Upload
santoshkumar
View
218
Download
0
Embed Size (px)
Citation preview
7/29/2019 M830 TechnicalSalesPublication En
1/12
MiCOM M830Disturbance Recorder
MiCOM M830
Disturbance Recorder
7/29/2019 M830 TechnicalSalesPublication En
2/122
Application and Scope
The MiCOM M830 device is a cost
effective disturbance recorder in
compact design. The M830
provides disturbance data recordingin medium- and high-voltage
systems. The systems can be solidly-
grounded, resistance grounded,
Petersen coil or insulated neutral
type.
The device has the following main
functions:
Definite-time overcurrent trigger,4 stages
Inverse-time overcurrent trigger,1 stage
Over-/undervoltage trigger
Limit value monitoring
Programmable scheme logic.
All main functions are individually
configurable and can be disabled
or enabled by the user as desired.
By means of a straight-forward
configuration procedure, the user
can adapt the device flexibly to the
scope required in each particular
application. Due to the powerful,
freely configurable logic of the
device, special applications can be
accommodated.
In addition to the features listed
above, as well as comprehensive
self-monitoring, the following
global functions are available in
the devices:
Parameter subset selection(4 alternative setting groups)
Operating data recording(time-tagged signal logging)
Disturbance recording(time-tagged signal recording
together with disturbance
recording of all measured
signals: phase currents, phase-to-
ground voltages and derived
residual current and neutral
displacement voltage.
The M830 is of compact design.
The boards are housed in a robust
aluminum case and electrically
connected via ribbon cables.
The nominal currents or the
nominal voltages, respectively, of
the measuring inputs can be set
with the help of function
parameters.
The nominal voltage range of the
optical coupler inputs is 24 to
250 V DC without internal
switching.
The auxiliary voltage input forthe power supply is a wide-range
design which can be internally
switched from a nominal voltage
range of 110 to 250 V DC (or 100
to 230 V AC) to 24 to 60 V DC. All
output relays are suitable for both
signal and trip duties.
MiCOM M830Disturbance Recorder
M830
TRIG1
TRIG3
TRIG2
Communication
Metering
Recording
Self Monitoring
I
V
LOGIC
LIMIT
Definite-time overcurrent trigger
Inverse-time overcurrent trigger
Over-/Undervoltage trigger
Limit Value Monitoring
Programmable Logic
TRIG1
TRIG2
TRIG3
LIMIT
LOGIC
Abreviations of Function Groups:
Figure 1: Functional overview
7/29/2019 M830 TechnicalSalesPublication En
3/123
Control and Display
Local control panel
17 LED indicators, 12 of whichallow freely configurable function
assignment
PC interface
Communication interfaces(optional)
IRIG-B time synchronization(optional).
Information exchange is via the
local control panel, the PC interface
and the optional communication
interfaces. Using this information
interface, the devices can be
integrated with substation control
systems or telecontrol systems. The
communication interface conformsalternatively to IEC 60870-5-103,
IEC 60870-5-101, DNP 3.0 or
Modbus.
Main Functions
Main functions are autonomous
function groups and can be
individually configured or disabled
to suit a particular application.
Function groups that are not
required and have been disabled by
the user are masked completely
(except for the configuration
parameter) and functional support
is withdrawn from such groups.
This concept permits an extensive
scope of functions and universal
application of the device in a single
design version, while at the same
time providing for a clear and
straight-forward setting procedure
and adaptation under
consideration.
Definite-Time Overcurrent
Trigger
A four-stage definite-time
overcurrent trigger (TRIG1) function
can be activated to start disturbance
recording.
Three separate measuring elements
are available for this purpose:
Maximum phase current
Negative-sequence current
Residual current
Inverse-Time Overcurrent
Trigger
The single-stage inverse-time
overcurrent trigger (TRIG2) function
operates with three separate
measuring elements:
Maximum phase current
Negative-sequence current Residual current
For the individual measuring
elements, the user can select from a
multitude of tripping characteristics
to trigger disturbance recording (see
table below).
Over-/Undervoltage Protection
The over-/undervoltage-time trigger
evaluates the fundamental of the
phase voltages and of the neutral
displacement voltage as well as the
positive-sequence voltage and
negative-sequence voltage obtained
from the fundamental of the three
phase-to-ground voltages. Two
definite-time-delay overvoltage
stages each are provided for
evaluation of the neutral
displacement voltage and negative-
sequence voltage. Two additional
definite-time-delay undervoltage
stages each are provided for
evaluation of the phase voltages
and the positive-sequence voltage.
Evaluation of the phase voltages
can be performed using either the
phase-to-phase voltages or the
phase-to-ground voltages as
desired. The neutral displacement
voltage is formed internally from the
three phase-to-ground voltages.
Limit Monitoring
A multitude of currents, voltages aremonitored to aid operation of the
power network. This function is not
intended to be used for any
protection purposes, as it has an
inherent 1 second delay.
E.g. for the 3-phase currents, the
Tripping Time Characteristics of Inverse-Time Overcurrent Trigger
7/29/2019 M830 TechnicalSalesPublication En
4/124
phase-to- ground voltages and the
phase-to- phase voltages the
highest and the lowest value is
determined. These are evaluated
using an operate value and time
delay set by the user. Thereby, these
currents and voltages can be
monitored for exceeding an upper
limit or falling below a lower limit.
Programmable Logic
User-configurable logic enables the
user to set up logic operations on
binary signals within a framework of
Boolean equations. By means of a
straightforward configuration
procedure, any of the signals of the
protection device can be linked by
logic OR or AND operations withthe possibility of additional negation
operations.
The output signal of an equation
can be fed into a further, higher-
order equation as an input signal
thus leading to a set of interlinked
Boolean equations.
The output signal of each equation
is fed to a separate timer stage with
two timer elements each and a
choice of operating modes. Thus
the output signal of each equation
can be assigned a freely
configurable time characteristic.
The two output signals of each
equation can be configured to each
available input signal after logic OR
linking. The user-configurable logic
function is then able to influence the
individual functions without external
wiring (block, reset, trigger, for
example).
Via non-storable continuous signals,
monostable trigger signals and
bistable stored setting/resetting
signals, the Boolean equations can
be controlled externally via any of
the devices interfaces.
Global Functions
Functions operating globally allow
the adaptation of the devicesinterfaces to the protected power
system, offer support during
commissioning and testing and
provide continuously updated
information on the operation, as
well as valuable analysis results
following events in the protected
system.
Clock Synchronization
The devices incorporate an internal
clock with a resolution of 1 ms. Allevents are time-tagged based on
this clock, entered in the recording
memory appropriate to their
significance and signaled via the
communication interface.
Alternatively two external
synchronization signals can be used
according to the selected
communication protocol: using one
of the protocols Modbus, DNP3,
IEC 60870-5-103, IEC 60870-5-101 the device will be synchronized
by a time telegram from a higher-
level substation control system or in
any other case it will be
synchronized using the IRIG-B signal
input. The internal clock will then be
adjusted accordingly and operate
with an accuracy of 10 ms if
synchronized via protocol and
1 ms if synchronized via IRIG-B
signal.
Parameter Subset Selection
The function parameters for setting
the protection functions are, to a
large extent, stored in four
independent parameter subsets.
Switching between these alternative
setting groups is readily achieved
via any of the devices interfaces.
Operating Data Recording
For the continuous recording of
processes in system operation or of
events, a non-volatile ring memory
entries is provided. The relevant
signals, each fully tagged with date
and time at signal start and signal
end, are entered in chronological
sequence. Included are control
actions such as the enabling or
disabling of functions as well as
local control triggering for testingand resetting. The onset and end of
events in the network, as far as
these represent a deviation from
normal operation (overload, ground
fault or short-circuit, for example)
are recorded.
Disturbance Recording
Disturbance recording comprises
event and disturbance recording
along with the stored faultmeasurands.
While a trigger condition persists in
the power system, the relevant
signals, each fully tagged with date
and time at signal start and signal
end, are entered into a non-volatile
memory in chronological sequence .
Furthermore, the sampled values of
all analog input variables such as
phase currents and phase-to-
ground voltages are recordedduring a fault.
Up to eight faults can be recorded.
If more than eight faults occur
without interim memory clearance
then the oldest fault recording is
overwritten.
Self-Monitoring
Comprehensive self-monitoringprocedures within the devicesensure that internal hardware or
software errors are detected and donot cause malfunctions of theprotective devices.
As the auxiliary voltage is turned on,
a functional test is carried out.
Cyclic self-monitoring tests are run
during operation. If test results
deviate from the default value then
the corresponding signal is entered
into the non-volatile monitoring
signal memory. The result of the
fault diagnosis determines whether
a blocking of the protection device
will occur or whether a warning only
is issued.
7/29/2019 M830 TechnicalSalesPublication En
5/125
Control
All data required for operation of
the disturbance recorder are
entered from the integrated local
control panel, and the data
important for system management
are read out there as well. The
following tasks can be handled via
the local control panel:
Readout and modification ofsettings
Readout of cyclically updatedmeasured operating data and
state signals
Readout of operating data logsand of monitoring signal logs
Resetting of the unit andtriggering of further control
functions designed to support
testing and commissioning tasks
The local control panel shown in
Figure 2 comprises the local control
elements and functions described
below.
Display
(1)The integrated local control
panel has a LCD displaywith4x20 alphanumeric characters.
17 LED indicators are provided forsignal display.
(2)5 LED indicators arepermanently assigned to signals.
(3)The remaining 12 LED
indicators are available for free
assignment by the user. Separate
adhesive labels are provided for
user-defined labeling of these
LED indicators according to the
chosen configuration.
Menu Tree
(4)By pressing the
cursor keys and
guided by the LCD display, the
user moves within a plain text
menu. All setting parameters
and measured variables as well
as all local control functions are
arranged in this menu which is
standardized for all devices of
the system. Changes to the
settings can be prepared and
confirmed by means of the
ENTER key which alsoserves to trigger local control
functions. In the event of
erroneous entries, exit from the
EDIT MODE with rejection of the
entries is possible at any time by
means of the CLEARkey C .
When the EDIT MODE is not
activated, pressing the CLEARkey has the effect of resetting the
indications. Pressing the READ
key G provides direct access toa preselected point in the menu.
Function keys
(5)4 function are available for free
assignment to any logical binary
input or control function. This
facilitates control, e.g. of manual
trip and close commands.
Type Label and PC Interface
(6)Type identification label with
information on the order
number, serial number and the
nominal electrical values.
(7)Dust covered (not shown here)
serial interface for connecting aPC.
Figure 2: Local control panel
Measured Value Panels
The configuration of the localcontrol panel allows the
installation of measured value
Panels on the LCD display. The
Panels are automatically
displayed for certain operation
conditions of the system. Priority
increases from normal operation
to operation under overload
conditions and finally to
operation following a short-
circuit in the system. Thedisturbance recorder thus
provides the measured value
data relevant for the prevailing
conditions.
Password Protection
Access barriers protect the entermode in order to guard against
inadvertent or unauthorized
changing of parameter settings
or triggering of control functions.
1
2
4
3
7
5
6
7/29/2019 M830 TechnicalSalesPublication En
6/126
Technical Data
General Data
DesignCase suitable for wall installation or flush-mountingfor control panels
Installation PositionVertical 30
Degree of ProtectionPer DIN VDE 0470 and EN 60529 or IEC 529.IP 51.
Weightapprox. 4 kg
DimensionsSee Dimensions
Terminal Connection DiagramsSee Connections
Terminals
PC InterfaceDIN 41652 connector (X6),type D-Sub, 9-pin.
Communication InterfaceOptical plastic fibers (X7 and X8):
F-SMA-interface per DIN 47258or IEC 874-2 per plastic fibersorBFOC-(ST)-interface 2.5 per DIN 47254-1or IEC 874-10 ger glass fiber
orLeads (X9, X10):Threaded terminal ends M2for wire cross-sections up to 1.5 mm
IRIG-B Interface (X11)BNC plug
All inputs and outputs (X1, X3)Threaded terminals for pin-terminal connection:
Threaded terminal ends M4,self-centering with wire protection forconductor cross sections of 0.5 to 6 mm2
or 2 x 2.5 mm
Creepage Distances and
ClearancesPer EN 61010-1 and IEC 664-1Pollution degree 3,working voltage 250 V,overvoltage category III,impulse test voltage 5 kV
Tests
Type TestTests according to EN 60255-6 or IEC 255-6
EMC
Interference SuppressionPer EN 55022 or IEC CISPR 22, Class A
1 MHz Burst Disturbance TestPer IEC 255 Part 22-1 or IEC 60255-22-1,
Class III,Common-mode test voltage: 2.5 kV,Differential test voltage: 1.0 kV,
Test duration: > 2 s, Source impedance: 200
Immunity to Electrostatic DischargePer EN 60255-22-2 or IEC 60255-22-2,Level 3,Contact discharge, single discharges: > 10,Holding time: > 5 s, Tes t voltage: 6 kV,
Test generator: 50 to 100 M, 150 pF / 330
Immunity to Radiated ElectromagneticEnergyPer EN 61000-4-3 and ENV 50204,Level 3,
Antenna distance to tested device:> 1 m on all sides,
Test field strength, frequ. band 80 to 1000 MHz:10 V/m,
Test using AM: 1 kHz / 80%,Single test at 900 MHz: AM 200 Hz / 100%
Electrical Fast Transient or BurstRequirementsPer IEC 60255-22-4,Test severity levels 4,Rise time of one pulse: 5 ns,Impulse duration (50% value): 50 ns,
Amplitude: 4 kV / 2 kV, resp.,Burst duration: 15 ms, Burst period: 300 ms,
Burst frequency: 2.5 kHz, Source impedance: 50
Surge Immunity TestPer EN 61000-4-5 or IEC 61000-4-5,
Level 4,Testing of power supply circuits,unsymmetrically/ symmetrically operated lines,Open-circuit voltage front time/
time to half-value: 1.2 / 50 s,Short-circuit current front time/
time to half-value: 8 / 20 s,Amplitude: 4 / 2 kV, Pulse frequency: > 5/min,
Source impedance: 12 / 42
Immunity to Conducted DisturbancesInduced by Radio Frequency FieldsPer EN 61000-4-6 or IEC 61000-4-6,Level 3,Disturbing test voltage: 10 V
Power Frequency Magnetic Field ImmunityPer EN 61000-4-8 or IEC 61000-4-8 ,
Level 4,Frequency: 50 Hz, Test field strength: 30 A/m
Alternating Component (Ripple) in DCAuxiliary Energizing QuantityPer IEC 255-11,12 %
Insulation
Voltage TestPer IEC 255-5 or EN 61010,2 kV AC, 60 sFor the voltage test of the power supply inputs,direct voltage (2.8 kV DC) must be used. The PCinterface must not be subjected to the voltage test.
Impulse Voltage Withstand TestPer IEC 255-5,Front time: 1.2 s, Time to half-value: 50 s,
Peak value: 5 kV, Source impedance: 500
Mechanical Robustness
Vibration TestPer EN 60255-21-1 or IEC 255-21-1,Test severity class 1,Frequency range in operation:
10 to 60 Hz, 0.035 mm, 60 to 150 Hz, 0.5 g,Frequency range during transport:
10 to 150 Hz, 1 g
Shock Response and Withstand Test,Bump Test
Per EN 60255-21-2 or IEC 255-21-2,Test severity class 1,
Acceleration: 5 g/15 g, Pulse duration: 11 ms
Seismic TestPer EN 60255-21-3 or IEC 255-21-3,Test procedure A, Class 1,Frequency range:
5 to 8 Hz, 3.5 mm / 1.5 mm8 to 35 Hz, 10/5 m/s2,
3 x 1 cycle
Routine TestTests per EN 60255-6 or IEC 255-6
Voltage TestPer IEC 255-5,
2.2 kV AC, 1 sFor the voltage test of the power supply inputs,direct voltage (2.8 kV DC) must be used. The PCinterface must not be subjected to the voltage test.
Additional Thermal Test100% controlled thermal endurance test, inputsloaded
Environmental ConditionsAmbient Temperature RangeRecommended temperature range:
-5C to +55C or +23F to +131FLimit temperature range:
-25C to +70C or -13F to +158F
Ambient Humidity Range 75 % relative humidity (annual mean),up to 56 days at 95% relative humidityand 40 C, condensation not permissible
Solar RadiationAvoid exposure of the front panel to direct solarradiation.
Ratings
Measurement InputsNominal frequencyfnom: 50 and 60 Hz (settable)
Operating range: 0.95 to 1.05 fnom
Current
Nominal current Inom: 1 and 5 A (settable)Nominal consumption per phase: < 0.1 VA at InomLoad rating:
continuous 4 Inom (20 A)
for 10 s: 30 Inom (150 A)
for 1 s: 100 Inom (500 A)
Nominal surge current: 250 Inom (1250 A)
VoltageNominal voltage Vnom: 50 to 130 V AC (settable)
Nominal consumption per phase:< 0.3 VA at Vnom = 130 V AC
Load rating: continuous 150 V AC
Binary Signal InputsNominal auxiliary voltage Vin,nom: 24 to 250 V DC
Operating range: 0.8 to 1.1 Vin,nom
with a residual ripple of up to 12% of Vin,nomPower consumption per input:
Vin = 19 to 110 V DC: 0.5 W 30%
Vin > 110 V DC: Vin x 5 mA 30%
7/29/2019 M830 TechnicalSalesPublication En
7/12
7/29/2019 M830 TechnicalSalesPublication En
8/128
Address List
Function ParametersGlobal Functions
PC link (PC):Command blocking: No/YesSig./meas.val.block.: No/Yes
Communication link (COMM1):
Command block. USER: No/YesSig./meas.block.USER: No/Yes
Binary output (OUTP):Outp.rel.block USER: No/Yes
Main function (MAIN):Device on-line: No (= off) /Yes (= on)Test mode USER: No/YesNominal frequ. fnom: 50 Hz/60 HzRotary field: Clockwise rotation/Anti-clockwise rot.Inom C.T. prim.: 1..10000 A
Vnom V.T. prim.: 0.1....1000.0 kVInom device: 1.0 A/5.0 A
Vnom V.T. sec.: 50...130 VConn. meas. circ. IP: Standard/OppositeMeas. value rel. IP: 0.000...0.200 InomMeas. value rel. V: 0.000...0.200 Vnom
Settl. t. IP,max,del: 0.1... 15.0...60.0 minFct.assign. block. 1: see selection tableFct.assign. block. 2: see selection tableFct. assign. fault: see selection table
Parameter subset selection (PSS):Control via USER: No/YesParam.subs.sel. USER:
Parameter subset 1Parameter subset 2Parameter subset 3Parameter subset 4
Keep time: 0.000...65.000 s /Blocked
Selfmonitoring (SFMON):Fct. assign. warning: see selection table
Fault recording (FT_RC):
Fct. assig. trigger: see selection tablePre-fault time: 1...50 periodsPost-fault time: 1...50 periodsMax. recording time: 5...300 periods
General Functions
Definite-time overcurrent trigger (TRIG1):Enabled USER: No/Yes
Inverse-time overcurrent trigger (TRIG2):Enabled USER: No/Yes
Over-/undervoltage trigger (TRIG3):Enable USER: No/Yes
Limit value monitoring (LIMIT):
Enabled USER: No/YesI>: / I>>: / I: / tI:/ V: / tV: / V: / tV: 0,010...1,000 Vnom/ BlockedtV>: /tV>>: 1...1000 s/ Blocked
Logic (LOGIC):Enabled USER: No/Yesvalid for y =1 ...8
Set 1 USER: No/Yesvalid for y = =1 ...32
Fct.assignm. outp. y: see selection tableOp. mode t output y:
Without timer stageOper./releas.delayOper.del./puls.dur.Op./rel.delay,retrigOp.del./puls.dur.,rtMinimum time
Time t1 output y: 0.00...600.00 sTime t2 output y: 0.00...600.00 sSig.assig. outp. y: see selection tableSig.assig.outp. y(t): see selection table
Parameter Subset(valid for parameter subsets x = 1 to 4)
Definite-time overcurrent trigger (TRIG1):Enable PSx: No/Yesvalid for y = > to >>>>:
I y PSx: 0,10...20,00 InomtI y PSx: 0,00...30,00 s/ BlockedIneg y PSx: 0,10...20,00 InomtIneg y: 0,00...30,00 s/ BlockedIN y: 0,10...20,00 InomtIN y: 0,00...30,00 s/ Blocked
Inverse-time overcurrent trigger (TRIG2):Enable PSx: No/Yesvalid for y = P or neg or N:
Iref,y PSx: 0.01...4.00 Inom /BlockedCharacteristic y PSx:
Definite TimeIEC Standard InverseIEC Very InverseIEC Extr. InverseIEC Long Time Inv.IEEE Moderately Inv.IEEE Very InverseIEEE Extremely Inv.
ANSI Normally Inv.ANSI Short Time Inv.ANSI Long Time Inv.
RI-Type InverseRXIDG-Type InverseFactor kt,y PSx: 0.05...10.00Release y PSx:
Without delay/Delayed as per char.
Over-/undervoltage trigger (TRIG3):Enable PSx: No/YesOperating mode PSx: Delta/StarEvaluation VNG PSx: Calculated/Measured
V> PSx: 0.20...1.50 Vnom(/3) / BlockedV>> PSx: 0.20...1.50 Vnom(/3) / BlockedtV> PSx: 0.00...100.00 s / BlockedtV> 3-pole PSx: 0.00...100.00 s / BlockedtV>> PSx: 0.00...100.00 s / Blocked
V< PSx: 0.20...1.50 Vnom(/3) / BlockedV> PSx: 0.20...1.50 Vnom/3 / BlockedtVpos> PSx: 0.00...100.00 s / BlockedtVpos>> PSx: 0.00...100.00 s / Blocked
Vpos< PSx: 0.20...1.50 Vnom/3 / BlockedVpos> PSx: 0.20...1.50 Vnom/3 / BlockedtVneg> PSx: 0.00...100.00 s / BlockedtVneg>> PSx: 0.00...100.00 s / Blocked
VNG> PSx: 0.02...1.00 Vnom(/3) / BlockedVNG>> PSx: 0.02...1.00 Vnom(/3) / BlockedtVNG> PSx: 0.00...100.00 s / Blocked
tVNG>> PSx: 0.00...100.00 s / BlockedtTransient PSx: 0.00...100.00 s / BlockedHyst. V meas. PSx: 1...10 %Hyst. V deduc. PSx: 1...10 %
Measured Operating DataMain Function (MAIN):Date: 01.01.1997...31.12.2096 dd.mm.yyTime of date: 00:00:00...23:59:59 hh:mm:ssTime switching: Standard time/Daylight saving timeFrequency f: 40.00...70.00 HzCurr. IP,max prim.: 0...25000 AIP,max prim.,delay: 0...25000 AIP,max prim.,stored: 0...25000 ACurr. IP,min prim.: 0...25000 ACurrent A prim.: 0...25000 ACurrent B prim.: 0...25000 A
Current C prim.: 0...25000 ACurrent (IP) prim.: 0...25000 A
Volt. VPG,max prim.: 0.0...2500.0 kVVolt. VPG,min prim.: 0.0...2500.0 kVVoltage A-G prim.: 0.0...2500.0 kVVoltage B-G prim.: 0.0...2500.0 kVVoltage C-G prim.: 0.0...2500.0 kV
Volt. VPG)/3 prim.: 0.0...2500.0 kVVolt. VPP,max prim.: 0.0...2500.0 kVVoltage VPP,min prim: 0.0...2500.0 kVVoltage A-B prim.: 0.0...2500.0 kVVoltage B-C prim.: 0.0...2500.0 kVVoltage C-A prim.: 0.0...2500.0 kVActive power P prim.: -999.9...1000.0 MWReac. power Q prim.: -999.9...1000.0 Mvar
Act.energy outp.prim: 0.00...650.00 MWhAct.energy inp. prim: 0.00...650.00 MWh
React.en. outp. prim: 0.00...650.00 Mvar hReact. en. inp. prim: 0.00...650.00 Mvar hCurrent IP,max p.u.: 0.000...25.000 InomIP,max p.u.,stored: 0.000...25.000 InomCurrent IP,min p.u.: 0.000...25.000 InomIP,max p.u.,delay: 0.000...25.000 InomCurrent A p.u.: 0.000...25.000 InomCurrent B p.u.: 0.000...25.000 InomCurrent C p.u.: 0.000...25.000 InomCurrent Ipos p.u.: 0.000...25.000 InomCurrent Ineg p.u.: 0.000...25.000 Inom
Current (IP) p.u.: 0.000...25.000 InomVoltage VPG,max p.u.: 0.000...25.000 VnomVoltage VPG,min p.u.: 0.000...25.000 VnomVoltage A-G p.u.: 0.000...25.000 VnomVoltage B-G p.u.: 0.000...25.000 VnomVoltage C-G p.u.: 0.000...25.000 VnomVoltage Vpos p.u.: 0.000...25.000 Vnom
Voltage Vneg p.u.: 0.000...25.000 VnomVolt. (VPG)/3 p.u.: 0.000...12.000 VnomVoltage VPP,max p.u.: 0.000...25.000 VnomVoltage VPP,min p.u.: 0.000...25.000 VnomVoltage A-B p.u.: 0.000...25.000 VnomVoltage B-C p.u.: 0.000...25.000 VnomVoltage C-A p.u.: 0.000...25.000 VnomActive power P p.u.: -7.500...7.500 SnomReac. power Q p.u.: -7.500...7.500 Snom
Active power factor: -1.000...1.000Load angle phi A: -180...180 Load angle phi B: -180...180 Load angle phi C: -180...180
Current I unfilt.: 0.000...25.000 Inom
7/29/2019 M830 TechnicalSalesPublication En
9/129
Dimensions
Surface-mounted case
Flush-mounted case with panel cutout
Figure 3: Dimensional drawings
7/29/2019 M830 TechnicalSalesPublication En
10/1210
Connections
Figure 4: Terminal connection diagramIncluding CT/VT standard connection example (application in MV system with isolated/compensated neutral)
Note : When using P1-P2 and S1-S2 identifications for the terminal polarity of CTs, the dot shown identifies the P1 and S1 terminals.
A
I> I> I>
B
C
X10
1
2
3
4
5
X7
1
X8
1
Output relays
X1
13
14
U100
VAux
(+)
(-)
PE
X1
9
10
1112
T5
T6
T7
U
V
WN
Voltage-measuring
inputs
X1
1
2
3
4
5
6
7
8
Current-measuring
inputs
T1
T2
T3
IA
IB
IC
Power supply
Vin
Vin
Signal inputs
U1
U2
X1
15
16
17
18
X3
35
36
32
33
34
29
30
31
27
28
22
26
25
24
23
19
20
21
X11
1
X6
2
3
5
Per order
IRIG-B
time synchronization
COMM2
wire link only
orwire link
X9
1
2
3
4
5
U17 X/Y
U18 X/Y
RS 485
U19
X//Y
D2[R]
D1[T]
RS 485
U20
X//Y
D2[R]
D1[T]
PC interface
RS 232
U16
X/Y
D1[T]D2[R]
E2[C]
COMM1
optical fiber link
K1
K2
K3
K4
K5
K6
K7
K8
M830
##
U21
7/29/2019 M830 TechnicalSalesPublication En
11/1211
Ordering Information
Variants Order No.
Disturbance Recorder M830 M830- 9 8 9 0 3 0 2 0 -401
in case with 36 terminalsfor surface-mounting or flush-mounting, including cover frame
Interfaces:
With communication interface -451 9 1
protocol: IEC 60870-5-103
With communication interface -456 9
only IRIG-B input for clock synchronization 0 0
protocol can be switched between: 2IEC 60870-5-101/-103, Modbus, DNP 3.0and IRIG-B input for clock synchronization(incl. interface COMM2 with fixed connection to wire, RS485, isolated)
for connection to wire, RS485, isolated 1for connection to plastic fiber, FSMA connector 2for connection to glass fiber, ST connector 4
Language:
English (German) (without order ext. no.)German (English) -801French (English) -802Spanish (English) -803
7/29/2019 M830 TechnicalSalesPublication En
12/12
TRANSMISSION & DISTRIBUTION Protection & Control, HQ, 60 Route de Sartrouville, BP58, F78230 Le Pecq Cedex. France
Tel: +33 (0) 134 80 79 00 Fax: +33 (0) 134 80 79 13 Email: [email protected] Internet: www.tde.alstom.com
2000 ALSTOM. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM.Other names mentioned, registered or not, are the property of their respective companies.
Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure shouldonly be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it.
We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.