Upload
hadan
View
228
Download
4
Embed Size (px)
Citation preview
Enclosed switches and safety switches
2CMC341002D0002 January 2009
Main Catalogue
32CMC341002D0002
Enclosed switches and safety switches
Contents
General description/Technical data ...................................................................................... 4Ratings ................................................................................................................................. 8
Switch-disconnectors / isolatorsPlastic enclosed side-operated switch-disconnectors / isolators ........................................ 10Aluminum enclosed side-operated switch-disconnectors / isolators .................................. 11Aluminum enclosed front-operated switch-disconnectors / isolators .................................. 12
Safety switchesPlastic enclosed side-operated safety switches ................................................................. 14Aluminum enclosed side-operated safety switches ............................................................ 15Aluminum enclosed front-operated safety switches ........................................................... 15
Fireman switchAluminum enclosed side-operated switch-disconnectors - Fireman switch ....................... 17
Pressure switchPressure switch - TBE 3 ..................................................................................................... 18
AccessoriesAuxiliary contacts, padlock ................................................................................................. 19Expander washer, cable tightening/glands, hose clamps, cable entries ............................ 20
Dimensions ...................................................................................................................... 21
Index ................................................................................................................................... 23
42CMC341002D0002
Advanced safety
ABB is proud to present a new range of small enclosed switches which comply with IEC 60 947-3. These switches have many different electrical mains applications, e.g. as main switches, switch-disconnectors, control switches, safety switches, fireman switches, etc. These products were developed with a focus on personal safety. A number of improvements have also been made in order to simplify installation work of the switches. The high level of quality guarantees a long and safe use.
Building on 30 years of experienceABB was quick to see the need for safe disconnection when servicing electrically-powered machinery, and has been active for many years in standardisation and product development within this field. ABB’s first safety switch was designed 30 years ago, and has since been improved to give even better safety and greater resist-ance against various environmental stresses. The new range of safety switches has been designed and tested in accordance with Machinery Directive EN 60204, and has been adapted for use in the most common applications in industrial, public and residential environments. The switches can be installed both indoors and outdoors.
Easy to install – safe to useThe new product range has been developed to bring benefits for both the installation engineer and the owner of the premises. Better access and simpler connection allow for faster, safer installation. Personal safety has been improved through measures such as the cover of the enclosure being interlocked so that it cannot be removed while the switch is in the on position. Even with the cover removed, the switch still features ingress protection (IP20), preventing accidental contact with live parts. The same applies to the neutral terminal.
The new switches are available in plastic and aluminum enclosures, in 2, 3, 4 and 6 pole versions.
One of the most common uses for the new switches is as safety switches for servicing and maintenance work. A locally-positioned lockable switch in the immediate vicinity of the machinery where work is to be carried out ensures a safe working environment for maintenance staff. In larger premises, disconnecting a section of the premises locally may also be preferable in terms of ac-cessibility, instead of disconnecting the entire premises using the main switch.
Main switches which comply with the European standard for machineryAccording to EU Directive EN 60204, Standard for machinery,
electrical equipment or machinery must be disconnected from the
electrical supply during maintenance or repairs.
In order to avoid unintentional or unauthorized start-ups,
switch-disconnectors should be fitted to the supply circuits for ma-
chinery:
- where a number of people work
- which can be started from different places
- which can be started automatically or by computer
- which cannot be seen from the place where it is started
- with complex control systems
- where there is a significant risk of personal injury in the event of an
undesired start-up
The enclosed disconnector must not be used for starting and stop-
ping or as an emergency stop device.
52CMC341002D0002
Plastic enclosed switch-disconnectors, side operated
Easy to install
• Terminals for 5-wire system: three phases + N + PE terminals
Easy to mount
• Degreeofprotection:IP65,IEC60529• Degreeofprotectionwithoutcover:IP20,IEC60529• EnclosureinPBT,UL94V1,Glowwire850˚(IEC60695-2-12)• ResistanceagainstUV-radiation:F1,UL746C• StandardIEC60947-3forSwitch-disconnectors• EuropeanStandardEN60204Safetyofmachinery
• CableoutletsMsizedthreadedknock-outs• 2-,3-,4-and6-poleversions• Lightgrey/darkgreyenclosurewithgrayhandle• Yellowenclosurehaveredhandle• HandleindicationI-0/ON-OFF• Suitablefor3-,4-and5-wiresystems
• Isolated neutral terminal with separated in/out connection.
IP 54 cable glands sealing plugs included
•
Handle,axisandswitchinsertisone system factory assembled.
•
•SwitchinsertUL94V0andglowwire 960˚(IEC60965-2-12)
• Optionforauxiliary contacts,(N.O./N.C.)
•Metric threaded knockouts
Knockout in the back of the box•
Cable strip length•• Knockout for ventilation. Water drain holes
• Handlepadlockablein”O” position as standard.• Knockout for padlock in ”I”position.• Shackle for 6 padlocks
62CMC341002D0002
Enclosed switches and safety switches
The range includes:Type BW: plastic enclosed switch-disconnectors/isolatorsType BWS: plastic enclosed safety switchesType KSE: aluminum enclosed switch-disconnectors/isolatorsTypeLBAS: aluminum enclosed safety switches
Special applications:Type KSF: fireman switchType TBE: pressure switch
The BW and BWS type enclosed switches / safety switches have enclosures made in impact resistant platic material. The KSE, KSF and LBAS types have enclosures made in aluminum alloy (silumin). The Enclosures are available in dif-ferent colors such as grey, yellow and white.
Safety switchesFor extra safety in motor applications it is common practice to connect the safety switch to the device controlling the motor with a signal
InstallationofswitchesBW,KSEandsafetyswitchesBWS,LBASExample of single line diagrams
Direct start
Ie AC23 16-63 A
Y/D-start
Ie AC23 100-630 A
Y/D-start
All kinds of
electrical
equipment
Switchgear or installation board
Safety switch
Safety switch
Safety switch
Air conditioning
Equipment
Pump ˜
Safety switch Motor ˜ Switch
Y/D Motor starter Safety switch 6-poles Motor ˜6 6
Y/D Motor starter Safety switch 3-poles
Safety switch 3-poles Motor ˜
3 3
3 31)
1) When two or more cables supply a motor or piece of equipment and several safety switches are installed, a label must be provided explaining the need to switch off all safety switches before maintenance or repair.
cable and an auxillary contact. All safety switches comes with a Normally Open auxiliary contact with 20ms early break, late make as standard. It is also possible to upgrade any enclosed switch with an extra auxiliary contact.
A complete range of accessories such as auxiliary contacts, neutral terminals and cable glands are available. The plastic enclosed switches and safety switches up to Ie 75 A are also available in 6 pole versions.
ABB offers a complete range of enclosed switches and safety switches covering the range Ith 25–630 A, Ie16–630A,forutilizationcategoryAC23AatUe400–690V.Isolationvoltagesupto1000V.TheABBCewe-Control switches comply with IEC 60 947-1 and IEC 60 947-3.
72CMC341002D0002
Typical examples of applications for ABB’s enclosed switches include in air-conditioning and cooling sys-tems, fans, lifts, conveyor belts, washing machines, restaurant kitchens and various industrial production facilities.
Dust, running water, chemicals, UV radiation, mechani-cal damage, etc., can cause significant environmental stress, which ABB’s enclosed switches can cope with easily.
The plastic enclosure is made from hardwearing PBT plastic (VALOX®) that complies with UL 94 V1 and has been glow-wire tested to 850°C in accordance with IEC 60 695-2-12. The metal enclosure is produced in coated aluminum alloy (Silumin), making it suitable for all in-/outdoor environments, from mountain areas to deserts.
The switches are also available in ATEX category 3 (zone 22) versions for use in environments where there is a risk of explosion.
Application
82CMC341002D0002
Enclosed switches Ratings IEC 60 947-3
Switches type BW and KSE
Safety switches type BWS andLBAS
Plastic and metal enclosure
Ie AC23A 16-90 A
Ith 25-125 A
For motors Pe up to 45 kW
Ue400-750V
Degree of protection: IP54 or IP65
BW225DP BW325L BW325W BW240DP BW340 KSE363 KSE380 KSE3100
BW225 W DP BW325 KS 240 DP BW440 KSE463 KSE480
KSE225DP BW325K BW640 LBAS336 LBAS363
KSF225 DP BW425 KSE340
BW325Y KSE440
BW625 BWS325
KSE325 BWS425
KSE425 BWS625
BWS316 BWS325Y
BWS416 BWS425Y
BWS616 BWS625Y
BWS316Y LBAS325
BWS416Y LBAS425
BWS616Y KSF340
BWS316F KSF 440
LBAS316
LBAS416
KSF 325
KSF 425
Isolationvoltage V 690 400 690 690 690 750 750 750
Uimp V 8 8 8 8 8 8 8 8 8
Rated thermal currentlthe at 40ºC A 25 25 25 32 40 40 63 80 115lthe at 60ºC A 50 63 80With minimum conductor mm2 4 4 4 10 10 16 25 35cross section
Operatingvoltage,Ue V 230 400 400 400 500 690 230 400 400 500 690 400 500 690 400 500 690 400 500 690
Rated currentle AC23A A 16 16 16 16 16 10 25 25 25 25 16 45 45 20 75 58 20 80 60 40le AC22A A 25 25 25 25 25 16 40 40 40 40 25 63 63 63 80 80 80 100 100 100
Max fuse, aM A 50 50 50 50 35 35 50 50 50 35 35 63 63 63 80 80 80 125 63 63
Conditional short-circuit
current kA 25 25 25 25 25 25 25 25 25 25 25 50 50 50 50 50 50 50 50 50
Fuse protected short-circuit making capacity kA 5.5 5.5 5.0 5.0 4.8 4.8 5.5 5.5 5.0 4.8 4.8 13 11 11 13 11 11 16.5 10 10
Rated making capacity ≤ 100A cos = 0,45 A 160 160 160 160 160 100 250 250 250 250 160 450 450 200 750 580 200 800 600 400
Rated breaking capacity
≤ 100A cos = 0,45 A 128 128 128 128 128 80 200 200 200 200 128 360 360 160 600 460 160 640 480 320
Max motor power kW 7,5 7.5 7.5 7.5 11 15 11 22 22 15 37 37 18.5 37 37 37
Terminals for cable
section Cu mm² 1 - 10 1 - 10 1 - 10 1 - 10 1 - 10 1.5 - 35 1.5 - 35 10 - 70
Earth terminal mm² 10 10 10 10 10 16 25 70
KSE3160 LBAS160/S KSE3250 KSE3315 KSE3500 KSE3630
LBAS125/S LBAS160/SK1) LBAS200/S LBAS250/S LBAS400/S LBAS630/S
LBAS125/SK1)
Isolationvoltage V 690 690 1000 1000 1000 1000
Uimp kV 12 12 12 12 12 12
Rated thermal current lthe A 160 160 270 315 500 630
Operatingvoltage,Ue V 400 500 690 400 500 690 400 500 690 400 500 690 400 500 690 400 500 690
Rated current le AC23A A 125 90 70 160 125 80 250 250 250 315 315 315 500 500 350 630 580 350
Max fuse A 200 200 200 250 250 250 400 400 400 400 400 400 630 630 630 800 800 800
Conditional short-circuit
current kA 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
Fuse protected short- circuit making capacity kA 18 18 18 18 18 18 35 35 35 35 35 35 50 50 50 60 60 60
Rated making capacity ≤ 100A cos = 0,45 > 100A cos = 0,35 A 1250 900 700 1600 1250 800 2500 2500 2500 3150 3150 3150 5000 5000 3500 6300 5800 3500
Rated breaking capacity ≤ 100A cos = 0,45 > 100A cos = 0,35 A 1000 720 560 1280 1000 640 2000 2000 2000 2520 2520 2520 4000 4000 2800 5760 4800 2800
Max motor power kW 55 55 55 75 75 75 132 160 200 160 200 250 250 315 315 315 355 355
Terminals for cable 10-70 10-70 2) 2) 2) 2) 2)
section Cu mm² or 1) or 1
Earth terminal mm² 50 50 2x300 2x300 2x300 2x300
Expander washes for Included Included Included Included Included Included safety protection in case of short-circuit
92CMC341002D0002
Switches type KSE
Safety switches type
LBAS(≥ 125A)
Metal enclosure
(aluminumalloy)
Ie AC23A 63-630 A
Ith 160-630 A
For motors Pe up to 355 kW
Ue400-690V
Degree of protection: IP65
1)Terminalscrewforcablelugs.(M8)2)Terminalscrewforcablelugs.(M12)
KSE3160 LBAS160/S KSE3250 KSE3315 KSE3500 KSE3630
LBAS125/S LBAS160/SK1) LBAS200/S LBAS250/S LBAS400/S LBAS630/S
LBAS125/SK1)
Isolationvoltage V 690 690 1000 1000 1000 1000
Uimp kV 12 12 12 12 12 12
Rated thermal current lthe A 160 160 270 315 500 630
Operatingvoltage,Ue V 400 500 690 400 500 690 400 500 690 400 500 690 400 500 690 400 500 690
Rated current le AC23A A 125 90 70 160 125 80 250 250 250 315 315 315 500 500 350 630 580 350
Max fuse A 200 200 200 250 250 250 400 400 400 400 400 400 630 630 630 800 800 800
Conditional short-circuit
current kA 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
Fuse protected short- circuit making capacity kA 18 18 18 18 18 18 35 35 35 35 35 35 50 50 50 60 60 60
Rated making capacity ≤ 100A cos = 0,45 > 100A cos = 0,35 A 1250 900 700 1600 1250 800 2500 2500 2500 3150 3150 3150 5000 5000 3500 6300 5800 3500
Rated breaking capacity ≤ 100A cos = 0,45 > 100A cos = 0,35 A 1000 720 560 1280 1000 640 2000 2000 2000 2520 2520 2520 4000 4000 2800 5760 4800 2800
Max motor power kW 55 55 55 75 75 75 132 160 200 160 200 250 250 315 315 315 355 355
Terminals for cable 10-70 10-70 2) 2) 2) 2) 2)
section Cu mm² or 1) or 1
Earth terminal mm² 50 50 2x300 2x300 2x300 2x300
Expander washes for Included Included Included Included Included Included safety protection in case of short-circuit
102CMC341002D0002
Enclosed switches Orderinginformation
Enclosure: Robustthermoplastic(PBT)Brand: ABBCable entries: Metric threaded knock-outs or knock-outs. Membrane glands/ sealingplugs(IP54)areincluded.WhenIP65degreeof protection is required compression glands must be used. Lockable: YesRatings: See page 8Dimensions: See page 21Degree of protection: IP 65Neutral and PE terminal: Included Auxiliary contacts: Not includedColorsEnclosure: LightgreyHandleandcover: Darkgrey(exceptfor*and**)
Plastic enclosed side-operated switch-disconnectors, 2-pole
Rated operational Cable entries Enclosure size Type Order number Weightcurrent [A] Up/down [mm] [kg]AC-22A AC-23A W H D 230V 400V 400V 25 25 16 2xM25/2xM25 111 130 60 BW225 DP 2CMA142400R1000 0.2925 25 16 2xM25/2xM25 111 130 60 BW225 W DP*) 2CMA142401R1000 0.29
40 40 25 2xM32/2xM32+1xM16 138 168 68 BW240 DP 2CMA142407R1000 0.39
Plastic enclosed side-operated switch-disconnectors, 3-pole
Rated operational Cable entries Enclosure size Type Order number Weightcurrent [A] Up/down [mm] [kg]AC-22A AC-23A W H D400V 500V 690V 500V
25 25 16 16 2xM25/2xM25 111 130 60 BW325 TPN 2CMA142403R1000 0.3125 25 16 16 2xM25/2xM25 111 130 60 BW325 W TPN*) 2CMA142402R1000 0.3125 25 16 16 2xM25/2xM25 111 130 60 BW325YTPN**) 2CMA142441R1000 0.3125 25 16 16 2xM25/2xM25 111 130 60 BW325 K TPN*) 2CMA142443R1000 0.3140 40 32 25 2xM32/ 138 168 68 BW340 TPN 2CMA142408R1000 0.41 2xM32+1xM16
Plastic enclosed side-operated switch-disconnectors, 3-pole
Rated operational Cable entries Enclosure size Type Order number Weightcurrent [A] Up/down [mm] [kg]AC-22A AC-23A W H D400V 500V 690V 400V
25 - - 16 2xM25/2xM25 111 130 62 BW325LTPN*) 2CMA142404R1000 0.31
Plastic enclosed side-operated switch-disconnectors, 4-pole
Rated operational Cable entries Enclosure size Type Order number Weightcurrent [A] Up/down [mm] [kg]AC-22A AC-23A W H D400V 500V 690V 500V
25 25 16 16 2xM25/2xM25 111 130 60 BW425 TPSN 2CMA142405R1000 0.31
40 40 32 25 2xM32/2xM32+1xM16 138 168 68 BW440 TPSN 2CMA142409R1000 0.41
Plastic enclosed side-operated switch-disconnectors, 6-pole
Rated operational Cable entries Enclosure size Type Order number Weightcurrent [A] Up/down [mm] [kg]AC-22A AC-23A400V 500V 690V 500V W H D 25 25 16 16 2xØ25+1xØ16 190 130 65 BW625 TPN 2CMA142406R1000 0.54 2xØ25+1xØ1640 40 32 25 2xØ25+1xØ16 190 130 65 BW640 TPN 2CMA142410R1000 0.54 2xØ25+1xØ16
*)Lightgreyboxandcover,darkgreyhandle**)Lightgreybox,yellowcover,redhandle
BW225 DP, BW325 TPNBW425 TPSN
BW625 TPN, BW640 TPN
2CM
C34
1011
F005
4
BW325 Y DP
2CM
C34
1011
F006
02C
MC
3410
11F0
066
BW240 DP, BW340 TPN,BW440 TPSN
2CM
C34
1011
F005
6
BW225 W DP, BW325 W TPN
2CM
C34
1011
F005
4
BW325 K TPN
BW325 L TPN
2CM
C34
1011
F007
22C
MC
3410
11F0
073
112CMC341002D0002
Enclosed switches Orderinginformation
Enclosure: Aluminumalloy-(PBTHandle)Brand: ABBCable entries: Metric threaded holes with membrane glands/sealing plugs (IP54)included.WhenIP65degreeofprotectionisrequired compression glands must be used. Lockable: YesRatings: See page 8Dimensions: See page 21Degree of protection: IP 65Neutral and PE terminal: Included Auxiliary contacts: Not includedColorsEnclosure: LightgreyHandleandcover: Darkgrey
Aluminum enclosed side-operated switch-disconnectors, 2-pole
Cable entries from top and bottom Rated operational Cable entries Enclosure size Type Order number Weightcurrent [A] Up/Down [mm] [kg]AC-22A AC-23A W H D230V 400V 400V
25 25 16 2xM25/2xM25 111 130 60 KSE225 DP 2CMA142411R1000 0.54
40 40 25 2xM32/2xM32+1xM16 138 168 68 KSE240 DP 2CMA142414R1000 0.78
Aluminum enclosed side-operated switch-disconnectors, 3-pole
Cable entries from top and bottom Rated operational Cable entries Enclosure size Type Order number Weight current [A] Up/Down [mm] [kg] AC-22A AC-23A W H D 400V 500V 690V 500V
25 25 16 16 2xM25/2xM25 111 130 60 KSE325 TPN 2CMA142412R1000 0.56
40 40 32 25 2xM32/2xM32+1xM16 138 168 68 KSE340 TPN 2CMA142415R1000 0.79
Aluminum enclosed side-operated switch-disconnectors, 4-pole
Cable entries from top and bottom Rated operational Cable entries Enclosure size Type Order number Weightcurrent [A] Up/Down [mm] [kg] AC-22A AC-23A W H D 400V 500V 690V 500V
25 25 16 16 2xM25/2xM25 111 130 60 KSE425 TPSN 2CMA142413R1000 0.56
40 40 32 25 2xM32/2xM32+1xM16 138 168 68 KSE440 TPSN 2CMA142416R1000 0.80
2CM
C34
2002
F000
8
KSE225 DP, KSE325 TPN,KSE425 TPSN
2CM
C34
2002
F001
0
KSE240 DP, KSE340 TPN,KSE440 TPSN
122CMC341002D0002
Enclosure: Aluminumalloy-(PBTHandle)Brand: ABBCable entries: Metric threaded holes with membrane glands/sealing plugs (IP54)included.WhenIP65degreeofprotectionisrequired compression glands must be used. Lockable: YesRatings: See page 8Dimensions: See page 22Degree of protection: IP 65Neutral and PE terminal: Included Auxiliary contacts: Not includedColorsEnclosure: LightgreyCover: Dark greyHandle: Black
Aluminum enclosed front-operated switch-disconnectors, 3-pole
Cable entries from top and bottom
Rated operational Cable entries Enclosure size Type Order number Weight current [A] Up/Down [mm] [kg] AC-22A AC-23A W H D 500V 690V 500V
63 63 45 2xM40/2xM40+1xM16 160 230 145 KSE363 TPN 2CMA144580R1000 1.75 80 80 75 2xM40/2xM40+1xM16 160 230 145 KSE380 TPN 2CMA144583R1000 1.75 100 100 80 2xM40/2xM40+1xM16 160 230 145 KSE3100 TPN 2CMA144585R1000 1.84
Cable entries from bottom
Rated operational Cable entries Enclosure size Type Order number Weight current [A] Down [mm] [kg] AC-22A AC-23A W H D 500V 690V 500V
63 63 45 2xM40+1xM16 160 230 145 KSE363 D/TPN 2CMA144581R1000 1.75
Aluminum enclosed front-operated switch-disconnectors, 4-pole
Cable entries from top and bottom Rated operational Cable entries Enclosure size Type Order number Weightcurrent [A] Up/Down [mm] [kg] AC-22A AC-23A W H D 500V 690V 500V
63 63 45 2xM40/2xM40+1xM16 160 230 145 KSE463 TPSN 2CMA144582R1000 1.83 75 80 80 2xM40/2xM40+1xM16 160 230 145 KSE480 TPSN 2CMA144584R1000 1.83
Enclosed switches Orderinginformation
KSE363 D/TPN
2CM
C34
1011
F007
8
KSE463 TPSN, KSE480 TPSN
KSE363 TPN, KSE380 TPN, KSE3100 TPN
2CM
C34
1011
F007
82C
MC
3410
11F0
075.
r
132CMC341002D0002
Enclosure: Aluminumalloy-(PBTHandle)Brand: CEWECable entries: Cable tightening/glands includedLockable: YesRatings: See page 9Dimensions: See page 22Degree of protection: IP 65Neutral and PE terminal: IncludedAuxilary contact: Not included
ColoursEnclosure: WhiteHandleandcover: Blackandred
Aluminum enclosed front-operated switch-disconnector, 3-pole
Cable entries from bottom
Rated operational Cable entries Enclosure size Type Order number Weight current [A] Up/Down [mm] [kg] AC-22A AC-23A W H D 690V 400V
160 135 2xØ18-48 400 405 234 KSE3160 2CMA144712R1000 9.7250 250 4xØ30-68 465 555 322 KSE32501) 2CMA144713R1000 23.0315 315 4xØ30-68 465 555 322 KSE33152) 2CMA144714R1000 23.0500 400 4xØ30-68 565 655 322 KSE35002) 2CMA144715R1000 36.0630 630 4xØ30-68 565 655 322 KSE36302) 2CMA144716R1000 37.0
1) Terminal screw for cable lugs. (M12) max 2//240mm2
2) Terminal screw for cable lugs. (M12) max 2//300mm2
Enclosed switches Orderinginformation
KSE3160
2CM
C34
1011
F002
3
KSE3250, KSE3315,KSE3500, KSE3630
2CM
C34
1011
F008
4
142CMC341002D0002
Safety switches Orderinginformation
Enclosure: Robustthermoplastic(PBT)Brand: ABBCable entries: Metric threaded knock-outs. Membrane glands/sealing plugs (IP54)areincluded.When IP 65 degree of protection is required compression glands must be used. Lockable: YesRatings: See page 8Dimensions: See page 21Degree of protection: IP 65Neutral and PE terminal: Included Auxiliarycontact: Included(1NO)ColorsEnclosure: LightgreyHandleandcover: Darkgrey.(Exceptfor*))
Plastic enclosed side-operated switch-disconnector, 3-pole
Rated operational Cable entries Enclosure size Type Order number Weightcurrent [A] Up/Down [mm] [kg] AC-23A AC-23A W H D 500V 690V Kwh
16 10 7,5 2xM25/2xM25 111 130 60 BWS316 TPN 2CMA142417R1000 0.32 25 16 11 2xM32/2xM32+1xM16 138 168 68 BWS325 TPN 2CMA142420R1000 0.41 16 10 7,5 2xM25/2xM25 111 130 60 BWS316YTPN*) 2CMA142423R1000 0.37 25 16 11 2xM32/2xM32+1xM16 138 168 68 BWS325YTPN*) 2CMA142426R1000 0.41 16 10 7,5 2xM25/2xM25 111 130 60 BWS316 F TPN**) 2CMA142440R1000 0.32
Plastic enclosed side-operated switch-disconnectors, 4-pole Rated operational Cable entries Enclosure size Type Order number Weight current [A] Up/Down [mm] [kg] AC-22A AC-23 W H D 500V 690V Kwh
16 10 7,5 2xM25/2xM25 111 130 60 BWS416 TPSN 2CMA142418R1000 0.32 25 16 11 2xM32/2xM32+1xM16 138 168 68 BWS425 TPSN 2CMA142421R1000 0.42 16 10 7,5 2xM25/2xM25 111 130 60 BWS416YTPSN*) 2CMA142424R1000 0.32 25 16 11 2xM32/2xM32+1xM16 138 168 68 BWS425YTPSN*) 2CMA142427R1000 0.42
Plastic enclosed side-operated switch-disconnectors, 6-pole
Rated operational Cable entries Enclosure size Type Order number Weightcurrent [A] Up/Down [mm] [kg] AC-22A AC-23 W H D 500V 690V Kwh
16 10 7,5 2xØ25+Ø16/2xØ25+Ø16 190 130 65 BWS616 TPN 2CMA142419R1000 0.54 25 16 11 2xØ25+Ø16/2xØ25+Ø16 190 130 65 BWS625 TPN 2CMA142422R1000 0.54 16 10 7,5 2xØ25+Ø16/2xØ25+Ø16 190 130 65 BWS616YTPN*) 2CMA142425R1000 0.54 25 16 11 2xØ25+Ø16/2xØ25+Ø16 190 130 65 BWS625YTPN*) 2CMA142428R1000 0.54 *) Light grey box, yellow cover, red handle**) Auxiliary contact not included
2CM
C34
1011
F005
4
BWS316 TPN, BWS416 TPSN
BWS316 Y TPN, BWS416 Y TPSN
2CM
C34
1011
F005
5
BWS616 TPN, BWS625 TPN
2CM
C34
1011
F006
6
BWS616 Y TPNBWS625 Y TPN
2CM
C34
1011
F007
02C
MC
3410
11F0
056
BWS325 TPN, BWS425 TPSN
BWS325 Y TPN, BWS425 Y TPSN
2CM
C34
1011
F006
0
152CMC341002D0002
Safety switches Orderinginformation
Enclosure: Aluminumalloy-(PBTHandle)Brand: ABBCable entries: Metric threaded holes with membrane glands/sealing plugs (IP54)included.WhenIP65degreeofprotectionisrequired compression glands must be used. Lockable: YesRatings: See page 8Dimensions: See page 21 and 22Degree of protection: IP 65Neutral and PE terminal: Included Auxiliarycontacts: Included(1NO)ColoursEnclosure: LightgreyHandleandcover: Darkgrey(Exceptfor*))
Aluminum enclosed side-operated switch-disconnector, 3-pole Cable entries from top and bottom
Rated operational Cable entries Enclosure size Type Order number Weightcurrent [A] Up/Down [mm] [kg]AC-22A AC-23 W H D500V 690V Kwh
16 10 7,5 2xM25/2xM25 111 130 60 LBAS316TPN 2CMA142430R1000 0.5725 16 11 2xM32/2xM32+1xM16 138 168 68 LBAS325TPN 2CMA142432R1000 0.80
Aluminum enclosed side-operated switch-disconnectors, 4-poleCable entries from top and bottom
Rated operational Cable entries Enclosure size Type Order number Weight current [A] Up/Down [mm] [kg]AC-22A AC-23 W H D500V 690V Kwh
16 10 7,5 2xM25/2xM25 111 130 60 LBAS416TPSN 2CMA142431R1000 0.5725 16 11 2xM32/2xM32+1xM16 138 168 68 LBAS425TPSN 2CMA142433R1000 0.81
Aluminum enclosed front-operated switch-disconnector, 3-pole Cable entries from top and bottom
Rated operational Cable entries Enclosure size Type Order number Weightcurrent [A] Up/Down [mm] [kg]AC-22A AC-23 W H D500V 690V Kwh
45 20 22 2xM40/2xM40+1xM16 160 230 145 LBAS336M/TPN*) 2CMA144635R1000 1.75 58 20 37 2xM40/2xM40+1xM16 160 230 145 LBAS363M/TPN*) 2CMA144636R1000 1.75 *) Light grey box, dark grey cover, black handle
2CM
C34
2002
F000
8
LBAS316TPN,LBAS416TPSN
2CM
C34
2002
F001
0
LBAS325 TPN. LBAS425 TPSN
2CM
C34
1011
F007
5
LBAS336 M/TPN. LBAS363 M/TPN
162CMC341002D0002
Enclosure: Aluminumalloy-(PBTHandle)Brand: CeweCable entries: Cable tightening/glands includedLockable: YesRatings: See page 9Dimensions: See page 22Degree of protection: IP 65Neutral terminal: Not included PE terminal: IncludedAuxiliarycontacts: Included(1NO)ColoursEnclosure: WhiteHandleandcover: Blackandred
Aluminum enclosed front-operated switch-disconnector, 3-pole Cable entries from bottom
Rated operational Cable entries Enclosure size Type Order number Weightcurrent [A] Down [mm] [kg]AC-23A W H D400V 500V 690V
125 90 70 2xØ18-48 400 405 234 LBAS125/S 2CMA144495R1000 9.70125 90 70 2xØ18-48 400 405 234 LBAS125/SK1) 2CMA144496R1000 10.40 160 125 80 2xØ18-48 400 405 234 LBAS160/S 2CMA144498R1000 9.70160 125 80 2xØ18-48 400 405 234 LBAS160/SK1) 2CMA144499R1000 10.40 250 250 250 4xØ30-68 465 555 235 LBAS200/S2) 2CMA144500R1000 23.00 315 315 315 4xØ30-68 465 555 235 LBAS250/S3) 2CMA144503R1000 23.00 500 500 350 4xØ30-68 565 655 235 LBAS400/S3) 2CMA144505R1000 26.00 630 580 350 4xØ30-68 565 655 235 LBAS630/S3) 2CMA144506R1000 27.00
1) Screw terminals for cable lugs max 95 mm2
2) Screw terminals for cable lugs max 2//240 mm2
3) Screw terminals for cable lugs max 2//300 mm2
- Extra auxiliary contacts to be ordered separately, see page 19.
Safety switches Orderinginformation
LBAS125/S, LBAS125/SK,LBAS160/S, LBAS160/SK
2CM
C34
1011
F002
3
LBAS200/S, LBAS250/SLBAS400/S, LBAS630/S
2CM
C34
1011
F008
4
172CMC341002D0002
Enclosed switches - Fireman switchOrderinginformation
General Technical DataEnclosure: Aluminum alloyBrand: ABBDegree of protection: IP 65Lockable: YesRatings: See page 8Dimensions: See page 22Auxiliarycontact: Included(1NO)
ColorsEnclosure: RedHandleandcover: Red StandardsDevices complying with - International standards IEC 60947-3-BrittishstandardsBS7671(Requirementsforelectricalinstallations)
Aluminum enclosed side-operated switch-disconnectors, 2-poleCable entries from top and bottom Rated operational Cable entries Enclosure size Type Order number Weightcurrent [A] Up/Down [mm] [kg]AC-22A W H D230V 400V
25 25 2xM25/2xM25 109 130 60 KSF225 DP 2CMA142435R1000 0.57
Aluminum enclosed side-operated switch-disconnectors, 3-poleCable entries from top and bottom Rated operational Cable entries Enclosure size Type Order number Weight current [A] Up/Down [mm] [kg] AC-22A W H D 400V 500V 690V
25 25 16 2xM25/2xM25 109 130 60 KSF325 TPN 2CMA142436R1000 0.59 40 40 32 2xM32/2xM32+1xM16 136 168 68 KSF340 TPN 2CMA142438R1000 0.82 25 25 16 2xM25/2xM25 109 130 60 KSF325NO/TPN*) 2CMA142442R1000 0.60
Aluminum enclosed side-operated switch-disconnectors, 4-poleCable entries from top and bottom Rated operational Cable entries Enclosue size Type Order number Weight current [A] Up/Down [mm] [kg]AC-22A W H D400V 500V 690V
25 25 16 2xM25/2xM25 109 130 60 KSF425 TPSN 2CMA142437R1000 0.59 40 40 32 2xM32/2xM32+1xM16 136 168 68 KSF440 TPSN 2CMA142439R1000 0.83
*) Auxiliary contact included.
2CM
C34
2002
F001
2
KSF225 DP, KSF325 TPN,KSF325 NO/TPN, KSF425 TPSN
2CM
C34
2002
F001
3
KSF340 TPN, KSF440 TPSN
182CMC341002D0002
Pressure switch - TBE 3Orderinginformation
EnclosureBottom: Aluminum alloyCover: Transparent polycarbonate All essential parts in non corrosive materialBrand: CeweTerminals: 2.5 mm2
Ratedcurrent: 10A(IEC60947-4)Degree of protection: IP 44
Area of usePressure switch TBE 3 used for pressure control of air or water systems. Pressure range up, to800kPa.(8kp/cm2).
Making and breaking pressureMaking and breaking pressures adjustable on two separate scales. Making from 100 to 600 kPa(1to6kp/cm2).Breakingpressureadjustablefrom200to800kPa(2-8kp/cm2).Minimumdifference200kPa(2kp/cm2).
Rated voltage Cable entries Pipe Enclosure size Type Order number WeightV Down entries [mm] [kg]0000 W H D
400 2xM20 R 1/2" 110 116 82 TBE 3 2CMA144551R1000 0.45
TBE 3
2CM
C30
6006
F000
1
192CMC341002D0002
Pressure switch - TBE 3Orderinginformation
MCB-01MCB-10
OA1G10OA1G01
OBEA10OBEA01
OZXK12OZXK1
L6
Auxiliary contact blockOrder Code Type 1) For switch type
1-pole making 10 A, 690 V1SFA611610R1001 MCB-10 KSE225...340, BE and BW325, 340, 625
1-pole breaking 10 A, 690 V1SFA611610R1010 MCB-01 KSE225...340, BE and BW325, 340, 625
1-pole making 10 A, 690 V2CMA144690R1000 OA1G10 KSE363, KSE380, KSE463, KSE480, KSEE3100, KSE4100
1-pole breaking 10 A, 690 V2CMA144691R1000 OA1G01 KSE363, KSE380, KSE463, KSE480, KSEE3100, KSE4100
1-pole making 10 A, 690 V2CMA144519R1000 OBEA 10 KSE3160, KSE3250, LBAS 125/S–160/S
1-pole breaking 10 A, 690 V2CMA144520R1000 OBEA 01 KSE3160, LBAS125/S–160/S
2-pole making/breaking for galvanically separated circuits, 10 A, 690 V2CMA144521R1000 OZXK 12 KSE3315, KSE3250, LBAS200/S, LBAS250/S2CMA144522R1000 OZXK 1 KSE3500, KSE3630, LBAS400/S, LBAS630/S
1) In all sizes of safety switches there is space for one more auxiliary contact block than included. In the KSE types there is space for 1 contact block (not included)
Ratings for auxiliary contact
For switch 25- 40A 63- 100A For safety switch 16- 25A 45- 75A 125-160A 200-630A IEC 60 947-5-1 IEC 60 947-5-1 IEC 60 947-5-1 IEC 60 947-5-1Rated thermal current A 10 16 10 10Duty category AC 12 AC 15 AC 12 AC 12Operating voltage V 690, 400, 240 690, 400, 240 690, 400, 240 690, 400, 240Rated current A 2 4 6 2 4 6 2 4 6 2 4 6
Padlock unit suitable for all switchesOrder Code Type Description
2CMA144539R1000 L6 Shackle for up to 6 padlocks
Mounting / spacer feetsOrder Code Description
2CMA170052R1000 Mounting / spacer feets
Accessories
202CMC341002D0002
Membrane gland-sealing plug
Accessories, LBAS
43 507 – Expander washer for LBAS125/S–160/S (K)43 585 – Expander tube for LBAS200/S–630/S43 519 – Cable tightening/gland for LBAS125/S–160/S (K)43 520 – Cable tightening/gland for LBAS200/S–630/S
43 506 – Hose clamp, stainless steel, for list no 43 51943 523 – Hose clamp, stainless steel, for list no 43 520
Neutral terminals for LBASOrder Code Type Description For switches type
2CMA144534R1000 NOLS1 Neutral terminal LBAS125/S–160/S (K)2CMA144535R1000 NOLS2 Neutral terminal LBAS200/S–630/S
Cable entries/sealing plugs for switches type KSE, Safety switches type KSA and LBAS and KSEE
Membraneglands/sealingplugs(IP54)inthermoplasticareincludedasfollows:1)
Type Cable entries size No of pcs. 2)For cable diam. (mm)+M/TPN “M” threads1) incl. IP 54
KSE 325.. M25 4 10-18 M16 1 6-11
KSE 340.. M25 4 10–18 M16 1 6-11
KSE 363.. M32 3 16–24 M16 1 6–11 KSE 380.. M32 3 16–24 M16 1 6–11
KSEE 3100.. M32 3 16–24 M16 1 6–11
KSA 316.. M20 4 10-18 M16 1 6-11
KSA 325.. M25 4 10–18 M16 1 6-11
LBAS 336.. M32 3 16–24 M16 1 6–11
LBAS 363.. M32 3 16–24 M16 1 6–11
1) The types specified can be used both as cable tightening and as sealing plug.2) The cable hole of the membrane gland has to be cut carefully in order to reach the IP 54 degree of protection.– If IP 65 degree of protection is requested compression glands must be used.
4351943520
43506
Accessories
212CMC341002D0002
Enclosed switches Dimension drawings
Plastic enclosed side-operated switch-disconnectors / safety switches
ØGA
B
XW
H
XYD
Type Size Cable entry Fixing dimensions W H D X Y A B G
2-pole, Plastic enclosed side-operated switch-disconnectors
BW 225... 111 130 60 2xM25 - 64 90 5BW 240... 138 168 68 2xM32 1xM16 90 127 53-pole, Plastic enclosed side-operated switch-disconnectors
BW 325... 111 130 60 2xM25 - 64 90 5BW 340... 138 168 68 2xM32 1xM16 90 127 53-pole, Plastic enclosed side-operated safety switches
BWS 316... 111 130 60 2xM25 - 64 90 5BWS 325... 138 168 68 2xM32 1xM16 90 127 54-pole, Plastic enclosed side-operated switch-disconnectors
BW 425... 111 130 60 2xM25 - 64 90 5BW 440... 138 168 68 2xM32 1xM16 90 127 54-pole, Plastic enclosed side-operated safety switches
BWS 416... 111 130 60 2xM25 - 64 90 5BWS 425... 138 168 68 2xM32 1xM16 90 127 56-pole, Plastic enclosed side-operated switch-disconnectors
BW 625... 190 130 65 2xø25 ø16 124 90 5BW 640 ... 190 130 65 2xø25 ø16 124 90 56-pole, Plastic enclosed side-operated safety switches
BWS 616... 190 130 65 2xø25 ø16 124 90 5BWS 625... 190 130 65 2xø25 ø16 124 90 5
ØGA
B
XW
H
XYD
Aluminum enclosed side-operated switch-disconnectors / safety switches
Type Size Cable entry Fixing dimensions W H D X Y A B G
2-pole, Aluminum enclosed side-operated switch-disconnectors
KSE 225... 111 130 60 2xM25 - 64 90 5KSE 240... 138 168 68 2xM32 1xM16 90 127 53-pole, Aluminum enclosed side-operated switch-disconnectors
KSE 325... 111 130 60 2xM25 - 64 90 5KSE 340... 138 168 68 2xM32 1xM16 90 127 53-pole, Aluminum enclosed side-operated safety switches
LBAS 316... 111 130 60 2xM25 - 64 90 5LBAS 325... 138 168 68 2xM32 1xM16 90 127 54-pole, Aluminum enclosed side-operated switch-disconnectors
KSE 425... 111 130 60 2xM25 - 64 90 5KSE 440... 138 168 68 2xM32 1xM16 90 127 54-pole, Aluminum enclosed side-operated safety switches
LBAS 416... 111 130 60 2xM25 - 64 90 5LBAS 425... 138 168 68 2xM32 1xM16 90 127 5
ØGA
B
W
H
XY
XYD
222CMC341002D0002
Enclosed switches Dimension drawings
X
XYD
H
W
A ØG
B
X
W
A øC
H
D
B
W
H
X
D
Aluminum enclosed front-operated switch-disconnectors / safety switches
Type Size Cable entry Fixing dimensions W H D X Y A B G
3-pole, Aluminum enclosed front-operated switch-disconnectors
KSE 363... 160 230 145 2xM40 1xM16 124 190 5.3KSE 380... 160 230 145 2xM40 1xM16 124 190 5.3KSE 3100... 160 230 145 2xM40 1xM16 124 190 5.33-pole, Aluminum enclosed front-operated safety swithes
LBAS 336... 160 230 145 2xM40 1xM16 124 190 5.3LBAS 363... 160 230 145 2xM40 1xM16 124 190 5.34-pole, Aluminum enclosed front -operated switch-disconnectors
KSE 463... 160 230 145 2xM40 1xM16 124 190 5.3KSE 480... 160 230 145 2xM40 1xM16 124 190 5.3
Type Size Cable entry Fixing dimensions H W D X A B C min/max min/max
3-pole, Aluminum enclosed front-operated switch-disconnectors
KSE 3160 405 400 234 2xØ18-48 340/414 331/405 8KSE 3250/3315 555 465 322 4xØ30-68 395/490 485/580 10
KSE3500/3630 655 565 322 4xØ30-68 495/590 585/680 10
3-pole, Aluminum enclosed front-operated safety switches
LBAS 125/160 405 400 234 2xØ18-48 340/414 331/405 8LBAS 200/250 555 465 322 4xØ30-68 395/490 485/580 10
LBAS400/630 655 565 322 4xØ30-68 495/590 585/680 10
Aluminum enclosed front-operated switch-disconnectors / safety switches
Aluminum enclosed side-operated switch-disconnectors - Fireman switch
ØGA
B
Type Size Cable entry Fixing dimensions W H D X Y A B G
2-pole, Aluminum enclosed side-operated switch-disconnectors
KSF 225... 109 130 60 2xM25 - 64 90 53-pole, Aluminum enclosed side-operated switch-disconnectors
KSF 325... 109 130 60 2xM25 - 64 90 5KSF 340... 136 168 68 2xM32 1xM16 90 127 54 pole-Aluminum
KSF 425... 109 130 60 2xM25 - 64 90 5KSF 440... 136 168 68 2xM32 1xM16 90 127 5
XW
H
XYD
232CMC341002D0002
Enclosed switches Index
Type Order number Page Discription
Accossories LBAS 43507 20 Expander washer
Accossories LBAS 43585 20 Expander tube
Accossories LBAS 43519 20 Cable tightening/gland
Accossories LBAS 43520 20 Cable tightening/gland
Accossories LBAS 43506 20 Hose clamp
Accossories LBAS 43523 20 Hose clamp
BW225 DP 2CMA142400R1000 10 Enclosed switch
BW225 W DP 2CMA142401R1000 10 Enclosed switch
BW240 DP 2CMA142407R1000 10 Enclosed switch
BW325 K TPN 2CMA142443R1000 10 Enclosed switch
BW325 L TPN 2CMA142404R1000 10 Enclosed switch
BW325 TPN 2CMA142403R1000 10 Enclosed switch
BW325 W TPN 2CMA142402R1000 10 Enclosed switch
BW325 Y TPN 2CMA142441R1000 10 Enclosed switch
BW340 TPN 2CMA142408R1000 10 Enclosed switch
BW425 TPSN 2CMA142405R1000 10 Enclosed switch
BW440 TPSN 2CMA142409R1000 10 Enclosed switch
BW625 TPN 2CMA142406R1000 10 Enclosed switch
BW640 TPN 2CMA142410R1000 10 Enclosed switch
BWS316 F TPN 2CMA142440R1000 14 Safety switch
BWS316 TPN 2CMA142417R1000 14 Safety switch
BWS316 Y TPN 2CMA142423R1000 14 Safety switch
BWS325 TPN 2CMA142420R1000 14 Safety switch
BWS325 Y TPN 2CMA142426R1000 14 Safety switch
BWS416 TPSN 2CMA142418R1000 14 Safety switch
BWS416 Y TPSN 2CMA142424R1000 14 Safety switch
BWS425 TPSN 2CMA142421R1000 14 Safety switch
BWS425 Y TPSN 2CMA142427R1000 14 Safety switch
BWS616 TPN 2CMA142419R1000 14 Safety switch
BWS616 Y TPN 2CMA142425R1000 14 Safety switch
BWS625 Y TPN 2CMA142428R1000 14 Safety switch
BWS626 TPN 2CMA142422R1000 14 Safety switch
Cable entries/sealing plug 20 Accessories
KSE225 DP 2CMA142411R1000 11 Enclosed switch
KSE240 DP 2CMA142414R1000 11 Enclosed switch
KSE3100 TPN 2CMA144585R1000 12 Enclosed switch
KSE3160 2CMA144712R1000 13 Enclosed switch
KSE325 TPN 2CMA142412R1000 11 Enclosed switch
KSE3250 2CMA144713R1000 13 Enclosed switch
KSE3315 2CMA144714R1000 13 Enclosed switch
KSE340 TPN 2CMA142415R1000 11 Enclosed switch
KSE3500 2CMA144715R1000 13 Enclosed switch
KSE363 D/TPN 2CMA144581R1000 12 Enclosed switch
KSE363 TPN 2CMA144580R1000 12 Enclosed switch
KSE3630 2CMA144716R1000 13 Enclosed switch
KSE380 TPN 2CMA144583R1000 12 Enclosed switch
KSE425 TPSN 2CMA142413R1000 11 Enclosed switch
KSE440 TPSN 2CMA142416R1000 11 Enclosed switch
KSE463 TPSN 2CMA144582R1000 12 Enclosed switch
KSE480 TPSN 2CMA144584R1000 12 Enclosed switch
KSF225 DP 2CMA142435R1000 17 Fireman enclosed switch
Type Order number Page Discription
KSF325 NO/TPN 2CMA142442R1000 17 Fireman enclosed switch
KSF325 TPN 2CMA142436R1000 17 Fireman enclosed switch
KSF340 TPN 2CMA142438R1000 17 Fireman enclosed switch
KSF425 TPSN 2CMA142437R1000 17 Fireman enclosed switch
KSF440 TPSN 2CMA142439R1000 17 Fireman enclosed switch
L6 2CMA144539R1000 19 Shackle
LBAS125/S 2CMA144495R1000 16 Safety switch
LBAS125/SK 2CMA144496R1000 16 Safety switch
LBAS160/S 2CMA144198R1000 16 Safety switch
LBAS160/SK 2CMA144489R1000 16 Safety switch
LBAS200/S 2CMA144500R1000 16 Safety switch
LBAS250/S 2CMA144503R1000 16 Safety switch
LBAS316 TPN 2CMA142430R1000 15 Safety switch
LBAS325 TPN 2CMA142432R1000 15 Safety switch
LBAS336 M/TPN 2CMA144635R1000 15 Safety switch
LBAS363 M/TPN 2CMA144636R1000 15 Safety switch
LBAS400/S 2CMA144505R1000 16 Safety switch
LBAS416 TPSN 2CMA142431R1000 15 Safety switch
LBAS425 TPSN 2CMA142433R1000 15 Safety switch
LBAS630/S 2CMA144506R1000 16 Safety switch
MCB-01 1SFA611610R1010 19 Auxiliary contact
MCB-10 1SFA611610R1001 19 Auxiliary contact
OA1G01 2CMA144691R1000 19 Auxiliary contact
OA1G10 2CMA144690R1000 19 Auxiliary contact
OBEA01 2CMA144520R1000 19 Auxiliary contact
OBEA10 2CMA144519R1000 19 Auxiliary contact
OZXK1 2CMA144522R1000 19 Auxiliary contact
OZXK12 2CMA144521R1000 19 Auxiliary contact
TBE 3 2CMA144551R1000 18 Pressure switch
ABB ABCewe-ControlBox 1005, SE-611 29 Nyköping, SwedenTelephone +46 155 29 50 00Telefax +46 155 28 81 10http://www.abb.com/lowvoltage
Cat
alog
ue 2
CM
C34
1002
D00
02 J
anua
ry 2
009,
Rev
APr
od. A
BB
AB
, Cew
e-C
ontro
l/XM
Cop
yrig
ht ©
AB
B A
B