Upload
delsonmmx
View
254
Download
0
Embed Size (px)
Citation preview
8/18/2019 MANUAL AGC - 3 PART 3.pdf
1/140
MULTI-LINE 2PARAMETER LIST
AGC Automatic Genset ControllerPARAMETER LIST
Alarm list
Parameter list
Document no.: 4189340563D
8/18/2019 MANUAL AGC - 3 PART 3.pdf
2/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 2 of 140
Table of contents
1. ABOUT THIS DOCUMENT .................................................................................................... 5
GENERAL PURPOSE ...................................................................................................................... 5
INTENDED USERS.......................................................................................................................... 5
CONTENTS/OVERALL STRUCTURE .................................................................................................. 5
2. WARNINGS AND LEGAL INFORMATION ........................................................................... 6
LEGAL INFORMATION AND RESPONSIBILITY ..................................................................................... 6
ELECTROSTATIC DISCHARGE AWARENESS ..................................................................................... 6
S AFETY ISSUES ............................................................................................................................ 6
DEFINITIONS ................................................................................................................................ 6
3. ALARM LIST .......................................................................................................................... 7
ALARM TABLE OVERVIEW .............................................................................................................. 8
REVERSE POWER AND OVERCURRENT PROTECTION ..................................................................... 11
VOLTAGE PROTECTIONS ............................................................................................................. 14
FREQUENCY PROTECTIONS ......................................................................................................... 16
BUSBAR VOLTAGE PROTECTIONS................................................................................................. 19
BUSBAR FREQUENCY PROTECTIONS ............................................................................................ 22
M AINS FAILURE PROTECTIONS ..................................................................................................... 25
OVERLOAD PROTECTIONS ........................................................................................................... 26
CURRENT UNBALANCE PROTECTION ............................................................................................ 28
VOLTAGE UNBALANCE PROTECTION ............................................................................................. 28
REACTIVE POWER IMPORT (LOSS OF EXCITATION) PROTECTION .................................................... 29
REACTIVE POWER EXPORT (OVEREXCITATION) PROTECTION ......................................................... 29
NEGATIVE SEQUENCE ................................................................................................................. 30
ZERO SEQUENCE ........................................................................................................................ 31
DIRECTIONAL OVERCURRENT PROTECTION .................................................................................. 32
BUSBAR UNBALANCE VOLTAGE .................................................................................................... 33
TIME-DEPENDENT UNDERVOLTAGE .............................................................................................. 33 NON-ESSENTIAL LOAD TRIP (LOAD SHEDDING) .............................................................................. 36
UNDERVOLTAGE AND REACTIVE POWER LOW ............................................................................... 38
SYNCHRONISATION AND BREAKER ALARMS .................................................................................. 39
SYNCHRONISATION AND BREAKER ALARMS .................................................................................. 39
REGULATION ALARMS ................................................................................................................. 42
DIGITAL INPUT 23-27 SETUP ....................................................................................................... 43
DIGITAL INPUT 43-55 SETUP ....................................................................................................... 43
DIGITAL INPUT 91-97 SETUP ....................................................................................................... 44
DIGITAL INPUT 102-108 SETUP ................................................................................................... 45
DIGITAL INPUT 112-117 SETUP ................................................................................................... 46
EMERGENCY STOP ..................................................................................................................... 47
DIGITAL INPUT 127-133 SETUP ................................................................................................... 47
ANALOGUE INPUT SETUP (OPTION M15.6) ................................................................................... 48
MULTI-FUNCTIONAL ANALOGUE INPUT SETUP ............................................................................... 51
SPEED AND RUNNING FEEDBACK SETUP ....................................................................................... 63
ANALOGUE INPUT SETUP (OPTION M15.8) ................................................................................... 66
AUX. SUPPLY SETUP ................................................................................................................... 69
STOP COIL WIREBREAK AND INTERNAL COMMUNICATION ALARMS .................................................. 70
ENGINE HEATER FAILURE ............................................................................................................ 70
B ATTERY TESTS ......................................................................................................................... 71
M AX. VENTILATION ...................................................................................................................... 73
SWITCHBOARD ERROR ................................................................................................................ 74
SWITCHBOARD ERROR ................................................................................................................ 74
EXTERNAL COMMUNICATION ERROR ............................................................................................ 75
ENGINE INTERFACE COMMUNICATION ALARMS .............................................................................. 76
8/18/2019 MANUAL AGC - 3 PART 3.pdf
3/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 3 of 140
POWER MANAGEMENT COMMUNICATION ERROR ........................................................................... 79
INTERNAL CAN COMMUNICATION ERROR ..................................................................................... 79
EXTERNAL I/O ALARM SETUP ....................................................................................................... 80
4. PARAMETER LIST .............................................................................................................. 82
P ARAMETER TABLE OVERVIEW .................................................................................................... 82
SYNCHRONISATION ..................................................................................................................... 85 REGULATION .............................................................................................................................. 87
DIGITAL OUTPUT SETUP .............................................................................................................. 92
ANALOGUE OUTPUT LIMITS .......................................................................................................... 97
TRANSDUCER OUTPUTS .............................................................................................................. 98
REGULATOR OUTPUT SELECTION ............................................................................................... 103
SYSTEM ................................................................................................................................... 104
GENERAL SETUP ...................................................................................................................... 104
COUNTERS AND TIMERS ............................................................................................................ 106
ALARM HORN ............................................................................................................................ 107
RUN COIL SETUP ...................................................................................................................... 107
RUNNING, START AND STOP ...................................................................................................... 108
BREAKER CONTROL .................................................................................................................. 109
POWER DERATE ....................................................................................................................... 110
IDLE START .............................................................................................................................. 110
ENGINE HEATER ....................................................................................................................... 111
ANALOGUE LOAD SHARING LINES OUTPUT .................................................................................. 111
M ASTER CLOCK ........................................................................................................................ 112
COOLING VENTILATION .............................................................................................................. 112
SUMMER/WINTER TIME .............................................................................................................. 112
FUEL TRANSFER PUMP LOGIC .................................................................................................... 113
ALARM JUMP ............................................................................................................................ 113
M AINS SETUP ........................................................................................................................... 114
TEST ....................................................................................................................................... 115
CONTROLLER SETTINGS ............................................................................................................ 115
M AINS FAILURE ........................................................................................................................ 116 Y1(X1) DROOP CURVE .............................................................................................................. 117
Y2(X2) DROOP CURVE .............................................................................................................. 118
EXTERNAL COMMUNICATION ...................................................................................................... 120
POWER MANAGEMENT INTERNAL COMMUNICATION ..................................................................... 120
ENGINE INTERFACE COMMUNICATION......................................................................................... 121
EXTERNAL I/O COMMUNICATION SETUP...................................................................................... 122
EVENT PRINTER ........................................................................................................................ 123
POWER MANAGEMENT SETUP .................................................................................................... 124
JUMP MENUS ............................................................................................................................ 130
COMMAND TIMERS .................................................................................................................... 134
GSM SETTINGS ........................................................................................................................ 135
P ASSWORDS ............................................................................................................................ 135
VDO 102 ................................................................................................................................. 136
VDO 105 ................................................................................................................................. 138
VDO 108 ................................................................................................................................. 138
MULTI-INPUT SELECTIONS ......................................................................................................... 138
4-20 M A INPUT SCALING ........................................................................................................... 139
EXTERNAL DIGITAL OUTPUTS ..................................................................................................... 139
EXTERNAL MODULE STATUS ...................................................................................................... 139
8/18/2019 MANUAL AGC - 3 PART 3.pdf
4/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 4 of 140
This document is valid for the following products:
AGC Software version 3.6X.X or later.
8/18/2019 MANUAL AGC - 3 PART 3.pdf
5/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 5 of 140
1. About this document
This chapter includes general user information about this handbook concerning the general
purpose, the intended users and the overall contents and structure.
General purpose
This document is the complete parameter list for DEIF’s Multi-line units with software version 3.
The document includes all parameters, which means that some of the option parameters included
may not be accessible in the system in question.
Intended users
The parameter list is mainly intended for the person responsible for the unit parameter setup. In
most cases, this would be a panel builder designer. Naturally, other users might also find useful
information here.
Contents/overall structure
The Parameter List is divided into chapters and in order to make the structure of the document
simple and easy to use, each chapter will begin from the top of a new page. The following will
outline the contents of each of the chapters.
About this document
This first chapter includes general information about this handbook as a document. It deals with
the general purpose and the intended users of the Parameter List. Furthermore, it outlines the
overall contents and structure of the document.
Warnings and legal information
The second chapter includes information about general legal issues and safety precautionsrelevant in the handling of DEIF products. Furthermore, this chapter will introduce note and warning
symbols, which will be used throughout the handbook.
Procedure for parameter setup
This chapter deals with the procedure to be followed, when the parameters are set up or changed.
By use of various illustrations this chapter will guide the user through the procedure for parameter
setup step by step.
Alarm list
This chapter includes a complete standard alarm list for setup. Therefore, this chapter is to be
used for reference, when information about specific alarms is needed.
Parameter list
This chapter includes a complete standard parameter list for setup. Therefore, this chapter is to be
used for reference, when information about specific parameters is needed.
8/18/2019 MANUAL AGC - 3 PART 3.pdf
6/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 6 of 140
2. Warnings and legal information
This chapter includes important information about general legal issues relevant in the handling of
DEIF products. Furthermore, some overall safety precautions will be introduced and
recommended. Finally, the highlighted notes and warnings, which will be used throughout this
handbook, are presented.
Legal information and responsibility
DEIF takes no responsibility for installation or operation of the generator set. If there is any doubt
about how to install or operate the generator set controlled by the unit, the company responsible for
the installation or the operation of the set must be contacted.
Electrostatic discharge awareness
Sufficient care must be taken to protect the terminals against static discharges during the
installation. Once the unit is installed and connected, these precautions are no longer necessary.
Safety issues
Installing the unit implies work with dangerous currents and voltages. Therefore, the installation
should only be carried out by authorised personnel who understand the risks involved in working
with live electrical equipment.
Definitions
Throughout this document a number of notes and warnings will be presented. To ensure that these
are noticed, they will be highlighted in order to separate them from the general text.
Notes
Warnings
The notes provide general information which will be helpful for the reader to
bear in mind.
The warnings indicate a potentially dangerous situation which could result in
death, personal injury or damaged equipment, if certain guidelines are not
followed.
Be aware of the hazardous live currents and voltages. Do not touch any AC
measurement inputs as this could lead to injury or death.
The units are not to be opened by unauthorised personnel. If opened anyway, the
warranty will be lost.
8/18/2019 MANUAL AGC - 3 PART 3.pdf
7/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 7 of 140
3. Alarm list
This chapter includes a complete alarm list, including all possible options. Therefore, this
chapter is to be used for reference when specific information about the individual parameters is
needed for the unit setup. An overview list can be seen on the next page.
The table consists of the following possible adjustments:
Setpoint: The alarm setpoint is adjusted in the setpoint menu. The setting is a percentage
of the nominal values.
Delay: The timer setting is the time that must expire from the alarm level is reached
until the alarm occurs.
Relay output A: A relay can be activated by output A.
Relay output B: A relay can be activated by output B.
Enable: The alarm can be activated or deactivated. ON means always activated, RUN
means that the alarm has run status. This means it is activated when the
running signal is present.
Fail class: When the alarm occurs the unit will react depending on the selected fail class.
Fail classes are:
Fail class DG (diesel
generator)
Mains unit BTB (bus tie
breaker)
F1 Block Block Block
F2 Warning Warning WarningF3 Trip GB Trip TB Trip BTB
F4 Trip + Stop Trip MB N/A
F5 Shutdown N/A N/A
F6 Trip MB N/A N/A
F7 Safety stop N/A N/A
F8 Trip MB/GB N/A N/A
Small differences due to the character of the parameters may exist between the
individual tables.
In the following, these abbreviations are used:G: Generator
GB: Generator breaker
TB: Tie breaker (for mains unit)
MB: Mains breaker
BTB: Bus tie breaker
BA: Busbar A (BTB unit)
BB: Busbar (BTB unit: Busbar B)
N/A: Not available
8/18/2019 MANUAL AGC - 3 PART 3.pdf
8/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 8 of 140
It is also possible to configure the
parameters by using the PC utility
software. It will be possible to make the
same configurations as described above.
By using the PC utility software, extra
functionality is available. For all theprotections it is possible to make an
automatic acknowledgement of the
alarm.
Alarm table overview
Protection - Analogue input setup
1000 G/M/BA -P> 1 4000 4-20 mA 91.1
1010 G/M/BA -P> 2 4010 4-20 mA 91.2
1030 G/M/BA I> 1 4020 W. fail ana 91
1040 G/M/BA I> 2 4030 4-20 mA 93.11050 G/M/BA I> 3 4040 4-20 mA 93.2
1060 G/M/BA I> 4 4050 W. fail ana 93
4060 4-20 mA 95.1
1100 G Iv > 1-6 4070 4-20 mA 95.2
1110 G Iv > 4080 W. fail ana 95
1130 G/M/BA I>> 1 4090 4-20 mA 97.1
1140 G/M/BA I>> 2 4100 4-20 mA 97.2
1150 G/M/BA U> 1 4110 W. fail ana 97
1160 G/M/BA U> 2
1170G/M/BA U< 1 Multi-analogue input setup (-contd)
1180 G/M/BA U< 2 4120 4-20mA 102.1
1190 G/M/BA U< 3 4130 4-20mA 102.2
1200 G/M/BA voltage trip 4140 V DC 102.1
1210 G/M/BA f> 1 4150 V DC 102.2
1220 G/M/BA f> 2 4160 PT 102.1
1230 G/M/BA f> 3 4170 PT 102.2
1240 G/M/BA f< 1 4180 VDO oil 102.1
1250 G/M/BA f< 2 4190 VDO oil 102.2
1260 G/M/BA f< 3 4200 VDO water 102.1
1270 BB U> 1 4210 VDO water 102.2
1280 BB U> 2 4220 VDO fuel 102.1
1290 BB U> 3 4230 VDO fuel 102.2
1300 BB U< 1 4240 W. fail 102
1310 BB U< 2 4250 4-20mA 105.1
1320 BB U< 3 4260 4-20mA 105.2
1330 BB U< 4 4270 V DC 105.1
1340 BB Voltage trip 4280 V DC 105.2
1350 BB f> 1 4290 PT 105.1
1360 BB f> 2 4300 PT 105.2
8/18/2019 MANUAL AGC - 3 PART 3.pdf
9/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 9 of 140
1370 BB f> 3 4310 VDO oil 105.1
1380 BB f< 1 4320 VDO oil 105.2
1390 BB f< 2 4330 VDO water 105.1
1400 BB f< 3 4340 VDO water 105.2
1410 BB f< 4 4350 VDO fuel 105.1
1420 df/dt (ROCOF) 4360 VDO fuel 105.2
1430 Vector jump 4370 W. fail 105
1440 BB pos seq volt 4380 4-20mA 108.11450 G/M/BA P> 1 4390 4-20mA 108.2
1460 G/M/BA P> 2 4400 V DC 108.1
1470 G/M/BA P> 3 4410 V DC 108.2
1480 G/M/BA P> 4 4420 PT 108.1
1490 G/M/BA P> 5 4430 PT 108.2
1500 G/M Unbalance current 4440 VDO oil 108.1
1510 G/M Unbalance volt 4450 VDO oil 108.2
1520 G -Q> 4460 VDO water 108.1
1530 G Q> 4470 VDO water 108.2
1540 G/M Neg. Seq. current 4480 VDO fuel 108.1
1550 G/M Neg. seq. voltage 4490 VDO fuel 108.2
1560 Neg. seq. select 4500 W. fail 108
1570 G/M/BA zero seq. current 4510 Overspeed 1
1580 G/M/BA zero seq. voltage 4520 Overspeed 21590 Zero seq. select 4530 Crank failure
1600 G/M/BA Directional overcurrent 1 4540 Run feedb. fail
1610 G/M/BA Directional overcurrent 2 4550 MPU wirebreak
1620 BB Unbalance U 4560 Hz/V failure
1630 Ut< SP 1-3 1 4570 Start failure
1640 Ut< SP 4-6 1 4580 Stop failure
1650 Ut< Activate 1 4590 Underspeed 1
1660 Ut< 1 4960 U< aux. term. 1
1670 Ut< SP 1-3 2 4970 U> aux. term. 1
1680 Ut< SP 4-6 2 4980 U< aux. term.98
1690 Ut< Activate 2 4990 U> aux. term.98
1700 Ut< 2
1800 NEL 1 I> System
1810 NEL 2 I> - General setup1820 NEL 3 I> 6270 Stop coil wire fail
1830 NEL 1 BB f> 6280 Int. comm. fail
1840 NEL 2 BB f> 6330 Engine heater 1
1850 NEL 3 BB f>
1860 NEL 1 P> 6410 Battery test
1870 NEL 2 P> 6420 Auto battery test
1880 NEL 3 P> 6430 Battery asymmetry
1890 NEL 1 P>> 6440 Battery asymmetry 1
1900 NEL 2 P>> 6450 Battery asymmetry 2
1910 NEL 3 P>>
1960 U and Q < 1 6470 Max ventilation 1
1970 U and Q < 2 6480 Max ventilation 2
1980 GB ext. tripped
6500 Blk. swbd error
Control 6510 Stp. swbd error
- Synchronisation
2120 Sync window 6540 Not in Auto
2130 GB/TB/BTB sync failure
2140 MB sync failure System
2150 Phase seq error - Communication
2154 Phase rotation
2160 GB/TB/BTB open fail 7520 Ext. comm. error
2170 GB/TB/BTB close fail 7530 CAN fail mode
2180 GB/TB/BTB pos. fail
2200 MB open fail 7570 EI comm. error
2210 MB close fail 7580 EIC warning
2220 MB pos. fail 7590 EIC shutdown
2270 Close before excitation fail 7600 EIC overspeed
7610 EIC coolant t. 1
8/18/2019 MANUAL AGC - 3 PART 3.pdf
10/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 10 of 140
- Regulation 7620 EIC coolant t. 2
2560 GOV reg. fail 7630 EIC oil press. 1
2630 Deload error 7640 EIC oil press. 2
2680 AVR reg. fail 7650 EIC oil temp. 1
7660 EIC oil temp. 2
Input/output
- Binary input setup 7870 Any BTB missing/appl hazard
3000 Dig. input 233010 Dig. input 24 7930 CAN 1 Comm error
3020 Dig. input 25 7940 CAN 2 Comm error
3030 Dig. input 26
3040 Dig. input 27 - External I/O
12000 Ext. Ain 1.1
3130 Dig. input 43 12010 Ext. Ain 1.2
3140 Dig. input 44
3150 Dig. input 45 12030 Ext. Ain 2.1
3160 Dig. input 46 12040 Ext. Ain 2.2
3170 Dig. input 47
3180 Dig. input 48 12060 Ext. Ain 3.1
3190 Dig. input 49 12070 Ext. Ain 3.2
3200 Dig. input 50
3210 Dig. input 51 12090 Ext. Ain 4.13220 Dig. input 52 12100 Ext. Ain 4.2
3230 Dig. input 53
3240 Dig. input 54 12120 Ext. Ain 5.1
3250 Dig. input 55 12130 Ext. Ain 5.2
3330 Dig. input 91 12150 Ext. Ain 6.1
3340 Dig. input 92 12160 Ext. Ain 6.2
3350 Dig. input 93
3360 Dig. input 94 12180 Ext. Ain 7.1
3370 Dig. input 95 12190 Ext. Ain 7.2
3380 Dig. input 96
3390 Dig. input 97 12210 Ext. Ain 8.1
12220 Ext. Ain 8.2
3400 Dig. input 102 12230 4-20 mA Ext in 1 scale3410 Dig. input 105
3420 Dig. input 108 12540 Ext dig. In 1
12550 Ext dig. In 2
3430 Dig. input 112 12560 Ext dig. In 3
3440 Dig. input 113 12570 Ext dig. In 4
3450 Dig. input 114 12580 Ext dig. In 5
3460 Dig. input 115 12590 Ext dig. In 6
3470 Dig. input 116 12600 Ext dig. In 7
3480 Dig. input 117 12610 Ext dig. In 8
12620 Ext dig. In 9
3490 Emergency stop 12630 Ext dig. In 10
12640 Ext dig. In 11
3500 Dig. input 127 12650 Ext dig. In 12
3510 Dig. input 128 12660 Ext dig. In 13
3520 Dig. input 129 12670 Ext dig. In 14
3530 Dig. input 130 12680 Ext dig. In 15
3540 Dig. input 131 12690 Ext dig. In 16
3550 Dig. input 132
3560 Dig. input 133
8/18/2019 MANUAL AGC - 3 PART 3.pdf
11/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 11 of 140
Reverse power and overcurrent protection
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1000 G/M/BA reverse power 1
1001G/M/BA
–P> 1Setpoint
-200.0%
0.0%-5.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
reverse power has been
continuously above the
programmed value
during the programmed
delay.
1002G/M/BA
–P> 1Timer
0.1 s
100.0 s10.0 s
1003G/M/BA
–P> 1
Relay
output A
Not used
Option dep.Not used
1004G/M/BA
–P> 1
Relay
output B
Not used
Option dep.Not used
1005G/M/BA
–P> 1Enable
OFF
ONON
1006 G/M/BA –P> 1
Fail class F1…F8 Trip GB(F3)
1010 G/M/BA reverse power 2
1011G/M/BA
–P> 2Setpoint
-200.0%
0.0%-5.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
reverse power has been
continuously above the
programmed value
during the programmed
delay.
1012G/M/BA
–P> 2Timer
0.1 s
100.0 s10.0 s
1013G/M/BA
–P> 2
Relay
output A
Not used
Option dep.Not used
1014G/M/BA
–P> 2
Relay
output B
Not used
Option dep.Not used
1015G/M/BA
–P> 2Enable
OFF
ONON
1016G/M/BA
–P> 2Fail class F1…F8
Trip GB
(F3)
1030 G/M/BA overcurrent 1
1031G/M/BA
I> 1Setpoint
50.0%
200.0%115.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
current has been
continuously above the
programmed value
during the programmed
delay.
1032G/M/BA
I> 1Timer
0.1 s
3200.0 s10.0 s
1033G/M/BA
I> 1
Relay
output A
Not used
Option dep.Not used
1034G/M/BA
I> 1
Relay
output B
Not used
Option dep.Not used
1035G/M/BA
I> 1Enable
OFF
ONON
1036G/M/BA
I> 1Fail class F1…F8
Warning
(F2)
1040 G/M/BA overcurrent 2
1041G/M/BA
I> 2Setpoint
50.0%
200.0%120.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
current has been
continuously above the
programmed value
during the programmed
1042G/M/BA
I> 2Timer
0.1 s
3200.0 s5.0 s
1043G/M/BA
I> 2
Relay
output A
Not used
Option dep.Not used
8/18/2019 MANUAL AGC - 3 PART 3.pdf
12/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 12 of 140
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1044G/M/BA
I> 2
Relay
output B
Not used
Option dep.Not used
delay.
1045G/M/BA
I> 2Enable
OFF
ONON
1046G/M/BA
I> 2Fail class F1…F8
Trip GB
(F3)
1050 G/M/BA overcurrent 3
1051G/M/BA
I> 3Setpoint
50.0%
200.0%115.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
current has been
continuously above the
programmed value
during the programmed
delay.
1052G/M/BA
I> 3Timer
0.1 s
3200.0 s10.0 s
1053G/M/BA
I> 3
Relay
output A
Not used
Option dep.Not used
1054G/M/BA
I> 3
Relay
output B
Not used
Option dep.Not used
1055G/M/BA
I> 3Enable
OFF
ONON
1056G/M/BA
I> 3Fail class F1…F8
Trip GB
(F3)
1060 G/M/BA overcurrent 4
1061G/M/BA
I> 4Setpoint
50.0%
200.0%120.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
current has been
continuously above the
programmed value
during the programmed
delay.
1062G/M/BA
I> 4Timer
0.1 s
3200.0 s5.0 s
1063G/M/BA
I> 4
Relay
output A
Not used
Option dep.Not used
1064 G/M/BAI> 4
Relayoutput B
Not usedOption dep.
Not used
1065G/M/BA
I> 4Enable
OFF
ONON
1066G/M/BA
I> 4Fail class F1…F8
Trip GB
(F3)
1100 Voltage-dependent overcurrent curve setting
1101 G Iv > (50%)Setpoint
I1
50.0%
200.0%110.0%
@50%
nom.
voltage
Designer’s
Reference
Handbook
Settings relate to
nominal generator
current.
The condition has to be
true i.e.
I1 (100%)Setpoint
I6
50.0%
200.0%200.0%
@100
% nom.
voltage
8/18/2019 MANUAL AGC - 3 PART 3.pdf
13/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 13 of 140
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1110 Voltage-dependent overcurrent alarm
1110 G Iv > Setpoint50.0%
200.0%110.0%
Designer’s
ReferenceHandbook
The alarm and fail class
are activated when theovercurrent has been
continuously above the
programmed value
during the programmed
delay. The setpoint
value is calculated
automatically by the
values in menus 1101-
1106.
1111 G Iv > Timer0.1 s
10.0 s1.0 s
1112 G Iv >Relay
output A
Not used
Option dep.Not used
1113 G Iv >Relay
output B
Not used
Option dep.Not used
1114 G Iv > ActivateOFF
ONON
1115 G Iv > Fail class F1…F8Trip GB
(F3)
1130 G/M/BA fast overcurrent 1
1131G/M/BA
I>> 1Setpoint
150.0%
350.0%150.0%
Designer’s
Reference
Handbook
The alarm settings
relate to the nominal
current setting.
The alarm and fail class
are activated when the
current has been
continuously above the
programmed value
during the programmed
delay.
1132G/M/BA
I>> 1Timer
0.0 s
100.0 s2.0 s
1133G/M/BA
I>> 1
Relay
output A
Not used
Option dep.Not used
1134G/M/BA
I>> 1
Relay
output B
Not used
Option dep.Not used
1135G/M/BA
I>> 1Enable
OFF
ONOFF
1136G/M/BA
I>> 1Fail class F1…F8
Trip GB
(F3)
1140 G/M/BA fast overcurrent 2
1141G/M/BA
I>> 2Setpoint
150.0%
350.0%200.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
current has been
continuously above the
programmed value
during the programmed
delay.
1142G/M/BA
I>> 2Timer
0.0 s
100.0 s0.5 s
1143G/M/BA
I>> 2
Relay
output A
Not used
Option dep.Not used
1144G/M/BA
I>> 2
Relay
output B
Not used
Option dep.Not used
1145G/M/BA
I>> 2Enable
OFF
ONOFF
1146G/M/BA
I>> 2Fail class F1…F8
Trip GB
(F3)
8/18/2019 MANUAL AGC - 3 PART 3.pdf
14/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 14 of 140
Voltage protections
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1150 G/M/BA overvoltage 1
1151G/M/BA
U> 1Setpoint
100.0%
120.0%103.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
voltage has been
continuously above the
programmed value
during the programmed
delay.
1152G/M/BA
U> 1Timer
0.1 s
100.0 s10.0 s
1153G/M/BA
U> 1
Relay
output A
Not used
Option
dep.
Not used
1154G/M/BA
U> 1
Relay
output B
Not used
Option
dep.
Not used
1155G/M/BA
U> 1 EnableOFF
ON OFF
1156G/M/BA
U> 1
Fail
classF1…F8
Warning
(F2)
1160 G/M/BA overvoltage 2
1161G/M/BA
U> 2Setpoint
100.0%
120.0%105.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
voltage has been
continuously above the
programmed value
during the programmed
delay.
1162G/M/BA
U> 2Timer
0.1 s
100.0 s5.0 s
1163G/M/BA
U> 2
Relay
output A
Not used
Option
dep.
Not used
1164 G/M/BAU> 2
Relayoutput B
Not usedOption
dep.
Not used
1165G/M/BA
U> 2Enable
OFF
ONOFF
1166G/M/BA
U> 2
Fail
classF1…F8
Warning
(F2)
1170 G/M/BA undervoltage 1
1171G/M/BA
U< 1Setpoint
40.0%
100.0%97.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
voltage has been
continuously under the
programmed value
during the programmeddelay.
1172G/M/BA
U< 1Timer
0.1 s
100.0 s10.0 s
1173G/M/BA
U< 1
Relay
output A
Not usedOption
dep.
Not used
1174G/M/BA
U< 1
Relay
output B
Not used
Option
dep.
Not used
1175G/M/BA
U< 1Enable
OFF
ONOFF
1176G/M/BA
U< 1
Fail
classF1…F8
Warning
(F2)
1180 G/M/BA undervoltage 2
1181G/M/BA
U< 2
Setpoint40.0%
100.0%
95.0%Designer’s
Reference
The alarm and fail class
are activated when the
8/18/2019 MANUAL AGC - 3 PART 3.pdf
15/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 15 of 140
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1182G/M/BA
U< 2Timer
0.1 s
100.0 s5.0 s
Handbook voltage has been
continuously under the
programmed value
during the programmeddelay.1183 G/M/BAU< 2 Relayoutput A
Not used
Optiondep.
Not used
1184G/M/BA
U< 2
Relay
output B
Not used
Option
dep.
Not used
1185G/M/BA
U< 2Enable
OFF
ONOFF
1186G/M/BA
U< 2
Fail
classF1…F8
Warning
(F2)
1190 G/M/BA undervoltage 3
1191G/M/BA
U< 3Setpoint
40.0%
100.0%95.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
voltage has beencontinuously under the
programmed value
during the programmed
delay.
1192G/M/BA
U< 3Timer
0.1 s
100.0 s5.0 s
1193G/M/BA
U< 3
Relay
output A
Not used
Option
dep.
Not used
1194G/M/BA
U< 3
Relay
output B
Not used
Option
dep.
Not used
1195G/M/BA
U< 3Enable
OFF
ONOFF
1196G/M/BA
U< 3
Fail
classF1…F8
Warning
(F2)
1200 G/M/BA Voltage trip
1201G/M/BA
Voltage tripSetpoint
Ph-Ph
Ph-NPh-Ph
Designer’s
Reference
Handbook
Selection between
phase-phase or phase-
neutral voltage detection.
When phase-phase
tripping is selected, the
voltage alarms relate to
the nominal voltage.
When phase-neutral
tripping is selected, the
voltage alarms relate to
the nominal voltage
divided by √3.
8/18/2019 MANUAL AGC - 3 PART 3.pdf
16/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 16 of 140
Frequency protections
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1210 G/M/BA overfrequency 1
1211G/M/BA
f> 1Setpoint
100.0%
120.0%103.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
frequency has been
continuously above the
programmed value
during the programmed
delay.
Frequency settings
relate to nominal
frequency setting.
1212G/M/BA
f> 1Timer
0.2 s
100.0 s10.0 s
1213G/M/BA
f> 1
Relay
output A
Not
used
Option
dep.
Not used
1214G/M/BA
f> 1
Relay
output B
Not
used
Option
dep.
Not used
1215G/M/BA
f> 1Enable
OFF
ONOFF
1216G/M/BA
f> 1Fail class F1…F8
Warning
(F2)
1220 G/M/BA overfrequency 2
1221G/M/BA
f> 2Setpoint
100.0%
120.0%105.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
frequency has been
continuously above theprogrammed value
during the programmed
delay.
1222G/M/BA
f> 2 Timer0.2 s
100.0 s 5.0 s
1223G/M/BA
f> 2
Relay
output A
Not
used
Option
dep.
Not used
1224G/M/BA
f> 2
Relay
output B
Not
used
Option
dep.
Not used
1225G/M/BA
f> 2Enable
OFF
ONOFF
1226G/M/BA
f> 2Fail class F1…F8
Warning
(F2)
1230 G/M/BA overfrequency 3
1231G/M/BA
f> 3Setpoint
100.0%
120.0%105.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
frequency has been
continuously above the
programmed value
during the programmed
delay.
1232G/M/BA
f> 3Timer
0.2 s
100.0 s5.0 s
1233G/M/BA
f> 3
Relay
output A
Not
used
Option
dep.
Not used
1234G/M/BA
f> 3
Relay
output B
Not
used
Option
dep.
Not used
Frequency settings relate to the nominal frequency setting.
8/18/2019 MANUAL AGC - 3 PART 3.pdf
17/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 17 of 140
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1235G/M/BA
f> 3Enable
OFF
ONOFF
1236
G/M/BA
f> 3 Fail class F1…F8
Warning
(F2)
1240 G/M/BA underfrequency 1
1241G/M/BA
f< 1Setpoint
80.0%
100.0%97.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
frequency has been
continuously under the
programmed value
during the programmed
delay.
1242G/M/BA
f< 1Timer
0.2 s
100.0 s10.0 s
1243G/M/BA
f< 1
Relay
output A
Not
used
Option
dep.
Not used
1244G/M/BA
f< 1
Relay
output B
Not
used
Optiondep.
Not used
1245G/M/BA
f< 1Enable
OFF
ONOFF
1246G/M/BA
f< 1Fail class F1…F8
Warning
(F2)
1250 G/M/BA underfrequency 2
1251G/M/BA
f< 2Setpoint
80.0%
100.0%95.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
frequency has been
continuously under the
programmed value
during the programmed
delay.
1252G/M/BA
f< 2Timer
0.2 s
100.0 s5.0 s
1253 G/M/BAf< 2
Relayoutput A
Not
usedOption
dep.
Not used
1254G/M/BA
f< 2
Relay
output B
Not
used
Option
dep.
Not used
1255G/M/BA
f< 2Enable
OFF
ONOFF
1256G/M/BA
f< 2Fail class F1…F8
Warning
(F2)
1260 G/M/BA underfrequency 3
1261 G/M/BAf< 3
Setpoint 80.0%100.0%
95.0% Designer’sReference
Handbook
The alarm and fail classare activated when the
frequency has been
continuously under the
programmed value
during the programmed
delay.
1262G/M/BA
f< 3Timer
0.2 s
100.0 s5.0 s
1263G/M/BA
f< 3
Relay
output A
Not
used
Option
dep.
Not used
1264G/M/BA
f< 3
Relay
output B
Not
used
Option
dep.
Not used
1265G/M/BA
f< 3
EnableOFF
ON
OFF
8/18/2019 MANUAL AGC - 3 PART 3.pdf
18/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 18 of 140
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1266G/M/BA
f< 3Fail class F1…F8
Warning
(F2)
8/18/2019 MANUAL AGC - 3 PART 3.pdf
19/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 19 of 140
Busbar voltage protections
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1270 Busbar overvoltage 1
1271 BB U> 1 Setpoint100.0%
120.0%103.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
voltage has been
continuously above the
programmed value during
the programmed delay.
1272 BB U> 1 Timer0.0 s
99.99 s10.0 s
1273 BB U> 1Relay
output A
Not used
Option
dep.
Not used
1274 BB U> 1 Relayoutput B
Not usedOption
dep.
Not used
1275 BB U> 1 EnableOFF
ONOFF
1276 BB U> 1Fail
classF1…F8
Warning
(F2)
1280 Busbar overvoltage 2
1281 BB U> 2 Setpoint100.0%
120.0%105.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
voltage has been
continuously above the
programmed value during
the programmed delay.
1282 BB U> 2 Timer0.0 s
99.99 s5.0 s
1283 BB U> 2Relay
output A
Not usedOption
dep.
Not used
1284 BB U> 2Relay
output B
Not used
Option
dep.
Not used
1285 BB U> 2 EnableOFF
ONOFF
1286 BB U> 2Fail
classF1…F8
Warning
(F2)
1290 Busbar overvoltage 3
1291 BB U> 3 Setpoint100.0%
120.0%
105.0%Designer’s
ReferenceHandbook
The alarm and fail class
are activated when thevoltage has been
continuously above the
programmed value during
the programmed delay.
1292 BB U> 3 Timer0.0 s
99.99 s5.0 s
1293 BB U> 3Relay
output A
Not used
Option
dep.
Not used
1294 BB U> 3Relay
output B
Not used
Option
dep.
Not used
1295 BB U> 3 EnableOFF
ONOFF
1296 BB U> 3Fail
classF1…F8
Warning
(F2)
Voltage settings relate to the nominal voltage setting.
8/18/2019 MANUAL AGC - 3 PART 3.pdf
20/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 20 of 140
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1300 Busbar undervoltage 1
1301 BB U< 1 Setpoint40.0%
100.0%97.0%
Designer’s
ReferenceHandbook
The alarm and fail class
are activated when thevoltage has been
continuously under the
programmed value during
the programmed delay.
1302 BB U< 1 Timer0.00 s
99.99 s10.0 s
1303 BB U< 1Relay
output A
Not used
Option
dep.
Not used
1304 BB U< 1Relay
output B
Not used
Option
dep.
Not used
1305 BB U< 1 EnableOFF
ONOFF
1306 BB U< 1Fail
classF1…F8
Warning
(F2)
1310 Busbar undervoltage 2
1311 BB U< 2 Setpoint40.0%
100.0%95.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
voltage has been
continuously under the
programmed value during
the programmed delay.
1312 BB U< 2 Timer0.00 s
99.99 s5.0 s
1313 BB U< 2Relay
output A
Not used
Option
dep.
Not used
1314 BB U< 2Relay
output B
Not used
Option
dep.
Not used
1315 BB U< 2 Enable
OFF
ON OFF
1316 BB U< 2Fail
classF1…F8
Warning
(F2)
1320 Busbar undervoltage 3
1321 BB U< 3 Setpoint40.0%
100.0%97.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
voltage has been
continuously under the
programmed value during
the programmed delay.
1322 BB U< 3 Timer0.00 s
99.99 s10.0 s
1323 BB U< 3Relay
output A
Not used
Option
dep.
Not used
1324 BB U< 3 Relayoutput B
Not used
Option
dep.
Not used
1325 BB U< 3 EnableOFF
ONOFF
1326 BB U< 3Fail
classF1…F8
Warning
(F2)
1330 Busbar undervoltage 4
1331 BB U< 4 Setpoint40.0%
100.0%95.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
voltage has been
continuously under the1332 BB U< 4 Timer0.00 s
99.99 s5.0 s
8/18/2019 MANUAL AGC - 3 PART 3.pdf
21/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 21 of 140
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1333 BB U< 4Relay
output A
Not used
Option
dep.
Not used
programmed value during
the programmed delay.
1334 BB U< 4Relay
output B
Not usedOption
dep.
Not used
1335 BB U< 4 EnableOFF
ONOFF
1336 BB U< 4Fail
classF1…F8
Warning
(F2)
1340 Busbar voltage trip
1341 BB voltage trip SetpointPh-Ph
Ph-NPh-Ph
Designer’s
Reference
Handbook
Selection between phase-
phase or phase-neutral
voltage detection.
8/18/2019 MANUAL AGC - 3 PART 3.pdf
22/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 22 of 140
Busbar frequency protections
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1350 Busbar overfrequency 1
1351 BB f> 1 Setpoint100.0%
120.0%103.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
frequency has been
continuously above the
programmed value
during the programmed
delay.
1352 BB f> 1 Timer0.00 s
99.99 s10.0 s
1353 BB f> 1Relay
output A
Not used
Option
dep.
Not used
1354 BB f> 1 Relayoutput B
Not usedOption
dep.
Not used
1355 BB f> 1 EnableOFF
ONOFF
1356 BB f> 1 Fail class F1…F8Warning
(F2)
1360 Busbar overfrequency 2
1361 BB f> 2 Setpoint100.0%
120.0%105.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
frequency has been
continuously above the
programmed value
during the programmeddelay.
1362 BB f> 2 Timer0.00 s
99.99 s5.0 s
1363 BB f> 2Relay
output A
Not usedOption
dep.
Not used
1364 BB f> 2Relay
output B
Not used
Option
dep.
Not used
1365 BB f> 2 EnableOFF
ONOFF
1366 BB f> 2 Fail class F1…F8Warning
(F2)
1370 Busbar overfrequency 3
1371 BB f> 3 Setpoint100.0%
120.0%
105.0%Designer’s
ReferenceHandbook
The alarm and fail class
are activated when thefrequency has been
continuously above the
programmed value
during the programmed
delay.
1372 BB f> 3 Timer0.00 s
99.99 s5.0 s
1373 BB f> 3Relay
output A
Not used
Option
dep.
Not used
1374 BB f> 3Relay
output B
Not used
Option
dep.
Not used
1375 BB f> 3 EnableOFF
ONOFF
1376 BB f> 3 Fail class F1…F8Warning
(F2)
Frequency settings relate to the nominal frequency setting.
8/18/2019 MANUAL AGC - 3 PART 3.pdf
23/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 23 of 140
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1380 Busbar underfrequency 1
1381 BB f< 1 Setpoint
80.0%
100.0% 97.0%
Designer’s
ReferenceHandbook
The alarm and fail class
are activated when thefrequency has been
continuously under the
programmed value
during the programmed
delay.
1382 BB f< 1 Timer0.00 s
99.99 s10.0 s
1383 BB f< 1Relay
output A
Not used
Option
dep.
Not used
1384 BB f< 1Relay
output B
Not used
Option
dep.
Not used
1385 BB f< 1 EnableOFF
ONOFF
1386 BB f< 1 Fail class F1…F8Warning
(F2)
1390 Busbar underfrequency 2
1391 BB f< 2 Setpoint80.0%
100.0%95.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
frequency has been
continuously under the
programmed value
during the programmed
delay.
1392 BB f< 2 Timer0.00 s
99.99 s5.0 s
1393 BB f< 2Relay
output A
Not used
Option
dep.
Not used
1394 BB f< 2Relay
output B
Not used
Option
dep.
Not used
1395 BB f< 2 Enable
OFF
ON OFF
1396 BB f< 2 Fail class F1…F8Warning
(F2)
1400 Busbar underfrequency 3
1401 BB f< 3 Setpoint80.0%
100.0%97.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
frequency has been
continuously under the
programmed value
during the programmed
delay.
1402 BB f< 3 Timer0.00 s
99.99 s10.0 s
1403 BB f< 3Relay
output A
Not used
Option
dep.
Not used
1404 BB f< 3 Relayoutput B
Not usedOption
dep.
Not used
1405 BB f< 3 EnableOFF
ONOFF
1406 BB f< 3 Fail class F1…F8Warning
(F2)
1410 Busbar underfrequency 4
1411 BB f< 4 Setpoint80.0%
100.0%95.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
frequency has been
continuously under the1412 BB f< 4 Timer0. 00 s
99.99 s5.0 s
8/18/2019 MANUAL AGC - 3 PART 3.pdf
24/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 24 of 140
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1413 BB f< 4Relay
output A
Not used
Option
dep.
Not used
programmed value
during the programmed
delay.
1414 BB f< 4Relay
output B
Not usedOption
dep.
Not used
1415 BB f< 4 EnableOFF
ONOFF
1416 BB f< 4 Fail class F1…F8Warning
(F2)
8/18/2019 MANUAL AGC - 3 PART 3.pdf
25/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 25 of 140
Mains failure protections
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1420 Df/dt (ROCOF)
1421 Df/dt (ROCOF) Setpoint1.5 Hz/s
10.0 Hz/s5.0 Hz/s
Option A1 The alarm and fail class
are activated when the
df/dt rate has been
continuously above the
programmed value during
the programmed number
of periods (delay).
1422 Df/dt (ROCOF) Timer
3 periods
20
periods
6 periods
1423 Df/dt (ROCOF)Relay
output A
Not used
Option
dep.
Not used
1424 Df/dt (ROCOF)Relay
output B
Not used
Option
dep.
Not used
1425 Df/dt (ROCOF) EnableOFF
ONOFF
1426 Df/dt (ROCOF) Fail class F1…F8Trip MB
(F6)
1430 Vector jump
1431 Vector jump Setpoint1.0 deg.
90.0 deg.10.0 deg.
Option A1 The alarm and fail class
are activated when a
vector jump is detected.
1432 Vector jumpRelay
output A
Not used
Option
dep.
Not used
1433 Vector jumpRelay
output B
Not used
Option
dep.
Not used
1434 Vector jump EnableOFF
ONOFF
1435 Vector jump Fail class F1…F8Trip MB
(F6)
1440 Busbar positive sequence voltage low
1471 BB pos seq volt Setpoint10.0%
110.0%70.0%
Option A4 The alarm and fail class
are activated when the
symmetrical (positive
sequence) voltage has
been continuously below
the programmed value
during the programmeddelay.
The timer factory setting is
set to 2 periods. This
means that the error has
to be active in 2 whole
periods before the alarm
will be tripped.
E.g. in a 50 Hz system, the
alarm will be activated if
the positive sequence is
below 70% of U nominal
voltage for 40 ms. The
alarm will trip the fail class
as soon as possible after
this delay.
1472 BB pos seq volt Timer1 period
9 periods2 periods
1473 BB pos seq voltRelay
output A
Not used
Option
dep.
Not used
1474 BB pos seq voltRelay
output B
Not used
Option
dep.
Not used
1475 BB pos seq volt EnableOFF
ONOFF
1476 BB pos seq volt Fail class F1…F8Trip MB
(F6)
8/18/2019 MANUAL AGC - 3 PART 3.pdf
26/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 26 of 140
Overload protections
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1450 G/M/BA overload 1
1451G/M/BA
P> 1Setpoint
-200.0%
200.0%100.0%
Designer’s
Reference
Handbook
Settings relate to nominal
power.
The alarm and fail class
are activated when the
power has been
continuously above the
programmed value during
the programmed delay.
1452G/M/BA
P> 1Timer
0.1 s
3200.0 s10.0 s
1453G/M/BA
P> 1
Relay
output A
Not used
Option
dep.
Not used
1454G/M/BA
P> 1
Relay
output B
Not used
Option
dep.
Not used
1455G/M/BA
P> 1 EnableOFF
ON OFF
1456G/M/BA
P> 1Fail class F1…F8
Warning
(F2)
1460 G/M/BA overload 2
1461G/M/BA
P> 2Setpoint
-200.0%
200.0%110.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
power has been
continuously above the
programmed value during
the programmed delay.
1462G/M/BA
P> 2Timer
0.1 s
3200.0 s5.0 s
1463G/M/BA
P> 2
Relay
output A
Not used
Option
dep.
Not used
1464 G/M/BAP> 2
Relayoutput B
Not usedOption
dep.
Not used
1465G/M/BA
P> 2Enable
OFF
ONOFF
1466G/M/BA
P> 2Fail class F1…F8
Trip GB
(F3)
1470 G/M/BA overload 3
1471G/M/BA
P> 3Setpoint
-200.0%
200.0%100.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
power has been
continuously above the
programmed value during
the programmed delay.
1472G/M/BA
P> 3Timer
0.1 s
3200.0 s10.0 s
1473G/M/BA
P> 3
Relay
output A
Not usedOption
dep.
Not used
1474G/M/BA
P> 3
Relay
output B
Not used
Option
dep.
Not used
1475G/M/BA
P> 3Enable
OFF
ONOFF
1476G/M/BA
P> 3Fail class F1…F8
Trip GB
(F3)
1480 G/M/BA overload 4
1481G/M/BA
P> 4
Setpoint-200.0%
200.0%
110.0%Designer’s
Reference
The alarm and fail class
are activated when the
8/18/2019 MANUAL AGC - 3 PART 3.pdf
27/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 27 of 140
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1482G/M/BA
P> 4Timer
0.1 s
3200.0 s5.0 s
Handbook power has been
continuously above the
programmed value during
the programmed delay.1483 G/M/BAP> 4 Relayoutput A
Not used
Optiondep.
Not used
1484G/M/BA
P> 4
Relay
output B
Not used
Option
dep.
Not used
1485G/M/BA
P> 4Enable
OFF
ONOFF
1486G/M/BA
P> 4Fail class F1…F8
Trip GB
(F3)
1490 G/M/BA overload 5
1491G/M/BA
P> 5Setpoint
-200.0%
200.0%100.0%
Designer’s
Reference
Handbook
The alarm and fail class
are activated when the
power has beencontinuously above the
programmed value during
the programmed delay.
1492G/M/BA
P> 5Timer
0.1 s
3200.0 s10.0 s
1493G/M/BA
P> 5
Relay
output A
Not used
Option
dep.
Not used
1494G/M/BA
P> 5
Relay
output B
Not used
Option
dep.
Not used
1495G/M/BA
P> 5Enable
OFF
ONOFF
1496G/M/BA
P> 5Fail class F1…F8
Trip GB
(F3)
8/18/2019 MANUAL AGC - 3 PART 3.pdf
28/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 28 of 140
Current unbalance protection
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1500 G/M/BA unbalanced current
1501G/M/BA
unbalance curr.Setpoint
0.0%
100.0%30.0%
Designer’s
Reference
Handbook
Settings relate to nominal
generator current.
The alarm and fail classare activated when the
difference between the
max. reading and the min.
reading of the 3 measured
currents has been
continuously above the
programmed value during
the programmed delay.
1502G/M/BA
unbalance curr.Timer
0.1 s
100.0 s10.0 s
1503G/M/BA
unbalance curr.
Relay
output A
Not used
Option
dep.
Not used
1504G/M/BA
unbalance curr.
Relay
output B
Not used
Option
dep.
Not used
1505G/M/BA
unbalance curr. EnableOFF
ON OFF
1506G/M/BA
unbalance curr.Fail class F1…F8
Trip GB
(F3)
Voltage unbalance protection
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1510 G/M/BA unbalanced voltage
1511G/M/BA
unbalance volt.Setpoint
0.0%
50.0%10.0%
Designer’s
Reference
Handbook
Settings relate to
nominal voltage.
The alarm and fail class
are activated when the
difference between the
max. reading and the
min. reading of the 3
measured generator
voltages has been
continuously above the
programmed value
during the programmed
delay.
1512G/M/BA
unbalance volt.Timer
0.1 s
100.0 s10.0 s
1513G/M/BA
unbalance volt.
Relay
output A
Not used
Option
dep.
Not used
1514G/M/BA
unbalance volt.
Relay
output B
Not used
Option
dep.
Not used
1515G/M/BA
unbalance volt.Enable
OFF
ONOFF
1516G/M/BA
unbalance volt. Fail class F1…F8Trip GB
(F3)
8/18/2019 MANUAL AGC - 3 PART 3.pdf
29/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 29 of 140
Reactive power import (loss of excitation) protection
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1520 G/M/BA reactive power import (loss of excitation)
1521 G/M/BA –Q> Setpoint0.0%
150.0%50.0%
Designer’s
Reference
Handbook
Settings relate to
nominal power.
The alarm and fail class
are activated when
imported VAr has been
continuously above the
programmed value
during the programmed
delay.
1522 G/M/BA –Q> Timer0.1 s
100.0 s10.0 s
1523 G/M/BA –Q>Relay
output A
Not used
Option
dep.
Not used
1524 G/M/BA –Q>Relay
output B
Not used
Option
dep.
Not used
1525 G/M/BA –Q> EnableOFF
ON OFF
1526 G/M/BA –Q> Fail class F1…F8Warning
(F2)
Reactive power export (overexcitation) protection
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1530 G/M/BA reactive power export (overexcitation)
1531 G/M/BA Q> Setpoint0.0%
100.0%60.0%
Designer’s
Reference
Handbook
Settings relate to
nominal power.
The alarm and fail class
are activated when
exported VAr has been
continuously above the
programmed value
during the programmed
delay.
1532 G/M/BA Q> Timer0.1 s
100.0 s10.0 s
1533 G/M/BA Q>Relay
output A
Not used
Option
dep.
Not used
1534 G/M/BA Q>Relay
output B
Not used
Option
dep.
Not used
1535 G/M/BA Q> EnableOFF
ONOFF
1536 G/M/BA Q> Fail class F1…F8Warning
(F2)
8/18/2019 MANUAL AGC - 3 PART 3.pdf
30/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 30 of 140
Negative sequence
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1540 G/M/BA negative sequence current
1541G/M/BA neg
seq ISetpoint
1.0%
100.0%20.0%
Option C2 Settings relate to
nominal current.
The alarm and fail
class are activated
when the negative
sequence has been
continuously above the
programmed value
during the programmed
delay.
1542G/M/BA neg
seq ITimer
0.2 s
100.0 s0.5 s
1543G/M/BA neg
seq I
Relay
output A
Not used
Option dep.Not used
1544G/M/BA neg
seq I
Relay
output B
Not used
Option dep.Not used
1545G/M/BA neg
seq IEnable
OFF
ONOFF
1546 G/M/BA negseq I
Failclass
F1…F8 Trip MB(F6)
1550 G/M/BA negative sequence voltage
1551G/M/BA neg
seq USetpoint
1.0%
100.0%5.0%
Option C2 Settings relate to
nominal voltage.
The alarm and fail
class are activated
when the negative
sequence has been
continuously above the
programmed value
during the programmed
delay.
1552G/M/BA neg
seq UTimer
0.2 s
100.0 s0.5 s
1553G/M/BA neg
seq U
Relay
output A
Not used
Option dep.Not used
1554G/M/BA neg
seq U
Relay
output B
Not used
Option dep.Not used
1555G/M/BA neg
seq UEnable
OFF
ONOFF
1556G/M/BA neg
seq U
Fail
classF1…F8
Trip MB
(F6)
1560 G/M/BA negative sequence selection
1561G/M/BA neg
seq selectSetpoint
G/M/BA
measurement
BB
measurement
G/M/BA
measurement
Option C2 Selection between
generator or busbar
measurement of
negative sequence
voltage.
8/18/2019 MANUAL AGC - 3 PART 3.pdf
31/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 31 of 140
Zero sequence
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1570 G/M/BA zero sequence current
1571G/M/BA zero
seq ISetpoint
0.0%
100.0%20.0%
Option C2 Settings relate to
nominal current.
The alarm and fail
class are activated
when the zero
sequence has been
continuously above the
programmed value
during the programmed
delay.
1572G/M/BA zero
seq ITimer
0.2 s
100.0 s0.5 s
1573G/M/BA zero
seq I
Relay
output A
Not used
Option dep.Not used
1574G/M/BA zero
seq I
Relay
output B
Not used
Option dep.Not used
1575G/M/BA zero
seq IEnable
OFF
ONOFF
1576 G/M/BA zeroseq I
Failclass
F1…F8 Trip MB(F6)
1580 G/M/BA zero sequence voltage
1581G/M/BA zero
seq USetpoint
0.0%
100.0%5.0%
Option C2 Settings relate to
nominal voltage.
The alarm and fail
class are activated
when the zero
sequence has been
continuously above the
programmed value
during the programmed
delay.
1582G/M/BA zero
seq UTimer
0.2 s
100.0 s0.5 s
1583G/M/BA zero
seq U
Relay
output A
Not used
Option dep.Not used
1584G/M/BA zero
seq U
Relay
output B
Not used
Option dep.Not used
1585G/M/BA zero
seq UEnable
OFF
ONOFF
1586G/M/BA zero
seq U
Fail
classF1…F8
Trip MB
(F6)
1590 G/M/BA zero sequence selection
1591G/M/BA zero
seq selectSetpoint
G/M/BA
measurement
BB
measurement
G/M/BA
measurement
Option C2 Selection between
generator or busbar
measurement of zero
sequence voltage.
8/18/2019 MANUAL AGC - 3 PART 3.pdf
32/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 32 of 140
Directional overcurrent protection
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1600 G/M/BA directional overcurrent 1
1601G/M/BA I> direct
1Setpoint
-200.0%
200.0%120.0%
Option A5 Settings relate to
nominal current.
The alarm and fail class
are activated when the
directional current has
been continuously above
the programmed value
during the programmed
delay.
The current
measurement is positive
when current is supplied
from the mains to theplant. The current
measurement is
negative when current is
being supplied to the
mains.
1602G/M/BA I> direct
1Timer
0.0 s
100.0 s0.1 s
1603G/M/BA I> direct
1
Relay
output A
Not used
Option
dep.
Not used
1604G/M/BA I> direct
1
Relay
output B
Not used
Option
dep.
Not used
1605G/M/BA I> direct
1 EnableOFF
ON OFF
1606G/M/BA I> direct
1Fail class F1…F8
Trip MB
(F6)
1610 G/M/BA directional overcurrent 2
1611G/M/BA I> direct
2Setpoint
-200.0%
200.0%130.0%
Option A5 Settings relate to
nominal current.
The alarm and fail class
are activated when the
directional current has
been continuously above
the programmed valueduring the programmed
delay.
The current
measurement is positive
when current is supplied
from the mains to the
plant. The current
measurement is
negative when current is
being supplied to the
mains.
1612G/M/BA I> direct
2Timer
0.0 s
100.0 s0.1 s
1613G/M/BA I> direct
2
Relay
output A
Not used
Option
dep.
Not used
1614G/M/BA I> direct
2
Relay
output B
Not used
Option
dep.
Not used
1615G/M/BA I> direct
2Enable
OFF
ONOFF
1616G/M/BA I> direct
2Fail class F1…F8
Trip MB
(F6)
8/18/2019 MANUAL AGC - 3 PART 3.pdf
33/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 33 of 140
Busbar unbalance voltage
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1620 BB unbalance U
1621 BB unbalance U Setpoint0.0%
50.0%6.0%
Designer’s
Reference
Handbook
Settings relate to average
actual voltage.
The alarm and fail class
are activated when the
difference between the
max. reading and the min.
reading of the 3 measured
busbar voltages has been
continuously above the
programmed value during
the programmed delay.
1622 BB unbalance U Timer0.1 s
100.0 s
10.0 s
1623 BB unbalance URelay
output A
Not used
Option
dep.
Not used
1624 BB unbalance URelay
output B
Not used
Option
dep.
Not used
1625 BB unbalance U EnableOFF
ON OFF
1626 BB unbalance U Fail class F1…F8Warning
(F2)
Time-dependent undervoltage
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1630 Time-dependent undervoltage 1 1-3
1631 Ut < 1 Setting 1
30.0%
120.0% 30.0%
Option A1 Curve setting for time-
dependent undervoltage.
Settings relate to
nominal generator
voltage.
The condition has to be
true i.e.
Ut(1)1≤Ut(2)≤Ut(3)≤
Ut(4)≤Ut(5)≤Ut(6).
If this is not fulfilled, the
worst-case setpoint Ut(6)
will be used.
1632 Ut < 1 Delay 10.00 s
20.00 s0.15 s
1633 Ut < 1 Setting 230.0%
120.0%70.0%
1634 Ut < 1 Delay 20.00 s
20.00 s0.15 s
1635 Ut < 1 Setting 330.0%
120.0%70.0%
1636 Ut < 1 Delay 30.00 s
20.00 s0.70 s
1640 Time-dependent undervoltage 1 4-6
1641 Ut < 1 Setting 430.0%
120.0%90.0%
Option A1 Curve setting for time-
dependent undervoltage.
Settings relate to
nominal generator
voltage.
The condition has to be
true i.e.
Ut(1)1≤Ut(2)≤Ut(3)≤
Ut(4)≤Ut(5)≤Ut(6).
If this is not fulfilled, the
worst-case setpoint Ut(6)
will be used.
1642 Ut < 1 Delay 40.00 s
20.00 s1.50 s
1643 Ut < 1 Setting 530.0%
120.0%90.0%
1644 Ut < 1 Delay 50.00 s
20.00 s2.00 s
1645 Ut < 1 Setting 630.0%
120.0%90.0%
1646 Ut < 1 Delay 60.00 s
20.00 s3.00 s
8/18/2019 MANUAL AGC - 3 PART 3.pdf
34/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 34 of 140
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1650 Time-dependent undervoltage 1 activation
1651 Ut < act 1 Activate30.0%
120.0%90%
Option A1 Activate is the voltage
value where the functiontimer starts.
Reset is the value where
the function timer is
reset to 0 ms.
Delay is the delay timer
for the reset.
The relay outputs will
activate immediately
when the function timer
starts.
1652 Ut < act 1 Recovery30.0%
120.0%95%
1653 Ut < act 1 Delay0.0 s
320.0 s1.00 s
1654 Ut < act 1 Relay
output A
Not used
Option
dep.
Not used
1655 Ut < act 1 Relay
output B
Not used
Option
dep.
Not used
1656 Ut < act 1 EnableOFF
ONOFF
1660 Time-dependent undervoltage 1
1661 Ut < 1Relay
output A
Not used
Option
dep.
Not used
Option A1 The alarm and fail class
is activated
instantaneously when
the voltage value is
under the programmed
value curve.1662 Ut < 1
Relay
output B
Not used
Option
dep.
Not used
1663 Ut < 1 EnableOFF
ONOFF
1664 Ut < 1 Fail class F1…F8Trip MB
(F6)
1670 Time-dependent undervoltage 2 1-3
1671 Ut < 2 Setting 130.0%
120.0%30.0%
Option A1 Curve setting for time-
dependent undervoltage.
Settings relate to
nominal generator
voltage.
The condition has to be
true i.e.
Ut(1)1≤Ut(2)≤Ut(3)≤
Ut(4)≤Ut(5)≤Ut(6).
If this is not fulfilled, the
worst-case setpoint Ut(6)
will be used.
1672 Ut < 2 Delay 10.00 s
20.00 s0.15 s
1673 Ut < 2 Setting 230.0%
120.0%70.0%
1674 Ut < 2 Delay 20.00 s
20.00 s0.15 s
1675 Ut < 2 Setting 330.0%
120.0%70.0%
1676 Ut < 2 Delay 30.00 s
20.00 s0.70 s
1680 Time-dependent undervoltage 2 4-6
1681 Ut < 2 Setting 430.0%
120.0%90.0%
Option A1 Curve setting for time-
dependent undervoltage.
Settings relate to
nominal generator
voltage.
The condition has to be
true i.e.
Ut(1)1≤Ut(2)≤Ut(3)≤
Ut(4)≤Ut(5)≤Ut(6).
If this is not fulfilled, the
worst-case setpoint Ut(6)
1682 Ut < 2 Delay 40.00 s
20.00 s1.50 s
1683 Ut < 2 Setting 530.0%
120.0%90.0%
1684 Ut < 2 Delay 50.00 s
20.00 s2.00 s
1685 Ut < 2 Setting 630.0%
120.0%90.0%
8/18/2019 MANUAL AGC - 3 PART 3.pdf
35/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 35 of 140
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1686 Ut < 2 Delay 60.00 s
20.00 s3.00 s
will be used.
1690 Time-dependent undervoltage 2 activation
1691 Ut < act 2 Activate30.0%
120.0%90%
Option A1 Activate is the voltage
value where the function
timer starts.
Reset is the value where
the function timer is
reset to 0 ms.
Delay is the delay timer
for the reset.
The relay output will
activate immediately
when the function timer
starts.
1692 Ut < act 2 Recovery30.0%
120.0%95%
1693 Ut < act 2 Delay0.0 s
320.0 s1.00 s
1694 Ut < act 2 Relay
output A
Not used
Option
dep.
Not used
1695 Ut < act 2 Relay
output B
Not used
Option
dep.
Not used
1696 Ut < act 2 Enable OFFON
OFF
1700 Time-dependent undervoltage 2
1701 Ut < 2Relay
output A
Not used
Option
dep.
Not used
Option A1 The alarm and fail class
is activated
instantaneously when
the voltage value is
under the programmed
value curve.1702 Ut < 2
Relay
output B
Not used
Option
dep.
Not used
1703 Ut < 2 EnableOFF
ONOFF
1704 Ut < 2 Fail class F1…F8
Trip MB
(F6)
8/18/2019 MANUAL AGC - 3 PART 3.pdf
36/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 36 of 140
Non-essential load trip (load shedding)
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1800 NEL 1 overcurrent
1801 NEL 1 I> Setpoint50.0%
200.0%100.0%
Designer’s
Reference
Handbook
Trip of non-essential load
due to overcurrent. This
function activates NEL
group 1.1802 NEL 1 I> Timer0.1 s
100.0 s5.0 s
1803 NEL 1 I> EnableOFF
ONOFF
1810 NEL 2 overcurrent
1811 NEL 2 I> Setpoint50.0%
200.0%100.0%
Designer’s
Reference
Handbook
Trip of non-essential load
due to overcurrent. This
function activates NEL
group 2.1812 NEL 2 I> Timer0.1 s
100.0 s8.0 s
1813 NEL 2 I> EnableOFF
ONOFF
1820 NEL 3 overcurrent
1821 NEL 3 I> Setpoint50.0%
200.0%100.0%
Designer’s
Reference
Handbook
Trip of non-essential load
due to overcurrent. This
function activates NEL
group 3.1822 NEL 3 I> Timer0.1 s
100.0 s10.0 s
1823 NEL 3 I> Enable OFFON
OFF
1830 NEL 1 busbar underfrequency
1831 NEL 1 bus f< Setpoint70.0%
100.0%95.0%
Designer’s
Reference
Handbook
Trip of non-essential load
due to low frequency. This
function activates NEL
group 1.1832 NEL 1 bus f< Timer0.1 s
100.0 s5.0 s
1835 NEL 1 bus f< EnableOFF
ONOFF
1840 NEL 2 busbar underfrequency
1841 NEL 2 bus f< Setpoint
70.0%
100.0% 95.0%
Designer’s
Reference
Handbook
Trip of non-essential load
due to low frequency. This
function activates NEL
group 2.1842 NEL 2 bus f< Timer0.1 s
100.0 s8.0 s
1845 NEL 2 bus f< EnableOFF
ONOFF
1850 NEL 3 busbar underfrequency
1851 NEL 3 bus f< Setpoint70.0%
100.0%95.0%
Designer’s
Reference
Handbook
Trip of non-essential load
due to low frequency. This
function activates NEL
group 3.1852 NEL 3 bus f< Timer0.1 s
100.0 s10.0 s
1855 NEL 3 bus f< EnableOFF
ONOFF
Setting values relate to the nominal setting.
8/18/2019 MANUAL AGC - 3 PART 3.pdf
37/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 37 of 140
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1860 NEL 1 overload
1861 NEL 1 P> Setpoint10.0%
200.0%100.0%
Designer’s
ReferenceHandbook
Trip of non-essential load
due to overload. Thisfunction activates NEL
group 1.1862 NEL 1 P> Timer0.1 s
100.0 s5.0 s
1865 NEL 1 P> EnableOFF
ONOFF
1870 NEL 2 overload
1871 NEL 2 P> Setpoint10.0%
200.0%100.0%
Designer’s
Reference
Handbook
Trip of non-essential load
due to overload. This
function activates NEL
group 2.1872 NEL 2 P> Timer0.1 s
100.0 s8.0 s
1875 NEL 2 P> EnableOFF
ONOFF
1880 NEL 3 overload
1881 NEL 3 P> Setpoint10.0%
200.0%100.0%
Designer’s
Reference
Handbook
Trip of non-essential load
due to overload. This
function activates NEL
group 3.1882 NEL 3 P> Timer0.1 s
100.0 s10.0 s
1885 NEL 3 P> EnableOFF
ONOFF
1890 NEL 1 high overload
1891 NEL 1 P>> Setpoint10.0%
200.0%110.0%
Designer’s
Reference
Handbook
Trip of non-essential load
due to high overload. This
function activates NEL
group 1.1892 NEL 1 P>> Timer 0.1 s999.9 s 1.0 s
1895 NEL 1 P>> EnableOFF
ONOFF
1900 NEL 2 high overload
1901 NEL 2 P>> Setpoint10.0%
200.0%110.0%
Designer’s
Reference
Handbook
Trip of non-essential load
due to high overload. This
function activates NEL
group 2.1902 NEL 2 P>> Timer0.1 s
999.9 s1.0 s
1905 NEL 2 P>> EnableOFF
ONOFF
1910 NEL 3 high overload
1911 NEL 3 P>> Setpoint10.0%
200.0%110.0%
Designer’s
Reference
Handbook
Trip of non-essential load
due to high overload. This
function activates NEL
group 3.1912 NEL 3 P>> Timer0.1 s
999.9 s1.0 s
1915 NEL 3 P>> EnableOFF
ONOFF
8/18/2019 MANUAL AGC - 3 PART 3.pdf
38/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 38 of 140
Undervoltage and reactive power low
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
1960 U and Q < 1
1961 U and Q < 1 Setpoint40.0%
100.0%85.0%
Option A1 The setting relates to the
generator nominal
voltage.
The condition for trip is
that the actual voltage
drops below the setting
value and the reactive
power is ≤ 0 kVAr.
1962 U and Q < 1 Timer0.1 s
3200.0 s0.5 s
1963 U and Q < 1Relay
output A
Option
dep.Not used
1964 U and Q < 1Relay
output B
Option
dep.Not used
1965 U and Q < 1 EnableOFF
ONOFF
1966 U and Q < 1 Fail class F1…F8 Warning(F2)
1970 U and Q < 2
1971 U and Q < 2 Setpoint40.0%
100.0%85.0%
Option A1 The setting relates to the
generator nominal voltage.
The condition for trip is that
the actual voltage drops
below the setting value and
the reactive power is ≤ 0
kVAr.
1972 U and Q < 2 Timer0.1 s
3200.0 s0.5 s
1973 U and Q < 2Relay
output A
Option
dep.Not used
1974 U and Q < 2Relay
output B
Option
dep.Not used
1975 U and Q < 2 EnableOFF
ONOFF
1976 U and Q < 2 Fail class F1…F8Warning
(F2)
1980 GB/MB external trip
1981 GB ext. trip EnableOFF
ONON
Designer’s
Reference
Handbook
The generator breaker or
the mains breaker has
been tripped by an
external device.1982 GB ext. trip Fail class F1…F8Warning
(F2)
1983 MB ext. trip EnableOFF
ONON
1984 MB ext. trip Fail class F1…F8Warning
(F2)
8/18/2019 MANUAL AGC - 3 PART 3.pdf
39/140
AGC-3 Alarm and Parameter List
DEIF A/S Page 39 of 140
Synchronisation and breaker alarms
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
2120 Synchronisation window
2121 Sync window Setpoint2.0%
20.0%15.0%
Designer’s
Reference
Handbook
The alarm will activate if
the actual voltage deviates
from nominal voltage with
the set percentage.2122 Sync window Timer0.1 s
2.0 s0.5 s
2123 Sync windowRelay
output A
Not used
Option
dep.
Not used
2124 Sync windowRelay
output B
Not used
Option
dep.
Not used
2125 Sync window Ena