Manual Issue 2.6

Measurement with Request Function via Profibus DP

ibaPDA-Request-FM458/TDC

Page 2: Manual - iba-ag.com

Manufacturer

iba AG

Koenigswarterstr. 44

90762 Fuerth

Germany

Contacts

Main office +49 911 97282-0

Fax +49 911 97282-33

Support +49 911 97282-14

Engineering +49 911 97282-13

E-Mail [email protected]

Web www.iba-ag.com

This manual must not be circulated or copied, or its contents utilized and disseminated,

without our express written permission. Any breach or infringement of this provision will

result in liability for damages.

©iba AG 2017, All Rights Reserved

The content of this publication has been checked for compliance with the described

hardware and software. Nevertheless, deviations cannot be excluded completely so that

the full compliance is not guaranteed. However, the information in this publication is

updated regularly. Required corrections are contained in the following regulations or can

be downloaded on the Internet.

The current version is available for download on our web site http://www.iba-ag.com.

Protection note

Windows® is a label and registered trademark of the Microsoft Corporation. Other

product and company names mentioned in this manual can be labels or registered

trademarks of the corresponding owners.

Version Date Revision Author Version SW

2.6 01/26/2017 New chapters 3.3.5 ff ko

Page 3: Manual - iba-ag.com

ibaPDA-Request-FM458/TDC Manual

Issue 2.6 i

Table of Contents

1 About this manual ........................................................................................... 3

1.1 Target group .................................................................................................. 3

1.2 Basic knowledge ............................................................................................ 3

1.3 Notations ....................................................................................................... 3

1.4 Used symbols ................................................................................................ 4

2 Requirements .................................................................................................. 5

2.1 Siemens hardware ......................................................................................... 5

2.2 Siemens software .......................................................................................... 5

2.3 iba hardware .................................................................................................. 5

2.4 iba software ................................................................................................... 5

3 Configuration .................................................................................................. 6

3.1 Overview ....................................................................................................... 6

3.2 Basics ............................................................................................................ 7

3.3 Configuration on FM458 / SIMATIC TDC side .............................................. 10

3.3.1 General Information ..................................................................................... 10

3.3.2 Hardware (Profibus) ..................................................................................... 10

3.3.3 Software ...................................................................................................... 11

3.3.3.1 Installation of FBAPDA library .................................................................................... 11

3.3.3.2 Wiring of blocks .......................................................................................................... 11

3.3.4 Description of blocks .................................................................................... 13

3.3.4.1 S7DB_P ...................................................................................................................... 13

3.3.4.2 SERPDA ..................................................................................................................... 14

3.3.4.3 SERPDB ..................................................................................................................... 15

3.3.5 Other characteristics .................................................................................... 15

3.3.5.1 Processor load ............................................................................................................ 15

3.3.5.2 Load limitation ............................................................................................................ 16

3.3.5.3 Transmission cycle ..................................................................................................... 16

3.4 Configuration on ibaPDA side ...................................................................... 17

3.4.1 For request with ibaCom-L2B ...................................................................... 17

3.4.2 For request with ibaBM-DPM-S ................................................................... 17

3.4.3 For request with ibaBM-DP .......................................................................... 19

3.4.4 Connecting .................................................................................................. 21

3.4.4.1 Connection Mode TCP/IP ........................................................................................... 21

3.4.4.2 Connection Mode PC/CP ........................................................................................... 21

3.4.4.3 Testing the connection ............................................................................................... 22

3.4.5 Generating the address book ....................................................................... 25

3.4.6 Creating a list of variables ............................................................................ 26

3.4.7 Starting measurement ................................................................................. 27

4 Appendix ........................................................................................................ 28

4.1 iba Library .................................................................................................... 28

4.1.1 Integrating the library ................................................................................... 28

4.1.2 Integrating the blocks ................................................................................... 29

4.2 Application examples ................................................................................... 30

Page 4: Manual - iba-ag.com

Manual ibaPDA-Request-FM458/TDC

ii Issue 2.6

4.3 Messages .................................................................................................... 31

4.3.1 SERPDA ..................................................................................................... 31

4.3.2 SERPDB ..................................................................................................... 32

5 Support and contact ..................................................................................... 33

Page 5: Manual - iba-ag.com

ibaPDA-Request-FM458/TDC Manual

Issue 2.6 3

1 About this manual

This manual describes the function, the design and the application of the software

ibaPDA-Request-FM458/TDC.

1.1 Target group

This manual addresses in particular the qualified professionals who are familiar with

handling electrical and electronic modules as well as communication and measurement

technology. A person is regarded as professional if he/she is capable of assessing safety

and recognizing possible consequences and risks on the basis of his/her specialist

training, knowledge and experience and knowledge of the standard regulations.

1.2 Basic knowledge

The following knowledge is required for the operation of the software ibaPDA-Request-

FM458/-TDC:

Basic knowledge of Windows operating system

Basic knowledge of operating web browsers

Basic knowledge of Profibus configuration

Basic knowledge of operating SIMATIC, CFC and D7-SYS

1.3 Notations

In this manual the following notations are used:

Action Notation

Menu command Menu "Logic diagram"

Calling the menu command Step 1 – Step 2 – Step 3 – Step x

Example: Select the menu Logic diagram - Add - New function block.

Keys <Key name>

Example: <Alt>; <F1>

Press the keys simultaneously <Key name> + <Key name>

Example: <Alt> + <Ctrl>

Buttons <Key name>

Example: <OK>; <Cancel>

File names, paths "Filename", "Path"

Example: "Test.doc"

Page 6: Manual - iba-ag.com

Manual ibaPDA-Request-FM458/TDC

4 Issue 2.6

1.4 Used symbols

If safety instructions or other notes are used in this manual, they mean:

The non-observance of this safety information may result in an imminent risk of death

or severe injury:

From an electric shock!

Due to the improper handling of software products which are coupled to

input and output procedures with control function!

The non-observance of this safety information may result in a potential risk of death or

severe injury!

The non-observance of this safety information may result in a potential risk of injury or

material damage!

Note

A note specifies special requirements or actions to be observed.

Important note

Note if some special features must be observed, for example exceptions from the rule.

Tip

Tip or example as a helpful note or insider tip to make the work a little bit easier.

Other documentation

Reference to additional documentation or further reading.

Page 7: Manual - iba-ag.com

ibaPDA-Request-FM458/TDC Manual

Issue 2.6 5

2 Requirements

2.1 Siemens hardware

For FM458-Request:

FM458-1 DP

MPI adapter or CP443-1 (Ethernet CP) for connection to programming device (PG)

or for SIMATIC TDC-Request:

CP50M1 with DP-interface

MPI-adapter or CP51M1 (Ethernet CP) for PG-connection

2.2 Siemens software

CFC V6.1 + HF1 , or higher

D7-SYS V6.2 + SP1 (FBSLIB 102500V617), or higher

If you use PC/CP connection: MPI-interface or STEP 7

2.3 iba hardware

PCI card ibaComL2B-x-8, or

Profibus monitor ibaBM-DPM-S and fiber optical PCI card ibaFOB-nn-D

Profibus monitor ibaBM-DP and a fiber optical input and output card of ibaFOB-D or

ibaFOB-Dexp type

2.4 iba software

ibaPDA V6.17.0 or later for FM458,

ibaPDA V6.23.0 or later for SIMATIC TDC

ibaPDA V6.32.0 or later with ibaBM-DP

Add-on license: ibaPDA-Request-FM458/TDC

Function block library: FBAPDA

version 080415V003 or higher

Page 8: Manual - iba-ag.com

Manual ibaPDA-Request-FM458/TDC

6 Issue 2.6

3 Configuration

3.1 Overview

For controls from Siemens, iba AG offers the following request solutions:

Target

system

Interface Transmission

via

iba interface Manual License

SIMADYN D CS12/13/14 fiber optical link ibaFOB-SD Request-SD-TDC Request-SD,

Request-TDC

SIMATIC TDC CP53

GDM ibaFOB-TDC

CP50 Profibus ibaBM-DP

ibaBM-DPM-S

ibaCom-L2B

Request-FM458/TDC

Request-FM458/TDC

S7-400 FM458

S7-CPU Request-S7 Request-S7

S7-300

TCP/IP, MPI, DP

Ethernet, MPI-adapter

PLC-Xplorer PLC-Xplorer

This manual describes the green highlighted areas of the table above.

Page 9: Manual - iba-ag.com

ibaPDA-Request-FM458/TDC Manual

Issue 2.6 7

3.2 Basics

The measuring data is transmitted via Profibus, either over the PCI card ibaCom-L2B or

the Profibus modules ibaBM-DPM-S or ibaBM-DP.

The online access (TCP/IP or DP/MPI) is used for the transmission of the address book

and the request handshake.

The following combinations are possible:

SIMATIC S7/FM458 with ibaCom-L2B card

SIMATIC S7/FM458 with ibaBM-DPM-S

SIMATIC S7/FM458 with ibaBM-DP

Page 10: Manual - iba-ag.com

Manual ibaPDA-Request-FM458/TDC

8 Issue 2.6

SIMATIC TDC with ibaCom-L2B card

SIMATIC TDC with ibaBM-DPM-S

SIMATIC TDC with ibaBM-DP

Page 11: Manual - iba-ag.com

ibaPDA-Request-FM458/TDC Manual

Issue 2.6 9

ibaPDA uses the interface of the Siemens programming device (PG-interface) for request

handshake and the transmission of address books. Depending on the hardware and

software installed, different access points are available for data acquisition:

TCP/IP: The connection to the control is established over corresponding CP

modules and the standard network interface of the PC. No additional software is

required for the connection.

PC/CP: There are several, SIMATIC-specific access points which fall under this

designation. In contrast to the TCP/IP connection, the STEP 7 software or

respectively the drivers for the MPI/DP interface must be installed on the PC for all

connection types within the PC/CP group.

MPI, Profibus: The connection to the control is established over the MPI or

Profibus interface of the PC (MPI-adapter or Siemens CP5611 or others).

TCP/IP, ISO: Either the standard network interface of the PC or a compatible

interface card should be used.

The transmission of measured data runs over Profibus DP to the iba-Profibus slaves:

ibaCom-L2B (ibaPDA Version 6.15.0 or higher) or

ibaBM-DPM-S (ibaPDA Version 6.17.0 or higher) or

ibaBM-DP (ibaPDA Version 6.32.0 or higher)

The number of data per connection depends on the type of the Profibus slave. If one

slave does not provide enough data, additional connections should be configured.

Note

For using the request functionality with ibaBM-DPM-S you further need to establish an

online connection between the ibaPDA PC and the ibaBM-DPM-S device, via Ethernet

TCP/IP or USB.

Page 12: Manual - iba-ag.com

Manual ibaPDA-Request-FM458/TDC

10 Issue 2.6

3.3 Configuration on FM458 / SIMATIC TDC side

3.3.1 General Information

Up to 122 Bytes can be transmitted per connection (i.e. per DP station) with ibaCom-

L2B, and up to 244 Bytes with ibaBM-DP/-DPM-S.

If this data volume is not sufficient, it is possible to configure several connections per

CPU (up to 8 per device).

Each connection requires:

A DP station of "ibaL2B/DPM64 (32R/32D)" or "ibaBM-DPM-S/DP-Monitor" type in

the hardware configuration

A triplet of the blocks S7DB_P, SERPDA and SERPDB in the CFC program. The

DB number in S7DB_P.XDB must be unique as well as the channel name and the

station number in SERPDB.AT.

A module FM458 request or TDC request in ibaPDA, the module must be uniquely

assigned to a DB.

If you want to request data from several CPUs from one TDC rack, connections have to

be configured in each of the CPUs. It is not possible to acquire data from several CPUs

with one connection.

3.3.2 Hardware (Profibus)

One iba-Profibus slave should be defined for each connection.

The following GSD files should be used:

Measurement with ibaCom-L2B: iba0F02.gsd

Add a module „ibaL2B/-DPM64 (32R/32D) <o>“ with the slot „FM458/TDC-Request“

(for up to 32 analog values and 32 digital values) in your hardware configuration.

You find the module in the hardware catalog under PROFIBUS-DP - Additional Field

Devices - General.

Page 13: Manual - iba-ag.com

ibaPDA-Request-FM458/TDC Manual

Issue 2.6 11

Measurement with ibaBM-DP/-DPM-S: ibaDPMSi.gsd

Add a module „ibaBM-DPM-S/DP-Monitor“ with the slots „S7-Req unit consistent

Slot 0" and „… Slot 1" (for up to 244 bytes) to your hardware configuration. You find

the module in the hardware catalog under PROFIBUS-DP - Additional Field Devices

- General.

3.3.3 Software

3.3.3.1 Installation of FBAPDA library

You will find a more detailed description of the installation in the appendix, chapter 4.1

“iba Library”.

3.3.3.2 Wiring of blocks

The so-called "agents" which handle the request procedure have to be programmed on

the FM458 component. The following function blocks are required for each connection:

Block S7DB_P (standard block)

This block creates a data block which is S7-compliant and to be used for data

exchange with ibaPDA.

We recommend creating a "DB10" for the first connection and "DB11", "DB12" etc.

for further connections.

Recommended time slice: T5

Block SERPDA (from iba's user library FBAPDA)

This block handles the handshake with ibaPDA via the related data block. It takes

the list of variables to be measured, calculates the memory addresses on that basis

and transmits the addresses to the SERPDB block.

Recommended time slice: T5

Block SERPDB (from iba's user library FBAPDA)

Every cycle, this block acquires the actual values from the calculated memory

addresses, puts them into the message buffer and transmits them to the specified

interface.

Recommended time slice: T1

Page 14: Manual - iba-ag.com

Manual ibaPDA-Request-FM458/TDC

12 Issue 2.6

Wiring of blocks for L2B-request:

Wiring of blocks for DPM-S/DP-request:

Note

Of course, the standard block "@PRODP" is still required once for initialization of the

Profibus interface!

If the size of one Profibus slave is insufficient to transmit all data required you can multiply

the capacity of data by copying these three blocks.

You should modify the following data of the copied blocks:

Data block number (connection to S7DB_P.XDB)

Channel name (name to SERPDB.AT)

Station number (address level 1 to SERPDB.AT)

Page 15: Manual - iba-ag.com

ibaPDA-Request-FM458/TDC Manual

Issue 2.6 13

3.3.4 Description of blocks

3.3.4.1 S7DB_P

Con. Description Configuration / Result

XDB Initialization connector for entry of

symbol name and number of the

"virtual" S7-DB

Recommended: DB10 ,

increasing numbers for further

connections

LEN Length of the DB in bytes Minimum: 2200

NBF Number of data buffers which are

held in this DB.

1

BSL Selection of buffer 1

SAV DB in SAVE-range 0

PTR Pointer on data buffer management -

DPT Pointer on net data "Connection to SERPDA.DPT"

QF Error bit (1 = error) 0 = no error

YF Status info 0000 = no error

Tip

Since version 6.15.3 of ibaPDA you can define a larger DB, e. g. with 10000 bytes, in

order to accelerate the transmission of the address book. But keep in mind that the run

time of the block SERPDA during address book transmission will increase with bigger

DB size!

Page 16: Manual - iba-ag.com

Manual ibaPDA-Request-FM458/TDC

14 Issue 2.6

3.3.4.2 SERPDA

Con Description Configuration / Result

TYP Type Measurement channel

"DP" = Data channel Profibus DP

"TC" = Data channel TCP/IP

"UD" = Data channel UDP

"SM" = Data channel SM128

„DB“ = Data channel DB

DP

(others not available yet)

DPT Contains memory address of the

data block

"Connection to S7DB_P.DPT"

ST Block status:

0...Waiting for startup of SERPDB

1...Waiting for synchronization with

ibaPDA

2...Normal (Standby) operation

3...Stop SERPDB

4...Start SERPDB

5...Transmitting address book

6...Cont. transmitting address book

7...Sending Req-error acknowledge

8...Sending acknowledge

9...Error

CVP Address of the common data area

with SERPDB

"Connection to SERPDB.ADR"

YTS Error status 0000 ... no error,

see chapter Messages "SERPDA"

YTZ Additional error label 0000 ... no error,

see chapter Messages "SERPDA"

QTS Ready for operation 0 ... out of operation / 1 ... OK

Page 17: Manual - iba-ag.com

ibaPDA-Request-FM458/TDC Manual

Issue 2.6 15

3.3.4.3 SERPDB

Con. Description Configuration / Result

CTS Initialization connector for the

configured component name

"Connection to component.connector"

AT Channel name.xx.y

Unique channel name acc. to TDC-

convention.

For Profibus:

xx = station number

y = 0: flag for byte swapping

ADR Address VPORT "Connection to SERPDA.CVP"

LIM Load limitation Recommended: 90.0

See chapter 3.3.5.2 “Load limitation”

FMT Format code:

0: DPMS format

1: 32-REAL format for ibaCom-L2B

LEN Net data length of measurement

channel in bytes

Must correspond to data length in the

GSD file.

For FMT=0: length according to

configured DP slave, max. 244

For FMT=1: exactly 136

ST Block status:

0...Waiting for initialization

1...Waiting for channel registration

2...Normal (Standby) operation

3...Start-up

4...Active (Sending)

5...Error

YTS Error status 0000 ... no error,

see chapter Messages "SERPDB"

YTZ Error supplementary code 0000 ... no error,

see chapter Messages "SERPDB"

QTS Ready for operation 1: OK

3.3.5 Other characteristics

3.3.5.1 Processor load

For the sporadic load due to transmission of the address book, the SERPDA function

block requires a computing time of max. ca. 10 ms to 20 ms per cycle. The time slice in

which the block is configured (normally T5) must therefore be chosen so that sufficient

processing time still remains for the sporadic T5 "Transmit address book" task.

If this time is not available, then an overload indication is displayed during address book

transmission. Since this overload is only sporadic and is caused in T5 and thus has no

influence on T1-T4 processing, this indication can be ignored and deleted again via

acknowledgement.

Page 18: Manual - iba-ag.com

Manual ibaPDA-Request-FM458/TDC

16 Issue 2.6

The cyclical transmission operation by the SERPDB function block requires computing time per transmission cycle for assignment of the measurement values in the local data buffer and for transmission of the data into the rack link.

3.3.5.2 Load limitation

In order to prevent a CPU overload due to the increase in computing time when making

a request, the blocks have a load limitation (connector LIM).

After the start of acquisition, the function block follows a kind of run-up ramp when taking

only parts of the requested values per cycle into its processing. During this phase the

required computing time is checked. If the load exceeds the value set at the LIM

connector, then the measurement values that have not yet been processed are rejected

and a “processor overload” error message appears in ibaPDA. The user needs to reduce

the number of the requested values in ibaPDA or increase the sampling time base

(ibaPDA base measuring rate or the PDA channel time bases) or increase the time slice

for the SERPDB in the TDC system.

When “LIM = 0.0”, load monitoring will be switched off.

Important note

The load is checked only at the start of acquisition. A load increase due to other acyclic

processes during on-going measurement are not detected by the SERPDB function

block.

Due to unfavorable temporal relations overload errors can occur despite monitoring. The

load increase in high-priority tasks has repercussions on the capacity of low-priority

tasks. But the latter lead to a load increase only after expiration of their task cycle. But

with slow low-priority task times the run-up of the SERPDB function block is already

completed at this point.

3.3.5.3 Transmission cycle

The SERPDB works in the configured sampling time (primarily T1).

If the data is requested by ibaPDA in a slower cycle, then the function block gears down

its own transmission cycle. In other words, it transmits no longer in the projected cycle

time, but rather in the cycle in which the data are read by ibaPDA (rounded to a multiple

of its own cycle). This way, the processor load can be reduced.

The transmission cycle is also limited by the Profibus cycle time which is based on the

bus data volume (number of participants and telegram length) and the bus bitrate. The

cycle time will be specified in HW Config and in ibaPDA diagnostics of the interfaces

ibaCom-L2B or ibaBM-DP.

Page 19: Manual - iba-ag.com

ibaPDA-Request-FM458/TDC Manual

Issue 2.6 17

3.4 Configuration on ibaPDA side

For configuration in ibaPDA, please follow these steps.

Start ibaPDA client

Open IO manager

3.4.1 For request with ibaCom-L2B

Add a module "L2B FM458 request" or "L2B TDC request" to ibaL2B hardware

interface

(or more if multiple connections to one or more CPUs are required)

3.4.2 For request with ibaBM-DPM-S

Add an "ibaBM-DPM-S" module to the ibaFOB...-X or -D interface.

Enter the IP-address of the ibaBM-DPM-S device into the IP-address field in the

“General” tab of the "ibaBM-DPM-S" module:

Either as a name e. g. "dpms_011D" or as IP-address, e. g. "192.168.11.123".

Page 20: Manual - iba-ag.com

Manual ibaPDA-Request-FM458/TDC

18 Issue 2.6

Note

It is necessary to have an online connection to the device via Ethernet or USB. See the

manual of the ibaBM-DPM-S device for how to establish and test such a connection.

Add a module "FM458 request" or "TDC request" to the ibaBM-DPM-S interface

(or more, if multiple connections to one or more CPUs are required).

Make the general module settings.

Important:

Number of signals (size of the tables): the length of the Profibus telegram must

not be exceeded.

Bus number: 0 = upper connector, 1 = lower connector

The station number (slave number) will be entered automatically when

establishing the connection (see below).

Note

The total number of signals of all modules of an ibaBM-DPM-S is limited by the fiber

optical connection to 512 analog and 512 digital signals.

Page 21: Manual - iba-ag.com

ibaPDA-Request-FM458/TDC Manual

Issue 2.6 19

3.4.3 For request with ibaBM-DP

Add an “ibaBM-DP” module to the ibaFOB-D interface.

When the device is used in Flex mode, the IP address of the device will be

adjusted automatically.

When the device is used in compatibility mode, enter the IP address of the device in

the field „IP Address“ on the „General“ tab: either the name e. g. "DP_000100" or

the IP address e. g. "192.168.11.123".

Page 22: Manual - iba-ag.com

Manual ibaPDA-Request-FM458/TDC

20 Issue 2.6

Note

The ibaBM-DP manual gives a more detailed description of the difference between Flex

mode and compatibility mode.

When the device is used in compatibility mode, an online connection to the device is

required, either over Ethernet or USB. For a description how to establish and test this

connection, please observe the ibaBM-DP manual.

Add a module "FM458 request" or "TDC request" to the ibaBM-DP interface at the

corresponding Profibus link (or more, if multiple connections to one or more CPUs

are required).

Make the general module settings.

Important:

Number of signals (size of the tables): the length of the Profibus telegram must

not be exceeded.

Bus number: 0 = left connector, 1 = right connector

The station number (slave number) will be entered automatically when

establishing the connection (see below).

Note

The total number of signals of all modules of an ibaBM-DP is limited by the fiber optical

connection: in Flex mode to 4060 Byte, in compatibility mode to 512 analog and 512

digital signals.

Page 23: Manual - iba-ag.com

ibaPDA-Request-FM458/TDC Manual

Issue 2.6 21

3.4.4 Connecting

On the Connection tab of the request modules you should enter the connection

parameters and test the connection.

3.4.4.1 Connection Mode TCP/IP

Connection type: not relevant

Timeout: 5 s (default)

Address: IP address of the CP443-5, FM458 or CP51M1,

e. g. "192.168.11.86"

Rack: Rack number of the S7 station or SIMATIC TDC station, e. g. "0"

Slot: Slot of the FM458 or CPU550/551, e. g. "3"

DB number: Number of the DB which has been configured with the S7DB_P-

block, e. g. "10"

3.4.4.2 Connection Mode PC/CP

Connection type: PG-connection

Timeout: 5 s (default)

Access point: Selection of access point, e. g. MPI

Configure PG/PC

interface: Here you can configure a special access point for ibaPDA

(see guidelines in manual of ibaPDA-PLC-Xplorer).

Address: MPI- or DP-address of the S7-CPU or CP50M1

Rack: Rack number of the S7-station or SIMATIC TDC station, e. g. "0"

Slot: Slot of the FM458 or CPU550/551, e. g. "3"

DB number: Number of the DB which has been configured with the S7DB_P-

block, e. g. "10"

Note

For using the connection mode PC/CP the SIMATIC-S7 communication software (e. g.

SIMATIC Manager or driver for MPI adapter) must be installed on the ibaPDA-PC too!

Page 24: Manual - iba-ag.com

Manual ibaPDA-Request-FM458/TDC

22 Issue 2.6

3.4.4.3 Testing the connection

If you do not know neither rack nor slot number you can click on the <Test>-button and

let the system search for the FM-component. The search results will list the MLFB

numbers of the installed components. The MLFB of the FM-component will be displayed

as a hyperlink.

After a mouse click on the hyperlink of the CPU the connection will be activated and rack

and slot number will be entered immediately into the corresponding fields.

If the correct DB number has been entered in the corresponding field the connection to

the request agent will be established and the Profibus diagnostic data from the DB will

be displayed.

The station number (slave number / slave address) will be entered automatically in the

module settings.

Page 25: Manual - iba-ag.com

ibaPDA-Request-FM458/TDC Manual

Issue 2.6 23

Examples for diagnostic information

Request over ibaCom-L2B

Request over ibaBM-DPM-S or ibaBM-DP

Page 26: Manual - iba-ag.com

Manual ibaPDA-Request-FM458/TDC

24 Issue 2.6

The following diagnostic information is available in the DB:

PLC status: e. g. "RUN" or "STOP"

DB version: version code e.g. "0.0.0.2"

FB version: version code e. g. "0.0.2.5"

DB length: length of the communication-DB

Software version: version code of the D7-Sys software

BGT name: standard name "BGTA00"

BG name: name of the CPU component from HWConfig, e. g. "4581DP"

T1...T5: time slices from CPU

Charts: number of charts

Profibus slaves: always "1"

Slave address: station number of the connected Profibus device

Format: format name (connector SERPDB.FMT)

Length: data length (connector SERPDB.LEN); this length must match the length

of the station configured in HWConfig.

Status: error status (connector SERPDB.YTS), see chapter Messages "SERPDB"

Error code: error code (connector SERPDB.YTZ), see chapter Messages

"SERPDB"

If no connection has been established to the service block the following reasons may

apply:

No TCP/IP connection

Wrong address, rack- or slot number

Wrong DB-number

DB too small (less than 2200 bytes)

Error in configuration of service blocks; an initialization error number will be

generated which corresponds to the YTS connector of the SERPDA block, see

chapter Messages "SERPDA"

Page 27: Manual - iba-ag.com

ibaPDA-Request-FM458/TDC Manual

Issue 2.6 25

3.4.5 Generating the address book

If the connection to the agents has been established, the address book can be loaded:

Enter the CPU name, e. g. "FM_1" or "TDC_N1"

This is absolutely necessary in order to distinguish single CPUs in case of multi-

processor systems.

Set option "macro filter" (only for ibaPDA version 6.15.3 or higher).

If the macro filter is enabled (= default), the contents of macro blocks will NOT be

added to the address book.

If the filter is disabled, the blocks of a macro will be taken into account too.

Click on button <Create address book>

The data of the address book will be transmitted. The address book file will be

stored in the folder ":.. \iba\ibaPDA\Server\FM458".

Tip 1

If you have configured multiple connections to a CPU it is enough to load an address

book of one connection. You can use the same address book for the other connections

to this CPU.

Tip 2

Depending on the project size the transmission of the address book could take some

time. You may accelerate this by moving the block SERPDA of this connection to the

time slice T4.

Tip 3

With ibaPDA version 6.15.3 or higher you can make the address book transmission

even faster by increasing the size of the DB for this connection!

Tip 4

With ibaPDA version 6.15.3 or higher you can further reduce the transmission time of

the address book by enabling the macro filter!

Note

You can also work with an address book not up-to-date. Shifts in memory have no effect

because the memory addresses are mapped on the symbols not until the time of

accessing the CPU. Access on function blocks which had been deleted in the meantime

will cause error messages.

Page 28: Manual - iba-ag.com

Manual ibaPDA-Request-FM458/TDC

26 Issue 2.6

3.4.6 Creating a list of variables

Select the address book which is related to this CPU connection in the field (combo box)

"CPU-name" on the “General” tab or on the “Connection” tab.

You have the following possibilities for creating a list of variables:

On one hand, you may click on <Edit FM458 symbols> (hyperlink) in the General

tab in the request module's dialog in order to open the browser.

On the other hand, you may click on a cell in the signal table, column Symbol, on

the tabs Analog or Digital of the module. If you click on the button in the cell, the

browser opens too.

But an easier way to select signals to be measured is the drag & drop method from

CFC-chart to the IO Manager in ibaPDA.

The essential requirement is that the ibaPDA-client is installed on the same PC like

the SIMATIC Manager.

Therefore, start the CFC-editor and the ibaPDA-client, windows in "restore down"

mode. Open ibaPDA IO Manager, module and signal table. Then click on the

connector in the CFC chart you want to measure, keep the left mouse key

depressed and drag it into the IO Manager on the desired row in the signal table

and let it drop. The CFC-connector is now available in the signal table of the L2B-

S7-Request module.

Page 29: Manual - iba-ag.com

ibaPDA-Request-FM458/TDC Manual

Issue 2.6 27

3.4.7 Starting measurement

By clicking the button <Apply> or <OK>, the IO configuration and the variable list will be

checked and applied to the ibaPDA server.

The following steps are performed:

Verification of the license and consistency of IO configuration

With ibaCom-L2B: Checking the Profibus connection

With ibaBM-DPM-S: Transfer of list of variables to the ibaBM-DPM-S device via

online connection (TCP/IP or USB)

With ibaBM-DP: Transfer of list of variables to the ibaBM-DP device via fiber optics

in Flex mode, and via online connection (TCP/IP or USB) in compatibility mode.

Request handshake: Transfer of list of variables to the FM458 or SIMATIC CPU via

online connection (TCP/IP, MPI or DP)

Checking of data storage configuration

After starting the measurement you can see the raw values of the requested variables in

the Analog or Digital tab of the ibaBM-DPM-S module.

This is not (yet) possible for measuring via ibaCom-L2B.

Page 30: Manual - iba-ag.com

Manual ibaPDA-Request-FM458/TDC

28 Issue 2.6

4 Appendix

4.1 iba Library

The iba library FBAPDA is suitable for the use with SIMATIC Manager V5.5 or higher. It

contains the Request blocks described in the manual, which are required for the use of

ibaPDA-Request-FM458/TDC.

You find the iba library on the DVD "iba Software & Manuals" under

…\04_Libraries_and_examples\10_Libraries\02_SIMATIC_TDC_FM458.

The following blocks are included:

iba connection Block name Note

general DCF77 For time synchronization

ibaFOB-TDC ibaFOB-SD ibaFOB-TDCexp ibaFOB-SDexp

SER04A Request administration

SER04B Request data transfer

ibaFOB-TDCexp

ibaFOB-SDexp

SER05A Request administration

SER05B Request data transfer

ibaBM-DP ibaBM-DPM-S ibaCom-L2B

SERPDA Request administration

SERPDB Request data transfer

4.1.1 Integrating the library

The library contains the files fbapda_fm1.a, fbapda_tdc_Cpu551.a,

fbapda_tdc_Cpu555.a, fbapda.msk, FBAPDA_A.HLP and FBAPDA_B.HLP.

Depending on the setting of the CFC compiler (under Options – Customize –

Compile/Download), they have to be copied into the STEP7-CFC block folder.

System data from installation: Copy the blocks to

…\STEP7\s7cfc\sdblocks.

System data from project folder: Copy the blocks to

…\STEP7\S7Proj\project_folder\Global\sdblocks.

Page 31: Manual - iba-ag.com

ibaPDA-Request-FM458/TDC Manual

Issue 2.6 29

Then, you can import the library into the project. Open the menu Options – Block Types

in the CFC chart and import FBAPDA.

4.1.2 Integrating the blocks

After having imported the library, the iba blocks are available in the catalog under

ibaPDA.

Drag the block via drag & drop into the chart.

Pay attention to the sequence and the time class of the blocks, see chapter “Wiring of

blocks”.

Page 32: Manual - iba-ag.com

Manual ibaPDA-Request-FM458/TDC

30 Issue 2.6

4.2 Application examples

You find application examples on the DVD "iba Software & Manuals":

For the ibaBM-DP device in the path

\04_Libraries_and_examples\31_ibaBM-DP\02_SIMATIC_TDC\Request\

and

\04_Libraries_and_examples\31_ibaBM-DP\03_SIMATIC_FM458\Request\

For the ibaBM-DPM-S device in the path

\04_Libraries_and_examples\30_ibaBM-DPM-S\02_SIMATIC_TDC\Request\

and

\04_Libraries_and_examples\30_ibaBM-DPM-S\03_SIMATIC_FM458\Request\

For the ibaCom-L2B device in the path

\04_Libraries_and_examples\40_ibaCom-L2B\02_SIMATIC_TDC\Request\

and

\04_Libraries_and_examples\40_ibaCom-L2B \03_SIMATIC_FM458\Request\

Examples are available for the following configurations:

iba SIMATIC CPU S7 project ibaPDA project

iba

BM

-

DP

S7 - FM458-1 FM458_DP_REQ_Vxx.zip ibaPDA_FM458_DP_REQ_Vxx.zip

SIMATIC TDC TDC_DP_REQ_Vxx.zip ibaPDA_TDC_DP_REQ_V01.zip

iba

BM

-

DP

M-S

S7 - FM458-1 FM458_DPMS_REQ_Vxx.zip ibaPDA_FM458_DPMS_REQ_Vxx.zip

SIMATIC TDC TDC_DPMS_REQ_Vxx.zip ibaPDA_TDC_DPMS_REQ_V01.zip

iba

Com

-

L2

B S7 - FM458-1 FM458_L2B_REQ_Vxx.zip ibaPDA_FM458_L2B_REQ_Vxx.zip

SIMATIC-TDC TDC_L2B_REQ_Vxx.zip ibaPDA_TDC_L2B_REQ_Vxx.zip

Page 33: Manual - iba-ag.com

ibaPDA-Request-FM458/TDC Manual

Issue 2.6 31

4.3 Messages

4.3.1 SERPDA

YTS YTZ Description

0 0 everything ok

1 frv *) error requesting global memory

2 frv *) error requesting VPORT-memory

3 frv *) error reading sample time

4 0 incorrect DB-address ( < 0x80000000 )

5 Order-ID unknown order-ID from ibaPDA

6 Status B block B has unexpected status

7 Sample time B sampling time of block B is 0 or bigger than of block A

8 0 DBT connector not or incorrectly connected

9 Length DB too small (less than 2200 Bytes)

12 Number number of requested values too large ( >512 )

15 Channel type transmission channel type not supported

16 Channel type unknown transmission channel type

17 0 block B doesn't answer

18 0 no valid values requested

20 frv error reading the own BGT-name

21 frv error reading the own PN-name

32 Seq no. error order sequence (unexpected follow-up message)

40 frv *) error system function sda_afpi_fp_name.

41 frv *) error system function sda_afpi_fb_anzahl_in_fp

42 frv *) error system function sda_afpi_fb_handle_nach_fb_nr

43 frv *) error system function sda_afpi_fb_name

44 frv *) error system function sda_afpi_fbk_anzahl

45 frv *) error system function sda_afpi_fbk_name

46 frv *) error system function sda_afpi_fbk_kbs

*) frv = function return values from system functions, see SIMATIC TDC/FM458 error

codes

Page 34: Manual - iba-ag.com

Manual ibaPDA-Request-FM458/TDC

32 Issue 2.6

4.3.2 SERPDB

YTS YTZ Description

0 0 everything ok

1 frv *) error requesting local memory

2 frv *) error reading sample time

3 frv *) error configuring data channel

4 0 inadmissible address on ADR-connector

5 frv *) permanent channel error

6 0 incorrect AT-connector (address level 1, station number)

7 0 incorrect AT-connector (address level 2 )

10 frv *) temporary channel error

11 0 warning, telegram buffer full

*) frv = function return values from system functions, see SIMATIC TDC/FM458 error

codes

Page 35: Manual - iba-ag.com

ibaPDA-Request-FM458/TDC Manual

Issue 2.6 33

5 Support and contact

Support

Phone: +49 911 97282-14

Fax: +49 911 97282-33

E-mail: [email protected]

Note

If you require support, indicate the serial number (iba-S/N) of the product.

Contact

Headquarters

iba AG

Koenigswarterstr. 44

90762 Fuerth

Germany

Phone: +49 911 97282-0

Fax: +49 911 97282-33

Email: [email protected]

Contact: Mr. Harald Opel

Regional and Worldwide

For contact data of your regional iba office or representative please refer to our web

site

www.iba-ag.com.