8
TM ® Liebert GXT4 , 5kVA - 10kVA Intelligent, Reliable UPS Protection

Liebert GXT4TM, 5kVA - 10kVA · UPS systems which provide clean power ideal for business critical applications wherein battery backup power is needed to protect network closets or

  • Upload
    others

  • View
    11

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Liebert GXT4TM, 5kVA - 10kVA · UPS systems which provide clean power ideal for business critical applications wherein battery backup power is needed to protect network closets or

TM®Liebert GXT4 , 5kVA - 10kVAIntelligent, Reliable UPS Protection

Page 2: Liebert GXT4TM, 5kVA - 10kVA · UPS systems which provide clean power ideal for business critical applications wherein battery backup power is needed to protect network closets or

Emerson Network Power, a business of Emerson, a global company that leads by applying a unique combination of industry expertise, technology, and resources to make the future of our customers' enterprises and networks possible.

Emerson Network Power's broad technology base and global expertise support a full spectrum of enterprise wide solution for today's business needs . We have been providing tailored solutions for protecting the operation of critical electronic systems in virtually every business segment right from customer premise equipment to global network .

Supported by our right combination of knowledge, experience, product selection and service capability.We are the true solution provider of our customer�s IT infrastructure, right from grid to chip level.

When the stakes are high, partner with Emerson Network Power to optimize your technology with �high-nines� reliability solutions specific to your infrastructure.

Emerson.Consider It Solved.

Customers call on Emerson whenthe stakes are the highest. Why?Because they know that we bringthem technology and engineeringto create solutions for their success.Whatever their challenge, they know that with Emerson by their side, they can �Consider It Solved.�

.

We are Emerson

Page 3: Liebert GXT4TM, 5kVA - 10kVA · UPS systems which provide clean power ideal for business critical applications wherein battery backup power is needed to protect network closets or

Today�s converged networks require increased availability and reliability. IT professionals require higher density power protection systems that adapt to mixed load voltages and plug types, while remaining easy to install and maintain.

The Liebert GXT4, a true on-line double conversion ®

UPS system is available in larger capacity models of 5kVA - 10kVA, and features integrated maintenance bypass, as well as optional extended battery runtime. Plus, Liebert Services and protects your UPS. The Liebert GXT4 UPS is designed for use in either rack or tower con�gurations.

As global leader, 220V, 230V and 240V 50/60 Hz models are offered with CE and C-tick markings.

Best Protection for Critical Network Applications

Ef�cient, CompactDesign

Flexible Con�gurationsand Design

Intuitive, IntelligentOperation

Designed Easy Serviceand Warranty

Flexible Monitoring &Management Options

Optimized Operational ExpensesHigh ef�ciency up to 97%ENERGY STAR Certi�ed

Multiple Battery and distribution options

Intuitive color LCD Interface Multiple con�guration options.standard web cards.

Hot -swappable Battery con�guration Liebert Service provides ultimate peace of mind

Monitoring and Shutdown software add �exibility to each installation

The Liebert Solution The Liebert GXT4 UPS meets the need for higher power ®

capacities in small spaces.

The Protection You Need from Damaging power problems

Always Protected !

Pure Sine-Wave

Outages Sags Surges Spikes Noise

Transient FrequencyDeviation

Under-Voltage

Over-Voltage

Harmonics

On line, Double Conversion UPS For Best in Protection

DynamicBypass

UtilitySurge

Suppression

Power FactorCorrection/Recti�er

ChargerInverter Load

Battery

Page 4: Liebert GXT4TM, 5kVA - 10kVA · UPS systems which provide clean power ideal for business critical applications wherein battery backup power is needed to protect network closets or

Energy Ef�cient Design

Liebert GXT4 UPS offers a variety of communication options to provide the monitoring and control capabilities demanded by today�s network computing systems.

Libert IntelliSlot Web Vard provides SNMP ®

(including SNMPv3) and IPv.6 and web-based management of your UPS

Built-in USB communications for use TMwithLibert Multilink Automated System

Shutdown Software

TMLiebert Nform Monitoring Software

Libert Universal Monitor And Remote Power Monitor Panels

Libert SiteScan®

TMTrellis Platform

Third-Party Monitoring Systems

Built-in contact closure signals. Provides dry contact communications to remotely monitor UPS operating modes.

Operation can be monitored using:

Liebert IntelliSlot Webcard provides SNMP and web-based management

Active ECO mode keeps the recti�er and inverter operating, allowing the inverter to remainsynchronized to bypass.

This synchronization allows the transfer of the connected equipment to UPSinverter power almost seamlessly if bypass power falls outside the user-set limits.

Once bypass powerreturns within the acceptable parameters, the UPS will return to Active ECO Mode operation

Active ECO mode provides best in class ef�ciency up to 97% without compromise

ENERGY STAR certi�ed UPS modelsUPS products meeting the EPA�s requirements use an average of 35% less energy than their standards counterparts.

Flexible Con�guration Flexible Monitoring & Management Options

Wider input voltage window Features a wide input voltage window that allows the UPS to support the critical load without having to transfer to battery, extending battery life for when it is truly needed

Rack/tower con�guration The versatile unit installs in either con�guration, and includes a rotating color LCD display.

Replaceable hot-swappable internalbatteries Provide 4-9 minutes of runtime at full load depending on the model.

Additional runtime with additionalbattery cabinets Up to 6 external battery cabinets. UPS cabinet includes rear panel plug-and-play connections for optional battery cabinets. 5kVA and 6kVA: 3U, 10kVA: 4U

Internal automatic and manualbypass Assures continuity of power tocritical loads during system maintenanceor in case of internal fault.

Automatic frequency detectionDetects and matches line input frequencies of either 60 or 50 Hz and can also be programmed to convert from one to the other.

Self-diagnostics. Automatically tests unit electronics and batteries. Designed to simplify maintenance and troubleshooting.

Arrays of accessories bundled with standard model ( such as Rail kit , IS-webcard etc. ), helps to save capital expense .

DynamicBypass

UtilitySurge

Suppression LoadPower Factor

Correction/Recti�erCharger

Inverter

Battery

Page 5: Liebert GXT4TM, 5kVA - 10kVA · UPS systems which provide clean power ideal for business critical applications wherein battery backup power is needed to protect network closets or

The Liebert GXT4 true on-line, high power density UPS systems which provide clean power ideal for business critical applications wherein battery backup power is needed to protect network closets or small data centers against costly downtimes.

For installation �exibility, the Liebert GXT4 UPS 5 and 6kVA models allow you to choose from several different wiring con�gurations made possible by the use of removable power distribution boxes (PODs) that simply plug into the rear of the UPS. The standards box provides terminal blocks for hardwired input and output connections. An optional hardwire version that includes a maintenance bypass is also availble

Adaptable Design

5 and 6kVA Models Offer True On-Line Power In A Convenient Rack Con�guration

10kVA Model Provide Even More Power

® TMThe Liebert GXT4 10kVA units offer a �exible solution for protecting rack-mount equipment, including VoIP and PoE

Speci�cally designed for use with the new generation of high power switches, these compact UPS systems pack 10kVA (9kW) of power into a 6U rack/tower package with �exible output voltage and optional power output distribution. The UPS includes built-in user replaceable batteries that can deliver up to 4 minutes at full load runtime and optional external battery cabinets to provide maximum �exibility in adding battery runtimes.

The UPS has output power factor 0.9. That is, 10kVA model provides9kW output power. The unit features integrated internal manualand automatic maintenance bypass and auto detection of extended battery cabinets.

The standard 10kVA model includes terminal blocks for hardwired connections of both input and output. The bundled power distribution module provides 4x IEC-C19 receptacles for bladeservers or high-end networking switches and 4 x IEC C13 receptacles.

Adaptable Design

Liebert GXT4 UPS 10kVA units feature three bays for one power modules and two battery modules. The chassis contains a bypass switch that allows all modules to be removed without powering down the connected load.

Hot - Swappable OperationPOD con�guration with UPS

POWERSOURCE POD

LOADEQUIPMENT

UPS

Removable Maintenance Bypass and Power Distribution Box

10 kVA Models

For 5/6 kVA For 10 kVA

Page 6: Liebert GXT4TM, 5kVA - 10kVA · UPS systems which provide clean power ideal for business critical applications wherein battery backup power is needed to protect network closets or

While today�s smaller, rack-based UPS system offer relatively trouble-free operation, the growing criticality of the systems they support has increased the cost of downtime. As a result, the need to maintain these smaller UPS systems is increasingly important.

Extended WarrantyChoose additional of 1-yr or 3-yr warranty on top of the 2-yr standard warranty for worry-free maintenance and total peace of mind.

Start-upOn-site system startup by a certi�ed Emerson Network Power Customer Engineer to assure con�dence that the equipment is up and running at optimum performance

Preventive maintenanceone or two times visits per year by an Emerson Network Power Customer Engineer for higher reliability and availability

On-site serviceShould you experience a problem, we will dispatch a certi�ed Emerson Network Power Customer Engineer to repair or replace, your equipment. Response guaranteed.

LiebertInstelliSlot Port

Terminal Block Communication

REPO

USB Port

C19 Output PowerReceptacles

External BatteryConnector

IT Power system Access Cover

Input CircuitBreaker

Knockoutsfor Hard-wiredPower Input

Output Circuit Breakers

MaintenanceBypass Breker

Output CircuitBreaker

C13 Output Receptacles

D89 Ports (Parallel Communication)

USB Port

C19 Output Receptacles

Output Circuit Breakers

External BatteryConnectorLiebert IntelliSlotPort

Terminal BlockCommunication

MaintenanceBypass Breaker

Output CircuitBreaker

C13 OutputReceptacles

Input CircuitBreaker

Output Circuit Breaker

Knockoutsfor Hard-wiredPower Input IT Power System

Access Cover

Rear View 5-6kVA Rear View 10kVA

Our Extended Service packagesoffer you complete peace of mind

BatteryIndicator

InverterIndicator

FaultIndicator

LCD Panel

ESC Button

BypassIndicator

ECO mode indicator

ENTER button

UP button Down button

Intuitive and intelligent Operation

GXT4-UPS 5kVA

O/P : 230V 50Hz 21.7A I/P : 230V 50Hz 17.3ABATT :100% 9MINSLOAD: 0%

Page 7: Liebert GXT4TM, 5kVA - 10kVA · UPS systems which provide clean power ideal for business critical applications wherein battery backup power is needed to protect network closets or

Battery Run-time Chart

Model Number

Used with UPS Model GXT4-5000RT230; GXT4-6000RT230; GXT4-10000RT230Dimensions, W x D x H, mm(in)Unit (with bezel) 430 x 581 x 173 (16.9 x 22.9 x 6.8)Weight, kg (lb)Unit 65 (143.3)Battery ParametersType Valve-regulated, non-spillable, lead acidQuantity x V 1 x 20 x 12V

Operating Temp, °C (°F) 0 to 40 (32 to 104)Storage Temp, °C (°F)Relative HumidityOperating Elevation

-15 to 50 (5 to 122)0-95% non-condensingUp to 1000m (3280.83 ft.) at 25°C (77°F)

AgencySafety IEC62040-1:2008 versionTransportation ISTA Procedure 1E

Load (%)

Internal Battery

10

20

30

40

50

60

70

80

90

100

105

52

40

27

21

17

14

12

10

9

97

47

33

22

17

14

11

9

8

6

98

42

25

17

12

9

7

6

5

4

5kVA 6kVA 10kVA

Load (%)

10

20

30

40

50

60

70

80

90

100

211

140

102

76

53

48

43

38

32

27

194

122

83

62

48

42

35

28

25

22

165

99

53

42

31

25

20

17

14

12

5kVA 6kVA 10kVA Load (%)

10

20

30

40

50

60

70

80

90

100

427

220

154

130

105

91

74

64

51

48

341

185

140

108

91

72

53

49

45

41

311

144

99

68

49

42

35

28

25

21

5kVA 6kVA 10kVA Load (%) 5kVA 6kVA 10kVA

Load (%) 5kVA 6kVA 10kVA Load (%) 5kVA 6kVA 10kVA Load (%) 5kVA 6kVA 10kVA

Environmental

GXT4-240VBATT

Internal Battery +1 External Battery Cabinet Internal Battery +2 External Battery Cabinet Internal Battery +3 External Battery Cabinet

10

20

30

40

50

60

70

80

90

100

441

326

204

160

143

126

107

97

81

73

429

303

167

146

126

105

92

76

66

53

344

166

133

99

74

53

48

42

42

31

Internal Battery +4 External Battery Cabinet Internal Battery +5 External Battery Cabinet Internal Battery +6 External Battery Cabinet

10

20

30

40

50

60

70

80

90

100

480

428

312

209

164

151

138

124

108

100

463

338

227

166

150

134

113

103

92

78

436

213

153

127

99

77

64

51

47

42

10

20

30

40

50

60

70

80

90

100

480

436

339

304

203

166

155

145

134

123

464

422

318

208

165

153

140

127

110

101

449

312

166

144

123

100

80

69

53

49

10

20

30

40

50

60

70

80

90

100

480

457

428

327

285

207

167

158

149

140

480

445

339

304

206

165

154

143

133

122

459

330

202

157

138

120

100

81

72

63

* Battery run time measured in minutes

External Battery Speci�cation

Page 8: Liebert GXT4TM, 5kVA - 10kVA · UPS systems which provide clean power ideal for business critical applications wherein battery backup power is needed to protect network closets or

ACP-GXT4-1-1-15-1

Emerson Network Power Asia Pacific

AustraliaT: 1800-065345F: 61-2-97438737

IndonesiaT: 62-21-2513003F: 62-21-2510622

JapanT: 81-3-54038594F: 81-3-54032924

KoreaT: 82-2-34831500F: 82-2-5927883

MalaysiaT: 603-78845000F: 603-78845188

New ZealandT: 64-3-3392060F: 64-3-3392063

PakistanT: 92-42-36622526 to 28F: 92-42-36622530

PhilippinesT: 63-2-7207400F: 63-2-6203693

SingaporeT: 65-64672211F: 65-64670130

ThailandT: 66-2-6178260F: 66-2-6178277 to 78

VietnamT: 84-4-37628908F: 84-4-37628909

IndiaT: 91-22-33154400F: 91-22-25828358

ChinaT: 86-755-86010808F: 86-755-86010909

Emerson Among Top 50 On Fortune Survey Of “Worlds Most Admired” Companies

Scan to learn more about Liebert GXT4 or go to www.emersonnetworkpower.com

® �

While every precaution has been taken to ensure accuracy and completeness in this brochure. Emerson Network Power assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.

Subscribe to EmersonConnect with us on:

Liebert GXT4 Technical Speci�cations - 5, 6 and 10 kVA models

User-Con�gurable

Storage Temp

Operating Elevation

Audible Nosie

Operating Temp

Waveform

Output AC

Environment Parameters

Rating

GXT4-5000RT230

Nominal Operating Frequency

Frequency

GXT4-6000RT230 GXT4-10000RT230Parameters

Input AC

50 or 60Hz (Factory Default is 50Hz)

200/208/220/230/240VAC

50HZ or 60Hz, Nominal

Sinewave

Recharge Time

Battery

Type

Qty x V x Rating

Valve-regulated, nonspillable, lead acid

20 x 12V

3 hours to 90% capacity after full discharge into 100% load

5000VA/4000W 6000VA/4800W 10000VA/9000W

0°C to +40°C (+32°F to 104°F)

-15°C to +50°C (5°F to 122°F)

Up to 1000m (3281 ft.) at 25°C (77°F) without derating

Operating Voltage Range 176 - 280VAC

Input Frequency Opertion 40-70Hz

Less than 55 dBA at 1 meter from the rear <50 dBA,at 1 meter from the front or sides

0% to 95%, non-condensingRelative Humidity

Safety

Agency

ESD

EMI/EMC/C-Tick EMC

IEC62040-1:2008 version, GS mark

IEC 62040-2 2nd Ed

IEC/EN EN61000-4-2, Level 4, Criteria A

Electrical Fast Transient

Radiated Susceptibility IEC/EN EN61000-4-2, Level 3, Criteria A

Weight(lb)(kg)

Dimension (H x W x D)(in)

Mechanical Parameters

430 x 574 x 217 (16.9 x 22.4 x 8.5)

132.2 (60)

Main Mode Overload >200% for 5 cycles; 151-200% for 1 seconds; 121-150% 10seconds;105-130% 1 minute

Transportation

Surge Immunity

IEC/EN EN61000-4-2, Level 2, Criteria A

IEC/EN EN61000-4-2, Level 1, Criteria A

ISTA Procedure 1E

430 x 581 x 261 (16.9 x 22.9 x 10.3)

154.3 (70)

Power distribution speci�cations

Input Power Connection

Output Power ConnectionIncludes(Manual Bypass Switch With Indicator Lamps)

Amp Rating 32 Amps2Single-phase (L-N-G) hardwire, 6-10mm (8-10AWG)2Single-phase (L-N-G) hardwire, 6-10mm (8-10AWG)

Two IEC 320 C19 16A/250V SocketsSix C13 10A/250V Sockets

32AInput Branch Circuit Breaker Supplied by User

Model Number PD2-CE6HDWRRMBS PD2-CE10HDWRMBS

Four IEC 320 C19 16A/250V SocketsFour C13 10A/250V Sockets

63A

VAC(Factory Default ) 230VAC

63A