Section Overview Our comprehensive line of single- and multi-function protection relays safeguard equipment and personnel in order to prevent expensive damage, downtime or injury due to electrical faults. The features and flexibility within the products and the software allow you to select the appropriate protection for each part of your electrical system. Product Selection Guide...................................................... 146-147 Ground-Fault Relays ............................................................ 148-151 Resistance Grounding Systems .......................................... 152-153 Motor and Feeder Protection Relays ..................................154-158 Supplemental Monitors ..............................................................159 Accessories ............................................................................... 160 PROTECTION RELAYS Table of Contents Download our full Protection Relay Catalog For more information on protection relays or to download our full- line relay catalog, visit www.littelfuse.com/ protectionrelays. 145 www.littelfuse.com © 2010 Littelfuse POWR-GARD ® Products Catalog Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Littelfuse POWR-GARD Products Catalog - Protection Relaysstevenengineering.com/.../28PG_PROTECTION-RELAYS.pdf · products for the harshest industrial ... Ground-fault protection relays

  • Upload
    vannhu

  • View
    218

  • Download
    2

Embed Size (px)

Citation preview

Page 1: Littelfuse POWR-GARD Products Catalog - Protection Relaysstevenengineering.com/.../28PG_PROTECTION-RELAYS.pdf · products for the harshest industrial ... Ground-fault protection relays

Section OverviewOur comprehensive line of single- and multi-function protection relays safeguard equipment and personnel in order to prevent expensive damage, downtime or injury due to electrical faults.

The features and flexibility within the products and the software allow you to select the appropriate protection for each part of your electrical system.

Product Selection Guide ......................................................146-147

Ground-Fault Relays ............................................................148-151

Resistance Grounding Systems ..........................................152-153

Motor and Feeder Protection Relays ..................................154-158

Supplemental Monitors ..............................................................159

Accessories ............................................................................... 160

protection relays

Table of Contents

Download our full Protection Relay Catalog

For more information on protection relays or to download our full-line relay catalog, visit www.littelfuse.com/protectionrelays.

145 www.littelfuse.com © 2010 Littelfuse POWR-GARD® Products CatalogCourtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 2: Littelfuse POWR-GARD Products Catalog - Protection Relaysstevenengineering.com/.../28PG_PROTECTION-RELAYS.pdf · products for the harshest industrial ... Ground-fault protection relays

Pro

PGR-5330 PGM-8325 PGN-1000 & PGN-3000

YES NO

pg. 153 pg. 153 pg. 153

Resistance Grounding Systems

RGRESISTANCE GROuNdING

Detect insulation Breakdown

PGR-2601 PGR-3100PGR-3200

YES

YES

pg. 150 pg. 150

pg. 153

pg. 150

NO

NO

Convert System to

Resistance Grounding

Ground-Fault Protection Relays

GROuNd FAulT PROTECTION

GFP

Ground Fault alarm level

PGR-4300 PGR-4704 PGR-5701

YES

pg. 153

pg. 151 pg. 151 pg. 151

NO

10 mA- 5 A

>5 A

NO

YES

Convert System to

Resistance Grounding

Ground Fault protection for Generators

PGR-6100

pg. 156

UnGroUnDeD Dc UnGroUnDeD ac soliDly GroUnDeD ac

Detect Ground Faults

locate Ground Fault & reduce transient

overvoltage

increase Up-time & reduce potential for

arc Flash

Basic

Ground Fault protection

& insulation Monitoring

resistance GroUnDeD ac systeM

pulsing, Digital Filtering, communications

and software

implement resistance Grounding

Product Selection Guide

146

RECO

MM

ENd

Ed P

ROd

uCT

SElE

CT F

EATu

RES

SElE

CT C

ATEG

ORY

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 3: Littelfuse POWR-GARD Products Catalog - Protection Relaysstevenengineering.com/.../28PG_PROTECTION-RELAYS.pdf · products for the harshest industrial ... Ground-fault protection relays

147

Protection Relays

Voltage protection & starter control

PGM-8134 PGM-8325 PGM-8600PGR-7200PGR-6100PGR-6800PGR-6150 PGR-6300PGR-6130 PGR-6200

MOTOR PROTECTION FEEdER PROTECTION SuPPlEMENTAl MONITORING

pg. 157 pg. 157pg. 156 pg. 157pg. 156 pg. 158 pg. 159pg. 159 pg. 153pg. 156

NO YES

Motor Protection Relays Feeder Protection Relays Monitors

SMMP FP

Typically >50 hp

Typically <75 hp

C

OK

Monitors

Monitor Ground

conductor

Monitor neutral to

Ground

Monitor insulation

Basic aDVanceD

Ground Fault protection

& insulation Monitoring

Multi-Function ieee/iec overload

protection

stanDarD aDVanceD pUMps

protection for low-Voltage Motors

(<1000 V)

Multi-Function overload

protection

Motor & Undercurrent

protection

RECOM

MEN

dEd

PROd

uCT

SElECT FEATuRES

SElECT CATEGO

RY

147Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 4: Littelfuse POWR-GARD Products Catalog - Protection Relaysstevenengineering.com/.../28PG_PROTECTION-RELAYS.pdf · products for the harshest industrial ... Ground-fault protection relays

What is a Ground Fault? A ground fault is an inadvertent contact between an energized conductor and ground or equipment frame. The return path of the fault current is through the grounding system and any personnel or equipment that becomes part of that system. Ground faults are frequently the result of insulation breakdown, but can also be caused by other forms of cable damage or human error.

It is important to note that damp, wet, and dusty environments require extra diligence in design and maintenance. Since water is conductive, it exposes degradation of insulation and increases the potential for hazards to develop.

Ground faults represent the vast majority of electrical faults experienced in most facilities. In fact, some studies have indicated that ground faults can make up more than 95% of the recorded electrical faults. By quickly detecting the fault and initiating the appropriate response, ground-fault relays minimize the damage and help protect personnel.

Ground-Fault Relays

With 35 years of experience designing and manufacturing products for the harshest industrial markets, POWR-GARD® ground-fault relays are out-of-box dependable and field-proven to be reliable in the toughest applications.

Ground faults are the most common type of fault in an electrical system, and most electrical codes require ground-fault protection for industrial systems.

Provides sensitive ground-fault protection without false tripping. Ground-fault relays are intelligent devices that are able to detect electrical problems in the early stages, minimizing the impact. This significantly reduces the damage, allowing for quick repairs.

RElIABIlITYSAFETY dOWNTIME

Ground-fault protection relays improve safety for workers and equipment without affecting the uptime of critical operations. Important in manufacturing environments, sensitive ground-fault relays with advanced filtering will detect the breakdown in insulation caused by moisture, vibration, chemicals, and dust.

The First Step in Protecting Equipment And Personnel

148Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 5: Littelfuse POWR-GARD Products Catalog - Protection Relaysstevenengineering.com/.../28PG_PROTECTION-RELAYS.pdf · products for the harshest industrial ... Ground-fault protection relays

Avoid False OperationPOWR-GARD® ground-fault relays are uniquely suited for use on systems with significant harmonic content, with microprocessor-based DFT-filtering technology. Selectable DFT filtering and peak detection algorithms are available to allow excellent filtering for both fixed-frequency and variable- frequency applications.

Feeders

Motors

Generators

Welders

Process Heaters

Variable-Frequency driVes

Simplify InstallationPOWR-GARD ground-fault relays can be surface and DIN-rail mounted, or panel mounted with available adapters. When replacing other ground-fault relays, existing CTs can be used in many cases, greatly simplifying the installation. Adapter plates are also available for many retrofits, minimizing the amount of work required to complete the upgrade.

TYPICAl APPlICATIONS

Ground faults on a solidly grounded system can cause significant damage because the resistance of the fault, ground return path, and transformer winding are all that limits the fault current. If this fault is not cleared it can very quickly escalate into a phase-to-phase fault, causing even more damage to equipment and hazards to personnel. POWR-GARD ground-fault relays provide flexible protection that can be used on a wide variety of applications.

Ground faults on an ungrounded system cannot be detected with current-sensing devices. Although the first ground fault does not produce a fault current, it is still a hazardous condition that needs to be corrected as soon as possible. POWR-GARD provides a series of products that not only indicate when a phase has faulted to ground, but also monitor the insulation resistance of the system. This provides an advance warning that a ground fault is imminent, due to insulation breakdown or mechanical damage.

Ground faults on a resistance-grounded system are limited to a specified value; therefore, the system may continue to operate with a ground fault. However, it remains critical for the ground fault to be detected and corrected as soon as possible. If a second ground fault develops, a phase-to-phase fault exists through the two ground faults. Sensitive ground-fault relays such as the PGR-4704 provide accurate detection of faults as low as 10 mA, while minimizing false operations with digital filtering algorithms.

SOlIdlY GROuNdEduNGROuNdEd RESISTANCE GROuNdEd

149Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 6: Littelfuse POWR-GARD Products Catalog - Protection Relaysstevenengineering.com/.../28PG_PROTECTION-RELAYS.pdf · products for the harshest industrial ... Ground-fault protection relays

150

Protection Relays

© 2010 Littelfuse POWR-GARD® Products Catalogwww.littelfuse.com

8

GroUnD-FaUlt protection

Features/BenefitsSensitive 1- to 20-mA trip settings•

A microprocessor-based ground-fault relay •for ungrounded dc systems

50-ms to 2.5-s time-delay settings•

Limits ground-fault current to 25 mA•

Form-A and Form-B trip contacts•

SpecificationsIEEE device Number: 76Gdimensions: H 75 mm (3.0”); W 55 mm (2.2”); d 115 mm (4.5”)Communications: Analog OutputWarranty: 5 Year

Web Resourceswww.littelfuse.com/pgr-2601

cataloG/systeM # speciFications accessoriesPGR-2601-OD 9-36 Vdc Control Power PGG Series Ground Reference Modules

PGA-0500 Analog Current MeterPGR-2601-OT 32-70 Vdc Control PowerPGR-2601-OU 75-275 Vac/dc 50/60 Hz Control Power

PGR-2601 DC Ground-Fault Relay For Ungrounded DC Systems

Features/BenefitsMeets NEC• ® Article 250.21 (B)

Indicates the presence of voltage on •each phase of a three-phase system by illuminating the LEDs

Indicates ground-fault and phase•

Lamp test button to verify operation•

Redundant long-life LEDs•

SpecificationsIEEE device Numbers: 27, 64dimensions: H 108 mm (4.3”); W 88.9 mm (3.5”); d 54 mm (2.1”)Warranty: 5 Year

Web Resourceswww.littelfuse.com/pgr-3100

cataloG/systeM # speciFications accessoriesPGR-3100 Panel Mount —

PGR-3100 Ground-Fault Indication System For Ungrounded AC Systems

Features/BenefitsMeets NEC Article 250.21 (B)•

Continuously monitors the insulation •integrity of ungrounded electrical systems for ground faults

Provides 2 warnings and 1 alarm•

Analog output for insulation reading•

SpecificationsIEEE device Number: 27, 64dimensions: H 99.7 mm (3.9”); W 75 mm (4.3”); d 110 mm (4.3”)Communications: Analog OutputWarranty: 5 Year

Web Resourceswww.littelfuse.com/pgr-3200

cataloG/systeM # speciFications accessories

PGR-3200 240 Vac Control PowerPGA-0510 Analog Insulation Meter PGH family High Tension Couplers

PGR-3200 Ground-Fault Protection System For Ungrounded AC Systems

Gro

un

d-F

ault

Rel

ays

GFP

GFP

GFP

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 7: Littelfuse POWR-GARD Products Catalog - Protection Relaysstevenengineering.com/.../28PG_PROTECTION-RELAYS.pdf · products for the harshest industrial ... Ground-fault protection relays

151

Protection Relays

www.littelfuse.com © 2010 Littelfuse POWR-GARD® Products Catalog

8

GroUnD-FaUlt protection

Features/BenefitsNo CTs needed•

Provides a simple method for tripping a ground-fault •condition on generators

Use with 3- or 4-pole transfer switches•

Monitors neutral-to-ground integrity•

Adjustable pick-up settings from 100 to 1200 A •

Adjustable time-delay settings from 0 to 1 sec•

SpecificationsIEEE device Numbers: 50G, 50N, 51G, 51Ndimensions: H 75 mm (3.0”); W 55 mm (2.2”); d 115 mm (4.5”)Communications: Analog OutputWarranty: 5 Year

Web Resourceswww.littelfuse.com/pgr-4300

PGR-4300 Generator Ground-Fault Relay For Solidly Grounded Systems

cataloG/systeM # speciFications accessoriesPGR-4300-12 12 Vdc Control Power

PGA-0500 Analog Current MeterPGR-4300-24 24 Vdc Control PowerPGR-4300-120 120 Vac Control Power

Features/BenefitsProvides sensitive ground-fault protection•

A microprocessor-based ground-fault relay for •resistance-grounded and solidly grounded systems

Microprocessor-based unit with DFT•

Non-volatile trip memory retains trip state•

Compatible with VFD applications•

Adjustable pick-up settings from 10 mA to 5 A •

Adjustable time-delay settings from 0.5 to 2.5 sec•

SpecificationsIEEE device Numbers: 50G, 50N, 51G, 51Ndimensions: H 75 mm (3.0”); W 55 mm (2.2”); d 115 mm (4.5”)Communications: Analog OutputWarranty: 5 Year

Web Resourceswww.littelfuse.com/pgr-4704

PGR-4704 Sensitive Ground-Fault Relay For Solidly and Resistance Grounded Systems

cataloG/systeM # speciFications accessoriesPGR-4704-24 24 Vdc Control Power PGA-0500 Analog Current Meter

PGC-5000 series Current TransformersPGR-4704-120 120 Vac Control PowerPGR-4704-240 240 Vac Control Power

Features/BenefitsChoice of input CT gives wide setting range•

A microprocessor-based ground-fault relay for •resistance-grounded and solidly grounded systems

Microprocessor-based unit with DFT•

Non-volatile trip memory retains trip state•

Compatible with VFD applications•

Adjustable pick-up settings from 1% to 99% of CT •primary rating, as low as 50 mA

Adjustable time-delay settings from 0.5 to 2.5 sec•

SpecificationsIEEE device Numbers: 50G, 50N, 51G, 51Ndimensions: H 75 mm (3.0”); W 55 mm (2.2”); d 115 mm (4.5”)Communications: Analog OutputWarranty: 5 Year

Web Resourceswww.littelfuse.com/pgr-5701

PGR-5701 Ground-Fault Relay For Solidly and Resistance Grounded Systems

cataloG/systeM # speciFications accessoriesPGR-5701-OD 9-36 Vdc Control Power PGA-0500 Analog Current Meter

PGC family Current TransformersPGR-5701-OT 32-70 Vdc Control PowerPGR-5701-OU 75-275 Vac/dc Control Power

Gro

un

d-Fau

lt Relays

GFP

RGGFP

RGGFP

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 8: Littelfuse POWR-GARD Products Catalog - Protection Relaysstevenengineering.com/.../28PG_PROTECTION-RELAYS.pdf · products for the harshest industrial ... Ground-fault protection relays

Resistance grounding solves the problems commonly associated with both ungrounded systems and solidly grounded systems by adding a resistor between the system neutral and ground. The specifications of the resistor are user determined to achieve a desired ground-fault current, which must be greater than the system capacitive charging current.

For systems 2.4 kV and higher, low-resistance grounding systems can be used. Typically in those systems the ground-fault current is 25 A or above and is cleared within 10 s.

Resistance Grounding

Properly sized resistance grounding systems solve two problems of ungrounded systems—transient overvoltages and difficulty locating ground faults. Resistance grounding systems eliminate transient overvoltages, single phase Arc-Flash hazards, and provide an ability to locate the ground fault. These capabilities reduce unscheduled shutdowns due to electrical faults and equipment damage. The PGN Family of Resistance Grounding Systems include all necessary components to convert or design a resistance- grounded system. Additional ground-fault relays (PGR-4704) can be installed on feeders to provide selective coordination as well as the ability to locate ground faults.

Resistance Grounding eliminates excessive ground-fault damage and single phase Arc-Flash Hazards associated with solidly grounded systems by reducing the ground-fault current to 5 A. Per IEEE Standard 141-1993, Arc-Flash hazards associated with ground faults are eliminated if the ground-fault current is reduced to 5 A or less.

A protection relay for resistance- grounded systems is used to detect a ground fault and to monitor the neutral-to-ground connection. The relay can provide a pulsing circuit that can assist in locating the ground fault. The relay can also alarm or trip if the neutral-to-ground path fails. For systems 5 kV and less, high-resistance grounding can be used. High-resistance grounding typically limits the resistor current to 10 A or less. By doing so, the ground fault can remain on the system, given that the system is rated for the voltage shift.

COSTSAFETY dOWNTIME

152Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 9: Littelfuse POWR-GARD Products Catalog - Protection Relaysstevenengineering.com/.../28PG_PROTECTION-RELAYS.pdf · products for the harshest industrial ... Ground-fault protection relays

153

Protection Relays

www.littelfuse.com © 2010 Littelfuse POWR-GARD® Products Catalog

8

Low-Resistance grounding is typically applied on transformers and generators, and limits the ground-fault current to 25 A and above. Since ground-fault current is above 25 A, the faulted feeder must be de-energized. The reduced ground-fault current allows for an orderly shut-down procedure, typically within 10 seconds.

Web ResourcesFor more information on Resistance Grounding Systems, visit www.littelfuse.com/pgn-1000

PGR-5330SENSINGRESISTOR

NGR

L2

PGM-8325

CT

L1

DescriptionThe PGM-8325 Neutral Grounding Monitor is used on resistance-grounded systems up to 25 kVac to monitor the integrity of the neutral-to-ground path for loose connection, corrosion, and ground faults, or NGR failure.

Features/BenefitsAdjustable ground-fault detection•

Adjustable time-delay settings•

Selectable fail-safe mode•

Conformally coated circuit boards•

SpecificationsIEEE device Numbers: 50G, 50N, 51G, 51N, 59N, 86dimensions: H 150 mm (5.9”);

W 109 mm (4.3”); d 100 mm (4.0”)

Warranty: 5 Year

Web Resourceswww.littelfuse.com/pgm-8325

cataloG/systeM # speciFications accessories

PGM-8325 120 Vac 50/60 Hz PGC-2000 series Current Transformers PGE family Sensing Resistors PGB-0302 or 0325 Remote IndicatorsPGM-8325-E 240 Vac 50/60 Hz

PGM-8325 NeutralGrounding Monitor

DescriptionAn advanced resistor-monitoring relay that measures neutral current, voltage and resistance.

Features/BenefitsPulsing feature to detect ground faults•

Monitors neutral-to-ground integrity•

Software for remote monitoring•

Several network communication options•

SpecificationsIEEE device Numbers: 50G, 50N, 51G, 51N, 59N, 86dimensions: H 150 mm (5.9”);

W 109 mm (4.3”); d 100 mm (4.0”)

Communications: RS-232; DeviceNet™, Profibus®, EthernetWarranty: 5 Year

Web Resourceswww.littelfuse.com/pgr-5330

cataloG/systeM # speciFications accessoriesPGR-5330-00-00 RS-232 Communications; 80-265 Vac/dc

PGE family Sensing Resistors PGC family Current Transformers

PGR-5330-01-00 RS-232 & DeviceNet™; 80-265 Vac/dcPGR-5330-02-00 RS-232 & Profibus®; 80-265 Vac/dcPGR-5330-03-00 RS-232 & Ethernet; 80-265 Vac/dc

PGR-5330 Resistance Grounding Relay

PGN-3000 High-Resistance Grounding System

High-Resistance grounding is typically applied on transformers and generators, and limits the ground-fault current to 10 A or less. Since ground-fault current is below 10 A, the faulted feeder can remain in operation. The reduced ground-fault current allows for an orderly shut-down procedure.

Web ResourcesFor more information on Resistance Grounding Systems, visit www.littelfuse.com/pgn-3000

PGR-5330

NGR

TRANSFORMERSECONDARY(Delta-connectedor wye-connectedwith inaccessible

neutral)

ZIGZAGTRANSFORMER

SENSINGRESISTOR

L2

PGM-8325

CT

L1

(Included with PGN Series f necessary)

PGN-1000 Low-Resistance Grounding System

Resistan

ce Gro

un

din

g S

ystems

RG

RG

RG

RGGFP

SM

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 10: Littelfuse POWR-GARD Products Catalog - Protection Relaysstevenengineering.com/.../28PG_PROTECTION-RELAYS.pdf · products for the harshest industrial ... Ground-fault protection relays

Safeguarding Critical Applications Motor Protection Relays prevent expensive damage to motors caused by overloads, jams, phase loss or unbalance, heat from non-electric sources, heavy start-ups or excessive operational cycles. Features, such as integrated protection, metering, data logging, and remote communications extend motor life and maximize process efficiency.

Feeder Protection Relays protect feeder circuits from overcurrents, ground faults, phase loss or other detrimental conditions in critical applications and processes. Feeder Protection Relays provide essential data for predictive and preventative maintenance—extending the life of equipment, enhancing safety and maximizing efficiency.

Over 50% of new motors fail within the first seven years of operation. Since motors and other electrical equipment represent a significant investment to many industrial operations, Motor and Feeder Protection relays are used to extend the life of this equipment and improve safety to personnel exposed to the equipment.

Motor Protection Relays provide overload protection for motors. This protection is required by various electrical codes to reduce the chance of fire caused by problems with the motor or load.

Littelfuse® Motor and Feeder Protection relays have a reduced-overcurrent feature that can reduce Arc-Flash Hazards during maintenance near energized equipment, allowing for a much safer system.

Modern industrial operations cannot tolerate unscheduled shutdowns, as each lost hour of production can cost hundreds of thousands of dollars. The cost of downtime combined with lost or scrapped production, replacement parts, motor rewinds and troubleshooting is significant. Motor Protection relays reduce unscheduled downtime and loss of productivity by continuously monitoring the motor performance to safeguard against unwanted damages. Littelfuse relays are field-proven and have been protecting motors for 35 years.

COSTSAFETY dOWNTIME

154

Motor and Feeder

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 11: Littelfuse POWR-GARD Products Catalog - Protection Relaysstevenengineering.com/.../28PG_PROTECTION-RELAYS.pdf · products for the harshest industrial ... Ground-fault protection relays

Protection Relays

Motor Protection relays provide basic overload protection for small motors to advanced protection for large motors to help extend the life of the motor. This is extremely important for large or critical motors or for smaller motors located in hard to access locations. POWR-GARD’s Motor Protection relays can provide a warning that a problem is developing before damage occurs, as well as uncover potential problems with the customer’s process.

Motors

PuMPs

Variable Frequency driVes

sWitcHGear

Motor control centers

Portable PoWer cables

electrical distribution

Process control Panels

PoWer distribution Panels

Feeder Protection relays are designed to detect faults in an electrical distribution system. They provide a high degree of flexibility and can coordinate with other protection devices on the system. Feeder Protection relays are used in processing, manufacturing, petroleum, chemical, mining, forestry, water, and waste water facilities. Modern Feeder Protection relays are an excellent choice for retrofitting obsolete electromechanical relays.

Motor Protection Comparison Chart

Motor Protection Typical Applications Feeder Protection Typical Applications

TYPICAl APPlICATIONS

155

FEATuRE BENEFIT PGR-6100 PGR-6130 PGR-6150 PGR-6200 PGR-6300 PGR-6800

oVerloaD (49, 51) Prevent insulation damage and fires. Extends motor life. 4 4 4 4 4oVercUrrent / JaM (50, 51) Prevents catastrophic failures and fires. Extends motor life. 4 4 4UnDercUrrent (37) Detects low-level or no-load conditions. 4 4 4 4cUrrent UnBalance / phase loss / phase reVerse (46)

Prevents overheating and extends motor life. 4 4 4 4 4GroUnD FaUlt (50G/n, 51G/n) Prevents catastrophic failures and fires. 4 4 4 4oVerteMperatUre (49) Extends motor life by ensuring that cooling is effective. 4 4 4 4oVerVoltaGe (59) Prevents stress to insulation. 4UnDerVoltaGe (27) Prevents a start attempt when it will damage the motor. 4VoltaGe UnBalance (47) Detects unhealthy supply voltage. 4DiFFerential (87) Provides sensitive protection for high-resistance winding faults. 4 4starter control Simplifies the installation by reducing component count. 4MeterinG Alphanumeric display of conditions. 4 4 4Data loGGinG Record of trips and starts. 4 4 4inteGrateD cts External current transformers not required. 4 4 4oFF-line MonitorinG Continuously monitors motor windings when de-energized. 4reDUceD oVercUrrent Minimizes Arc-Flash Hazards during maintenance. 4 4coMMUnications Provides means to interface with the relay remotely. 4 4 4

NOTE: IEEE Device Numbers are shown in parenthesis after the applicable features.

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 12: Littelfuse POWR-GARD Products Catalog - Protection Relaysstevenengineering.com/.../28PG_PROTECTION-RELAYS.pdf · products for the harshest industrial ... Ground-fault protection relays

156

Protection Relays

© 2010 Littelfuse POWR-GARD® Products Catalogwww.littelfuse.com

8

Motor protection relays

Features/BenefitsOnline monitoring to detect ground faults•

Offline monitoring of insulation resistance•

Continuously monitors for predictive protective •capabilities

CT loop monitoring•

Individual alarm contacts (form C)•

Individual analog outputs to indicate insulation •resistance and ground-fault current

SpecificationsIEEE device Numbers: 50, 50G, 50N, 51, 51G, 51N, 74dimensions: H 99.7 mm (3.9”); W 75 mm (3”); d 110 mm (4.3”)Communications: 2 Analog OutputsWarranty: 5 years

Web Resourceswww.littelfuse.com/pgr-6100

cataloG/systeM # speciFications accessories

PGR-6100-120 24 Vdc/120 Vac Control Power PGA-0500-series Analog Meters PGC Family Current Transformers PGH Family High Tension CouplersPGR-6100-240 240 Vac Control Power

cataloG/systeM # speciFications FUll-loaD cUrrent accessoriesPGR-6131-24 24 Vac/dc 4-16.7 A

PGB-6130, Remote Indication and Reset Assembly

PGR-6131-120 120 Vac 4-16.7 APGR-6131-240 240 Vac 4-16.7 APGR-6132-24 24 Vac/dc 15-40.5 A PGR-6132-120 120 Vac 15-40.5 APGR-6132-240 240 Vac 15-40.5 APGR-6133-24 24 Vac/dc 40-91 APGR-6133-120 120 Vac 40-91 APGR-6133-240 240 Vac 40-91 A

Features/BenefitsNo external CT required for currents up to 91 A•

Cause-of-trip indication•

N.O. and N.C. alarm contacts•

Adjustable overload trip class setting•

Adjustable current pickup•

Overtemperature (PTC) protection•

Thermal overload protection•

SpecificationsIEEE device Numbers: 46, 49, 51dimensions: H 83 mm (3.3”); W 78 mm (3.1”); d 99 mm (3.9”)Warranty: 5 years

Web Resourceswww.littelfuse.com/pgr-6130

cataloG/systeM # speciFications accessoriesPGR-6150-24 24/48 Vdc (Control Unit)

PGR-6150-OPI Operator InterfacePGR-6150-240 120/240 Vac/dc (Control Unit)

Features/Benefits13 protective functions•

2 relay outputs, 1 digital input•

No external CT required for currents < 25 A•

Thermal protection through starting, running, •overload and cooling cycles

RS-485 interface with Modbus• ® RTU

Optional PGR-6150-OPI Operator Interface•

SpecificationsIEEE device Numbers: 37, 46, 49, 50, 50G, 50N, 51, 51G, 51N, 66dimensions (Relay): H 83 mm (3.3”); W 78 mm (3.1”); d 99 mm (3.95”)dimensions (OPI): H 56 mm (2.2”); W 106 mm (4.2”); d 23 mm (0.9”)Communications: RS-485 with Modbus® RTUWarranty: 5 years

Web Resourceswww.littelfuse.com/pgr-6150

PGR-6150 Motor Protection System

PGR-6130 Motor Protection Relay

PGR-6100 Motor Ground-Faultand Insulation Relay

Mo

tor

Pro

tect

ion

Rel

ays

MP

MP

MP

FP

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 13: Littelfuse POWR-GARD Products Catalog - Protection Relaysstevenengineering.com/.../28PG_PROTECTION-RELAYS.pdf · products for the harshest industrial ... Ground-fault protection relays

157

Protection Relays

www.littelfuse.com © 2010 Littelfuse POWR-GARD® Products Catalog

8

Motor protection relays

cataloG/systeM # speciFications FUll-loaD cUrrent accessoriesPGR-6801-24 24 Vac/dc 7-19.6 A

PGB-6800, Remote Indication and Reset Assembly

PGR-6801-120 120 Vac 7-19.6 APGR-6801-240 240 Vac 7-19.6 APGR-6802-24 24 Vac/dc 19-44.2 APGR-6802-120 120 Vac 19-44.2 APGR-6802-240 240 Vac 19-44.25 APGR-6803-24 24 Vac/dc 40-90.4 APGR-6803-120 120 Vac 40-90.4 APGR-6803-240 240 Vac 40-90.4 A

cataloG/systeM # speciFications accessoriesPGR-6200-00-00 RS-232 Communications PGC Family Current Transformers

PGA-0140 Differential Current Module PGA-0120 Temperature Input Module

PGR-6200-01-00 RS-232 & RS-485 CommunicationsPGR-6200-02-00 RS-232 & DeviceNet™ CommunicationsPGR-6200-04-00 RS-232 & Ethernet Communications

Features/BenefitsNo external CT required for currents up to 90 A•

Cause-of-trip indication•

N.O. and N.C. alarm contacts•

Adjustable overload trip class setting•

Adjustable current pickup•

Undercurrent protection•

Thermal overload protection•

SpecificationsIEEE device Numbers: 37, 46, 49, 51dimensions: H 83 mm (3.3”) W 78 mm (3.1”) d 99 mm (3.9”)Warranty: 5 years

Web Resourceswww.littelfuse.com/pgr-6800

Features/BenefitsReduced overcurrent setting for maintenance•

Dynamic thermal modeling•

Communications for different networks•

Optional RTD protection•

Optional differential protection•

Conformal coating•

Modular system and compact design makes •installation easy for new or retrofit applications

SpecificationsIEEE device Numbers: 37, 38, 46, 49, 50, 50G, 50N, 51, 51G, 51N, 66, 74, 86, 87dimensions: H 96 mm (3.78”); W 96 mm (3.78”); d 132 mm (5.2”)Communications: RS-232 (Standard); RS-485, DeviceNet™, Ethernet (Optional)Warranty: 10 years

Web Resourceswww.littelfuse.com/pgr-6200

cataloG/systeM # speciFications accessoriesPGR-6300-01-00 RS-485 Communication PGC Family Current Transformers

PGA-0120 Temperature Input Module PGA-0140 Differential Current Module

PGR-6300-02-00 RS-485 & DeviceNet™ CommunicationPGR-6300-03-00 RS-485 & Profibus® CommunicationPGR-6300-04-00 RS-485 & Ethernet Communication

Features/BenefitsOvercurrent reduction setting for maintenance•

Monitors voltage, current, and temperature•

22 motor protection functions•

Conformal coating•

Dynamic thermal modeling•

Starter control, Metering, and Data Logging•

Optional RTD protection with hazardous-location •certified RTD module

Optional differential protection•

Modular design makes installation easy•

SpecificationsIEEE device Numbers: 1, 2, 3, 5, 9, 14, 18, 19, 27, 34, 37, 38, 46, 47, 48, 49, 50, 50G, 50N, 51, 51G, 51N, 55, 59, 66, 74, 81, 86, 87, 94dimensions (OPI): H 98 mm (3.86”); W 192 mm (7.56”); d 0.42 mm (1.65”)Communications: Allen-Bradley® DF1 and Modbus® RTU (Standard); DeviceNet™, Profibus®, Ethernet (Optional)Warranty: 10 years

Web Resourceswww.littelfuse.com/pgr-6300

PGR-6300 Motor Protection System

PGR-6800 Pump Protection Relay

PGR-6200 Motor Protection Relay

Mo

tor P

rotectio

n R

elays

MP

MP

MP

MOTOR PROTECT ON SYSTEMPGR 6150 SERIES

POWR-GARD®

C

OK O L AM L KD RO OREXT T T ME

GRO ND FAU T OP N CT TC FA LU E UND RCU RENT

OV RT MP

UNB LAN E PH SE SE UENCE

POWER

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 14: Littelfuse POWR-GARD Products Catalog - Protection Relaysstevenengineering.com/.../28PG_PROTECTION-RELAYS.pdf · products for the harshest industrial ... Ground-fault protection relays

158

Protection Relays

© 2010 Littelfuse POWR-GARD® Products Catalogwww.littelfuse.com

8

FeeDer protection relays, kits anD accessories

cataloG/systeM # speciFications accessoriesPGR-7200-00-00 RS-232 Communications

PGC Family Current TransformersPGR-7200-01-00 RS-232 & RS-485 Communications

PGR-7200-02-00 RS-232 & DeviceNet™ Communications

PGR-7200-04-00 RS-232 & Ethernet Communications

Features/BenefitsProtection, metering, and data-logging functions•

Programmable using the operator interface, the TIA-232 •port, or an optional communications network

IEC & IEEE protection curves•

CT saturation compensation•

Communications for different networks•

Two set-point groups•

SpecificationsIEEE device Numbers: 26, 46, 49, 50, 50G, 50N, 51, 51G, 51N, 74, 86dimensions: H 96 mm (3.78”); W 96 mm (3.78”); d 132 mm (5.2”)Communications: RS-232, RS-485, DeviceNet™, EthernetWarranty: 10 years

Web Resourceswww.littelfuse.com/pgr-7200

Features/BenefitsDirect replacement for GE Multilin 169, 269, 369 •and 469 relays (mounting holes and openings are exact match)

Microprocessor-based protection •

Proven reliability•

Conformally coated circuit boards•

Additional protective functions, including reduced •overcurrent and dynamic thermal model

Pre-wired module allows minimal change-out time•

Use existing current transformers and RTD •temperature sensors (and PTs on PGR-6310 applications)

Ability to match existing overcurrent curves•

100% factory-tested, pre-assembled components•

Web Resourceswww.littelfuse.com/pgr-6210 www.littelfuse.com/pgr-6310

PGR-7200 Feeder Protection Relay

PGR-6210 and PGR-6310 Motor Protection Retrofit Kits

PGK Family Panel Mount Adapters

Features/BenefitsAdd communications capability to older •switchgear and improve system performance

Save cost by not calibrating older •electromechanical devices

Conformally coated circuit boards*•

Additional protective functions, •including reduced overcurrent and dynamic thermal model*

Minimal change-out time by using •existing CTs

PGR-6200 and PGR-6300 can use existing •RTDs with an optional RTD module

Ability to match existing overcurrent curves*•

*Included on PGR-6200, PGR-6300 and PGR-7200

relay to replace: panel MoUnt relayAB BULLETIN 1406 PGK-0014 PGR-6300FPL-GFRM PGK-0006 PGR-4700FPL-GFRM PGK-0006 PGR-5701GE S1 PGK-0009 PGR-6200GE S1 PGK-0009 PGR-7200GE LODTRAK III PGK-0010 PGR-6200

GE MULTILIN 169, 269, OR 369PGK-0013 PGR-6300PGK-0016 PGR-6200PGK-0016 PGR-7200

GE MULTILIN 469 PGK-0024 PGR-6300GE MULTILIN P4A PGK-0015 PGR-6200GE MULTILIN P4A PGK-0015 PGR-7200GEC/MCGG PGK-0003 PGR-4700GEC/MCGG PGK-0003 PGR-5701GE & WESTINGHOUSE FT-11 PGK-0012 PGR-6200P & B GOLDS Contact Factory PGR-7200WESTINGHOUSE CO9 & CO11 Contact Factory PGR-7200

Replacements

Feed

er P

rote

ctio

n R

elay

s

FP

MP

PGR-6210 Ordering Information PGR-6310 Ordering Information

MoDUle coMMUnications

pGr–6210 – X X0 = None 0 = RS-232

1 = RTD PGA-0120 1 = RS-232 & RS-485

2 = RS-232 & DeviceNet™

3 = RS-232 & Ethernet

MoDUles coMMUnications

pGr–6310 – X X

0 = None 0 = RS-232

1 = 1 RTD PGA-0120 1 = RS-232 & RS-485

2 = 2 RTD PGA-0120 2 = RS-232 & DeviceNet™

3 = 1 Differential PGA-0140 3 = RS-232 & Ethernet

4 = 1 Differential PGA-0140 + 1 RTD PGA-0120

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 15: Littelfuse POWR-GARD Products Catalog - Protection Relaysstevenengineering.com/.../28PG_PROTECTION-RELAYS.pdf · products for the harshest industrial ... Ground-fault protection relays

159

Protection Relays

www.littelfuse.com © 2010 Littelfuse POWR-GARD® Products Catalog

8

sUppleMental Monitors

Features/BenefitsFail-safe ground check circuit•

Combination ground-wire monitor and • ground-fault relay

Zener-characteristic termination device•

High-induced-ac rejection•

DFT (harmonic) filter•

SpecificationsIEEE device Numbers: 3GC, 50G, 50N, 51G, 51Ndimensions: H 213 mm (8.4”); W 99 mm (3.9”); d 145 mm (5.7”)Warranty: 5 Year

Web Resourceswww.littelfuse.com/pgm-8134

cataloG/systeM # speciFications accessories

PGM-8134-00 60-265 Vac; 80-370 Vdc Control PowerPGC-4000 series Current Transformers PGA-0TA6 or 0TA7 Termination Device

PGM-8134 Ground Continuity Monitor

Features/BenefitsProvides 2 warnings and 1 alarm•

Monitors insulation resistance for failures•

Operates on grounded, resistance grounded or •ungrounded systems up to 6 kV

Analog output for insulation reading•

1 local and 2 remote resets•

DIN-rail or surface mount•

SpecificationsIEEE device Number: 86dimensions: H 99.7 mm (3.9”); W 75 mm (3”); d 110 mm (4.3”)Warranty: 5 Year

Web Resourceswww.littelfuse.com/pgm-8600

cataloG/systeM # speciFications accessories

PGM-8600 240 Vac Control PowerPGA-0510 Analog Insulation Meter PGH Family High Tension Couplers

PGM-8600 Insulation Monitor

Supplemental Monitors work together with existing protection to enhance electrical system safety and performance. These monitors are designed for application-specific functionality such as insulation monitoring, and ground-continuity monitoring.

Ground-check monitors are used to detect problems in equipment ground conductors. Mobile equipment typically has an extra wire, sometimes called a pilot wire, routed with the phase and ground conductors. A ground-check monitor

uses this pilot wire to send a signal down to the equipment to a terminating device. The signal then returns on the equipment ground conductor to the monitor.

The most common reason for electrical system failure is insulation breakdown. Insulation monitors can be installed at any point in the system to detect a problem with the insulation. The monitor is connected to one phase and injects a dc signal to continuously measure the system’s insulation resistance.

Su

pp

lemen

tal Mo

nito

rs

SM

SM

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 16: Littelfuse POWR-GARD Products Catalog - Protection Relaysstevenengineering.com/.../28PG_PROTECTION-RELAYS.pdf · products for the harshest industrial ... Ground-fault protection relays

8

160

Protection Relays

© 2010 Littelfuse POWR-GARD® Products Catalogwww.littelfuse.com

FaMily proDUct

pGa analog Meters

pGa communication converter cables

pGa termination assemblies

pGa-0120 temperature input Module

pGa-0140 Differential current Module

FaMily proDUct

pGB remote indication and reset

pGc current transformers

pGe sensing resistors

pGG Ground reference Modules

pGh high tension couplers

AccessoriesMost protective relays require an accessory for operation. Consult www.littelfuse.com/protectionrelays for a complete listing.

Features/BenefitsThe PGT-0400 tests the entire ground-fault circuit •including current transformers, wiring, ground-fault relay and the operation of the interrupting device

Current range is 0.5 to 9.9 A•

Duration range is 0.1 to 9.9 s or continuous output•

Lightweight and compact for portability•

Specificationsdimensions: H 219 mm (8.6”) W 99 mm (3.9”) d 143 mm (5.6”)Warranty: 5 Year

Web Resourceswww.littelfuse.com/pgt-0400

cataloG/systeM # speciFicationsPGT-0400 120 Vac Control Power

PGT-0400 Ground-Fault Relay Test Unit

Software

soFtware

product software For

PGW-COMM Relay Interface Software

PGR-6200 PGR-6300 PGR-7200

VPG-6200Virtual Motor Protection Relay

PGR-6200

VPG-6300Virtual Motor Protection System

PGR-6300

VPG-7200Virtual Feeder Protection Relay

PGR-7200

soFtware

product software For

PGW-FLSH Firmware Update Utility

PGR-5330 PGR-6200 PGR-6300 PGR-7200

PGW-5330 Relay Interface Software

PGR-5330

PGW-OSTT PGR-6200 Online Self-Training Tutorial

PGR-6200

PGW-6150 Relay Interface Software

PGR-6150

accessories

Acc

esso

ries

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com