‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’Answering the needs of the market

Ian StewartPassive installer scheme managerMay 2011

Page 2: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

Why is passive fire protection so important?Ø Maintains structural stability of steel frame buildingsØ Reduces deflection of floorsØ Maintains compartmentation Ø Reduces spread of smokeØ Maintains escape routes

What happens if it fails?Ø Potential building collapseØ Potential loss of lifeØ Major rebuilding cost

Page 3: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

Why Passive installer schemes?

• Reduces the risk of loss of life and product failures by ensuring professional installation

• Reduces damage caused to property and hence insurance losses should a fire occur

• Allows installers to comply with AD-B Vol2• Encourages insurers and building control that fire

safety has been given appropriate consideration• Reduced liability

Page 4: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

Benefits of Passive installer schemes• Reduces risk for manufacturers, end users, insurers,

clients, specifiers, contractors, legislators ………• Differentiation for installers• Installer self certifies his work• Encourages maintenance of passive via O&M manuals• Regulatory Reform order• Reduced liability• Create a level playing field for installers

Page 5: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

LPCB Passive installer schemes

Installer schemes are available in the form of Loss Prevention Standard (LPS) for the following Passive Fire Protection products :-

• Fire doors (Maintenance and repair) LPS 1197• Fire shutters (Maintenance and repair) LPS 1197• Smoke barriers (Maintenance and repair) LPS 1197• Fire doors (Installation) LPS 1271• Security doors (Installation) LPS 1271• Fire shutters (Installation) LPS 1271• Smoke barriers (Installation) LPS 1271• Compartment wall systems (LPS 1208 tested) LPS 1500• Penetration, cavity barriers and linear gaps LPS 1531• Board fire protection LPS 1531• Intumescent coatings LPS 1531• Spray fire protection LPS 1531• Fire rated ductwork LPS 1531• Fire resistant dampers LPS 1531• Fire rated compartment walls LPS 1531• Offsite applied intumescent coatings LPS 1531

Page 6: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

• LPS 1500 Issue 2.0

• Requirements for the LPCB Approval and Listing of companies installing fire resistant compartment wall systems in buildings

• This standard defines the requirements for companies installing fire resisting compartment walling systems approved by LPCB to the requirements of LPS 1208.

LPS 1500

Page 7: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

Summary of LPS 1500

• New installer scheme specifically for the installation of LPCB Approved Composite Construction Elements. – Load-bearing compartment walls and partitions– Non Loading bearing compartment walls and partitions – External wall – Curtain wall– Cavity Barriers– Roofs (where fire resistance is required)– Load-bearing compartment floors – Insulated Panels for enclosing production and storage areas in

food factories.

Page 8: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

Typical composite panel application

Screw fixings to steel Fast fire wall construction

Page 9: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

Summary of LPS 1500

• New Approach to Schemes for the Installers of Passive Fire Protection.

• Provides a link between LPCB Approved Products and competency and training of Installers

• Technical site inspection based assessment scheme.

Page 10: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

Summary of LPS 1500

• Applications3 companies approved

• Technical issues1. Distance the panels can be unsupported or unrestrained2. Fire break at wall and soffit3. Door installation4. Penetration details

Page 11: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

• LPS 1531 Issue 1.0

• Requirements for the LPCB Approval and Listing of companies installing or applying passive fire protection products

• This standard defines the requirements for companies installing or applying a generic range of passive fire protection products

LPS 1531

Page 12: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

LPS 1531Installer scheme specifically for the installation of the following passive fire protection products or systems.Appendix: 1. Penetration, cavity barriers and linear gap seals2. Fire rated board and cladding to structural elements3. Intumescent coatings to structural elements4. Fire rated spray materials5. Fire rated ductwork systems6. Fire resisting dampers7. Fire resistant compartment wall systems 8. Offsite application of intumescent coatings to structural elements

Page 13: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

Fire Stopping

Allowing for new cables? Missed out floor penetration

Page 14: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

Fire Stopping

Channel or stud framing missing?

Page 15: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

Fire Stopping

How do you fire stop this?

Page 16: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

Fire Stopping

Use of Foam fillers?Patress seals?

Fire curtains with dampers?

Page 17: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

Intumescent coatings

Exposed external steel balcony What went wrong?

Page 18: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

Intumescent coatingson-site application

High Humidity & low temp

Brush applied too thick

Water damage

Page 19: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

Intumescent coatings – offsite application

Off-site intumescenttouch up and damage repair

Page 20: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

Summary of LPS 1531

• New Approach to Schemes for the Installers of Passive Fire Protection.

• Installers will self certify their work with an LPCB Certificate of Conformity

• Improved standards of passive fire protection productinstallation

• Site surveillance inspection of up to 15% of installations.• Technical site inspection based assessment scheme.

Page 21: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

Summary of LPS 1531

• Applications• Processing 4• Approved 33

• Technical issues1. Fire rated damper installation. (Ref new GBG out at this show)2. Framing out penetrations in drywalls3. Use of PU foams

Page 22: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

LPS 1197 Service and Maintenance of DoorsMaintenance contractors

• LPS1197: Issue 3.0Requirements for the LPCB Approval and Listing of companies Undertaking the Maintenance and Repair of Doorsets, Shutters and Active Smoke/Fire Barriers

• LPCB approved maintenance contractors who repair and maintainfiredoors and shutters are approved in accordance with LPS1197.

• Fire doors (Maintenance and repair) LPS 1197• Fire shutters (Maintenance and repair) LPS 1197• Smoke barriers (Maintenance and repair) LPS 1197

Page 23: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

Summary of LPS1197

• Applications• Approved 12

• Technical issues• None to report• Ensure performance criteria are met.

Page 24: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

LPS 1271 Fire and Security Door InstallersInstallation contractors

• LPS1271: Issue 1.0Requirements for the LPCB Approval and Listing of companies installing fire and security doorsets and shutters and smoke barriers

• LPCB approved maintenance contractors who repair and maintainfiredoors and shutters are approved in accordance with LPS1271.

• Fire doors (Installation) LPS 1271• Security doors (Installation) LPS 1271• Fire shutters (Installation) LPS 1271• Smoke barriers (Installation) LPS 1271

Page 25: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

Summary of LPS1271

• Applications• Processing 2

• Approved 8

• Technical issues• None to report • Ensure performance criteria are met

Page 26: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

Fire doors

Page 27: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

Fire door testing

Page 28: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

Fire resistant shutters

Page 29: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

BRE Passive inspection serviceAn independent third party site inspection can:

ØProvide confidence to all interested parties that the Passive Fire Protectionhas been installed correctly and in accordance with the manufacturersrecommendations.

ØConfirm that the choice of products is suitable for the application.

ØEnsure that the workmanship is of a standard that ensures the fireprotection will meet the design specification.

Inspection is best carried out at an early stage during installation thus enabling the sub-contractor to have the opportunity to rectify any problems rather than impact on the critical path of the construction.

Page 30: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

The Red Books

Products and services approved by us arelisted in the RedBooks • Volume 1 Fire Detection and Alarm products

and services. Related installers.

• Volume 2 Passive fire protection products and services. Security protection systems. Related installers. Management systems. Construction products.

• Available on-line at www.redbooklive.com

• CD and hard copy

Page 31: ‘LPCB Passive Installer Schemes (including LPS … · ‘LPCB Passive Installer Schemes (including LPS 1500/1531/1197/1271)’ Answering the needs of the market Ian Stewart Passive

Thank you for your attention

BRE Global answering the needs of the market

Ian StewartPassive installer scheme managerMay 2011