Heat pump 50Hz/R410A0CIM0-02E (Replaces 0CIM0-02D)
Part 1 General information
Part 2 Product data
Part 3 Design and installation
Part 4 Special Part
50Hz/R410A
Introduction PrefaceNew era brings the more sophisticated and advanced buildings which in turn demands for specialized and optimized directexpansion air conditioning systems. Also energy efficiency, environment friendly, low noise and low maintenance are thefeatures which are essential for these systems.
As a part of vertical integration LG makes all the key components in house, which gives us an edge to LG to make betterand latest technology products with best quality in optimized time.
and systems are equipped with inverter technology and R410A refrigerant which is perfect solutionto various installation locations.
This Engineering product data book incorporates information about the product itself, and installation, designing for and system.
The comprehensive study of this book will improve your knowledge about the system and its application in detail.
LG Electronics Inc.Air Conditioning & Energy Solution Company
Part 1 General information1. Model line up2. Nomenclature3. Appearance4. Combination
1. Model line up
Heat pump 50Hz/R410A _ 1
Part 1 General inform
ation
1.1 Outdoor units(1 phase)
Nominal Capacity(kW) 4.1 4.7Model Name A2UW14GFA0[MU2M15 UL2]
A2UW16GFA0[MU2M17 UL2]
No.of connectable indoor units Max.2Total capacity index of connectable indoor units kBtu/h 21 24
Power supply 220-240V, 1, 50Hz
Chassis
Nominal Capacity(kW) 5.3 6.2Model Name A3UW18GFA0[MU3M19 UE2]
A3UW21GFA0[MU3M21 UE2]
No.of connectable indoor units Max.3Total capacity index of connectable indoor units kBtu/h 30 33
Power supply 220-240V, 1, 50Hz
Chassis
Nominal Capacity(kW) 7.0 7.9 8.8Model Name A4UW24GFA0[MU4M25 U42]
A4UW27GFA0[MU4M27 U42]
A5UW30GFA0[MU5M30 U42]
No.of connectable indoor units Max.4 Max.5Total capacity index of con-nectable indoor units kBtu/h 39 41 48Power supply 220-240V, 1, 50Hz
Chassis
1. Model line up
2 _ Heat pump 50Hz/R410A
Part
1 G
ener
al in
form
atio
n (1 phase)
(1 phase)
Nominal Capacity(kW) 13.5 14.1 16.7Model Name A7UW42LFA0[FM41AH U32]
A8UW48LFA0[FM49AH U32]
A9UW56LFA0[FM57AH U32]
No.of connectable indoor units Max.7 Max.8 Max.9Total capacity index of con-nectable indoor units kBtu/h 54 63 73Power supply 380-415V, 3, 50Hz
Chassis
Nominal Capacity(kW) 11.7 14.1 16.7Model Name A7UW40GFA0[FM40AH UO2]
A8UW48GFA0[FM48AH U32]
A9UW56GFA0[FM56AH U32]
No.of connectable indoor units Max.7 Max.8 Max.9Total capacity index of con-nectable indoor units kBtu/h 52 63 73Power supply 220-240V, 1, 50Hz
Chassis
(3 phase)
Nominal Capacity(kW) 11.7Model Name A5UW40GFA0[MU5M40 UO2]No.of connectable indoor units Max.5Total capacity index of connectable indoor units kBtu/h 52Power supply 220-240V, 1, 50Hz
Chassis
Heat pump 50Hz/R410A _ 3
1. Model line up
Part 1 General inform
ation
No. of connectable indoor units Max. 2 Max. 3 Max. 4 Model name PMBD3620 PMBD3630 PMBD3640 Connectable indoor unit capacity kBtu/h 5~24 5~24 5~24
BD unit
1.2 BD(Branch distributor) units
1.3 BranchesBranchType
No. of BDUnits
AccessoryModel Name
ApplicableModel
SpecificationsGas Liquid
Y-Branch 2 PMBL5620 1, 3
BranchKit 3 PMBL1203F0 1, 3
To BD unit 19.05
19.05
To ODU19.05
To BD unit 19.05
To ODU19.05
To BD unit 9.52
9.52
To ODU9.52
To BD unit 9.52
To ODU9.52
4 _ Heat pump 50Hz/R410A
Part
1 G
ener
al in
form
atio
n
2. Nomenclature2.1 Outdoor unit(Global)
Electrical rating
Indicates that this is multi system outdoor unit using R410AEx) A4U : Connectable max. 4 indoor units A9U : Connectable max. 9 indoor units
Model type W : DC inverter heat pump
Ex) 24,000 Btu/h Class '24', 27,000 Btu/h Class '27'Cooling/heating capacity
G : 220-240V, 1, 50Hz / 220V, 1, 60HzL : 380-415V, 3, 50Hz / 380V, 3, 60Hz
Multi type
Function
A : Basic
F : Free joint multi type
Serial number
A4U W 27 G F A 0
P M BD 36 2 0
Serial number
Number of connectable indoor units
Max. capacity of connectable indoor units36 mean that 5k~24k Indoor unit connected to BD unit
BD : Branch distributor
M : Multi system
P : Parts
2.2 BD units(Global)
Heat pump 50Hz/R410A _ 5
Part 1 General inform
ation
2. Nomenclature
MU4 M 27
Pipe Connecting TypeM : Multiple pipes
Cooling/heating capacityEx) 18,000 Btu/h Class '18'
Serial number
Outdoor unit chassis name
Indicates that this is multi system outdoor unit using R410AEx) MU3 : Connectable max. 3 indoor units MU4 : Connectable max. 4 indoor units
U4 2
FM 40 U3 2A H
Model Ttype
Outdoor unit chassis name
Serial number
H : Heat pump
Type of refrigerantA : R410A
Cooling/heating capacityEx) 48,000 Btu/h Class '48' Model typeFM : Free joint type inverter multi( )
2.3 Outdoor unit(Europe)
6 _ Heat pump 50Hz/R410A
Part
1 G
ener
al in
form
atio
n
3. AppearanceLG multi system provides various indoor units such as wall mounted, ART COOL, ART COOL Mirror, ceiling cassette,ceiling concealed duct, ceiling & floor , Ceiling suspended and console.
Outdoor unit
Outdoor unit
Y Branch(Applicable for only BD unit)
BD(Branch distributor) unit
Heat pump 50Hz/R410A _ 7
Part 1 General inform
ation
4. Combination4.1 Selection procedureOutdoor units selectionIn general, outdoor unit may be selected as follows, though the location of the unit, and usage of the room, etc. should beconsidered.The combination of indoor and outdoor unit was to be decided that the sum of indoor unit capacity index should be smallerthan the max. combination capacity of outdoor unit. Up to Max.9 indoor units can be connected to one outdoor unit. It is rec-ommended to choose a large capacity outdoor unit if the installation space is large enough.
Model name
Nominal Capacity(kW)
4.10 4.69 5.27 6.15
4.69 5.27 6.33 7.03
Max. 2 Uints Max. 2 Uints Max. 3 Uints Max. 3 Uints
21 24 30 33
4.1 4.7 5.3 6.2
A2UW14GFA0[MU2M15 UL2]
A2UW16GFA0[MU2M17 UL2]
A3UW18GFA0[MU3M19 UE2]
A3UW21GFA0[MU3M21 UE2]
Rated capacity (kW)
Connectable indoor units
Number of indoor units
Heating
Cooling
Maximum Total Capacity Index (kBtu/h)
Model name
7.0 7.9 8.8 11.7
7.03 7.91 8.79 11.2
8.44 9.08 10.1 12.5
Max. 4 Uints Max. 4 Uints Max. 5 Uints Max. 5 Uints
39 41 48 52
A4UW24GFA0[MU4M25 U42]
A4UW27GFA0[MU4M27 U42]
A5UW30GFA0[MU5M30 U42]
A5UW40GFA0[MU5M40 UO2]
Rated capacity (kW)
Connectable indoor units
Number of indoor units
Heating
Cooling
Maximum Total Capacity Index (kBtu/h)
Nominal Capacity(kW)
Model name
11.7 14.1 16.7
11.2 14.0 15.5
12.5 16.0 17.4
Max. 7 units Max. 8 units Max. 9 units
52 63 73
A7UW40GFA0[MU5M40 UO2]
A8UW48GFA0[FM48AH U32]
A9UW56GFA0[FM56AH U32]
Rated capacity (kW)
Connectable indoor units
Number of indoor units
Heating
Cooling
Maximum Total Capacity Index (kBtu/h)
Nominal Capacity(kW)
/ (1 phase)
8 _ Heat pump 50Hz/R410A
Part
1 G
ener
al in
form
atio
n
4. Combination
Indoor units selectionLook up the table on combination of indoor and outdoor unit, and determine the appropriate indoor unit capacitywhich satisfies the given thermal load.For proper system operation, refer to the following:1) At least 2 indoor units should be connected to outdoor unit.2) Total capacity of indoor units connected should be minimum 40% of outdoor unit rated capacity.3) Calculation method for the connectable total capacity of indoor unit sum up the capacity of indoor unit, but
high static duct type indoor unit capacity weights 1.3 times.
Indoor Unit Model Name -05G- -07G- -09G- -12G- -18G- -24G-
Capacity Index(kBtu/h) 5 7 9 12 18 24
(3 phase)
Model name
13.5 14.1 16.7
11.2 14.0 15.5
12.5 16.0 17.4
Max. 7 units Max. 8 units Max. 9 units
54 63 73
A7UW42LFA0[FM41AH U32]
A8UW48LFA0[FM49AH U32]
A9UW56LFA0[FM57AH U32]
Rated capacity (kW)
Connectable indoor units
Number of indoor units
Heating
Cooling
Maximum Total Capacity Index (kBtu/h)
Nominal Capacity(kW)
BD units selection (accessory)
Branch units selection(accessory)
PMBD3620 PMBD3630 PMBD3640 1~2 units 1~3 units 1~4 units 5~24 5~24 5~24
BD UnitNumber of Indoor Unit
Indoor Unit Capacity index (kBtu/h)Connectableindoor units
Y Branch Type 1 Not required 2 PMBL5620 3 PMBL1203F0
Connected number ofBD units
Heat pump 50Hz/R410A _ 9
Part 1 General inform
ation
4. Combination4.2 Combination of indoor and outdoor unitThe total capacity index of indoor units is the sum of capacity index of each units and should be within the capacity index ofthe outdoor unit.
Nominal Capacity of Outdoor Unit 4.1 kW
4.7 kW5.3 kW6.2 kW
7.0 kW / 7.9 kW8.8 kW
11.7 kW / 13.5 kW 14.1 kW / 16.7 kW
Indoor Unit Type Indoor Unit CapacityIndex (kBtu/h) Connectable Indoor Units
Wall mounted
5 O O O O7 O O O O9 O O O O
12 O O O O18 - O O O24 - - O O
ART COOL 9 O O O O12 O O O O
ART COOL Mirror
7 O O O O9 O O O O
12 O O O O18 - O O O24 - - O O
Ceiling Cassette(1-way)
9 O O O O12 O O O O
Ceiling Cassette(4-way)
5 O O O O7 O O O O9 O O O O
12 O O O O18 - O O O24 - - O O
Ceiling & Floor andCeiling Suspended
9 O O O O12 O O O O18 - O O O24 - - O O
Ceiling Concealed Duct(High Static Pressure)
18 - O O O24 - - O O
Ceiling Concealed Duct (Low Static Pressure)
9 O O O O12 O O O O18 - O O O24 - - O O
Console9 O O O O
12 O O O O18 - O O O
Part 2 Product data
n Outdoor units1. Multiple piping type 2. Distributor type (1 phase)3. Distributor type (3 phase)4. BD Unit (Distributor Box)
Multiple piping type 1. Power supply2. List of functions3. Specifications4. Combination table5. Dimensions6. Piping diagrams7. Wiring diagrams8. Capacity tables9. Operation range10. Electrical characteristics11. Field wiring diagram12. Sound levels
Heat Pump 50Hz/R410A _ 1
1. Multiple piping type MULTI F
Part 2 Product data_Outdoor units
1.1 Power supply
External wiring procedure- The power supply work is needed only to the outdoor unit. The power supply to the indoor unit is conducted through the
transmission wiring. Therefore, the power supply work can be carried out at just one place of the outdoor unit. It willcontribute to simplify the work procedure and to save cost.
- Wiring cable size must comply with the applicable local and national code.
Outdoor unit
[Indoor unit]
Power supply
Circuit breaker
Earth wire
Type Outdoor unit Capacity[kBtu/h(kW)] Circuit breaker capacity Power supply
Heat Pump
A2UW14GFA0 [MU2M15 UL2] 14.0 (4.10)15A
220-240V, 1, 50Hz
A2UW16GFA0 [MU2M17 UL2] 16.0 (4.69)A3UW18GFA0 [MU3M19 UE2] 18.0 (5.27)
20AA3UW21GFA0 [MU3U21 UE2] 21.0 (6.15)A4UW24GFA0 [MU4M25 U42] 24.0 (7.03)
25AA4UW27GFA0 [MU4M27 U42] 27.0 (7.91)A5UW30GFA0 [MU5M30 U42] 30.0 (8.79)A5UW40GFA0 [MU5M40 UO2] 38.2 (11.2) 30A
1. Multiple piping type MULTI F
2 _ Heat Pump 50Hz/R410A
Part
2 Pro
duct
data_
Outdo
or un
its
1.2 List of functions
[Note] O: Applied, X: Not applied Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with
separate package.
Category Functions A2UW14GFA0 [MU2M15 UL2]A2UW16GFA0 [MU2M17 UL2]
Reliability
Defrost / Deicing OHigh pressure switch XLow pressure switch XPhase protection XRestart delay (3-minutes) OSelf diagnosis OSoft start OTest function X
Convenience
Night Silent Operation OWiring Error Check OPeak Control OMode Lock OForced Cooling Operation (Outdoor Unit) O
Network function Network soluation(LGAP) O
Device A2UW14GFA0 [MU2M15 UL2]A2UW16GFA0 [MU2M17 UL2]
Central Controller
Simple Controller XFunction controller XFunction Scheduler XAC Ez XAC Smart ll XOption Kit (SD card type) XACP(Advanced Control Platform) XAC Manager XPI485 XDO(Digital Output) Kit X
BNU(Building Network Unit)
LONWORKS Gateway XBACnet Gateway X
InstallationY branch XHeader branch XAir Guide X
PDI(power distribution indicator) XODU Dry Contact XLow Ambient Kit O (Logical operation)
Heat Pump 50Hz/R410A _ 3
1. Multiple piping type MULTI F
Part 2 Product data_Outdoor units
[Note] O: Applied, X: Not applied Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with
separate package.* : A5UW40GFA0 [MU5M40 UO2] model only is applied.
Category FunctionsA3UW18GFA0 [MU3M19 UE2] A3UW21GFA0 [MU3M21 UE2]A4UW24GFA0 [MU4M25 U42] A4UW27GFA0 [MU4M27 U42]A5UW30GFA0 [MU5M30 U42] A5UW40GFA0 [MU5M40 UO2]
Reliability
Defrost / Deicing OHigh pressure switch XLow pressure switch XPhase protection XRestart delay (3-minutes) OSelf diagnosis OSoft start OTest function X
Convenience
Night Silent Operation OWiring Error Check OPeak Control OMode Lock OForced Cooling Operation (Outdoor Unit) O
Network function Network soluation(LGAP) O
DeviceA3UW18GFA0 [MU3M19 UE2] A3UW21GFA0 [MU3M21 UE2]A4UW24GFA0 [MU4M25 U42] A4UW27GFA0 [MU4M27 U42]A5UW30GFA0 [MU5M30 U42] A5UW40GFA0 [MU5M40 UO2]
Central Controller
Simple Controller PQCSB101S0Function controller PQCSB101S0 + PQCSC101S0Function Scheduler PQCSB101S0 + PQCSD130A0AC Ez PQCSZ250S0AC Smart ll PQCSW320A1EOption Kit (SD card type) PQCSE341A0 / PQCSE342A0ACP(Advanced Control Platform) PQCPA11A0E / PQCPB11A0EAC Manager PQCSS520A0EPI485 PMNFP14A0/PMNFP14A1DO(Digital Output) Kit PQNFP00T0
BNU(Building Network Unit)
LONWORKS Gateway PQNFB16A1BACnet Gateway PQNFB17B0
InstallationY branch XHeader branch XAir Guide X
PDI(power distribution indicator) PQNUD1S00ODU Dry Contact O*Low Ambient Kit O (Logical operation)
1. Multiple piping type MULTI F
4 _ Heat Pump 50Hz/R410A
Part
2 Pro
duct
data_
Outdo
or un
its
1.3 Specifications
Note :1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27C(80.6F) DB / 19C(66.2F) WBOutdoor 35C(95F) DB / 24C(75.2F) WB
- Heating Temperature : Indoor 20C(68F) DB / 15C(59F) WBOutdoor 7C(44.6F) DB / 6C(42.8F) WB
- Piping Length : Interconnected Pipe Length = 7.5m- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.3. Due to our policy of innovation some specifications may be changed without notification.4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
Outdoor unit A2UW14GFA0[MU2M15 UL2]A2UW16GFA0[MU2M17 UL2]
Testing Combination
CapacityCooling Min.~Rated~Max. kWMin.~Rated~Max. Btu/hHeating Min.~Rated~Max. kWMin.~Rated~Max. Btu/h
Power Input Cooling Min.~Rated~Max. kWHeating Min.~Rated~Max. kWSEER / SCOP Wh / WhSeasonal Energy Label Cooling / Heating -Annual Energy Consumption Cooling / Heating kWh
Power Supply V , , HzRunning Current Cooling Min.~Rated~Max. AHeating Min.~Rated~Max. AStarting Current Cooling Max. AHeating Max. AWiring Connections Power Supply Cable (included Earth) No. x mm2 (AWG)Power and Communication Cable (included Earth) Outdoor ~ BD unit No. x mm2 (AWG)
CombinationSum of Indoor Units Capacity kBtu/hNumber of Indoor Units EANumber of BD Units EA
Casing Color -Dimensions W x H x D mmW x H x D inchNet Weight kg (lbs)
Compressor Type -Model Model x No.Motor type -Motor Output W x No.
Refrigerant
Type -Precharged Amount g (oz)Chargeless-Pipe Length m (ft)Additional Charging Volume g/m (oz/ft)Control -
Refrigerant Oil Type -Charged volume cc x No.Heat Exchanger (Row x Column x Fins per inch) x No. -Fan Type -Air Flow Rate m3/min x No.Fan Motor TypeOutput W x No.Sound Pressure Level Cooling Rated dB(A)Heating Rated dB(A)Sound Power Level Cooling Max. dB(A)Piping Connections Liquid Outer Dia. mm(inch) x No.Gas Outer Dia. mm(inch) x No.
Piping LengthTotal Piping Max. m (ft)Main Piping Max. m (ft)Total Branch Piping Max. m (ft)Each Branch Piping Max. m (ft)
Maximum HeightDifference
Outdoor Unit ~ Indoor Unit Max. m (ft)Indoor Unit ~ Indoor Unit Max. m (ft)
Operation Range (Outdoor Temperature)
Cooling Min. ~ Max. DB ( DB)Heating Min. ~ Max. WB ( WB)
MS07AQ NB0 x 2EA MS09AQ NB0 x 2EA 0.88 ~ 4.10 ~ 5.39 0.88 ~ 4.69 ~ 5.39
3,000 ~ 14,000 ~ 18,400 3,000 ~ 16,000 ~ 18,4000.97 ~ 4.69 ~ 5.69 0.97 ~ 5.27 ~ 5.69
3,300 ~ 16,000 ~ 19,400 3,300 ~ 18,000 ~ 19,4000.29 ~ 1.02 ~ 1.63 0.29 ~ 1.26 ~ 1.630.29 ~ 1.08 ~ 1.66 0.29 ~ 1.28 ~ 1.66
6.1 / 3.8 6.1 / 3.8A++ / A A++ / A
235 / 1,732 270 / 1,842
220-240, 1, 50 220-240, 1, 501.3 ~ 4.6 ~ 7.4 1.3 ~ 5.8 ~ 7.41.3 ~ 4.9 ~ 7.5 1.3 ~ 5.8 ~ 7.5
- -
- -
3C x 2.5 (12) 3C x 2.5 (12)- -
21 242 2- -
Warm Gray Warm Gray770 545 288 770 545 288
30-5/16 x 21-15/32 x 11-11/32 30-5/16 x 21-15/32 x 11-11/3237 (81.6) 37 (81.6)
Twin Rotary Twin RotaryGKT141MA x 1 GKT141MA x 1
BLDC BLDC1,500 (at 60Hz) x 1 1,500 (at 60Hz) x 1
R410A R410A1,400 (49.4) 1,400 (49.4)
15 (49.2) 15 (49.2)20 (0.22) 20 (0.22)
Electronic Expansion Valve Electronic Expansion ValveFVC68D FVC68D570 x 1 570 x 1
(2 x 24 x 14) x 1 (2 x 24 x 14) x 1Propeller Propeller28.2 x 1 28.2 x 1BLDC BLDC43 x 1 43 x 1
49 4951 5159 62
6.35 (1/4) x 2 6.35 (1/4) x 2 9.52 (3/8) x 2 9.52 (3/8) x 2
30 (98.4) 30 (98.4)- -
- -
20 (65.6) 20 (65.6)15 (49.2) 15 (49.2)7.5 (24.6) 7.5 (24.6)
-10 (14.0) ~ 46 (114.8) -10 (14.0) ~ 46 (114.8)-18 (-0.4) ~ 18 (64.4) -18 (-0.4) ~ 18 (64.4)
Heat Pump 50Hz/R410A _ 5
1. Multiple piping type MULTI F
Part 2 Product data_Outdoor units
Note :1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27C(80.6F) DB / 19C(66.2F) WBOutdoor 35C(95F) DB / 24C(75.2F) WB
- Heating Temperature : Indoor 20C(68F) DB / 15C(59F) WBOutdoor 7C(44.6F) DB / 6C(42.8F) WB
- Piping Length : Interconnected Pipe Length = 7.5m- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.3. Due to our policy of innovation some specifications may be changed without notification.4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
Outdoor unit A3UW18GFA0[MU3M19 UE2]A3UW21GFA0[MU3M21 UE2]
Testing Combination
CapacityCooling Min.~Rated~Max. kWMin.~Rated~Max. Btu/hHeating Min.~Rated~Max. kWMin.~Rated~Max. Btu/h
Power Input Cooling Min.~Rated~Max. kWHeating Min.~Rated~Max. kWSEER / SCOP Wh / WhSeasonal Energy Label Cooling / Heating -Annual Energy Consumption Cooling / Heating kWh
Power Supply V , , HzRunning Current Cooling Min.~Rated~Max. AHeating Min.~Rated~Max. AStarting Current Cooling Max. AHeating Max. AWiring Connections Power Supply Cable (included Earth) No. x mm2 (AWG)Power and Communication Cable (included Earth) Outdoor ~ BD unit No. x mm2 (AWG)
CombinationSum of Indoor Units Capacity kBtu/hNumber of Indoor Units EANumber of BD Units EA
Casing Color -Dimensions W x H x D mmW x H x D inchNet Weight kg (lbs)
Compressor Type -Model Model x No.Motor type -Motor Output W x No.
Refrigerant
Type -Precharged Amount g (oz)Chargeless-Pipe Length m (ft)Additional Charging Volume g/m (oz/ft)Control -
Refrigerant Oil Type -Charged volume cc x No.Heat Exchanger (Row x Column x Fins per inch) x No. -Fan Type -Air Flow Rate m3/min x No.Fan Motor TypeOutput W x No.Sound Pressure Level Cooling Rated dB(A)Heating Rated dB(A)Sound Power Level Cooling Max. dB(A)Piping Connections Liquid Outer Dia. mm(inch) x No.Gas Outer Dia. mm(inch) x No.
Piping LengthTotal Piping Max. m (ft)Main Piping Max. m (ft)Total Branch Piping Max. m (ft)Each Branch Piping Max. m (ft)
Maximum HeightDifference
Outdoor Unit ~ Indoor Unit Max. m (ft)Indoor Unit ~ Indoor Unit Max. m (ft)
Operation Range (Outdoor Temperature)
Cooling Min. ~ Max. DB ( DB)Heating Min. ~ Max. WB ( WB)
MS07AQ NB0 x 3EA MS07AQ NB0 x 3EA1.35 ~ 5.27 ~ 6.33 1.41 ~ 6.15 ~ 7.32
4,600 ~ 18,000 ~ 21,600 4,800 ~ 21,000 ~ 25,0001.41 ~ 6.33 ~ 7.27 1.47 ~ 7.03 ~ 7.76
4,800 ~ 21,600 ~ 24,840 5,000 ~ 24,000 ~ 26,5000.14 ~ 1.29 ~ 2.08 0.14 ~ 1.58 ~ 2.360.18 ~ 1.53 ~ 2.64 0.21 ~ 1.71 ~ 2.72
6.1 / 3.9 6.1 / 3.9A++ / A A++ / A
304 / 2,118 356 / 2,226
220-240, 1, 50 220-240, 1, 500.6 ~ 6.0 ~ 9.0 0.6 ~ 6.6 ~ 10.3
0.8 ~ 7.0 ~ 11.5 0.9 ~ 7.4 ~ 11.8- -
- -
3C x 2.5 (12) 3C x 2.5 (12)- -
30 333 3- -
Warm Gray Warm Gray870 655 320 870 655 320
34-1/4 x 25-25/32 x 12-19/32 34-1/4 x 25-25/32 x 12-19/3245 (99.2) 45 (99.2)
Twin Rotary Twin RotaryGKT141MA x 1 GKT176MA x 1
BLDC BLDC1,500 (at 60Hz) x 1 1,500 (at 60Hz) x 1
R410A R410A1,700 (60.0) 1,800 (63.5)22.5 (73.8) 22.5 (73.8)20 (0.22) 20 (0.22)
Electronic Expansion Valve Electronic Expansion ValveFVC68D FVC68D570 x 1 670 x 1
(2 x 28 x 14) x 1 (2 x 28 x 14) x 1Propeller Propeller
50 x 1 50 x 1BLDC BLDC
85.4 x 1 85.4 x 150 5152 5364 64
6.35 (1/4) x 3 6.35 (1/4) x 3 9.52 (3/8) x 3 9.52 (3/8) x 3
50 (164.0) 50 (164.0)- -
- -
25 (82.0) 25 (82.0)15 (49.2) 15 (49.2)7.5 (24.6) 7.5 (24.6)
-10 (14.0) ~ 48 (118.4) -10 (14.0) ~ 48 (118.4)-18 (-0.4) ~ 18 (64.4) -18 (-0.4) ~ 18 (64.4)
1. Multiple piping type MULTI F
6 _ Heat Pump 50Hz/R410A
Part
2 Pro
duct
data_
Outdo
or un
its
Outdoor unit A4UW24GFA0[MU4M25 U42]A4UW27GFA0[MU4M27 U42]
Testing Combination
CapacityCooling Min.~Rated~Max. kWMin.~Rated~Max. Btu/hHeating Min.~Rated~Max. kWMin.~Rated~Max. Btu/h
Power Input Cooling Min.~Rated~Max. kWHeating Min.~Rated~Max. kWSEER / SCOP Wh / WhSeasonal Energy Label Cooling / Heating -Annual Energy Consumption Cooling / Heating kWh
Power Supply V , , HzRunning Current Cooling Min.~Rated~Max. AHeating Min.~Rated~Max. AStarting Current Cooling Max. AHeating Max. AWiring Connections Power Supply Cable (included Earth) No. x mm2 (AWG)Power and Communication Cable (included Earth) Outdoor ~ BD unit No. x mm2 (AWG)
CombinationSum of Indoor Units Capacity kBtu/hNumber of Indoor Units EANumber of BD Units EA
Casing Color -Dimensions W x H x D mmW x H x D inchNet Weight kg (lbs)
Compressor Type -Model Model x No.Motor type -Motor Output W x No.
Refrigerant
Type -Precharged Amount g (oz)Chargeless-Pipe Length m (ft)Additional Charging Volume g/m (oz/ft)Control -
Refrigerant Oil Type -Charged volume cc x No.Heat Exchanger (Row x Column x Fins per inch) x No. -Fan Type -Air Flow Rate m3/min x No.Fan Motor TypeOutput W x No.Sound Pressure Level Cooling Rated dB(A)Heating Rated dB(A)Sound Power Level Cooling Max. dB(A)Piping Connections Liquid Outer Dia. mm(inch) x No.Gas Outer Dia. mm(inch) x No.
Piping LengthTotal Piping Max. m (ft)Main Piping Max. m (ft)Total Branch Piping Max. m (ft)Each Branch Piping Max. m (ft)
Maximum HeightDifference
Outdoor Unit ~ Indoor Unit Max. m (ft)Indoor Unit ~ Indoor Unit Max. m (ft)
Operation Range (Outdoor Temperature)
Cooling Min. ~ Max. DB ( DB)Heating Min. ~ Max. WB ( WB)
Note :1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27C(80.6F) DB / 19C(66.2F) WBOutdoor 35C(95F) DB / 24C(75.2F) WB
- Heating Temperature : Indoor 20C(68F) DB / 15C(59F) WBOutdoor 7C(44.6F) DB / 6C(42.8F) WB
- Piping Length : Interconnected Pipe Length = 7.5m- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.3. Due to our policy of innovation some specifications may be changed without notification.4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
MS07AQ NB0 x 4EA MS07AQ NB0 x 4EA1.32 ~ 7.03 ~ 8.50 1.32 ~ 7.91 ~ 9.49
4,500 ~ 24,000 ~ 29,000 4,500 ~ 27,000 ~ 32,4001.45 ~ 8.44 ~ 9.38 1.47 ~ 9.08 ~ 10.6
4,950 ~ 28,800 ~ 32,000 5,000 ~ 31,000 ~ 36,0000.44 ~ 1.67 ~ 2.59 0.44 ~ 1.98 ~ 3.010.50 ~ 1.80 ~ 2.99 0.50 ~ 2.01 ~ 3.60
6.1 / 3.8 6.1 / 3.8A++ / A A++ / A
402 / 3,095 453 / 3,242
220-240, 1, 50 220-240, 1, 502.0 ~ 7.2 ~ 11.1 2.0 ~ 8.5 ~ 13.22.2 ~ 8.1 ~ 12.8 2.2 ~ 9.1 ~ 15.8
- -
- -
3C x 2.5 (12) 3C x 2.5 (12)- -
39 414 4- -
Warm Gray Warm Gray950 834 330 950 834 330
37-13/32 x 32-27/32 x 13 37-13/32 x 32-27/32 x 1364 (141.1) 64 (141.1)
Twin Rotary Twin RotaryGJT240MA x 1 GJT240MA x 1
BLDC BLDC2,020 (at 60Hz) x 1 2,020 (at 60Hz) x 1
R410A R410A3,200 (112.9) 3,200 (112.9)37.5 (123.0) 37.5 (123.0)
20 (0.22) 20 (0.22)Electronic Expansion Valve Electronic Expansion Valve
FVC68D FVC68D900 x 1 900 x 1
(2 x 38 x 14) x 1 (2 x 38 x 14) x 1Propeller Propeller
60 x 1 60 x 1BLDC BLDC
124.2 x 1 124.2 x 151 5153 5362 63
6.35 (1/4) x 4 6.35 (1/4) x 4 9.52 (3/8) x 4 9.52 (3/8) x 4
70 (229.7) 70 (229.7)- -
- -
25 (82.0) 25 (82.0)15 (49.2) 15 (49.2)7.5 (24.6) 7.5 (24.6)
-10 (14.0) ~ 48 (118.4) -10 (14.0) ~ 48 (118.4)-18 (-0.4) ~ 18 (64.4) -18 (-0.4) ~ 18 (64.4)
Heat Pump 50Hz/R410A _ 7
1. Multiple piping type MULTI F
Part 2 Product data_Outdoor units
Note :1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27C(80.6F) DB / 19C(66.2F) WBOutdoor 35C(95F) DB / 24C(75.2F) WB
- Heating Temperature : Indoor 20C(68F) DB / 15C(59F) WBOutdoor 7C(44.6F) DB / 6C(42.8F) WB
- Piping Length : Interconnected Pipe Length = 7.5m- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.3. Due to our policy of innovation some specifications may be changed without notification.4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
Outdoor unit A5UW30GFA0[MU5M30 U42]A5UW40GFA0[MU5M40 UO2]
Testing Combination
CapacityCooling Min.~Rated~Max. kWMin.~Rated~Max. Btu/hHeating Min.~Rated~Max. kWMin.~Rated~Max. Btu/h
Power Input Cooling Min.~Rated~Max. kWHeating Min.~Rated~Max. kWSEER / SCOP Wh / WhSeasonal Energy Label Cooling / Heating -Annual Energy Consumption Cooling / Heating kWh
Power Supply V , , HzRunning Current Cooling Min.~Rated~Max. AHeating Min.~Rated~Max. AStarting Current Cooling Max. AHeating Max. AWiring Connections Power Supply Cable (included Earth) No. x mm2 (AWG)Power and Communication Cable (included Earth) Outdoor ~ BD unit No. x mm2 (AWG)
CombinationSum of Indoor Units Capacity kBtu/hNumber of Indoor Units EANumber of BD Units EA
Casing Color -Dimensions W x H x D mmW x H x D inchNet Weight kg (lbs)
Compressor Type -Model Model x No.Motor type -Motor Output W x No.
Refrigerant
Type -Precharged Amount g (oz)Chargeless-Pipe Length m (ft)Additional Charging Volume g/m (oz/ft)Control -
Refrigerant Oil Type -Charged volume cc x No.Heat Exchanger #1_(Row x Column x Fins per inch) x No. -#2_(Row x Column x Fins per inch) x No. -Fan Type -Air Flow Rate m3/min x No.Fan Motor TypeOutput W x No.Sound Pressure Level Cooling Rated dB(A)Heating Rated dB(A)Sound Power Level Cooling Max. dB(A)Piping Connections Liquid Outer Dia. mm(inch) x No.Gas Outer Dia. mm(inch) x No.
Piping LengthTotal Piping Max. m (ft)Main Piping Max. m (ft)Total Branch Piping Max. m (ft)Each Branch Piping Max. m (ft)
Maximum HeightDifference
Outdoor Unit ~ Indoor Unit Max. m (ft)Indoor Unit ~ Indoor Unit Max. m (ft)
Operation Range (Outdoor Temperature)
Cooling Min. ~ Max. DB ( DB)Heating Min. ~ Max. WB ( WB)
MS07AQ NB0 x 5EA MS09AQ NB0 x 5EA1.32 ~ 8.79 ~ 10.6 0.88 ~ 11.2 ~ 13.5
4,500 ~ 30,000 ~ 36,000 3,000 ~ 38,200 ~ 46,0001.47 ~ 10.1 ~ 12.1 0.97 ~ 12.5 ~ 15.0
5,000 ~ 34,500 ~ 41,400 3,300 ~ 42,700 ~ 51,2000.44 ~ 2.20 ~ 3.38 0.78 ~ 2.73 ~ 4.150.50 ~ 2.20 ~ 3.70 0.82 ~ 2.81 ~ 4.45
6.1 / 3.8 6.1 / 3.9A++ / A A++ / A
505 / 3,353 643 / 4,236
220-240, 1, 50 220-240, 1, 502.0 ~ 9.9 ~ 16.2 3.5 ~ 12.1 ~ 18.42.2 ~ 9.8 ~ 16.5 3.6 ~ 12.5 ~ 19.7
- -
- -
3C x 2.5 (12) 3C x 3.5 (10)- -
48 525 5- -
Warm Gray Warm Gray950 834 330 950 1,170 330
37-13/32 x 32-27/32 x 13 37-13/32 x 46-1/16 x 1364 (141.1) 84 (185.2)
Twin Rotary Twin RotaryGJT240MA x 1 GPT442MBA x 1
BLDC BLDC2,020 (at 60Hz) x 1 4,000 (at 60Hz) x 1
R410A R410A3,200 (112.9) 3,800 (134.0)37.5 (123.0) 37.5 (123.0)
20 (0.22) 20 (0.22)Electronic Expansion Valve Electronic Expansion Valve
FVC68D FVC68D900 x 1 1,300 x 1
(2 x 38 x 14) x 1 (2 x 32 x 14) x 1- (2 x 22 x 14) x 1
Propeller Propeller60 x 1 45 x 2BLDC BLDC
124.2 x 1 85.4 x 251 5353 5564 67
6.35 (1/4) x 5 6.35 (1/4) 5 9.52 (3/8) x 5 9.52 (3/8) 5
75 (246.1) 85 (278.9)- -
- -
25 (82.0) 25 (82.0)15 (49.2) 15 (49.2)7.5 (24.6) 7.5 (24.6)
-10 (14.0) ~ 48 (118.4) -10 (14.0) ~ 48 (118.4)-18 (-0.4) ~ 18 (64.4) -18 (-0.4) ~ 18 (64.4)
1. Multiple piping type MULTI F
8 _ Heat Pump 50Hz/R410A
Part
2 Pro
duct
data_
Outdo
or un
its
Models : A2UW14GFA0 [MU2M15 UL2]
Cooling
Heating
Note :1. Cooling Capacity is based on : indoor temp.27CDB, 19CWB
; outdoor temp. 35CDB, 24CWB2. Heating Capacity is based on : indoor temp.20CDB, 15CWB
; outdoor temp. 7CDB, 6CWB3. Maximum total capacity index of connected indoor units is 21 kBtu/h. 4. At least two indoor units should be connected to outdoor unit.5. Total capacity of indoor units connected should be minimum 40% of outdoor unit rated capacity.
5 - 5 1.5 - 3,000 0.9 5,000 1.5 6,000 1.8 290 480 600 1UNIT 7 - 7 2.1 - 4,200 1.2 7,000 2.1 8,400 2.5 320 520 620 9 - 9 2.6 - 5,400 1.6 9,000 2.6 10,800 3.2 400 660 850
12 - 12 3.5 - 7,200 2.1 12,000 3.5 14,400 4.2 530 880 1,220 5 5 10 1.5 1.5 6,000 1.8 10,000 2.9 11,500 3.4 480 800 1,090 5 7 12 1.5 2.1 7,200 2.1 12,000 3.5 13,800 4.0 530 880 1,220 5 9 14 1.5 2.6 8,400 2.5 14,000 4.1 16,100 4.7 620 1,020 1,450 5 12 17 1.4 3.3 9,600 2.8 16,000 4.7 18,400 5.4 770 1,260 1,630
2 UNIT 7 7 14 2.1 2.1 8,400 2.5 14,000 4.1 16,100 4.7 620 1,020 1,450 7 9 16 2.1 2.6 9,600 2.8 16,000 4.7 18,400 5.4 770 1,260 1,630 7 12 19 1.7 3.0 9,600 2.8 16,000 4.7 18,400 5.4 770 1,260 1,630 9 9 18 2.3 2.3 9,600 2.8 16,000 4.7 18,400 5.4 770 1,260 1,630 9 12 21 2.0 2.7 9,600 2.8 16,000 4.7 18,400 5.4 770 1,260 1,630
Combination(kBtu/h) Each capacity(kW)
Total Capacity (kW)Cooling
Min Rated MaxInput(W)
Unit-A Unit-B Total Unit-A Unit-B Btu/h kW Btu/h kW Btu/h kW Min Rated Max
Operation
5 - 5 1.6 - 3,300 1.0 5,500 1.6 6,000 1.8 290 480 600 1 UNIT 7 - 7 2.5 - 5,100 1.5 8,400 2.5 9,200 2.7 340 560 710 9 - 9 3.2 - 6,500 1.9 10,800 3.2 11,800 3.5 420 700 890
12 - 12 3.9 - 8,000 2.3 13,200 3.9 14,500 4.2 520 860 1,120 5 5 10 1.6 1.6 6,600 1.9 11,000 3.2 12,100 3.5 450 740 940 5 7 12 1.6 2.3 8,000 2.3 13,200 3.9 14,500 4.2 520 860 1,090 5 9 14 1.7 3.0 9,600 2.8 16,000 4.7 17,200 5.0 650 1,080 1,390 5 12 17 1.6 3.7 10,800 3.2 18,000 5.3 19,400 5.7 780 1,280 1,660
2 UNIT 7 7 14 2.3 2.3 9,600 2.8 16,000 4.7 17,200 5.0 650 1,080 1,390 7 9 16 2.3 3.0 10,800 3.2 18,000 5.3 19,400 5.7 780 1,280 1,660 7 12 19 1.9 3.3 10,800 3.2 18,000 5.3 19,400 5.7 780 1,280 1,660 9 9 18 2.6 2.6 10,800 3.2 18,000 5.3 19,400 5.7 780 1,280 1,660 9 12 21 2.3 3.0 10,800 3.2 18,000 5.3 19,400 5.7 780 1,280 1,660
Combination(kBtu/h) Each capacity(kW)
Total Capacity (kW)Heating
Min Rated MaxInput(W)
Unit-A Unit-B Total Unit-A Unit-B Btu/h kW Btu/h kW Btu/h kW Min Rated Max
Operation
1.4 Combination table
Heat Pump 50Hz/R410A _ 9
1. Multiple piping type MULTI F
Part 2 Product data_Outdoor units
Models : A2UW16GFA0 [MU2M17 UL2]
Cooling
Heating
Note :1. Cooling Capacity is based on : indoor temp.27CDB, 19CWB
; outdoor temp. 35CDB, 24CWB2. Heating Capacity is based on : indoor temp.20CDB, 15CWB
; outdoor temp. 7CDB, 6CWB3. Maximum total capacity index of connected indoor units is 24 kBtu/h. 4. At least two indoor units should be connected to outdoor unit.5. Total capacity of indoor units connected should be minimum 40% of outdoor unit rated capacity.
5 - 5 1.5 - 3,000 0.9 5,000 1.5 6,000 1.8 290 480 600 1 UNIT 7 - 7 2.1 - 4,200 1.2 7,000 2.1 8,400 2.5 320 520 620 9 - 9 2.6 - 5,400 1.6 9,000 2.6 10,800 3.2 400 660 850
12 - 12 3.5 - 7,200 2.1 12,000 3.5 14,400 4.2 530 880 1,220 5 5 10 1.5 1.5 6,000 1.8 10,000 2.9 11,500 3.4 480 800 1,090 5 7 12 1.5 2.1 7,200 2.1 12,000 3.5 13,800 4.0 530 880 1,220 5 9 14 1.5 2.6 8,400 2.5 14,000 4.1 16,100 4.7 620 1,020 1,450 5 12 17 1.4 3.3 9,600 2.8 16,000 4.7 18,400 5.4 760 1,260 1,630
2 UNIT 7 7 14 2.1 2.1 8,400 2.5 14,000 4.1 16,100 4.7 620 1,020 1,450 7 9 16 2.1 2.6 9,600 2.8 16,000 4.7 18,400 5.4 760 1,260 1,630 7 12 19 1.7 3.0 9,600 2.8 16,000 4.7 18,400 5.4 760 1,260 1,630 9 9 18 2.3 2.3 9,600 2.8 16,000 4.7 18,400 5.4 760 1,260 1,630 9 12 21 2.0 2.7 9,600 2.8 16,000 4.7 18,400 5.4 760 1,260 1,630
12 12 24 2.3 2.3 9,600 2.8 16,000 4.7 18,400 5.4 760 1,260 1,630
Combination(kBtu/h) Each capacity(kW)
Total Capacity (kW)Cooling
Min Rated MaxInput(W)
Unit-A Unit-B Total Unit-A Unit-B Btu/h kW Btu/h kW Btu/h kW Min Rated Max
Operation
5 - 5 1.6 - 3,300 1.0 5,500 1.6 6,000 1.8 290 480 600 1 UNIT 7 - 7 2.5 - 5,100 1.5 8,400 2.5 9,200 2.7 340 560 710 9 - 9 3.2 - 6,500 1.9 10,800 3.2 11,800 3.5 420 700 890
12 - 12 3.9 - 8,000 2.3 13,200 3.9 14,500 4.2 520 860 1,120 5 5 10 1.6 1.6 6,600 1.9 11,000 3.2 12,100 3.5 450 740 940 5 7 12 1.6 2.3 8,000 2.3 13,200 3.9 14,500 4.2 520 860 1,090 5 9 14 1.7 3.0 9,600 2.8 16,000 4.7 17,200 5.0 650 1,080 1,390 5 12 17 1.6 3.7 10,800 3.2 18,000 5.3 19,400 5.7 770 1,280 1,660
2 UNIT 7 7 14 2.3 2.3 9,600 2.8 16,000 4.7 17,200 5.0 650 1,080 1,390 7 9 16 2.3 3.0 10,800 3.2 18,000 5.3 19,400 5.7 770 1,280 1,660 7 12 19 1.9 3.3 10,800 3.2 18,000 5.3 19,400 5.7 770 1,280 1,660 9 9 18 2.6 2.6 10,800 3.2 18,000 5.3 19,400 5.7 770 1,280 1,660 9 12 21 2.3 3.0 10,800 3.2 18,000 5.3 19,400 5.7 770 1,280 1,660
12 12 24 2.6 2.6 10,800 3.2 18,000 5.3 19,400 5.7 770 1,280 1,660
Combination(kBtu/h) Each capacity(kW)
Total Capacity (kW)Heating
Min Rated MaxInput(W)
Unit-A Unit-B Total Unit-A Unit-B Btu/h kW Btu/h kW Btu/h kW Min Rated Max
Operation
1. Multiple piping type MULTI F
10 _ Heat Pump 50Hz/R410A
Part
2 Pro
duct
data_
Outdo
or un
its
Models : A3UW18GFA0 [MU3M19 UE2]
Cooling
5 - - 5 1.5 - - 4,600 1.3 5,000 1.5 6,000 1.8 140 358 5787 - - 7 2.1 - - 4,600 1.3 7,000 2.1 8,400 2.5 196 502 809
1 Unit 9 - - 9 2.6 - - 5,400 1.6 9,000 2.6 10,800 3.2 252 645 1,04012 - - 12 3.5 - - 7,200 2.1 12,000 3.5 14,400 4.2 336 860 1,38718 - - 18 5.3 - - 10,800 3.2 18,000 5.3 21,600 6.3 504 1,290 2,0805 5 - 10 1.5 1.5 - 6,000 1.8 10,000 2.9 12,000 3.5 280 717 1,1565 7 - 12 1.5 2.1 - 7,200 2.1 12,000 3.5 14,400 4.2 336 860 1,3875 9 - 14 1.5 2.6 - 8,400 2.5 14,000 4.1 16,800 4.9 392 1,003 1,6185 12 - 17 1.5 3.5 - 10,200 3.0 17,000 5.0 20,400 6.0 476 1,218 1,9645 18 - 23 1.5 5.3 - 13,800 4.0 23,000 6.7 27,600 8.1 504 1,290 2,0807 7 - 14 2.1 2.1 - 8,400 2.5 14,000 4.1 16,800 4.9 392 1,003 1,618
2 Unit 7 9 - 16 2.1 2.6 - 9,600 2.8 16,000 4.7 19,200 5.6 448 1,147 1,8499 9 - 18 2.6 2.6 - 10,800 3.2 18,000 5.3 21,600 6.3 504 1,290 2,0807 12 - 19 1.9 3.3 - 10,800 3.2 18,000 5.3 21,600 6.3 504 1,290 2,0809 12 - 21 2.3 3.0 - 10,800 3.2 18,000 5.3 21,600 6.3 504 1,290 2,08012 12 - 24 2.6 2.6 - 10,800 3.2 18,000 5.3 21,600 6.3 504 1,290 2,0807 18 - 25 1.5 3.8 - 10,800 3.2 18,000 5.3 21,600 6.3 504 1,290 2,0809 18 - 27 1.8 3.5 - 10,800 3.2 18,000 5.3 21,600 6.3 504 1,290 2,08012 18 - 30 2.1 3.2 - 10,800 3.2 18,000 5.3 21,600 6.3 504 1,290 2,0805 5 5 15 1.5 1.5 1.5 9,000 2.6 15,000 4.4 18,000 5.3 420 1,075 1,7335 5 7 17 1.5 1.5 2.1 10,200 3.0 17,000 5.0 20,400 6.0 476 1,218 1,9645 5 9 19 1.4 1.4 2.5 10,800 3.2 18,000 5.3 21,600 6.3 504 1,290 2,0805 5 12 22 1.2 1.2 2.9 10,800 3.2 18,000 5.3 21,600 6.3 504 1,290 2,0805 7 7 19 1.4 1.9 1.9 10,800 3.2 18,000 5.3 21,600 6.3 504 1,290 2,0805 7 9 21 1.3 1.8 2.3 10,800 3.2 18,000 5.3 21,600 6.3 504 1,290 2,0805 7 12 24 1.1 1.5 2.6 10,800 3.2 18,000 5.3 21,600 6.3 504 1,290 2,0805 9 9 23 1.1 2.1 2.1 10,800 3.2 18,000 5.3 21,600 6.3 504 1,290 2,080
3 Unit 5 9 12 26 1.0 1.8 2.4 10,800 3.2 18,000 5.3 21,600 6.3 504 1,290 2,0805 12 12 29 0.9 2.2 2.2 10,800 3.2 18,000 5.3 21,600 6.3 504 1,290 2,0807 7 7 21 1.8 1.8 1.8 10,800 3.2 18,000 5.3 21,600 6.3 504 1,290 2,0807 7 9 23 1.6 1.6 2.1 10,800 3.2 18,000 5.3 21,600 6.3 504 1,290 2,0807 9 9 25 1.5 1.9 1.9 10,800 3.2 18,000 5.3 21,600 6.3 504 1,290 2,0807 7 12 26 1.4 1.4 2.4 10,800 3.2 18,000 5.3 21,600 6.3 504 1,290 2,0809 9 9 27 1.8 1.8 1.8 10,800 3.2 18,000 5.3 21,600 6.3 504 1,290 2,0807 9 12 28 1.3 1.7 2.3 10,800 3.2 18,000 5.3 21,600 6.3 504 1,290 2,0809 9 12 30 1.6 1.6 2.1 10,800 3.2 18,000 5.3 21,600 6.3 504 1,290 2,080
Combination(kBtu/h) Each capacity(kW)
Total Capacity (kW)Cooling
Min Rated MaxInput(W)
Unit-A Unit-B Unit-C Total Unit-A Unit-B Unit-C Btu/h kW Btu/h kW Btu/h kW Min Rated Max
Operation
Note :1. Cooling Capacity is based on : indoor temp.27CDB, 19CWB
; outdoor temp. 35CDB, 24CWB2. Heating Capacity is based on : indoor temp.20CDB, 15CWB
; outdoor temp. 7CDB, 6CWB3. Maximum total capacity index of connected indoor units is 30 kBtu/h. 4. At least two indoor units should be connected to outdoor unit.5. Total capacity of indoor units connected should be minimum 40% of outdoor unit rated capacity.
Heat Pump 50Hz/R410A _ 11
1. Multiple piping type MULTI F
Part 2 Product data_Outdoor units
Note :1. Cooling Capacity is based on : indoor temp.27CDB, 19CWB
; outdoor temp. 35CDB, 24CWB2. Heating Capacity is based on : indoor temp.20CDB, 15CWB
; outdoor temp. 7CDB, 6CWB3. Maximum total capacity index of connected indoor units is 30 kBtu/h. 4. At least two indoor units should be connected to outdoor unit.5. Total capacity of indoor units connected should be minimum 40% of outdoor unit rated capacity.
5 - - 5 1.6 - - 4,800 1.4 5,500 1.6 6,325 1.9 180 425 733 7 - - 7 2.5 - - 4,800 1.4 8,400 2.5 9,660 2.8 252 595 1,027 1 Unit 9 - - 9 3.2 - - 6,480 1.9 10,800 3.2 12,420 3.6 324 765 1,320 12 - - 12 4.2 - - 8,640 2.5 14,400 4.2 16,560 4.9 432 1,020 1,760 18 - - 18 6.3 - - 12,960 3.8 21,600 6.3 24,840 7.3 648 1,530 2,640 5 5 - 10 1.8 1.8 - 7,200 2.1 12,000 3.5 13,800 4.0 360 850 1,467 5 7 - 12 1.8 2.5 - 8,640 2.5 14,400 4.2 16,560 4.9 432 1,020 1,760 5 9 - 14 1.8 3.2 - 10,080 3.0 16,800 4.9 19,320 5.7 504 1,190 2,053 5 12 - 17 1.8 4.2 - 12,240 3.6 20,400 6.0 23,460 6.9 612 1,445 2,493 5 18 - 23 1.8 6.3 - 16,560 4.9 27,600 8.1 31,740 9.3 648 1,955 3,373 7 7 - 14 2.5 2.5 - 10,080 3.0 16,800 4.9 19,320 5.7 504 1,190 2,053 2 Unit 7 9 - 16 2.5 3.2 - 11,520 3.4 19,200 5.6 22,080 6.5 576 1,360 2,347 9 9 - 18 3.2 3.2 - 12,960 3.8 21,600 6.3 24,840 7.3 648 1,530 2,640 7 12 - 19 2.3 4.0 - 12,960 3.8 21,600 6.3 24,840 7.3 648 1,530 2,640 9 12 - 21 3.2 4.2 - 12,960 3.8 21,600 6.3 24,840 7.3 648 1,530 2,640 12 12 - 24 3.2 3.2 - 12,960 3.8 21,600 6.3 24,840 7.3 648 1,530 2,640 7 18 - 25 1.8 4.6 - 12,960 3.8 21,600 6.3 24,840 7.3 648 1,530 2,640 9 18 - 27 2.1 4.2 - 12,960 3.8 21,600 6.3 24,840 7.3 648 1,530 2,640 12 18 - 30 2.5 3.8 - 12,960 3.8 21,600 6.3 24,840 7.3 648 1,530 2,640 5 5 5 15 1.8 1.8 1.8 10,800 3.2 18,000 5.3 20,700 6.1 540 1,275 2,200 5 5 7 17 1.8 1.8 2.5 12,240 3.6 20,400 6.0 23,460 6.9 612 1,445 2,493 5 5 9 19 1.7 1.7 3.0 12,960 3.8 21,600 6.3 24,840 7.3 648 1,530 2,640 5 5 12 22 1.4 1.4 3.5 12,960 3.8 21,600 6.3 24,840 7.3 648 1,530 2,640 5 7 7 19 1.7 2.3 2.3 12,960 3.8 21,600 6.3 24,840 7.3 648 1,530 2,640 5 7 9 21 1.5 2.1 2.7 12,960 3.8 21,600 6.3 24,840 7.3 648 1,530 2,640 5 7 12 24 1.3 1.8 3.2 12,960 3.8 21,600 6.3 24,840 7.3 648 1,530 2,640 5 9 9 23 1.4 2.5 2.5 12,960 3.8 21,600 6.3 24,840 7.3 648 1,530 2,640 3 Unit 5 9 12 26 1.2 2.2 2.9 12,960 3.8 21,600 6.3 24,840 7.3 648 1,530 2,640 5 12 12 29 1.1 2.6 2.6 12,960 3.8 21,600 6.3 24,840 7.3 648 1,530 2,640 7 7 7 21 2.1 2.1 2.1 12,960 3.8 21,600 6.3 24,840 7.3 769 1,530 2,640 7 7 9 23 1.9 1.9 2.5 12,960 3.8 21,600 6.3 24,840 7.3 648 1,530 2,640 7 9 9 25 1.8 2.3 2.3 12,960 3.8 21,600 6.3 24,840 7.3 648 1,530 2,640 7 7 12 26 1.7 1.7 2.9 12,960 3.8 21,600 6.3 24,840 7.3 648 1,530 2,640 9 9 9 27 2.1 2.1 2.1 12,960 3.8 21,600 6.3 24,840 7.3 648 1,530 2,640 7 9 12 28 1.6 2.0 2.7 12,960 3.8 21,600 6.3 24,840 7.3 648 1,530 2,640 9 9 12 30 1.9 1.9 2.5 12,960 3.8 21,600 6.3 24,840 7.3 648 1,530 2,640
Combination(kBtu/h) Each capacity(kW)
Total Capacity (kW)Heating
Min Rated MaxInput(W)
Unit-A Unit-B Unit-C Total Unit-A Unit-B Unit-C Btu/h kW Btu/h kW Btu/h kW Min Rated Max
Operation
Heating
1. Multiple piping type MULTI F
12 _ Heat Pump 50Hz/R410A
Part
2 Pro
duct
data_
Outdo
or un
its
Models : A3UW21GFA0 [MU3U21 UE2]Cooling
Note :1. Cooling Capacity is based on : indoor temp.27CDB, 19CWB
; outdoor temp. 35CDB, 24CWB2. Heating Capacity is based on : indoor temp.20CDB, 15CWB
; outdoor temp. 7CDB, 6CWB3. Maximum total capacity index of connected indoor units is 33 kBtu/h. 4. At least two indoor units should be connected to outdoor unit.5. Total capacity of indoor units connected should be minimum 40% of outdoor unit rated capacity.
5 - - 5 1.5 - - 4,800 1.4 5,000 1.5 5,500 1.6 140 376 562 7 - - 7 2.1 - - 6,300 1.8 7,000 2.1 7,700 2.3 140 527 787 1 Unit 9 - - 9 2.6 - - 6,300 1.8 9,000 2.6 9,900 2.9 252 677 1,011 12 - - 12 3.5 - - 7,200 2.1 12,000 3.5 13,200 3.9 336 903 1,349 18 - - 18 5.3 - - 10,800 3.2 18,000 5.3 19,800 5.8 504 1,354 2,023 5 5 - 10 1.5 1.5 - 6,000 1.8 10,000 2.9 11,000 3.2 280 752 1,124 5 7 - 12 1.5 2.1 - 7,200 2.1 12,000 3.5 13,200 3.9 336 903 1,349 5 9 - 14 1.5 2.6 - 8,400 2.5 14,000 4.1 15,400 4.5 392 1,053 1,573 7 7 - 14 2.1 2.1 - 8,400 2.5 14,000 4.1 15,400 4.5 392 1,053 1,573 7 9 - 16 2.1 2.6 - 9,600 2.8 16,000 4.7 17,600 5.2 448 1,204 1,798 5 12 - 17 1.5 3.5 - 10,200 3.0 17,000 5.0 18,700 5.5 476 1,279 1,910 2 Unit 9 9 - 18 2.6 2.6 - 10,800 3.2 18,000 5.3 19,800 5.8 504 1,354 2,023 7 12 - 19 2.1 3.5 - 11,400 3.3 19,000 5.6 20,900 6.1 532 1,430 2,135 9 12 - 21 2.6 3.5 - 12,600 3.7 21,000 6.2 23,100 6.8 588 1,580 2,360 5 18 - 23 1.5 5.3 - 13,800 4.0 21,000 6.2 23,100 6.8 588 1,580 2,360 12 12 - 24 3.4 3.4 - 13,800 4.0 21,000 6.2 23,100 6.8 588 1,580 2,360 7 18 - 25 2.0 5.1 - 14,400 4.2 21,000 6.2 23,100 6.8 588 1,580 2,360 9 18 - 27 2.3 4.7 - 14,400 4.2 21,000 6.2 23,100 6.8 588 1,580 2,360 12 18 - 30 2.8 4.2 - 14,400 4.2 21,000 6.2 23,100 6.8 588 1,580 2,360 5 5 5 15 1.5 1.5 1.5 9,000 2.6 15,000 4.4 18,000 5.3 420 1,129 1,686 5 5 7 17 1.5 1.5 2.1 10,200 3.0 17,000 5.0 20,400 6.0 476 1,279 1,910 5 5 9 19 1.5 1.5 2.6 11,400 3.3 19,000 5.6 22,800 6.7 532 1,430 2,135 5 7 7 19 1.5 2.1 2.1 11,400 3.3 19,000 5.6 22,800 6.7 532 1,430 2,135 5 7 9 21 1.5 2.1 2.6 12,600 3.7 21,000 6.2 25,000 7.3 588 1,580 2,360 7 7 7 21 2.1 2.1 2.1 12,600 3.7 21,000 6.2 25,000 7.3 588 1,580 2,360 5 5 12 22 1.5 1.5 3.5 13,200 3.9 21,000 6.2 25,000 7.3 588 1,580 2,360 7 7 9 23 2.1 2.1 2.6 13,800 4.0 21,000 6.2 25,000 7.3 588 1,580 2,360 5 9 9 23 1.5 2.6 2.6 13,800 4.0 21,000 6.2 25,000 7.3 588 1,580 2,360 5 7 12 24 1.5 2.1 3.5 14,400 4.2 21,000 6.2 25,000 7.3 588 1,580 2,360 7 9 9 25 2.0 2.5 2.5 14,400 4.2 21,000 6.2 25,000 7.3 588 1,580 2,360 3 Unit 5 9 12 26 1.4 2.4 3.2 14,400 4.2 21,000 6.2 25,000 7.3 588 1,580 2,360 7 7 12 26 1.9 1.9 3.2 14,400 4.2 21,000 6.2 25,000 7.3 588 1,580 2,360 9 9 9 27 2.3 2.3 2.3 14,400 4.2 21,000 6.2 25,000 7.3 588 1,580 2,360 7 9 12 28 1.8 2.3 3.0 14,400 4.2 21,000 6.2 25,000 7.3 588 1,580 2,360 5 5 18 28 1.3 1.3 4.5 14,400 4.2 21,000 6.2 25,000 7.3 588 1,580 2,360 5 12 12 29 1.2 2.9 2.9 14,400 4.2 21,000 6.2 25,000 7.3 588 1,580 2,360 5 7 18 30 1.2 1.6 4.2 14,400 4.2 21,000 6.2 25,000 7.3 588 1,580 2,360 9 9 12 30 2.1 2.1 2.8 14,400 4.2 21,000 6.2 25,000 7.3 588 1,580 2,360 7 12 12 31 1.6 2.7 2.7 14,400 4.2 21,000 6.2 25,000 7.3 588 1,580 2,360 5 9 18 32 1.1 2.0 4.0 14,400 4.2 21,000 6.3 25,000 7.3 588 1,580 2,360 7 7 18 32 1.5 1.5 4.0 14,400 4.2 21,000 6.3 25,000 7.3 588 1,580 2,360 9 12 12 33 1.9 2.6 2.6 14,400 4.2 21,000 6.3 25,000 7.3 588 1,580 2,360
Combination(kBtu/h) Each capacity(kW)
Total Capacity (kW)Cooling
Min Rated MaxInput(W)
Unit-A Unit-B Unit-C Total Unit-A Unit-B Unit-C Btu/h kW Btu/h kW Btu/h kW Min Rated Max
Operation
Heat Pump 50Hz/R410A _ 13
1. Multiple piping type MULTI F
Part 2 Product data_Outdoor units
Heating
Note :1. Cooling Capacity is based on : indoor temp.27CDB, 19CWB
; outdoor temp. 35CDB, 24CWB2. Heating Capacity is based on : indoor temp.20CDB, 15CWB
; outdoor temp. 7CDB, 6CWB3. Maximum total capacity index of connected indoor units is 33 kBtu/h. 4. At least two indoor units should be connected to outdoor unit.5. Total capacity of indoor units connected should be minimum 40% of outdoor unit rated capacity.
5 - - 5 1.6 - - 5,000 1.5 5,500 1.6 6,050 1.8 210 407 648 7 - - 7 2.3 - - 7,560 2.2 8,000 2.3 8,800 2.6 210 570 907 1 Unit 9 - - 9 2.9 - - 7,560 2.2 10,000 2.9 10,900 3.2 378 733 1,166 12 - - 12 3.9 - - 7,920 2.3 13,200 3.9 14,500 4.2 504 977 1,554 18 - - 18 5.8 - - 11,880 3.5 19,800 5.8 21,800 6.4 756 1,466 2,331 5 5 - 10 1.6 1.6 - 6,600 1.9 11,000 3.2 12,100 3.5 420 814 1,295 5 7 - 12 1.6 2.5 - 8,340 2.4 13,900 4.1 15,290 4.5 504 977 1,554 5 9 - 14 1.6 2.9 - 9,300 2.7 15,500 4.5 18,500 5.4 588 1,140 1,813 7 7 - 14 2.5 2.5 - 10,080 3.0 16,800 4.9 18,500 5.4 588 1,140 1,813 7 9 - 16 2.5 3.2 - 11,520 3.4 19,200 5.6 21,100 6.2 672 1,303 2,072 5 12 - 17 1.6 3.9 - 11,220 3.3 18,700 5.5 23,700 6.9 714 1,384 2,202 2 Unit 9 9 - 18 3.2 3.2 - 12,960 3.8 21,600 6.3 23,700 6.9 756 1,466 2,331 7 12 - 19 2.5 4.2 - 13,680 4.0 22,800 6.7 25,000 7.3 798 1,547 2,461 9 12 - 21 3.2 4.2 - 15,120 4.4 24,000 7.0 26,500 7.8 882 1,710 2,720 5 18 - 23 1.6 5.8 - 15,180 4.4 24,000 7.0 26,500 7.8 882 1,710 2,720 12 12 - 24 3.9 3.9 - 15,840 4.6 24,000 7.0 26,500 7.8 882 1,710 2,720 7 18 - 25 2.3 5.9 - 16,680 4.9 24,000 7.0 26,500 7.8 882 1,710 2,720 9 18 - 27 2.8 5.6 - 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720 12 18 - 30 3.4 5.1 - 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720 5 5 5 15 1.6 1.6 1.6 9,900 2.9 16,500 4.8 18,150 5.3 630 1,221 1,943 5 5 7 17 1.6 1.6 2.5 11,640 3.4 19,400 5.7 21,340 6.3 714 1,384 2,202 5 5 9 19 1.6 1.6 2.9 12,600 3.7 21,000 6.2 23,100 6.8 798 1,547 2,461 5 7 7 19 1.6 2.5 2.3 13,140 3.9 21,900 6.4 24,090 7.1 798 1,547 2,461 5 7 9 21 1.6 2.5 2.9 14,340 4.2 24,000 7.0 26,500 7.8 882 1,710 2,720 7 7 7 21 2.5 2.5 2.5 15,120 4.4 24,000 7.0 26,500 7.8 882 1,710 2,720 5 5 12 22 1.6 1.6 3.9 14,520 4.3 24,000 7.0 26,500 7.8 882 1,710 2,720 7 7 9 23 2.5 2.5 3.2 16,560 4.9 24,000 7.0 26,500 7.8 882 1,710 2,720 5 9 9 23 1.6 2.9 2.9 15,300 4.5 24,000 7.0 26,500 7.8 882 1,710 2,720 5 7 12 24 1.8 2.5 4.2 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720 7 9 9 25 2.4 3.0 3.0 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720 3 Unit 5 9 12 26 1.6 2.9 3.9 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720 7 7 12 26 2.3 2.3 3.9 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720 9 9 9 27 2.8 2.8 2.8 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720 7 9 12 28 2.1 2.7 3.6 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720 5 5 18 28 1.5 1.5 5.4 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720 5 12 12 29 1.5 3.5 3.5 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720 5 7 18 30 1.4 2.0 5.1 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720 9 9 12 30 2.5 2.5 3.4 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720 7 12 12 31 1.9 3.3 3.3 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720 5 9 18 32 1.3 2.4 4.7 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720 7 7 18 32 1.8 1.8 4.7 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720 9 12 12 33 2.3 3.1 3.1 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720
Combination(kBtu/h) Each capacity(kW)
Total Capacity (kW)Heating
Min Rated MaxInput(W)
Unit-A Unit-B Unit-C Total Unit-A Unit-B Unit-C Btu/h kW Btu/h kW Btu/h kW Min Rated Max
Operation
1. Multiple piping type MULTI F
14 _ Heat Pump 50Hz/R410A
Part
2 Pro
duct
data_
Outdo
or un
its
5 - - - 5 1.5 - - - 4,500 1.3 5,000 1.5 5,500 1.6 444 740 1,029 7 - - - 7 2.1 - - - 6,300 1.8 7,000 2.1 7,700 2.3 444 740 1,029 1 UNIT 9 - - - 9 2.6 - - - 6,300 1.8 9,000 2.6 9,900 2.9 540 900 1,167 12 - - - 12 3.5 - - - 7,200 2.1 12,000 3.5 13,200 3.9 660 1,100 1,294 18 - - - 18 5.3 - - - 10,800 3.2 18,000 5.3 19,800 5.8 1,020 1,700 2,225 24 - - - 24 7.0 - - - 14,400 4.2 24,000 7.0 25,500 7.5 1,470 2,450 3,088 5 5 - - 10 1.5 1.5 - - 6,000 1.8 10,000 2.9 11,000 3.2 396 660 794 5 7 - - 12 1.5 2.1 - - 7,200 2.1 12,000 3.5 13,200 3.9 408 680 843 5 9 - - 14 1.5 2.6 - - 8,400 2.5 14,000 4.1 15,400 4.5 492 820 980 7 7 - - 14 2.1 2.1 - - 8,400 2.5 14,000 4.1 15,400 4.5 492 820 980 7 9 - - 16 2.1 2.6 - - 9,600 2.8 16,000 4.7 17,600 5.2 636 1,060 1,294 5 12 - - 17 1.5 3.5 - - 10,200 3.0 17,000 5.0 18,700 5.5 720 1,200 1,451 9 9 - - 18 2.6 2.6 - - 10,800 3.2 18,000 5.3 19,800 5.8 810 1,350 1,676 7 12 - - 19 2.1 3.5 - - 11,400 3.3 19,000 5.6 20,900 6.1 924 1,540 1,843 9 12 - - 21 2.6 3.5 - - 12,600 3.7 21,000 6.2 23,100 6.8 1,128 1,880 2,441 2 UNIT 5 18 - - 23 1.5 5.3 - - 13,800 4.0 23,000 6.7 23,100 6.8 1,374 2,290 2,854 12 12 - - 24 3.4 3.4 - - 13,800 4.0 23,000 6.7 25,500 7.5 1,374 2,290 2,854 7 18 - - 25 2.0 5.1 - - 14,400 4.2 24,000 7.0 26,500 7.8 1,410 2,350 3,147 9 18 - - 27 2.3 4.7 - - 14,400 4.2 24,000 7.0 27,500 8.1 1,410 2,350 3,147 5 24 - - 29 1.2 5.8 - - 14,400 4.2 24,000 7.0 27,500 8.1 1,410 2,350 3,147 12 18 - - 30 2.8 4.2 - - 14,400 4.2 24,000 7.0 28,800 8.4 1,410 2,350 3,147 7 24 - - 31 1.6 5.4 - - 14,400 4.2 24,000 7.0 29,000 8.5 1,410 2,350 3,147 9 24 - - 33 1.9 5.1 - - 14,400 4.2 24,000 7.0 29,000 8.5 1,410 2,350 3,147 18 18 - - 36 3.5 3.5 - - 14,400 4.2 24,000 7.0 29,000 8.5 1,410 2,350 3,147 12 24 - - 36 2.3 4.7 - - 14,400 4.2 24,000 7.0 29,000 8.5 1,410 2,350 3,147 5 5 5 - 15 1.5 1.5 1.5 - 9,000 2.6 15,000 4.4 18,000 5.3 396 660 1,784 5 5 7 - 17 1.5 1.5 2.1 - 10,200 3.0 17,000 5.0 20,400 6.0 432 720 1,860 5 5 9 - 19 1.5 1.5 2.6 - 11,400 3.3 19,000 5.6 22,800 6.7 570 950 1,294 5 7 7 - 19 1.5 2.1 2.1 - 11,400 3.3 19,000 5.6 22,800 6.7 570 950 1,294 5 7 9 - 21 1.5 2.1 2.6 - 12,600 3.7 21,000 6.2 25,200 7.4 738 1,230 1,588 7 7 7 - 21 2.1 2.1 2.1 - 12,600 3.7 21,000 6.2 25,200 7.4 738 1,230 1,588 5 5 12 - 22 1.5 1.5 3.5 - 13,200 3.9 22,000 6.4 26,400 7.7 828 1,380 1,696 7 7 9 - 23 2.1 2.1 2.6 - 13,800 4.0 23,000 6.7 27,600 8.1 912 1,520 1,814 5 9 9 - 23 1.5 2.6 2.6 - 13,800 4.0 23,000 6.7 27,600 8.1 912 1,520 1,814 5 7 12 - 24 1.5 2.1 3.5 - 14,400 4.2 24,000 7.0 28,800 8.4 990 1,650 1,971 7 9 9 - 25 2.0 2.5 2.5 - 14,400 4.2 24,000 7.0 28,800 8.4 990 1,650 1,971 5 9 12 - 26 1.4 2.4 3.2 - 14,400 4.2 24,000 7.0 28,800 8.4 990 1,650 1,971 7 7 12 - 26 1.9 1.9 3.2 - 14,400 4.2 24,000 7.0 28,800 8.4 990 1,650 1,971 9 9 9 - 27 2.3 2.3 2.3 - 14,400 4.2 24,000 7.0 28,800 8.4 990 1,650 1,971 7 9 12 - 28 1.8 2.3 3.0 - 14,400 4.2 24,000 7.0 28,800 8.4 990 1,650 1,971 3 UNIT 5 5 18 - 28 1.3 1.3 4.5 - 14,400 4.2 24,000 7.0 28,800 8.4 990 1,650 1,971 5 12 12 - 29 1.2 2.9 2.9 - 14,400 4.2 24,000 7.0 28,800 8.4 990 1,650 1,971 5 7 18 - 30 1.2 1.6 4.2 - 14,400 4.2 24,000 7.0 28,800 8.4 990 1,650 1,971 9 9 12 - 30 2.1 2.1 2.8 - 14,400 4.2 24,000 7.0 28,800 8.4 990 1,650 1,971 7 12 12 - 31 1.6 2.7 2.7 - 14,400 4.2 24,000 7.0 28,800 8.4 990 1,650 1,971 5 9 18 - 32 1.1 2.0 4.0 - 14,400 4.2 24,000 7.0 28,800 8.4 990 1,650 1,971 7 7 18 - 32 1.5 1.5 4.0 - 14,400 4.2 24,000 7.0 28,800 8.4 990 1,650 1,971 9 12 12 - 33 1.9 2.6 2.6 - 14,400 4.2 24,000 7.0 28,800 8.4 990 1,650 1,971 7 9 18 - 34 1.4 1.9 3.7 - 14,400 4.2 24,000 7.0 28,800 8.4 990 1,650 1,971 5 5 24 - 34 1.0 1.0 5.0 - 14,400 4.2 24,000 7.0 28,800 8.4 990 1,650 1,971 5 12 18 - 35 1.0 2.4 3.6 - 14,400 4.2 24,000 7.0 28,800 8.4 990 1,650 1,971 5 7 24 - 36 1.0 1.4 4.7 - 14,400 4.2 24,000 7.0 28,800 8.4 990 1,650 1,971 12 12 12 - 36 2.3 2.3 2.3 - 14,400 4.2 24,000 7.0 28,800 8.4 990 1,650 1,971 9 9 18 - 36 1.8 1.8 3.5 - 14,400 4.2 24,000 7.0 28,800 8.4 990 1,650 1,971 7 12 18 - 37 1.3 2.3 3.4 - 14,400 4.2 24,000 7.0 28,800 8.4 990 1,650 1,971 5 9 24 - 38 0.9 1.7 4.4 - 14,400 4.2 24,000 7.0 28,800 8.4 990 1,650 1,971 7 7 24 - 38 1.3 1.3 4.4 - 14,400 4.2 24,000 7.0 28,800 8.4 990 1,650 1,971 9 12 18 - 39 1.6 2.2 3.2 - 14,400 4.2 24,000 7.0 28,800 8.4 990 1,650 1,971
Models : A4UW24GFA0 [MU4M25 U42]
CoolingCombination
(kBtu/h) Each capacity(kW)Total Capacity (kW)
Cooling
Min Rated MaxInput(W)
Unit-A Unit-B Unit-C Unit-D Total Unit-A Unit-B Unit-C Unit-D Btu/h kW Btu/h kW Btu/h kW Min Rated Max
Operation
Heat Pump 50Hz/R410A _ 15
1. Multiple piping type MULTI F
Part 2 Product data_Outdoor units
Note :1. Cooling Capacity is based on : indoor temp.27CDB, 19CWB
; outdoor temp. 35CDB, 24CWB2. Heating Capacity is based on : indoor temp.20CDB, 15CWB
; outdoor temp. 7CDB, 6CWB3. Maximum total capacity index of connected indoor units is 39 kBtu/h. 4. At least two indoor units should be connected to outdoor unit.5. Total capacity of indoor units connected should be minimum 40% of outdoor unit rated capacity.
5 5 5 5 20 1.5 1.5 1.5 1.5 12,000 3.5 20,000 5.9 24,000 7.0 852 1,420 1,971 5 5 5 7 22 1.5 1.5 1.5 2.1 13,200 3.9 22,000 6.4 26,400 7.7 924 1,540 2,206 5 5 5 9 24 1.5 1.5 1.5 2.6 14,400 4.2 24,000 7.0 28,500 8.4 990 1,670 2,510 5 5 7 7 24 1.5 1.5 2.1 2.1 14,400 4.2 24,000 7.0 28,500 8.4 990 1,670 2,510 5 5 7 9 26 1.4 1.4 1.9 2.4 14,400 4.2 24,000 7.0 28,500 8.4 990 1,670 2,510 5 7 7 7 26 1.4 1.9 1.9 1.9 14,400 4.2 24,000 7.0 28,500 8.4 990 1,670 2,510 5 5 5 12 27 1.3 1.3 1.3 3.1 14,400 4.2 24,000 7.0 28,500 8.4 990 1,670 2,510 5 5 9 9 28 1.3 1.3 2.3 2.3 14,400 4.2 24,000 7.0 28,500 8.4 990 1,670 2,510 5 7 7 9 28 1.3 1.8 1.8 2.3 14,400 4.2 24,000 7.0 28,500 8.4 990 1,670 2,510 7 7 7 7 28 1.8 1.8 1.8 1.8 14,400 4.2 24,000 7.0 28,500 8.4 990 1,670 2,510 5 5 7 12 29 1.2 1.2 1.7 2.9 14,400 4.2 24,000 7.0 28,500 8.4 990 1,670 2,510 5 7 9 9 30 1.2