    PT TRANSPORTASI GAS INDONESIA

    BELILAS GBS Maintenance:

    1. GTGC A, Node 8 Error, PLC product Obsolete

    2. GTGC A, Engine Flame Out

    3. GTGC A, GP Over speed

    4. Gas & Detection System, Power Supply BA04

    Product Obsolete

  • 7/31/2019 Maintenance Problem

    2/19

    GTGC A,Node 8 Error, PLC product Obsolete

    Date/Time GTGC A O & M

    01-05-2009 @17.14 FL367 Node 8 Connector Error (Alarmcant Reset, Unit UnavailableUnplanned)

    Check wiring connection of Module FlexI/O ZF 2080

    Check PLC by Software found errorsignal at ZF2081 N63 : 17 Active Node 8 Slot 1 Error active.

    Check Connection of ZF2081, OKReset Power to ZF2081 and measurepower to ZF2081, OK

    Suspected Module Flex I/O ZF2081Problem (Alarm cant Reset)

    Shutdown Historical :

  • 7/31/2019 Maintenance Problem

    3/19

    GTGC A,Node 8 Error, PLC product Obsolete

    Date/Time GTGC A O & M

    02-05-2009 Control Net not working Normally

    Replaced Net module with New Module

    Check and Monitoring PLC programperformance.

    Found Node 8 Slot 2 Error at ModuleZF2082

    Function Test of enclosure fan 1 & 2with bypass module, found Enclosure

    Fan Normal Run

    Perform Program simulation

    Function Test Relay related to ModuleI/O ZF2080 to ZF2083

    Shutdown Historical :

  • 7/31/2019 Maintenance Problem

    4/19

    GTGC A,Node 8 Error, PLC product Obsolete

    Date/Time GTGC A O & M

    03-05-2009 Function test Equipment that isconnected to ZF2082 (Post Lube Fan 1and Fan 2)

    04-05-2009 Replace Discrete Module and ComboModule Flex I/O

    Consult to Transavia,PT :

    Found the problem is that eachreplacement of the Net adapter module

    must be perform network reconfigureusing software RS network for ControlNet.

    (RS software progress on order)

    Shutdown Historical :

  • 7/31/2019 Maintenance Problem

    5/19

    GTGC A,Node 8 Error, PLC product Obsolete

    Date/Time GTGC A O & M

    07-05-2009 Try to communicate between PLC & RSnetwork, failed.

    08-05-2009 Reconfiguration

    09-05-2009 Reconfiguration

    10-05-2009 Reconfiguration

    11-05-2009 Reconfiguration

    12-05-2009 Found Module 1794-ACNR ser A F/W rev D

    (Module Discontinue) PLC ObsoleteReplaced Module 1794-ACNR ser A F/W rev Dwith Module 1794-ACNR ser A F/W rev E(Spare from Transavia,PT. Last stock noproduction yet)

    Shutdown Historical :

  • 7/31/2019 Maintenance Problem

    6/19

    GTGC A,Node 8 Error, PLC product Obsolete

    Date/Time GTGC A O & M

    12-05-2009 Found No communication to Node 8 AddressModule

    Recommendation from Transavia,PT:

    Need to Prepare upgrade the Control net adapterand PLC5/40C processor to Control net 1.5Protocol or other option is change to controllogix system.

    05-10-2009 Upgrading PLC:

    Replace 7ea Control Net Adapter 1.5 ser C 1794-ACNR 1.25 to ser C 1794-ACNR 1.5

    Replace 1 ea PLC5 Programmable Controllers1785-L40C 32 ser E to 1785-L40C 15 ser F

    Shutdown Historical :

  • 7/31/2019 Maintenance Problem

    7/19

    GTGC A,Node 8 Error, PLC product Obsolete

    Date/Time GTGC A O & M

    05-10-2009 Reconfigure Control net network and downloadto processor.

    Testing Control net network, found only Chanel A

    working properly but Chanel B as redundant isnot working properly.

    06-10-2009 Try to using only 2 Module(2 node) installed, butthe problem not solve.

    Found new PLC is not working properly

    especially on redundant control net network.Switch back 7ea Control Net Adapter 1.5 ser C1794-ACNR 1.5 to ser C 1794-ACNR 1.25

    Switch back 1 ea PLC5 Programmable Controllers1785-L40C 15 ser F to 1785-L40C 32 ser E

    Shutdown Historical :

  • 7/31/2019 Maintenance Problem

    8/19

    GTGC A,Node 8 Error, PLC product Obsolete

    Date/Time GTGC A O & M

    06-10-2009 Put back new PLC5 by Transavia,PT to claim toRockwell

    Shutdown Historical :

  • 7/31/2019 Maintenance Problem

    9/19

    GTGC A, Engine Flame Out

    Date/Time GTGC A O & M

    02-12-2009 @11.39 FN472 Engine Flame Out, Restart OK

    08-12-2009 @11.39 FN472 Engine Flame Out, Restart OK

    09-12-2009 @11.37 FN472 Engine Flame Out, Restart OK

    11-12-2009 @11.37 FN472 Engine Flame Out, Restart OK

    18-12-2009 Press Switch S349(PCD) calibration ,retighten nut & bolt, and cableconnection

    PMV calibration, cable connection check

    and retighten, recondition CM switch

    30-12-2009 @11.34 FN472 Engine Flame Out, Restart OK

    31-12-2009 @11.34 FN472 Engine Flame Out, Restart OK

    04-01-2010 TPD 344 Test, EGF 344 function Test

    Shutdown Historical :

  • 7/31/2019 Maintenance Problem

    10/19

    GTGC A, Engine Flame Out

    Date/Time GTGC A O & M

    25-01-2010 @11.32 FN472 Engine Flame Out, Restart OK

    26-01-2010 @11.34 FN472 Engine Flame Out, Restart OK

    27-01-2010 @11.34 FN472 Engine Flame Out, Restart OK

    28-01-2010 @11.34 FN472 Engine Flame Out, Restart OK

    30-01-2010 @11.32 FN472 Engine Flame Out, Restart OK

    01-02-2010 @11.32 FN472 Engine Flame Out, Restart OK

    02-02-2009 Monitor Voltage of DP Switch S349

    (PCD) line from TCS(Control Room)-JB(field) record voltage if shutdownhappened (No Engine Flame Out)

    03-02-2010 @11.32 FN 472 Engine Flame Out, and FL346EGF344 Position failed, Restart OK

    Shutdown Historical :

  • 7/31/2019 Maintenance Problem

    11/19

    GTGC A, Engine Flame Out

    Date/Time GTGC A O & M

    04-01-2010 @11.32 FN 472 Engine Flame Out, and FL346EGF344 Position failed, Restart OK

    05-02-2010 PM 8K, Function Test EGF344 & PMV

    Surge Valve20-02-2010 TCS Panel Often power loss suddenly

    Check physically TCS Batteries, Find1pc Batteries burn out. ReplacedBattery and Engine Flame Out Solved.

    Shutdown Historical :

  • 7/31/2019 Maintenance Problem

    12/19

    GTGC A, GP Over speed

    Date/Time GTGC A O & M

    21-11-2011 @22.59 FN476 GP Over Speed, Restart OK

    22-11-2011 Engine Wash

    23-11-2011 @01.02 FN476 GP Over Speed, Restart OK

    14-12-2011 @17.17 FN476 GP Over Speed, Restart OK

    14-12-2011 @20.47 FN476 GP Over Speed, Restart OK

    14-12-2011 @20.52 FN476 GP Over Speed, Restart OK

    14-12-2011 @21.01 FN476 GP Over Speed, Restart OK

    14-12-2011 @21.32 FN476 GP Over Speed, Restart OK14-12-2011 Check probe sensor, retighten cable

    connection line TCS-JB-Sensor

    20-12-2011 @21.41 FN476 GP Over Speed, Restart OK

    21-12-2011 Replace Probe Sensor

    Shutdown Historical :

  • 7/31/2019 Maintenance Problem

    13/19

    GTGC A, GP Over speed

    Date/Time GTGC A O & M

    26-12-2011 FN476 GP Over Speed, Restart OK

    26-12-2011 Check measure frequency & voltage

    Test NGP sensor using tools FT51010

    calibration:

    NGP 100 ; 75 ; 50 ; 25 ; 0

    Freq 3000 ; 2500 ; 1500 ; 750 ; 0

    24-01-2012 @00.21 FN 476 GP Over Speed, Restart OK

    24-01-2012 Check cable connection at JB, retighten24-01-2012 @02.23 FN476 GP Over Speed, Restart OK

    24-01-2012 @03.04 FN476 GP Over Speed, Restart OK

    29-01-2012 FN476 GP Over Speed, Restart OK

    Shutdown Historical :

  • 7/31/2019 Maintenance Problem

    14/19

    GTGC A, GP Over speed

    Date/Time GTGC A O & M

    29-01-2012 FN476 GP Over Speed, Restart OK

    29-01-2012 Check probe sensor, retighten cableconnection line TCS-JB-Sensor

    Calibrations Backup Over speed

    Check cable sensor of PT

    10-02-2012 FN476 GP Over Speed, Restart OK

    Swap Burrier from GTGC C to A

    11-02-2012 FN476 GP Over Speed, Restart OKCheck and measure shield grounding

    14-03-2012 FN476 GP Over Speed, Restart OK

    Shutdown Historical :

  • 7/31/2019 Maintenance Problem

    15/19

    GTGC A, GP Over speed

    Date/Time GTGC A O & M

    14-03-2012 Dismantle and install new EGFReconnected all cables and tubesFunction test with RS logix5 program

    15-03-2012 Test Crank failed, FN476 GP Over speed28-03-2012 Replace module ZF2091, ZF2092 and

    ZF2093 with new module , RESET onPLC (as per solar suggestion)

    28-03-2012 Start Failed, FN476 GP Over Speed

    30-03-2012 Change the resistor on ZF2090 (fromnode 07 to node 05) from 10K ohm to20K ohm(as per Solar suggestion)

    30-03-2012 Start Failed, FN476 GP Over Speed

    Shutdown Historical :

  • 7/31/2019 Maintenance Problem

    16/19

    GTGC A, GP Over speed

    Date/Time GTGC A O & M

    05-04-2012 Perform Troubleshooting with FSR:

    Checked ground system at ControlConsole (PE, IE, IS) Found that there is

    no connection between them wichmean that ground rod are not bondedtogether.

    Checked shield installation for NGPspeed probe. Found that shield is notconnect to IS ground bar but connect

    to other shield cables that connect toanywhere. Tracked shield of cable ofthe NGP speed and connected to ISground bar.

    Checked installation of the NGP speed

    probe

    Shutdown Historical :

  • 7/31/2019 Maintenance Problem

    17/19

    GTGC A, GP Over speed

    Date/Time GTGC A O & M

    Found that shield that use wire markerof NGP speed probe come from cableFuel Signal of EGF system. Ensureshield connection of EGF system arecorrect base on Electrical Schematic.

    Edit logic for temporary to capturespike at GP speed measurement insidethe logic.

    06-04-2012 Start GTGC Unit, collect data from

    Controller using Strip chart (using RS5and External Strip chart).

    Found unit run normally and there is nospike at GP speed

    Shutdown Historical :