Installation Manual IM 1033-1

Group: Chiller

Part Number: 331499601

Effective: February 2010

Supersedes: November 2009

Magnitude™ Frictionless Centrifugal Chiller

Model WME

400 to 550 tons (1400 to 1900 kW)

3/60/460

R-134a

Page 2: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid

2 Magnitude Model WME Frictionless Centrifugal Chillers IM 1033

Table of Contents INTRODUCTION .................................................... 3

INSTALLATION ...................................................... 4

RECEIVING AND HANDLING ..................................... 4 LOCATION AND MOUNTING...................................... 4 LOCATION AND MOUNTING...................................... 5 SYSTEM WATER VOLUME ........................................ 6 WATER PIPING ......................................................... 8 SYSTEM PUMPS...................................................... 11 FIELD INSULATION GUIDE...................................... 11 RELIEF VALVES...................................................... 12

ELECTRICAL........................................................ 14

POWER WIRING ..................................................... 14

CONTROL WIRING.................................................. 14

DIMENSIONS......................................................... 16

WEIGHTS AND PHYSICAL DATA.................... 23

PRESTART SYSTEM CHECKLIST.................... 24

OPERATION .......................................................... 25

OPERATOR RESPONSIBILITIES ................................ 25 STANDBY POWER ................................................... 25 MICROTECH E CONTROL ................................... 25

Recognize Safety Symbols, Words, and Labels

The following symbols and labels are used throughout this manual to indicate immediate or potential hazards. It is the responsibility of the owner and installer to read and comply with all safety information and instructions accompanying these symbols. Failure to heed safety information increases the risk of property damage and/or product damage, serious personal injury or death. Improper installation, operation and maintenance can void the warranty.

CAUTION

Cautions indicate potentially hazardous situations, which can result in personal injury or equipment damage if not avoided.

WARNING

Warnings indicate potentially hazardous situations, which can result in property damage, severe personal injury, or death if not avoided.

DANGER

Dangers indicate a hazardous situation which will result in death or serious injury if not avoided.

Manufactured in an ISO certified facility

©2009 McQuay International. Illustrations and data cover the McQuay International product at the time of publication and we reserve the right to make changes in design and construction at anytime without notice. ™® The following are trademarks or registered trademarks of their respective companies: BACnet from ASHRAE; LONMARK, LonTalk, LONWORKS, and the LONMARK logo are managed, granted and used by LONMARK International under a license granted by Echelon Corporation; Compliant Scroll from Copeland Corporation; ElectroFin from AST ElectroFin Inc.; Modbus from Schneider Electric; Victaulic from Victaulic Company; Magnitude, Energy Analyzer, FanTrol, MicroTech E, Open Choices, and SpeedTrol from McQuay International.

Page 3: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid

IM 1033 Magnitude Model WME Frictionless Centrifugal Chillers 3

Introduction

General Description Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid chilling units. Each unit is completely assembled and factory tested before shipment. Model WME is cooling-only.

In the Magnitude Model WME, each unit has one compressor connected to a condenser and evaporator. The chillers use refrigerant R-134a to reduce the size and weight of the package compared to negative pressure refrigerants and since R-134a operates at a positive pressure over the entire operation range, no purge system is required.

The controls are pre-wired, adjusted and tested. Only normal field connections such as piping, electrical and interlocks, etc. are required, thereby simplifying installation and increasing reliability. Most necessary equipment protections and operating controls are factory-installed in the control panel.

The chillers are designed for indoor, non-freezing locations. If indoor freezing temperatures are possible, special procedures described in this manual must be followed to drain the unit. Outdoor locations require a special weatherproof design.

Application The procedures presented in this manual apply to standard Model WME chillers. Refer to the Operating Manual, OMM 1034 for detailed information about chiller operation and the MicroTech-E unit controller.

All McQuay centrifugal chillers are factory tested prior to shipment and must be initially started at the job site by a factory trained McQuay service technician. Failure to follow this startup procedure can affect the equipment warranty.

The standard limited warranty on this equipment covers parts that prove defective in material or workmanship. Specific details of this warranty can be found in the warranty statement furnished with the equipment.

Nomenclature

W M E 0500

W = Water-cooled

M = Magnetic Bearing

Vintage

Chiller Model, Nominal Tons

Page 4: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid

4 Magnitude Model WME Frictionless Centrifugal Chillers IM 1033

Installation

Receiving and Handling The unit should be inspected immediately after receipt for possible damage.

All McQuay centrifugal water chillers are shipped FOB factory and all claims for handling and shipping damage are the responsibility of the consignee.

Insulation corners from the evaporator's rigging hole locations are shipped loose and should be glued in place after the unit is finally placed. Neoprene vibration pads are also shipped loose. Check that these items have been delivered with the unit.

If so equipped, leave the shipping skid in place until the unit is in its final position. This will aid in handling the equipment.

Extreme care must be used when rigging the equipment to prevent damage to the control panels or refrigerant piping. See the certified dimension drawings included in the job submittal for the center of gravity of the unit. Consult the local McQuay sales office for assistance if the drawings are not available.

The unit can be lifted by fastening the rigging hooks to the four outside corners of the unit where the rigging eyes are located. Lengthwise and crossway spreader bars must be used between the rigging lines to prevent damage to the control panels, piping and especially the large Variable Frequency Drive (VFD) power panel located at one end of the unit.

Figure 1, Lifting Points

Lifting Points

Lifting Point

Lifting Point (Outside Corner Hidden)

VFD Power Panel

Power Cable Entry

Note: This drawing is for general reference only. Refer to dimension drawings for actual location of components.

Page 5: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid

IM 1033 Magnitude Model WME Frictionless Centrifugal Chillers 5

Location and Mounting The unit must be mounted on a level concrete or steel base and must be located to provide service clearance at one end of the unit for possible removal of evaporator tubes and/or condenser tubes. The length of the vessel should be allowed at one end for this purpose. Doors or removable wall sections can be utilized for tube clearance. Evaporator and condenser tubes are rolled into the tube sheets to permit replacement if necessary. Minimum clearance at all other points, including the top, is 3 feet (1 meter) unless greater clearance is required by other codes or job conditions. The National Electric Code (NEC) can require four feet or more clearance in and around electrical components and must be checked.

Operating Limits

Daikin McQuay Magnitude units are designed for indoor, non-freezing locations. Outdoor locations will require special design considerations.

Table 1: Operating Parameters

Leaving chilled water (ice duty not available) 38°F to 60°F

(3.3°C to 15°C)

Max. operating evaporator inlet fluid temperature 66°F (19°C)

Max. startup evaporator inlet fluid temperature 90°F (32°C)

Max. standby inlet fluid temperature 105°F (46°C)

Min. condenser water entering temperature See Figure 3,

page 6

Max. leaving condenser water temperature 105°F (46°C)

Vibration Pads The shipped-loose neoprene vibration pads should be located under the corners of the unit (unless the job specifications state otherwise). They are installed to be flush with the sides and outside edge of the feet. Most Model WME units have six mounting feet although only the outer four are required. Six pads are shipped and the installer can place pads under the middle feet if desired.

Mounting Make sure that the floor or structural support is adequate to support the full operating weight of the unit.

It is usually not necessary to bolt the unit to the mounting slab or framework; but should this be desirable, 1 1/8" (28.5 mm) mounting holes are provided in the unit support at the four corners.

Note: Units are shipped with refrigerant valves closed to isolate the refrigerant for shipment. Valves must remain closed until start-up by the McQuay technician.

Nameplates There are several identification nameplates on the chiller:

The unit nameplate is located on the side of the VFD panel. This plate also lists the unit refrigerant charge, electrical data and the unit model number and serial number, which should be used when communicating with McQuay.

Vessel nameplates are located on the evaporator and condenser. Along with other information, they have a National Board Number (NB) and serial number, either of which identifies the vessel (but not the entire unit).

A compressor nameplate is located on the compressor itself and contains identification numbers.

Page 6: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid

6 Magnitude Model WME Frictionless Centrifugal Chillers IM 1033

System Water Volume All chilled water systems need adequate time to recognize a load change, respond to that load change and stabilize, without undesirable short cycling of the compressors or loss of control. In air conditioning systems, the potential for short cycling usually exists when the building load falls below the minimum chiller plant capacity or on close-coupled systems with very small water volumes. Some of the things the designer should consider when looking at water volume are the minimum cooling load, the minimum chiller plant capacity during the low load period and the desired cycle time for the compressors. Assuming that there are no sudden load changes and that the chiller plant has reasonable turndown, a rule of thumb of “gallons of water volume equal to two to three times the chilled water gpm flow rate” is often used. A properly designed storage tank should be added if the system components do not provide sufficient water volume.

Figure 2, Unit Water Volumes

Evaporator Water Volume US Gallon (L)

Condenser Water Volume US Gallon (L)

E3612 191 (723) C3012 144 gal. (545 L) E3012 147 (555) C2612 111 gal. (419 L)

Condenser Water Temperature

Figure 3: MODEL WME Minimum Entering Condenser Water Temperature (EXV) (10F Range at Full Load)

30

35

40

45

50

55

60

65

0 10 20 30 40 50 60 70 80 90 100

Percent Load

ECWT (°F) 46°F LChWT

44°F LChWT

42°F LChWT

When the ambient wet bulb temperature is lower than design, the entering condenser water temperature of Magnitude model WME chillers can be lowered to improve chiller performance.

Chillers can start with entering condenser water temperatures as low as 40°F (4.4°C). For short periods of time during startup, the entering condenser water temperature can even be lower than the leaving chilled water temperature.

Magnitude model WME chillers are equipped with electronic expansion valves (EXV) and will run with entering condenser water temperatures as low as shown in Figure 3 or as calculated from the following equation on which the curves are based:

Min. ECWT = 5.25+(LWT)-0.75*DTFL*(PLD/100)+14 *(PLD/100)2 Where:

ECWT = Entering condenser water temperature LWT = Leaving chilled water temperature DTFL = Chilled Water Delta-T at full load PLD = The percent chiller load point to be checked

Page 7: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid

IM 1033 Magnitude Model WME Frictionless Centrifugal Chillers 7

For example; at 44°F LWT, 10°F Delta-T at full load, and 50% full load operation, the entering condenser water temperature could be as low as 49°F. This provides excellent operation with water-side economizer systems.

Depending on local climatic conditions, using the lowest possible entering condenser water temperature may be more costly in total system power consumed than the expected savings in chiller power would suggest, due to the excessive fan power required.

In this scenario, cooling tower fans would continue to operate at 100% capacity at low wet bulb temperatures. The trade-off between better chiller efficiency and fan power should be analyzed for best overall system efficiency. McQuay’s Energy Analyzer program can optimize the chiller/tower operation for specific buildings in specific locales.

Even with tower fan control, some form of water flow control, such as tower bypass, is recommended.

Figure 4 illustrate two temperature-actuated tower bypass arrangements. The “Cold Weather” scheme provides better startup under cold ambient air temperature conditions. The bypass valve and piping are indoors and thus warmer, allowing for warmer water to be immediately available to the condenser. The check valve may be required to prevent air at the pump inlet.

Figure 4, Bypass, Mild Weather Operation

Condenser water temperature control The standard MicroTech controller is capable of three stages of tower fan control plus an analog control of either a three-way tower-bypass valve or variable speed tower-fan motor. Stages are controlled from condenser-water temperature. The three-way valve can be controlled to a different water temperature or track the current tower stage. This allows optimum chilled water plant performance based upon specific job requirements.

Pumps The condenser water pump(s) must be cycled off when the last chiller of the system cycles off. This will keep cold condenser water from migrating refrigerant to the condenser. Cold liquid refrigerant in the condenser can make start-up difficult. In addition, turning off the condenser water pump(s) when the chillers are not operating will conserve energy.

Include thermometers and pressure gauges at the chiller inlet and outlet connections and install air vents at the high points of piping. Where noise and vibration are critical and the unit is mounted on spring isolators, flexible piping and conduit connections are necessary.

Variable Fluid Flow Rates and Tube Velocities Many chiller system control and energy optimization strategies require significant changes in evaporator and condenser water flow rates. The Magnitude model WME chiller line is particularly well suited to take full advantage of these energy saving opportunities provided that the maximum and minimum fluid flow rates are

Bypass, Cold Weather Operation

Page 8: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid

8 Magnitude Model WME Frictionless Centrifugal Chillers IM 1033

taken into consideration for a specific application. The sales engineer has the flexibility to use different combinations of shell size, number of tubes, and pass arrangements to select the optimum chiller for each specific application.

Both excessively high and excessively low fluid flow rates should be avoided. Excessively high fluid flow rates and correspondingly high tube velocities will result in high fluid pressure drops, high pumping power, and potentially tube corrosion and or tube corrosion damage. Excessively low fluid flow rates and correspondingly low velocities should also be avoided as they will result in poor heat transfer, high compressor power, sedimentation and tube fouling. Excessively high and low tube velocities can be particularly problematic and damaging in open loop systems.

Rates of Fluid Flow Change If it is decided to vary the evaporator water flow rate the rate of change should not exceed 50% per minute and should not exceed the minimum or maximum velocity limits as determined by the McQuay chiller software program.

Vibration Mounting The Magnitude model WME chillers are almost vibration-free. Consequently, floor mounted spring isolators are not usually required. Rubber mounting pads are shipped with each unit. It is wise to continue to use piping flexible connectors to reduce sound transmitted into the pipe and to allow for expansion and contraction.

System Water Volume All chilled water systems need adequate time to recognize a load change, respond to that load change and stabilize, without undesirable short cycling of the compressors or loss of control. In air conditioning systems, the potential for short cycling usually exists when the building load falls below the minimum chiller plant capacity or on close-coupled systems with very small water volumes.

Some of the things the designer should consider when looking at water volume are the minimum cooling load, the minimum chiller plant capacity during the low load period and the desired cycle time for the compressors.

Assuming that there are no sudden load changes and that the chiller plant has reasonable turndown, a rule of thumb of “gallons of water volume equal to two to three times the chilled water gpm flow rate” is often used.

A properly designed storage tank should be added if the system components do not provide sufficient water volume.

System Analysis Although we recommend analyzing the entire system, it is generally effective to place the chiller in the most efficient mode because it is a large energy consumer.

The McQuay Energy Analyzer program is an excellent tool to investigate the entire system efficiency, quickly and accurately. It is especially good at comparing different system types and operating parameters. Contact your local McQuay sales office for assistance on your particular application.

Water Piping Vessel Drains at Start-up

Unit vessels are drained of water in the factory and are shipped with the drain plugs in the heads removed and stored in the control panel or with open ball valves in the drain hole. Be sure to replace plugs or close the valves prior to filling the vessel with fluid.

Page 9: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid

IM 1033 Magnitude Model WME Frictionless Centrifugal Chillers 9

Evaporator and Condenser Water Piping

All evaporators and condensers come standard with Victaulic® AWWA C-606 groove nozzles (also suitable for welding), or optional flange connections. The installing contractor must provide matching mechanical connections or transitions of the size and type required.

! CAUTION

If welding is to be performed on the mechanical or flange connections, remove temperature sensors and thermal dispersion flow switch from the nozzles to prevent damage to those components. Also properly ground the unit or severe damage to the MicroTech E unit controller can occur.

Water pressure gauge connection taps and gauges must be provided in the field piping at the inlet and outlet connections of both vessels for measuring the water pressure drops. The pressure drops and flow rates for the various evaporators and condensers are job specific and the original job documentation can be consulted for this information.

Be sure that water inlet and outlet connections match certified drawings and stenciled nozzle markings. The condenser is connected with the coolest water entering at the bottom to maximize subcooling.

! CAUTION

When common piping is used for both heating and cooling modes, care must be taken to provide that water flowing through the evaporator cannot exceed 110°F which can cause the relief valve to discharge refrigerant or damage controls.

The piping must be supported to eliminate weight and strain on the fittings and connections. Piping must also be adequately insulated. A cleanable 20-mesh water strainer must be installed in both water inlet lines. Sufficient shutoff valves must be installed to permit draining the water from the evaporator or condenser without draining the complete system.

Victaulic® Couplings

Use the following steps when installing Victaulic couplings: 1. Check for smooth pipe between the pipe end and the groove. Remove any indentations, projections, or

weld seams. Failure to do this can result in a leaking joint. 2. Apply a thin coat of Victaulic or silicon lubricant to the gasket lips and exterior. 3. Position the gasket over the pipe end without overhanging the pipe. 4. Join the pipes together and slide the gasket into position, centering it between the groves. 5. Install the housing halves over the gasket, making sure that the housing’ keys engage the groves on

both pipes. 6. Install the bolts and thread the nuts on hand tight. Make sure that the oval heads of the bolts seat

properly in the bolt holes. 7. Tighten the nuts evenly by alternating sides until metal to metal contact is made on the housing bolt

pads. Make sure that the housing keys completely engage the pipe grooves.

Page 10: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid

10 Magnitude Model WME Frictionless Centrifugal Chillers IM 1033

Tower Filtering and Treatment Owners and operators must be aware that if the unit is operating with a cooling tower, cleaning and flushing the cooling tower is required. Make sure tower blow-down or bleed-off is operating. Atmospheric air contains many contaminants, which increases the need for water treatment.

! CAUTION

The use of untreated water will result in corrosion, erosion, slime buildup, scaling, or algae formation. Water treatment service must be used. McQuay International is not responsible for damage or faulty operation from untreated or improperly treated water.

Special care must be taken when utilizing open system water that is usually not treated (such as lakes, rivers, and ponds). Special tube and water head material may be required to reduce damage from corrosion.

Flow Switches Thermal dispersion flow switches are provided as standard. They are mounted in an evaporator and condenser water nozzle and factory wired.

An additional paddle-type flow switch can be installed in the vessel outlet piping as an added precaution to signal the presence of adequate water flow to the vessels before the unit can start. They also serve to shut down the unit in the event that water flow is interrupted to guard against evaporator freeze-up or excessive discharge pressure. They are not necessary for unit operation.

Figure 5, Unit-Mounted Flow Switch

Figure 6, Flow Switch Mounting

If flow switches, by themselves, are being used, electrical connections in the Unit Control Panel must be made per the field wiring diagram on page 15. The normally open contacts of the flow switch must be wired between the terminals. Flow switch contact quality must be suitable for 24 VAC, low current (16ma). Flow switch wire must be in separate conduit from any high voltage conductors (115 VAC and higher).

Figure 7, Flow Switch Flow Rates inch 1 1/4 1 1/2 2 2 1/2 3 4 5 6 8

Pipe Size (NOTE) mm 32 (2) 38 (2) 51 63 (3) 76 102 (4) 127 (4) 153 (4) 204 (5)

gpm 5.8 7.5 13.7 18.0 27.5 65.0 125.0 190.0 205.0 Flow

Lpm 1.3 1.7 3.1 4.1 6.2 14.8 28.4 43.2 46.6

gpm 3.7 5.0 9.5 12.5 19.0 50.0 101.0 158.0 170.0

Min. Adjst.

No Flow Lpm 0.8 1.1 2.2 2.8 4.3 11.4 22.9 35.9 38.6

gpm 13.3 19.2 29.0 34.5 53.0 128.0 245.0 375.0 415.0 Flow

Lpm 3.0 4.4 6.6 7.8 12.0 29.1 55.6 85.2 94.3

gpm 12.5 18.0 27.0 32.0 50.0 122.0 235.0 360.0 400.0

Max. Adjst.

No Flow Lpm 2.8 4.1 6.1 7.3 11.4 27.7 53.4 81.8 90.8

1. A segmented 3-inch paddle (1, 2, and 3 inches) is furnished mounted, plus a 6-inch paddle loose. 2. Flow rates for a 2-inch paddle trimmed to fit the pipe. 3. Flow rates for a 3-inch paddle trimmed to fit the pipe. 4. Flow rates for a 3-inch paddle. 5. Flow rates for a 6-inch paddle 6. There is no data for pipe sizes above 8-inch. A switch minimum setting should provide protection against no flow and close well before design flow is reached.

Flow direction marked on switch

I in. (25mm) NPT flow switch connection

Tee

Page 11: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid

IM 1033 Magnitude Model WME Frictionless Centrifugal Chillers 11

! CAUTION

Freeze Notice: Neither the evaporator nor the condenser is self-draining; Both must be blown out to help avoid damage from freezing.

The piping should also include thermometers at the inlet and outlet connections and air vents at the high points.

The water heads can be interchanged (end for end) so that the water connections can be made at either end of the unit. If this is done, new head gaskets must be used and control sensors relocated.

In cases where the water pump noise can be objectionable, vibration isolation sections are recommended at both the inlet and outlet of the pump. In most cases, it will not be necessary to provide vibration eliminator sections in the condenser inlet and outlet water lines. But they can be required where noise and vibration are critical.

System Pumps Operation of the chilled water pump can be to: 1. Cycle the pump with the compressor, 2. Operate continuously, or 3. Start automatically by a remote source.

The cooling tower pump must cycle with the chiller. The holding coil of the cooling tower pump motor starter must be rated at 115 volts, 60 Hz, with a maximum volt-amperage rating of 100. A control relay is required if the voltage-amperage rating is exceeded. See the Field Wiring Diagram or in the cover of control panel for proper connections.

All interlock contacts must be rated for no less than 10 inductive amps. The alarm circuit provided in the control center utilizes 115-volts AC. The alarm used must not draw more than 10 volt amperes.

Field Insulation Guide Factory insulation is an available option (0.75” or 1.5”). If field insulated, the following components should be insulated to prevent condensation on Magnitude model WME chillers.

Figure 8, Insulation Guide

Evaporator Evaporator Water Heads Expansion valve

Motor Cooling lines ( rotor) Suction Elbow VFD cooling return line

Stator cooling return line Evaporator Tube Sheet

Notes:

1. The discharge line can be insulated for sound reduction, as an option. 2. The compressor body does not require insulation. 3. Insulation quantities: E3612 = 129 sq.ft. (12 m2), E3012=115 sq ft. (11 m2)

Page 12: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid

12 Magnitude Model WME Frictionless Centrifugal Chillers IM 1033

Relief Valves

Figure 9: Typical Vent Piping

As a safety precaution and to meet code requirements, each chiller is equipped with pressure relief valves located on the condenser, evaporator, and oil sump vessel for the purpose of relieving excessive refrigerant pressure (caused by equipment malfunction, fire, etc.) to the atmosphere. Most codes require that relief valves be vented to the outside of a building, and this is a desirable practice for all installations. Relief piping connections to the relief valves must have flexible connectors.

Note: Remove plastic shipping plugs (if installed) from the inside of the valves prior to making pipe connections. Whenever vent piping is installed, the lines must be run in accordance with local code requirements; where local codes do not apply, the latest issue of ANSI/ASHRAE Standard 15 code recommendations must be followed.

Condensers have two relief valves as a set with a three-way valve separating the two valves (large condensers will have two such sets). One valve remains active at all times and the second valve acts as a standby.

Figure 10, Relief Valve Data

Model Relief Valve

Location Pressure Setting

Discharge Cap.

Conn. Size No. of Valves

Evaporator Top of

Evaporator 200 psi

75.5 lb air/min

1 in. FPT 1 WME

Condenser Top of

Condenser 200 psi

75.5 lb air/min

1 in. FPT 2

Figure 11, Condenser 3-Way Valve

Page 13: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid

IM 1033 Magnitude Model WME Frictionless Centrifugal Chillers 13

Refrigerant Vent Piping Twin relief valves mounted on a transfer valve are used on the condenser so that one relief valve can be shut off and removed, leaving the other in operation. Only one of the two is in operation at any time.

Vent piping is sized for only one valve of the set since only one can be in operation at a time. In no case would a combination of evaporator and condenser sizes require more refrigerant than the pumpdown capacity of the condenser. Condenser pumpdown capacities are based on the current ANSI/ASHRAE Standard 15 that recommends 90% full at 90°F (32C). To convert values to the older AHRI standard, multiply pumpdown capacity by 0.888.

Sizing Vent Piping (ASHRAE Method) Relief valve pipe sizing is based on the discharge capacity for the given evaporator or condenser and the length of piping to be run. Discharge capacity for R-134a vessels is calculated using a complicated equation that accounts for equivalent length of pipe, valve capacity, Moody friction factor, pipe ID, outlet pressure and back pressure. The formula, and tables derived from it, are contained in ASHRAE Standard 15-2001.

Using the ASHRAE formula and basing calculations on the 225 psi design yields a conservative pipe size, which is summarized in Figure 12. The table gives the pipe size required per relief valve. When valves are piped together, the common piping must follow the rules set out in the following paragraph on common piping.

Figure 12. Relief Valve Piping Sizes

Equivalent length (ft) 2.2 18.5 105.8 296.7 973.6 4117.4 Pipe Size inch (NPT) 1 1/4 1 1/2 2 2 1/2 3 4 Moody Factor 0.0209 0.0202 0.0190 0.0182 0.0173 0.0163

NOTE: A 1-inch pipe is too small for the flow from the valves. A pipe increaser must always be installed at the valve outlet.

Common Relief Valve Piping According to ASHRAE Standard 15, the pipe size cannot be less than the relief valve outlet size. The discharge from more than one relief valve can be run into a common header, the area of which cannot be less than the sum of the areas of the connected pipes. For further details, refer to ASHRAE Standard 15. The common header can be calculated by the formula:

DCommon D D Dn

1

222 2 0 5

.....

The above information is a guide only. Consult local codes and/or latest version of ASHRAE Standard 15 for sizing data.

Page 14: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid

14 Magnitude Model WME Frictionless Centrifugal Chillers IM 1033

Electrical

Wiring, fuse and wire size must be in accordance with the National Electric Code (NEC).

Important: Voltage unbalance not to exceed 2% with a resultant current unbalance of 6 to 10 times the voltage unbalance per NEMA MG-1, 1998 Standard. This is an important restriction that must be adhered to.

Power Wiring

CAUTION Qualified and licensed electricians must perform wiring. Shock hazard exists.

CAUTION

Connections to terminals must be made with copper lugs and copper wire.

Use only copper supply wires with ampacity based on 75°C conductor rating. (Exception: for equipment rated over 2000 volts, 90°C or 105°C rated conductors should be used).

The VFD nameplate will indicate the RLA setting required in the MicroTech-E controller. The RLA setting is for the VFD output amps not the input amps. Follow name plate values for output RLA.

Control Wiring The control circuit power on Magnitude model WME chillers is supplied by the unit-mounted VFD.

Figure 13, Unit Control Panel

.

External Control Wiring Entry (4)

External Control Terminal Strip

USB Ports (2)

Normal Shutdown Switch

Immediate Shutdown Switch

External Normal Shutdown Switch

Ethernet Port

Page 15: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid

IM 1033 Magnitude Model WME Frictionless Centrifugal Chillers 15

Figure 14, Field Control Wiring Diagram

Note: The above wiring connections are located on the I/O board in the control panel.

Page 16: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid

16 Magnitude Model WME Frictionless Centrifugal Chillers IM 1033

Dimensions

Figure 15: Model WME0500 - E3612/C3012 -2-pass, M2 standard motor (See page 20 for drawing notes)

170.4 EVAP. (UNIT OVERALL)4329

169.0 COND.4292

36.7

CONDRELIEF VALVES

933

67.5

EVAPRELIEF VALVE

1715

145.43694

5.3133

5.3133

UNITCTRL.BOX

M2VFD

EVAP

CONDENSER

FRONT VIEW

X

Y

4,6,7

4,6,74,6,7

3

3

16.8427

13.7348

6.2157

148.23764

4.0101

46.91192

LF

LB RB

RFX

Z

O.I.T.S.

3

3TOP VIEW

47.01195

68.51741

96.8

UNITO/A

2460

2.563

19.3489

60.5

VFDHEIGHT

1537

69.01753

77.0 UNIT O/A1956

13.8349

52.31327

RIGHT VIEW

4,9,11

Z

Y

4

6,7CONDENSER HEAD 2-PASS

VICTAULIC 150 PSI WATERSIDE

6,7EVAPORATOR HEAD 2-PASS

VICTAULIC 150 PSI WATERSIDE

This information is accurate at time of printing. McQuay reservesthe right to change design, specification and product data withoutnotice. Purchaser must determine that the equipment is fit andsufficient for the job specifications. No change to this data may bemade unless approved in writing by McQuay. McQuay's LimitedProduct Warranty applies to all McQuay equipment.

*R3327487020A3*WME500 - E3612RA C3012RA M2 150PSI W/S

77.01956

40.31023

25.4645

16.0406

7.2183

148.23764

TYP.Ø 1.13 [ 29]

MTNG. HOLE

25.5646

40.11019

92.82356

8.0TYP.203

5.1129

1.4TYP.

354.0

TYP.102

TOP VIEW

ENVELOPE OF UNIT

Z

X

12

M2VFD

UNIT CONT. BOX

4,12,134

MOUNTING FEET

9.8INLET

2489.8

OUTLET248

TYP.

Ø 12.0[305]NOM.

CL

CL16.0406

8.1OUTLET

207

8.1INLET

207

Ø 10.0[254]NOM.TYP.

CL

CL

16.0406

Page 17: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid

IM 1033 Magnitude Model WME Frictionless Centrifugal Chillers 17

Figure 16: Model WME0500 - E3612/C3012 - 2-pass, M3 (Low THD) motor (See page 20 for drawing notes)

60.0VFD

HEIGHT1523

96.3UNITO/A

2446

2.563

WME500 - E3612RA C3012RA M3 150PSI W/S*R3327488020A2*

170.4 EVAP. (UNIT OVERALL)4329

169.0 COND.4292

36.7COND

RELIEF VALVES

933

67.5EVAP

RELIEF VALVE

1715

145.43694

5.3133

5.3133

UNITCTRL.BOX

M3VFD

EVAP

CONDENSER

FRONT VIEW

X

Y

4,6,7

4,6,74,6,7

3

3

16.8427

13.7348

6.2157

148.23764

4.0101

46.91192

LF

LB RB

RFX

Z

O.I.T.S.

3

3 TOP VIEW

47.01195

68.51741

19.3489

69.01753

77.0 UNIT O/A1956

13.8349

52.31327

RIGHT VIEW

4,9,11

Z

Y

4

6,7CONDENSER HEAD 2-PASS

VICTAULIC 150 PSI WATERSIDE

6,7EVAPORATOR HEAD 2-PASS

VICTAULIC 150 PSI WATERSIDE

This information is accurate at time of printing. McQuay reservesthe right to change design, specification and product data withoutnotice. Purchaser must determine that the equipment is fit andsufficient for the job specifications. No change to this data may bemade unless approved in writing by McQuay. McQuay's LimitedProduct Warranty applies to all McQuay equipment.

MOUNTING FEET

77.01956

16.0406

7.2183

148.23764

TYP.Ø 1.13 [ 29]

MTNG. HOLE

40.11019

8.0TYP.203

5.1129

1.4TYP.

354.0

TYP.102

TOP VIEW

ENVELOPE OF UNIT

Z

X

12

UNIT CONT. BOX4

9.8INLET

2489.8

OUTLET248

TYP.

Ø 12.0[305]NOM.

CL

CL16.0406

8.1OUTLET

207

8.1INLET

207

Ø 10.0[254]NOM.TYP.

CL

CL

16.0406

30.1764

27.8707

54.01372

83.52122

M3VFD

4,12,13

Page 18: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid

18 Magnitude Model WME Frictionless Centrifugal Chillers IM 1033

Figure 17: Model WME0500 - E3012/C2612 -2-pass, M2 standard motor (See page 20 for drawing notes)

WME500 - E3012RA C2612RA M2 150PSI W/S2 3*R3327483020A2*

145.43694

5.3133

5.3133

32.7

CONDRELIEF VALVES

831

60.2

EVAPRELIEF VALVE

1530

169.0 EVAP. (UNIT OVERALL)4292

164.6 COND.4181

3

3

UNITCTRL.BOXEVAPORATOR

CONDENSER

FRONT VIEW

4,6,7

4,6,74,6,7

M2VFD

X

Y17.3438

42.81087

61.81568

58.0147366.01676

11.3286

44.31124

68.4

UNIT O/A1737

60.5

VFDHEIGHT

1537

2.563

92.9

UNITO/A

2359

RIGHT VIEW

4,9,11

4

Z

Y

16.8427

6.2157

13.7348

1.538

38.9989

148.23764

TOP VIEW

LF RF

RBLB

O.I.T.S.

X

Z

3

3

6,7

CONDENSER HEAD 2-PASSVICTAULIC 150 PSI WATERSIDE

6,7

EVAPORATOR HEAD 2-PASS VICTAULIC 150 PSI WATERSIDE

This information is accurate at time of printing. McQuay reservesthe right to change design, specification and product data withoutnotice. Purchaser must determine that the equipment is fit andsufficient for the job specifications. No change to this data may bemade unless approved in writing by McQuay. McQuay's LimitedProduct Warranty applies to all McQuay equipment.*R3327483020A3*

40.31023

25.4645

66.01676

7.218316.0

406

148.23764

21.0533

40.11019

92.72356

2.153

8.0

TYP.203

1.4

TYP.35

2.665

4.0

TYP.102

TOP VIEW

ENVELOPE OF UNIT12

M2VFD

Ø 1.13 [29]MTNG. HOLE

TYP.

UNIT CONT. BOX

MOUNTING FEET

X

Z

4,12,13

4

8.1

OUTLET207

8.1

INLET207

CL

CL

Ø 10.0[254]

NOM.TYP.

16.0406 7.1

OUTLET180

7.1

INLET180

Ø 8.0[203]

NOM.TYP.

CL

CL

13.0330

Page 19: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid

IM 1033 Magnitude Model WME Frictionless Centrifugal Chillers 19

Figure 18: Model WME0500 - E3012/C2612 - 2-pass, M3 (Low THD) motor (See page 20 for drawing notes)

92.3UNITO/A

2345

60.0VFD

HEIGHT1523

2.563

70.7UNIT O/A

1796

WME500 - E3012RA C2612RA M3 150PSI W/S*R3327484020A2*

145.43694

5.3133

5.3133

32.7COND

RELIEF VALVES

831

60.2EVAP

RELIEF VALVE

1530

169.0 EVAP. (UNIT OVERALL)4292

164.6 COND.4181

3

3

UNITCTRL.BOXEVAPORATOR

CONDENSER

FRONT VIEW

4,6,7

4,6,74,6,7

M3VFD

X

Y17.3438

42.81087

61.81568

58.0147366.01676

11.3286

44.31124

RIGHT VIEW

4,9,11

4

Z

Y

16.8427

6.2157

13.7348

1.538

38.9989

148.23764

TOP VIEW

LF RF

RBLB

O.I.T.S.

X

Z

3

3

6,7CONDENSER HEAD 2-PASS

VICTAULIC 150 PSI WATERSIDE

6,7EVAPORATOR HEAD 2-PASS

VICTAULIC 150 PSI WATERSIDE

This information is accurate at time of printing. McQuay reservesthe right to change design, specification and product data withoutnotice. Purchaser must determine that the equipment is fit andsufficient for the job specifications. No change to this data may bemade unless approved in writing by McQuay. McQuay's LimitedProduct Warranty applies to all McQuay equipment.

66.01676

7.218316.0

406

148.23764

40.11019

8.0TYP.203

1.4TYP.35

2.665

4.0TYP.102

TOP VIEW

ENVELOPE OF UNIT12 Ø 1.13 [29]

MTNG. HOLETYP.

UNIT CONT. BOX

MOUNTING FEET

X

Z

4

8.1OUTLET

2078.1

INLET207

CL

CL

Ø 10.0[254]NOM.TYP.

16.0406 7.1

OUTLET180

7.1INLET

180

Ø 8.0[203]NOM.TYP.

CL

CL

13.0330

23.4594

2.051

54.01372

30.1764

83.52122

M3VFD

4,12,13

Page 20: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid

20 Magnitude Model WME Frictionless Centrifugal Chillers IM 1033

Drawing Notes

1 All dimensions are in inches [millimeters] unless noted otherwise.

2 Final connections must allow for 0.5 inch +/- (12.7mm) manufacturing tolerances.

3 1.00-inch FPT [25.4 mm] evaporator and condenser relief valves must be piped per ANSI / ASHRAE 15. Number of relief valves is 1 per evaporator and 2 per condenser.

4 .375 inch [9 mm] suction nozzle relief valve must be piped per ANSI / ASHRAE 15.

5 Clearances:

• Allow a minimum of 3 ft. on all for sides and the top sides of chiller to allow for service access.

• Provide a minimum of 3 ft. clearance in front of chiller starter panel or according to NEC or local codes.

• Provide a minimum of 14 ft. clearance on one end of the chiller for tube removal.

6 Electric Panels- Most codes require 48 inches (1219 mm) clearance in front of control boxes and electrical panels. Check codes for your location.

7 3.25-inch [83mm] diameter lifting holes are provided. See installation manual IM 1033 (available on www.mcquay.com) for lifting instructions.

8 All water connections are given in standard U.S. pipe sizes. Standard connections are suitable for welding or victaulic couplings.

9 Unit shown has standard right-hand water connections. Left-hand connections are available for either vessel. For right hand evaporator the inlet and outlet nozzles are reversed. ANSI-flanged connections are available upon request. When using ANSI-flanged connections add 0.5 inch [13 mm] to each flanged end.

10 Dimensions shown are for units (evaporator / condenser) with standard design pressures. The waterside design pressure is 150 PSI {1034 kPa}. Consult the factory for unit dimensions with higher design pressures.

11 The unit vibration isolator pads are provided for field installation and when fully loaded are 0.250 inches [6 mm] thick.

12 These values are for units with standard wall thickness copper tubing only.

13 The shipping skid adds 4.00 inches [105 mm] to the overall unit height.

14 If main power wiring is brought up through the floor, this wiring must be outside the envelope of the unit.

15 The unit is shipped with an operating charge of refrigerant.

16 Optional marine water box connections are available upon request.

Table 4: WME 0500 Overall Dimensions (2-Pass with right-hand connections)

E36__ C30__ E30__ C26__ In. (mm)

3- 6- 3- 6-

Length 170 (4329) 170 (4329) 169 (4292) 169 (4292)

Width 78 (1985) 78 (1985) 70 (1785) 73 (1844)

Height 97 (2460) 95 (2446) 93 (2359) 92 (2345)

Page 21: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid

IM 1033 Magnitude Model WME Frictionless Centrifugal Chillers 21

Standard Head Connection Dimensions Figure 5: Standard Head Connection Dimensions (Victaulic and Flanged)

Figure 19: Standard Head Dimensions

1 PASS 2 PASS 3 PASS Return Head

Evaporator Diameter

AA BB AA BB FF GG AA BB FF UU

E30 14.00 16.00 10.75 16.00 8.13 16.00 6.625 16.00 10.19 9.78

E36 16.00 16.00 12.75 16.00 9.75 16.00 8.625 16.00 11.81 11.26

1 PASS 2 PASS 3 PASS Return Head

Condenser Diameter

AA BB AA BB FF GG AA BB FF UU

C30 14.00 16.00 10.75 16.00 8.13 16.00 6.625 16.00 10.19 9.78

C36 16.00 16.00 12.75 16.00 9.75 16.00 8.625 16.00 11.81 11.26

Page 22: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid

22 Magnitude Model WME Frictionless Centrifugal Chillers IM 1033

Marine Water Box Dimensions

Marine water boxes are an available option on all evaporator and condenser sizes. Caution: There is some nomenclature confusion in the industry. We refer to our standard dished heads as “dished heads”. Some manufacturers refer to them, or similar devices as “water boxes”. They are not “marine water boxes” with removable end covers as illustrated below.

Figure 20: Marine Water Box Dimensions with Victaulic or Flanged Connections

1 PASS 2 PASS 3 PASS Evap.

Dia. AAA BBB CCC DDD EEE AAA BBB CCC DDD EEE FFF GGG AAA BBB CCC DDD EEE FFF

E36 16.00 27.00 43.50 42.00 21.00 12.75 24.00 29.50 28.00 14.00 9.75 24.00 8.625 24.00 29.50 28.00 14.0

0 11.81

E30 14.00 21.00 27.75 26.50 13.25 10.75 21.00 27.75 26.50 13.25 8.13 21.00 6.625 21.00 27.75 26.50 13.2

5 10.19

1 PASS 2 PASS 3 PASS Cond.

Dia. AAA BBB CCC DDD EEE AAA BBB CCC DDD EEE FFF GGG AAA BBB CCC DDD EEE FFF

C30 14.00 21.00 27.75 26.50 13.25 10.75 21.00 27.75 26.50 13.25 8.13 21.00 6.625 21.00 27.75 26.5 13.2

5 10.14

C26 10.75 19.00 21.25 20.00 10.00 8.625 19.00 21.25 20.00 10.00 7.07 19.00 6.625 19.00 21.25 20.00 10.0

0 8.07

Notes: 1.Dimensions in inches. 2.Flanges are ANSI raised face. Mating flanges by others. 3.Some condensers with flanges can have staggered connections due to flange interference. Consult factory. 4.Flanges add 0.5 inches to the distance from the vertical centerline to the flange face compared to Victaulic.

Page 23: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid

IM 1033 Magnitude Model WME Frictionless Centrifugal Chillers 23

Weights and Physical Data

Lifting and Mounting Weights

Figure 21: Corner Identification

NOTES:

1 The block shown above is the mounting footprint, not the entire unit footprint.

2 Lifting holes in the top of the tube sheets are 3.25-inch (83 mm) diameter.

3 Mounting holes in the feet are 1.125-inch diameter.

Table 1:: Lifting and Mounting Weights

Lifting (Shipping) Weight, lbs (kg) Center of Gravity in. (mm) WME

Model Vessel Models

(Size) Motor Code LF RF LB RB Total X Y Z

0500 E3612/C3012 M2 4003

(1816) 4479

(2032) 3940

(1787) 4408

(1999) 16830 (7634)

76.8 (1951)

38.0 (964)

34.2 (869)

0500 E3012/C2612 M2 3130

(1420) 3626

(1645) 2997

(1359) 3471

(1575) 13224 (5998)

78.0 (1981)

36.1 (917)

28.4 (721)

0500 E3612/C3012 M3 4245

(1925) 5090

(2309) 3886

(1763) 4660

(2114) 17880 (8110)

79.3 (2014)

39.2 (996)

33.0 (838)

0500 E3012/C2612 M3 3389

(1537) 4272

(1938) 2925

(1327) 3687

(1673) 14274 (6475)

81.1 (2060)

37.5 (952)

26.9 (683)

Mounting (Operating) Weight, lbs (kg) Center of Gravity in. (mm) WME Model

Vessel Models (Size)

Motor Code LF RF LB RB Total X Y Z

0500 E3612/C3012 M2 4632

(2101) 5044

(2288) 4742

(2151) 5164

(2342) 19580 (8882)

75.8 (1925)

37.2 (946)

34.9 (886)

0500 E3012/C2612 M2 3556

(1613) 4001

(1815) 3520

(1597) 3959

(1796) 15036 (6820)

77.0 (1956)

35.4 (898)

28.8 (732)

0500 E3612/C3012 M3 4879

(2213) 5649

(2562) 4682

(2124) 5421

(2459) 20630 (9358)

78.0 (1981)

38.3 (974)

33.8 (859)

0500 E3012/C2612 M3 3821

(1733) 4641

(2105) 3443

(1562) 4181

(1897) 16086 (7297)

79.7 (2024)

36.7 (931)

27.5 (699)

NOTES:

1. See unit dimension drawing for lifting and mounting locations. 2. The block shown above is the mounting footprint, not the entire unit footprint. 3. Lifting holes in the top of the tube sheets are 3.25-inch (83 mm) diameter. 4. Mounting holes in the feet are 1.125-inch diameter.

Page 24: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid

24 Magnitude Model WME Frictionless Centrifugal Chillers IM 1033

Prestart System Checklist

Yes No N/A

Chilled Water Piping complete

Water system filled, vented ...........................................................

Pumps installed, (rotation checked), strainers cleaned..................

Controls (3-way, face and bypass dampers, bypass valves, etc.) operable

Water system operated and flow balanced to meet unit design requirements

Condenser Water (*)

Cooling tower flushed, filled and vented .....................................

Pumps installed, (rotation checked), strainers cleaned .................

Controls (3-way, bypass valves, etc.) operable ............................

Water system operated and flow balanced to meet unit requirements

Electrical

Power leads connected ..................................................................

Control interlock wiring complete and complies with specifications

Pump starters and interlock wired ................................................

Cooling tower fans and controls wired .........................................

Wiring complies with National Electrical Code and local codes .

Condenser pump starting relay (CWR) installed and wired .........

Miscellaneous

Relief valve piping complete ........................................................

Thermowells, thermometers, gauges, control wells, controls, etc., installed

Minimum system load of 80% of machine capacity available for testing and adjusting controls ...................................................................

Job Name/Location _______________________________________________________

McQuay Order Number__________________________

Date __________

Signature ________________________________

Note: This checklist must be completed and sent to the local McQuay service location two weeks prior to start-up.

Page 25: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid

IM 1033 Magnitude Model WME Frictionless Centrifugal Chillers 25

Operation

Operator Responsibilities It is important that the operator become familiar with the equipment and the system before attempting to operate the chiller. In addition to reading this manual, the operator should study operation manual OM 1034 available at www.mcquay.com and the control diagram furnished with the unit before starting, operating, or shutting it down.

During the initial startup of the chiller the McQuay technician will be available to answer any questions and instruct in the proper operating procedures.

It is recommended that the operator maintain an operating log for each individual chiller unit. In addition, a separate maintenance log should be kept of the periodic maintenance and servicing activities.

This McQuay centrifugal chiller represents a substantial investment and deserves the attention and care normally given to keep this equipment in good working order. If the operator encounters abnormal or unusual operating conditions, it is recommended that a McQuay service technician be consulted.

McQuay International conducts training for centrifugal operators at its factory Training Center in Staunton, Virginia, several times a year. These sessions are structured to provide basic classroom instruction and include hands-on operating and troubleshooting exercises. For further information, contact your McQuay representative.

Standby Power It is essential that any centrifugal chiller connected to standby power come to a complete stop on grid power and then be restarted with the standby power. Attempting to switch from regular grid line power to auxiliary power while the compressor is running can result in extreme transient torque that will severely damage the compressor.

MicroTech E Control Figure 22, MicroTech E Control Panel

All chillers are equipped with the McQuay MicroTech E control system consisting of:

Operator 15-inch color touchscreen interface panel (shown at the left).

Unit Control Panel containing the MicroTech E controller, USB interface and miscellaneous switches and field connection terminals.

Compressor Controller located in the compressor housing, containing the bearing controls and I/O points for the compressor.

VFD power panel containing various drive components and incoming power connections.

NOTE: Detailed information on the operation of the MicroTech E control is contained in OMM 1034.

Page 26: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid

26 Magnitude Model WME Frictionless Centrifugal Chillers IM 1033

Page 27: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid
Page 28: Magnitude™ Frictionless Centrifugal Chiller€¦ · Daikin McQuay Magnitude model WME frictionless centrifugal chillers are complete, self-contained, automatically controlled fluid

(800) 432-1342 www.mcquay.com IMM 1033 (02/10)

All McQuay equipment is sold pursuant to McQuay’s Standard Terms and Conditions of Sale and Limited Product Warranty. Consult your local McQuay Representative for warranty details. Refer to form 933-430285Y. To find your local representative, go to www.mcquay.com

This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.mcquay.com.