 by the difference diff2

    w and S2 has not exceeded the threshold max2.

    The feed pump A3 runs when:

    wS4 is greater than the threshold min3w and S4 is greater than S2 by the difference diff3w and S2 has not exceeded the threshold max3.

    A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1

    A2 = S3 > (S2 + diff2) & S3 > min2 & S2 < max2

    A3 = S4 > (S2 + diff3) & S4 > min3 & S2 < max3

    required settings:

    diff1 coll. S1 TK S2 A1diff2 heat source S3 TK S2 A2diff3 boilerS4 TK S2 A3min1 switch-on temp. coll. S1 A1min2 switch-on t. heat source S3 A2min3 switch-on temp. boilerS4 A3max1 limit TK S2 A1max2 limit TK S2 A2max3 limit TK S2 A3

    S1 S3 S4

    min1 min2 min3

    S2max1max2max3

    diff2

    A2diff1A1

    diff3

    A3

    S3A2

    A3S4

    S1

    A1S2

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    49/116

    49

    3 consumers and 3 feed pumps (3 independent differential loops) - program 512

    Program 512: Pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1w and S2 has not exceeded the threshold max1.

    Feed pump A2 runs when:

    wS3 is greater than the threshold min2w and S3 is greater than S4 by the difference diff2

    w and S4 has not exceeded the threshold max2.

    The feed pump A3 runs when:

    wS5 is greater than the threshold min3w and S5 is greater than S6 by the difference diff3

    w and S6 has not exceeded the threshold max3.

    A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1A2 = S3 > (S4 + diff2) & S3 > min2 & S4 < max2A3 = S5 > (S6 + diff3) & S5 > min3 & S6 < max3

    required settings:

    diff1 coll.1 S1 TK1 S2 A1

    diff2 coll.2 S3 TK2 S4 A2diff3 coll.3 S5 TK3 S6 A3min1 switch-on temp. coll.1 S1 A1min2 switch-on temp. coll.2 S3 A2min3 switch-on temp. coll.3 S5 A3max1 limit TK1 S2 A1max2 limit TK2 S4 A2max3 limit TK3 S6 A3

    S1 S3 S5min1 min2 min3

    S2 S4 S6

    max1 max2 max3

    diff2

    A2diff1

    A1

    diff3

    A3

    S3

    S4A2

    S5

    A3S6

    S1

    S2A1

    TK1 TK2 TK3

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    50/116

    50

    2 independent differential loops and independent burner requirement - program 528

    Program 528: Pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    Feed pump A2 runs when:

    wS3 is greater than the threshold min2w and S3 is greater than S4 by the difference diff2

    w and S4 has not exceeded the threshold max2.

    Output A3 switches on when S6 falls below threshold min3.

    Output A3 switches off (dominant) when S5 exceeds max3.

    A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1A2 = S3 > (S4 + diff2) & S3 > min2 & S4 < max2

    A3 (on) = S6 < min3 A3 (off) = S5 > max3All programs +1:

    The burner requirement (A3) only occurs via sensorS6.

    Output A3 switches on when S6 falls below threshold min3.

    Output A3 switches off (dominant) when S6 exceeds max3.

    A3 (on) = S6 < min3 A3 (off) = S6 > max3

    required settings:

    diff1 coll.1 S1 TK1 S2 A1diff2 coll.2 S3 TK2 S4 A2

    min1 switch-on temp. coll.1 S1 A1min2 switch-on temp. coll.2 S3 A2min3 burner req. on TK3 S6 A3max1 limit TK1 S2 A1max2 limit TK2 S4 A2max3 burner req. off TK3 S5 A3

    S1 S3min1 min2

    S2 S4max1 max2

    diff2

    A2diff1

    A1

    burnerA3

    S6 min3

    S5 max3

    S1

    A3 S5

    S6

    S2A1

    TK1 TK3

    S3

    S4A2

    TK2

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    51/116

    51

    Cascade: S1 S2 S3 S4 - program 544

    Program 544: Solar pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    The feed pump A2 runs when:

    wS2 is greater than the threshold min2w and S2 is greater than S3 by the difference diff2

    w and S3 has not exceeded the threshold max2.

    The feed pump A3 runs when:

    wS3 is greater than the threshold min3w and S3 is greater than S4 by the difference diff3

    w and S4 has not exceeded the threshold max3.

    A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1A2 = S2 > (S3 + diff2) & S2 > min2 & S3 < max2

    A3 = S3 > (S4 + diff3) & S3 > min3 & S4 < max3

    required settings:

    diff1 coll. S1 TK1 S2 A1diff2 TK1 S2 TK2 S3 A2diff3 TK2 S3 TK3 S4 A3min1 switch-on temp. coll S1 A1min2 switch-on temp. TK1 S2 A2min3 switch-on temp. TK2 S3 A3max1 limit TK1 S2 A1max2 limit TK2 S3 A2max3 limit TK3 S4 A3

    S1min1

    max1S2

    min2

    max2S3

    min3

    S4max3

    diff2A2

    diff1A1

    diff3A3

    S1

    S2A1

    A3S3S4

    TK1 TK2 TK3

    A2

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    52/116

    52

    Cascade: S1 S2 / S3 S4 S5 - program 560

    Program 560: Pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    The feed pump A2 runs when:

    wS3 is greater than the threshold min2w and S3 is greater than S4 by the difference diff2w and S4 has not exceeded the threshold max2.

    The feed pump A3 runs when:

    wS4 is greater than the threshold min3w and S4 is greater than S5 by the difference diff3

    w and S5 has not exceeded the threshold max3.

    A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1A2 = S3 > (S4 + diff2) & S3 > min2 & S4 < max2A3 = S4 > (S5 + diff3) & S4 > min3 & S5 < max3

    S1 S3min1 min2

    S2 S4max1 max2

    min3

    S5max3

    diff3A3

    diff1A1

    diff2A2

    required settings:

    diff1 coll. S1 TK1 S2 A1

    diff2 TK1 S3 TK2 S4

    A2diff3 TK2 S4 TK3 S5 A3min1 switch-on temp. coll. S1 A1min2 switch-on temp. TK1 S3 A2min3 switch-on temp. TK2 S4 A3max1 limit TK1 S2 A1max2 limit TK2 S4 A2max3 limit TK3 S5 A3

    S1

    S2A1A3

    S3S5

    TK1 TK3

    S4

    TK2

    A2

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    53/116

    53

    Cascade: S4 S1 S2 + burner requirement - program 576

    Program 576: Feed pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    The feed pump A2 runs when:

    wS4 is greater than the threshold min2w and S4 is greater than S1 by the difference diff2

    w and S1 has not exceeded the threshold max2.

    Output A3 switches on when S4 falls below threshold min3.

    Output A3 switches off (dominant) when S3 exceeds max3.

    A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1A2 = S4 > (S1 + diff2) & S4 > min2 & S1 < max2

    A3 (on) = S4 < min3 A3 (off) = S3 > max3

    All programs +1:

    The burner requirement (A3) only occurs via sensorS4.

    Output A3 switches on when S4 falls below threshold min3.

    Output A3 switches off (dominant) when S4 exceeds max3.

    A3 (on) = S4 < min3 A3 (off) = S4 > max3

    Required settings:

    diff1 TK2 S1 TK3 S2 A1diff2 TK1 S4 TK2 S1 A2

    min1 switch-on temp. TK2 S1

    A1min2 switch-on temp. TK1 S4 A2min3 burner req. on TK1 S4 A3max1 limit TK3 S2 A1max2 limit TK2 S1 A2max3 burner req. off TK1 S3 A3

    S4min2

    S1max2min1

    S2max1

    diff1

    A1

    diff2

    A2

    burnerA3

    S4 min3

    S3 max3

    A1A3 S3

    S4S2

    TK3TK2TK1

    S1A2

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    54/116

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    55/116

    55

    2 generators on 2 consumers + burner requirement - program 608

    No diagram available!

    Program 608: Pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S3 by the difference diff1

    w and S3 has not exceeded the threshold max1.

    or

    wS2 is greater than the threshold min2w and S2 is greater than S3 by the difference diff1

    w and S3 has not exceeded the threshold max1.

    Pump A2 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S4 by the difference diff2

    w and S4 has not exceeded the threshold max1.or

    wS2 is greater than the threshold min2w and S2 is greater than S4 by the difference diff2

    w and S4 has not exceeded the threshold max2.

    Output A3 switches on when S6 falls below threshold min3.

    Output A3 switches off (dominant) when S5 exceeds max3.

    A1 = S1> (S3 + diff1) & S1 > min1 & S3 < max1or S2 > (S3 + diff1) & S2 > min2 & S3 < max1

    A2 = S1 > (S4 + diff2) & S1 > min1 & S4 < max1or S2 > (S4 + diff2) & S2 > min2 & S4 < max1

    A3 (on) = S6 < min3 A3 (off) = S5 > max3

    Program 609:The burner requirement (A3) only occurs via sensorS6.

    Output A3 switches on when S6 falls below threshold min3.

    Output A3 switches off (dominant) when S6 exceeds max3.

    A3 (on) = S6 < min3 A3 (off) = S6 > max3

    S1 S2min1 min2

    S3 S4

    max1 max2

    burnerA3

    S6 min3S5 max3

    required settings:

    diff1 boiler1 S1 TK1 S3 A1 boiler2 S2 TK1 S3 A1

    diff2 boiler1 S1 TK2 S4 A2 boiler2 S2 TK2 S4 A2

    min1 switch-on t. boiler1 S1 A1min2 switch-on t. boiler2 S2 A2min3 burner req. on S6 A3max1 limit TK1 S3 A1max2 limit TK2 S4 A2max3 burner req. offS5 A3

    diff1

    A1

    diff1A1

    diff2A2

    diff2

    A2

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    56/116

    56

    Program 610:As with program 608, but the burner requirement (A3) comes from S2 and S5.

    Output A3 switches on when S2 falls below threshold min3.

    Output A3 switches off (dominant) when S5 exceeds max3.

    A3 (on) = S2 < min3 A3 (off) = S5 > max3

    Program 611:As with program 608, but the burner requirement (A3) comes from sensorS2.

    Output A3 switches on when S2 falls below threshold min3.

    Output A3 switches off (dominant) when S2 exceeds max3.

    A3 (on) = S2 < min3 A3 (off) = S2 > max3

    Program 612:As with program 608, but the burner requirement (A3) comes from S4 and S5.

    Output A3 switches on when S4 falls below threshold min3.

    Output A3 switches off (dominant) when S5 exceeds max3.

    A3 (on) = S4 < min3 A3 (off) = S5 > max3

    Program 613:As with program 608, but the burner requirement (A3) comes from sensorS4.

    Output A3 switches on when S4 falls below threshold min3.

    Output A3 switches off (dominant) when S4 exceeds max3.

    A3 (on) = S4 < min3 A3 (off) = S4 > max3

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    57/116

    57

    Solar power system with one consumer and swimming pool - program 624

    Program 624: Solar pump A1 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    Solar pump A2 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S3 by the difference diff2

    w and S3 has not exceeded the threshold max2.

    Filter pump A3 runs when:wA3 is released by a time window (caution: without time window A3 is always ON)orw pump A2 is running w and A2 is on automatic mode.

    A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1A2 = S1 > (S3 + diff2) & S1 > min1 & S3 < max2A3 = (A3 = on) or (A2 = automatic mode)

    All programs +1:

    Instead of the two pumps, one pump and a three-way valve are used (pump-valve system).The speed control (if activated) only affects loop 1.

    A1 ... common pump A2 ... valve (A2/S has power when loading tank TK2)

    All programs +2:

    In addition, ifS4 exceeds the threshold max3,pump A1 is switched off.

    All programs +4: Both solar loops have separate switch-on thresholds at S1:

    output A1 retains min1, and A2 switches at min2.

    The priorities forTK1 and TK2 can be set in the parameter menu underPA. In addition, asolar priority function can be set for this diagram in the menu PRIOR (see solar priorities onpage 88 for more details).

    S1min1

    S2 S3max1 max2

    diff2A2, A3

    diff1A1

    required settings:

    diff1 coll. S1 TK1 S2 A1diff2 coll. S1 TK2 S3 A2min1 switch-on temp. coll. S1 A1, A2min2 see all programs +4

    max1 limit TK1 S2 A1max2 limit TK2 S3 A2max3 see all programs +2

    S2S3

    S1

    A3A2A1

    TK2TK1

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    58/116

    58

    Preparation of hot water including circulation and solar power system program 640

    Only makes sense if the speed control is activated!

    Program 640: Pump A1 runs when:

    w the flow switch (FS)S6 detects flow.

    The circulation pump A2 runs when:

    wS3 is greater than the threshold min2w and S3 is greater than S4 by the difference diff2

    w and S4 has not exceeded the threshold max2.

    Solar pump A3 runs when:

    wS1 is greater than the threshold min1w and S1 is greater than S2 by the difference diff1

    w and S2 has not exceeded the threshold max1.

    A1 = flow switch FS (S6) = ONA2 = S3 > (S4 + diff2) & S3 > min2 & S4 < max2A3 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1

    All programs +1:

    Circulation pump A2 is only switched on when in addition to the basic function the volumeflow switch (FS) S6 is on (A1 = ON).

    diff2

    A2diff1

    A3

    S1 S3

    min1 min2

    S2 S4max1 max2

    A1 = FS (S6) = ON

    required settings:

    diff1 coll. S1 TK S2 A3diff2 TK S3 circ. return S4 A2min1 switch-on temp. coll. S1 A3min2 switch-on temp TK S3 A2max1 limit TK S2 A3max2 limit circ. return S4 A2

    S1

    A2A1

    WW

    S2

    S3

    S4

    S5

    A3KW

    S6

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    59/116

    59

    Preparation of hot water including circulation and burner requirement program 656

    Only makes sense if the speed control is activated!

    Program 656: Pump A1 runs when:

    w the flow switch (FS)S5 detects flow.

    The circulation pump A2 runs when:

    wS3 is greater than the threshold min1w and S3 is greater than S4 by the difference diff1

    w and S4 has not exceeded the threshold max1.

    Output A3 switches on when S3 falls below threshold min2.

    Output A3 switches off (dominant) when S2 exceeds max2.

    A1 = Flow switch FS (S5) = ONA2 = S3 > (S4 + diff1) & S3 > min1 & S4 < max1 A3 (on) = S3 < min2 A3 (off) = S2 > max2

    All programs +1:

    Circulation pump A2 is only switched on when in addition to the basic function the volumeflow switch (FS)S5 is on (A1 = ON).

    All programs +2:The burner requirement (A3) only occurs via sensorS3.

    Output A3 switches on when S3 falls below threshold min2.

    Output A3 switches off (dominant) when S3 exceeds max2.

    A3 (on) = S3 < min2 A3 (off) = S3 > max2

    required settings:

    diff1 TK S3 circulation return S4 A2min1 switch-on temp. TK S3 A3min2 burner req. on TK3 S3 A3max1 limit circulation return S2 A2max2 burner req. off TK S2 A3

    S3

    min1

    S4max1 A1 = FS (S5) = ON

    diff1

    A2

    burner

    A3S3 min2S2 max2

    S3

    A3S2

    A2A1 S5

    WW

    S4

    S1

    KW

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    60/116

    60

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    61/116

    61

    Installation instructions

    Installing the sensor(s):

    The sensors must be arranged and installed properly for the system to function correctly.

    To this end, make sure that they are completely inserted in the immersion sleeves. Thethreaded cable connections provided can be used to provide strain relief. The clip-onsensors must be insulated to protect them from being influenced by the ambienttemperature. Water must be kept out of the immersion sleeves when used outdoors(damage from freezing).

    In general, the sensors may not be exposed to moisture (such as condensation water),which might enter the cast resin and damage the sensor. If this happens, heating thesensor to 90C for an hour might help. When using immersion sleeves in NIRO tanks(inoxydable) or pools, pay attention to theirnon-corrosion properties.

    l Collector sensor (red or green cable with connection box): Insert either in the tube

    directly soldered or riveted to the absorber and sticking out of the collectors frame or in a t-shaped connector on the outer collectors supply line collector tube. Screw an immersionsleeve with an MS (brass) threaded cable connection (= to protect from moisture) into thisT-shaped connector and insert the sensor. To protect from lightening, the connection boxhas parallel overvoltage protection between the sensor and the extension cable.

    l Boiler sensor (boiler supply line): This sensor is either screwed into the boiler with animmersion sleeve or attached to the boilers supply line at a slight distance.

    l Tank sensor: The sensor that the solar power system needs should be used with animmersion sleeve for fin coil heat exchangers just above the exchanger or, if integratedbare-tube heat exchangers are used, on the lower third of the exchanger or the exchangers

    return line so that the immersion sleeve is inside the exchangers tube. The sensor thatmonitors the heating of the tank from the boiler is installed at the level of the desiredamount of hot water during the heating season. The plastic threaded cable connectionsprovided can be used to provide strain relief. They must not be installed below the register /exchanger.

    l Buffer sensor: The sensor that the solar power system needs is installed on the bottomof the tank just below the solar heat exchanger using the immersion sleeve provided. Theplastic threaded cable connections provided can be used to provide strain relief. It isrecommended that the sensor be used between the middle and the upper third of the buffertank using the immersion sleeve as a reference sensor for the heaters hydraulics or - flushwith the tanks wall - under the insulation.

    l Pool sensor (swimming pool): Put a T-shaped connector on the suction lineimmediately on the line leading from the pool and screw the sensor in with an immersionsleeve. In the process, make sure that the material used is non-corroding. Another option isto put the sensor on the same spot using hose clamps or adhesive tape and to providethermal insulation for ambient influences.

  • 8/7/2019 Manual panouri solare UVR61_V2_5_engl

    62/116

    62

    l Clip-on sensor: Use pipe clamps, hose clamps, and the like must be attached to therespective line. Make sure that suitable material is used (corrosion and temperatureresistance, etc.). Then, the sensor has to be well insulated so that the tube temperature canbe taken exactly and influences from the ambient temperature can be ruled out.

    l Hot water sensor: When the control system is used in hot water systems with anexternal heat exchanger and variable-speed pump, changes in the amount of water have tobe reacted to quickly. Hence, the hot water sensor has to be put directly on the heatexchanger