  • Catalogue2013

    LinergyDistribution & Connection systems

    Low Voltage

  • 25/01/2013 3

    Presentation 4

    Linergy distribution systems

    Distribution blocks 15

    Device feeders 23

    Power busbars 43

    Hot plugs 67

    Linergy connection systems

    Terminal blocks & bars 73

    Index 134

    Linergy distribution & connection systems

    Contents

    00_00-Sommaire Version : 1.0

  • 25/01/2013 EDCED112024Version : 1.044

    All Schneider Electric distribution and connection systems have now been brought together into a single brand name:

    Linergy

  • 25/01/2013EDCED112024 Version : 1.0 5

    Now,think Linergy!

    Because Linergy is

    Reliable > Linergy is fully compliant with IEC standards, and some systems are also multi-standard.

    > All Linergy distribution and connection systems have been designed and tested to work together (synergies with Schneider Electric devices).

    > Linergy, brings you the benefit of an energy-efficient switchboard.

    Safer > Linergy IPxxB everywhere. > Linergy is a "Hot plug" solution, enabling connections without turning off the switchboard (energised connection).

    > Linergy simplifies wiring, thus directly contributing to enhancing panel reliability.

    Flexible > Linergy is a complete range of more than 800 references, suitable for all type of applications (electrical distribution, process and control, datacenters, etc.).

    > Linergy can be easily adapted to technical demand, customer habits and preferences.

    > Thanks to their compactness, Linergy products can be easily installed into a minimum of space.

    > Linergy is easy to implement in the shortest possible time. > With Linergy you can make changes to your panel on the installation site, right up to the last minute.

    And much more

    Available

    everywhere

  • 25/01/2013 EDCED112024Version : 1.06

    Linergy

    6Inside Prisma and Spacial SFP, you benefit from IEC 61439 tested solutions

  • 25/01/2013EDCED112024 Version : 1.0 7

    With Linergy, you will be able to connect your rows regardless of the enclosure you have chosen.

    Linergy DSDistribution Blocks

    > Compact solution

    > Cabling capacity of up to 60 connection points

    > Screw connection models

    > Minimum space required

    > Quick connection models

    Linergy TBTerminal Blocks and Bars

    > Quick distribution of up to 54 outgoers

    > Maximum flexibility to balance your phases

    > No creepage campaign thanks to clamp technology

    Linergy FM Device Feeders

    > Complete family of products to cover all needs

    > Easy to install

    > Compactness up to 100 A

    Linergy FH Device Feeders

  • 25/01/2013 EDCED112024Version : 1.08

    Linergy

    8Inside Prisma and Spacial SFP, you benefit from IEC 61439 tested solutions

  • 25/01/2013EDCED112024 Version : 1.0 9

    Linergy offers you smart power network solutions for your switchboard.

    Linergy BWPower Busbars

    > Solutions available up to 630 A

    > Solutions can be adapted to all switchboard architectures

    > Maximum flexibility to balance your phases

    > SmartLink support for communication

    Linergy FMDevice Feeders

    Linergy FHDevice Feeders

    > All lengths available (up to 1 m)

    > Comb busbars compatible with auxiliaries

    > Quick connection models

    > Easy to wire

    > Compact solution

    > Cabling capacity of up to 52 connection points

    Linergy DX Distribution Blocks

  • 25/01/2013 EDCED112024Version : 1.010

    Linergy

    10Inside Prisma and Spacial SFP, you benefit from IEC 61439 tested solutions

  • 25/01/2013EDCED112024 Version : 1.0 11

    Linergy also offers the most advanced busbar solutions while remaining simple.

    > Compact (3 x 4P / 4 x 3P) solution

    > Reliable connection

    > Quick connection system dedicated to Compact NSX up to 250 A

    Linergy FC Device Feeders

    > Compactness of up to 250 A

    > Simplicity of use

    > Quick connection system dedicated to Compact NSX

    Linergy DPDistribution Blocks

    Linergy LGY/ LGYE Power Busbars

    > Solutions available up to 4000 A

    > Connection everywhere without drilling (with LGY and LGYE profile)

    Linergy TR Terminal Blocks and Bars

    > Simplicity of use

    > Consistency and cross-functionality guaranteed

    > Few references for a maximum of applications

  • 25/01/2013 EDCED112024Version : 1.012

    Linergy

    12

  • 25/01/2013EDCED112024 Version : 1.0 13

    Thanks to Linergy, you can now have the scalable and flexible panel that you deserve.

    Linergy FT Device Feeders

    > Optimised productivity and efficiency of your control panel

    > Easy to install

    > High reliability

    > Solutions available up to 4000 A

    > Panel devices powered everywhere inside the panel

    Linergy LGY / LGYE Power Busbars

    > Quick connection plates for Compact and TeSys offers

    > Multi-standard offering up to 630 A

    Linergy BZ Power Busbars

    Linergy HK "Hot Plug" Distribution

    > Panel easily upgradeable

    > Reliable "hot plug" modification or upgrade

    > Multi-standard system of up to 160 A

  • 14

  • 25/01/2013 15

    Linergy distribution systems Distribution blocksContents

    Linergy DS 16

    Screw distribution blocks 16

    Linergy DX 18

    Quick distribution blocks 18

    Linergy DP 20

    Quick distribution blocks 20

    01_00-Sommaire Version : 1.0

  • Version : 1.2 25/01/2013 CA907023-EN_FR

    PB

    1112

    50-2

    0

    PB

    1112

    51-2

    0

    PB

    1112

    52-2

    0

    PB

    1112

    43-2

    0

    PB

    1112

    54-3

    0P

    B11

    1253

    -30

    16

    Linergy DSScrew distribution blocks

    Linergy distribution systems Distribution blocks

    Descrip t io n b Single-pole or four-pole distribution block that can be installed on a standard DIN

    rail or on a mounting plate. b Compatible with Prisma G and P, Pragma, Mini Pragma and Resbo series

    switchboards. b Incomers and feeders are connected to screw terminals that accept rigid or

    flexible cables with ferrule. b O ptional: additional neutral terminal strip for four-pole distribution block.

    Ad v ant ages b Simplified power supply for main incomers. b Easy phase balancing. b Easy, effortless cabling due to excellent accessibility. b Visible cabling. b Insulation between phases. b The single-pole distribution blocks are adj acent and bridgeable via the second

    incoming hole for parallel connection.

    I EC/ EN 60947- 7- 1, I EC/ EN 61439- 1 & 2

    Screw d ist rib u t io n b l o ck sNu m b er o f p o l es1P 4P Neu t ral t erm inal st rip

    Rated operational current 125 A 160 A 250 A 100 A 125 A 160 A 100 A 125 ATotal connections capacity

    10 13 14 4 x 7 4 x 12 4 x 15 4 x 12 7 12 15

    Term inal cap acit yDiameter 2 x 9.5 mm 2 x 12 mm 1 x 15.3 mm 2 x 7.5 mm 1 x 9 mm 1 x 9.5 mm 1 x 12 mm 2 x 7.5 mm 1 x 9 mm 1 x 9.5 mm

    2 x 7.5 mm 3 x 7.5 mm 1 x 10 mm 5 x 5.5 mm 7 x 7.5 mm 3 x 8.5 mm 3 x 9 mm 5 x 5.5 mm 7 x 7.5 mm 3 x 8.5 mm6 x 5.8 mm 8 x 5.8 mm 4 x 6 mm - 4 x 6.5 mm 11 x 6.5 mm 8 x 7.5 mm - 4 x 6.5 mm 11 x 6.5 mm- - 8 x 7.5 mm - - - - - - -

    Rated peak withstand current ( Ipk)

    25 k 36 k 60 k 24 k 26 k 28 k 36 k - - -

    Rated short-time withstand current ( Icw) ( IEC/EN 60947-7-1)

    4.2 kArms/1 s 8.4 kArms/1 s 14.4 kArms/1 s 3 kArms/1 s 4.2 kArms/1 s 4.2 kArms/1 s 8.4 kArms/1 s - - -

    W idth ( number of 9 mm pitches)

    3 4 5 8 14 20 18 7 14 17

    Dimension (HxWxD) 85x27x50.5 85x36x50.5 85x45x50.5 100x71x50.5 100x126x50.5 100x162x50.5 100x174x50.5 20x70x35 20x125x35 20x155x35W eight ( g) 125 163 239 210 390 559 567 63 111 149Neutral terminal strip ( optional)

    - - - LGY N1007 LGY N12512 LGY N12515 LGY N12512 - - -

    Reference LGY112510 LGY116013 LGY125014 LGY410028 LGY412548 LGY412560 LGY416048 LGYN1007 LGYN12512 LGYN12515

  • Version : 1.2 25/01/2013CA907023-EN_FR

    PB

    1112

    44-2

    0

    PB

    1112

    45-2

    0

    PB

    1112

    46-2

    0

    PB

    1112

    47-2

    0

    PB

    1112

    48-2

    0

    PB

    1112

    49-2

    0

    DB

    4050

    05

    17

    Tech nical d at aCo m m o n ch aract erist ics

    Rated insulation voltage ( U i) 500 V ACRated operational voltage ( U e) 230 V AC ( Ph/N)

    440 V AC ( Ph/Ph)Rated impulse withstand voltage ( U imp) 8 kVRated conditional short-circuit current of an assembly

    Up to the breaking capacity of Schneider Electric feeder circuit breakers, even in cascading configuration

    Network frequency 50/60 HzPollution degree 3Overvoltage category III

    Ad d it io nal t ech nical ch aract erist icsReference temperature 40 CO perating temperature -25 C to 55 CDielectric withstand ( IEC/EN 60947-1) 2500 V AC

    Linergy DSScrew distribution blocks

    Linergy distribution systems Distribution blocks

    Screw d ist rib u t io n b l o ck sNu m b er o f p o l es1P 4P Neu t ral t erm inal st rip

    Rated operational current 125 A 160 A 250 A 100 A 125 A 160 A 100 A 125 ATotal connections capacity

    10 13 14 4 x 7 4 x 12 4 x 15 4 x 12 7 12 15

    Term inal cap acit yDiameter 2 x 9.5 mm 2 x 12 mm 1 x 15.3 mm 2 x 7.5 mm 1 x 9 mm 1 x 9.5 mm 1 x 12 mm 2 x 7.5 mm 1 x 9 mm 1 x 9.5 mm

    2 x 7.5 mm 3 x 7.5 mm 1 x 10 mm 5 x 5.5 mm 7 x 7.5 mm 3 x 8.5 mm 3 x 9 mm 5 x 5.5 mm 7 x 7.5 mm 3 x 8.5 mm6 x 5.8 mm 8 x 5.8 mm 4 x 6 mm - 4 x 6.5 mm 11 x 6.5 mm 8 x 7.5 mm - 4 x 6.5 mm 11 x 6.5 mm- - 8 x 7.5 mm - - - - - - -

    Rated peak withstand current ( Ipk)

    25 k 36 k 60 k 24 k 26 k 28 k 36 k - - -

    Rated short-time withstand current ( Icw) ( IEC/EN 60947-7-1)

    4.2 kArms/1 s 8.4 kArms/1 s 14.4 kArms/1 s 3 kArms/1 s 4.2 kArms/1 s 4.2 kArms/1 s 8.4 kArms/1 s - - -

    W idth ( number of 9 mm pitches)

    3 4 5 8 14 20 18 7 14 17

    Dimension (HxWxD) 85x27x50.5 85x36x50.5 85x45x50.5 100x71x50.5 100x126x50.5 100x162x50.5 100x174x50.5 20x70x35 20x125x35 20x155x35W eight ( g) 125 163 239 210 390 559 567 63 111 149Neutral terminal strip ( optional)

    - - - LGY N1007 LGY N12512 LGY N12515 LGY N12512 - - -

    Reference LGY112510 LGY116013 LGY125014 LGY410028 LGY412548 LGY412560 LGY416048 LGYN1007 LGYN12512 LGYN12515

    On LGY412560 and LGY416048 referencesInput cabling facilitated by side terminals

    Term inal t ech nical d at aTyp e PZ2 screwDiameter 5.5 mm 5.8 mm 6 mm 6.5 mm 7.5 mm 8.5 mm 9 mm 9.5 mm

    Section Rigid cable 1.5 to 16 mm 1.5 to 16 mm 1.5 to 16 mm 1.5 to 16 mm 2.5 to 25 mm 6 to 35 mm 10 to 35 mm 10 to 35 mmFlexible cable or with ferrule

    1.5 to 10 mm 1.5 to 10 mm 1.5 to 10 mm 1.5 to 10 mm 1.5 to 16 mm 4 to 25 mm 4 to 25 mm 6 to 35 mm

    Tightening torq ue 2 N.m 2 N.m 2 N.m 2 N.m 2 N.m 2 N.m 2.5 N.m 2.5 N.mTyp e Hc screwDiameter 9.5 mm 10 mm 12 mm 15.3 mm -

    Section Rigid cable 10 to 35 mm 1.5 to 50 mm 25 to 70 mm 35 to 120 mmFlexible cable or with ferrule

    6 to 35 mm 1.5 to 35 mm 16 to 50 mm 25 to 95 mm

    Tightening torq ue 8 N.m 4 N.m 1 P: 9 N.m 4P: 5 N.m 14 N.m

  • 25/01/201318

    IEC 60947-7-1, IEC 61439-2

    Description b Downstream circuits are connected from the front, to spring terminals. b Contact pressure automatically adapts to the size of the conductor. b Contacts are insensitive to vibrations and thermal variations. b Only one cable (flexible or rigid) can be inserted per terminal.

    Linergy distribution systems Distribution blocks

    Linergy DXQuick distribution blocks

    Quick distribution blocksNumber of poles 4P, incomers from top 4P, incomers from bottom 4P 1P

    Rated operational current at 40 (Ie) 63 A 63 A 125 A 160 A 160 ARated conditional short-circuit current of an assembly

    (Isc) The reinforced breaking capacity due to cascading in circuit breaker combinations is maintained. The worst-case situations have been tested.

    The reinforced breaking capacity due to cascading in circuit breaker combinations is maintained. The worst-case situations have been tested.

    20 kA/60 ms max according to IEC 61439-1 20 kA/60 ms max according to IEC 61439-1 32 kA

    Rated insulation voltage (Ui) 500 V AC 500 V AC 750 V 750 V 750 VRated operational voltage (Ue) 440 V AC 440 V AC 690 VAC 690 VAC 690 VACRated impulse withstand voltage (Uimp) 6 kV 6 kV 8 kV 8 kV 8 kVRated short-time current Icw (Icw) 4.5 kA rms/1s 4.5 kA rms/1sRated operational frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 HzDegree of protection IPxxB IPxxB IPxxB IPxxB IPxxBIncoming terminals 1 tunnel terminal 25/ph 1 tunnel terminal 25/ph 1 tunnel terminal 35/ph 1 tunnel terminal 35/ph 1 tunnel terminal 70/phTotal connection capacity, outgoing terminals 24 connections:

    4 x 6/phase12 x 6/neutral

    24 connections:4 x 6/phase12 x 6/neutral

    52 connections:7 x 4/phase3 x 6/phase2 x 10/phase1 x 16/phase (screw terminal)

    52 connections:7 x 4/phase3 x 6/phase2 x 10/phase1 x 16/phase (screw terminal)

    6 connections:6 x 16/phase

    Dimensions (H x W x D) 96.5 x 72 x 628 x 9 mm pitch

    96.5 x 72 x 628 x 9 mm pitch

    127 x 108 x 488 x 9 mm pitch

    127 x 108 x 488 x 9 mm pitch

    95 x 36 x 704 x 9 mm pitch

    Installation Clipped onto a DIN rail Clipped onto a DIN rail Screwed to plain or slotted backplate or onto DIN rail Screwed to plain or slotted backplate or onto DIN rail Onto DIN railOther Possible to combine 2 terminal blocks

    (2nd terminal block supplied from enclosed terminals in the 1st, Imax of 2nd terminal block: 80 A)

    Possible to combine 2 terminal blocks (2nd terminal block supplied from enclosed terminals in the 1st, Imax of 2nd terminal block: 80 A)

    Standard for installation inside Prisma IEC 61439-2 IEC 61439-2 IEC 61439-2 IEC 61439-2 IEC 61439-2Glow-wire 60695-2-11 960C 960C 960C 960C 960CDegree of pollution 3 3 3 3 3References 04040 04041 04045 04046 04031

    Accessories(4 x 125 A flexible connectors) Copper spacer (batch of 4)

    References - - 04047 04037

    LIN003-EN_FRVersion : 1.0

    PB

    1044

    99

    PB

    5009

    24

    PB

    1045

    00

    PB

    1044

    99

  • 25/01/2013 19

    Advantages b A reliable electrical connection, no maintenance required

    (tightness guaranteed over time) b Quick connection b Easy phase balancing b Ease of rewiring if the switchboard is expanded or modified

    Linergy distribution systems Distribution blocks

    Linergy DXQuick distribution blocks

    Quick distribution blocksNumber of poles 4P, incomers from top 4P, incomers from bottom 4P 1P

    Rated operational current at 40 (Ie) 63 A 63 A 125 A 160 A 160 ARated conditional short-circuit current of an assembly

    (Isc) The reinforced breaking capacity due to cascading in circuit breaker combinations is maintained. The worst-case situations have been tested.

    The reinforced breaking capacity due to cascading in circuit breaker combinations is maintained. The worst-case situations have been tested.

    20 kA/60 ms max according to IEC 61439-1 20 kA/60 ms max according to IEC 61439-1 32 kA

    Rated insulation voltage (Ui) 500 V AC 500 V AC 750 V 750 V 750 VRated operational voltage (Ue) 440 V AC 440 V AC 690 VAC 690 VAC 690 VACRated impulse withstand voltage (Uimp) 6 kV 6 kV 8 kV 8 kV 8 kVRated short-time current Icw (Icw) 4.5 kA rms/1s 4.5 kA rms/1sRated operational frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 HzDegree of protection IPxxB IPxxB IPxxB IPxxB IPxxBIncoming terminals 1 tunnel terminal 25/ph 1 tunnel terminal 25/ph 1 tunnel terminal 35/ph 1 tunnel terminal 35/ph 1 tunnel terminal 70/phTotal connection capacity, outgoing terminals 24 connections:

    4 x 6/phase12 x 6/neutral

    24 connections:4 x 6/phase12 x 6/neutral

    52 connections:7 x 4/phase3 x 6/phase2 x 10/phase1 x 16/phase (screw terminal)

    52 connections:7 x 4/phase3 x 6/phase2 x 10/phase1 x 16/phase (screw terminal)

    6 connections:6 x 16/phase

    Dimensions (H x W x D) 96.5 x 72 x 628 x 9 mm pitch

    96.5 x 72 x 628 x 9 mm pitch

    127 x 108 x 488 x 9 mm pitch

    127 x 108 x 488 x 9 mm pitch

    95 x 36 x 704 x 9 mm pitch

    Installation Clipped onto a DIN rail Clipped onto a DIN rail Screwed to plain or slotted backplate or onto DIN rail Screwed to plain or slotted backplate or onto DIN rail Onto DIN railOther Possible to combine 2 terminal blocks

    (2nd terminal block supplied from enclosed terminals in the 1st, Imax of 2nd terminal block: 80 A)

    Possible to combine 2 terminal blocks (2nd terminal block supplied from enclosed terminals in the 1st, Imax of 2nd terminal block: 80 A)

    Standard for installation inside Prisma IEC 61439-2 IEC 61439-2 IEC 61439-2 IEC 61439-2 IEC 61439-2Glow-wire 60695-2-11 960C 960C 960C 960C 960CDegree of pollution 3 3 3 3 3References 04040 04041 04045 04046 04031

    Accessories(4 x 125 A flexible connectors) Copper spacer (batch of 4)

    References - - 04047 04037

    LIN003-EN_FR Version : 1.0

    PB

    5023

    70

    DD

    3833

    00-L

    IN

    PB

    5009

    24

    PB

    5009

    25-2

    PB

    1038

    10

  • 25/01/201320

    Description b The Linergy DP Quick distribution block is designed for installation directly

    downstream of Compact NSX and INS up to 250 A. It can also be clipped onto a modular rail.

    Advantages b It is quick to mount in the horizontal position. E lectrical connections are made

    directly to the device terminals. b It is the same width as the devices and does not take up any additional space

    in the switchboard. b The connection terminals are slanted to facilitate cable entry and avoid exc eeding

    the bending radius of the flexible and rigid cables.

    IEC 60947-7-1, IEC 61439-1 & 2

    Linergy distribution systems Distribution blocks

    Linergy DPQuick distribution blocks

    Quick distribution blocks for compact devices Additional blockNumber of poles 3P 4P 3P 4P

    Rated operational current (Ie) 250 A 250 A 250 A 250 ARated peak withstand current (Ipk) 32 kA 32 kATotal connection capacity, outgoing terminals 27 connections:

    6 x 10/phase3 x 16/phase

    36 connections:6 x 10/phase3 x 16/phase

    2 connections:2 x 35 per pole

    2 connections:2 x 35 per pole

    Incomer terminals 1 cable lug 120 mm per poleDimensions (H x W x D) 105 x 138 x 63 140 x 138 x 64Installation On mounting plate or DIN rail On mounting plateProduct certifications ASE F A - K E M A ASE F A - K E M AStandard for installation inside Prisma IE C 61439 -1-2 IE C 61439 -1 & 2G low-wire 6069 5-2-11 9 60C 9 60CReferences 04033 04034 04155 04156

    Accessories

    Description 2 x 352 3P for Linergy DP 250 A

    2 x 352 4P for Linergy DP 250 A

    References 04155 04156

    LIN002-E N_ F RVersion : 1.0

    PB

    5023

    71

    PB

    5023

    71

    PB

    1038

    12

    PB

    1038

    11P

    B50

    2371

    PB

    5023

    71

    PB

    1038

    12

  • 25/01/2013 21

    InstallationIt can also be mounted downstream of vertically mounted Compact NS X 100/ 250 and Interpact INS 250 devices in the enclosures.In this case, the Linergy DP is mounted on a depth-adj ustable modular rail.

    Directly on the mounting plates of horizontally mounted Compact NS X 100/ 250 and Interpact INS 250 devices in the enclosures.

    T ech nical dataCommon ch aracteristicsRated conditional short-circuit current of an assembly

    (Icc) The reinforced breaking capacity due to cascading in circuit-breaker combinations is maintained.The worst-case situations have been tested.

    Rated insulation voltage (U i) 750 V ACRated operational voltage (U e) 69 0 VRated impulse withstand voltage (U imp) 8 kVNetwork frequency 50/60 HzDegree of protection IPxxBDegree of pollution 3Overvoltage category III

    Additional tech nical ch aracteristicsReference temperature 40COperating temperature -25C to 55C

    Linergy distribution systems Distribution blocks

    Linergy DPQuick distribution blocks

    LIN002-E N_ F R Version : 1.0

    DD

    3807

    80D

    D38

    1346

  • 22

  • 25/01/2013 23

    Linergy distribution systems Device feedersContents

    Linergy FM 24

    Quick device feeders 24

    Linergy FH 26

    Horizontal comb busbar for 27 mm pitch for C120, NG125Horizontal comb busbar for 18 mm pitch for Acti 9 / Multi 9Horizontal comb busbar for 9 mm pitch for Acti 9, C60Horizontal comb busbar for 18 mm pitch for DomaeHorizontal biconnect comb busbar for 18 mm pitch

    2627293132

    Linergy FV 33

    Vertical comb busbar 33

    Linergy FC 34

    Feeders for Compact NSX & INS 34

    Linergy FT 36

    Tesys comb busbar 36

    02_00-Sommaire Version : 1.0

  • 25/01/201324

    Linergy distribution systems Device feeders

    Linergy FMQuick device feeders

    Description b Distribution over full rows of modular devices. b The distribution block is generally supplied by busbars in enclosures and cubicles. b E asy phase balancing. b M ix of devices and functions in the same row. b Installation 160 A: clipped onto the back of a modular rail or screwed onto a solid or

    pre-slotted plate.

    Distribution blocksNumber of poles 4P 4P 4P 2P 3P 4P 4P

    63 A 8 0 A 160 A 200 A 200 A 200 A 200 ARated peak withstand current (Ipk) 15 k 15 k 27 k 25 k 25 k 30 k 27 kRated conditional short-circuit current of an assembly

    (Isc) The cascading reinforced breaking capacity when combining circuit breakers is maintained. The worst-case scenarios have been tested. The characteristics are exa ctly right for the connected devices. Circuit breakers and switches still have their temperature derating curves, and their whole performance is maintained.

    The cascading reinforced breaking capacity when combining circuit breakers is maintained. The worst-case scenarios have been tested.

    Insulation voltage (U i) 500 V AC 500 V AC 750 V AC 750 V AC 750 V AC 750 V ACRated voltage (U e) 440 V AC 440 V AC 690 V AC 690 V AC 690 V AC 690 V ACRated impulse withstand voltage (U imp) 6 kV 6 kV 8 kV 8 kV 8 kV 8 kVM axi mum current (Imax) - - 50 A for feeder for 10 mm2 cable/63 A for feeder for 2 10 mm2 cablesRated operational frequency 50/60 H] 50/60 H]Degree of protection IPxxB IP20 IPxxBSupply at incoming terminals E nclosed terminals for cables up to 25 mm2 Enclosed terminals for flexible cables 6 to 25 mm2

    or rigid cables 10 to 35 mm2Direct onto the row by cable 50 mm2 with crimped lug, or flexible bar 20 x 3F rom Linergy B W insulated busbar in enclosure or cubicle with connection ref. 04021F rom Linergy B S sheathed busbar with connection ref. 04024F rom Linergy B S rear busbar with connection ref. 04029

    Total connection capacity at outgoing terminals 6pring terminals: 4 for each phase (2 x 1 to 4 mm2 2 x 1 to 6 mm2) 8 for the neutral (4 x 1 to 4 mm2 4 x 1 to 6 mm2)

    6pring terminals for rigid or flexible cables without ferrule: 6 for each phase (1 to 6 mm2)18 for the neutral (1 to 6 mm2)

    6 connection points for each phase9 connection points for the neutral

    12 connection points for the phase and the neutral

    12 connection points for each phase18 connection points for the neutral

    W idth 24 9-mm pitches 12 18-mm modules

    48 9-mm pitches 24 18-mm modules

    24 9-mm pitches 12 18-mm modules

    48 9-mm pitches24 18-mm modules

    72 9-mm pitches36 18-mm modules

    Composition Stripped copper connections (L= 100 mm) 10 x 4 mm2 + 6 x 6 mm2

    6tripped copper connections (L 105 mm) 6 mm2 (12 blue + 12 black)

    2 sachets with 12 stripped copper connections 10 mm2 (L= 100 mm)Protective covers for power supply rows (IPxxB )F ixi ng accessories for power supply rows

    References 04008 04000 04018 04012 04013 04014 04026

    Installation

    Clipped onto the back of a modular rail, or screw fixing.

    Clipped onto the back of a modular rail, or screw fixing.

    Can be mounted in Pragma E volution enclosures and in Prisma Pack 160

    IEC 60947-7-1, IEC 61439-2

    LIN022-E N_ F RVersion : 1.0

    PB

    1045

    05-5

    0

    DD

    3816

    61-L

    IN

    DD

    3840

    88-L

    IN

    DD

    3816

    64-L

    IN

    DB

    1241

    95-L

    IND

    B12

    4196

    -LIN

  • 25/01/2013 25

    Linergy distribution systems Device feeders

    Linergy FMQuick device feeders

    Distribution blocksNumber of poles 4P 4P 4P 2P 3P 4P 4P

    63 A 8 0 A 160 A 200 A 200 A 200 A 200 ARated peak withstand current (Ipk) 15 k 15 k 27 k 25 k 25 k 30 k 27 kRated conditional short-circuit current of an assembly

    (Isc) The cascading reinforced breaking capacity when combining circuit breakers is maintained. The worst-case scenarios have been tested. The characteristics are exa ctly right for the connected devices. Circuit breakers and switches still have their temperature derating curves, and their whole performance is maintained.

    The cascading reinforced breaking capacity when combining circuit breakers is maintained. The worst-case scenarios have been tested.

    Insulation voltage (U i) 500 V AC 500 V AC 750 V AC 750 V AC 750 V AC 750 V ACRated voltage (U e) 440 V AC 440 V AC 690 V AC 690 V AC 690 V AC 690 V ACRated impulse withstand voltage (U imp) 6 kV 6 kV 8 kV 8 kV 8 kV 8 kVM axi mum current (Imax) - - 50 A for feeder for 10 mm2 cable/63 A for feeder for 2 10 mm2 cablesRated operational frequency 50/60 H] 50/60 H]Degree of protection IPxxB IP20 IPxxBSupply at incoming terminals E nclosed terminals for cables up to 25 mm2 Enclosed terminals for flexible cables 6 to 25 mm2

    or rigid cables 10 to 35 mm2Direct onto the row by cable 50 mm2 with crimped lug, or flexible bar 20 x 3F rom Linergy B W insulated busbar in enclosure or cubicle with connection ref. 04021F rom Linergy B S sheathed busbar with connection ref. 04024F rom Linergy B S rear busbar with connection ref. 04029

    Total connection capacity at outgoing terminals 6pring terminals: 4 for each phase (2 x 1 to 4 mm2 2 x 1 to 6 mm2) 8 for the neutral (4 x 1 to 4 mm2 4 x 1 to 6 mm2)

    6pring terminals for rigid or flexible cables without ferrule: 6 for each phase (1 to 6 mm2)18 for the neutral (1 to 6 mm2)

    6 connection points for each phase9 connection points for the neutral

    12 connection points for the phase and the neutral

    12 connection points for each phase18 connection points for the neutral

    W idth 24 9-mm pitches 12 18-mm modules

    48 9-mm pitches 24 18-mm modules

    24 9-mm pitches 12 18-mm modules

    48 9-mm pitches24 18-mm modules

    72 9-mm pitches36 18-mm modules

    Composition Stripped copper connections (L= 100 mm) 10 x 4 mm2 + 6 x 6 mm2

    6tripped copper connections (L 105 mm) 6 mm2 (12 blue + 12 black)

    2 sachets with 12 stripped copper connections 10 mm2 (L= 100 mm)Protective covers for power supply rows (IPxxB )F ixi ng accessories for power supply rows

    References 04008 04000 04018 04012 04013 04014 04026

    Connections to th e distribution block

    4P 200 A connection (supplied with fixing accessories)

    4P 200 A connection (supplied with fixing accessories)

    4P 200 A connection (supplied with fixing accessories)

    4P 160 A connection for Linergy F M 1/2 row

    Allows power supply from Linergy B W busbar Linergy B S sheathed busbar Linergy B S rear busbar SwitchgearReferences 04021 04024 04029 04030

    S pare parts

    4 covers for 160/200 A Linergy F0 rowsReferences 01202

    LIN022-E N_ F R Version : 1.0

    DD

    3816

    73-L

    IN

    DD

    3816

    72-L

    IN

    DD

    3816

    70-L

    IN

    DD

    3816

    71-L

    IN

    DD

    3816

    74-L

    IN

    DD

    3834

    72-L

    IN

    DD

    3836

    17-L

    IN

    DD

    3845

    05-L

    IN

    PD

    3906

    61R

  • 25/01/201326

    Linergy distribution systems Device feeders

    Linergy FHHorizontal comb busbar for 27 mm pitchfor C120, NG125

    DescriptionComb busbars make it easier to install Schneider E lectric products.

    b Supplied with 2 side plates, IP 2 b Outgoing feeders can be marked b Cutting markings on the copper bars and the insulating material

    IEC 60664-1

    C120, NG 125 27 mm poles, cuttableNumber of poles 1P 2P 3P 4P

    Supplied with 2 side plates, IP2 and 4 tooth cover end-piecesOutgoing feeders can be markedCutting markings on the copper bars and the insulating materialU nused teeth can be insulated with tooth covers

    Rated operational current at 40C

    (Ie) 125 A

    Rated conditional short-circuit current of an assembly

    (Isc) Compatible with the breaking capacity of Schneider E lectric circuit breakers

    Insulation voltage (U i) 620 VRated voltage (U e) 500 VF ire resistance to IE C 69 5-2-1 Self-ext inguishing 9 60C 30 sColour RAL 7016 (anthracite grey)

    U se Power supply by connector recommended

    Number of 27 mm modules 16 16 15 16Set of 1

    References 148 11 148 12 148 13 148 14

    Installation

    1 2

    Comb busbars allow dismountability (1-2)

    AccessoriesNumber of poles 1P, 2P, 3P, 4P

    T ooth covers Insulated connectorCompatible with all Schneider E lectric comb busbarsClip onto the comb busbar' s insulating material, which gives them very great stabilityReceive clip-on markers allowing circuit identification

    U seF or 25 mm2 semi-rigid cable

    Set of 20 4References 148 18 148 8 5

    Installation

    LIN001-E N_ F RVersion : 1.0

    0309

    20d

    0309

    20d

    DB

    1059

    77-L

    IN

    0309

    21d

    DB

    1059

    77

    DB

    1059

    76

    PG

    1340

    71

  • 25/01/2013 27

    Linergy FHHorizontal comb busbar for 18 mm pitchfor Acti 9 / Multi 9

    Linergy distribution systems Device feeders

    DescriptionComb busbars make it easier to install Schneider E lectric products.

    b Can be sawn and cut in a single pass b Supplied with two IP20 lateral end-pieces exce pt for 57 module references b The end-pieces are compulsory after cutting b 7he phases are identified by symbols on each side of the comb busbar for installation in all

    positions b Cutting marks on the insulating material b The special comb busbars for circuit breakers with 9 mm auxi liaries have a 9 mm gap for

    inserting iOF and iSD

    IEC 60947-7-1, IEC 61439-2

    Acti 9 / M ulti 9 18 mm poles, cuttableNumber of poles 1P 2P 3P 4P 3 ( N+ P) Aux + 1P Aux + 2P Aux + 3P Aux + 4P3 ( Aux + 1P)3 ( Aux + N+ 1P)

    Rated operational current at 40C

    (Ie) 100 A

    Rated conditional short-circuit current of an assembly

    (Isc) Compatible with the breaking capacity of Schneider E lectric circuit breakers

    Insulation voltage (U i) 500 VRated voltage (U e) 415 VF ire resistance to IE C 69 5-2-1Self-ext inguishing 9 60C 30 sColour RAL 7016 (anthracite grey)U se

    Power supply by connector recommended Type L1 L1L2 L1L2L3...NL1L2L3 NL1NL2

    N L3AuxL 1... Aux L1L2 Aux L1L2L3 Aux NL1

    L2L3Aux L1 Aux L2 Aux L3

    Aux L1 Aux L2 Aux L3

    Set of 1 1 1 1 1 1 1 1 1 1 1References6 modules of 18 mm A9X PH 106- - - - - - - - - -12 modules of 18 mm A9X PH 112 A9X PH 212 A9X PH 312 A9X PH 412 A9X PH 512- - - - - -18 modules of 18 mm - - - - A9X PH 518- - - - - -24 modules of 18 mm A9X PH 124 A9X PH 224 A9X PH 324 A9X PH 424 A9X PH 524- - - - - -57 modules of 18 mm A9X PH 157 A9X PH 257 A9X PH 357 A9X PH 457 A9X PH 557 A9X AH 157 A9X AH 257 A9X AH 357 A9X AH 457 A9X AH 657 A9X AH 557

    Installation

    AccessoriesNumber of poles 1P 2P 3P 4P - - -

    End-pieces T ooth covers ConnectorsM onoconnect Double terminals

    Lateral end-pieces providing IP20 protection Insulate teeth that have been left free

    Comb busbar power supply. Horizontal incomer on each side. F or 35 mm2 cable. Tightening torque 4 N.m

    Set of 10 10 10 10 20 4 4

    References A9X PE110 A9X PE210 A9X PE310 A9X PE410 A9X PT 920 A9X PCM 04 A9X PCD04

    LIN001-E N_ F R Version : 1.0

    PB

    1102

    52-2

    4

    PB

    5023

    79

    PB

    1102

    90-

    40

    PB

    1107

    93-

    40

    DB

    4048

    06

    DB

    4048

    06

    PB

    1102

    58-1

    5

    PB

    1102

    59-2

    2

    PB

    1081

    38-2

    5

  • 25/01/201328

    Linergy distribution systems Device feeders

    Linergy FHHorizontal comb busbar for 18 mm pitchfor Acti 9 / Multi 9

    DescriptionComb busbars make it easier to install Schneider E lectric products.7he phases are identified by symbols on each side of the comb busbar.Dismountability of devices with Acti 9 .

    IEC 60947-7-1, IEC 61439-2

    Acti 9 / M ulti 9 18 mm poles, not cuttableNumber of poles 1P 2P 3P 4P 3 ( N+ P)

    Rated operational current at 40C (Ie) 100 ARated conditional short-circuit current of an assembly

    (Isc) Compatible with the breaking capacity of Schneider E lectric circuit breakers

    Insulation voltage (U i) 500 VRated voltage (U e) 415 VF ire resistance to IE C 69 5-2-1 Self-ext inguishing 9 60C 30 sColour RAL 7016 (anthracite grey)U se

    Power supply by connector recommended Type L1 L1L2 L1L2L3 NL1L2L3 NL1NL2NL3Set of 1 1 1 1 1References12 modules of 18 mm A9X PM 112 A9X PM 212 A9X PM 312 A9X PM 412 A9X PM 512

    Installation

    Accessories

    T ooth covers ConnectorsDouble terminals M onoconnect

    Insulate teeth that have been left free Comb busbar power supply U se

    Horizontal incomer on each sideF or 35 mm2 cableTightening torque 4 N.m

    Set of 20 4 4References A9X PT 920 A9X PCD04 A9X PCM 04Installation

    LIN001-E N_ F RVersion : 1.0

    PB

    1102

    31-1

    5

    PB

    5023

    80

    PB

    1102

    90-

    40

    PB

    1107

    93-

    40

    PB

    1102

    57-1

    0

    PB

    1102

    59-1

    5

    PB

    1102

    58-2

    2

    PB

    1081

    62-3

    8

    PB

    1081

    64-3

    8

  • 25/01/2013 29

    Linergy distribution systems Device feeders

    DescriptionComb busbars ensure:

    b E asy, reliable mounting of 1P+ N and 3P+ N, TL, CT, ID, V, B P and Cm switchgear: tooth positioning opposite the device terminals is ensured by indexi ng of copper parts

    b C60/ID G roup F eeder comb busbars contain two different parts: v Connection of G roup F eeder switchgear: C60 (3P+ N) or ID (3P+ N) circuit breaker in 18 mm

    modules, powered by cables, through the bottom, directly by the terminals v Connection of Clario, Prodis and Librio switchgear in 9 mm modules

    IEC 60439-1

    Linergy FHHorizontal comb busbar for 9 mm pitchfor Acti 9, C60

    Acti 9 Ph + N 9 mm poles, cuttableNumber of poles 1P+ N 3P+ N

    21501 21505Complete comb busbars (supplied with 4 side plates and 1 tooth cover)

    Rated operational current at 40C (Ie) 80 ARated conditional short-circuit current of an assembly

    (Isc) Compatible with the breaking capacity of Schneider E lectric circuit breakers

    Insulation voltage (U i) 440 VRated voltage (U e) 230 V (P4 + N) - 400 V (3Ph + N)Rated impulse withstand voltage (U imp) 6 kVDegree of protection IP20F ire resistance to IE C 69 5-2-1 Self-ext inguishing 9 60C 30 sColour RAL 7035Number of 18 mm modules Comb

    busbar12 18 24 12 18 24

    Tooth cover

    3 3 6 3 3 6

    References 21501 19512 21503 21505 09516 21507Comb busbars aloneNumber of 18 mm modules Comb

    busbar48 48

    References 2108 9 21093

    C60/ ID G roup F eeder comb busbars aloneNumber of poles 3P+ N

    Rated operational current at 40C (Ie) 80 ARated conditional short-circuit current of an assembly

    (Isc) Compatible with the breaking capacity of Schneider E lectric circuit breakers

    Insulation voltage (U i) 440 VRated voltage (U e) 230 V (P4 + N) - 400 V (3Ph + N)Rated impulse withstand voltage (U imp) 6 kVDegree of protection IP20F ire resistance to IE C 69 5-2-1 Self-ext inguishing 9 60C 30 sColour RAL 7035Number of 18-mm modules 12 48 48Power supply Through left-hand Through left-hand Through right-handReferences 10545 10546 10547

    AccessoriesNumber of poles 1P+ N 3P+ N

    End-pieces T ooth covers ( 3 x 18 -mm modules) T ooth covers ( 1 x 18 -mm module) Connectors ( grey )Set of 40 12 10 4References 021094 021095 021096 010405 021098

    LIN001-E N_ F R Version : 1.0

    DB

    1237

    29

    DB

    1237

    30

    DB

    1011

    84-1

    0

    DB

    1237

    32

    DB

    1237

    33

    DB

    1237

    31

    PB

    5023

    82

  • 25/01/201330

    Acti 9 9 mm poles, cuttableNumber of poles 1P+ N 3P+ N 1P+ N 3P+ N

    A9 N21036Comb busbars Comb busbars DPN V igi

    Rated operational current at 40C (Ie) 63 ARated conditional short-circuit current of an assembly

    (Isc) Compatible with the breaking capacity of Schneider E lectric circuit breakers

    Insulation voltage (U i) 500 VRated voltage (U e) 230 V ( P4 + N) - 400 V (3Ph + N)Degree of protection IP20F ire resistance to IE C 69 5-2-1 Self-ext inguishing 9 60C 30 sColour RAL 7035Number of 18-mm modules 56 56 56 56References A9N21035 A9N21036 A9N21037 A9N21038

    AccessoriesNumber of poles 1P+ N 3P+ N

    End-pieces Connectors ( grey ) Neutral connectors ( blue) T ooth cover ( 1 x 18 mm module)Set of 20 10 10 10References A9N21039 A9N21040 A9N21041 A9N21042 A9N21050

    Linergy distribution systems Device feeders

    Linergy FHHorizontal comb busbar for 9 mm pitchfor Acti 9

    IEC 60439-1

    Description b Connection of Clario, Prodis and Librio switchgear in 9 mm modules b The special comb busbars for circuit breaker have a gap of 9 mm for inserting OF , SD,

    OF -SD/OF auxi liaries b The comb busbars for 3P+ N circuit breakers and auxi liaries are compatible with Prisma

    switchboard b 1P+ N comb busbars with Prisma and Pragma 24

    LIN001-E N_ F RVersion : 1.0

    PB

    1108

    04-1

    0

    PB

    1108

    05-1

    0

    PB

    1108

    06-1

    0

    PB

    1108

    07-1

    0

    PB

    1108

    01-1

    0

    PB

    5023

    83

  • 25/01/2013 31

    Linergy distribution systems Device feeders

    Linergy FHHorizontal comb busbar for 18 mm pitchfor Domae

    DescriptionComb busbars:

    b E nsure easy reliable mounting of switchgear: tooth positioning opposite the device terminals is ensured by indexi ng of copper parts.

    b Can be sawn and cut. b Are supplied with two IP20 lateral end-pieces (the end-pieces are compulsory) . b U nused teeth can be insulated with tooth covers.

    IEC 60439-1, IEC60664

    Domae 18 mm poles, cuttableNumber of poles 1P 2P 3P 4P L 1N/ L 2N/ L 3N

    Rated operational current at 40C

    (Ie) 63 A

    Rated conditional short-circuit current of an assembly

    (Isc) Compatible with the breaking capacity of Schneider E lectric circuit breakers

    Insulation voltage (U i) 500 VRated voltage (U e) Ph/N 230 V AC

    Ph/Ph 400 V ACF ire resistance to IE C 69 5-2-1 Self-ext inguishing 850C 30 sColour RAL 7035Power supply B y 16 mm2 semi-rigid or 10 mm2 flexible cable

    W ith connectorNumber of 18 mm modules 12 57 12 57 12 57 12 57 57References 1038 7 1038 8 1038 9 10390 10391 10392 10393 10394 10395

    Installation

    Accessories

    T y pe Connectors ( 4, 35 mm ) End-pieces ( 2 ph ases) End-pieces ( 3 ph ases) End-pieces ( 4 ph ases)T ooth coversSet of 1 10 10 10 10References 10397 10398 10399 10405 10396

    LIN001-E N_ F R Version : 1.0

    PB

    1016

    26-3

    5

    PB

    5023

    72P

    B10

    1630

    _S

    E-4

    0

    PB

    1016

    32-1

    0

    PB

    5023

    76

    PB

    1108

    98

    PB

    5023

    73

  • 25/01/201332

    Linergy distribution systems Device feeders

    Linergy FHHorizontal biconnect comb busbar for 18 mm pitch

    DescriptionDistribution and sub-distribution of the electric power supplyF ast assembly and disassembly of connected devices

    IEC60664-1

    H orizo ntal biconnect comb busbar

    18 mm poles, cuttable

    Number of poles 1P 2P 3P 4P

    Rated operational current at 40C (Ie) 63 ARated conditional short-circuit current of an assembly

    (Isc) Compatible with the breaking capacity of Schneider E lectric circuit breakers

    Insulation voltage (U i) 500 VRated voltage (U e) Ph/N 230 V AC

    Ph/Ph 400 V ACF ire resistance to IE C 69 5-2-1 Self-ext inguishing 9 60C 30 sColour RAL 7035 (grey)U se

    Power supply: into box lug (25 mm rigid or 16 mm flexible) or by connector (35 mm rigid or 25 mm flexible with ferrule)Type L1 L1L2 L1L2L3 L1L2L3L4Number 18 mm, modules 12 18 57 12 18 57 12 18 57 12 18 57Set of 1 1 1 1 1 1 1 1 1 1 1 1References R9X F H 112 R9X F H 118 R9X F H 157 R9X F H 212 R9X F H 218 R9X F H 257 R9X F H 312 R9X F H 318 R9X F H 357 R9X F H 412 R9X F H 418 R9X F H 457

    Installation

    H orizo ntal biconnect comb busbar 18 mm poles, cuttableNumber of poles 4P

    Rated operational current at 40C (Ie) 63 ARated conditional short-circuit current of an assembly (Isc) Compatible with the breaking capacity of Schneider E lectric circuit breakersInsulation voltage (U i) 500 VRated voltage (U e) Ph/N 230 V AC

    Ph/Ph 400 V ACF ire resistance to IE C 69 5-2-1 Self-ext inguishing 9 60C 30 sColour RAL 7035 (grey)U se Type NL1L2L3L4 - NL1NL2NL3 NL1NL2NL3Number 18 mm, modules 18 18 57Set of 1 1 1References R9X F H 518 G R9X F H 518 R9X F H 557

    Installation

    AccessoriesNumber of poles 1P 2P 3P 4P

    End-pieces T ooth covers ConnectorsSet of 10 20 4References R9X E110 R9X E210 R9X E310 R9X E410 R9X T 20 R9X F C04

    LIN001-E N_ F RVersion : 1.0

    PB

    1108

    76-1

    5

    PB

    1108

    79-1

    5

    PB

    1108

    82-1

    5

    PB

    1108

    85-1

    5

    PB

    1108

    88-1

    5

    PB

    1108

    89-1

    5

    PB

    5023

    81

    DB

    4059

    95

    DB

    4059

    95

    PB

    1108

    95-

    15

    PB

    1108

    98

    PB

    1108

    99

    -30

  • 25/01/2013 33

    Linergy distribution systems Device feeders

    Linergy FVVertical comb busbar

    DescriptionProvide a 2P supply to the main incomers from one row to the next :

    b Centre line between rows: 125 mm or 150 mm b Distances between terminals: 9 mm or 18 mm pitch

    IEC 60664-1

    V ertical comb busbars

    Direct power supply to circuit breaker or residual current circuit breaker terminalsRated operational current at 40C (Ie) 80 ARated conditional short-circuit current of an assembly

    (Isc) Compatible with the breaking capacity of Schneider E lectric circuit breakers

    Insulation voltage (U i) 500 VRated voltage (U e) 415 VF ire resistance to IE C 69 5-2-1 Self-ext inguishing 850C 30 sDistance between upstream terminals 9 mm 18 mm 18 mm 9 mm 18 mmDistance between downstream terminals 9 mm 9 mm 18 mm 9 mm 18 mmCentre line between rows 125 mm 150 mmColour RAL 7035 (light grey) RAL 7016 (anthracite grey)References 14900 14909 14910 14901 14911

    Installation

    LIN001-E N_ F R Version : 1.0

    PB

    5023

    84

    PB

    5023

    77P

    B10

    6071

    _40

    PB

    1060

    73_

    40

    PB

    1060

    63-4

    0

    PB

    1060

    72_

    40

    PB

    1060

    74_

    40

  • 25/01/201334

    Fix ed Co m p act NSX100/ 250 w it h t o ggl e and I nt erp act I NS250

    Fix ed / p l u g- in Co m p act NSX, al l o p erat ing syst em s (1) (2)

    Nu m b er o f p o l es4P 3P 4P 3P 4P 3P

    Linergy FC w it h p re- w ired co nnect o rsLinergy FC w it h p re- w ired co nnect o rsLinergy FCw it h o u t co nnect o rs (3)

    Connection to Linergy LGY busbars Flat Linergy B S or Linergy LGY busbars Linergy B S or Linergy LGY , LGY E busbars

    Number of devices 4 3 4 3 4 3

    Composition Self-adhesive labels to mark the phases for connections to the busbars

    References 04403 04404 04405 04406 04407 04408

    I nst al l at io n

    Auxiliary wires running in the built-in trunking. Phase marking on the front of the distribution block.

    Linergy distribution systems Device feeders

    Linergy FCFeeders for Compact NSX & INS

    Descrip t io nLinergy FC is an insulated horizontal distribution block, directly connected to the mounting plate.

    b The design and small size blend perfectly with the devices. b It can be supplied by flat or Linergy busbars positioned to the left or right. b Fully insulated, Linergy FC contributes to the safety of people and property. b Numerous well distributed vents ensure natural convection and optimum cooling of the

    conductors. b The circuit breakers can be easily connected from the front. It is simple to replace a device

    or to add a device in a reserve slot. b There are markings ( N, L1, L2, L3) on the front and the sides for the phases. b The running of auxiliary cables between the devices and the corresponding terminal blocks

    is also taken into account. Spacious trunking is built into the blocks for the auxiliary wiring. b It can supply 3 compact 4P, or 4 compact 3P, whatever the rating ( from 100 to 250 A) and the

    operating systems (toggle, rotary handle, motor mechanism), whether fixed or plug-in, front or rear connection.

    I EC 61439- 1 & 2

    ( 1) For plug-in Compact NSX circuit breakers, order the adapter LV429306 ( 3P) or LV429307 ( 4P) with the base.(2) 7he connection of a Linergy F& distribution block using pre-wired connectors or insulated flexible bars is not compatible with Form 2 partitioning (04922).In this case, use the form 2 restoration kit (04924): see the Prisma P catalogue.(3) 0ake the connection with flexible bars, 32 x 8 mm (04753) : see the Prisma P catalogue.

    Accesso ries

    To o t h co v ersThe covers block off the reserve terminals on a Linergy FC four-pole distribution blockMade of an insulating material, they simply clip on from the front

    References 04809

    LIN010-EN_FRVersion : 1.0

    DD

    3812

    47

    DD

    3812

    49

    DD

    3812

    51-L

    IN

    DD

    3812

    52-L

    IN

    DD

    3812

    50-L

    IN

    DD

    3835

    94-L

    IN

    DD

    3812

    55-L

    IN

    PB

    3905

    69P

    B39

    0570

  • 25/01/2013 35

    Linergy distribution systems Device feeders

    Linergy FCFeeders for Compact NSX & INS

    Tech nical d at a Co m m o n ch aract erist icsRated operational current at 40 ( In) Distribution block derating follows the normal

    derating curves of Compact NSX and INS devicesRated insulation voltage ( U i) 750 VRated operational voltage ( U e) 690 VRated impulse withstand voltage U imp 8 kVRated peak withstand current ( Ipk) 50 kA rmsRated conditional short-circuit current of an assembly

    Short-circuit withstand current compatible with the breaking capacity of the Compact NSX circuit breakers connected to the distribution block

    Reference temperature 40 CO perating temperature 60&

    Linergy FC sel ect io n t ab l e fo r sp ecial casesI n (A) d ep end ing o n t h e t em p erat u re insid e t h e sw it ch b o ardTemperature ( C) 40 45 50 55 60 65 70Inc ( A) 3P 800 800 775 750 725 700 675

    4P 675 675 655 635 615 595 570

    b To obtain the maximum permissible current for the Linergy FC distribution block, apply the rated diversity factor RDF:

    b 3P 5DF 0.8 b 4P 5DF 0.9

    LIN010-EN_FR Version : 1.0

  • 25/01/201336

    Co m b inat io n b l o ck s S- sh ap e b u sb ars

    115 A b u sb ars fo r co nnect ing co nt act o rs in p aral l el

    Set s o f 3- p o l e 63 A b u sb ars

    B etween GV2 and contactor LC1 K or LP1 K

    B etween GV2 and contactor LC1 D09 D38

    B etween GV2 mounted on LAD 311 and contactor LC1 D09 D38

    For circuit-breakers GV3 P and GV3 L

    and contactors LC1 D40AD 65A

    Contactors LC1 D40AD 65A 2 tap-offs 3 tap-offs 4 tap-offs 5 tap-offsPit ch m m45 54 72 45 54 45 54 72 54

    Set of 10 10 10 2 3References GV2 AF01 GV2 AF3 GV2 AF4 GV3 S GV3 G264 GV3 G364 GV2 G245 GV2 G254 GV2 G272 GV2 G345 GV2 G354 GV2 G445 GV2 G454 GV2 G472 GV2 G554

    Linergy distribution systems Device feeders

    Linergy FTTesys comb busbar

    Accesso ries

    Pro t ect iv e end co v er Term inal b l o ck fo r su p p l y t o o ne o r m o re GV2 G b u sb ar set s

    Co v er fo r t erm inal b l o ck

    Fl ex ib l e 3- p o l e co nnect ing a GV2 t o a co nt act o r LC1- D09 D25

    Ad ap t er p l at es Heigh t co m p ensat io n p l at eMo t o r st art er ad ap t er p l at e Co nnect io ns u p st ream / d o w nst ream

    For unused busbar outlets

    Connection from the top &an be fitted with current limiter GV1 L3 ( GV2 ME and GV2 P)

    For mounting in modular panels

    Centre distance between mounting rails: 100 120 mm

    For mounting a GV2 ME or GV2 P and contactor LC1 D09 D38 with front faces aligned

    7.5 mm W ith 3-pole connection for mounting a GV2 and a contactor LC1 D09 D25

    For connecting GV2 ME to a printed circuit board

    Set of 5 1 1 10 10 1 10 1 10References GV1 G10 GV1 G09 GV1 G05 LA9 E07 GV1 G02 LAD 311 GV1 F03 GK2 AF01 GV2 GA01

    Accesso ries fo r m ain p o l e and co nt ro l co nnect io nsNu m b er o f p o l es 4- p o l e 10 m m 2 3- p o l e 25 m m 22- p o l e 3- p o l e 4- p o l e

    Co nnect o rs fo r cab l e, size (1 co nnect o r) Link s fo r p aral l el co nnect io n o fFor use with contactors LC1

    (a) DT20, DT25 D09D 38 D09D 38 DT20, DT25 ( 4P) DT32, DT40 ( 4P)D40AD 65A D80, D95 D09D 38 D40AD 65A D80, D95 DT20, DT25 D80, D95(c) DT20, DT25 D09D 38 D09D 38 DT20, DT25 ( 4P) DT32, DT40 ( 4P)D40AD 65A D80 D09D 38 D40AD 65A D80, D95 DT20, DT25 D80

    Set of 1 1 10 10 10 1 2 10 1 1 2 2References LAD 92560 LA9 D3260 LA9 D2561 LA9 D1261 LAD 96061 LAD 9P32 LA9 D80961 LAD 9P3 LAD 9P33 LA9 D80962 LA9 D1263 LA9 D80963

    Descrip t io nIt is much easier to create protection and control blocks, thanks to a range of accessories.These can be used to:

    b Supply power to a group of blocks ( combs and connection blocks GV2 G ) b Fix a fuse-carrier and a contactor on top of one another ( mounting plate LAD 311) b Interconnect a fuse-carrier and its contactor ( rigid wiring modules GV2 AF , LAD 3 ) b U sing them creates considerably more space in the switchboard and reduces the wiring time

    LIN011-EN_FRVersion : 1.0

    PB

    5023

    91

    PB

    5023

    99

    PB

    5023

    92

    PB

    5023

    93

    DF5

    3779

    2-LI

    N

    DF5

    3779

    7-LI

    N

    DF5

    1099

    5-LI

    N

    PB

    5023

    90

    PB

    5023

    89

    PB

    5023

    88

    PB

    5023

    97

    PB

    5023

    87

  • 25/01/2013 37

    Co m b inat io n b l o ck s S- sh ap e b u sb ars

    115 A b u sb ars fo r co nnect ing co nt act o rs in p aral l el

    Set s o f 3- p o l e 63 A b u sb ars

    B etween GV2 and contactor LC1 K or LP1 K

    B etween GV2 and contactor LC1 D09 D38

    B etween GV2 mounted on LAD 311 and contactor LC1 D09 D38

    For circuit-breakers GV3 P and GV3 L

    and contactors LC1 D40AD 65A

    Contactors LC1 D40A D65A 2 tap-offs 3 tap-offs 4 tap-offs 5 tap-offsPit ch m m45 54 72 45 54 45 54 72 54

    Set of 10 10 10 2 3References GV2 AF01 GV2 AF3 GV2 AF4 GV3 S GV3 G264 GV3 G364 GV2 G245 GV2 G254 GV2 G272 GV2 G345 GV2 G354 GV2 G445 GV2 G454 GV2 G472 GV2 G554

    Linergy distribution systems Device feeders

    Linergy FTTesys comb busbar

    Accesso ries

    Pro t ect iv e end co v er Term inal b l o ck fo r su p p l y t o o ne o r m o re GV2 G b u sb ar set s

    Co v er fo r t erm inal b l o ck

    Fl ex ib l e 3- p o l e co nnect ing a GV2 t o a co nt act o r LC1- D09 D25

    Ad ap t er p l at es Heigh t co m p ensat io n p l at eMo t o r st art er ad ap t er p l at e Co nnect io ns u p st ream / d o w nst ream

    For unused busbar outlets

    Connection from the top &an be fitted with current limiter GV1 L3 ( GV2 ME and GV2 P)

    For mounting in modular panels

    Centre distance between mounting rails: 100 120 mm

    For mounting a GV2 ME or GV2 P and contactor LC1 D09 D38 with front faces aligned

    7.5 mm W ith 3-pole connection for mounting a GV2 and a contactor LC1 D09 D25

    For connecting GV2 ME to a printed circuit board

    Set of 5 1 1 10 10 1 10 1 10References GV1 G10 GV1 G09 GV1 G05 LA9 E07 GV1 G02 LAD 311 GV1 F03 GK2 AF01 GV2 GA01

    Accesso ries fo r m ain p o l e and co nt ro l co nnect io nsNu m b er o f p o l es 4- p o l e 10 m m 2 3- p o l e 25 m m 22- p o l e 3- p o l e 4- p o l e

    Co nnect o rs fo r cab l e, size (1 co nnect o r) Link s fo r p aral l el co nnect io n o fFor use with contactors LC1

    (a) DT20, DT25 D09D 38 D09D 38 DT20, DT25 ( 4P) DT32, DT40 ( 4P)D40AD 65A D80, D95 D09D 38 D40AD 65A D80, D95 DT20, DT25 D80, D95(c) DT20, DT25 D09D 38 D09D 38 DT20, DT25 ( 4P) DT32, DT40 ( 4P)D40AD 65A D80 D09D 38 D40AD 65A D80, D95 DT20, DT25 D80

    Set of 1 1 10 10 10 1 2 10 1 1 2 2References LAD 92560 LA9 D3260 LA9 D2561 LA9 D1261 LAD 96061 LAD 9P32 LA9 D80961 LAD 9P3 LAD 9P33 LA9 D80962 LA9 D1263 LA9 D80963

    LIN011-EN_FR Version : 1.0

    PB

    5023

    94

    PB

    5023

    95

    PB

    5023

    86

    PB

    5023

    98

    PB

    5023

    96

  • 25/01/201338

    Linergy distribution systems Device feeders

    Linergy FTTesys comb busbar

    Fo r 3- p o l e rev ersing co nt act o rs

    LAD 9R1 LAD 9R3 LA9 D8069Kit s fo r assem b l y o f rev ersing co nt act o rs Po w er co nnect io ns Fo r st ar- d el t a st art er

    Composition b A mechanical interlock LAD 9V2 with electrical interlock LAD 9V1

    b A set of power connections LAD 9V5 ( parallel) and LAD 9V6 ( reversing)

    b A mechanical interlock LAD 9V2 without electrical interlock

    b A set of power connections LAD 9V5 ( parallel) and LAD 9V6 ( reversing)

    b A mechanical interlock LAD 4CM

    b A set of power connections LA9 D65A69

    b A set of parallel bars b A set of reverser bars

    b 1 time delay contact block LAD S2 ( LC1 D09D 80) b Power circuit connections ( LC1 D09D 80) b Hardware required for fixing the contactors onto the mounting plate (L&1 D80)

    For contactors LC1 D09 to D38 LC1 D40A to D65A

    LC1 D09 to D38 with screw terminals or connectors

    LC1 D09D 32 with spring terminal connections

    LC1 D40A to D65A

    LC1 D80 and D95 (a)

    LC1 D80 and D95 (c)

    LC1 D115 and D150

    LC1 D09 and D12 LC1 D18 to D32 LC1 D40A and D50A

    LC1 D80 Eq u ip m ent m o u nt ing p l at es

    LC1 D09, D12 and D18

    LC1 D32 LC1 D40A and D50A

    LC1 D80

    References LAD 9R1V LAD 9R1 LAD 9R3 LAD 9V5 + LAD 9V6

    LAD 9V12 + LAD 9V13

    LA9 D65A69 LA9 D8069 LA9 D8069 LA9 D11569 LAD 91217 LAD 93217 LAD 9SD3 LA9 D8017 LA9 D12974 LA9 D32974 - LA9 D80973

    Fo r 4- p o l e ch angeo v er co nt act o r Fo r 3- p o l e ch angeo v er co nt act o r p airs

    LA9 D6570 LA9 D8070Kit s fo r assem b l y o f ch angeo v er co nt act o r p airs

    Set s o f p o w er co nnect io ns Mech anical int erl o ck s Set s o f p o w er co nnect io ns

    Composition b A mechanical interlock LAD 9V2 with electrical interlock LAD 9V1

    b A set of power connections ( changeover) LAD 9V7

    b A mechanical interlock LAD 9V2 without electrical interlock

    b A set of power connections ( changeover) LAD 9V7

    Comprising a set of parallel bars W ithout integral electrical interlock

    W ith integral electrical interlock

    Comprising a set of parallel bars

    For contactors LC1 DT20 to DT40 withscrew terminals or connectors

    LC1 DT60A and DT80A

    LC1 D80004 LP1 D80004 LC1 D115004 LC1 DT203 to DT403with spring terminals

    LC1 D80004 LP1 D80004 LC1 D40AD 65A LC1 D115 and D150 LC1 D115 and D150

    References LAD T9R1V LAD T9R1 LA9 D65A70 LA9 D8070 LA9 D8070 LA9 D11570 LAD 9V9 LA9 D8070 LA9 D8070 LAD 9R3S LA9 D11502 LA9 D11571

    LIN011-EN_FRVersion : 1.0

    DF5

    3772

    9-LI

    N

    DF5

    3773

    0-LI

    N

    DF5

    3773

    1-LI

    N

    DF5

    3773

    4-LI

    N

    DF5

    3773

    5-LI

    N

  • 25/01/2013 39

    Linergy distribution systems Device feeders

    Linergy FTTesys comb busbar

    Fo r 3- p o l e rev ersing co nt act o rs

    LAD 9R1 LAD 9R3 LA9 D8069Kit s fo r assem b l y o f rev ersing co nt act o rs Po w er co nnect io ns Fo r st ar- d el t a st art er

    Composition b A mechanical interlock LAD 9V2 with electrical interlock LAD 9V1

    b A set of power connections LAD 9V5 ( parallel) and LAD 9V6 ( reversing)

    b A mechanical interlock LAD 9V2 without electrical interlock

    b A set of power connections LAD 9V5 ( parallel) and LAD 9V6 ( reversing)

    b A mechanical interlock LAD 4CM

    b A set of power connections LA9 D65A69

    b A set of parallel bars b A set of reverser bars

    b 1 time delay contact block LAD S2 ( LC1 D09D 80) b Power circuit connections ( LC1 D09D 80) b Hardware required for fixing the contactors onto the mounting plate (L&1 D80)

    For contactors LC1 D09 to D38 LC1 D40A to D65A

    LC1 D09 to D38 with screw terminals or connectors

    LC1 D09D 32 with spring terminal connections

    LC1 D40A to D65A

    LC1 D80 and D95 (a)

    LC1 D80 and D95 (c)

    LC1 D115 and D150

    LC1 D09 and D12 LC1 D18 to D32 LC1 D40A and D50A

    LC1 D80 Eq u ip m ent m o u nt ing p l at es

    LC1 D09, D12 and D18

    LC1 D32 LC1 D40A and D50A

    LC1 D80

    References LAD 9R1V LAD 9R1 LAD 9R3 LAD 9V5 + LAD 9V6

    LAD 9V12 + LAD 9V13

    LA9 D65A69 LA9 D8069 LA9 D8069 LA9 D11569 LAD 91217 LAD 93217 LAD 9SD3 LA9 D8017 LA9 D12974 LA9 D32974 - LA9 D80973

    Fo r 4- p o l e ch angeo v er co nt act o r Fo r 3- p o l e ch angeo v er co nt act o r p airs

    LA9 D6570 LA9 D8070Kit s fo r assem b l y o f ch angeo v er co nt act o r p airs

    Set s o f p o w er co nnect io ns Mech anical int erl o ck s Set s o f p o w er co nnect io ns

    Composition b A mechanical interlock LAD 9V2 with electrical interlock LAD 9V1

    b A set of power connections ( changeover) LAD 9V7

    b A mechanical interlock LAD 9V2 without electrical interlock

    b A set of power connections ( changeover) LAD 9V7

    Comprising a set of parallel bars W ithout integral electrical interlock

    W ith integral electrical interlock

    Comprising a set of parallel bars

    For contactors LC1 DT20 to DT40 withscrew terminals or connectors

    LC1 DT60A and DT80A

    LC1 D80004 LP1 D80004 LC1 D115004 LC1 DT203 to DT403with spring terminals

    LC1 D80004 LP1 D80004 LC1 D40AD 65A LC1 D115 and D150 LC1 D115 and D150

    References LAD T9R1V LAD T9R1 LA9 D65A70 LA9 D8070 LA9 D8070 LA9 D11570 LAD 9V9 LA9 D8070 LA9 D8070 LAD 9R3S LA9 D11502 LA9 D11571

    LIN011-EN_FR Version : 1.0

  • 25/01/201340

    Linergy distribution systems Device feeders

    Linergy FTTesys comb busbar

    Co m p o nent s fo r assem b l ing 3- p o l e rev ersing co nt act o rs and ch angeo v er co nt act o r p airs

    3-pole reversing contactors for motor control 3-pole changeover contactor pairsHo rizo nt al m o u nt ing LC1 F115 LC1 F150 LC1 F185 LC1 F225 LC1 F265 LC1 F330 LC1 F400 LC1 F500 LC1 F630

    o r F800Fo r assem b l y o f 3- p o l e rev ersing co nt act o rs fo r m o t o r co nt ro l References

    LA9 FF976 LA9 F15076 LA9 FG976 LA9 F22576 LA9 FH976 LA9 FJ976 LA9 FJ976 LA9 FK976 LA9 FL976

    Fo r assem b l y o f 3- p o l e ch angeo v er co nt act o r p airs References

    LA9 FF982 LA9 F15082 LA9 FG982 LA9 F22582 LA9 FH982 LA9 FJ982 LA9 FJ982 LA9 FK982 LA9 FL982

    Co m p o nent s fo r assem b l ing 3 and 4- p o l e ch angeo v er co nt act o r p airs

    4-pole changeover contactor pairsHo rizo nt al m o u nt ing LC1 F1154 LC1 F1504 LC1 F1854 LC1 F2254 LC1 F2654 LC1 F3304 LC1 F4004 LC1 F5004 LC1 F6304Set o f p o w er co nnect io ns References

    LA9 FF977 LA9 F15077 LA9 FG977 LA9 F22577 LA9 FH977 LA9 FJ977 LA9 FJ977 LA9 FK977 LA9 FL977

    Accesso ries

    LA9 602 LA9 F 601Link s fo r p aral l el co nnect io n o f p o l es (in p airs) Link s fo r s t ar co nnect io n o f 3 p o l esLC1 F1154 LC1 F1504,

    F1854LC1 F2254, F2654, F3304, F4004

    LC1 F5004 LC1 F6304 LC1 F115 LC1 F150, F185

    LC1 F225, F265, F330, F400

    LC1 F500 LC1 F630, F800

    References LA9 FF602 LA9 FG602 LA9 FH602 LA9 FK602 LA9 FL602 LA9 FF601 LA9 FG601 LA9 FH601 LA9 FK601 LA9 FL601

    LIN011-EN_FRVersion : 1.0

    8131

    55-L

    IN81

    3168

    -LIN

    8131

    54-L

    IN

    8130

    87-L

    IN

    8130

    88-L

    IN

  • 25/01/2013 41

    Linergy distribution systems Device feeders

    Linergy FTTesys comb busbar

    Righ t - angl ed co nnect o rs

    LA9 F 981 LA9 F 979Co nt act o rs LC1 F115 LC1 F150, F185 LC1 F225, F265, F330, F400Thermal overload relays LR9 F5 67, LR9 F67 LR9 F5 69, F5 71, LR9 F69, F71 LR9 F7 75,LR9 F75W idth ( mm) 15 20 25Type Rear Side Large

    surface areaRear Side Large

    surface areaRear Side Large

    surface areaReferences LA9 FF981 LA9 FF979 LA9 FF980 LA9 FG981 LA9 FG979 LA9 FG980 LA9 FJ981 LA9 FJ979 LA9 FJ980

    Righ t - angl ed co nnect o rs

    LA9 FL980Co nt act o rs LC1 F500 LC1 F630, F800Thermal overload relays LR9 F7 79, F7 81, LR9 F79, F81 LR9 F7 81, LR9 F81W idth ( mm) 30 40Type Rear Side Large

    surface areaRear Side Large

    surface areaReferences LA9 FK981 LA9 FK979 LA9 FK980 LA9 FL981 LA9 FL979 LA9 FL980

    Accesso riesCo nt act o rs LC1 F115 LC1 F150

    and F 185LC1 F185 LC1 F225 and F265 LC1 F330

    and F400LC1 F400 LC1 F500 LC1 F630,

    F800Thermal overload relays

    LR9 F5 57, F5 63, LR9 F5 67, F5 69, LR9 F69, F71

    LR9 F5 57, F5 63

    LR9 F5 71, LR9 F71

    LR9 F5 71, LR9 F71

    LR9 F7 75, F 79, LR9 F75, F79

    LR9 F7 75, F7 79, LR9 F75, F79

    LR9 F7 81, LR9 F81

    LR9 F7 75, F7 79, LR9 F7 81, LR9 F75, F79, F81

    LR9 F7 81, LR9 F81

    W idth ( mm) 15 20 25 25 25 25 25 30 40References LA7 F401 LA7 F402 LA7 F407 LA7 F403 LA7 F404 LA7 F404 LA7 F404 LA7 F405 LA7 F406

    LIN011-EN_FR Version : 1.0

    8130

    91-L

    IN

    8130

    93-L

    IN

    DF5

    1048

    7-LI

    N

  • 42

  • 25/01/2013 43

    Linergy distribution systems Power busbarsContents

    Linergy BS 44

    5ear flat busbars up to 400 AMulti-stage busbars up to 630 AMulti-stage distribution block up to 630 ACommon accessories up to 630 A

    44454647

    Linergy BW 48

    Insulated busbars up to 630 A 48

    Linergy LGY, LGYE, BS 50

    Selection guide up to 4000 A 50

    Linergy LGY, LGYE, BS 51

    Lateral 51

    Linergy LGY, BS 54

    Rear 54

    Linergy LGYE, BS 56

    Horizontal 56

    Linergy BZ 58

    Quick busbar systems 58

    03_00-Sommaire Version : 1.0

  • 25/01/201344

    Linergy distribution systems Power busbars

    Linergy BSRear flat busbars up to 400 A

    DescriptionThe busbar can be 3-pole or 4-pole with ratings between 160 A and 400 A. 2 lengths are available: 1000 and 1400 mm, which can be cut as required. The number of supports depends on the installation maxi mum rated current.

    160 to 400 A copper busbars

    160 A 250 A 400 ARated peak withstand current (Ipk) 30 k 40 k 55 kRated insulation voltage (U i) 1000 V 1000 V 1000 VRated short-time current (Icw) 10 kA rms/1s 13 kA rms/1s 25 kA rms/1sConductor cross-section 15 x 5 mm 20 x 5 mm 32 x 5 mmInstallation Threaded M 6 holes every 25 mm all the way up

    Connection by: 16 to 50 mm2 flexible cables with crimped lugsSet of 4L ength ( mm) 1000 1400 1000 1400 1000 1400References 04161 04171 04162 04172 04163 04173

    Insulating busbar support ( 1)Distance between supports depending on Icw/Ipk (2)

    10 kA rms/1 s/30 k 450 mm 450 mm 450 mm 13 kA rms/1 s/40 k - 450 mm 450 mm 15 kA rms/1 s/40 k - 450 mm 450 mm 20 kA rms/1 s/45 k - - 300 mm 25 kA rms/1 s/55 k - - 225 mm

    Installation On the rear uprights6crewed onto a solid or pre-slotted plate (fixing centres 450 x 200 mm)

    References 04191 04191 04191

    IPx x B insulating protective sh ieldLength 470 mm 470 mm 470 mmHeight 100 mm 100 mm 100 mmComposition 6upplied with fixingsReferences 04198 04198 04198

    (1) The supports allow installation of a 5th busbar with 15 or 20 x 5 mm cross-section to create the earth collector.(2) Linergy F M 200 A distribution blocks with connections ref. 04029 can act as intermediate supports (max. distance apart 200 mm) in addition to the support

    ref. 04191 at the top and bottom.

    IEC 61439-1 & 2

    LIN040-E N_ F RVersion : 1.0

    PD

    3905

    32-S

    E

    DD

    3813

    88-L

    IND

    D38

    1389

    -LIN

    AC

    _05

    832-

    LIN

  • 25/01/2013 45

    Linergy distribution systems Power busbars

    Linergy BSMulti-stage busbars up to 630 A

    DescriptionM ulti-stage busbars are installed in a sheath L = 300 mm.W e strongly recommend dividing the current between 2 cubicles or enclosures j oined on either side.All the connection points are easily accessible from the front.The busbar orientation makes them easier to tighten and facilitates running the cables between them.The current can be 3-pole or 4-pole with ratings between 160 A and 630 A.2 lengths are available: 1000 and 1400 mm, which can be cut as required.The number of supports depends on the installation maxi mum rated current.

    160 to 630 A copper busbars

    160 A 250 A 400 A 630 ARated peak withstand current (Ipk) 30 k 40 k 55 k 55 kRated insulation voltage (U i) 750 V 750 V 750 V 750 VRated short-time current (Icw) 10 kA rms/1s 13 kA rms/1s 15, 20 kA rms/1s 25 kA rms/1sSupply at incoming terminals Connection by: 16 to 50 mm2 flexible cables with crimped lugsConductor cross-section 15 x 5 mm 20 x 5 mm 32 x 5 mm 32 x 8 mmInstallation F lat copper busbar with threaded M 6 holes every 25 mm all the way upSet of 4L ength ( mm) 1000 1400 1000 1400 1000 1400 1000 1400References 04161 04171 04162 04172 04163 04173 Pending 04174

    Insulating busbar support ( 1)6upport fixing centres in accordance with Icw/Ipk (2)

    10 kA rms/1 s/30 k 450 mm 450 mm 450 mm 450 mm 13 kA rms/1 s/40 k - 450 mm 450 mm 450 mm 15 kA rms/1 s/40 k - 450 mm 450 mm 20 kA rms/1 s/45 k - - 300 mm 300 mm 25 kA rms/0.6 s/55 k - - 300 mm - 25 kA rms/1 s/55 k - - - 300 mm

    Installation Installation on functional uprights in Prisma. 6crewed onto a solid or pre-slotted plate (450 x 200 mm fixing centres)

    References 04192 04192 04192 04192

    IPx x B insulating protective sh ieldLength 250 mm 250 mm 250 mm 250 mmHeight 1500 mm 1500 mm 1500 mm 1500 mmComposition F ixi ng accessories supplied with support ref. 04192References 04197 04197 04197 04197

    IEC 61439-1 & 2

    LIN040-E N_ F R Version : 1.0

    PD

    3905

    33_

    SE

    DD

    3813

    88-L

    IND

    D38

    139

    5-LI

    ND

    D38

    139

    6-LI

    N

  • 25/01/201346

    Linergy distribution systems Power busbars

    Linergy BSMulti-stage distribution block up to 630 A

    M ulti-stage distribution blocks

    160 A 250 A 400 A 630 ARated peak withstand current (Ipk) 30 k 30 k 40 k 40 kRated insulation voltage (U i) 750 V ACRated operational voltage (U e) 440 VRated impulse withstand voltage (U imp) 8 kVRated short-time current (Icw) 10 kA rms/1 s 13 kA rms/1 s 20 kA rms/1 s 25 kA rms/1 sTotal connection capacity 4 incomers per phase: 12.2 mm clearance holes

    13 outgoers per phase 16 to 50 mm2: M 6 tapped holesB usbar cross-section 15 x 5 mm 20 x 5 mm 32 x 5 mm 32 x 8 mmDimensions (mm)

    Installation Screwed in horizontal position on functional uprights in enclosures and cubicles (Prisma G )Screwed in vertical position on sheathed uprights (Prisma G )6crewed onto a solid or pre-slotted plate (fixing centres 450 x 200 mm)Screwed onto adapter ref. 03595 (Prisma P)

    Composition 2 multi-stage supports made of an insulating material4 slanted copper busbars, with holes every 25 mm1 pack of 36 M 6 x 16 screws + contact washers1 IPxxB front insulating shield

    References 04052 04053 04054 04055

    IEC 61439-1 & 2

    DescriptionThe distribution block can be installed horizontally in the device zone or vertically in the 300 mm wide duct of enclosures and cubicles.The distribution block is made up of:

    b two staggered supports made of an insulating material b four slanted copper bars with holes every 25 mm

    LIN040-E N_ F RVersion : 1.0

    PD

    3906

    59R

    DD

    3813

    42-L

    IN

    DD

    3813

    43-L

    IN

    DD

    3813

    44-L

    IN

  • 25/01/2013 47

    Incomer accessories

    Connectors for copper or aluminium cablesRated operational current at 40 (Ie) 160 A 250 A 400 ASupply at incoming terminals 70 mm2 cables 16 to 185 mm2 cables 70 to 300 mm2 cablesComposition 6upplied with fixings at busbar endSet of 4References 07051 07052 07053

    O utgoer accessories

    Class 8.8 fixingsComposition 20 M 6 x 20 screws + 20 nuts

    + 40 contact washers40 M 6 x 16 screws + 40 contact washers

    References 04194 04195

    Linergy distribution systems Power busbars

    Linergy BSCommon accessories up to 630 A

    LIN040-E N_ F R Version : 1.0

    E56

    852

    E56

    851

    E56

    850

    DD

    3813

    98-

    LIN

  • 25/01/201348

    Linergy BWInsulated busbars up to 630 A

    Linergy distribution systems Power busbars

    Description b Compact busbar, IPx x B, ready for installation (supplied complete with supports and end caps) b Shaped busbar, threaded M 6 with 25-mm pitch, can be cut with 200-mm pitch (150 mm for the

    125 A) b B usbar installed on insulating supports, screwed onto the rear uprights b W ide selection of tested pre-wired connectors b Clip-on covers to protect against direct contact (IPxxB ) . Can easily be cut to allow connections

    to pass through to the switchgear b E nds protected by end caps

    L inergy B W busbar125 A 160 A 250 A 400 A 630 A

    Rated peak withstand current (Ipk) 20 k 30 k 30 k 52.5 k 52.5 kRated insulation voltage (U i) 500 V 750 V 750 V 750 V 1000 VRated impulse withstand voltage (U imp) 8 kV 8 kV 8 kV 8 kV 8 kVRated short-time current (Icw) 8.5 kA rms/1 s 10 kA rms/1 s 13 kA rms/1 s 20 kA rms/1 s 25 kA rms/1 sL ength ( mm) 450 750 1000 1400 1000 1400 1000 1400 1000 1400References 3P 04103 04107 04111 04116 04112 04117 04113 04118 04114 04119

    4P 04104 04108 04121 04126 04122 04127 04123 04128 04124 04129

    S pare parts

    L inergy B W busbar supportsRated operational current at 40 (Ie) 125 A 160 A 250 A 400 A 630 AComposition 2 busbar supports 2 end caps packet of fixing accessoriesReferences - 01210 01210 01210 01211

    IPx x B clip-on coversLength (mm) 200Set of 2References - 01201 01201 01201 01201

    Accessories

    IPx x B tap-off terminals 200 A connections IPx x B insulating covers Class 8.8 fixing accessories

    F or one 6 mm2 cable and one 10 mm2 cable (U i) : 750 V

    F or one 1 to 16 mm2 cable (U i) : 750 V

    Covers which can be clipped on and cut to size are used to isolate the connectors of a connection with cables of cross-section 10 to 25 mm2

    M 6 x 12 + 20 M 6 contact washers

    U sed for connecting

    b All switchgear equipped with enclosed terminals

    b Linergy F M 160/200 A

    b All switchgear equipped with enclosed terminals

    b Linergy F M 63/80/160/200 A

    b Linergy F M 200 A

    Set of 12 12 4 8 20References 04151 04152 04021 04150 04158

    LIN005-E N_ F RVersion : 1.0

    PD

    3903

    37

    PB

    5023

    75

    DD

    3813

    85-L

    IN

    DD

    3834

    72-L

    IN

    DD

    3834

    98-

    LIN

    DD

    3849

    52_

    L13-

    LIN

    DD

    3849

    51_

    L13-

    LIN

  • 25/01/2013 49

    Linergy distribution systems Power busbars

    Linergy BWInsulated busbars up to 630 A

    L inergy B W busbar connections w ith pow er supply unit

    Pow er supply units w ith connections U niversal pow er supply units + pre-w ired connectors

    U niversal pow er supply units + connections to be made (flexible insulated busbars can be used)

    U sed for connecting Compact

    b Horizontal NSX 100/250 with or without Vigi

    b Horizontal INS-INV250

    b Horizontal NSX 400

    b Horizontal INS-INV320/400

    b Horizontal NSX 630

    b Horizontal INS-INV500/630

    b E nclosed NSX 100/250 with toggle switch

    b E nclosed vertical INS-INV250

    b Sheathed NSX 100/250 with or without Vigi

    b Sheathed vertical INS-INV250

    b Sheathed NSX 400/630 with or without Vigi

    b Sheathed INS-INV320/630

    b E nclosed horizontal NSX 100/250 with rotary handle or remote control

    b Vertical F upact INF 100/160, F upact ISF T100/250

    b E nclosed NSX 400/630 with or without Vigi

    b E nclosed INS-INV320/630

    References 04060 04070 04071 04061 + 04062 04061 + 04064 04074 + 04073 04061 04074

    Pre-w ired connectors

    Connections IPx x B 3/ 4P monobloc connection

    IPx x B 3/ 4P monobloc connection

    Connections

    35 mm2 ferrule + 45 angled connector

    45 mm2 ferrule + 45 angled connector

    Quick connection on the busbar equipped with a male ferrule for enclosed terminals. Neutral identified by the colour blue.

    -

    Rated operational current at 40

    (Ie) 125 A 160 A 160 A 160 A 200 A

    Length 230 mm 250 mm 440 mm 150 mm -U sed for connecting b NG 125, INS

    with enclosed terminals ref. 28 947 or 28 948

    b INS160, NG 125, NG 160

    b NG 160 (left-hand position) , Vigi NG 160 (middle position)

    b NG 125, INS160, C120, iC120

    b NG 160 (left-hand position) , NG 125, INS160, C120, iC120

    b Linergy F M 200 A

    Set of 4 4 1 1 4References 04145 04146 04148 04147 04021

    LIN005-E N_ F R Version : 1.0

    DD

    3805

    22-L

    IN

    DD

    3805

    93-

    LIN

    DD

    3813

    79-L

    IN

    DD

    3832

    76-L

    IN

    DD

    3832

    74-L

    IN

    DD

    3834

    72-L

    IN

    DD

    3832

    94-

    LIN

    DD

    3832

    95-

    LIN

  • 25/01/201350

    Linergy distribution systems Power busbars

    Linergy LGY, LGYE, BSSelection guide up to 4000 A

    Descrip t io nPrisma P and SFP/PH switchboards have a complete, coherent system for routing the electrical current:

    b optimised busbars b pre-wired connectors b customised distribution blocks

    I EC 61439- 1 & 2

    Ho rizo nt al b u sb ar

    /*

  • 25/01/2013 51

    Linergy distribution systems Power busbars

    Linergy LGYLateral profiles up to 3200 A

    /LQHUJ\/* 31 590 A 760 A 950 A 1170 A 1480 A 1820 A 2260 A 2920 A

    Number of profiles per phase 1 2References 04502 04503 04504 04505 04506 04504 04505 04506

    Bu sb ar su p p o rt s

    700 mmmax.

    700 mmmax.

    387.5 mmmax.

    Characteristics An end stop must be fitted on the bottom support 01109 ( sold in lots of 12)

    Number depending on Icw ( kA rms/1 s)

    25 3 2 x 3 30 - 3 2 x 3 40 - 3 2 x 3 50 - 4 2 x 3 60 - 5 2 x 4 65 - 5 2 x 4 75 - 7 2 x 5 85 - 8 2 x 5

    References ( + set of 2 upright adaptersNSYSFPA for installation in SFP/PH cubicle)

    Eq u ip o t ent ial b o nd ing3 eq uipotential bonding items must be installed between the busbars

    -

    Connection made with a flat 80 x 10 mm busbar between 2 L150 sheaths

    Co nnect io ns t o t h e Linergy BS h o rizo nt al b u sb ar

    Characteristics Fixings supplied. O rder 1 connection per phaseReferences acco rd ing t o h o rizo nt al b u sb ar size

    5 mm thick ( 1000 A) 04635 ( 1600 A) -10 mm thick Width 80 mm 2 x 04636

    W idth > 80 mm + 04642 2 x + 2 x04642

    Accesso ries

    Linergy screw Plain washer IdentificationLinergy screw Characteristics Sold in lots of 20: 20 screws + 20 nuts + 20 contact washers, class 8.8.

    7he screws slide into the profile and are then locked in the desired position.References 25 mm long (for lug and flexible busbar connection)

    39 mm long 04767 ( for copper busbar connection)Steel plain washers

    Characteristics M8 sold in lots of 20References ext. 20 mm

    ext. 24 mm 04773ext. 28 mm

    B rass plain washers

    Characteristics 08 sold in lots of 20 for connection of 25 mm2 lugs to LinergyReferences ext. 20 mm 04775

    Identification Characteristics 12 clip-on supports + N, L1, L2, L3, PE, PEN labelsReferences

    LIN039-EN_FR Version : 1.0

    DD

    3812

    33-L

    IN

    DD

    3812

    34-L

    IN

    DD

    3812

    35-L

    IN

    DD

    3812

    36-L

    IN

    DD

    3812

    37-L

    IN

    DD

    3812

    35-L

    IN

    DD

    3812

    36-L

    IN

    DD

    3812

    37-L

    IN

    DD

    3815

    09N

    ew_m

    odif-

    LIN

    DD

    3807

    41-L

    IN

    DD

    3807

    41-L

    IN

    DD

    3807

    41-L

    IN

    DD

    3807

    42-L

    IN

    DD

    3823

    27R

    DD

    3825

    76-L

    IN

    8C-D

    D38

    1240

    -ret

    -LIN

    DD

    3812

    18-L

    IN

    DD

    3812

    19-L

    IN

    DD

    3812

    22-L

    IN

  • 25/01/201352

    Linergy distribution systems Power busbars

    Linergy LGYELateral profiles up to 4000 A

    /LQHUJ\/* 31 630 A 800 A 1000 A 1250 A 1650 A 2000 A 2440 A 3200 A 3350

    Length to cut for side mounting 1675 mm 1625 mmNumber of profiles per phase 1References 04560 04561 04562 04563 04564 04565 04566 04567 04568

    Bu sb ar su p p o rt s

    Fixed support 04661 Support arm 04662 04666Characteristics 3 fixed supports are compulsory to hold the busbar in position.

    If more than 3 supports are needed, use support arms ( in addition) .Number depending on Icw ( kA rms/1 s)

    30 3 40 - 5 3 50 - 5 3 60 - 5 3 65 - 5 75 - 7 5 85 - 7 100 - 9

    References 04661 (fixed support) + 04662 ( support arm if necessary)

    04661 (fixed support) + 04671 (fixings) + 04662 ( support arm if necessary)

    04661 (fixed support) + 04646 ( sold in lots of 12 spacers) + 04662 ( support arm if necessary)

    Wed ging b u sb ars in p o sit io n

    Wedge fitted on bottom support Wedge fitted on bottom supportCharacteristics 7he bottom support is used to place profiles and ensure they are in the correct position.

    It is not considered to be a busbar support.References 04663 ( bottom support) 04666 ( bottom support) +04661 (fixed support)

    04658 ( pack of 12 replacement shims) 04659 ( pack of 12 replacement shims)

    Co nnect io ns t o t h e Linergy Ev o l u t io n LGYE h o rizo nt al b u sb ar

    1600 A 2000/2500 A 3200/4000 ACharacteristics Supplied with fixings.

    References are supplied individually: 1 connection per phase.References acco rd ing t o h o rizo nt al b u sb ar size04604 ( short connection)

    04605 ( long connection)04607

    LIN039-EN_FRVersion : 1.0

    DD

    3845

    36_L

    IN

    DD

    3812

    26-L

    IN

    DD

    3845

    38-L

    IN

    DD

    3845

    39-L

    IN

    DD

    3845

    40-L

    IN

    DD

    3845

    41-L

    IN

    DD

    3845

    42-L

    IN

    DD

    3845

    43-L

    IN

    DD

    3845

    44-L

    IN

    DD

    3846

    07-L

    IN

    DD

    3808

    29-L

    IN

    DD

    3816

    50-L

    IN

    DD

    3831

    94-L

    IN

    DD

    3845

    77-L

    IN

    DD

    3845

    76-L

    IN

    DD

    3845

    75-4

    vis-

    LIN

    DD

    3845

    75-L

    IN

  • 25/01/2013 53

    Linergy distribution systemsPower busbars

    Linergy BSLateral flat busbars up to 3200 A

    Fl at b u sb arsU p t o 1600 A U p t o 3200 A

    I n Prism a P sh eat h L150 L150 L300 2 x L150I n SFP/ PH sh eat h L300 D500/ 600/ 800 L300 D500/ 600/ 800 -Pre-slotted copper,1675 mm long

    12.5

    12.5

    12.5

    Permissible current for an ambient temp. of 35 C around the switchboard

    IP 31 800 A 1000 A 1400 A 1800 A 1200 A 1400 A 1800 A 2050 A 2300 A 2820 A 3200 A 3200 AIP > 31 750 A 900 A 1250 A 1600 A 1080 A 1250 A 1600 A 1850 A 2000 A 2500 A 2820 A 2820 A

    B usbar cross-section ( mm) 60 x 5 80 x 5 60 x 5 80 x 5 50 x 10 60 x 10 80 x 10 50 x 10 60 x 10 80 x 10 100 x 10 80 x 10Number of busbars per phase 1 2 1 2References 04516 04518 04516 04518 04525 04526 04528 04525 04526 04528 pending 04528

    Bu sb ar su p p o rt s

    IL[HGIL[HGVKLPDUPDUP

    PPPD[PPPD[PPPD[PPPD[PPPD[PPPD[IL[HG Description Attach directly to the sheath frame. 3 fi xed supports are compulsory to hold the busbar in position. If more than 3 supports are needed, use support arms ( in addition) .The bottom wedge support is used to place the busbar and ensure it is in the correct position. It does not count as a busbar support.

    Number of supportsdepending on Icw ( kA rms/1 s)

    15 3 3 2 x 3 25 5 3 3 2 x 3 30 5 5 3 2 x 3 40 7 5 5 2 x 3 50 7 5 2 x 3 60 7 5 2 x 5 65 7 5 2 x 5 75 9 7 2 x 5 85 7 2 x 5

    References o f su p p o rt s d ep end ing o n d ist ance b et w een b ars and sh eat h d ep t h

    Prisma P sheath 75 mm distance between bars

    L150 mm 04661 (fi xed) 04662 ( arm) + 04663( shim)L300 mm 04661 (fi xed) 04662 ( arm) + 04666+ 04661 ( shim) ( 1)

    SFP sheath L30075 mm distance between bars

    D500 mm NSYBV500 (fi xed) 04662 ( arm) + NSYAS500( shim) ( 1)

    D600 mm NSYBV600 (fi xed) 04662 ( arm) + NSYAS600( shim) ( 1)

    D800 mm NSYBV800 (fi xed) 04662 ( arm) + NSYAS800( shim) ( 1)

    SFP sheath L300115 mm distance between bars

    D800 mm NSYBV800L (fi xed) 04678 ( arm) + NSYAS800L( shim) ( 1)

    ( 1) If using a 100 x 10 bars, add a pack of screws ref. 04671 for each fi xed support 04661 and arm support 04662.

    Co nnect io ns t o t h e Linergy BS h o rizo nt al b u sb ar

    Characteristics For a busbar with 75 mm distance between bars, the bars must be completely covered.Staggered assembly points between one bar and the next, to maintain the necessary clearance distances.( 2)

    References 04636, 04637 are supplied individually: 1 connection per phase.Reference 04642 consists of 2 M8 x 140 screws which can replace the original M8 x 120 screws.

    1 bar per phase 2 bars per phase double busbar

    50 x 10 60 x 10 80 x 10 50 x 10 60 x 10 80 x 10 100 x 10 80 x 10Reference o f t h e co nnect io n p iece d ep end ing o n h o rizo nt al b u sb ar size

    80 mm Pending 04636 04637 04637 04638 04636 x 2> 80 mm Pending 04636 + 04642 04637

    + 04642

    04637 + 04642 04638 ( 04636+ 04642 ) x 2

    ( 2) Drill hole dimensions for 5 mm thick horizontal busbars

    12.5

    12.5

    LIN039-EN_FR Version : 1.0

    DD

    3833

    98-L

    IN

    DD

    3815

    05-L

    IN

    DD

    3807

    24A

    -LIN

    10B

    -DD

    3838

    44-r

    et-L

    IN

    11B

    -DD

    3814

    99-r

    et-L

    IN

    DD

    3833

    99_m

    odif-

    LIN

  • 25/01/201354

    Linergy distribution systems Power busbars

    Linergy LGYRear profiles up to 1600 A

    /LQHUJ\/* 31 590 A 760 A 950 A 1170 A 1480 A

    Number of profiles per phase 1References 04502 04503 04504 04505 04506

    Bu sb ar su p p o rt s

    350 mmmax.

    350 mmmax.

    350 mmmax.

    350 mmmax.

    387.5 mmmax.

    Number depending on Icw ( kA rms/1 s)

    25 3 30 4 40 5 50 7

    Characteristics An end stop must be fitted on the bottom support 01109 ( sold in lots of 12)

    References 04652

    &RQQHFWLRQVWRWKH/LQHUJ\%6KRUL]RQWDODWEXVEDU

    04635 connection to 5 mm thick horizontal busbar

    04036 connection to 10 mm thick horizontal busbar

    Characteristics Fixings supplied, order 1 connection per phase.For part of the connection, flexible insulated busbars are needed.

    References acco rd ing t o h o rizo nt al b u sb ar size

    5 mm thick 0463510 mm thick

    Width 80 mm 04636W idth > 80 mm 04636 + 04642

    Accesso ries

    Screw + nut + contact washer Plain washer IdentificationLinergy screw Characteristics Sold in lots of 20: 20 screws + 20 nuts + 20 contact washers, class 8.8

    7he screws slide into the profile and are then locked in the desired positionReference 25 mm wide 04766 (for lug and flexible busbar connection)

    39 mm wide 04767 ( for copper busbar connection)Steel plain washers

    Characteristics M8 sold in lots of 20Reference ext. 20 mm 04772

    ext. 24 mm 04773ext. 28 mm 04774

    B rass plain washers

    Characteristics 08 sold in lots of 20 for connection of 25 mm2 lugs to LinergyReference ext. 20 mm 04775

    Identification Characteristics 12 clip-on supports + N, L1, L2, L3, PE, PEN labelsReference 04794

    LIN039-EN_FRVersion : 1.0

    DD

    3812

    33-L

    IN

    DD

    3812

    34-L

    IN

    DD

    3812

    35-L

    IN

    DD

    3812

    36-L

    IN

    DD

    3812

    37-L

    IN

    DD

    3812

    42-L

    IND

    D38

    1243

    -LIN

    DD

    3812

    41N

    ew_m

    odif-

    LIN

    DD

    3812

    44-L

    IN

    9C-D

    D38

    1245

    -ret

    -LIN

    DD

    3812

    18-L

    IN

    DD

    3812

    19-L

    IN

    DD

    3812

    22-L

    IN

  • 25/01/2013 55

    Linergy distribution systemsPower busbars

    Linergy BSRear flat busbars up to 1600 A

    Fl at b u sb arsU p t o 1600 A

    At t h e b ack o f a Prism a P cu b icl e L650At t h e b ack o f a SFP/ PH cu b icl e L700 - L700Pre-slotted copper,1670 mm long

    12.5

    12.5

    12.5

    800 A 1000 A 1400 A 1800 A 1000 A 1200 A 1600 APermissible current for an ambient temperature of 35 C around the switchboard

    IP 31 800 A 1000 A 1400 A 1800 A - - -IP > 31 750 A 900 A 1250 A 1600 A 1080 A 1250 A 1600 A

    B usbar cross-section ( mm) 60 x 5Number of busbars per phase 1 2 1References 04516 04518 04516 04518 04525 04526 04528

    Bu sb ar su p p o rt s

    Fixed busbar support 04653 B usbar support arm 04662

    OOOCZ

    OOOCZ

    OOOCZ

    OOOCZ

    OOOCZ

    OOOCZ

    Characteristics 3 fi xed supports ref. 04653 are compulsory to keep the busbar vertical. If more than 3 supports are needed, use support arms ref. 04662 ( in addition) .Metal shim ref. 04669 ( sold in lots of 100) , 5 mm thick, is screwed onto the busbar.It rests on a fi xed support and is used to wedge the busbar in position.

    W edging: 1 busbar/phase

    W edging: 2 busbars/phaseNumber depending on Icw ( kA rms/1 s)

    15 3 3 25 5 3 3 30 5 5 40 7 5 5 50 7 5 60 7 65 7 75 9 85

    References 04653 (fi xed) 04662 ( arm) + 04669( shim)

    &RQQHFWLRQVWRWKH/LQHUJ\%6KRUL]RQWDODWEXVEDU

    04635 connection to horizontal busbar5 mm thick

    04636 connection to horizontal busbar10 mm thick

    Characteristics For part of the connection, fl exible insulated busbars are need