April 6, 2017 Mr. Chad Wiese Madison Metropolitan School District Building Services 4711 Pflaum Road Madison, WI 53718 Subject: Water Testing for Lead Sherman Middle/Shabazz City High School 1610 Ruskin St. Dear Mr. Wiese: As requested by the Madison Metropolitan School District (MMSD), TRC Environmental Corporation (TRC) performed testing for lead in water at Sherman Middle/Shabazz City High School. Testing Procedures Water testing was performed consistent with the United States Environmental Protection Agency’s (USEPA’s) guidance document “3Ts for Reducing Lead in Drinking Water in Schools: Revised Technical Guidance (USEPA 2006).” The 3Ts document suggests an action limit of 20 parts per billion (ppb) for lead, but MMSD has selected a more conservative action limit of 15 ppb. TRC collected samples from cold water outlets on the interior of the buildings, including: hallway drinking fountains, classroom drinking fountains, water bottle refill stations, kitchen food preparation sinks, Family and Consumer Education (FACE) classroom sinks, faculty lounge sinks, nurse’s office sinks, \\NTAPBMADISON\MSNVOL6\\WPMSN\PJT2\274235\0000\MADISON SD WATER TESTING REPORT.DOCX

Madison SD - Water Testing Report - Merged Letters for … for lead was performed using the EPA Method 200.8 (inductively‐coupled plasma with mass spectrometry) and achieved detection

Embed Size (px)

Citation preview

  • April 6, 2017

    Mr. Chad Wiese Madison Metropolitan School District Building Services 4711 Pflaum Road Madison, WI 53718

    Subject: Water Testing for Lead Sherman Middle/Shabazz City High School 1610 Ruskin St.

    Dear Mr. Wiese:

    As requested by the Madison Metropolitan School District (MMSD), TRC Environmental Corporation (TRC) performed testing for lead in water at Sherman Middle/Shabazz City High School.

    Testing Procedures Water testing was performed consistent with the United States Environmental Protection Agencys (USEPAs) guidance document 3Ts for Reducing Lead in Drinking Water in Schools: Revised Technical Guidance (USEPA 2006). The 3Ts document suggests an action limit of 20 parts per billion (ppb) for lead, but MMSD has selected a more conservative action limit of 15 ppb.

    TRC collected samples from cold water outlets on the interior of the buildings, including:

    hallway drinking fountains,

    classroom drinking fountains,

    water bottle refill stations,

    kitchen food preparation sinks,

    Family and Consumer Education (FACE) classroom sinks,

    faculty lounge sinks,

    nurses office sinks,

    \\NTAPBMADISON\MSNVOL6\\WPMSN\PJT2\274235\0000\MADISON SDWATER TESTING REPORT.DOCX

  • Madison Metropolitan School District Lead in Water Testing April 6, 2017 Sherman Middle/Shabazz City High School Page 2

    ice machines,

    taps nearest the incoming source water supply, and

    swimming pools.

    Preliminary sample locations were identified by maps provided by MMSD. Following completion of sampling, TRC prepared a map of each school annotated with the final sample locations and identification numbers for each outlet. See Appendix A: Location Map.

    Water sampling was conducted on March 22 & 25, 2017. During sample collection, each 250 mL bottle was marked with a school identification number (228) followed by the unique sample point identifier (e.g., 2281A, 2281B). Consistent with USEPA guidance, two samples were collected from each of the cold water outlets being tested. The first sample collected was the first draw sample (also called an A sample). The first draw sample is the first flow of water from the outlet into the bottle and represents the water standing in the fixture. The second flush sample (also called a B sample) was collected into a new sample bottle after the water had been allowed to continuously flow from the outlet for 30 seconds. The flush sample represents the water from the plumbing line behind the wall and outlet. Flush samples from refrigerated taps were sampled after 15 minutes of continuous flow (rather than 30 seconds) to account for water that resides in the cold water reservoir. At the tap nearest the incoming source water supply, only a single flush sample was collected. With assistance from MMSD and school staff, TRC attempted to collect samples after the tap was left unused for a period of 8 hours, but no longer than 18 hours, as recommended by the USEPA guidance. This required sampling in the early morning hours and over weekends. Upon completion of a sampling event, the sample bottles were packaged and shipped under proper chainofcustody to TestAmerica in Savannah, GA a Wisconsin NR 149 certified drinking water laboratory (certification #999819810).

    Analytical Method Analysis for lead was performed using the EPA Method 200.8 (inductivelycoupled plasma with mass spectrometry) and achieved detection limits of 1.0 ppb or less.

    Samples Collected and Analytical Results TRC assessed a total of 23 fixtures within this school. Fixtures that were broken or not in use were documented as such and not sampled.

    Of the 22 first draw samples collected from the school, 3 had results greater than or equal to the MMSD action level of 15 ppb for lead. At locations where the A sample lead results were 15 ppb or greater, the lab analyzed the corresponding B sample. Of the 3

    \\NTAPBMADISON\MSNVOL6\\WPMSN\PJT2\274235\0000\MADISON SDWATER TESTING REPORT.DOCX

  • Madison Metropolitan School District Lead in Water Testing April 6, 2017 Sherman Middle/Shabazz City High School Page 3

    B samples analyzed, 0 met or exceeded the 15 ppb action level. A table listing the analytical results by outlet sampled is included in Appendix B.

    Recommendations Although not required under the USEPA guidance, TRC agrees with MMSDs conservative decision to suspend the use of water at fixtures where the A sample result is 15 ppb or greater until that fixture has been repaired or replaced and retested. Once analysis of all lead water testing data from an individual building is complete, TRC can help devise a longterm operation and maintenance plan based on USEPA guidance.

    TRC appreciates the opportunity to assist MMSD with this project. If you have any questions or comments concerning this report, please call James at (608) 8263666.

    Sincerely,

    TRC Environmental Corporation

    James E. Wedekind, P.G. John B. Tweddale, P.G., CHMM Project Manager Principal Consultant

    cc: Mike MacDonald d

    \\NTAPBMADISON\MSNVOL6\\WPMSN\PJT2\274235\0000\MADISON SDWATER TESTING REPORT.DOCX

  • Appendix A

    Location Map

    \\NTAPBMADISON\MSNVOL6\\WPMSN\PJT2\274235\0000\MADISON SDWATER TESTING REPORT.DOCX

  • 100

    u 101

    U

    151A 104

    105B

    106

    D

    110 U

    162

    169

    U D

    D

    t

    135A S ni ks Ru

    WELL

    AREA

    U

    D

    U 119A

    119B

    D

    U

    139A

    139B

    160 171102A 156

    153 157

    155102

    154

    148103

    !!P !!P 152 150A 149228-1 152A228-2228 151160 3105 - 150

    152B

    !!P

    146

    168 147

    TT RR CC-- GG II

    SS LEGEND !! WATER SAMPLE LOCATIONP

    PlotDate

    : 4/4/20

    17,08:30

    :45AMby

    JPAPEZ

    --LAYOU

    T:ANSIB

    (11"x17")

    Coo

    rdinate

    System

    : 0NAD19

    83StateP

    laneWisc

    onsinSo

    uthFIPS

    4803Fee

    t(FootU

    S) Path

    : E:\M

    MSD\201

    7_274235

    \MMSD_

    FINAL.mx

    d Map

    Rotation

    :

    107 228-21

    145 105A 144105E 144F

    DC 144E !!P144D 144C

    144B 144A 140E 140D

    108 108A 120C109 120B

    120F 120A228-10 120

    120D 120E

    143 228-67

    140C 127 133B 133126 142228127A !!P

    !!P 111 113 120G 228-22

    !!P

    ELV.228-4 -141 !!P!!P 140B140 125 133A 134

    RAMP 163

    D228-5 U 140A

    NOTES 1. BASE MAP IMAGERY FROM DANE COUNTY, 2014.2. SCHOOL FACILITIES PLAN DRAWINGS SUPPLIED BYMMSD.3. SAMPLE LOCATIONS AND FEATURES SHOWN AREAPPROXIMATE.

    164B 121 130 130A166114 129A 131A124 135129B 131B122 167B129C 131C129 131128 129G 131F

    123 165

    !!P

    134A

    F E 132C129D 131D132A E 132B 228-9 116

    !!P 136B!!P167 228-8

    112 136

    132

    116A164A 137

    118

    %1 " = 40 ' 1:480165 119

    167A 138 138A

    132C 139

    PROJECT:

    MMSD WATER SAMPLING TITLE:

    PROJ NO.: 274235 CHECKED BY: A. SCHROEDER APPROVED BY: J. WEDEKIND DATE: APRIL 2017

    DRAWN BY:

    FILE NO.: MMSD_FINAL.mxd

    SHERMAN/SHABAZZ (228)FLOOR 1 SAMPLES J. PAPEZ

    FIGURE 1.A 708 Heartland Trail, Suite 3000Madison, WI 53717Phone: 608.826.3600www.trcsolutions.com

    http:www.trcsolutions.com

  • D

    251 D 261

    SEE ROOF PLAN

    201

    235A

    206 208

    210 D SEE ROOF PLAN

    232

    228

    SEE ROOF PLAN

    260

    D 230A

    253 D 229A

    U

    t n S i ks Ru

    D D

    U

    D

    241

    240200

    202 239

    238228-11 237202A!!P 250

    203 204 236

    235 259

    206B 205A

    205

    207

    234

    230A

    TT RR CC -- GGII SS LEGEND

    !! WATER SAMPLE LOCAT ONP IPlot

    Date:

    4/4/2017,

    08:30:45

    AM by J

    PAPEZ

    --LAYOU

    T: ANSI B

    (11"x17")

    Coo

    rdinate

    System

    : 0NAD 19

    83 StateP

    lane Wis

    consin So

    uth FIPS

    4803 Fee

    t (Foot U

    S) Path

    : E:\M

    MSD\201

    7_274235

    \MMSD_

    FINAL.mx

    d Map

    Rotatio

    n:

    233 209206A

    252

    228-13 231

    !!P!! 230P

    228-14 229

    258

    NOTES 1. BASE MAP IMAGERY FROM DANE COUNTY, 2014.2. SCHOOL FACILITIES PLAN DRAWINGS SUPPLIED BYMMSD.3. SAMPLE LOCATIONS AND FEATURES SHOWN AREAPPROXIMATE.

    !!P 228-12 227A212A 212B

    ABOVE LOCKER ROOM 227

    213 228-15 226A !!!!P212 P257 228-16

    228-20 226 228-18 219 !!P PP !!!!!! P216 228-17228-19

    255 225

    219A

    %1 " = 40 ' 1:480256

    217 218

    224

    257A 222 221

    220A 220 223

    PROJECT:

    MMSD WATER SAMPLING TITLE:

    257B PROJ NO.: 274235

    CHECKED BY: A. SCHROEDER APPROVED BY: J. WEDEKIND DATE: APRIL 2017

    DRAWN BY:

    FILE NO.: MMSD_FINAL.mxd

    SHERMAN/SHABAZZ (228)FLOOR 2 SAMPLES J. PAPEZ

    FIGURE 1.B 708 Heartland Trail, Suite 3000Madison, WI 53717Phone: 608.826.3600www.trcsolutions.com

    http:www.trcsolutions.com

  • Appendix B

    Analytical Results

    \\NTAPBMADISON\MSNVOL6\\WPMSN\PJT2\274235\0000\MADISON SDWATER TESTING REPORT.DOCX

  • Table 1 Summary of Lead Results Sherman/Shabazz - 228

    Madison, Wisconsin

    SAMPLE NUMBER FIXTURE TYPE SAMPLE DATE

    LEAD CONCENTRATION (ppb)

    228-1-A Water cooler 03/22/2017 0.97 228-3-A Faucet/sink 03/22/2017 23 228-3-B Faucet/sink 03/22/2017 3.2 228-4-A Service connection 03/22/2017 1.1 228-5-A Water cooler 03/22/2017 0.38 228-6-A Water cooler 03/22/2017 0.28 J 228-7-A Water cooler 03/22/2017 0.22 J 228-8-A Faucet/sink 03/22/2017 9.5 228-9-A Faucet/sink 03/22/2017 1.6 228-10-A Water cooler 03/22/2017 0.58 228-11-A Water cooler 03/22/2017 1.4 228-12-TAP1-A Water cooler 03/22/2017