Hot runner temperature controller1/16 DIN - 48 x 48
M2 line ccU s e r m a n u a l • M . I . U . M 2 - 2 / 0 3 . 0 1 • C o d . J 3 0 - 4 7 8 - 1 A M 2 I E
ASCON spa20021 Bollate(Milan) Italyvia Falzarego, 9/11Tel. +39 02 333 371 Fax +39 02 350 4243http://www.ascon.ite-mail [email protected]
ASCON spa
ISO 9001C e r t i f i e d
ULC US
LISTED
Hot runner temperature controller1/16 DIN - 48 x 48
M2 line cc
274.8275.0
123
2
MANSP2REM
ULC US
LISTED
2
Information
ccNOTES
ON ELECTRIC
SAFETY AND
ELECTROMAGNETIC
COMPATIBILITY.
Please, read carefully these instructions before proceeding withthe installation of the controller.Class II instrument, rear panel mounting.
This controller has been designed with compliance to:Regulations on electrical apparatus (appliance, systems and installa-tions) according to the European Community directive 73/23/EEC amend-ed by the European Comunity directive 93/68/EEC and the Regulationson the essential protection requirements in electrical apparatus EN61010-1 : 93 + A2:95.
Regulations on Electromagnetic Compatibility according to theEuropean Community directive n089/336/EEC, amended by the EuropeanCommunity directive n° 92/31/EEC, 93/68/EEC, 98/13/EECand the following regulations:Regulations on RF emissionsEN61000-6-3 : 2001 residential environmentsEN61000-6-4 : 2001 industrial environmentsRegulation on RF immunity EN61000-6-2 : 2001 industrial equipment and system
It is important to understand that it’s responsibility of the installer to ensurethe compliance of the regulations on safety requirements and EMC.This device has no user serviceable parts and requires special equipmentand specialised engineers. Therefore, a repair can be hardly carried ondirectly by the user. For this purpose, the manufacturer provides techni-cal assistance and the repair service for its Customers. Please, contact your nearest Agent for further information.All the information and warnings about safety and electromagneticcompatibility are marked with the B sign, at the side of the note.
3
Table of contents
1 INSTALLATION .............................................................................................................................Page 42 ELECTRICAL CONNECTIONS.......................................................................................Page 83 PRODUCT CODING ................................................................................................................Page 164 OPERATIONS................................................................................................................................Page 205 AUTOMATIC TUNING ..........................................................................................................Page 386 SPECIAL FUNCTIONS ........................................................................................................Page 407 TECHNICAL SPECIFICATIONS.....................................................................................Page 45
TABLE OF CONTENTS
Main universal input
Control Alarms
Resources
OP1PV
AUX OP2
Setpoint
OP3
Operating mode
2 Single OP2 OP1 OP3action
3 Double OP1 OP3 OP2action
4 Double OP1 OP2 OP3action
5 Double OP2 OP3 OP1action
1 Single OP1 OP2 OP3action
M2
Fuzzy tuning with automatic selection
One shotAuto tuning
One shotNatural Frequency
Special functions
Auxiliary input (option)
Digital input (option)IL
IL connected functions
Continuous tuning
Adaptive
(option)
(option)
4
1 - Installation
1 INSTALLATION
Installation must only be carriedout by qualified personnel.
Before proceeding with the instal-lation of this controller, follow theinstructions illustrated in this man-ual and, particularly the installationprecautions marked with the Bsymbol, related to the EuropeanCommunity directive on electricalprotection and electromagneticcompatibility.
BTo prevent hands or metal touch-ing parts that may be electricallylive, the controllers must beinstalled in an enclosure and/orin a cubicle.
1.1 GENERAL DESCRIPTION
IP 20 Terminal BlockEN61010 - 1 (IEC1010 - 1)
Product code label
Sealing front panel gasket
Mounting clamps
Panel surface
Front panelIP65 protection
EN 650529 (IEC 529)
5
1 - Installation
1.2 DIMENSIONAL DETAILS
48 mm1.89 in
120 mm4.72 in
48 mm1.89 in
20 mm max0.79 in max
1.3 PANEL CUT-OUT
65 mm min2.56 in min
45+0.6 mm1.78+0.023 in
45+
0.6
mm
1.78
+0.
023
in
65 m
m m
in2.
56 i
n m
in
6
1 - Installation
Special conditions
M Altitude > 2000 m
T Temperature >50°C
%Rh Humidity > 95 %
P Conducting atmosphere Use filter
Warm up
Use forced air ventilation
Use 24V~ supply version
Suggestions
Forbidden Conditions D
C Corrosive atmosphere
E Explosive atmosphere
Operating conditions
M Altitude up to 2000 m
T Temperature 0… 50°C
%Rh Relative humidity 5… 95 % non-condensing
1.4 ENVIRONMENTAL RATINGS B
7
1 - Installation
1.5.1 INSERT THE INSTRUMENT
1 Prepare panel cut-out2 Check front panel gasket posi-
tion3 Insert the instrument through
the cut-out
UL note
[1] For Use on a Flat Surface ofa Type 2 and Type 3 ‘raintight’Enclosure.
1.5.2 INSTALLATION SECURING
1 Fit the mounting clamps2 Push the mounting clamps
towards the panel surface tosecure the instrument
1
3
2
1.5.3 CLAMPS REMOVING
1 Insert the screwdriver in the clipsof the clamps
2 Rotate the screwdriver
1
2
1.5.4 INSTRUMENT UNPLUGGING B
1 Push and 2 pull to remove the instrument
Electrostatic discharges can dam-age the instrumentBefore removing the instrument the
operator mustdischarge himselfto ground
1
2
1
1MΩ
1.5 PANEL MOUNTING [1]
1
1
2
8
2 - Electrical connections
2 ELECTRICALCONNECTIONS
UL note[1] Use 60/70 °C copper (Cu) con-
ductor only.
2.1 TERMINATION UNIT [1] B
16 screw terminals
Option terminals
Holding screw 0.5 Nm
Pin connectorq 1.4 mm0.055 in max
ØFork-shapeAMP 165004Ø 5.5 mm - 0.21 in
Stripped wireL 5.5 mm - 0.21 in
Terminals
L
0,5Nm
6
5
4
3
2
1
12
11
10
9
16
15
18
17
14
13
Positive screwdriver PH1Negative screwdriver 0,8 x 4 mm
6
5
4
3 9
2
1
12
11
10
18
17
16
15
14
13
RTD
N
L
B
TAO
P3NO
C
OP
2-RNO
C
NO
COP
1
OP
2-L
bTC
mA mV
A
11
9 LOGICINPUT
Rear terminal
cover
5.7 mm0.22 in
Wire size1 mm2 (18 AWGSolid/Stranded)
9
2 - Electrical connections
PRECAUTIONS B
Despite the fact that the instrumenthas been designed to work in anharsh and noisy environmental(level IV of the industrial standardIEC 801-4), it is recommended tofollow the following suggestions.
AAll the wiring must comply with thelocal regulations.
The supply wiring should be rout-ed away from the power cables.Avoid to use electromagnetic con-tactors, power Relays and highpower motors nearby.Avoid power units nearby, espe-cially if controlled in phase angle
Keep the low level sensor inputwires away from the power linesand the output cables.If this is not achievable, use shield-ed cables on the sensor input, withthe shield connected to earth.
2.2 PRECAUTIONS AND ADVISED CONDUCTOR COURSE B
BB
6
5
4
3
2
1
12
11
10
9
L
N
C D
16
15
B B
6
5
4
3
2
1
12
11
10
9
L
N
C D
16
15
B
18
17
14
13
18
17
14
13
C C
A A
A = SupplyB = OutputsC = Analog
inputsD = Logic
input/output
Conduit for supply and output cables
Conduit for low level sensor cables
10
2 - Electrical connections
2.3 EXAMPLE OF WIRING DIAGRAM (HEAT COOL CONTROL) B
Fuse[5]
6
Power supply
CT Current transformer 50 mA
Fuse[5]
Powersupplyswitch
OP2
OP1
V~
PTC [4]
5
4
3
2
1
12
11
10
9[6]
16
15Fuse 2A~T
[6]
Alarm
V~OP2
18
17
14
13OP3 [6]
V~
TC
HeatingV~
V~Cooling
[3]
Notes:1] Make sure that the power supply
voltage is the same indicated onthe instrument.
2] Switch on the power supply onlyafter that all the electrical con-nections have been completed.
3] In accordance with the safety reg-ulations, the power supply switchshall bring the identification of therelevant instrument. The powersupply switch shall be easilyaccessible from the operator.
4] The instrument is is PTC pro-tected. In case of failure it is sug-gested to return the instrument tothe manufacturer for repair.
5] To protect the instrument internalcircuits use:- 2 A~ T fuses for Relay outputs
6] Relay contacts are already pro-tected with varistors.Only in case of 24 V ~ induc-tive loads, use model A51-065-30D7 varistors (on request)
11
2 - Electrical connections
2.3.1 POWER SUPPLY B
Switching power supply with mul-tiple isolation and internal PTC• Standard version:
nominal voltage:100 - 240V~ (- 15% + 10%)Frequency 50/60Hz
• Low Voltage version:Nominal voltage: 24V~ (- 25% + 12%)Frequency 50/60Hz or 24V– (- 15% + 25%)
• Power consumption 3VA max
L
N
1
2
Included PTC
Supply
2.3.2 PV CONTROL INPUT B
A For L-J-K-S-T thermocouple type• Connect the wires with the
polarity as shown• Use always compensation cable
of the correct type for the ther-mocouple used
• The shield, if present, must beconnected to a proper earth.
B For Pt100 resistance thermometer
• If a 3 wires system is used, usealways cables of the same diam-eter (1mm2 min.) (line 20 Ω/leadmaximum resistance)
• When using a 2 wires system, usealways cables of the same diam-eter (1,5mm2 min.) and put ajumper between terminals 5 and 6
C For ∆T (2x RTD Pt100) SpecialAWhen the distance between
the controller and the sensoris 15 mt. using a cable of 1.5mm2 diameter, produces anerror on the measure of 1°C(1°F).
R1 + R2 must be <320Ω
Wire resistance150Ω max
For 3 wires onlyMaximumresistance/line 20Ω
Use wires of thesame length and1.5 mm2 size.Maximumresistance/line 20Ω
5
6
12
A
B
A
R1
R2
5
6
12
B
b
A
5
6
12
2 - Electrical connections
D For mA, mV
Rj >10MΩ
mV mA5
6External
Shunt 2.5Ω
2.3.2 PV CONTROL INPUTB
2.3.3 AUXILIARY INPUT (option) B
For current transformer CTNot isolatedFor the measure of the load cur-rent (see page 34)
• Primary coil10A…100A• Secondary coil 50mA default
100mA jumper selectable
18
17
10…100A50/100mA
loadCT
~
5 watt burden resistor0.5Ω for 1A secondarytransformer coil0.1Ω for 5A secondarytransformer coil
Jumper for 100 mA
secondary transformer coil
2.3.4 DIGITAL INPUT (option) (page 35) B
• The input is active when thelogic state is ON, correspond-ing to the contact closed
• The input is inactive when thelogic state is OFF, correspond-ing to the contact open
11
10
9
TTLopen
collector
NPNopen collector
IsolatedcontactCom.
IL 1 C1
• To use with APG2-DRSPCboard, see page 40.
13
2 - Electrical connections
2.3.5 OP1 - OP2 - OP3 OUTPUTS B
The functionality associated to each of the OP1, OP2 and OP3 input is definedduring the configuration of the instrument index l(see page 18).The suggested combinations are:
OP2 output can be Relay (Std) orlogic (option).The “jumper” on the auxiliaryboard selects the output type:
Link Pins 1-2 for OP2-RelayLink Pins 2-3 for OP2-Logic
Note[1] With heat / cool control AL2 and AL3 share in or mode the same output
(the free one).
12
3
Jumper
Auxiliaryboard
AlarmsAL2
OP1Heat OP2-R OP3
OP2-LHeat OP1 OP3
OP1Heat
OP3Cool
OP2-R[1]
OP1Heat
OP2-LCool
OP3[1]
OP2-LHeat
OP3Cool
OP1[1]
AL3
Doubleaction
Doubleaction
Doubleaction
Singleaction
Singleaction
Control outputs
E
D
C
B
A
OP1 - OP3
OP2 - R
Relay output
Relay outputOP2 - L Logic output
Heatload
Staticrelay
10
11
OP2
14
2 - Electrical connections
Relay output• SPST Relay N.O., 2A/250 V~
for resistive load, fuse 2A ~ T
Logic output not isolated • 0…5V–, ±20%, 30 mA max
2.3.5-A SINGLE ACTION RELAY (TRIAC) CONTROL OUTPUT B
2.3.5-B SINGLE ACTIONLOGIC CONTROL OUTPUT B
2.3.5-C DOUBLE ACTION RELAY/RELAY CONTROL OUTPUT B
2.3.5-D DOUBLE ACTION RELAY/LOGIC CONTROL OUTPUT B
2.3.5-E DOUBLE ACTION LOGIC/RELAY CONTROL OUTPUT B
LoadStaticrelay
10
11
OP2
Fuse
Coil of theheat loadcontactor
3
4OP1
Fuse
Coil of theheat loadcontactor
3
4OP1
Fuse
Coil of theheat loadcontactor
3
4OP1
Fuse
Coil of thecool loadcontactor
13
14OP3
Fuse
Coil of thecool loadcontactor
13
14OP3
Coolload
Staticrelay
10
11
OP2
Varistor forinductive load24V~ only
Varistor forinductive load24V~ only
Varistor forinductive load24V~ only
Varistor forinductive load24V~ only
15
2 - Electrical connections
2.3.6 ALARMS OUTPUTSB
Fuse
Coil of theload alarm contactor
3
4OP1
Fuse
Coil of theload alarm contactor
15
16OP2
Fuse
Coil of theload alarm contactor
13
14OP3
e The outputs OP1, OP2 (Relayoptional) and OP3, can be usedas alarm outputs only if they arenot configured as control outputs.
Varistor for inductive load24V~ only
16
3 - Product coding
3 PRODUCT CODING
The complete code is shown onthe instrument label. The informa-tions about product coding areaccessible from the front panel bymean of a particular proceduredescribed at section 4.2.2 page 21
L
C D
M N
B
P/NCONFS/NV~(L-N).100÷240V 50/60 Hz - 2,6W
: M2-3600-0000: 2002: A0A-9909/0013
3600Hard
123
2
MANSP2REM
Basic product code (hardware)
Instrument Label
Configuration code (software)
17
3 - Product coding
3.1 MODEL CODE
The product code indicates the specific hardware configuration of the instrument, that can be modified, byspecialized engineers only.
Line Basic Accessories Configur.
M 2 A B C D - E F G 0 / I L M NModel:
Power supply A100 - 240V~ (- 15% + 10%) 324V~ (- 25% + 12%) or 24V– (- 15% + 25%) 5
Line 2M
Front panel colour GDark (std) 0Beige 1
User manual FItalian/English (std) 0French/English 1German/English 2Spanish/English 3
Only Logic 6
OP2 Outputs BRelay and Logic 1
CT [1]
Digital input DOptions
Not fitted 0None
9 3Fitted 0None
C0
93Current transformer input (CT) [1] 0
Digital remote setpoint control + Safety average OP on sensor break 8Safety average OP on sensor break 7
Special functions ENot fitted 0SP Raise/Lower by digital input 6
[1] Only for B=1
18
3 - Product coding
3.2 CONFIGURATION CODING
The configuration code consists of4 digits that identify the operat-ing characteristic of the controller,as chosen by the user.Section 4.6 at page 35 reports theinstructions how to set a new con-figuration code.
The configuration code can be dis-played on the front panel, follow-ing the instructions at page 21 sec-tion 4.2.2.
I L M N
Conf2002
Input type and range ITR Pt100 IEC751 0TR Pt100 IEC751 1TC L Fe-Const DIN43710 2TC J Fe-Cu45% Ni IEC584 3TC T Cu-CuNi 4TC K Cromel -Alumel IEC584 5TC S Pt10%Rh-Pt IEC584 6DC input 0…50 mV, linear 7DC input 10…50 mV, linear 8Custom input and range [1] 9
-328…752 °F32…2192 °F32…2912 °F
-99.9…572.0 °F-328…1112 °F32…1112 °F32…1112 °F
-200 …400 °C0…1200 °C0…1600 °CEngineering units
-99.9…300.0 °C
Engineering units
-200…600 °C0…600 °C0…600 °C
Control action type MReverse (single action)Direct (single action)
0Linear Cool (Heat/Cool double action)1On-Off Cool (Heat/Cool double action)
Heat/Cool action
67
Control mode Output configuration [1] L
Control OP1- OP3 / alarm AL2 on OP2
PID 0
Control OP1- OP2 / alarm AL2 on OP3
Control OP1 / alarm AL2 on OP21Control OP2 / alarm AL2 on OP1
On - Off 2Control OP1 / alarm AL2 on OP23Control OP2 / alarm AL2 on OP1
Control OP2- OP3 / alarm AL2 on OP1 8
[1] For instance, other thermocouples types, ∆T (with 2 PT 100), custom lineari-sation etc.
19
3 - Product coding
AIf, when the controller is poweredup for the first time, the displayshows the following message
it means that the controller hasnot been configured yet.
The controller remain in stand-byuntil the configuration code is setcorrectly (see chapter 4.6 page 35).
9999Conf
123
4
Alarm 2 type and function NDisabled 0Sensor break alarm / Loop Break Alarm
Absolute 2active high3active low
Deviation active high 4active low 5
Bandactive out 6active in 7
Heater break by CT [2]
active during ON output state 8active during OFF output state 9
1
For alarm 3 type and function see page 34
Note [2] Only with CT options.
Deviation active high
Heater break by CT [2]
4
active during ON output state
active low
Alarm 3 type and function O
8
Disabled 0
5
Band
Sensor break alarm / Loop Break Alarm 1
Absolute 2active high
active during OFF output state
3active low
active out
9
6active in 7
20
4 - Operations
4 OPERATIONS 4.1.A KEYS FUNCTIONS AND DISPLAY IN OPERATOR MODE
274.8275.0
123
MAN
Setpointsetting
OP1 output ONOP2 output ONOP3 output ON
Menuaccess
Enter key forselection andvalue settingconfirmation
PV control inputin engineeringunits
OperatingSetpoint
(At the poweron the target
Setpoint valueis displayed
for 3 seconds)
Output statusLEDs(red):
When the measuredvalue is greater thansensor high range
2
When the measuredvalue is less than thesensor low range
Fuzzy Tuning running(green):blinkingManual
operating mode(green): steady
SP2Stand-by
Setpoint enable(green): steady
REM
Digital remoteSetpoint control
(see page 40)
Valuesmodification
Enter key forselection andvalue settingconfirmationAccess to the
menu for:- configuration- parameter setting
Parameter value
Parameter mnemonic
35.0p.b.
123
A / M
2
4.1.B KEYS FUNCTIONS AND DISPLAY IN PROGRAMMING MODE
21
4 - Operations
4.2 DISPLAY
During the operation, the para-meters values cannot be modi-fied by the user
4.2.1 OF THEPROCESS VARIABLES
4.2.2 OF THE CONFIGURATIONCODES
275..0274.8
°C274.8
Out 63.4
t.Cur 47
s.p.275.0
Operator mode
Engineeringunits [1]
OP1 output(auto) [2]
Load current [3]
Local Setpoint (manual)
Note[1] See table page 37[2] This display is not presented if the
instrument has been configured asan On - Off controller
[3] Value in Ampere. Only with CToption (see page 34)
°C274.8
275..0274.8
Hard3600
Conf2002
rel. 00A
Operator mode
Engineeringunits [1]
Basic product code (see page 16)
Configurationcode (see page 18)
Software release
Example: M2 - 3600 - 2002 / Release 00A
22
4 - Operations
Operatormode working Setpointdisplayed
Local Setpoint display
Setpoint modification
Setpoint entry.The operation isacknowledged byone flash of the display.
4.3 PARAMETER SETTING
Press $ or % momentarily tochange the value of 1 unit everypushContinued pressing of $ or %changes the value, at rate thatdoubles every second. Releasingthe button the rate of changedecreases.In any case the change of the valuestops when it has reached themax/min limit set for the parameter.
In case of Setpoint modification: press $ or % once to displaythe local Setpoint instead of work-ing Setpoint.To evidence this change the dis-play flashes once. Then theSetpoint can be modified
4.3.1 NUMERIC ENTRY(i.e. the modification of the Setpoint value from 275.0 to 240.0 )
after 2 s
—Lower
—Raise
275.0274.8
275.0274.8
230.0274.8
240.0274.8
240.0 °C
Unit °C
Unit °f
Unit °C
Unit °f
Unitnone
Unit ph
23
4 - Operations
Engineering UnitsDegree Centigrade
Degree Fahrenheit
Degree Centigrade
Degree Fahrenheit
no unitsdefined
Ph
4.3.2 MNEMONIC CODES SETTING (e.g. configuration see page 35)
Press the $ or % to display the next or previous mnemonic forthe selected parameter. Continued pressing of $ or % will display further mnemonics at arate of one mnemonic every 0.5 s. The mnemonic displayed at the timethe next parameter is selected, is the one stored in the parameter.
4.3.3 KEYPAD LOCK
To lock/unlock the keypad pressthe keys í and è simulta-neously for 2 seconds.To confirm the keypad lock/unlockthe display flashes once.
The keypad lock/unlock can beachieved by serial communicationstoo.
AThe keypad lock is main-tained in case of powerfailure.
274.8275.0
2
operator mode
Press simultaneouslyfor 2 seconds
24
4 - Operations
4.3.4 OUTPUTS LOCK
The outputs are switched to theOFF status by pressing the keysè and %together.When the outputs are locked , themessage #Off is displayedinstead of the Setpoint value.To unlock the outputs press againthe keys simultaneously (the Soft-start will be enabled).
The outputs lock/unlock can beachieved by serial communica-tions too
AThe outputs lock/unlock ismaintained in case ofpower failure.
274.8OFF
2
operator mode
Press simultaneouslyfor 2 seconds
4.3.5 AUTO / MAN
• Press è to confirm. Back to operator mode.
• The led shows the manualmode status.
• When manual mode is active,the Setpoint display shows theoutput value, that can be mod-ified by $ %
MAN
A.ManAuto
275..0274.8
A.ManMan
Operator mode
Select #Manto switch to manual mode
Select #Autoto switch to automaticmode
4.3.5 DIGITAL REMOTE SETPOINT CONTROL
(code E=6 or 8, see pag. 17)Holding pressed simultaneously fortwo second the % and è keysthe Setpoint raise/lower functioncomes inhibited to indefinite time.The return to the full functionality ispossible still pressing simultane-ously for two second the% andè keys.
AThe raise/lower function lock ismaintained in case of power fail-ure
274.8275.0
2
operator mode
Press simultaneouslyfor 2 seconds
275..0
é 5:0
t.i.
é 5:0
p.b.
é 0
A3s.p
274.8 A.Man
O.C.
t.c.
é 1:00
t.d.
é 20
é 1:00
25
4 - Operations
4.4 PARAMETERISATION
AThe parameter setting procedurehas a timeout. If no keys arepressed for, at least, 30 seconds,the controller switches back, auto-matically, to the operator mode.
After having selected the parame-ter or the code, press $ and %to display or modify the value (seepage 22) The value is entered whenthe next parameter is selected, bypressing the è key.
Pressing the í key, the next groupof parameters is presented on thedisplay.
Valuesmodification
Modification/selection
enter
Prametermenu
selection
35.0p.b.
Parametervalue
Parametermnemonic
M2 Operator modeAuto/Manselection(see page 24)
AL3 alarm threshold [1](see page 28)
Proportional band(PID algorithm only)0.5…999.9% of span
Integral time (PID algorithm only)0ff / 0.1…100.0 min
Derivative time (PID algorithm only)0.5…999.9% of span
Cycle time(Time proportioning only)1…200 s
Overshoot control(PID algorithm only)0.01…1.00
Note[1] It is not presented if the con-
troller has been configuredwith alarm n° 2 not active orof sensor break type. DigitN/M of the configurationcode is assigned to 0 or 1.
[2] These values are not auto-matically stored on the PIDmenu parameters P.b., t.i, t.d.
tune
5000
é 0:5
d.bnd
é100:0
Op. H
é100:0
Op.HC
hy.é 0:5
hy. C
r.C.Ga
é 20
t.c. C
é 33
pAssé 0
A2s.p
OK
é 1:0
é 0:5
p.b. a
T.i. A
ADPT
26
4 - Operations
Cool cycle time (heat/cool with cool timeproportioning only)1…200 s
Cool relative gain (heat/cool configuration only)0.1…10.0
Cool output hysteresis (On-Off control only)0.1…10.0% range
Password entryonly if Code value≥5000 (see pages 35…37)
1st GROUPAL2 alarm threshold [1](see page 28)
Dead band(heat/cool configuration only)-10.0…10.0%
Control output high limit(PID algorithm only)10.0…100.0%
Cool control output high limit(heat/cool PID configuration only)10.0…100.0%
Control output hysteresis(On-Off control only)0.1…10.0% of span
2nd GROUPTuning run/stop (PID algorithm only)
Continuous Tuning start(adaptive tuning)(PID algorithm only) PrGh
Calculated Proportional band [2] (display only)(available when adaptivetuning is selected)
Calculated Integral Time[2] (display only)(available when adaptivetuning is selected)
PARAMETER MENU
Back to the 1st parameter group
Code entryfrom 5000 to 9999Must be equal to thevalue of the parame-ter Code
YESNO
éF.sécala
é 0
é Off
é Off
éIn.sécala
t.d. Aé I
s.p. 2
sl. u
sl. d
s.p. l
s.p. H
s.p.In
é 0:5
A2hy
énone
A2L.béH. r éange
éL. r éange
27
4 - Operations
Calculated derivativetime [2] (display only)(available when adaptivetuning is selected)
Stand-by Setpoint s.p. l…s.p. H
Setpoint ramp up 0ff/0.1…999.9digit/min
Setpoint ramp down0ff/0.1…999.9digit/min
Setpoint low limit low range… s.p. H
Setpoint high limits.p. l…high range
Setpoint inc./decr. value by digital input(if option installed)0…full range
AL2 hysteresis0.1…10.0% of span [1]
AL2 latching and blocking functionsnone / Ltchbloc / Lt.bL
28
4 - Operations
pass
énone
é Off
é Off
é Off
é Off
st.Op
é 1
st.tM
sa.Opé 0é Off
In.shA3L.b
A3hyé 0:5
t.LbA
t.Fil
d.Err
Password entryonly if Code value <5000 (see pages 35…37)
AL3 hysteresis0.1…10.0% of span [1]
AL3 latching and blocking functionsnone / Ltchbloc / Lt.bL
LBA delay(see page 31)0ff= sensor break1…9999 s LBA
Filter time constant1…30 s or Off
Input shift -60…60 digits
Error dead band (PID algorithm only)0ff/0.1…10.0 digits
Soft-start output value(PID algorithm and 0ff/0.1…100.0%
Soft-start activation time (only if st.Op different than0ff) 1…9999 s
Output safety value 0.0…100.0% (not shown if E = 7 or E = 8see page 17)(-100.0…100.0% forheat/cool)
Direct access to the configuration(pages 35 … 37)
Back to the 2nd parameter group
Proportional band
This parameter specifies the pro-portional band coefficient that mul-tiplies the error (SP - PV)
Integral time
It is the integral time value, thatspecifies the time required by theintegral term to generate an outputequivalent to the proportional term.When Off the integral term is notincluded in the control algorithm.
Derivativetime
It is the time required by the proportionalterm P to repeat the output provided bythe derivative term D. When Off thederivative term is not included in thecontrol algorithm.
Control output cycle time Cycle time cool
It’s the cycle time of the logic con-trol output. The PID time propor-tional control output is providedthrough the pulse width modula-tion of the digital waveform.
#t.c. C#t.c.
#t.d.
#t.i.
#p.b.
29
4 - Operations
4.5 PARAMETERS
Band alarmOnOff
Activeout
Activein
hy
SP
Full scaleFull scale
hy
Alarm threshold
OnOff
Deviation alarmOnOff
Activehigh
Activelow
hy
+ high range- low rangeAlarm threshold
OnOff
SP
Absolute alarmOnOff
Activehigh
Activelow
hy
High rangeLow rangeAlarm threshold
OnOff
T
Sensor break or input disconnection
over-range
under-range
VisualisationSensor
The controller parameters havebeen organised in group, accord-ing to their functionality area.
AL2 alarm threshold AL3 alarm threshold
The alarm occurrences handle theOP1, OP2 and OP3 outputs, in dif-ferent ways, according to the con-figured types of alarms, as illus-trated.With double action control out-put, AL2 and AL3 share in ormode the same output (the freeone) (see table on page 13)
#A3s.p#A2s.p
FIRST GROUP
30
4 - Operations
Overshoot control
(Automatically disabled when theadaptive tuning is running).This parameter specifies the span ofaction of the overshoot control. Settinglower values (0.99 —> 0.01) the over-shoot generated by a Setpoint changeis reduced. The overshoot controldoesn’t affect the effectiveness of thePID algorithm. Setting 1, the over-shoot control is disabled.
Heat/Cool dead band
This parameter specifies the widthof the deadband between the Cooland the Heat channel.
Control outputhigh limitCool outputhigh limit
It specifies the maximum value thecontrol output can be set
Control outputhysteresisCool outputhysteresis#hy. C
#hy.
#Op.HC#Op. H
#d.bnd
#O.C.
Control or alarm output hysteresisspan, set in % of the full scale.
Off
SPOn
Hysteresis of the threshold
hy
Setpoint incre-ment/decrement
step value by digital input
AL2 alarm hysteresisAL3 alarm hysteresis
Hysteresis of the threshold of boththe alarms, that activate OP1 andOP2 control output. It is specifiedas a % of the full scale.
AL2, AL3 latching and blocking functions
For each alarm it is possible toselect the following functionsnone noneLtch latchingbloc blockingLt.bL both latching and blocking
#A2L.b#A3L.b
#A3hy#A2hy
#s.p.In
SECOND GROUP
Stand-bySetpoint
Setpoint ramp upSetpointramp down
This parameter specifies the max-imum rate of change of the Setpointin digit/min. When the parameter isOff, this function is disabled.
Setpoint low limitSetpoint high limit
Low / high limit of the Setpoint value.
#s.p. H#s.p. l
#sl. d#sl. u
#S.P. 2
31
4 - Operations
#Ltch ALARM ACKNOWLEDGE FUNCTIONThe alarm, once occurred, is pre-sented on the display until to thetime of acknowledge. The acknowledge operation con-sists in pressing any key.After this operation, the alarmleaves the alarm state only whenthe alarm condition is no longerpresent.
#bloc START-UP DISABLING
DisableSP∆SP
OnOff
Start-up
∆SP Disable
SP
OnOff
Start-up
Ramp down
Ramp up
∆SP Threshold = SP ± range
ALARMS WITH LBA (LOOP BREAK ALARM) AND SENSOR BREAK OPERATIONSelect the code 1 on n or o configuration indexes (see pages 18 or19). The following parameter is then available:
LBA delay#t.LbASetting a value between 1 and9999 s the alarm works asLBA+Sensor break with delay [1]This condition is shown by meansa red led as well as the blinking PVdisplay.
Setting OFF the alarm works asSensor break with immediateaction.This condition is shown by meansthe red led of the selected alarm aswell as:
When the cause of the alarm disappears, the alarm status stops.
or275.08888
275.08888____ ----
Note [1] In case of sensor break, con-dition, the alarm action is immediate.
275.0274.8
mA
°C
OP1
32
4 - Operations
Input filter time constant
Time constant, in seconds, of the RCinput filter applied to the PV input.When this parameter is set to Offthe filter is bypassed.
Input shift
This value is added to the measuredPV input value. Its effect is to shift thewhole PV scale of up to ± 60 digits.
Error Dead Band
Inside this band for (PV - SP), the con-trol output does not change to protectthe actuator (output Stand-by)
#d.Err
#In.sh
Filter response100%
0
PV63,2%
t.Fil Time
#t.fil Soft-startcontrol outputvalue
Value of the control output duringthe Soft-start activation time.
Soft-startactivation time
Time duration (starting from thepower on) of the Soft-start func-tion.
Soft-startphase
100%
Start up
#St.tM
#St.OP
OP
Time
#st.tM
#St.OP OutputSafety Value
Output Value in case of inputanomalyNot shown if E = 7 or E = 8 (seepage 17)
#Sa.OP
SECOND GROUP
33
4 - Operations
By a sole PID control algorithm, thecontroller handles two different out-puts, one of these performs theHeat action, the other one the Coolaction.It is possible to overlap the out-puts. The dead band parameter #d.bnd,is the zone where it is possible toseparate or overlap the Heat andCool actions.
The Cool action can be adjustedusing the relative cool gain para-meter #r.C.Ga.
To limit the Heat and Cool outputsthe parameters #0p. H and #0p.HCcan be used.
When there is an overlap, the dis-played output # OUt shows thealgebric sum of the Heat and Cooloutputs.
HEAT COOL CONTROL
A Heat /Cool actions separated
Insert positive #d.bnd value(0…10%)
B Heat /Cool actions overlapped
Insert negative #d.bnd value (-10…0%)
100%
100%
#d.b.nd
#Op.HC#Op. H
50%
Heatoutput
Cooloutput0%
0%PID output
-100%
100%
100%
#d.b.nd
#Op.HC#Op. H
50%
Heatoutput
Cooloutput0%
0%PID output
-100%
C Cool action adjustingExample with different relative coolgains
D On-Off Cool action
100%
100%
#d.b.nd
#hy. C
50%
Heatoutput
Cooloutput0%
0%PID output
On
Off
100%
100%
#d.b.nd
#r.C.Ga 0.1…10.0
50%
Heatoutput
Cooloutput0%
0%PID output
-100%
=2.0=1.0=0.5
34
4 - Operations
CURRENT TRANSFORMER INPUT
With CT option it is possible to dis-play the load current and set analarm threshold.It is possible to set AL2 or AL3(index 8 and 9) to have an alarmwhen, during the ON time of thetime proportional output, the loadcurrent is less then the specifiedthreshold or, during the OFF time,there is at least 3% of full scale
load currentThe alarm condition must be longerthan 120 ms to set the alarm.During the OFF time the parame-ter tCur latches the last on timecurrent value
Example:CT input on OP1, alarm on AL2 dur-ing on time (configuration digit N = 8)
ON ON
ON ON
3%
A2s.p
t.Cur
120 ms 120 ms
OFFOP1
AL2 OFF OFF OFF
Load
cur
rent
275..0274.8
Code
A.Man
sc.Hi
Ht.f.s
IL.Fn
Password [2]0…999933 default from factory
High range [1](linear scale only)-999…9999
Digital input function(only if installed)(see table 2)
CT primary high range(only if installed) 10…200 A
35
4 - Operations
4.6 CONFIGURATION
The configuration of the controlleris specified through a 4 digit codethat defines the type of input, ofcontrol output and of the alarms.(sect. 3.2 page 18)
Press $ or % to display thenext parameter or the next codeand change its value.The new value entered is stored intothe controller when the next para-meter is selected by pressing è.Pressing the í the next groupof parameters is displayed.
Valuesmodification
Enter key forselection andvalue settingconfirmation
Configurationmenu access
200.2Conf
Parametervalue
Parametermnemonic
M2
Operator mode Auto / Man selection (see page 24)
2002
tune
I L M N
A2s.p
Con2sc.lo
sc.d.d
ConfUnit
5000
pAss
OK
Direct access to the configuration
36
4 - OperationsCONFIGURATION MENU
1st GROUP 2nd GROUP
AL3 configuration code(see table O, page 19)
Engineering units(see table 1)
N° of decimals(linear scale only)0…3
Low range [1](linear scale only)-999…9999
Entry of digits I-L-M-N of the configuration code
(chapter 3.2 page 18 and 19)
YES
NO
Password entryonly if Codevalue ≥5000
Code entryfrom 5000 to 9999Must be equal to thevalue of the parameterCode
pass
33
OK
37
4 - Operations
Code entryfrom 0 to 4999 (33 default from factory)The entered password must correspond tothe one store in the Code parameter.
Password entryonly if Code value <5000
ADirect access to the configuration
A From parameterisation (see page 27).B At the first power on when the
controller is not configured:
In this situation, the controller has its outputs and inputs not active.This situation ends when a correct configuration code is entered.
Conf9999
Table 1 - Supported Engineering Units.
Notes[1] Minimum Range 100 digits.[2] To avoid free parameter access
insert 5000…9999[3] If option installed
mV nUVolt UmA MA
Centigrade degrees* °C
Ampere
Fahrenheit degrees * °f
ABar bArPSI
none none
psIRh rhpH ph* For inputs from thermocouple or
resistance thermometer, the choiceis between °C and °F only.
Stand-by Setpoint s.p. 2Remote Setpoint control [3] CuSt
Not used OffKeypad lock keb.IAuto/Man A.Man
Table 2- Digital input functions
NOYES
38
5 - Automatic tuning
275..0274.8
tunestop
tunestrt
Operatormode
press until
To startselect strt
To stop select stop
Step response
SP
Natural frequency
Start of autotuneoperation
PV variable
Control output
PV variable
Control output
tuning start
End of the tuningoperating and setting of
the new calculatedterms.
Setpoint change End of the tuningoperating and setting of
the new calculatedterms.
5 AUTOMATICTUNING
Two tuning methods are provided:• Initial one shot Fuzzy-tuning • Continuous, self learning
Adaptive Tuning
The Fuzzy-Tuning allows the calcu-lation of the optimal PID terms para-meters, monitoring the response ofthe process to disturbances.The controller provides 2 types of“one shot” tuning algorithm, thatare selected automatically accord-ing to the process condition whenthe operation is started.Step responseThis type is selected when, at thestart of the autotune operation, thePV is far from the Setpoint of morethan 5% of the span.This method has the big advantageof fast calculation, with a reasonableaccuracy in the term calculation.Natural frequencyThis type is selected when the PV isclose to the SP Setpoint.This method has the advantage of
a better accuracy in the term cal-culation with a reasonable speedcalculation.The Fuzzy Tuning determinesautomatically the best method touse to calculate the PID term,according the process conditions.
The green led blinking goes onwhen the Fuzzy Tuning is inprogress. At the end of this opera-tion, the calculated PID terms para-meter are stored and used by thecontrol algorithm and the controllergoes back to the operator mode.The green led becomes off.
39
5 - Automatic tuning
The self-learning Adaptive Tuningis not intrusive. It doesn’t affect theprocess, at all, during the phase ofcalculation of the optimal termsparameters.
It is particularly suitable for con-trolling process whose controlcharacteristics change withtime or are not linear in relationto the Setpoint values.It doesn’t require any operation bythe user. It is simple and works fine:it samples continuously theprocess response to the variousperturbations, determining the fre-quency and the amplitude of thesignals. On the basis of this dataand their statistical values, storedin the instrument, it modifies auto-matically the PID term parameters.It is the ideal for all applicationswhere it is required to change con-
Perturbation
Newparameters
Continuous adaptive tune
tinuously the PID terms parame-ters, in order to adjust the PID tothe changes of the processdynamic conditions.
In case of power off with theAdaptive Tuning enabled, thevalues of the PID terms para-meters are lost. At the power onthe Adaptive Tuning starts auto-matically and computes againthe values of the PID terms para-meters.
275..0274.8
Adptstop
Adptstrt
tuneStop
Operatormode
press until
press è
To startselect strt
To stop selectstop
40
6 - Special functions
6 SPECIAL FUNCTIONS
Two special functions are available:6.1 Safety average OP on
sensor break6.2 Digital remote setpoint control
(Setpoint raise/lower + Stand-by Setpoint)
This function is available only if theindex E of the model code (seepage 17) engages the value 7 or 8.The averages comes effected, fil-tering the output with a first orderfilter with around 50 seconds ofconstant of time. Such filter isactive in a continuous way whenthe input is in conditions of normaloperation; in conditions of outscale the refresh of the filter comesjammed and the reached valuebecomes the output. The #Sa.OP parameter (see pages28,32) doesn't appear when theoption is enabled.
This function is available only if theindex E of the product code of themodel (see page 17) engages thevalue 6 or 8 and the digital inputoption (C index= 9) is present.The parameter of configuration#Il...fn (see page 35) allows to setthe Cust value that enable thefunction.Connecting to the digital input anoutput of the APG2- DRSPC card(see manual N. M.I.U. DRSPC J30-628-1ADRSPC) it is possible:
1. To increase the Setpoint of astep
2. To decrease the Setpoint of thesame step
3. To select the Stand-by Setpoint#S.P. 2 (see page 27)
The value of the step has givenfrom the # .S.P.In parameter (seepages 27,30).
6.1 SAFETY STATE USING THE AVERAGE OF THE OUTPUT
6.2 DIGITAL INPUT WITH REMOTE SETPOINT CONTROL
41
6 - Special functions
When the option is activated the Ü led comes alight and the func-tion of the digital input it is the following:
Digital input disabled The instrument operates on local Setpoint
Raise function activation
The local Setpoint increase of the value of S.P.In, Ü led flashes threetimes to point out the operation
Lower function activationThe local Setpoint decrease of the value ofS.P.In, the Ü led flashes three times topoint out the operation
Stand-by SP selectionThe controller uses the Stand-by SetpointS.P. 2, the ä led alight points out thestate
42
7 - Technical specification
7 TECHNICAL SPECIFICATIONS
Common characteristics
A/D converter with resolution of 50,000 pointsUpdate measurement time: 0.2 secondsSampling time: 0.5 secondsInput bias: - 60…+ 60 digitInput filter with enable/disable: 1…30 seconds
Accuracy0.25% ± 1 digits for temperature sensors0.1% ± 1 digits (for mV and mA)
Between 100…240V~the error is minimal
Resistance thermometer(for ∆T: R1+R2 must be <320Ω)
Pt100Ω at 0°C(IEC 751)°C/°F selectable
2 or 3 wires connectionBurnout (with any combination)
Max. wire Res: 20Ω max(3 wires)Sensitivity: 0.1°C/10° E. T.<0.1°C / 10Ω Wire Res.
Thermocouple
L,J,T,K,S(IEC 584)Rj >10MΩ°C/°F selectable
Internal cold junctioncompensation con NTCError 1°C/20°C ±0.5°CBurnout
Line: 150Ω max Input drift:<2µV/°C.Env. Temp<0.5µV / 10Ω Wire Res.
DC input (current)4…20mA,0-20mAwith external shunt 2.5ΩRj >10MΩ
Engineering unitsConf. decimal point positionInit. Sc -999…9999Full Sc. -999…9999(min. range of 100 digits)
Input drift:<0.1% / 20°C Env. Temp.
DC input (voltage)10…50mV, 0-50mVRj >10MΩ
Total configurability(see par. 3.2 page 18
par. 4.6 page 35)
PV Input(see page11,12 and page 18)
Description
From keypad the user selects:- the type of input - the associated functions and the corresponding outputs- the type of control algorithm - the type of output and the safe conditions - the type and functionality of the alarms - the values of all the control parameters.
Features(at 25°C environmental temp.)
43
7 - Technical specification
Features(at 25°C environmental temp.) Description
Single action
DoubleactionHeat/cool
CT auxiliary input(option)
Current transformer(see page 12)
50 or 100 mAinput hardwareselectable
Current visualisation 10 … 200AWith 1A resolutionand Heater Break Alarm
Digital input(option)
The closure of the externalcontact produces any ofthe following actions:
Auto/Man mode change, Stored Setpoint activation, Keypad lock,Remote Setpoint Control
Operating mode and Outputs
1 doubleaction PIDloop or On/Offwith 1 or 2alarms
Control output AL2 alarm AL3 alarmOP1-Relay OP2-Logic or Relay(opt.) OP3-Relay/TriacOP2 -Logic OP1-Relay OP3-Relay/TriacOP1-Relay OP3-Relay OP2-Logic or Relay(opt.)OP1-Relay OP2 Logic OP3-Relay/TriacOP2 Logic OP3-Relay OP1-Relay
Control mode
Algorithm PID with overshoot control or On-OffProportional band (P) 0.5…999.9%
PID algorithmIntegral time (I) 0.1…100.0 min
OFF = ODerivative time (D) 0.01…10.00 min
1…200 sDead band -10.0…10.0%
Heat / cool control action
Cool relative gain 0.1…10.0
Cool cycle time 1…200 sOvershoot control 0.01…1.00
PID algorithmHigh limit 100.0…10.0% (heat) -100.0…-10.0%(cool)Hysteresis 0.1…10.0% On-Off algorithm
Error band 0.1…10.0 digitCycle time
44
7 - Technical specification
OP1 output SPST Relay N.O., 2A/250V~ for resistive load
Active low
Protection by varistor for 220V ~and capacitor
OP2 outputLogic not isolated: 5V–, ± 10%, 30mA maxSPST Relay(option),N.O., 2A/250V~ for resistive load
Jumper selectable (page 13)
OP3 output SPST Relay N.O., 2A/250V~ for resistive load,
Features(at 25°C environmental temp.) Description
AL2 - AL3 alarms
Hysteresis 0.1…10.0% c.s.
Action
Active highAction type
Deviation threshold ±range
Band threshold 0…range
Absolute threshold whole range
Sensor break, heater break alarm,Latching/Blocking, Loop Break Alarm
Setpoint
Local and stand-by, digital input or serial communications
Ramp up and down. User inhibited 0.1…999.9 digit/min
Low limit from low range to high limit
High limit from low limit to high range
Tuning
Fuzzy-Tuning The controller selects automaticallythe best method according to the process conditions
Step response
Natural frequency
Auto/Man station Standard with bumpless function, by keypad, digital input or serial communications
Adaptive Tuning self-learning, not intrusive, analysis of the process response to perturbations andcontinuously calculation of the PID parameters
45
7- Technical specification
Features(at 25°C environmental temp.) Description
Operational safety
Measure input Detection of out of range, short circuit or sensor break with automaticactivation of the safety strategies and alerts on display
Control output Safety value: -100%…100% or Average (option)
Parameters Parameter and configuration data are stored in a non volatile memory foran unlimited time
Access protectionPassword to access the configuration and parameters data,keypad lock, output lock
General characteristics
Power supply(fuse protected)
100 - 240V~ (- 15% + 10%) 50/60 Hz or 24V~ (- 25% + 12%), 50/60 Hz and 24V– (- 15% + 25%)Power consumption 2.6W max
Safety Compliance to EN61010-1 (IEC 1010 – 1), installation class 2 (2500V) pollution class 2, instrument class II
Electromagnetic compatibility Compliance to the CE standards (see page 2)
Protection EN60529 (IEC 529) IP65 front panel
Dimensions 1/16 DIN - 48 x 48, depth 120 mm, weight 130 gr. apx.
UL and cUL Omologation File 176452
1 WARRANTY
We warrant that the prod-ucts will be free fromdefects in material andworkmanship for 3 yearsfrom the date of delivery.The warranty above shallnot apply for any failurecaused by the use of theproduct not in line with theinstructions reported on thismanual.
G.&
P. G
rafic
a &
Pub
blic
ità •
Gaz
zani
ga (B
G) •
e-m
ail:
G&
P@
ma
il.c
sg
-ne
t.it
46
Warranty
47
SUBSIDIARY
FRANCEASCON FRANCE
Phone 0033 1 64 30 62 62Fax 0033 1 64 30 84 98
AGENCE SUD-EST
Phone 0033 4 74 27 82 81Fax 0033 4 74 27 81 71
AGENCE RÉGION-EST
Phone 0033 3 89 76 99 89Fax 0033 3 89 76 87 03
DISTRIBUTORS
ARGENTINAMEDITECNA S.R.L.Phone +5411 4585 7005Fax +5411 4585 3437
AUSTRALIAIPA INDUSTRIAL PYROMETER
(AUST) PTY.LTDPhone +61 8 8352 3688Fax +61 8 8352 2873
FINLAND & ESTONIATIM-TOOL OY
Phone +358 50 501 2000Fax +358 9 50 55 144
GERMANYMESA INDUSTRIE ELEKTRONIK GMBHPhone +49 2365 915 220Fax +49 2365 915 225
GREECECONTROL SYSTEM
Phone +30 23 10 521 055-6 Fax +30 23 10 515 495BRANCH OFFICE
Phone +30 1 646 6276Fax +30 1 646 6862
HOLLANDTEMPCONTROL I.EP. B.V.Phone +31 70 347 64 31Fax +31 70 38 22 55 16
PORTUGALREGIQUIPAMENTOS LDAPhone +351 21 989 0738Fax +351 21 989 0739
SPAININTERBIL S.L.Phone +34 94 453 50 78Fax +34 94 453 51 45
BRANCH OFFICES
Phone +34 93 311 98 11 Fax +34 93 311 93 65 Phone +34 91 656 04 71Fax +34 91 656 04 71
SWITZERLANDCONTROLTHERM GMBHPhone +41 1 954 37 77Fax +41 1 954 37 78
TURKEY KONTROL SISTEMLERI LTDPhone +90 216 527 96 15Fax +90 216 527 96 20
UNITED KINGDOMEUKERO CONTROLS LTDPhone +44 20 8568 4664Fax +44 20 8568 4115
ASCON’S WORLDWIDE SALES NETWORK