2212020091.0504/08/17Page 1 of 20
Atlas Copco Ltd. trading as Atlas Copco MedicalUnit 18 Nuffield Way, Abingdon, Oxfordshire, UK OX14 1RLwww.beaconmedaes.com
Medical Air Plant SystemThe Medical Air system shall conform to EN ISO 7396-1 and NHS Health Technical Memorandum HTM02-01 (or NHS Health Technical Memorandum HTM2022 EurPh if selected). Medical quality air to the European Pharmacopoeia monograph shall be delivered at pressures of 400 kPa (4 bar), 700kPa (7 bar) or 10,000 kPa (10 bar) gauge for supply of the hospital medical or surgical air systems. The entire system shall be ‘duplexed’ such that any single functional component failure will not affect the integrity of the medical compressed air supply.
Sources Of Supply - HTM02-01/EN ISO 7396-1Triplex or quadruplex compressor configurations will produce the primary supply with two compressors in standby. Each compressor will be capable of supplying the specified volumetric flow for duplex and triplex plant, and half flow for quadruplex. For duplex plant the secondary supply shall be from an automatic manifold capable of supplying at average demand for 4 hours. For triplex and quadruplex plant the standby compressors will form the secondary supply.
Sources Of Supply - HTM2022 EurPhDuplex, triplex or quadruplex compressor configurations will produce the primary supply with one compressor on standby. A secondary supply shall be from an automatic manifold capable of supplying at average demand for 4 hours.
Control SystemThe central control system shall provide an intelligent human machine interface incorporating on board flash memory and real-time clock for recording operational parameters in the in built event log. The central control system shall operate at low voltage and include BMS connection for plant fault, plant emergency, reserve fault and pressure fault. Visualisation of plant inputs, outputs and status through a web browser, using a simple Ethernet connection shall be available. The central control unit shall incorporate a user friendly 5.7” high-definition colour display with clear pictograms and LED indicators, providing easy access to system operational information.
A mechanical back-up facility shall ensure continued operation in the event of a control system malfunction. The control system shall normally employ automatic rotation of the lead compressor to maximise life and ensure even wear.
Oil-Free CompressorsCompressors shall be Atlas Copco Medical (MED), oil free compressors suitable for both continuous and frequent start/stop operation at a nominal outlet pressure of 8,000 kPa (8 bar), 10,000 kPa (10 bar) or 13,000 kPa (13 bar) gauge. The following technology types shall be available:
Technology Nominal Output Pressure
LF-MED - Reciprocating (piston)* 10 bar
SF-MED - Scroll 10 bar
ZT (VSD option) - Tooth 10 bar / 8 bar
mAIR Oil Free Medical Air Plant Systems– EN ISO 7396-1/HTM 02-01 and HTM2022 EurPh
380V 60Hz, 4 bar, 7 Bar & 10 Bar OutletSPECIFICATION
OIL
-FRE
E M
EDIC
AL
AIR
SYS
TEM
S
* LE-MED (oil-less piston) with 13 bar outlet available upon request
Refer to diagram 1. Technology versus flow and pressure for selecting a suitable compressor technology for the intended application.
ISO Compressors shall conform to ISO 7396-1 standards. HTM Compressor shall comply with HTM02-01/HTM2022 standards and shall include an additional pressure sensor and temperature sensor, required for transmitting additional alarm conditions. An additional analogue ammeter and inter locking isolator shall also be included.
UL, AS and MOM standard compressors (including 3rd party certification) are all available as standard - please contact sales. Water cooled version of compressors shall be available for international regions with high ambient temperature environment
Variable Speed Drive - OptionalVariable Speed Drive (VSD) shall be available on compressor(s). By including an AC-DC converter, along with associated control hardware and software it will enable the compressor to match it’s running speed on a 1:1 ratio with the flow demand required by hospital. By using such technology energy of savings of up to 35% shall be achievable as well as prolonged machine life. Start currents will be reduced and the motor will run from 0-100% speed increasing or decreasing it’s speed as necessary to continuously match the required demand. The compressor shall operate from 400-1300kPa (4-13 bar) gauge.
VSD air plant shall incorporate VSD controllers on all compressors, cycling the lead compressor to ensure even wear as per HTM02-01 requirements.
Dryer/Filter/Regulator SystemThe duplexed filter and dryer module shall incorporate high efficiency water separators, filters, heatless regenerative desiccant dryer, dust/activated carbon filters, hopcolite filters (option) and bacterial filters with autoclavable element. Electrical contacts shall be installed on the filters to provide warning alarms on the dryer controller in the event of high pressure drop (ie blockage) and shall also include connections for BMS. Contaminants in the delivered air downstream of the bacterial filters shall be maintained at levels below those shown in the following table:
Contaminant Threshold
H2O 67 ppm v/v
Dry particulates Free from visible particulates in a 75 litre sample
Oil (droplet or mist) 0.1 mg/m³
CO 5 ppm v/v
CO2 500 ppm v/v
SO2 1 ppm v/v
NO 2 ppm v/v
NO2 2 ppm v/v
2212020091.0504/08/17Page 2 of 20
Atlas Copco Ltd. trading as Atlas Copco MedicalUnit 18 Nuffield Way, Abingdon, Oxfordshire, UK OX14 1RLwww.beaconmedaes.com
Dryer Purge Control - OptionalThe dryer control system shall incorporate a Purge Saver Energy Management system that freezes the regeneration of the desiccant once adequate dew point is reached in the inactive tower. Only when the dewpoint level in the active tower deteriorates to an unacceptable level will the intelligent controller switch towers. This shall be achieved by including an additional dew point sensor and associated software in the dryer controller to effectively manage the system as well as providing on screen measurements of purge savings.
Dew Point MonitoringThe dryer shall incorporate a ceramic dew point hygrometer with an accuracy of ±10C in the range -20 to -800C atmospheric dew point and 4-20mA analogue output. Aluminium oxide or palladium wire sensors are not acceptable. An alarm condition shall trigger on the dryer control panel if the dew point exceeds a -460C atmospheric set point. The plant control unit shall incorporate a multifunctional LCD displaying, amongst other things, the dew point of the delivered air to enable monitoring of the air quality by the hospitals estates department. Volt free contacts shall be included to enable the dew point alarm signal to be connected to a central medical gas alarm system and/or building management system (BMS). To enable periodic calibration of the dew point sensor element, the hygrometer shall be remotely connected downstream of the dryer via a micro-bore tube. It is not acceptable to install the sensor directly into the medical air supply pipeline.
Receiver AssemblyAir receivers shall comply with DIRECTIVE 97/23/EC, supplied with relevant test certificates. Each air receiver shall be of steel construction with a powder coated paint finish and shall be fitted with a zero loss electronic drain valve. Float type drain valves are not acceptable. The receiver assembly shall be fitted with a pressure safety valve capable of passing the maximum flow output of the compressor at 10% receiver overpressure. The receiver shall be further protected by a safety pressure relief valve and include a pressure gauge.
Optional ItemsThere shall be the followings options available for enhanced operation of the air plant system:-
• MOM standard receivers with 3rd party certification, hot dip galvanised steel inside and out
• EWD zero loss electronic water drains for the dMED dryer including secure mounting to the dryer base
• VSD compressors• CO and CO2 monitors including full integration into the ES-MED
central controller giving alarm warnings when unacceptable CO and CO2 levels are present
Condensate Management Options
OSS Oil/water separator, 900/1500/1800 l/min at 20/25/35 degrees celcius - metric 8102046466
OSS Oil/water separator, 900/1500/1800 l/min at 20/25/35 degrees celcius - imperial 8102046458
* NOTE - SUITABLE FOR SMALLER COMPRESSORS LE5-10/GA5-11/GA VSD+ 7-11
OSC35 Oil/water separator, 2100 l/min 8102 0452 45
OSC95 Oil/water separator, 5700 l/min 8102 0452 52
OSC145 Oil/water separator, 8700 l/min 8102 0452 60
OSC355 Oil/water separator, 21300 l/min 8102 0452 78
CE MarkingThe standard range of BeaconMedæs Medical Air plant systems are ‘CE’ marked under the Medical Devices Directive 93/42/EEC with approval from notified body no. 0088 (Lloyd’s Register Quality Assurance). Under this directive, the specified products are classified as Class IIa Medical Devices.
2212020091.0504/08/17Page 3 of 20
Atlas Copco Ltd. trading as Atlas Copco MedicalUnit 18 Nuffield Way, Abingdon, Oxfordshire, UK OX14 1RLwww.beaconmedaes.com
Diagram 1. Technology versus flow and pressure
2212020091.0504/08/17Page 4 of 20
Atlas Copco Ltd. trading as Atlas Copco MedicalUnit 18 Nuffield Way, Abingdon, Oxfordshire, UK OX14 1RLwww.beaconmedaes.com
Receiver Selection Table
Receiver Capacity (litres) 250 500 1000 1500 2000 3000
Maximum working pressure (bar) 11 11 11 11 11 11
Individual Receiver Dimensions (diameter, height, mm) 457/2000 610/2105 762/2580 900/2600 1067/2725 1220/3010
Receiver Weight (kg) 155 195 380 520 800 1000
Receiver pipe size (mm) 28 28 42 42 42 42
Receiver Part Number 8102340570 8102340574 8102340576 8102340578 8102340580 8102340582
Receiver Accessory Kit 8102340590 8102340594 8102340596 8102340598 8102340600 8102340602
Receiver Capacity (litres) 250 500 1000 1500 2000 3000
Maximum working pressure (bar) 14 14 14 14 14 14
Individual Receiver Dimensions (diameter, height, mm) 457/2000 610/2105 762/2580 900/2600 1067/2725 1220/3010
Receiver Weight (kg) 160 200 500 520 950 1200
Receiver pipe size (mm) 28 28 42 42 42 42
Receiver Part Number 8102340571 8102340575 8102340577 8102340579 8102340581 8102340583
Receiver Accessory Kit 8102340591 8102340595 8102340597 8102340599 8102340601 8102340603
* Accessory kit for medical air receiver complete with plant data plate, test certificate, pressure safety valve, zero-loss electronic drain valve (with isolation and bypass valve), pressure gauge (with isolation valve), safety pressure relief valve, fusible plug, copper inlet and outlet union connection pipes (each with isolation valve).
Combined Air Plant Sizing Guide - HTM02-01In HTM02-01, the relative size of receiver capacity and compressor capacity on surgical air or combined medical/surgical air systems changes according to the design flow rate. In order to correctly calculate the receiver capacity and compressor capacity, both the medical and surgical design flow-rates (DF’s) are required. It should be noted that for all combined air systems, an additional duplex regulating station (ordered separately) is needed to supply the medical air pipeline.
Table 1: Surgical Air Plant Flow Rate Multiplier Value ‘A’.
Surgical Air Compressors
Design Flow (l/min)
Value ‘A’ FAD (l)
<500 0.33 x DF
500-3500 0.66 x DF
>3500 0.5 x DF
Table 2: Surgical Air Receiver Multiplier Value ‘B’.
Surgical Air Receivers
Design Flow (l/min)
Value ‘B’ Receiverwater capacity (l)
<500 1 x 200% x DF
500-2000 2 x 66.6% x DF
2001-3500 2 x 50% x DF
>3500 3 x 33.3% x DF
2212020091.0504/08/17Page 5 of 20
Atlas Copco Ltd. trading as Atlas Copco MedicalUnit 18 Nuffield Way, Abingdon, Oxfordshire, UK OX14 1RLwww.beaconmedaes.com
Example 1 - Small Day Treatment Centre (Upgrade)
Flow Rate and Dryer SizingMedical Air DF = 555 l/min (FAD) (4 Bar)Surgical Air DF = 1138 l/min (FAD) (7 Bar)Combined/total DF = 1693 l/min (FAD) (11 Bar high pressure system)
A dryer greater than 1693 l/min outlet flow should be selected (outlet flow is the inlet flow minus purge losses)= dMED25 inlet flow 2025 l/min, outlet flow 1746 l/min Flow Rate and Compressor SizingFrom Table 1 surgical air DF is between 500-3500 l/min, so the multiplying factor ‘A’ = 0.66
Compressor flow rate = Med. DF + (Surg. DF x A) = 555 + (1138 x 0.66) = 555 + 751 = 1306 l/min
We also need to add the purge losses to the compressor output. For additional purge consumption use:- dMED inlet - dMED outlet = purge losses lpm = 2025 - 1746 = 279 l/min
Compressors should be selected with a flow rate greater than 1306 l/min + 279 l/min = 1585 l/min
Receiver SizingFrom Table 2 surgical air DF is between 500-2000 l/min, so the multiplying factor ‘B’ = 2 x 2/3
Capacity = (Med. DF x 0.5) + (Surg. DF x B) = (555 x 0.5) + (1138 x 2 x 2/3) = 278 + 1518 = 1796 litres
A combination of receivers with a minimum number of 2 should be selected
Selected receiver capacity = 2000 litres (2 x 1000 litre)
Plant System SelectionSelected plant part number = Piston cAIR-1930-PLF or Tooth cAIR-2142-TZF.
If no standard model is available for selection from the standard range a bespoke configuration of dryer, compressors and receivers
are available and can be quoted by our sales and sales support teams.Example 2 - Large District Hospital
Flow Rate and Dryer SizingMedical Air DF = 4920 l/min (FAD) (4 Bar)Surgical Air DF =2888 l/min (FAD) (11 Bar)Combined/total DF = 7808 l/min (FAD) (11 Bar high pressure system)
A dryer greater than 7808 l/min should be selected (outlet flow is the inlet flow minus purge losses)= dMED145 inlet flow 11745 l/min, outlet flow 10124 l/min Flow Rate and Compressor SizingFrom Table 1 surgical air DF is between 500-3500 l/min, so the multiplying factor ‘A’ = 0.66
Plant flow rate = Med. DF + (Surg. DF x Value ‘A’) = 4920 + (2888 x 0.66) = 4920 + 1907 = 6827 l/min
We also need to add the purge losses to the compressor output. For additional purge consumption use:- dMED inlet - dMED outlet = purge losses lpm = 11745 - 10124 = 1621 l/min
Compressors should be selected with a flow rate greater than 6827 l/min + 1621 l/min = 8448 l/min
Receiver SizingFrom Table 2 surgical air DF is between 2001-3500 l/min, so the multiplying factor ‘B’ = 2 x 1/2
Capacity = (Med. DF x 0.5) + (Surg. DF x B) = (4920 x 0.5) + (2888 x 2 x 1/2) = 2460 + 2888 = 5348 litres
A combination of receivers with a minimum number of 2 should be selected
Selected receiver capacity = 6000 litres (3 x 2000 litre)
Plant System SelectionSelected plant part number = Oil-free tooth cAIR-8000-PZV7
If no standard model is available for selection from the standard range a bespoke configuration of dryer, compressors and receivers are available and can be quoted by our sales and sales support teams.
Combined Air Plant Sizing Guide - HTM02-01 - Examples
2212020091.0504/08/17Page 6 of 20
Atlas Copco Ltd. trading as Atlas Copco MedicalUnit 18 Nuffield Way, Abingdon, Oxfordshire, UK OX14 1RLwww.beaconmedaes.com
Typical Layout
Compressors
Dryer
Receivers
Note:- Inter connecting pipework (brown illustration) between components to be made on site and provided by the installer. Controller CAN cables are provided as a 10m assembly with each compressor which can be shortened on site if required.
Compressors
Dryer
Receivers
2212020091.0504/08/17Page 7 of 20
Atlas Copco Ltd. trading as Atlas Copco MedicalUnit 18 Nuffield Way, Abingdon, Oxfordshire, UK OX14 1RLwww.beaconmedaes.com
ZT-MED (Tooth) Oil-free Compressor Selection Table - Fixed Speed
Model Name ZT15 MED ZT18 MED ZT22 MED ZT30 MED ZT37 MED ZT45 MED
Output flow (litres/minute) * 8.6 bar variant 2052 2724 3222 4578 5562 6516
Output flow (litres/minute) * 10 bar variant 1842 2310 2736 n/a n/a n/a
Footprint L x W x H (mm) 1760 x 1026 x 1621
1760 x 1026 x 1621
1760 x 1026 x 1621
2005 x 1026 x 1880
2440 x 1026 x 1880
2440 x 1026 x 1880
Compressor weight (kg) 1060 1080 1086 1432 1432 1432
Service connection (mm) 42 42 42 42 42 42
Noise level/pump (dB[A]) 67 70 72 66 68 70
Maximum ambient temperature (0C) 46 46 46 46 46 46
Supply voltage (v) ** 380 380 380 380 380 380
Supply frequency (Hz) 60 60 60 60 60 60
Nominal motor rating (kW) 15 18 22 30 37 45
Full load current per compressor (A) 32.5 46 54.7 70.7 70.7 109.5
ISO Part Number - 8.6 bar 8102339755 8102339777 8102339799 8102339823 8102339830 8102339840
HTM Part Number - 8.6 bar 8102339756 8102339778 8102339800 on request on request on request
ISO Part Number - 10 bar 8102339745 8102339767 8102339789 n/a n/a n/a
HTM Part Number - 10 bar 8102339746 8102339768 8102339790 n/a n/a n/a
* Output flow stated at reference conditions** 230V 60 Hz 3 phase available on request
2212020091.0504/08/17Page 8 of 20
Atlas Copco Ltd. trading as Atlas Copco MedicalUnit 18 Nuffield Way, Abingdon, Oxfordshire, UK OX14 1RLwww.beaconmedaes.com
ZT-MED (Tooth) Oil-free Compressor Selection Table - Variable Speed Drive
Model Name ZT22VSD MED ZT37VSD MED ZT55VSD MED
Output flow (litres/minute) * 8.6 bar variant 1206 - 3216 2472 - 5706 2472 - 8328
Output flow (litres/minute) * 10 bar variant 1182 - 2844 n/a n/a
Footprint L x W x H (mm) 2195 x 1026 x 1621
2440 x 1026 x 1880
2440 x 1026 x 1880
Compressor weight (kg) 1120 1432 1432
Service connection (mm) 42 42 42
Noise level/pump (dB[A]) 72 71 71
Maximum ambient temperature (0C) 46 46 46
Supply voltage (v) 380 380 380
Supply frequency (Hz) 60 60 60
Nominal motor rating (kW) 22 37 55
Full load current per compressor (A) 55.5 92.1 138.8
Starting current (A) nominal nominal nominal
ISO Part Number - 8.6 bar n/a 8102339835 8102339845
HTM Part Number - 8.6 bar n/a on request on request
ISO Part Number - 10 bar 8102339811 n/a n/a
HTM Part Number - 10 bar 8102339812 n/a n/a
* Output flow stated at reference conditions** Variable speed drive compressor operate from 4-13 bar at 0-100% speed - start currents nominal for VSD
2212020091.0504/08/17Page 9 of 20
Atlas Copco Ltd. trading as Atlas Copco MedicalUnit 18 Nuffield Way, Abingdon, Oxfordshire, UK OX14 1RLwww.beaconmedaes.com
SF-MED (Scroll) Oil-free Compressor Selection Table - Fixed Speed
Model Name SF2 MED SF4 MED SF6 MED SF8+ MED SF11+ MED
Output flow (litres/minute) * 10 bar variant 204 354 420 804 1218
Footprint L x W x H (mm) 760 x 690 x 835
760 x 690 x 835
760 x 690 x 835
1670 x 750 x 1230
1670 x 750 x 1230
Compressor weight (kg) 125 133 157 450 450
Service connection (mm) 15 15 15 28 28
Noise level/pump (dB[A]) 56 58 59 63 63
Maximum ambient temperature (0C) 46 46 46 46 46
Supply voltage (v) 380 380 380 380 380
Supply frequency (Hz) 60 60 60 60 60
Nominal motor rating (kW) 3.1 4.1 5.8 8 11
Full load current per compressor (A) 5.9 7.8 11 TBC TBC
ISO Part Number - 10 bar 8102 3398 89 8102 3398 91 8102 3400 31 8102 3398 97 8102 3398 99
HTM Part Number - 10 bar 8102 3398 90 8102 3398 92 8102 3400 32 8102 3398 98 8102 3399 00
* Output flow stated at reference conditions
2212020091.0504/08/17Page 10 of 20
Atlas Copco Ltd. trading as Atlas Copco MedicalUnit 18 Nuffield Way, Abingdon, Oxfordshire, UK OX14 1RLwww.beaconmedaes.com
SF-MED (Scroll) Oil-free Compressor Selection Table Continued....- Fixed Speed
Model Name SF15+ MED SF17+ MED SF22+ MED
Output flow (litres/minute) * 10 bar variant 1608 1836 2436
Footprint L x W x H (mm) 1628 x 750 x 1844
1628 x 750 x 1844
1628 x 750 x 1844
Compressor weight (kg) 180 180 180
Service connection (mm) 28 28 28
Noise level/pump (dB[A]) 63 64 65
Maximum ambient temperature (0C) 46 46 46
Supply voltage (v) 380 380 380
Supply frequency (Hz) 60 60 60
Nominal motor rating (kW) 15 17 22
Full load current per compressor (A) TBC TBC TBC
ISO Part Number - 10 bar 8102 3399 07 8102 3399 09 8102 3399 11
HTM Part Number - 10 bar 8102 3399 08 8102 3399 10 8102 3399 12
* Output flow stated at reference conditions
2212020091.0504/08/17Page 11 of 20
Atlas Copco Ltd. trading as Atlas Copco MedicalUnit 18 Nuffield Way, Abingdon, Oxfordshire, UK OX14 1RLwww.beaconmedaes.com
LF-MED (Piston) Oil-free Compressor Selection Table Continued....- Fixed Speed
Model Name LF5 MED LF7 MED LF10 MED
Output flow (litres/minute) * 10 bar variant 546 720 1092
Footprint L x W x H (mm) 1000 x 550 x 720 1000 x 550 x 720 1000 x 550 x 720
Compressor weight (kg) TBC TBC TBC
Service connection (mm) 22 22 22
Noise level/pump (dB[A]) 68 72 74
Maximum ambient temperature (0C) 46 46 46
Supply voltage (v) 380 380 380
Supply frequency (Hz) 60 60 60
Nominal motor rating (kW) 5.11 6.38 8.73
Full load current per compressor (A) 9.7 12.1 16.6
ISO Part Number - 10 bar n/a n/a n/a
HTM Part Number - 10 bar TBC 8102 3399 39 8102 3399 32
* Output flow stated at reference conditions** TM = tank mounted compressor
2212020091.0504/08/17Page 12 of 20
Atlas Copco Ltd. trading as Atlas Copco MedicalUnit 18 Nuffield Way, Abingdon, Oxfordshire, UK OX14 1RLwww.beaconmedaes.com
Dryer Selection Table
Model Name dMED7 dMED15 dMED25 dMED35 dMED45 dMED65 dMED80 dMED100 dMED145
Inlet flow at 7.5 bar (litres/minute) 420 780 1500 2100 3000 4200 4800 6000 8700
Output flow (litres/minute) at 4 bar line pressure * 342 632 1230 1722 2430 3444 3936 4860 7047
Inlet flow at 10 bar (litres/minute) 504 936 1800 2520 3600 5040 5760 7200 10440
Output flow (litres/minute) at 7 bar line pressure * 426 788 1530 2142 3030 4284 4896 6060 8787
Inlet flow at 13 bar (litres/minute) 567 1053 2025 2835 4050 5670 6480 8100 11745
Output flow (litres/minute) at 10 bar line pressure * 489 905 1755 2457 3480 4916 5616 6960 10092
Footprint L x W x H (mm)2120 x 1130 x 1590
2120 x 1130 x 1590
2120 x 1130 x 1590
2120 x 1130 x 1590
2120 x 1130 x 1590
2120 x 1130 x 1760
2120 x 1470 x 1590
2120 x 1470 x 1610
2120 x 1470 x 1610
Dryer weight (kg) 434 436 448 450 502 607 724 793 919
nlet and outlet connections (mm) 15 15 15 28 28 28 28 28 28
Supply voltage (v) 230 230 230 230 230 230 230 230 230
Supply frequency (Hz) 60 60 60 60 60 60 60 60 60
Central control supply - single phase (mm2/Amps)
1.5(2)
1.5(2)
1.5(2)
1.5(2)
1.5(2)
1.5(2)
1.5(2)
1.5(2)
1.5(2)
Part Number - dryer at 4 bar outlet
8102
370
1 84
8102
370
1 60
8102
370
1 63
8102
370
1 66
8102
370
1 69
8102
370
1 72
8102
370
1 75
8102
370
1 78
8102
370
1 81
Part Number - dryer at 7 bar outlet
8102
370
1 85
8102
370
1 61
8102
370
1 64
8102
370
1 67
8102
370
1 70
8102
370
1 73
8102
370
1 76
8102
370
1 79
8102
370
1 82
Part Number - dryer at 10 bar outlet
8102
370
1 86
8102
370
1 62
8102
370
1 65
8102
370
1 68
8102
370
1 71
8102
370
1 74
8102
370
1 77
8102
370
1 80
8102
370
1 83
Drawing Number
2212
020
5 28
2212
020
5 28
2212
020
5 28
2212
020
5 28
2212
020
5 28
2212
020
5 28
2212
020
5 28
2212
020
5 28
2212
020
5 28
* Output flow stated includes calculated purge lost during the regenration process of between 15-19% depending on model and inlet pressure.
Notes on plant
• Design flow in terms of free air delivered after losses at working pressure with the reserve compressor(s) on standby. Tolerance ±5%.• Component dimensions supplied do not include maintenance access space, and are provided to allow customer to arrange plant components within plant room. Complete installation drawings are available on request. Quote the drawing number required.• Duplex systems must be installed with a manifold as the third source of supply for HTM02-01 compliance.• Mean sound level in accordance with ISO 2151.• Electrical details are provided for guidance only. Site conditions may impose a larger cable size. For exact cable sizing, and fuse / MCB ratings, consult a qualified electrical engineer.
2212020091.0504/08/17Page 13 of 20
Atlas Copco Ltd. trading as Atlas Copco MedicalUnit 18 Nuffield Way, Abingdon, Oxfordshire, UK OX14 1RLwww.beaconmedaes.com
Standard Models
HTM02-01 Medical Air 4 bar - ZT (Tooth) compressors- Fixed Speed
Model Number
mA
IR-1
674-
TZF4
mA
IR-2
000-
TZF4
mA
IR-2
154-
TZF4
mA
IR-3
936-
QZF
4
mA
IR-4
308-
QZF
4
mA
IR-4
860-
QZF
4
mA
IR-5
469-
QZF
4
mA
IR-6
000-
PZF4
Design flow (litres/minute) 1674 2000 2154 3936 4308 4860 5469 6000
Number of compressors 3 3 3 4 4 4 4 5
Type of compressor ZT-MED 15
ZT-MED 18
ZT-MED 18
ZT-MED 18
ZT-MED 18
ZT-MED 22
ZT-MED 22
ZT-MED 18
Type of dryer dMED35
dMED45
dMED45
dMED80
dMED100
dMED100
dMED145
dMED145
Number of receivers 2 2 2 2 2 2 2 2
Receiver volume (l) (each) 500 500 1000 1000 1500 1500 1500 1500
Part
Num
ber
8102
369
1 53
8102
369
1 54
8102
369
1 55
8102
369
1 58
8102
369
1 59
8102
369
1 60
8102
369
1 61
8102
369
1 62
HTM02-01 Medical Air 4 bar - ZT (Tooth) compressors- Variable Speed
Model Number
mA
IR-2
000-
TZV4
mA
IR-2
450-
TZV4
mA
IR-3
935-
QZV
4
mA
IR-4
860-
QZV
4
mA
IR-5
650-
QZV
4
mA
IR-6
000-
PZV4
Design flow (litres/minute) 2000 2450 3935 4860 5650 6000
Number of compressors 3 3 4 4 4 5
Type of compressor ZT-MED VSD 22
ZT-MED VSD 22
ZT-MED VSD 22
ZT-MED VSD 22
ZT-MED VSD 22
ZT-MED VSD 22
Type of dryer dMED80
dMED80
dMED80
dMED100
dMED145
dMED145
Number of receivers 2 2 2 2 2 2
Receiver volume (l) (each) 500 1000 1000 1500 1500 1500
Part
Num
ber
8102
369
5 33
8102
340
3 83
8102
340
3 84
8102
340
3 85
8102
340
3 86
8102
340
3 87
2212020091.0504/08/17Page 14 of 20
Atlas Copco Ltd. trading as Atlas Copco MedicalUnit 18 Nuffield Way, Abingdon, Oxfordshire, UK OX14 1RLwww.beaconmedaes.com
HTM02-01 Combined Medical & Surgical Air 7 bar - ZT (Tooth) compressors- Fixed Speed
Model Number
cAIR
-153
0-TZ
F7
cAIR
-176
5-TZ
F7
cAIR
-214
0-TZ
F7
cAIR
-261
0-TZ
F7
cAIR
-353
0-Q
ZF7
cAIR
-452
5-Q
ZF7
cAIR
-489
5-Q
ZF7
cAIR
-522
0-Q
ZF7
cAIR
-522
0-PZ
F7-3
Design flow (litres/minute) 1530 1765 2142 2610 3530 4525 4895 5220 5220
Required compressor output * 1270 1470 1778 2148 2940 3792 4064 4427 4764
Required receiver volume * 1401 1622 1962 2623 3245 3427 3672 4000 4305
Number of compressors 3 3 3 3 4 4 4 4 4
Type of compressor ZT-MED 15
ZT-MED 15
ZT-MED 18
ZT-MED 22
ZT-MED 15
ZT-MED 18
ZT-MED 22
ZT-MED 22
ZT-MED 22
Type of dryer dMED25
dMED35
dMED35
dMED45
dMED65
dMED80
dMED80
dMED100
dMED100
Number of receivers 2 2 2 2 2 2 2 2 2
Receiver volume (l) (each) 1000 1000 1000 1500 2000 2000 2000 2000 3000
Part
Num
ber
8102
342
6 95
8102
342
6 96
8102
342
6 97
8102
342
6 98
8102
368
8 20
8102
368
8 22
8102
368
8 23
8102
368
8 24
8102
368
8 25
Model Number
cAIR
-600
0-PZ
F7
cAIR
-606
0-PZ
F7-3
cAIR
-636
0-PZ
F7-3
cAIR
-636
0-PZ
F7
cAIR
-800
0-PZ
F7
cAIR
-874
0-PZ
F7-3
cAIR
-874
0-PZ
F7
Design flow (litres/minute) 6000 6060 6360 8000 8000 8740 8740
Required compressor output * 4980 5030 5277 5277 6000 6555 6555
Required receiver volume * 4500 4545 4768 4768 6000 6555 6555
Number of compressors 5 5 5 5 5 5 5
Type of compressor ZT-MED 18
ZT-MED 18
ZT-MED 18
ZT-MED 18
ZT-MED 22
ZT-MED 22
ZT-MED 22
Type of dryer dMED100
dMED100
dMED145
dMED145
dMED145
dMED145
dMED145
Number of receivers 3 2 2 3 3 3 4
Receiver volume (l) (each) 1500 3000 3000 2000 2000 3000 2000
Part
Num
ber
8102
368
8 27
8102
368
8 28
8102
368
8 29
8102
368
8 30
8102
368
8 31
8102
368
8 32
8102
368
8 33
* Flow output based on a 50/50 split of medical and surgical air design flow (D.F) For examples on how to calculate the required design flow, compressor flow and receiver volume refer to earlier page, in line with HTM02-01 requirements and tables.
2212020091.0504/08/17Page 15 of 20
Atlas Copco Ltd. trading as Atlas Copco MedicalUnit 18 Nuffield Way, Abingdon, Oxfordshire, UK OX14 1RLwww.beaconmedaes.com
HTM02-01 Combined Medical & Surgical Air 7 bar - ZT (Tooth) compressors- Variable Speed
Model Number
cAIR
-274
0-TZ
V
cAIR
-489
5-Q
ZV7
cAIR
-533
5-Q
ZV7
cAIR
-548
0-ZV
7-3
cAIR
-548
0-Q
ZV7
cAIR
-600
0-PZ
V7
cAIR
-800
0-PZ
V7
cAIR
-878
5-PZ
V7
cAIR
-878
5-ZV
7-3
Design flow (litres/minute) 2740 4896 5333 5480 5480 6000 8000 8787 8787
Required compressor output * 2272 4064 4427 4544 4544 4500 6000 6590 6590
Required receiver volume * 2507 3672 4000 4106 4106 4500 6000 6590 6590
Number of compressors 3 4 4 4 4 5 5 5 5
Type of compressor ZT-MED VSD 22
ZT-MED VSD 22
ZT-MED VSD 22
ZT-MED VSD 22
ZT-MED VSD 22
ZT-MED VSD 22
ZT-MED VSD 22
ZT-MED VSD 22
ZT-MED VSD 22
Type of dryer dMED45
dMED80
dMED100
dMED100
dMED100
dMED145
dMED145
dMED145
dMED145
Number of receivers 2 2 2 2 3 3 3 4 3
Receiver volume (l) (each) 1500 2000 2000 3000 1500 1500 2000 2000 3000
Part
Num
ber
8102
368
8 34
8102
368
8 35
8102
368
8 36
8102
368
8 37
8102
368
8 38
8102
368
8 39
8102
368
8 40
8102
368
8 41
8102
368
8 42
* Flow output based on a 50/50 split of medical and surgical air design flow (D.F) For examples on how to calculate the required design flow, compressor flow and receiver volume refer to earlier page, in line with HTM02-01 requirements and tables.
HTM2022 Medical Air 4 bar - ZT (Tooth) compressors- Fixed Speed
Model Number
mA
IR-1
675-
DZF
4
mA
IR-2
000-
DZF
4
mA
IR-2
155-
DZF
4
mA
IR-2
465-
DZF
4
mA
IR-3
935-
TZF4
mA
IR-4
310-
TZF4
mA
IR-4
860-
TZF4
mA
IR-5
470-
TZF4
mA
IR-6
000-
QZF
4
Design flow (litres/minute) 1675 2000 2155 2465 3936 4310 4860 5470 6000
Required receiver volume 850 1000 1086 1278 1968 2172 2430 2825 3000
Number of compres-sors 2 2 2 2 3 3 3 3 4
Type of compressor ZT-MED 15
ZT-MED 18
ZT-MED 18
ZT-MED 22
ZT-MED 18
ZT-MED 18
ZT-MED 22
ZT-MED 22
ZT-MED 18
Type of dryer dMED35
dMED45
dMED45
dMED65
dMED80
dMED100
dMED100
dMED145
dMED145
Number of receivers 2 2 2 2 2 2 2 2 2
Receiver volume (l) (each) 500 500 1000 1000 1000 1500 1500 1500 1500
Part
Num
ber
8102
368
9 90
8102
368
9 91
8102
368
9 92
8102
369
6 19
8102
368
9 95
8102
368
9 96
8102
368
9 97
8102
368
9 98
8102
368
9 99
2212020091.0504/08/17Page 16 of 20
Atlas Copco Ltd. trading as Atlas Copco MedicalUnit 18 Nuffield Way, Abingdon, Oxfordshire, UK OX14 1RLwww.beaconmedaes.com
HTM2022 Medical Air 4 bar - ZT (Tooth) compressors- Variable Speed
Model Number
mA
IR-2
000-
DZV
4
mA
IR -3
935-
TZV4
mA
IR -4
860-
TZV4
mA
IR -5
455-
TZV4
mA
IR-6
000-
QZV
4
Design flow (litres/minute) 2000 3936 4860 5455 6000
Required receiver volume 1000 1968 2430 2705 3000
Number of compressors 2 3 3 3 4
Type of compressor ZT-MED VSD 22
ZT-MED VSD 22
ZT-MED VSD 22
ZT-MED VSD 22
ZT-MED VSD 22
Type of dryer dMED45
dMED80
dMED100
dMED145
dMED145
Number of receivers 2 2 2 2 2
Receiver volume (l) (each) 500 1000 1500 1500 1500
Part
Num
ber
8102
342
2 42
8102
342
2 45
8102
342
2 46
8102
342
2 47
8102
342
2 48
HTM2022 Combined Medical & Surgical Air 7 bar - ZT (Tooth) compressors- Fixed Speed
Model Number
cAIR
-153
0-D
ZF7
cAIR
-193
0-D
ZF7
cAIR
-214
0-D
ZF7
cAIR
-216
5-D
ZF7
cAIR
-386
5-TZ
F7
cAIR
-461
0-TZ
F7-3
cAIR
-579
0-Q
ZF-3
cAIR
-606
0-Q
ZF7
cAIR
-655
5-Q
ZF7
cAIR
-758
5-PZ
F7
Design flow (litres/minute) 1530 1930 2140 2165 3865 4610 5790 6060 6555 7585
Number of compressors 2 2 2 2 3 3 4 4 4 5
Type of compressor
ZT-MED 15
ZT-MED 18
ZT-MED 22
ZT-MED 22
ZT-MED 18
ZT-MED 22
ZT-MED 18
ZT-MED 22
ZT-MED 22
ZT-MED 18
Type of dryer dMED25
dMED35
dMED35
dMED45
dMED65
dMED80
dMED100
dMED100
dMED145
dMED145
Number of receivers 1 1 1 1 1 1 1 2 2 2
Receiver volume (l) (each) 1000 1000 1500 1500 2000 3000 3000 2000 2000 2000
Part
Num
ber
8102
369
0 88
8102
369
0 89
8102
369
0 90
8102
369
0 91
8102
369
0 93
8102
369
0 95
8102
369
0 96
8102
369
0 97
8102
369
0 98
8102
369
0 99
2212020091.0504/08/17Page 17 of 20
Atlas Copco Ltd. trading as Atlas Copco MedicalUnit 18 Nuffield Way, Abingdon, Oxfordshire, UK OX14 1RLwww.beaconmedaes.com
Model Number
cAIR
-800
0-PZ
F7
cAIR
-878
5-PZ
F7-3
cAIR
-878
5-PZ
F7
Design flow (litres/minute) 8000 8785 8785
Number of compressors 5 5 5
Type of compressor
ZT-MED 22
ZT-MED 22
ZT-MED 22
Type of dryer dMED145
dMED145
dMED140
Number of receivers 2 2 3
Receiver volume (l) (each) 2000 3000 1500
Part
Num
ber
8102
369
1 00
8102
369
1 01
8102
369
1 02
HTM2022 Combined Medical & Surgical Air 7 bar - ZT (Tooth) compressors- Variable Speed
Model Number
cAIR
-200
0-D
ZV7
cAIR
-214
0-D
ZV7
cAIR
-227
5-D
ZV7
cAIR
-482
5-TZ
V7
cAIR
-600
0-Q
ZV7
cAIR
-606
0-Q
ZV7
cAIR
-688
0-Q
ZV7
cAIR
-800
0-PZ
V7
cAIR
-878
5PZV
7-3
cAIR
-878
5-PZ
V7
Design flow (litres/minute) 2000 2142 2274 4824 6000 6060 6879 8000 8087 8787
Number of compressors 2 2 2 3 4 4 4 5 5 5
Type of compressor
ZT-MED VSD 22
ZT-MED VSD 22
ZT-MED VSD 22
ZT-MED
VSD 22
ZT-MED VSD 22
ZT-MED VSD 22
ZT-MED VSD 22
ZT-MED VSD 22
ZT-MED VSD 22
ZT-MED VSD 22
Type of dryer dMED35
dMED35
dMED45
dMED80
dMED100
dMED100
dMED145
dMED145
dMED145
dMED145
Number of receivers 1 1 1 1 1 2 2 2 2 3
Receiver volume (l) (each) 1000 1500 1500 3000 3000 2000 2000 2000 3000 1500
Part
Num
ber
8102
369
1 04
8102
369
1 05
8102
369
1 06
8102
369
1 10
8102
369
1 11
8102
369
1 12
8102
369
1 13
8102
369
1 14
8102
369
1 15
8102
369
1 16
2212020091.0504/08/17Page 18 of 20
Atlas Copco Ltd. trading as Atlas Copco MedicalUnit 18 Nuffield Way, Abingdon, Oxfordshire, UK OX14 1RLwww.beaconmedaes.com
HTM02-01 Combined Medical & Surgical Air 7 bar - SF (Scroll) compressors- Fixed Speed
Model Number
cAIR
-410
-TSF
7
cAIR
-790
-TSF
7
cAIR
-945
-TSF
7
cAIR
-131
0-TS
F7
cAIR
-137
5-TS
F7
cAIR
-153
0-TS
F7
cAIR
-169
0-TS
F7
cAIR
-171
5-Q
SF7
cAIR
-214
0-Q
SF7
cAIR
-258
0-Q
SF7
cAIR
-271
0-Q
SF7
Design flow (litres/minute) 410 790 945 1310 1310 1530 1690 1715 2140 2580 2710
Required compressor output * 274 524 630 1086 1086 1270 1404 1422 1788 2142 2250
Required receiver volume * 515 985 1184 1199 1258 1401 1549 1569 1962 2364 2483
Number of compressors 3 3 3 3 3 3 3 4 4 4 4
Type of compressor
SF-MED 4
SF-MED 8
SF-MED 11
SF-MED 15
SF-MED 17
SF-MED 22
SF-MED 22
SF-MED 11
SF-MED 15
SF-MED 15
SF-MED 17
Type of dryer dMED7
dMED15
dMED25
dMED25
dMED25
dMED25
dMED35
dMED35
dMED35
dMED45
dMED45
Number of receivers 1 2 2 2 2 2 2 2 2 2 2
Receiver volume (l) (each) 1000 500 1000 1000 1000 1000 1000 1000 1000 1500 1500
Part
Num
ber
8102
342
6 74
8102
342
6 75
8102
342
6 76
8102
342
6 77
8102
342
6 78
8102
342
6 79
8102
342
6 80
8102
342
6 81
8102
342
6 82
8102
342
6 83
8102
369
1 29
Model Number
cAIR
-338
5-Q
SF7
cAIR
-489
5-PS
F7
cAIR
-542
0-H
SF7-
3
cAIR
-542
0-H
SF7
cAIR
-659
5-H
SF7-
3
cAIR
-659
5-H
SF7
cAIR
-730
0-H
SF7-
3
cAIR
-730
0-H
SF7
Design flow (litres/minute) 3385 4895 5420 5420 6595 6595 7300 7300
Required com-pressor output * 2808 4064 4500 4500 5475 5475 5475 5475
Required receiver volume * 3099 3672 4066 4066 4947 4947 5475 5475
Number of compressors 4 5 6 6 6 6 6 6
Type of compressor
SF-MED 22
SF-MED 22
SF-MED 17
SF-MED 17
SF-MED 22
SF-MED 22
SF-MED 22
SF-MED 22
Type of dryer dMED65
dMED80
dMED100
dMED100
dMED145
dMED145
dMED145
dMED145
Number of receivers 2 2 2 3 2 3 3 4
Receiver volume (l) (each) 2000 2000 3000 2000 3000 2000 3000 2000
Part
Num
ber
8102
342
6 85
8102
342
6 88
8102
342
6 89
8102
342
6 90
8102
342
6 91
8102
342
6 92
8102
342
6 93
8102
342
6 94
2212020091.0504/08/17Page 19 of 20
Atlas Copco Ltd. trading as Atlas Copco MedicalUnit 18 Nuffield Way, Abingdon, Oxfordshire, UK OX14 1RLwww.beaconmedaes.com
HTM02-01 Combined Medical & Surgical Air 7 bar - SF (Scroll) compressors- Fixed Speed
Model Number
cAIR
-410
-TSF
7
cAIR
-790
-TSF
7
cAIR
-945
-TSF
7
cAIR
-131
0-TS
F7
cAIR
-137
5-TS
F7
cAIR
-153
0-TS
F7
cAIR
-169
0-TS
F7
cAIR
-171
5-Q
SF7
cAIR
-214
0-Q
SF7
cAIR
-258
0-Q
SF7
cAIR
-271
0-Q
SF7
Design flow (litres/minute) 410 790 945 1310 1310 1530 1690 1715 2140 2580 2710
Required compressor output * 274 524 630 1086 1086 1270 1404 1422 1788 2142 2250
Required receiver volume * 515 985 1184 1199 1258 1401 1549 1569 1962 2364 2483
Number of compressors 3 3 3 3 3 3 3 4 4 4 4
Type of compressor
SF-MED 4
SF-MED 8
SF-MED 11
SF-MED 15
SF-MED 17
SF-MED 22
SF-MED 22
SF-MED 11
SF-MED 15
SF-MED 15
SF-MED 17
Type of dryer dMED7
dMED15
dMED25
dMED25
dMED25
dMED25
dMED35
dMED35
dMED35
dMED45
dMED45
Number of receivers 1 2 2 2 2 2 2 2 2 2 2
Receiver volume (l) (each) 1000 500 1000 1000 1000 1000 1000 1000 1000 1500 1500
Part
Num
ber
8102
342
6 74
8102
342
6 75
8102
342
6 76
8102
342
6 77
8102
342
6 78
8102
342
6 79
8102
342
6 80
8102
342
6 81
8102
342
6 82
8102
342
6 83
8102
369
1 29
Model Number
cAIR
-338
5-Q
SF7
cAIR
-489
5-PS
F7
cAIR
-542
0-H
SF7-
3
cAIR
-542
0-H
SF7
cAIR
-659
5-H
SF7-
3
cAIR
-659
5-H
SF7
cAIR
-730
0-H
SF7-
3
cAIR
-730
0-H
SF7
Design flow (litres/minute) 3385 4895 5420 5420 6595 6595 7300 7300
Required com-pressor output * 2808 4064 4500 4500 5475 5475 5475 5475
Required receiver volume * 3099 3672 4066 4066 4947 4947 5475 5475
Number of compressors 4 5 6 6 6 6 6 6
Type of compressor
SF-MED 22
SF-MED 22
SF-MED 17
SF-MED 17
SF-MED 22
SF-MED 22
SF-MED 22
SF-MED 22
Type of dryer dMED65
dMED80
dMED100
dMED100
dMED145
dMED145
dMED145
dMED145
Number of receivers 2 2 2 3 2 3 3 4
Receiver volume (l) (each) 2000 2000 3000 2000 3000 2000 3000 2000
Part
Num
ber
8102
342
6 85
8102
342
6 88
8102
342
6 89
8102
342
6 90
8102
342
6 91
8102
342
6 92
8102
342
6 93
8102
342
6 94
HTM2022 Combined Medical & Surgical Air 7 bar - SF (Scroll) compressors- Fixed Speed
Model Number
cAIR
-400
-DSF
7
cAIR
-530
-DSF
7
cAIR
-750
-DSF
7
cAIR
-790
-DSF
7
cAIR
-100
0-D
SF7
cAIR
-108
5-D
SF7
cAIR
-114
0-D
SF7
cAIR
-151
0-D
SF7
cAIR
-153
0-TS
F7
cAIR
-200
0-TS
F7
cAIR
-214
0-TS
F7
Design flow (litres/minute) 400 530 750 790 1000 1085 1140 1510 1530 2000 2140
Number of compressors 2 2 2 2 2 2 2 2 3 3 3
Type of compressor
SF-MED 6
SF-MED 8
SF-MED 11
SF-MED 15
SF-MED 15
SF-MED 15
SF-MED 17
SF-MED 22
SF-MED 11
SF-MED 15
SF-MED 15
Type of dryer dMED7
dMED7
dMED25
dMED25
dMED25
dMED25
dMED25
dMED25
dMED25
dMED35
dMED35
Number of receivers 1 1 1 1 1 1 1 1 1 1 1
Receiver volume (l) (each) 250 500 500 500 500 1000 1000 1000 1000 1000 1500
Part
Num
ber
8102
369
0 67
8102
369
0 68
8102
369
0 69
8102
369
0 70
8102
369
0 71
8102
369
0 72
8102
369
0 73
8102
369
0 74
8102
369
0 75
8102
369
0 76
8102
369
0 77
Model Number
cAIR
-225
0-TS
F7
cAIR
-331
0-Q
SF7
cAIR
-347
5-Q
SF7
cAIR
-448
0-Q
SF7-
3
cAIR
-477
5-PS
F7-3
cAIR
-599
0-PS
F7
Design flow (litres/minute) 2250 3310 3475 4480 4775 5990
Number of compressors 3 4 4 4 5 5
Type of compressor
SF-MED 17
SF-MED 15
SF-MED 17
SF-MED 22
SF-MED 17
SF-MED 22
Type of dryer dMED45
dMED65
dMED65
dMED80
dMED100
dMED100
Number of receivers 1 1 1 1 1 2
Receiver volume (l) (each) 1500 2000 2000 3000 3000 1500
Part
Num
ber
8102
369
0 78
8102
369
0 81
8102
369
0 82
8102
369
0 85
8102
369
0 86
8102
369
0 87
In an effort to continuously improve our products, the right is reserved to change the specification of the items described herein at any time. Please contact us for further information and up to date specifications.
2212020091.0504/08/17Page 20 of 20
Atlas Copco Ltd. trading as Atlas Copco MedicalUnit 18 Nuffield Way, Abingdon, Oxfordshire, UK OX14 1RLwww.beaconmedaes.com 0088
HTM02-01 Combined Medical & Surgical Air 7 bar - LF (Piston) compressors- Fixed Speed
Model Number
cAIR
425
-TLF
7
cAIR
600
-TLF
7
cAIR
-790
-TLF
7
cAIR
-123
5-TL
F7
cAIR
-141
0-Q
LF
cAIR
-214
0-Q
LF7
cAIR
-214
0-PL
F7
cAIR
-327
5-H
LF7
Design flow (litres/minute) 425 600 790 1235 1410 2140 2140 3275
Required compressor output * 282 398 524 822 1170 1806 1806 3612
Required receiver volume * 530 748 985 1545 1291 1962 1962 3000
Number of compressors 3 3 3 3 4 4 5 6
Type of compressor LF-MED 5
LF-MED 5
LF-MED 7
LF-MED 10
LF-MED 7
LF-MED 10
LF-MED 7
LF-MED 10
Type of dryer dMED7
dMED15
dMED15
dMED25
dMED25
dMED35
dMED35
dMED65
Number of receivers 1 2 2 2 2 2 2 2
Receiver volume (l) (each) 1000 500 500 1000 1000 1000 1000 1500
Part
Num
ber
8102
342
6 63
8102
342
6 64
8102
342
6 65
8102
342
6 66
8102
342
6 67
8102
342
6 68
8102
342
6 69
8102
342
6 72
* Flow output based on a 50/50 split of medical and surgical air design flow (D.F) For examples on how to calculate the required design flow, compressor flow and receiver volume refer to earlier page, in line with HTM02-01 requirements and tables.
HTM2022 Combined Medical & Surgical Air 7 bar - LF (Piston) compressors- Fixed Speed
Model Number
cAIR
-410
-DLF
7
cAIR
-500
-DLF
7
cAIR
-780
-DLF
7
cAIR
-100
0-TL
F7
cAIR
-105
0-TL
F7
cAIR
-153
0-TL
F7
cAIR
-160
0-Q
LF7
cAIR
-200
0-Q
LF7
cAIR
-214
0-Q
LF7
cAIR
-222
0-Q
LF7
cAIR
-389
5-H
LF7
Design flow (litres/minute) 410 500 780 1000 1050 1530 1600 2000 2140 2220 3895
Number of compressors 2 2 2 3 3 3 4 4 4 4 6
Type of compressorLF-
MED 5
LF-MED
7
LF-MED
10
LF-MED
5
LF-MED
7
LF-MED
10
LF-MED
7
LF-MED
10
LF-MED
10
LF-MED
10
LF-MED
10
Type of dryer dMED7
dMED15
dMED15
dMED25
dMED25
dMED25
dMED35
dMED35
dMED35
dMED45
dMED65
Number of receivers 1 1 1 1 1 1 1 1 1 1 1
Receiver volume (l) (each) 250 250 500 500 1000 1000 1000 1000 1500 1500 2000
Part
Num
ber
8102
369
1 17
8102
369
1 18
8102
369
1 19
8102
369
1 20
8102
369
1 21
8102
369
1 22
8102
369
1 23
8102
369
1 24
8102
369
1 25
8102
369
1 26
8102
369
1 28