11
Page 1 of 11 (Rev. 10/2019) M100LED DI_v9.0 In a continuing effort to offer the best product possible, we reserve the right to change, without notice, specifications or materials that in our opinion will not alter the function of the product. Specification sheets found at www.selux.us are the most recent versions and supercede all other printed or electronic versions. Selux Corporation © 2019, T 845-834-1400, 800-735-8927, F 845-834-1401, www.selux.us Project: Type: Qty: Date: Customer: M100 LED Direct/Indirect Order Code: - - - - - - - - - - - - - - NB LMO Symmetric with Satine Lens A2 LMO Asymmetric 20° Wall Washer with Satine Lens BW LMO Batwing with Satine Lens A5 LMO Asymmetric 5° Wall Grazer with Satine Lens PX 5 Blank Cover Series L1DI M100 LED Direct/Indirect L1DI L1DI * Custom colors are available, please consult factory Emergency Options EC 13,14 Emergency Circuit Wiring 13 See page 7 for full details and restrictions 14 For emergency options with sensors, please consult factory 14 4’ available with DIM driver only. ≥8’ available with all DIM driver options. 1B35 1,2 710lm/8.7W per foot 1B30 1,2 606lm/7.3W per foot 1B25 1,2 543lm/6.4W per foot 1B20 1,2 410lm/4.8W per foot 1 Values calculated from a 4’ fixture @4000K using LW Shielding and DIM driver. For additional information please see page 2. 2 Mixed output available 4’ and up, see page 7 for details. 3 Not available with Lutron 4 Use BLNK for Piix™ modules with blank sections. Drawings required to show Piix™ module and blank section configurations. IT90 Lit “T” section IX90 Lit “X” section IL90 Lit Horizontal 90° Corner Configuration Options Direct Light Engine CCT 30 3000K 90+ CRI 35 3500K 90+ CRI 40 4000K 90+ CRI Direct Shielding LW LED Optimized White lens Mounting C Cable S Swivel Stem RS Rigid Stem W Wall Mount Nominal Fixture Length 02 2 ft. 04 4 ft. 03 3 ft. 05 5 ft. 06 6 ft. 08 8 ft. 07 7 ft. XX Runs (over 12’) are available in 1’ nominal increments, round up to the nearest foot and replace the “xx” with the # (i.e. 13=13’ nominal) Finish WH* White SV* Silver SP* Specify Premium Color Voltage 120 120 Volt 277 277 Volt 27 2700K 90+ CRI 09 9 ft. 11 11 ft. 10 10 ft. 12 12 ft. UNV 120 through 277 50/60hz capable Indirect Light Engine Indirect Shielding LW LED Optimized white lens Individual fixtures, Runs and Configurations are supplied in nominal lengths to ensure full, even, illumination. See pages 2 through 5 for additional details. 1B35 1,2 710lm/8.7W per foot 1B30 1,2 606lm/7.3W per foot 1B25 1,2 543lm/6.4W per foot 1B20 1,2 410lm/4.8W per foot MI Clear Lens with Microprism DL Damp Location Rated FS In-Line Fuse 9 SS option for linear section only 10 Piix™ modules are switched sepa- rate standard. Minimum 6’ M100 required for Piix™ module. Fixture Options SS 9 Separate Switching DML 6,8 eldoLED SOLO- drive 0-10V (Logarithmic) Driver DMD 6,8 eldoLED DALI (Logarithmic) DE1 6 Lutron EcoSystem 6 See page 6 for full details 7 120V only 8 EM option not available in 4’ length DC2 6,7 Lutron 2-Wire DM 6,8 eldoLED SOLOdrive 0-10V (Linear) DIM 6 0-10V (Linear) Sensor Options xE 11,12 Enlighted Replace “x” with quantity xS1 11,12 Sensor Switch Daylight xS2 11,12 Sensor Switch Occ/Vac xS3 11,12 Sensor Switch Occ/Vac/ Daylight 11 Minimum length 2’ See page 8 for full details and restrictions LED WARRANTY 5 YEAR ARRA Compliant ADA Compliant 12 Required DIM driver (0-10V) LW LW 1B45 1,2,3 893lm/11.2W per foot 1B40 1,2,3 807lm/9.9W per foot 1B45 1,2,3 893lm/11.2W per foot 1B40 1,2,3 807lm/9.9W per foot 347 347 Volt (consult factory) DC5 Lutron 5-Series (consult factory) xSN nLight enabled (consult factory) BL* Semi-Matte Black EMR Remote Micro Inverter (consult factory) EM 13,14,15 Integral EM Battery Pack (consult factory) xV Lutron Vive (consult factory) CCEA CCEA Approved (consult factory) #P1 10 1 Cell Piix ~332lm/3.5W per cell #P3 10 3 Cell Piix ~332lm/3.5W per cell BLNK 2,4 Provide quantity (#) of Piix™ modules required. Piix™ modules provided with same CCT, finish and driver as M100. Standard module provided with Black Baffle and 35º reflectors. For other configurations, please consult factory. Example: 2P1 will yield an M100 with two (2) 1 cell Piix™ modules located at either end of the fixture. 5 PX direct shielding for use with BLNK direct light engine

M100 LED Direct/Indirect [L1D1] selux...Indirect Light Engine Indirect Shielding LW LED Optimized white lens Individual fixtures, Runs and Configurations are supplied in nominal lengths

  • Upload
    others

  • View
    28

  • Download
    0

Embed Size (px)

Citation preview

Page 1 of 11 (Rev. 10/2019)

M100LED DI_v9.0In a continuing effort to offer the best product possible, we reserve the right to change, without notice, specifications or materials that in our opinion will not alter the function of the product. Specification sheets found at www.selux.us are the most recent versions and supercede all other printed or electronic versions.

Selux Corporation © 2019, T 845-834-1400, 800-735-8927, F 845-834-1401, www.selux.us

Project:

Type: Qty:

Date: Customer:

M100LED Direct/Indirect

Order Code: - - - - - - - - - - - - - -

NB LMO Symmetric with Satine Lens

A2 LMO Asymmetric 20° Wall Washer with Satine Lens

BW LMO Batwing with Satine Lens

A5 LMO Asymmetric 5° Wall Grazer with Satine Lens

PX5 Blank Cover

Series L1DI M100 LED Direct/Indirect

L1DI

L1DI

* Custom colors are available, please consult factory

Emergency Options

EC13,14 Emergency Circuit Wiring

13 See page 7 for full details and restrictions14 For emergency options with sensors, please

consult factory14 4’ available with DIM driver only.

≥8’ available with all DIM driver options.

1B351,2 710lm/8.7W per foot

1B301,2 606lm/7.3W per foot

1B251,2 543lm/6.4W per foot

1B201,2 410lm/4.8W per foot

1 Values calculated from a 4’ fixture @4000K using LW Shielding and DIM driver. For additional information please see page 2.

2 Mixed output available 4’ and up, see page 7 for details.

3 Not available with Lutron4 Use BLNK for Piix™ modules with blank sections. Drawings required to show Piix™ module and blank section configurations.

IT90 Lit “T” section

IX90 Lit “X” section

IL90 Lit Horizontal 90° Corner

Configuration Options

Direct Light Engine

CCT30 3000K 90+ CRI

35 3500K 90+ CRI

40 4000K 90+ CRI

Direct Shielding

LW LED Optimized White lens

Mounting C Cable

S Swivel Stem

RS Rigid Stem

W Wall Mount

Nominal Fixture Length

02 2 ft.

04 4 ft.

03 3 ft.

05 5 ft.

06 6 ft.

08 8 ft.

07 7 ft.

XX Runs (over 12’) are available in 1’ nominal increments, round up to the nearest foot and replace the “xx” with the # (i.e. 13=13’ nominal)

Finish WH* White

SV* Silver

SP* Specify Premium Color

Voltage 120120 Volt

277277 Volt

27 2700K 90+ CRI

09 9 ft.

11 11 ft.

10 10 ft.

12 12 ft.

UNV120 through 277 50/60hz capable

Indirect Light Engine

IndirectShielding

LW LED Optimized white lens

Individual fixtures, Runs and Configurations are supplied in nominal lengths to ensure full, even, illumination. See pages 2 through 5 for additional details.

1B351,2 710lm/8.7W per foot

1B301,2 606lm/7.3W per foot

1B251,2 543lm/6.4W per foot

1B201,2 410lm/4.8W per foot

MI Clear Lens with Microprism

DL

Damp Location Rated

FS In-Line Fuse

9 SS option for linear section only10 Piix™ modules are switched sepa-

rate standard. Minimum 6’ M100 required for Piix™ module.

Fixture Options

SS9 Separate Switching

DML6,8 eldoLED SOLO-drive 0-10V (Logarithmic)

Driver DMD6,8 eldoLED DALI(Logarithmic)

DE16 Lutron EcoSystem

6 See page 6 for full details7 120V only8 EM option not available in 4’ length

DC26,7 Lutron 2-Wire

DM6,8 eldoLED SOLOdrive 0-10V (Linear)

DIM6 0-10V (Linear)

Sensor Options

xE11,12 Enlighted

Replace “x” with quantity

xS111,12 Sensor Switch Daylight

xS211,12 Sensor Switch Occ/Vac

xS311,12 Sensor Switch Occ/Vac/Daylight

11 Minimum length 2’ See page 8 for full details and restrictions

LED WARRANTY

5YEAR ARRA

CompliantADA

Compliant

12 Required DIM driver (0-10V)

LW

LW

1B451,2,3 893lm/11.2W per foot

1B401,2,3 807lm/9.9W per foot

1B451,2,3 893lm/11.2W per foot

1B401,2,3 807lm/9.9W per foot

347347 Volt (consult factory)

DC5 Lutron 5-Series (consult factory)

xSN nLight enabled (consult factory)

BL* Semi-Matte Black

EMRRemote Micro Inverter (consult factory)

EM13,14,15 Integral EM Battery Pack (consult factory)

xV Lutron Vive (consult factory)

CCEA CCEA Approved (consult factory)

#P110 1 Cell Piix ~332lm/3.5W per cell

#P310 3 Cell Piix ~332lm/3.5W per cell

BLNK2,4

► Provide quantity (#) of Piix™ modules required.► Piix™ modules provided with same CCT, finish and driver as M100. Standard module provided with Black Baffle and 35º reflectors. For other configurations, please consult factory.

Example: 2P1 will yield an M100 with two (2) 1 cell Piix™ modules located at either end of the fixture.

5 PX direct shielding for use with BLNK direct light engine

Page 2 of 11 (Rev. 10/2019)

M100LED DI_v9.0

In a continuing effort to offer the best product possible, we reserve the right to change, without notice, specifications or materials that in our opinion will not alter the function of the product. Specification sheets found at www.selux.us are the most recent versions and supercede all other printed or electronic versions.

Selux Corporation © 2019, T 845-834-1400, 800-735-8927, F 845-834-1401, www.selux.us

M100LED Direct/Indirect

6” (152mm)

3 11/16” (94mm)

3 15/16” (100mm)

Construction:

Housing - Continuous, low copper 6063-T6 extruded aluminum profile with aluminum end-caps, available as Individual fixtures (up to 12’) or Runs.

Geartray - Low copper 6063-T6 extruded aluminum profile.

Shielding - Extruded, impact resistant acrylic snap in lens:- LED Optimized White Lens (LW)- Clear Lens with Microprism (MI)“LMO” refers to the Selux proprietary LED optical system - Light modulation optics. These lenses are offered in M100 behind a Satine Lens for even illumination and comfortable lit appearance.- “LMO” Symmetric Lens (NB)- “LMO” Asymmetric 20° Wall Washer (A2) - “LMO” Asymmetric 5° Wall Grazer (A5)- “LMO” Batwing (BW)

Mounting(s)- 1/16” Aircraft Cable, Ø5/8” Swivel or Rigid Steel Stem, Wall Bracket, (see pages 3 through 5 for details). ** Cable, Stem and Wall mountings may not be symmetrical for Runs and Configurations due to the use of modular housing lengths. If symmetri-cal suspensions are required please consult the factory.

Standard Luminaire lengths - All standard luminaires are supplied in nominal lengths to ensure full, even, illumination. Runs and Configurations are available in approximately 1’ increments starting at the nominal 12’ fixture length. ** Individual luminaires are not joinable in the field.

Exact length luminaires - Individual luminaires, Runs, and Configuration are available in exact lengths to meet your project needs. Please con-sult factory with your requirements. ** Lens luminance may soften at the very ends of the straight sections for exact length luminaires.

L10 Joiner(s) - Runs and Configurations are supplied in multiple housings that are joined together in the field using the supplied L10 Joining System. This allows ease of installation and ensures a uniform appearance (see page 7 for detail).

Weight: 4.3 lb. per foot.

Electrical/Performance:

LED Light Engine - Brand-name mid-power LEDs create a high efficiency LED light engine able to provide a lumen maintenance of 96% at 25,000 hours and 93% at 60,000 hours at 25ºC per TM-21 reports. Reported L70 greater than 60,000 hours.

Delivered Lumens - Due to LED manufacturer’s tolerances the listed output has a ±5% toler-ance. For outputs based on different shielding or CCT please see photometry section at the end.

CCT - Available in 2700K, 3000K, 3500K and 4000K, tolerance within a 3-step MacAdam ellipse.

CRl - 90+.

All Drivers - High efficiency, constant current, soft start, Electronic Class 2 with a PFC>0.90. For more detailed information on the available drivers please see page 6.

Sensors - Selux offers a variety of integral sensor options. Sensors are placed on the direct side of the fixture, but can control the Indirect lighting. For details and specifications, please refer to page 9.

Emergency - There are multiple emergency options available - Emergency Circuit, Remote Micro Inverter, and Integral EM Battery Pack Please consult factory for use of sensors with emergency options. For more details on EC op-tions, see page 7.

Thermal Performance:

Ambient Operating Temperature - Luminaires suitable for maximum ambient temperature of 35°C (95°F) for all drivers.Luminaires are suitable for minimum ambient temperatures of:-40ºC (-40ºF) for DIM, DM, DML, and DMD drivers.0ºC (32ºF) for DC2 and DE1 drivers.

Luminaire Finish:

Powder Coat - All Selux luminaries are finished in high quality polyester powder coating in our Tiger Drylac certified facility and are tested in accordance with test specifications for coatings from ASTM and PCI.

All products undergo a five stage intensive pretreatment process where product is thor-oughly cleaned, phosphated, and sealed. Selux powder coated products provide excellent salt and humidity resistance as well as ultra violet resistance for color retention.

Standard interior colors are White (WH), Semi-Matte Black (BL), and Silver (SV). Selux premium colors (SP) are available, please specify from your Selux color selection guide.

Warranty:

5 Year Limited LED Luminaire Warranty - Selux offers a 5 Year Limited Warranty to the original purchaser that the M100 series LED luminaire shall be free from defects in mate-rial and workmanship for up to five (5) years from date of shipment. This limited warranty covers the LED driver and LED light engine when installed according to Selux instructions and operated within the Ambient Temperature. For additional details and exclusions, see “Selux Terms and Condition of Sale.”

Certifications and Compliance:

NRTL - For Dry and Damp location (I.E. cULus)ADA CompliantARRA CompliantRoHS Compliant

LW lens shown for reference

Page 3 of 11 (Rev. 10/2019)

M100LED DI_v9.0

In a continuing effort to offer the best product possible, we reserve the right to change, without notice, specifications or materials that in our opinion will not alter the function of the product. Specification sheets found at www.selux.us are the most recent versions and supercede all other printed or electronic versions.

Selux Corporation © 2019, T 845-834-1400, 800-735-8927, F 845-834-1401, www.selux.us

M100LED Direct/Indirect

Cable Mounting (C)

Outlet box for feed only (by others)

L1DI Cable (C) Suspension Detail (Feed location(s) only)

L1DI Cable (C) Suspension Detail (Non-Feed location(s) only)

Cross bar with 1/4”-20 rod and ground screw

1/4” x 5” diameter canopy (White)

2x White cable stay

Cord strain relief bushing

1/4”-20 Threaded rod (supplied and installed in the field by others)

1. Ø1/16” Aircraft Cable with chrome gripper for easy adjustment (48” max. from ceiling to luminaire).

2x Outlet box screws (by others)

1/4”-20 Slip ring coupler

Feed cord (White)

1/16” Aircraft cable

1/4”-20 Slip ring coupler

1/16” Aircraft cable

Chrome gripper

Luminaire

1/4” x 2” diameter canopy (White)

Cable Mounting (C) - Dimensions

Nominal Length

“A” Housing Length

* “B” (Ref.) End Suspensions

“C” Mid. Suspension

“D” Feed Location

“E” Illuminated Length

Feet/Inch MM Feet/Inch MM Feet/Inch MM Feet/Inch MM Feet/Inch MM

02 (2 ft.) 2' - 1/4" 616 2” 50.8 1' - 10 1/2" 572 0' - 7/8" 22 2” 50.8

03 (3 ft.) 3' - 5/16" 923 2” 50.8 2' - 10 5/8" 879 0' - 7/8" 22 2” 50.8

04 (4 ft.) 3' - 11 7/16" 1205 3” 76.2 3' - 9 11/16" 1161 0' - 7/8" 22 3" 76.2

05 (5 ft.) 4' - 11 7/16" 1510 3” 76.2 4' - 9 11/16" 1466 0' - 7/8" 22 3" 76.2

06 (6 ft.) 5' - 11 7/16" 1815 3” 76.2 5' - 9 11/16" 1770 0' - 7/8" 22 3" 76.2

07 (7 ft.) 6' - 11 7/16" 2119 3” 76.2 6' - 9 11/16" 2075 0' - 7/8" 22 3" 76.2

08 (8 ft.) 7' - 11 7/16" 2424 3” 76.2 7' - 9 11/16" 2380 0' - 7/8" 22 3" 76.2

09 (9 ft.) 8' - 11 7/16" 2729 3” 76.2 8' - 9 11/16" 2685 0' - 7/8" 22 3" 76.2

10 (10 ft.) 9' - 11 7/16" 3034 3” 76.2 9' - 9 11/16" 2990 0' - 7/8" 22 3" 76.2

11 (11 ft.) 10' - 11 7/16" 3339 3” 76.2 10' - 9 11/16" 3294 0' - 7/8" 22 3" 76.2

12 (12 ft.) 11' - 11 7/16" 3643 3” 76.2 11' - 9 11/16" 3599 0' - 7/8" 22 3" 76.2

*Dimension(s) rounded to the nearest 1/16” with a ± 1/16” (1mm) tolerance.

Chrome gripper

Luminaire

Cable Mounting (C)

Min. 5/8” to Max. 3/4”

Page 4 of 11 (Rev. 10/2019)

M100LED DI_v9.0

In a continuing effort to offer the best product possible, we reserve the right to change, without notice, specifications or materials that in our opinion will not alter the function of the product. Specification sheets found at www.selux.us are the most recent versions and supercede all other printed or electronic versions.

Selux Corporation © 2019, T 845-834-1400, 800-735-8927, F 845-834-1401, www.selux.us

M100LED Direct/Indirect

Stem Mounting (S and RS)

Outlet box (supplied and installed by others)

L1DI Swivel Stem (S) Suspension Detail (feed wires through stem supplied by others)

L1DI Rigid Stem (RS) Suspension Detail (feed wires through stem supplied by others)

Hemispherical assembly

3/8” IP Crossbar with ground screws

1 7/16” x 5” diameter canopy (White)

1. Ø5/8” Swivel Stem provides 30° swivel and can be cut in field (48” max. from ceiling to luminaire).

2. Ø5/8” Rigid Stem is fixed and is not able to be cut/adjusted in field (48” max. from ceiling to luminaire).

Cotter pin

3/8” IP steel swivel stem (White)

Luminaire

Luminaire

Outlet box (supplied and installed by others)

3/8” IP nipple (supplied and installed by others)

Suspension hickey

1/4” x 5” diameter Canopy (White)

Canopy securing screw

Swivel (S) and Rigid Stem (RS) Mountings - Dimensions

Nominal Length

“A” Housing Length

* “B” (Ref.) End Suspensions

“C” Mid. Suspension

“D” Feed Location

“E” Illuminated Length

Feet/Inch MM Feet/Inch MM Feet/Inch MM Feet/Inch MM Feet/Inch MM

02 (2 ft.) 2' - 1/4" 616 0' - 7/8" 22 1' - 10 1/2" 572 0' - 7/8" 22 1' - 9" 534

03 (3 ft.) 3' - 5/16" 923 0' - 7/8" 22 2' - 10 5/8" 879 0' - 7/8" 22 2' - 7 5/8" 803

04 (4 ft.) 3' - 11 7/16" 1205 0' - 7/8" 22 3' - 9 11/16" 1161 0' - 7/8" 22 3' - 8 3/16" 1123

05 (5 ft.) 4' - 11 7/16" 1510 0' - 7/8" 22 4' - 9 11/16" 1466 0' - 7/8" 22 4' - 8 1/4" 1428

06 (6 ft.) 5' - 11 7/16" 1815 0' - 7/8" 22 5' - 9 11/16" 1770 0' - 7/8" 22 5' - 8 1/4" 1733

07 (7 ft.) 6' - 11 7/16" 2119 0' - 7/8" 22 6' - 9 11/16" 2075 0' - 7/8" 22 6' - 8 3/16" 2037

08 (8 ft.) 7' - 11 7/16" 2424 0' - 7/8" 22 7' - 9 11/16" 2380 0' - 7/8" 22 7' - 8 3/16" 2342

09 (9 ft.) 8' - 11 7/16" 2729 0' - 7/8" 22 8' - 9 11/16" 2685 0' - 7/8" 22 8' - 8 3/16" 2647

10 (10 ft.) 9' - 11 7/16" 3034 0' - 7/8" 22 9' - 9 11/16" 2990 0' - 7/8" 22 9' - 8 1/4" 2952

11 (11 ft.) 10' - 11 7/16" 3339 0' - 7/8" 22 10' - 9 11/16" 3294 0' - 7/8" 22 10' - 8 1/4" 3257

12 (12 ft.) 11' - 11 7/16" 3643 0' - 7/8" 22 11' - 9 11/16" 3599 0' - 7/8" 22 11' - 8 3/16" 3561

*Dimension(s) rounded to the nearest 1/16” with a ± 1/16” (1mm) tolerance.

Swivel Stem (S) and Rigid Stem (RS) Mounting

Dress nut

Square nut

Square nut

Square nut

Square nut

3/8” IP steel stem (White)

Dress nut

Page 5 of 11 (Rev. 10/2019)

M100LED DI_v9.0

In a continuing effort to offer the best product possible, we reserve the right to change, without notice, specifications or materials that in our opinion will not alter the function of the product. Specification sheets found at www.selux.us are the most recent versions and supercede all other printed or electronic versions.

Selux Corporation © 2019, T 845-834-1400, 800-735-8927, F 845-834-1401, www.selux.us

M100LED Direct/Indirect

Wall Mounting (W)

For patterns and configurations that are to include a wall mounted option, please see page 9 for details.

1. Aluminum wall bracket (by Selux)2. 4”x4” or 2”x4” J-Box at feed location (supplied and installed by

others).3. 1/4”-20 Threaded rod, 1/4”-20 lock washer and 1/4”-20 nut required to

anchor the wall bracket. Mounting hardware supplied and installed to code by others.

Wall Mount (W) (Covers a 4x4 or 2x4 J-Box)

Wall (W) Mount - Dimensions

Nominal Length

“A” Housing Length

* “B” (Ref.) End Suspensions

“C” Mid. Suspension

“D” Feed Location

Feet/Inch MM Feet/Inch MM Feet/Inch MM Feet/Inch MM

02 (2 ft.) 2' - 1/4" 616 0' - 3 1/8" 79 1' - 6 1/16" 458 0' - 3 1/8" 79

03 (3 ft.) 3' - 5/16" 923 0' - 6 1/8" 156 2' - 1/8" 612 0' - 6 1/8" 156

04 (4 ft.) 3' - 11 7/16" 1205 0' - 6 1/8" 156 2' - 11 3/16" 894 0' - 6 1/8" 156

05 (5 ft.) 4' - 11 7/16" 1510 0' - 6 1/8" 156 3' - 11 3/16" 1199 0' - 6 1/8" 156

06 (6 ft.) 5' - 11 7/16" 1815 0' - 6 1/8" 156 4' - 11 3/16" 1504 0' - 6 1/8" 156

07 (7 ft.) 6' - 11 7/16" 2119 0' - 6 1/8" 156 5' - 11 3/16" 1808 0' - 6 1/8" 156

08 (8 ft.) 7' - 11 7/16" 2424 0' - 6 1/8" 156 6' - 11 3/16" 2113 0' - 6 1/8" 156

09 (9 ft.) 8' - 11 7/16" 2729 0' - 6 1/8" 156 7' - 11 3/16" 2418 0' - 6 1/8" 156

10 (10 ft.) 9' - 11 7/16" 3034 0' - 6 1/8" 156 8' - 11 3/16" 2723 0' - 6 1/8" 156

11 (11 ft.) 10' - 11 7/16" 3339 0' - 6 1/8" 156 9' - 11 3/16" 3028 0' - 6 1/8" 156

12 (12 ft.) 11' - 11 7/16" 3643 0' - 6 1/8" 156 10' - 11 3/16" 3332 0' - 6 1/8" 156

*Dimension(s) rounded to the nearest 1/16” with a ± 1/16” (1mm) tolerance.

4” (102mm)

4” (102mm)

1” (25mm)

4 15/16” (126mm)

Page 6 of 11 (Rev. 10/2019)

M100LED DI_v9.0

In a continuing effort to offer the best product possible, we reserve the right to change, without notice, specifications or materials that in our opinion will not alter the function of the product. Specification sheets found at www.selux.us are the most recent versions and supercede all other printed or electronic versions.

Selux Corporation © 2019, T 845-834-1400, 800-735-8927, F 845-834-1401, www.selux.us

M100LED Direct/Indirect

Driver Quantity

2 ft. 3 ft. 4 ft. 5 ft. 6 ft. 7 ft. 8 ft. 9 ft. 10 ft. 11 ft. 12 ft. RUN

DIM 1 1 2 3 4 3 4 5 6 5 6Approximately 2 driver per 4 ft.

DM, DML and DMD drivers 1 1 2 2 2 3 4 4 4 5 6Approximately 2 drivers per 4 ft.

DC2 and DE1 drivers 1 2 2 3 4 4 4 5 6 6 6 Consult Factory

Drivers:

0-10V linear dimming (DIM)Luminaires supplied with drivers offering the capability of either normal switched operation or 0-10V dimming for linear dimming curve. Fixtures ship wired for dimming. For on/off functionality, simply cap the dimming leads. Minimum dimming level preset at factory to 1%. (Due to size con-straints, 1’ luminaires are supplied with a driver from a different manufac-turer than 2’ and above luminaires. For details, please consult factory.)

eldoLED SOLOdrive 0-10V linear dimming (DM)Luminaires supplied with SOLOdrive 0-10V dimming driver for linear dim-ming curve. Minimum dimming level preset at factory to 1%. For “dim to dark” (down to 0.1%), please consult factory.

eldoLED SOLOdrive 0-10V logarithmic dimming (DML)Luminaires supplied with SOLOdrive 0-10V dimming driver for logarithmic dimming curve. Minimum dimming level preset at factory to 1%. For “dim to dark” (down to 0.1%), please consult factory.

eldoLED SOLOdrive DALI dimming (DMD)Luminaires supplied with SOLOdrive DALI dimming driver for logarithmic dimming curve. Minimum dimming level preset at factory to 1%. For “dim to dark” (down to 0.1%), please consult factory.

LUTRON 2-wire dimming (DC2)Luminaires supplied with Hi-Lume 2-wire dimming driver (120V only) programmed for Constant Current Reduction (CCR). For Pulse Width Modulation (PWM) dimming, please consult factory. Minimum dimming level down to 1%.

LUTRON EcoSystem dimming (DE1)Luminaires supplied with Hi-Lume EcoSystem (4 wire, digital link) dim-ming driver programmed for Constant Current Reduction (CCR). For Pulse Width Modulation (PWM) dimming, please consult factory. Minimum dimming level down to 1% with SoftOn/FadeToBlack.

* For control recommendations, please consult factory.

*For inrush and control current, please refer to the driver manufacturers’ spec sheets.

Wiring Diagrams Sensor Wiring Diagrams

ENLIGHTED

ELDO 0-10V

SENSORSWITCH

(+)(-) 0-10V AUX (+)

AUX (-)

LED LIGHTENGINE

CONTROL UNITCU-4E-FM

SENSORSU-5E-IL

Live

120

/277

V

Neu

tra

l

blu

ew

hite

whitered

purplegray

Enlighted

DIM DRIVER

- The following wire(s) are in addition to the standard above -

Gray = (-) DALI or 0-10V Dimming ControlPurple = (+) DALI or 0-10V Dimming Control

Violet = “E1” Digital Link Dimming ControlViolet/White = “E2” Digital Link Dimming ControlDE1, DC5

0-10V linear (DIM) 0-10V linear eldoLED SOLOdrive (DM)0-10V logarithmic eldoLED SOLOdrive (DML)DALI eldoLED SOLOdrive (DMD)

DIM, DM, DML & DMD

Lutron EcoSystem (DE1)Lutron 5-Series (DC5)

Page 7 of 11 (Rev. 10/2019)

M100LED DI_v9.0

In a continuing effort to offer the best product possible, we reserve the right to change, without notice, specifications or materials that in our opinion will not alter the function of the product. Specification sheets found at www.selux.us are the most recent versions and supercede all other printed or electronic versions.

Selux Corporation © 2019, T 845-834-1400, 800-735-8927, F 845-834-1401, www.selux.us

M100LED Direct/Indirect

Fuse (FS) - Fusing, luminaires supplied with a in-line fuse located on the hot wire for each feed (supplied with an 8A slow burn fuse).

Damp Location (DL) -Luminaires are suitable for use in damp location(s). Examples of such locations include protected areas under canopies, marquees, roofed porches, and similar locations where the fixture(s) are protected from direct contact with rain, snow, or excessive moisture (such as ocean spray). Interior locations include areas subject to moderate de-grees of moisture, such as basements and certain barns and cold storage buildings.

*For Damp Location with sensors, please consult factory.

Mixed Output - Luminaires have ability to offer mixed light engines (i.e. 1B35 direct and 1B25 indirect) starting at 4’ and then in 2’ steps (i.e. 6’, 8’, 10’, 12’, etc.).

Joiner System - Standard for Runs and Configurations

Separate Switching (SS) - Luminaire available with the Direct side switched separately from the Indirect side starting at the 4’ nominal length and then in 2’ nominal steps, i.e. 6’, 8’, 10’, 12’, etc. Luminaire is intended to be wired to the same panel/breaker (not intended for Emergency use).

* If the project requires different separate switching than outlined above please consult the factory.

*For Separate Switching with sensors, please consult factory.

Emergency Circuit (EC) - Luminaires with EC option compliant to UL 924 listed emergency luminaire. EC luminaires are intended to be wired to separate panels/breakers for emergency use.

- For 1’ to 6’ nominal luminaires, the entire fixture is wired for operation on emergency circuit.

- For 7’ and up nominal luminaires, the first 4’ nominal length is wired for operation by a separate EM circuit by default to meet the required “Life Safety Code” (NFPA 101).

*If a different configuration is needed please consult the factory.

*For EC with sensors, please consult factory.

5/32”

Page 8 of 11 (Rev. 10/2019)

M100LED DI_v9.0

In a continuing effort to offer the best product possible, we reserve the right to change, without notice, specifications or materials that in our opinion will not alter the function of the product. Specification sheets found at www.selux.us are the most recent versions and supercede all other printed or electronic versions.

Selux Corporation © 2019, T 845-834-1400, 800-735-8927, F 845-834-1401, www.selux.us

M100LED Direct / Indirect

Standard Sensor Placement - for other placement options, please consult factory. For functionality and limitations, please see sensor details above.

Lens Aluminum Sensor Plate -to be painted same as fixture unless specified otherwise

Qty 1 Sensor - Beginning Qty 2 Sensor - Beginning and End (9’ fixtures and longer)

Qty 3+ Sensor - For spacing between sensors, please consult the sensor manufacturer

Beginning of Run

Notes: 1. For spacing between sensors, please consult the sensor manufacturer. 2. Exact sensor placement and coverage will be defined by approved factory drawing. 3. Sections controlled by sensors may not be symmetrical - consult factory for layout.

3” (76mm)

* Lit section will be the fixture length minus 3” for sensor plate.

Fixture Length

Lit Section*

3 15/16”” (100mm)

Factory Presets - Sensors come from the sensor manufacturer with factory presets for each of the settings in above chart. Please see sensor manufacturers’ spec sheets for details on presets and re-programming.

Commissioning - Commissioning of sensors and installation by others. Contact sensor manufacturer for details and costs associated with commissioning the system prior to specification of sensors.

Enlighted SU-5E-IL (E)Enlighted Micro Sensor SU-5E-IL (Independent Lighting) provided as standard with an Enlighted CU-4E-FM Fixture Mount Control Unit integral to fixture. If SU-5E-CL (Connected Lighting) or SU-5E-IoT (Internet of Things) is desired, please contact factory. Occupancy/vacancy, thermal, daylight sensing plus Tunable White, Room & Zone control, Internet of Things (IoT) data collection and reporting control. For full details, please see SU-5E-(IoT/CL/IL) spec sheet on the Enlighted website. Must be paired with a 0-10V driver with auxiliary (DIM driver selection). Commissioning by Enlighted.

*Please contact Enlighted for complete details prior to specifying.

Sensor Switch MSD EZ (S)Occupancy/vacancy and daylight harvesting. For full functionality and programming options, select settings option 3. If a different settings option is selected, other settings may be unavailable. For full details, please see MSD EZ spec sheets on the Sensor Switch website. Must be paired with DIM driver selection. Manual control of dimming not available with MSD EZ sensor. *Please contact Sensor Switch for complete details prior to specifying.

*Sensor can control up to 30 drivers. Please refer to driver quantity chart on page 7. Multiple sensors may be required for longer lengths.

Occupancy Vacancy Daylight Harvesting Driver Compatibility

Enlighted SU-5E-IL (E) √ √ √ DIM

Sensor Switch MSD EZ (S) √ √ √ DIM

Sensor Ordering Chart

Quantity Sensor Settings*

x Number of Sensors E Enlighted SU-5E-IL

S Sensor Switch MSD EZ

1 Daylight

2 Occupancy/Vacancy

3 Daylight/Occupancy/Vacancy

* Settings not available with Enlighted

Page 9 of 11 (Rev. 10/2019)

M100LED DI_v9.0

In a continuing effort to offer the best product possible, we reserve the right to change, without notice, specifications or materials that in our opinion will not alter the function of the product. Specification sheets found at www.selux.us are the most recent versions and supercede all other printed or electronic versions.

Selux Corporation © 2019, T 845-834-1400, 800-735-8927, F 845-834-1401, www.selux.us

M100LED Direct/Indirect

Listed below are the minimum lengths and details for standard shapes. These standard shapes can be combined with each other and/or the standard luminaire lengths, ensuring full even illumination. If you have any questions, please consult the factory.

The minimum standard lengths for “L” shapes:- IL90 or V90 open shapes is 4’ x 4’ nominal (example: leg, 90, leg)- IL90 or V90 closed shapes is 6’ x 6’ nominal (example: 90, leg, 90)

(Exception is that the IL90 and V90’s can be joined directly to provide a 4’ x 4’ nominal shape)

*For sensors in configurations, please consult factory

Standard Direct/Indirect shapes/configurations:

For patterns and configurations that are to include a wall-mounted option, please consult factory to identify location, on which side of housing and spacing of brackets required.

The minimum standard lengths for “T” and “X” shapes:- IT90 = 4’ nominal on the short leg and 8’ nominal on the long side- IX90 = 8’ nominal for either direction

Selux is capable of supplying a wide range of project solutions including different shapes, angles, and sizes to meet the project requirements. Due to the complex nature of these project specific layout(s) we ask that you please consult the factory with the project requirements for review.

Project Specific Direct/Indirect shapes/configurations:

Direct/Indirect Lit Corner and Section - Dimensions

IL90 IT90 IX90

Feet/Inch MM Feet/Inch MM Feet/Inch MM

“A” Housing (Outside) 2' - 2 1/16" 662

“A1” Housing (Inside) 1' - 10 1/8" 562

“B” Housing 2' - 2 1/16" 662

* “B1” Ref. 2' - 1/8" 612

“C” Housing 4' - 3/16" 1224

* “C1” Ref. 2' - 1/8" 612

“D” Housing 4' - 3/16" 1224

* “D1” Ref. 2' - 1/8" 612

*Dimension(s) rounded to the nearest 1/16” with a ± 1/16” (1mm) tolerance.

Note: The indirect side of the cable and stem mounted configurations has small unlit sections for suspensions. For wall mounted configurations, the indirect side is fully lit.

Page 10 of 11 (Rev. 10/2019)

L10DI_SS

In a continuing effort to offer the best product possible, we reserve the right to change, without notice, specifications or materials that in our opinion will not alter the function of the product. Specification sheets found at www.selux.us are the most recent versions and supercede all other printed or electronic versions.

Selux Corporation © 2019, T 845-834-1400, 800-735-8927, F 845-834-1401, www.selux.us

M100LED Direct/Indirect

Photometry

258

516

773

1031

1

2

Maximum Candela = 1031 Located At Horizontal Angle = 22.5, Vertical Angle = 1.5# 1 - Vertical Plane Through Horizontal Angles (90 - 270)# 2 - Vertical Plane Through Horizontal Angles (0 - 180)

LW Optics / 69W LED / 4000K CCT

Catalog #: L1DI-1B35-1B35-40-LW-LW-X-04-XX-UNVReport #: 11685024.05 Delievered Lumens: 5677 Input Watts: 69.4848Efficacy: 82 CCT: 4000KCRI: 95.7

528

1055

1583

2110

12

Maximum Candela = 2110 Located At Horizontal Angle = 0, Vertical Angle = .5# 1 - Vertical Plane Through Horizontal Angles (90 - 270)# 2 - Vertical Plane Through Horizontal Angles (0 - 180)

MI Optics / 69W LED / 4000K CCT

Catalog #: L1DI-1B35-1B35-40-MI-MI-X-04-XX-UNVReport #: 11800001.02 Delievered Lumens: 6342 Input Watts: 69.4865Efficacy: 91 CCT: 4000KCRI: 95.7

Page 11 of 11 (Rev. 10/2019)

L10DI_SS

In a continuing effort to offer the best product possible, we reserve the right to change, without notice, specifications or materials that in our opinion will not alter the function of the product. Specification sheets found at www.selux.us are the most recent versions and supercede all other printed or electronic versions.

Selux Corporation © 2019, T 845-834-1400, 800-735-8927, F 845-834-1401, www.selux.us

M100LED Direct/Indirect

Photometry

4000K3500K3000K2700K

Light Engine Lumens Wattages1B45 1.258 1.2851B40 1.137 1.1401B35 1.000 1.0001B30 0.855 0.8381B25 0.766 0.7401B20 0.578 0.552

LWMINBA2A5BW

L100 LED Photometry Multiplier Table

CCT Multiplier

Light Engine Multiplier

1.0000.9720.9630.931

1.0611.0291.0541.008

Lens Multiplier1.0001.050

CCT multipliers apply to the photometry, IES files, and per foot values listed on page one (light engine).

Light engine and lens multiplier supplied for per foot values listed on page one (light engine).