LMR Electric Fire Pump Controllers with Transfer SwitchFeatures
1-1
For more information visit: www.chfire.com BR05805039K/B
Product Features
FT50 Reduced Voltage - Primary Resistor
January 2006
Run Period Timer
Elapsed Time Meter
Last 2048 Messages
Number of Operations Counter
Microprocessor Control
EATON Cutler-Hammer LMR Transfer SwitchFire Pump Controllers are microprocessorbased. All events surrounding the operation ofthe controller are stored within the memory,thus giving the ability to diagnose andtroubleshoot problems based on an actualhistory of events. Events are time and datestamped.
A main display unit provides a read-out ofparameters such as current pressure, voltsand amps and will display error messages aswell as provide alarm indication. A statusreport is available which provides a record ofthe current state of the controller. The reportcan be printed locally via the printer / recorder.
LCD Message Retrieval
The 2 line liquid crystal display allows viewing ofall messages and event information withoutopening the front door of the controller.Messages can also be downloaded to a laptopcomputer via the communications port locatedon the top of the main microprocessor board.
The run period timer is built into the LMRmicroprocessor and can be accessed via themembrane / keypad. It is programmable from0-45 minutes and should be reset to ten (10)minutes when the controller is placed in service.
The internal microprocessor stores the mostrecent 2048 messages in it’s memory. Themessages can be printed, viewed on the LCDscreen or downloaded to a laptop. Eachmessage is time and date stamped. The LCDdisplay acts as a paperless chart recorder.
Emergency Start Operator
A mechanically operated emergency start handleactivates the motor contactor independent of anyelectrical control circuits or pressure switch input.
The LMR monitors and records the run time ofthe motor, in hours, whenever the pump isrunning. The actual run time can be viewed onthe LCD display in 1 hour increments.
The LMR controller monitors and records thenumber of times the pump has started. The actualcount can be viewed on the LCD display.
The FT50 Transfer Switch Controller isselected when it is necessary to meetlimitations on inrush current. A resistor isinserted in the power supply to the motor for asmooth acceleration. The main contactor by-passes the resistor after a short accelerationtime and applies full voltage to the motorterminals. Starting line current is 65% of theacross-the-line starting inrush (approximately390% of rated full load amperes). The FT50can be programmed for either fully automaticor semi-automatic operations.
Volts and Amps Display
The LCD display located on the main display panel,simultaneously indicates the voltage and amps onall three phases of power coming into the controller.
NEMA 2 Enclosures
All LMR controllers come standard with NEMA2 enclosures unless otherwise ordered.Available options include: NEMA 3R, 4, 4X, 12.
Product Description
Electrically and MechanicallyInterlocked
Voltage & Frequency Sensing
Engine Test Button
Alarm Relay
Automatic Transfer
The Automatic Transfer Switch Option may beadded to any FD type Fire Pump Controllerwhenever automatic transfer from normal toalternate power is required.The automatic Transfer Switch and Fire PumpController are each mounted in separateenclosures to form one unit and interwired.
The alarm relay is de-energized to indicate an absenceof an alarm state and energized to indicate thepresence of an alarm condition.Alarm conditions include:
Improper Circuit Breaker OperationMotor Operator FailureLockoutFailsafe ConditionAborted Engine TestAborted Plant ExerciserUnsuccessful in-phase Transition
The ATC-300 controller membrane is equipped withseven keypad input buttons which are used toprogram the controller as well as set operatingparameters.
The ATC-300 continuously monitors the normal sourcefor out of range setpoint values. When the source isoutside the dropout setpoints, the source will becomeunavailable.This prompts a transfer to the alternate source.Retransfer occurs when the normal source’s frequencyand/or voltage return within pickup setpoints.
The FT Series TransferSwitches will perform anautomatic transfer fromNormal to Alternate sourcewhen the Voltage drops to85% of normal, or there isa loss of any phase and/orPhase Reversal.
Five LED’s indicate the status of the powersources.Source 1 Available Source 1 ConnectedSource 2 Available Source 2 ConnectedUnit Status
The panel mounted, multi-function, microprocessorbased ATC-300 controlleraccurately monitors twopower sources andprovides the necessaryintelligence to reliablyoperate the transfer switchthrough a series ofprogrammed sensing andtiming functions.
ATC - 300
LED Status Indication
Keypad Programming
The FT Series transfer switch operatingmechanisms are mechanically interlocked toprevent the normal and alternate source fromconnecting at the same time.The switch operates upon signals received from theATC-300 controller.
An engine test button is provided on the ATC-300controller that can be used to test the Source 2(generator) engine. The operator can select theengine run test time (0-600 minutes).As well, a silence pushbutton is provided whichde-energizes the alarm bell.
Technical Data and Specifications
Standards & Certification
Line Terminals (Incoming Cables)
Status & Alarm Indication
BR05805039K/B
Pressure
102 PSI
The LMR Electric Fire Pump Controllers meetor exceed the requirements of UnderwritersLaboratories, Underwriters LaboratoriesCanada, Factory Mutual, the CanadianStandards Association, New York City buildingcode, CE mark requirements and are built toNFPA 20 standards.
An additional output relay labeled Future #1,can be user programmed to operate for nine(9) different functions. Programming is done inthe LMR menu using the membrane / keypad.
Product Features
Additional Output Relay
Common Alarm Relay and Contacts
The LMR controller has a common alarm relaywhich de-energizes whenever there are anyalarm conditions present. This relay isenergized under normal conditions and hasLED status indication on the main relay board.
LMR Electric Fire Pump Controllers with Transfer SwitchFeatures
1-2
FT50 Reduced Voltage - Primary Resistor
January 2006
For more information visit: www.chfire.com
N. Y. C.APPROVED
* Coils available: 380V-50Hz, 380V-60Hz, 415V-50Hz, 415V-60Hz.
Line Terminals on Main Isolation Switch (Incoming Cables)
Max. Hp
200 - 208
40 40 100 100 -
75 75 150 200 200
100 125 200 250 300
150 200 350 400 400
30 30 60 75 100
LINE VOLTAGE
220 - 240 * 380 - 415 440 - 480 550 - 600
Qty. & Cable Sizes Service Entrance GND.LUGQty. & Cable Sizes
(1)#14-1/0 PER (CU/AL) (1)#14-2/0 (CU/AL)
(1)#4-4/0 PER (CU/AL) (1)#14-2/0 (CU/AL)
(1)#3-350MCM (CU/AL) (1)#4-350MCM (CU/AL)
(2)3/0-250MCM (CU/AL) (2)#4-350MCM (CU/AL)
(2)250-350MCM (CU/AL) (2)#2-600MCM (CU/AL)
Alarm & Status Indication
The display panel is equipped with nine redAlarm LED’s and nine green Status LED’s whichindicate various functions and operations of thecontroller. The membrane keypad has curveddome windows which allow viewing from a wideangle.
Extra Set of Form-C Contacts forPhase Reversal and Phase Failure
The phase reversal and phase failure relayscome standard with an extra set of contactsthat can be used for remote alarm indication.
Pressure Transducer: 0 - 600 psi
Each LMR controller is equipped with astainless steel, 0-600 psi pressure switchcapable of withstanding a momentary surgepressure of 1000 psi.
NEMA Rated Contactors
NEMA rated Freedom or A200 Series EATONCutler-Hammer contactors are used in all LMRfire pump controllers. A wide variety of coilvoltages are available for domestic andinternational use.
Weekly Test Timer
The weekly test timer allows the user to set thecontroller to automatically start and stop thecontroller once per week. The number of weeksbetween tests is set via the front keypad. Theweekly test date and time can be viewed on theLCD display.
Sequential Start Timer
The sequential start timer is used to program astart delay after an automatic start request. Thisfunction is used for staging the start of pumps in amultiple pump application and also in Dieselbackup applications.
The industrial grade thermal printer is housedin a rugged steel enclosure within the controller.The on/off switch, feed and reset buttons arefront accessible. A bi-color status LED is alsovisible on the front of the printer. Greenindicates - “Printer Operational’ while yellowindicates - “Out of Paper”.
Printer / Recorder
Power TransferSwitch
�� ������ �� ������� ��������
�� ����� ��� ������� ��������
�� ���� � �����
�������� ���������
���������� �������������� �������
�� ���� ��� �� �����
�� ������ �� ������� ��������
�� ����� ��� ������� ��������
�������� ���������
���������� �������������� �������
����
�����
���� � �
���� �
���� �
����
��������� ��������
������
��� ����
� � ������
�� �����
���������
���������
�� �����
���� ���
���� ���
����
����
Power TransferSwitch
�� ������ �� ������� ��������
�� ����� ��� ������� ��������
�������� ���������
���������� �������������� �������
�� ���� � �����
�� ���� ��� �� �����
ControllerFire Pump
���
�� ���� � �����
�� ���� ��� �� �����
Dimensions
For more information visit: www.chfire.com
1-3
N. Y. C.APPROVED
NOTES:1. All enclosures finished in FirePump red.2. Cable Entrance either top or bottom.3. Standard Enclosure type NEMA 2.
FT50 Primary Resistor
Withstand Rating
Standard Intermediate High
Line VoltageMotor Hp Approx. WeightLbs. (Kg)
5 - 40
5 - 50
5 - 75
5 - 100
5 - 100
200 - 208V
220 - 240V
* 380 - 415V
440 - 480V
550 - 600V 25,000 100,000
150,000 200,000100,000 610
(277)
* Coils available: 380V-50Hz, 380V-60Hz, 415V-50Hz, 415V-60Hz.
LMR Electric Fire Pump Controllers with Transfer SwitchFeatures
FT50 Reduced Voltage - Primary Resistor
January 2006
BR05805039K/B
Power TransferSwitch
�� ������ �� ������� ��������
�� ����� ��� ������� ��������
�� ���� � �����
�������� ���������
�� ���� ��� �� �����
���������� �������������� �������
��������� ��������
���� �
���� �
���� � �
����
���� ���
���� ���
�� �����
� � ������
��� ����
������
�� �����
���������
���������
����
����
�����
����
�� ������ �� ������� ��������
�� ����� ��� ������� ��������
�� ���� � �����
�������� ���������
���������� �������������� �������
�� ���� ��� �� �����
Power TransferSwitch Controller
Fire Pump
���
�� ������ �� ������� ��������
�� ����� ��� ������� ��������
�������� ���������
���������� �������������� �������
�� ���� � �����
�� ���� ��� �� �����
Dimensions
For more information visit: www.chfire.com
1-4
N. Y. C.APPROVED
NOTES:1. All enclosures finished in FirePump red.2. Cable Entrance either top or bottom.3. Standard Enclosure type NEMA 2.
* Coils available: 380V-50Hz, 380V-60Hz, 415V-50Hz, 415V-60Hz.
LMR Electric Fire Pump Controllers with Transfer SwitchFeatures
FT50 Primary Resistor
FT50 Reduced Voltage - Primary Resistor
Withstand Rating
Standard Intermediate High
Line VoltageMotor Hp Approx. WeightLbs. (Kg)
50 - 150
60 - 200
100 - 300
125 - 400
125 - 500
200 - 208V
220 - 240V
* 380 - 415V
440 - 480V
550 - 600V 25,000 35,000
Consult Factory Consult Factory100,000 1190
(540)
January 2006
BR05805039K/B
�����
����
��
�����
Electrical Wiring Schematic
For more information visit: www.chfire.com
N. Y. C.APPROVED
1-5LMR Electric Fire Pump Controllers with Transfer SwitchFeatures
FT50 Primary Resistor
FT50 Reduced Voltage - Primary Resistor
January 2006
BR05805039K/B
EM
ER
GE
NC
YS
OU
RC
E
AT
C-3
00
CO
NT
RO
LL
ER
SO
UR
CE
NO
RM
AL
CO
NT
RO
LC
IRC
UIT
1-6
For more information visit: www.chfire.com
N. Y. C.APPROVED
LMR Electric Fire Pump Controllers with Transfer SwitchFeatures
Electrical Wiring Schematic
FT Automatic Power Transfer Switch
FT50 Reduced Voltage - Primary Resistor
January 2006
BR05805039K/B
UT
ILIT
Y#2
AT
C-3
00
CO
NT
RO
LL
ER
UT
ILIT
Y
CO
NT
RO
LC
IRC
UIT
#1
Electrical Wiring Schematic
1-7LMR Electric Fire Pump Controllers with Transfer SwitchFeatures
For more information visit: www.chfire.com
N. Y. C.APPROVED
FT2U Automatic Power Transfer Switch c/w Second Utility
FT50 Reduced Voltage - Primary Resistor
January 2006
BR05805039K/B
Options - Wiring Diagram
Main Terminal Block: TB1 Transfer Switch Terminal Block
Typical Controller Connection
Relay Card
NOTES:1. Terminal 49 is common to all dry contact inputs.DO NOT APPLY A VOLTAGE ON THESE TERMINALS2. Contacts shown in de-energized state (Fail Safe).
NOTES:1. To Control Circuit2. Spare for Customer Connections3. To TB14. To Shunt Trip5. Contacts Shown in De-Energized State - (Fail Safe)
1-8LMR Electric Fire Pump Controllers with Transfer SwitchFeatures
FT50 Reduced Voltage - Primary Resistor
For more information visit: www.chfire.com
January 2006
BR05805039K/B
Catalog Number Selection
FT50 PRIMARY RESISTOR Controller Catalog Numbering System
For more information visit: www.chfire.com
1-9LMR Electric Fire Pump Controllers with Transfer SwitchFeatures
FT50 Reduced Voltage - Primary Resistor
January 2006
BR05805039K/B
Catalog Number Selection Chart - FT50 (Gen Set) Catalog Number Selection Chart - FT50 (Gen Set)
Catalog Number Voltage Hp Price Catalog Number Voltage Hp Price
FT50-15A 200-208V 15 $18,360 FT50-15D 440 - 480V 15 $18,360
FT50-20A 60 HZ 20 $18,360 FT50-20D 60 HZ 20 $18,360
FT50-25A 25 $18,360 FT50-25D 25 $18,360
FT50-30A 30 $18,580 FT50-30D 30 $18,360
FT50-40A 40 $20,420 FT50-40D 40 $18,440
FT50-50A 50 $20,420 FT50-50D 50 $18,480
FT50-60A 60 $22,440 FT50-60D 60 $20,260
FT50-75A 75 $22,840 FT50-75D 75 $20,500
FT50-100A 100 $26,660 FT50-100D 100 $21,520
FT50-125A 125 $32,880 FT50-125D 125 $24,380
FT50-150A 150 $38,740 FT50-150D 150 $25,300
FT50-15B 220 - 240V 15 $18,360 FT50-200D 200 $28,020
FT50-20B 60 HZ 20 $18,360 FT50-250D 250 $35,140
FT50-25B 25 $18,360 FT50-300D 300 $35,840
FT50-30B 30 $18,360 FT50-350D 350 $43,600
FT50-40B 40 $20,420 FT50-400D 400 $43,600
FT50-50B 50 $20,460 FT50-15E 550 - 600V 15 $18,360
FT50-60B 60 $22,440 FT50-20E 60 HZ 20 $18,360
FT50-75B 75 $22,460 FT50-25E 25 $18,360
FT50-100B 100 $25,600 FT50-30E 30 $18,360
FT50-125B 125 $32,880 FT50-40E 40 $18,440
FT50-150B 150 $33,800 FT50-50E 50 $18,480
FT50-200B 200 $39,340 FT50-60E 60 $20,260
FT50-15C 380 - 415V 15 $18,360 FT50-75E 75 $20,280
FT50-20C 50 / 60 HZ 20 $18,360 FT50-100E 100 $21,520
FT50-25C 25 $18,360 FT50-125E 125 $23,700
FT50-30C 30 $18,360 FT50-150E 150 $24,620
FT50-40C 40 $18,440 FT50-200E 200 $25,900
FT50-50C 50 $18,480 FT50-250E 250 $34,080
FT50-60C 60 $20,480 FT50-300E 300 $35,840
FT50-75C 75 $20,500 FT50-350E 350 $38,660
FT50-100C 100 $22,680 FT50-400E 400 $38,660
FT50-125C 125 $24,380 FT50-450E 450 $46,600
FT50-150C 150 $28,020 FT50-500E 500 $46,600
FT50-200C 200 $35,140
FT50-250C 250 $40,080
FT50-300C 300 $40,780
1-10LMR Electric Fire Pump Controllers with Transfer SwitchFeatures
For more information visit: www.chfire.com
Catalog Number Selection
FT50 - Adder for Second Utility Alternate Power Source - Option 2U
Standard FT Controlle r + 2U Dual Utility Price Adder = Dual Utility Trans fe r Sw itch Controlle r
FT50-100D-LMR-L1-X1 + 2U = FT50-100D-LMR-L1-X1-2U
21,520.00 + 4,010.00 = 25,530.00
FT50 Reduced Voltage - Primary Resistor
Catalog Number Selection Chart - 2nd Utility Adder Catalog Number Selection Chart - 2nd Utility Adder
Catalog Number Voltage Hp 2U Adder Price Catalog Number Voltage Hp 2U Adder Price
FT50-15A 200-208V 15 $4,010 FT50-15D 440 - 480V 15 $4,010
FT50-20A 60 HZ 20 $4,010 FT50-20D 60 HZ 20 $4,010
FT50-25A 25 $4,010 FT50-25D 25 $4,010
FT50-30A 30 $4,010 FT50-30D 30 $4,010
FT50-40A 40 $4,010 FT50-40D 40 $4,010
FT50-50A 50 $4,010 FT50-50D 50 $4,010
FT50-60A 60 $4,010 FT50-60D 60 $4,010
FT50-75A 75 $4,010 FT50-75D 75 $4,010
FT50-100A 100 $4,010 FT50-100D 100 $4,010
FT50-125A 125 $5,750 FT50-125D 125 $4,010
FT50-150A 150 $5,750 FT50-150D 150 $4,010
FT50-15B 220 - 240V 15 $4,010 FT50-200D 200 $4,010
FT50-20B 60 HZ 20 $4,010 FT50-250D 250 $4,010
FT50-25B 25 $4,010 FT50-300D 300 $5,750
FT50-30B 30 $4,010 FT50-350D 350 $5,750
FT50-40B 40 $4,010 FT50-400D 400 $5,750
FT50-50B 50 $4,010 FT50-15E 550 - 600V 15 $4,010
FT50-60B 60 $4,010 FT50-20E 60 HZ 20 $4,010
FT50-75B 75 $4,010 FT50-25E 25 $4,010
FT50-100B 100 $4,010 FT50-30E 30 $4,010
FT50-125B 125 $4,010 FT50-40E 40 $4,010
FT50-150B 150 $5,750 FT50-50E 50 $4,010
FT50-200B 200 $5,750 FT50-60E 60 $4,010
FT50-15C 380 - 415V 15 $4,010 FT50-75E 75 $4,010
FT50-20C 50 / 60 HZ 20 $4,010 FT50-100E 100 $4,010
FT50-25C 25 $4,010 FT50-125E 125 $4,010
FT50-30C 30 $4,010 FT50-150E 150 $4,010
FT50-40C 40 $4,010 FT50-200E 200 $4,010
FT50-50C 50 $4,010 FT50-250E 250 $4,010
FT50-60C 60 $4,010 FT50-300E 300 $4,010
FT50-75C 75 $4,010 FT50-350E 350 $4,010
FT50-100C 100 $4,010 FT50-400E 400 $5,750
FT50-125C 125 $4,010 FT50-450E 450 $5,750
FT50-150C 150 $4,010 FT50-500E 500 $5,750
FT50-200C 200 $4,010
FT50-250C 250 $4,010
FT50-300C 300 $5,750
To determine the price of a Second Utility Transfer Switch:Add together both the list price of the Standard Transfer Switch Controller and the above price.2U
January 2006
BR05805039K/B
Product Selection
For more information visit: www.chfire.com
FT50 PRIMARY RESISTOR Controller Catalog Numbering System
1-11LMR Electric Fire Pump Controllers with Transfer SwitchFeatures
FT50 Reduced Voltage - Primary Resistor
FT LMR
30 = Across the Line A - Built-in Alarm System40 = Part Winding B - Alarm Bell50 = Primary Resistor C1 - Extra Contacts "Pump Run" (one N.O. std.)60 = Autotransformer C2 - Extra Contacts "AC Power Failure" (two sets std.)70 = Wye Delta (Star-Delta) Open C3 - Extra Contacts "Phase Rev." (two sets std.)80 = Wye Delta (Star-Delta) Closed C4 - Remote Contacts (2 Form C) Low Reservoir90 = Soft Start C5 - Remote Contacts (2 Form C) High Reservoir
E1 - NEMA 3R - Raintight Enclosure
E2 - NEMA 4 - Watertight Enclosure (Ref Dwg. Page 1-3)NEMA 4 - Watertight Enclosure (Ref Dwg. Page 1-4)
Horsepower E3 - NEMA 12 - Industrial Dust Tight Enclosure15 40 100 250 450 E5 - NEMA 4X - Stainless Steel Enclosure (Ref Dwg. Page 1-3)20 50 125 300 500 NEMA 4X - Stainless Steel Enclosure (Ref Dwg. Page 1-4)25 60 150 350 E8 - Tropicalization30 75 200 400 E9 - NEMA 4X - Painted Steel (Ref. Dwg. Page 1-3)
NEMA 4X - Painted Steel (Ref. Dwg. Page 1-4)
E10 - NEMA 4X - 316 Stainless Steel Enclosure (Ref. Dwg. Page 1-3)NEMA 4X - 316 Stainless Steel Enclosure (Ref. Dwg Page 1-4)
Voltage EX - Export CratingA = 200 - 208V 60 HZ F - Floor Stand (Standard c/w floor mounted enclosures)B = 220 - 240V 60 HZ F2 - Floor Stand - 2 Inch HeightC = 380 - 415V 50/60 HZ H - High Withstand Rating (refer to tables)D = 440 - 480V 60 HZ I - Intermediate Withstand Rating (refer to tables)E = 550 - 600V 60 HZ P7 - Low Suction Pressure Switch c/w Pilot Light
P8 - Low Suction Shutdown (Requires P7)
P10 - Pressure Transducer - Sea Water Rated
P13 - Externally Mounted Pressure Transducer
R1 - Space Heater (120 / 220V)
R2 - Space Heater c/w Thermostat
R3 - Space Heater c/w Humidistat
R4 - Low Pump Room Temperature Switch and Pilot LightL1 = English X1 - Printer/Pressure RecorderL2 = French X2 - 4 - Inch Chart Recorder (10 - 300 psi fresh water)L5 = Spanish 2U - Second Utility
Language
Microprocessor Control
OptionsStarting Type
LMR Series
January 2006
BR05805039K/B
Product Selection
Options
For more information visit: www.chfire.com
1-12LMR Electric Fire Pump Controllers with Transfer SwitchFeatures
Designation Description Price
A Built-in Alarm System $350
B Alarm Bell $110
C1 Extra Contacts "Pump Run" (one N.O. std.) $90
C2 Extra Contacts "AC Pow er Failure" (tw o sets std.) $90
C3 Extra Contacts "Phase Rev." (tw o sets std.) $90
C4 Remote Contacts (2 Form C) Low Reservoir $90
C5 Remote Contacts (2 Form C) High Reservoir $90
E1 NEMA 3R - Raintight Enclosure $760
E2 NEMA 4 - Watertight Enclosure (Ref Dw g. Page 1-3) $2,400
NEMA 4 - Watertight Enclosure (Ref Dw g. Page 1-4) $4,400
E3 NEMA 12 - Industrial Dust Tight Enclosure $50
E5 NEMA 4X - Stainless Steel Enclosure (Ref Dw g. Page 1-3) $4,000
NEMA 4X - Stainless Steel Enclosure (Ref Dw g. Page 1-4) $6,000
E8 Tropicalization $550
E9 NEMA 4X - Painted Steel (Ref. Dw g. Page 1-3) $3,200
NEMA 4X - Painted Steel (Ref. Dw g. Page 1-4) $5,200
E10 NEMA 4X - 316 Stainless Steel Enclosure (Ref. Dw g. Page 1-3) $7,200
NEMA 4X - 316 Stainless Steel Enclosure (Ref. Dw g. Page 1-4) $11,000
EX Export Crating $525
F Floor Stand (Standard c/w f loor mounted enclosures) Std.
F2 Floor Stand - 2 Inch Height $25
H High Withstand Rating (refer to tables) $3,230
I Intermediate Withstand Rating (refer to tables) $1,520
L1 Language - English N / C
L2 Language - French N / C
L5 Language - Spanish $200
P7 Low Suction Pressure Sw itch c/w Pilot Light $570
P8 Low Suction Shutdow n (Requires P7) Std.
P10 Pressure Transducer - Sea Water Rated $300
P13 Externally Mounted Pressure Transducer $250
R1 Space Heater (120 / 220V) $250
R2 Space Heater c/w Thermostat $320
R3 Space Heater c/w Humidistat $320
R4 Low Pump Room Temperature Sw itch and Pilot Light $290
X1 Printer/Pressure Recorder $1,075
X2 4 Inch Chart Recorder ( 10 - 300 psi fresh w ater) $700
2U Second Utility See Page 1-10 for details
FT50 Reduced Voltage - Primary Resistor
January 2006
BR05805039K/B
1-13LMR Electric Fire Pump Controllers with Transfer SwitchFeatures
This Page Intentionally Left Blank
For more information visit: www.chfire.com
FT50 Reduced Voltage - Primary Resistor
January 2006
BR05805039K/B
EATONCutler-Hammer403 East Lake Blvd., Airdrie, Alberta, T4A 2G1Canadatel: 403-948-7955fax: 403-948-6967www.chfire.com
© 2006 Eaton CorporationAll Rights ReservedPrinted in CanadaPublication No.: BR05805039K/BJanuary 2006
FIRE PUMP CONTROLLERS
Fire Pump Controller Family
FD20
Limited Service Controller
FD30
Across-the-Line
FD40
Part Winding
FD50
Primary Resistor
FD60
Autotransformer
FD70
WYE DELTAOpen Transition
(Star-Delta)
FD80
WYE DELTAClosed Transition
(Star-Delta)
FD90
Soft Start
FT SERIES
Transfer Switches
FDM
FD100 / 110
Diesel EngineControllers
FDF
FDM
Medium VoltageControllers
FDF
Foam PumpControllers
FDC
CompactControllers
FDR
ResidentialControllers
FDJP / JY
Jockey PumpControllers
FDAP-M
Remote AlarmPanels
For more information on Eaton Cutler-Hammer Fire Pump Controllers, email us at [email protected] or call us at 1-877-860-7955.
January 2006