Upload
phammien
View
242
Download
2
Embed Size (px)
Citation preview
P A C K A G E D E L E C T R I C / E L E C T R I C
LCHEnergence® Rooftop Units
60 HZBulletin No. 210541
December 2017 Supersedes May 2017
MODEL NUMBER IDENTIFICATION
3 to 6 TonsNet Cooling Capacity - 34,800 to 72,000 Btuh
Optional Electric Heat - 7.5 to 30 kW
L C H 060 H 4 E N 1 YBrand/Family
L = Energence®
Unit Type C = Packaged Electric Cooling w/ optional Electric Heat
Major Design Sequence H = 1st Generation
Nominal Cooling Capacity - Tons 036 = 3 Tons 048 = 4 Tons 060 = 5 Tons 072 = 6 Tons 074 = 6 Tons
Cooling Efficiency H = High Efficiency
S = Standard Efficiency
Refrigerant Type 4 = R-410A
Blower Type E = Direct Drive (ECM) T = Belt Drive (2 Speed) B = Belt Drive (1 Speed)
Factory Installed Electric Heat N = No Heat C = 7.5 kW Electric Heat E = 15 kW Electric Heat G = 22.5 kW Electric Heat J = 30 kW Electric Heat
Minor Design Sequence 1 = 1st Revision 2 = 2nd Revision 3 = 3rd Revision
Voltage P = 208/230V-1 phase-60hz Y = 208/230V-3 phase-60hz G = 460V-3 phase-60hz J = 575V-3 phase-60hz
ASHRAE 90.1COMPLIANT
P R O D U C T S P E C I F I C AT I O N S
LCH 3-6 TON ROOFTOP UNITS
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 2
• ECM Blower And Condenser Fan Motors - Direct drive units features ECM blower and condenser fan motors to allow energy efficient MSAV® (multi-stage air volume) operation during all operating conditions. Blower setpoints can be easily set in the field through the Prodigy 2.0 Unit Controller reducing setup time.
• Two-Stage Scroll Compressor - All 3 to 5 ton and 6 ton 074 models feature a two-stage scroll compressor which allows Energence rooftop units to deliver just the necessary amount of cooling needed to meet the space’s demand. Single speed scroll compressor is furnished on 6 ton 072 models.
• Lennox’ Environ™ Coil System - Smaller, lighter condenser coil.• Hinged Access Panels - Provide quick access to components and protect panels and roof from damage during
servicing.• Isolated Compressor Compartment - Allows performance check during normal compressor operation without
disrupting airflow.• Corrosion-Resistant Removable, Reversible Drain Pan - Provides application flexibility, durability and improved
serviceability.• Thermostatic Expansion Valves - Provide peak cooling performance across the entire application range.• Humiditrol® Dehumidification System Option - Patented system allows for independent control of temperature
and humidity, providing enhanced comfort control.• MERV 13 Filters - Available as factory or field option, provide an enhanced level of indoor air quality, and can help
the building qualify for additional LEED credits.• Foil-Faced Insulation - Insulation on all internal surfaces that have contact with airflow helps minimize airborne
fibers and improve IAQ.• Common Components - Many maintenance items are standard throughout the entire product line, reducing the
need to carry different parts to the job or maintain in inventory.
Prodigy® Control SystemStandard on every Energence rooftop unit, the Prodigy® 2.0 unit controller is the center of the Prodigy Control System. The intuitive user interface makes setup, troubleshooting and service easier than ever. Each unit tracks the runtime of every major component and records the date and time when service or maintenance is performed.
SmartWire™ SystemThe SmartWire system simplifies field sensor or thermostat installation through advanced connectors that are keyed and color-coded to help prevent miswiring. Not only is the wire coloring scheme standardized across all models, each connection is intuitively labeled to make troubleshooting and servicing quick and easy.
FEATURES AND BENEFITS
APPROVALSAHRI Certified to AHRI Standard 210/240-2008 (3 thru 5 ton models) and AHRI Standard 340/360-2007 (6 ton models).ETL listed.Efficiency rating certified by CSA.Components bonded for grounding to meet safety standards for servicing required by UL, ULC and National and Canadian Electrical Codes.All models are ASHRAE 90.1 compliant.EnErgy Star® certified units are designed to use less energy, help save money on utility bills, and help protect the environment.The EnErgy Star® Partner of the Year Award signifies that Lennox has made outstanding contributions to design energy efficient units that will lower energy bills, while meeting industry standards for comfort and indoor air quality. Lennox was the first HVAC manufacturer to win this award and has been a four-time recipient since 2003.ISO 9001 Registered Manufacturing Quality System.
A
Lennox’ Energence® packaged rooftop unit product line was created to save energy with intelligence by offering some of the highest energy efficiency ratings available with a powerful, easy to use unit controller. This makes Energence rooftop units perfect for business owners looking for an HVAC product with the lowest total cost of ownership. Energence rooftop units feature:
B
C D
E
F
G
H
I
J
K
L
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 3
FEATURES AND BENEFITS
APPROVALSAHRI Certified to AHRI Standard 210/240-2008 (3 thru 5 ton models) and AHRI Standard 340/360-2007 (6 ton models).ETL listed.Efficiency rating certified by CSA.Components bonded for grounding to meet safety standards for servicing required by UL, ULC and National and Canadian Electrical Codes.All models are ASHRAE 90.1 compliant.EnErgy Star® certified units are designed to use less energy, help save money on utility bills, and help protect the environment.The EnErgy Star® Partner of the Year Award signifies that Lennox has made outstanding contributions to design energy efficient units that will lower energy bills, while meeting industry standards for comfort and indoor air quality. Lennox was the first HVAC manufacturer to win this award and has been a four-time recipient since 2003.ISO 9001 Registered Manufacturing Quality System.
A
Dealer Design AwardLennox has received the Dealer Design Award from an independent panel of dealer-contractors selected by Air Conditioning, Heating & Refrigeration News (”The News”) magazine. Their decision is based on ”best in categories” of installation, maintenance and service as well as quality and performance.
WARRANTYLimited five years on compressors.Limited three years on the Lennox’ Environ™ Coil System.Limited three years on Prodigy® 2.0 Unit Controller.Limited five years Optional High Performance Economizers.Limited one year all other covered components.
COOLING SYSTEMDesigned to maximize sensible and latent cooling performance at design conditions.System can operate from 0°F to 125°F without any additional controls.
R-410A RefrigerantNon-chlorine based, ozone friendly, R-410A.
Copeland Scroll Ultra Tech™ Two-Stage Compressor (3 to 5 Ton and 6 Ton 074 Models)Scroll compressors on all models for high performance, reliability and quiet operation. Two-stage scroll compressors are furnished on 3 to 5 ton and 6 ton 074 models for increased part load efficiency. Single speed scroll furnished on 6 ton 072 models.Resiliently mounted on rubber grommets for quiet operation.
Compressor Crankcase HeaterProtects against refrigerant migration that can occur during low ambient operation.
Thermal Expansion ValveAssures optimal performance throughout the application range.Removable element head.
Filter/DrierHigh capacity filter/drier protects the system from dirt and moisture.
High Pressure SwitchProtects the compressor from overload conditions such as dirty condenser coils, blocked refrigerant flow, or loss of outdoor fan operation.
Low Pressure SwitchProtects the compressor from low pressure conditions such as low refrigerant charge, or low/no airflow.
FreezestatProtects the evaporator coil from damaging ice build-up due to conditions such as low/no airflow, or low refrigerant charge.
B
C
CONTENTSAccessory Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . .57Blower Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31Cooling Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56Electrical/Electric Heat Data . . . . . . . . . . . . . . . . . . . . . . . .44Electric Heat Capacities . . . . . . . . . . . . . . . . . . . . . . . . . .52Features And Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Humiditrol® Dehumidification System Ratings . . . . . . . . . . . . . . .29Model Number Identification . . . . . . . . . . . . . . . . . . . . . . . . 1Optional Conventional Temperature Control Systems . . . . . . . . . . .53Options / Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . .15Outdoor Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . .55Prodigy® Control System . . . . . . . . . . . . . . . . . . . . . . . . . . 7Sequence Of Operation. . . . . . . . . . . . . . . . . . . . . . . . . . .22Specifications - Belt Drive. . . . . . . . . . . . . . . . . . . . . . . . . .21Specifications - Direct Drive. . . . . . . . . . . . . . . . . . . . . . . . .20Sunsource® Commercial Energy System . . . . . . . . . . . . . . . . . .12Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52Weight Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 4
COOLING SYSTEM (continued)Lennox’ Environ™ Coil System Condenser coil features lightweight, all aluminum brazed fin construction.Constructed of three components: a flat extrusion tube, fins in-between the flat extrusion tube and two refrigerant manifolds.Environ™ Coil System Features:• Improved heat transfer
performance due to high primary surface area (flat tubes) versus secondary surface (fins).
• Smaller internal volume (reduced refrigerant charge).
• High durability (all aluminum construction).
• Fewer brazed joints.• Compact design (reduces unit
weight).• Easy maintenance/cleaning.Face-split design.Mounting brackets with rubber inserts secure coil to unit providing vibration dampening and corrosion protection.
Evaporator CoilCopper tube construction, enhanced rippled-edge aluminum fins, flared shoulder tubing connections, silver soldered construction for improved heat transfer. Factory leak tested. Cross row circuiting with rifled tubing optimizes both sensible and latent cooling capacity.
D
Condensate Drain PanPlastic pan, sloped to meet drainage requirements of ASHRAE 62.1.Side or bottom drain connections.Reversible to allow connection at back of unit.
Variable Speed Outdoor Coil Fan MotorVariable speed (ECM) fan motor for energy efficient MSAV® (multi-stage air volume) operation and quiet operation.Thermal overload protected, totally enclosed, permanently lubricated ball bearings, shaft up, wire basket mount.
Outdoor Coil FanPVC coated fan guard furnished.
Required Selections
Cooling CapacitySpecify nominal cooling capacity of the unit.
Cooling Efficiency (3 to 5 Ton models only)Specify either standard or high efficiency.
E
Options/Accessories
Factory InstalledConventional Fin/Tube Condenser Coil (replaces Environ Coil System)Copper tube construction, enhanced rippled-edge aluminum fins, flared shoulder tubing connections, silver soldered construction.NOTE - Required if Humiditrol® Dehumidification System is ordered.
Service ValvesFully serviceable brass valves installed in discharge & liquid lines.Not available for units equipped with Environ Coil System or Humiditrol option.
Factory or Field InstalledCondensate Drain TrapField installed only, may be factory enclosed to ship with unit.Available in copper or PVC.
Drain Pan Overflow SwitchMonitors condensate level in drain pan, shuts down unit if drain becomes clogged.
FEATURES AND BENEFITS
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 5
CABINETConstructionHeavy-gauge steel panels and full perimeter heavy-gauge galvanized steel base rail provides structural integrity for transportation, handling, and installation.Base rails have rigging holes.Three sides of the base rail have forklift slots.Raised edges around duct and power entry openings in the bottom of the unit provide additional protection against water entering the building.
Airflow ChoiceUnits are shipped in downflow (vertical) configuration, can be field converted to horizontal airflow configuration without any optional kits.
Duct FlangesProvided for horizontal duct attachment.
Power EntryElectrical lines can be brought through the unit base or through horizontal access knock-outs
Exterior PanelsConstructed of heavy-gauge, galvanized steel with a two-layer enamel paint finish.
InsulationAll panels adjacent to conditioned air are fully insulated with non-hygroscopic fiberglass insulation.Unit base is fully insulated. The insulation also serves as an air seal to the roof curb, eliminating the need to add a seal during installation.
F
Access PanelsHinged tool-less access panels are provided for the economizer/filter section, and compressor/controls section.All hinged panels have seals and quarter-turn latching handles to provide a tight air and water seal.NOTE - Optional Economizers, Power Exhaust, Outdoor Air Dampers and Barometric Relief Dampers for 060/072/074 models include a filler panel for proper cabinet fit.
Required Selections
Airflow ConfigurationSpecify horizontal or downflow.
Options/Accessories
Factory InstalledCorrosion ProtectionA completely flexible immersed coating with an electrodeposited dry film process. (AST ElectroFin E-Coat) Meets Mil Spec MIL-P-53084, ASTM B117 Standard Method Salt Spray Testing.Indoor Corrosion Protection: - Coated coil - Coated reheat coil (Humiditrol) - Painted blower housing - Painted baseOutdoor Corrosion Protection: - Coated coil - Painted base
Field InstalledCombination Coil/Hail GuardsHeavy gauge steel frame painted to match cabinet with expanded metal mesh to protect the outdoor coil from damage.
G BLOWERA wide selection of supply air blower options are available to meet a variety of airflow requirements.
Blower Motor ChoiceOverload protected, equipped with ball bearings.Variable-speed ECM direct drive motors are offered on 036, 048 and 060 models.Belt drive motors with two-speed capability (low static/high static) are available on 036, 048, 060 and 074 models in several different sizes to maximize air performance.Single speed belt drive motors are available in different sizes to meet static requirements on 072 models.
Supply Air BlowerForward curved blades, blower wheel is statically and dynamically balanced.All belt drive motors have adjustable pulley for speed change.
Ordering InformationSpecify motor horsepower and drive kit number when base unit is ordered.
Required SelectionsOrder one drive kit, see Drive Kit Specifications Table.
Options/Accessories
Factory InstalledBlower Belt Auto TensionerProvides proper tension to belt drive blower belt without the need for regular adjustments. Maintains airflow and proper performance.
H
FEATURES AND BENEFITS
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 6
FEATURES AND BENEFITS
ELECTRICALSmartWire™ SystemAdvanced wiring connectors are keyed and color-coded to prevent miswiring. Wire coloring scheme is standardized across all models. Each connection is intuitively labeled to make troubleshooting and servicing quick and easy.
Electrical PlugsPositive connection electrical plugs are used to connect common accessories or maintenance parts for easy removal or installation.
Required Selections
Voltage ChoiceSpecify when ordering base unit.
Options/Accessories
Factory InstalledCircuit BreakersHACR type. For overload and short circuit protection. Factory wired and mounted in the power entry panel. Current sensitive and temperature activated. Manual reset.
Phase/Voltage Detection (3 Phase models only)Phase detection monitors power supply to assure phase is correct at unit start-up. If phase is incorrect, the unit will not start and an alarm code is reported to the unit controller. Protects unit from being started with incorrect phasing which could lead to issues such as compressors running backwards.Voltage detection monitors power supply voltage to assure proper voltage. If voltage is not correct (over/under voltage conditions) the unit will not start and an alarm code is reported to the unit controller.
SCR (Silicon Controlled Rectifier) Electric Heat ControlThe SCR Electric Heat Control modulates small, precise increments of power to the electric heat load eliminating temperature fluctuations associated with mechanical controls.
Almost instantaneous operation with no moving parts.Zero-Cross (fast cycling) feature improves electric heater life with less contraction and expansion of the heating elements.The SCR operates when there is no call for heat from the building control system or thermostat. SCR air tempering is controlled by a secondary thermostat and remote duct sensor (ordered separately). A call for heat overrides the SCR and modulates the SCR to 100% heat output. A call for cooling or dehumidification (for Humiditrol® equipped units) also overrides the SCR.Available for all voltages and electric heat sizes.NOTE - Blower Proving Switch is required and must be ordered separately for factory installation. See Controls in the Options/Accessories table. NOTE - Available for use with conventional thermostat controls or Novar® control systems only.
Factory or Field InstalledDisconnect SwitchAccessible from outside of unit, spring loaded weatherproof cover furnished.
Electric HeatHelix wound nichrome elements, individual element limit controls, wiring harness. Unit fuse block is furnished as standard. See Options / Accessories tables for ordering information.
GFI Service Outlets (2)115V ground fault circuit interrupter (GFCI) type, non-powered, field-wired.
Field InstalledGFI Weatherproof CoverSingle-gang cover.Heavy-duty UV-resistant polycarbonate case construction.Hinged base cover with gasket.
I
INDOOR AIR QUALITYAir FiltersDisposable 2 inch filters furnished as standard.
Options/Accessories
Factory or Field InstalledHealthy Climate® High Efficiency Air FiltersDisposable MERV 8 or MERV 13 (Minimum Efficiency Reporting Value based on ASHRAE 52.2) efficiency 2-inch pleated filters.
Healthy Climate® UVC Germicidal Lamps
Helps eliminate mold and bacterial growth on the evaporator and drain pans. Improves indoor air quality and maintains efficiency of system by reducing fouling of evaporator coil.
Indoor Air Quality (CO2) SensorsMonitors CO2 levels, reports to the Prodigy® 2.0 Unit Controller which adjusts economizer dampers as needed.
J
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 7
PRODIGY 2.0 UNIT CONTROLLER
The Prodigy 2.0 unit controller is a microprocessor-based controller that provides flexible control of all unit functions.
Features:LCD Display - Easy to read menu with buttons for menu navigation.during setup and diagnostics. 4 lines x 20 character display.Menu LEDs - Four LEDs (Data, Setup, Service, Settings) aid in menu navigation.Main Menu and Help Buttons - Quick navigation to home screen and built-in help functions.Scroll, Value Adjustment Select and Save ButtonsSimplified Setup Procedure - SETUP menu insures proper installation and setup of the rooftop unit.Profile Setup - Copy key settings between units with the same configuration greatly reducing setup time.USB Port - Allows a technician to download and transfer unit information to help verify service was performed. USB drive will also allow updating software on the Prodigy Control System to obtain enhanced functionality without the need to change components.Unit Controller SoftwareUnit Self-Test - Unit Controller can perform a rooftop unit self-test to verify individual critical component and system performance. Included is an economizer test function that helps assure the economizer is operating correctly.Time Clock with Run-time Information
Built-In Functions Include:Adjustable Blower On/Off DelayBuilt-in Control Parameter DefaultsCompressor Time-Off Delay
K DDC CompatibleDirty Filter Switch InputDischarge Air Temperature ControlDisplay/Sensor ReadoutEconomizer Control Options - See Economizer / Outdoor Air / Exhaust Options.Fresh Air TemperingExtensive Unit Diagnostics - Over 100 diagnostic and status messages in English.Exhaust Fan Control Modes - Fresh air damper position.Permanent Diagnostic Code StorageField Adjustable Control Parameters - Over 200 different control settings.Indoor Air Quality Input - Demand Control Ventilation readyLow Ambient Controls - Cooling operation down to 0°F.Gas Valve Time Delay Between First and Second StageMinimum Compressor Run TimeNetwork Capable - Can be daisy chained to other units or controls.Night Setback ModeReturn Air Temperature Limit ControlSafety Switch Input - Allows Controller to respond to a external safety switch trip.Service Relay OutputSmoke Alarm Mode - Four choices (unit off, positive pressure, negative pressure, purge).Staging - Up to 2 heat/2 cool (standard Prodigy 2.0 unit controller thermostat input). Up to 3 cool with additional relay. Up to 4 cool with room sensor or network operation.“Strike Three” ProtectionGas Reheat Control - Simultaneous heating and cooling operation for controlling humidity for process air applications such as supermarkets.
On Demand Dehumidification - Monitors and controls condenser hot gas reheat operation with Humiditrol® option.Thermostat Bounce DelayWarm Up Mode DelayLED IndicatorsPC Interface - Connect to the Prodigy 2.0 unit controller from a PC with the Lennox Unit Controller Software.Room Sensor Operation - Controls temperature.Options/Accessories
Factory or Field InstalledBlower Proving SwitchMonitors blower operation, shuts down unit if blower fails.Dirty Filter SwitchSenses static pressure increase indicating dirty filter condition.
Control Options
Factory InstalledSmartAirflow™ System (Available for 3, 4, and 5 Ton High Efficiency Models Equipped With a Direct Drive Blower and Economizer)Complete airflow management system that precisely controls the economizer damper for accurate ventilation. Allows the installer to directly enter the design-specified supply air (blower) and outdoor air volume (economizer minimum position) parameters without the need to manually take measurements and adjust settings. Also monitors supply air volume and outside air volume as well as customizable diagnostics.
Factory or Field InstalledFresh Air TemperingUsed in applications with high outside air requirements. The Controller energizes the first stage heat as needed to maintain a minimum supply air temperature for comfort, regardless of the thermostat demand. When ordered as a factory option, the sensor ships with the unit but must be field installed.
PRODIGY® CONTROL SYSTEM
NOTE - Prodigy Control System features shown vary with the type of rooftop unit the control is installed in.NOTE - See separate Prodigy Control System Product Specifications Bulletin for additional information.
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 8
Controls Options (continued)Smoke DetectorPhotoelectric type, installed in supply air section, return air section or both sections. Available with power board and single sensor (supply or return) or power board and two sensors (supply and return). Power board located in unit control compartment.
Interoperability via BACnet® or LonTalk® ProtocolsCommunication compatible with third-party automation systems that support the BACnet Application Specific Controller device profile, LonMark® Space Comfort Controller functional profile, or LonMark Discharge Air Controller functional profile.
Commercial Control SystemsL Connection® Network Control SystemComplete building automation control system for single or multi-zone applications. Options include local interface, software for local or remote communication, and hardware for networking other control functions. See L Connection Network Control System Product Specifications Bulletin for details.
Aftermarket DDCNovar® ETM modules and options.
ThermostatsControl system and thermostat options. Aftermarket unit controller options.
Field InstalledGeneral Purpose Control KitPlug-in control provides additional analog and digital inputs/outputs for field installed options.
Humidity Sensor KitHumidity sensor required with factory installed Humiditrol® dehumidification option or Supermarket reheat field selectable option.
OPTIONS / ACCESSORIES
ECONOMIZER OPTIONSEconomizer operation is set and controlled by the Prodigy 2.0 Unit Controller.Simple plug-in connections from economizer to unit controller for easy installation.All Energence rooftop units are equipped with factory installed CEC Title 24 approved sensors for outside, return and discharge air temperature monitoring.Optional sensors may be used instead of unit sensors to determine whether outdoor air is suitable for free cooling. See Options/Accessories table.
Factory or Field InstalledEconomizer (Standard and High Performance Common Features)Outdoor Air Hood is furnished.Factory installed Economizer can be ordered with three exhaust options:• Barometric Relief Dampers
and Exhaust Hood.• Power Exhaust Fan (includes
Exhaust Hood). NOTE - See Power Exhaust Fan section for additional requirements.
• No Exhaust.Field installed Economizer includes Barometric Relief Dampers with Exhaust Hood.Barometric Relief Dampers allow relief of excess air, aluminum blade dampers prevent blow back and outdoor air infiltration during off cycle, bird screen furnished. Hood is furnished.Required when Economizer is factory installed with field installed Power Exhaust Fan option. Required (less exhaust hood) when Economizer is factory installed with factory installed Power Exhaust Fan optionDemand Control Ventilation (DCV) ready using optional CO2 sensors.Horizontal Economizer Conversion kit is available for field installation.
L Standard Economizer Features (Not for Title 24)Gear-driven action, return air and outdoor air dampers, plug-in connections to unit, neoprene blade edge seals, 24-volt, fully-modulating spring return motor.NOTE: The Free Cooling default setting for outdoor air temperature sensor is 55°F.
High Performance Economizer Features Approved for California Title 24 building standards.
Low leakage dampers are Air Movement and Control Association International (AMCA) Class 1A Certified - Maximum 3 CFM per sq. ft. leakage at 1 in. w.g.
ASHRAE 90.1 compliant.
Gear-driven action, high torque 24-volt fully-modulating spring return damper motor, return air and outdoor air dampers, plug-in connections to unit, nylon bearings, enhanced neoprene blade edge seals and flexible stainless steel jamb seals to minimize air leakage.NOTE - High Performance Economizers are not approved for use with enthalpy controls in Title 24 applications.NOTE - The Free Cooling setpoint for Title 24 applications must be set based on the Climate Zone where the system is installed. See Section 140.4 “Prescriptive Requirements for Space Conditioning Systems” of the California Energy Commission’s 2013 Building Energy Efficiency Standards.Refer to Installation Instructions for complete setup information.
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 9
OPTIONS / ACCESSORIES
ECONOMIZER OPTIONS (continued)Differential Sensible ControlFactory setting. Uses outdoor air and return air sensors that are furnished with the unit. The Prodigy 2.0 Unit Controller compares outdoor air temperature and return air and using setpoints, enables the economizer when the outdoor air temperature is below the configured setpoint and cooler than return air.NOTE - Differential Sensible Control can be configured in the field to provide Offset Differential Sensible Control or Single Sensible Control.In Offset Differential Sensible Control mode, the economizer is enabled if the temperature differential (offset) between outdoor air and return air reaches the configured setpoint. In Single Sensible Control mode, the economizer is enabled when outdoor air temperature falls below the configured setpoint.
Global ControlThe unit controller communicates with a DDC system with one global sensor (enthalpy or sensible) to determine whether outside air is suitable for free cooling on all units connected to the control system. Sensor must be field provided.NOTE - Global control with enthalpy is not approved for Title 24 applications.
Factory or Field InstalledSingle Enthalpy Temperature Control (Not for Title 24)Outdoor air enthalpy sensor enables Economizer if the outdoor enthalpy is less than the setpoint of the control.
Differential Enthalpy Control (Not for Title 24)Order two Single Enthalpy Controls. One is field installed in the return air section, the other in the outdoor air section. Allows the economizer control to select between outdoor air or return air, whichever has lower enthalpy.
Field InstalledOutdoor Air CFM ControlMaintains constant outdoor air volume levels on the supply air fan and varying unit airflows. Using information from a velocity sensor located in the rooftop unit outdoor air section, the Prodigy® 2.0 unit controller changes the economizer position to help minimize the effect of supply fan speed changes on outdoor air volume levels. Setpoint for outdoor air volume is established by field testing.
NOTE - Not available with Demand Control Ventilation (CO2 Sensor) or Building Pressure Control.
Building Pressure ControlMaintains constant building pressure level.Using information from a differential pressure between the outdoor air and the building air, the Prodigy® 2.0 unit controller changes the economizer position to help maintain a constant building pressure.
NOTE - Not available with Demand Control Ventilation (CO2 Sensor) or Outdoor Air CFM Control.
Horizontal Economizer Conversion KitInsulated panel covers the bottom return air opening on the unit base to convert downflow economizer to horizontal air flow.
EXHAUST OPTIONS
Factory or Field InstalledPower Exhaust FanInstalls internal to unit for downflow applications with economizer option. Provides exhaust air pressure relief. Interlocked to run when supply air blower is operating, fan runs when outdoor air dampers are 50% open (adjustable), motor is overload protected.Fan is 16 in. diameter with 4 fan blades and a 1/3 hp motor.NOTE - If Power Exhaust is field installed with a factory installed Economizer, the Economizer must be ordered with No Exhaust option and Barometric Relief Dampers and Exhaust Hood must also be ordered separately for field installation.NOTE - If Power Exhaust is factory installed with a factory installed Economizer, the Barometric Relief Dampers without Exhaust Hood must also be ordered separately for field installation.
OUTDOOR AIR OPTIONS
Factory or Field InstalledOutdoor Air Dampers - Downflow or Horizontal Single blade damper, 0 to 25% (fixed) outdoor air adjustable, installs in unit. Automatic model features fully modulating spring return damper motor with plug-in connection. Manual model features a slide damper. Maximum mixed air temperature in cooling mode: 100°F.Outdoor Air Hood is furnished.
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 10
ROOF CURBSNailer strip furnished, mates to unit, US National Roofing Contractors Approved, shipped knocked down.
Hybrid Roof Curbs, DownflowRoof curb can be assembled using interlocking tabs to fasten corners together. No tools required.Curb can also be fastened together with furnished hardware.Available in 8, 14, 18, and 24 inch heights.See Options/Accessories table.
Adjustable Pitch CurbFully adjustable pitch curb provides a level platform for rooftop units allowing flexible installations on roofs with uneven or sloped angles.Maximum slope is 3/4 in. per foot in any direction.Uses interlocking tabs to fasten corners together. No tools required.Hardware is furnished to connect upper curb with lower curb.Available in 14 inch height.
Adaptor Curbs (not shown)Curbs are regionally sourced. Dimensions will vary based upon the source. Contact your local sales representative for a detailed cut sheet with applicable dimensions.
OPTIONS / ACCESSORIES
CEILING DIFFUSERSCeiling Diffusers (Flush or Step-Down)Diffuser face and grilles with white powder coat finish, insulated (UL listed duct liner), diffuser box with collars for duct connection, fixed blades (flush diffusers) and double deflection blades (step-down diffusers), provisions for suspending, internally sealed (prevents recirculation), removable return air grille, adapts to T-bar ceiling grids or plaster ceilings.
Transitions (Supply and Return)Used with diffusers, installs in roof curb, galvanized steel construction, flanges furnished for duct connection to diffusers, fully insulated.
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 11
OPTIONS / ACCESSORIES
HUMIDITROL DEHUMIDIFICATION® SYSTEM
NOTE - Not available with Environ Coil System. Conventional Fin/Tube condenser coil must be ordered as a factory option.Factory installed option designed to control humidity.Provides dehumidification on demand using ASHRAE 90.1 recommended method for comfort conditioning humidity control.Unit comes equipped with one row reheat coil, solenoid valve and humidity controller.In addition to a thermostat or room sensor used for conventional operation, a humidity sensor is required and must be located in the occupied space. Remote Mounted Humidity Sensor Kit is required for field installation.The humidity sensor provides input to the Unit Controller which is used to control activation of the dehumidification operation.Reheat controls are located in the compressor control section of the unit for easy access.
BenefitsImproves indoor air quality.Helps prevents damage due to
high humidity levels.Improves comfort levels by reducing space humidity levels.
OPERATIONNo Dehumidification DemandThe unit will operate conventionally whenever there is a demand for cooling or heating and no dehumidification demand.Free cooling is only permitted when there is no demand for dehumidification.
Dehumidification Demand OnlyThe Unit Controller is factory set at 60% relative humidity setpoint and can be adjusted at the Unit Controller or with optional Unit Controller Software.For L Connection® Network Control Panel (NCP) applications, the humidity setpoint can be adjusted at the NCP.Reheat operation will initiate on a dehumidification demand and does not require a cooling demand.The unit will operate in the dehumidification mode until the relative humidity of the conditioned space is below the setpoint.The reheat coil is sized to provide
68°F to 75°F supply air during reheat operation.This reduces sensible cooling capacity and extends compressor run time to control humidity when the cooling load is low.A solenoid valve diverts hot gas from the compressor to the reheat coil.The cooled and dehumidified air from the evaporator is reheated as it passes through the reheat coil.The de-superheated and partially condensed refrigerant continues to the outdoor condenser coil where condensing is completed. The unit will continue to operate in this mode until the dehumidification demand is satisfied.See Sequence of Operation for additional information.
Dehumidification and Cooling Demand (Thermostat/Room Sensor Application)Two-stage compressor models (036, 048, 060, 074)If both a dehumidification and a Y1 cooling demand occur, the system will operate in the full cooling mode at first stage indoor air flow. If a Y2 cooling demand occurs along with a dehumidification demand, the system operates in full cooling mode at full cooling airflow until the Y2 cooling demand is satisfied. Then the system will revert to the dehumidification mode if a dehumidification mode demand is present.
Single speed compressor model (072H)If both a dehumidification and a cooling demand occur, the system will operate in cooling until the cooling demand is satisfied. Then the system will energize thedehumidification mode.
Options/AccessoriesHumidity Sensor Kit Remote Mounted Humidity sensor required with factory installed Humiditrol® Option or Supermarket reheat field selectable option.
TYPICAL DEHUMIDIFICATION SCHEMATIC
REHEATCOIL
EVAPORATORCOIL
SOLENOID VALVE
RETURNAIR
CONDENSERCOIL
OUTDOORAIR
COMPRESSORSUPPLYAIR
CHECK VALVEEXPANSION
VALVE
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 12
SUNSOURCE® COMMERCIAL ENERGY SYSTEM
SYSTEM OVERVIEWAll Energence® 3 through 6 ton commercial rooftop units are upgradable to the SunSource® Commercial Energy System.Solar energy is first used to meet building cooling/heating demands. When the cooling and heating system is not operating, the system powers lighting, appliances and other electronic devices in the building. And in some locations, any surplus power is sent back to the utility company for a possible credit (check with your local utility company for availability).The SunSource® Commercial Energy System consists of the following components:1. Energence® 3 to 6 ton commercial rooftop units
with factory installed Solar Power Entry Option (circuit protection for solar power and line voltage wiring).
2. Solarworld Solar Modules (up to 24 modules with three-phase power, up to 16 modules with single-phase power) may be used to vary the amount of electricity generated).
3. Enphase Microinverter, converts Direct Current to Alternating Current power.
4. Enphase Envoy Communications Gateway that monitors energy usage.
5. Enphase Enlighten™ Performance Monitoring Website
Wiring from the roof mounted solar modules is routed to the rooftop unit.NOTE - Refer to separate Product Specifications Bulletin for the SunSource® Commercial Energy System for more detailed information. See section Solar - Kits/Accessories.Also refer to SunSource® Commercial Energy System Applications and Design Guidelines Manual (Corp. 1303-L1) for complete information on designing, sizing and installing a complete system.
APPROVALSSunSource® Commercial Energy System is listed by ETL to UL 1995 and can be installed to comply with the NEC.The SunSource® Energy System for Commercial Rooftop Units meets the requirements for federal tax credits listed under the U.S. Emergency Economic Stabilization Act of 2008, covering 30% of the cost of the solar modules, including installation.
BASIC SYSTEM REQUIREMENTSSufficient south-facing open roof space.Broadband Internet connection.240V single-phase, 208V three-phase, or 460V three-phase. NOTE: Transformers must be ordered for voltages other
than 240V single-phase or 208V three-phase WYE.
Grid Interconnection Agreement.
SOLAR POWER ENTRY OPTIONA factory installed power entry option is available for Energence® rooftop units that provides a connection point for SunSource® solar modules.The option provides circuit protection (fuses) for the solar connection and rooftop unit components.An externally accessible disconnect (non-fused) is also included to shutdown the system for service. Field wiring connections are made directly to the disconnect for the utility connection and to pigtails for easy solar connection.Local codes may require a field provided solar disconnect and/or a field provided fused HVAC disconnect.
LEN
OX
N
LEN
OX
N
LEN
OX
N
LEN
OX
N
LEN
OX
N
LEN
OX
N
™
™
BC
D
F
E
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 13
SUNSOURCE® COMMERCIAL ENERGY SYSTEM
SOLAR MODULESCaptures solar energy to convert into AC power through the Enphase Microinverter.
Laminated solar module structure consists of the solar glass, two ethylene vinyl acetate (EVA) sheets, the solar cell matrix and a back sheet.Thick low-iron safety glass withstands extreme weather conditions and heavy snow loads.Solar modules are ETL/Intertek listed for the US and Canada to UL Standard 1703 and meet National and Canadian Electrical Code requirements.
Solar Module FrameClear anodized aluminum frame with cast aluminum corner keys.Low profile with extended flange.Compatible with “top-down” and “bottom-up” mounting methods.Eight grounding locations (Four corners of the frame and four locations along the length of the module in the extended flange).Extended cable lengths for easier installation.
ENPHASE MICROINVERTER
Converts Direct Current (DC), captured by a solar module, to Alternating Current (AC) power. Each solar module is paired with one Enphase Microinverter. Installed beneath each solar module on the roof.Enphase Microinverters operate independently from each other allowing solar modules that are not shaded or dirty to operate with optimum performance.Supports low-light and low-voltage operation.
FLAT ROOF MOUNTING SYSTEMPanelClaw® Polar Bear III roof mounting system is designed to maximize array construction speed.
Innovative system consists of three major components (Support, Ballast Tray and Claw).Modular, adaptable design with single module tilt-up feature to facilitate access to roof, wiring and maintenance.10 degree nominal tilt angle.Fully ballasted or mechanically attached.• Support - Galvanized steel tubing. (1) Support
unit with pre-installed integrated recycled rubber pads and mounting hardware.
• Ballast Tray - Angled fit with locking end-tab to fully capture ballast blocks. Hemmed edges and chamfered corners prevent wiring from coming into contact with sharp edges. Ballast blocks are field provided.
• Claw - Attachment to module using standard module mounting holes. UL 2703 certified for electric bonding and grounding. G90 galvanized steel.
ENPHASE ENGAGE CABLE SYSTEM• Enphase Engage Cable - Enphase Engage Cable
(shown with connector) is a 12 AWG cable with pre-installed connectors that plug into the Enphase Microinverter.
• Four wire cable (240V single-phase)• Five wire cable (208V three-phase)• Enphase Engage Cable Terminator - Each Enphase
Engage Cable is terminated at a junction or combiner box. The opposite end of the cable must be terminated with an Enphase Engage Cable Terminator cap.
• Enphase Engage Disconnect Tool - Specialized tool that disconnects ble from an Enphase Microinverter or watertight sealing cap.
• Enphase Water-tight Sealing Cap - Use when open connections on the Enphase Engage Cable are not mated to an Enphase Microinverter.
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 14
SUNSOURCE® COMMERCIAL ENERGY SYSTEM
SYSTEM MONITORINGEnphase Envoy Communications Gateway (with Wireless Capability)The Enphase Envoy Communications Gateway monitors Enphase Microinverter (on solar modules) performance and can be connected to a broadband internet connection to send data to the Enphase Enlighten™ web site for online monitoring. The Enphase Envoy Communications Gateway is not required, but must be used if system performance monitoring is desired.Limited system monitoring is also available locally with the Envoy and a personal computer if no internet connection is available.Various Event Messages are also available when monitoring the system via a personal computer locally.Connection options include:• Wireless N USB adaptor (802.11b/g/n)• Ethernet RJ45 (cable included)NEMA 1 indoor enclosure.Contents - (1) Envoy Communications Gateway, (1) Wireless N USB adaptor (1) 6 ft. power cord, (1) 10 ft. orange Ethernet RJ45 cable.CSA (US/C) listed.
Line Communications FilterEnvoy Communications Gateway mounted in a
weatherproof NEMA 4 enclosure.For outdoor installations, installations with transformers, or when multiple communications modules are used on one
building.Contains the Enphase Envoy Communications Gateway and terminal blocks for easy power hookup from the Enphase Microinverter branch circuits distribution to the electrical meter or distribution panel. A filter removes any electrical interference from other devices or multiple Envoy Communication Gateways in the same building.Unit is UL listed for the US and Canada and meet National Electrical Code requirements.
Enphase Enlighten™ Performance Monitoring WebsitePowered by the Enphase Envoy Communications Gateway, the Enphase Enlighten™ Performance Monitoring website allows the user to keep track of building energy usage and see environmental benefits in real time.See demos, view reference
installations and other additional information at: http://enlighten.enphaseenergy.com/
SYSTEM ORDERING• Specify the number of Solar Module CE (Custom
Engineered) Kits required. The system will be shipped as a complete package.
Each kit includes:• One Solarworld Solar Module• One Enphase Microinverter• One Enphase Engage Cable (no. of connectors
are determined by total number of Solar Module Kits ordered)
• One PanelClaw® Polar Bear Mounting System for the Solar Module
• Hardware for mounting• Custom engineering drawings and full design for
solar system• Energence® 3 to 6 ton packaged rooftop unit must
be ordered with the factory installed Solar Power Entry Option.
• Enphase Envoy Communications Gateway or Line Communications Filter must be ordered separately.
• Transformers must be ordered separately. See Options/Accessories table.
Contact your nearest Lennox Sales Representative for ordering information.
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 15
OPTIONS / ACCESSORIES
Item Model Number
Catalog Number
Unit Model Number036 048 060 072 074
COOLING SYSTEM
Condensate Drain Trap PVC - C1TRAP20AD2 76W26 OX OX OX OX OXCopper - C1TRAP10AD2 76W27 OX OX OX OX OX
Conventional Fin/Tube Condenser Coil (replaces Environ Coil System) Factory O O O O ODrain Pan Overflow Switch E1SNSR71AD1 68W88 OX OX OX OX OXEfficiency Standard Factory O O O
High Factory O O O O OService valves (not for Environ™ Coil System or Humiditrol equipped units) Factory O O O O O
BLOWER - SUPPLY AIR
Motors Direct Drive - 0.50 hp Factory ODirect Drive - 0.75 hp Factory O
Direct Drive - 1 hp Factory OBelt Drive - .75 hp (2 Speed) Factory O O
Belt Drive - 1 hp (2 Speed) Factory O O OBelt Drive - 2 hp (2 Speed) Factory O O O
Belt Drive - 1 hp Standard Efficiency Factory OBelt Drive - 2 hp Standard Efficiency Factory O
Drive Kits See Blower Data Tables for selection
Kit A01 - T1DRKT001-1 - 673-1010 rpm Factory OKit A02 - T1DRKT002-1 - 745-1117 rpm Factory OKit A03 - T1DRKT003-1 - 833-1250 rpm Factory OKit A05 - T1DRKT005-1 - 897-1346 rpm Factory O
Kit A06 - T1DRKT006-1 - 1071-1429 rpm Factory OKit A07 - T1DRKT007-1 - 1212-1548 rpm Factory O
Kit AA01 - T1DRKT001AP1 - 522-784 rpm Factory O OKit AA02 - T1DRKT002AP1 - 632-875 rpm Factory O O
Kit AA03 - T1DRKT003AP1 - 798-1105 rpm Factory O OBlower Belt Auto-Tensioner Factory O O O O O
CABINET
Combination Coil/Hail Guards C1GARD51A-1 13R98 X XC1GARD51AT1 13T03 X X X
Corrosion Protection (indoor coil / outdoor coil) Factory O O O O ONOTE - Catalog and model numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 16
OPTIONS / ACCESSORIES
Item Model Number
Catalog Number
Unit Model Number036 048 060 072 074
CONTROLS
Blower Proving Switch C1SNSR35FF1 53W65 OX OX OX OX OXCommercial Controls CPC Einstein Integration Factory O O O O O
Prodigy® Control System - BACnet® Module - C0CTRL60AE1L 59W51 OX OX OX OX OXProdigy® Control System - LonTalk® Module - C0CTRL65FF1 54W27 OX OX OX OX OX
Novar® 2051 - E0CTRL30A1 64W72 OX OX OX OX OXNovar® LSE Factory O O O O O
L Connection® Building Automation System - - - X X X X XDirty Filter Switch E1SNSR55AP1 53W66 OX OX OX OX OXGeneral Purpose Control Kit E1GPBK30C1 13J78 X X X X XFresh Air Tempering C1SNSR75AD1 58W63 OX OX OX OX OX1 SmartAirflow™ System (Supply and Ventilation Airflow Control) Factory O O OSmoke Detector - Supply or Return (Power board and one sensor)
C1SNSR44AP1 53W78 OX OX OX OX OX
Smoke Detector - Supply and Return (Power board and two sensors)
C1SNSR43AP1 53W79 OX OX OX OX OX
ELECTRICAL
Voltage 208/230V - 1 phase Factory 2 O 2 O 2 O60 hz 208/230V - 3 phase Factory O O O O O
460V - 3 phase Factory O O O O O575V - 3 phase Factory O O O O O
HACR Circuit Breakers Factory O O O O ODisconnect Switch (See Electrical / Electric Heat Tables for selection)
80 amp - T2DISC080AH1 20W21 OX OX150 amp - T2DISC150AH1 20W22 OX
80 amp T2DISC080NH1 20W24 OX OX OX150 amp - T2DISC150NH1 20W25 OX OX OX
GFI Service Outlets
15 amp non-powered, field-wired (208/230V, 460V only) LTAGFIK10/15 74M70 OX OX OX OX OX20 amp non-powered, field-wired (575V only) C1GFCI20FF1 67E01 OX OX OX OX OX
Weatherproof Cover for GFI C1GFCI99FF1 10C89 X X X X XPhase/Voltage Detection - 3 Phase Models Only Factory O O O O O1 Available for 3, 4 and 5 ton high efficiency models equipped with direct drive blower and Economizer.2 208/230-1ph not available on belt drive units.NOTE - Catalog and model numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 17
OPTIONS / ACCESSORIES
Item Model Number
Catalog Number
Unit Model Number036 048 060 072 074
ELECTRIC HEAT
7.5 kW 208/230V-1ph - E1EH0075AN1P 46W28 OX OX OX
208/230V-3ph - E1EH0075AN1Y 46W31 OX OX OX OX OX460V-3ph - E1EH0075AN1G 46W35 OX OX OX OX OX575V-3ph - E1EH0075AN1J 46W39 OX OX OX OX OX
15 kW 208/230V-1ph - E1EH0150AN1P 46W29 OX OX OX
208/230V-3ph - E1EH0150AN1Y 46W32 OX OX OX OX OX460V-3ph - E1EH0150AN1G 46W36 OX OX OX OX OX575V-3ph - E1EH0150AN1J 46W40 OX OX OX OX OX
22.5 kW 208/230V-1ph - E1EH0225N1P 46W30 OX
208/230V-3ph - E1EH0225N1Y 46W33 OX OX OX460V-3ph - E1EH0225N1G 46W37 OX OX OX575V-3ph - E1EH0225N1J 46W41 OX OX OX
30 kW 208/230V-3ph - E1EH0300N-1Y 46W34 OX OX460V-3ph - E1EH0300N-1G 46W38 OX OX575V-3ph - E1EH0300N-1J 46W42 OX OX
SCR (Silicon Controlled Rectifier) Electric Heat ControlThermostat (required)Duct Sensor (required)
Factory O O O O O45N59 X X X X X45N60 X X X X X
ECONOMIZER
Standard Economizer With Outdoor Air Hood (Sensible Control) (Not for Title 24)Standard Economizer - Includes Barometric Relief Dampers and Exhaust Hood
E1ECON30A-2- 90W59 OX OX OX OX OX
Standard Economizer - Includes Barometric Relief Dampers and Exhaust Hood and Power Exhaust
Factory O O O O O
Standard Economizer - No Exhaust Option Factory O O O O OHigh Performance Economizer With Outdoor Air Hood (Sensible Control) (Approved for California Title 24 Building Standards / AMCA Class 1A Certified)High Performance Economizer - Includes Barometric Relief Dampers and Exhaust Hood
E1ECON17A-1 10U54 OX OX OX OX OX
Economizer AccessoriesHorizontal Economizer Conversion Kit T1HECK00AN1 17W45 X X X X XEconomizer ControlsDifferential Enthalpy (Not for Title 24) Order 2 - C1SNSR64FF1 53W64 OX OX OX OX OXSensible Control Sensor is Furnished Factory O O O O OSingle Enthalpy (Not for Title 24) C1SNSR64FF1 53W64 OX OX OX OX OXGlobal Control Sensor Field Provided Factory O O O O OBuilding Pressure Control E1GPBK20C1 13J77 X X X X XOutdoor Air CFM Control E1GPBK10C1 13J76 X X X X X
OUTDOOR AIR
Outdoor Air Dampers With Outdoor Air HoodMotorized C1DAMP21A-1 15D17 OX OX OX OX OXManual C1DAMP11A-2 15D18 OX OX OX OX OXNOTE - Catalog and model numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 18
OPTIONS / ACCESSORIES
Item Model Number
Catalog Number
Unit Model Number036 048 060 072 074
POWER EXHAUST FAN (DOWNFLOW ONLY)
Standard StaticNote: Factory installed Power Exhaust Fan includes Exhaust Hood. Barometric Relief Dampers without Exhaust Hood are required (order separately).Note: Field installed Power Exhaust Fans do not include Exhaust Hood. Barometric Relief Dampers with Exhaust Hood are required (order separately).
208/230V-1 or 3ph - C1PWRE10A-1P 79W87 OX OX OX OX OX460V-3ph - C1PWRE10A-1G 79W88 OX OX OX OX OX575V-3ph - C1PWRE10A-1J 79W89 OX OX OX OX OX
BAROMETRIC RELIEF1 Barometric Relief Dampers with Exhaust Hood C1DAMP50A-1- 74W38 X X X X X2 Barometric Relief Dampers without Exhaust Hood C1DAMP50A-2- 72W89 X X X X X
HUMIDITROL® CONDENSER REHEAT OPTION
Humiditrol (NOTE - Not available with Environ Coil System. Conventional Fin/Tube condenser coil must be ordered as a factory option)
Factory O O O O O
Humidity Sensor Kit, Remote mounted (required) C0SNSR31AE-1 17M50 X X X X X
INDOOR AIR QUALITY
Air FiltersHealthy Climate® High Efficiency Air FiltersOrder 4 per unit
MERV 8 (16 x 20 x 2 in.) - C1FLTR15A-1- 54W20 OX OXMERV 13 (16 x 20 x 2 in.) - T1FLTR40A-1- 52W37 OX OXMERV 8 (20 x 20 x 2 in.) - C1FLTR15D-1- 54W21 OX OX OX
MERV 13 (20 x 20 x 2 in.) - C1FLTR40D-1- 52W39 OX OX OXReplaceable Media Filter With Metal Mesh
16 x 20 x 2 in. (Order 4) - K1FLTR30A-1 39W09 X X
Frame (includes non-pleated filter media)
20 x 20 x 2 in. (Order 4) - K1FLTR30A-2 44N60 X X X
Replaceable Media Filter With Metal Mesh
16 x 20 x 2 in. (Order 4) - K1FLTR30A-1 39W09 X X
Frame (includes non-pleated filter media)
20 x 20 x 2 in. (Order 4) - K1FLTR30A-2 44N60 X X X
Indoor Air Quality (CO2) SensorsSensor - Wall-mount, off-white plastic cover with LCD display C0SNSR50AE1L 77N39 X X X X XSensor - Wall-mount, off-white plastic cover, no display C0SNSR52AE1L 87N53 X X X X XSensor - Black plastic case with LCD display, rated for plenum mounting
C0SNSR51AE1L 87N52 X X X X X
Sensor - Wall-mount, black plastic case, no display, rated for plenum mounting
C0MISC19AE1 87N54 X X X X X
CO2 Sensor Duct Mounting Kit - for downflow applications C0MISC19AE1- 85L43 X X X X XAspiration Box - for duct mounting non-plenum rated CO2 sensors (87N53 or 77N39)
C0MISC16AE1- 90N43 X X X X X
UVC Germicidal Lamps3 Healthy Climate® UVC Light Kit (208/230V-1ph) C1UVCL10AN1- 50W90 OX OX OX OX OX1 Required when Economizer is factory installed (no exhaust option) with field installed Power Exhaust Fan option.2 Required when Economizer is factory installed with factory installed Power Exhaust Fan option.3 Lamps operate on 110-230V single-phase power supply. Step-down transformer may be ordered separately for 460V and 575V units. Alternately, 110V power supply may be used to directly power the UVC ballast(s)
NOTE - Catalog and model numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 19
OPTIONS / ACCESSORIES
Item Model Number
Catalog Number
Unit Model Number036 048 060 072 074
ROOF CURBS
Hybrid Roof Curbs, Downflow8 in. height C1CURB70A-1 11F50 X X X X X14 in. height C1CURB71A-1 11F51 X X X X X18 in. height C1CURB72A-1 11F52 X X X X X24 in. height C1CURB73A-1 11F53 X X X X XTransition CurbMatches Energence® 036-074 Units to existing L Series® Curbs E1CURB60A-1 20W06 X X X X X
CEILING DIFFUSERS
Step-Down - Order one RTD9-65S 13K60 X X XRTD11-95S 13K61 X X
Flush - Order one FD9-65S 13K55 X X XFD11-95S 13K56 X X
Transitions (Supply and Return) - Order one T1TRAN10AN1 17W53 X X XT1TRAN20N-1 17W54 X X
Sunsource® Commercial Energy System
Solar Module CE Kit
One 285W Solar Module (silver frame), One PanelClaw Polar Bear III Mounting System and One Enphase M250 Microinverter
10U67 X X X X X
Solar Power Entry with Disconnect Factory O O O O OEnphase Envoy Communications Gateway with Communications Booster (internal) 13L89 X X X X XLine Communication Filter (external) C1C400D11A 10F93 X X X X XTransformer (6 kW) E1TRFM15AD3Y (208Y to 208 VAC Delta) 11H71 X X X X X
E1TRFM15AD2Y (230 VAC Delta) 11H28 X X X X XE1TRFM15AD3G (460 VAC Delta or Wye) 11H29 X X X X X
NOTE - Catalog and model numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 20
SPECIFICATIONS - DIRECT DRIVEGeneral Data Nominal Tonnage 3 Ton 4 Ton 5 Ton
Model Number LCH036H4E LCH048H4E LCH060H4E
Efficiency Type High High High
Blower Type Multi-Speed Direct Drive
Multi-Speed Direct Drive
Multi-Speed Direct Drive
Cooling Performance
Gross Cooling Capacity - Btuh 36,600 50,100 61,6001 Net Cooling Capacity - Btuh 36,000 49,000 60,000
AHRI Rated Air Flow - cfm 1200 1600 1750
Total Unit Power - kW 2.8 3.8 4.71 SEER (Btuh/Watt) - 208/230V-1-3ph 18.0 17.6 17.1
1 SEER (Btuh/Watt) - 460V-3ph, 575V-3ph 17.0 17.0 17.01 EER (Btuh/Watt) - 208/230V-1-3ph 12.8 12.8 12.7
1 EER (Btuh/Watt) - 460V-3ph, 575V-3ph 12.5 12.8 12.7
Refrigerant Type R-410A R-410A R-410A
Refrigerant Charge
Environ™ Coil System 4 lbs. 5 oz. 5 lbs. 4 oz. 7 lbs. 2 oz.
Conventional Fin/Tube Coil 8 lbs. 8 oz. 11 lbs. 2 oz. 14 lbs. 0 oz.
Conventional Fin/Tube With Humiditrol® Option 9 lbs. 3 oz. 12 lbs. 4 oz. 16 lbs. 0 oz.
Electric Heat Available - See Page 17 7.5 and 15 kW 7.5 and 15 kW 7.5, 15 and 22.5 kW
Compressor Type (one per unit) Two-Stage Scroll Two-Stage Scroll Two-Stage Scroll
Outdoor Coil Environ (Fin/Tube)
Net face area (total) - sq. ft. 11.70 (15.60) 14.50 (15.60) 17.80 (19.30)
Tube diameter - in. 0.71 (3/8) 0.71 (3/8) 0.71 (3/8)
Number of rows 1 (1.5) 1 (2) 1 (2)
Fins per inch 20 (20) 20 (20) 20 (20)
Outdoor Coil Fans
Motor - (No.) horsepower (1) 1/3 (ECM) (1) 1/3 (ECM) (1) 1/3 (ECM)
Motor rpm 715-810 645-810 930-1100
Total Motor Input - watts 112-160 89-165 230-350
Diameter - (No.) in. (1) 24 (1) 24 (1) 24
Number of blades 3 3 3
Total air volume - cfm 3400-3795 2910-3675 4315-4980
Indoor Coil
Net face area (total) - sq. ft. 7.78 7.78 9.72
Tube diameter - in. 3/8 3/8 3/8
Number of rows 3 4 4
Fins per inch 14 14 14
Drain connection (Number) and size - in. (1) 1 NPT (1) 1 NPT (1) 1 NPT
Expansion device type Balanced Port Thermostatic Expansion Valve, removable power head3 Indoor
BlowerNominal motor HP 0.50 (ECM) 0.75 (ECM) 1 (ECM)
Blower wheel nominal diameter x width - in. (1) 10 X 10 (1) 10 X 10 (1) 11 X 10
Filters Type of filter disposable
Number and size - in. (4) 16 X 20 X 2 (4) 20 x 20 x 2
Electrical characteristics 208/230V - 60 hz - 1 phase 208/230V, 460V, or 575V - 60 hz -3 phase
NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.1 AHRI Certified to AHRI Standard 210/240: 95°F outdoor air temperature and 80°F db/67°F wb entering evaporator air; minimum external duct static pressure.2 Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of
motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate.
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 21
SPECIFICATIONS - BELT DRIVEGeneral Data Nominal Tonnage 3 Ton 4 Ton 5 Ton 6 Ton 6 Ton
Model Number LCH036S4T LCH048S4T LCH060S4T LCH072H4B LCH074H4TEfficiency Type Standard Standard Standard High High
Blower Type Two Speed Belt Drive
Two Speed Belt Drive
Two Speed Belt Drive
Single Speed Belt Drive
Two Speed Belt Drive
Cooling Performance
Gross Cooling Capacity - Btuh 35,800 49,100 61,600 73,500 72,000Net Cooling Capacity - Btuh 1 34,800 1 48,000 1 60,000 2 72,000 2 69,000
AHRI Rated Air Flow - cfm 1200 1600 1750 1920 2100Total Unit Power - kW 3.0 3.9 4.8 6.0 5.7
SEER (Btuh/Watt) 1 15.0 1 15.0 1 15.5 - - - - - -EER (Btuh/Watt) 1 11.6 1 11.6 1 12.3 2 12.0 2 12.0IEER (Btuh/Watt) - - - - - - - - - 2 13.5 2 16.0Refrigerant Type R-410A R-410A R-410A R-410A R-410A
Refrigerant Charge
Environ™ Coil System 4 lbs. 3 oz. 5 lbs. 4 oz. 7 lbs. 3 oz. 7 lbs. 8 oz. 7 lbs. 2 oz.Conventional Fin/Tube Coil 8 lbs. 8 oz. 11 lbs. 2 oz. 14 lbs. 0 oz. 13 lbs. 12 oz. 13 lbs. 11 oz.
Conventional Fin/Tube With Humiditrol® Option
9 lbs. 3 oz. 12 lbs. 4 oz. 16 lbs. 0 oz. 15 lbs. 3 oz. 15 lbs. 11 oz.
Electric Heat Available - See Page 17 7.5 and 15 kW 7.5 and 15 kW 7.5, 15 and 22.5 kW
7.5, 15, 22.5 and 30 kW
7.5, 15, 22.5 and 30 kW
Compressor Type (one per unit) Two-Stage Scroll Two-Stage Scroll Two-Stage Scroll Scroll Two-Stage ScrollOutdoor Coil Environ (Fin/Tube)
Net face area (total) - sq. ft. 11.70 (15.60) 14.5 (15.60) 17.80 (19.30) 17.80 (19.30) 17.80 (19.30)Tube diameter - in. 0.71 (3/8) 0.71 (3/8) 0.71 (3/8) 0.71 (3/8) 0.71 (3/8)
Number of rows 1 (1.5) 1 (2) 1 (2) 1 (2) 1 (2)Fins per inch 20 (20) 20 (20) 20 (20) 20 (20) 20 (20)
Outdoor Coil Fans
Motor - (No.) horsepower (1) 1/6 (PSC) (1) 1/4 (PSC) (1) 1/3 (PSC) (1) 1/3 (PSC) (1) 1/3 (PSC)Motor rpm 825 825 1075 1075 1075
Total Motor Input - watts 168 230 410 410 375Diameter - (No.) in. (1) 24 (1) 24 (1) 24 (1) 24 (1) 24
Number of blades 3 3 3 3 3Total air volume - cfm 3000 3300 4800 4800 4800
Indoor Coil
Net face area (total) - sq. ft. 7.78 7.78 9.72 9.72 9.72Tube diameter - in. 3/8 3/8 3/8 3/8 3/8
Number of rows 3 4 4 4 4Fins per inch 14 14 14 14 14
Drain connection (Number) and size - in. (1) 1 NPT (1) 1 NPT (1) 1 NPT (1) 1 NPT (1) 1 NPTExpansion device type Balanced Port Thermostatic Expansion Valve, removable power head
5 Indoor Blower and Drive Selection
No. of Speeds 2 2 2 1 2Nominal motor HP
Low static 0.75 0.75 1 1 1High static 1 2 2 2 2
Maximum usable motor output (US Only)
Low static 0.86 0.86 1.15 1.15 1.15High static 1.15 2.3 2.3 2.3 2.3
Motor - Drive kit number A01 low 449-673
high 673-1010 A05
low 598-897 high 897-1346
A02 low 497-673
high 745-1117 A06
low 714-953 high 1071-1429
A03 low 555-833
high 833-1250 A07
low 808-1032 high 1212-1548
AA01 522 - 784 rpm
AA02 632 - 875 rpm
AA03 798 - 1105 rpm
AA01 522-784 rpm
AA02 632-875 rpm
AA03 798-1105 rpm
Blower wheel nominal diameter x width - in. (1) 10 X 10 (1) 10 X 10 (1) 10 X 10 (1) 15 X 9 (1) 15 X 9Filters Type of filter disposable
Number and size - in. (4) 16 X 20 X 2 (4) 20 X 20 X 2Electrical characteristics 208/230V, 460V, or 575V - 60 hz - 3 phaseNOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.1, 2 AHRI Certified to AHRI Standard 1 210/240 or 2 340/360: 95°F outdoor air temperature and 80°F db/67°F wb entering evaporator air; minimum external duct static
pressure.3 Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of
motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate.
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 22
SEQUENCE OF OPERATION
Objective: Outline the unit functions as a result of room thermostat or zone sensor demands.
Given: When economizer is present, it will function as initial part of the unit cooling system. When not present, unit will function as if outdoor ambient is high and sensed as not suitable.
DIRECT DRIVE AND BELT DRIVE SYSTEM OPERATION (3 THROUGH 5 TONS AND 6 TON 074 MODELS):
Note: Direct drive units feature ECM condenser fans that are staged to match the compressor’s capacity. When the compressor is operating at first stage, the condenser fan is operating at low speed. The condenser fan switches to high speed when the compressor switches to second stage to match operation.
Modulating Outdoor Air Damper:
Damper minimum positions #1 and 2 are adjusted during unit setup to provide minimum fresh air requirements at the indicated supply fan speeds per ASHRAE 62.1.
• Supply fan is off and the outdoor air damper is closed
• Supply fan is on low speed and the outdoor air damper is at minimum position 1
• Supply fan is on high speed and the outdoor air damper is at minimum position 2 1 Unit Features an Economizer and Outdoor Air is Suitable
Cooling - Thermostat or Zone Sensor Mode (Up to 3 stages Y1, Y2, Y3)
Y1 demand:
1st: Compressor is off, supply fan is on low speed, economizer modulates (minimum to maximum open position) to maintain 55°F supply air temperature (default unit controller setting)
2nd: After 5 minutes (default unit controller setting), supply fan switches to high speed. Economizer continues modulating with supply fan on high speed to maintain 55°F supply air temperature
Y2 demand:
1st: Compressor is off, supply fan is on high speed, and economizer modulates to maintain 55°F supply air temperature
2nd: Economizer opens to maximum. If economizer stays at maximum open for 3 minutes (default unit controller setting) compressor is energized and operates at first stage while supply fan stays on high speed
1 Outdoor air suitability is determined by the energy state of outdoor ambient (enthalpy or sensible) and its ability to achieve the desired free cooling effects. Outdoor air suitability can also be determined by a third party controller and provided to the RTU via a network connection.
Y3 demand:
1st: Economizer is at maximum open and compressor operates at first stage. If economizer stays at maximum open for 3 minutes (default unit controller setting) compressor switches to second stage operation while supply fan stays on high speed
Unit Does not Feature an Economizer (or Outdoor Air Is Not Suitable)
Cooling - Thermostat or Zone Sensor (Up to 2 stages Y1, Y2)
Y1 demand:
1st: Compressor operates at first stage and supply fan operates at low speed Y2 demand:
1st: Compressor operates at second stage and supply fan operates at high speed
(Continued on Next Page)
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 23
SEQUENCE OF OPERATION
DIRECT DRIVE AND BELT DRIVE SYSTEM OPERATION (3 THROUGH 5 TONS AND 6 TON 074 MODELS) (Continued):
Dehumidification Mode (economizer free cooling is locked out):
Unit features the Humiditrol® dehumidification system
No Y1, Y2 demand but a call for dehumidification:
1st: Compressor operates at second stage, supply fan operates at low speed, and the reheat valve is energized
Y1 demand:
1st: Compressor operates at second stage, outdoor fan operates at high speed, supply fan oper-ates at low speed and the reheat valve is de-energized
Y2 demand:
1st: Compressor operates at second stage, supply fan operates at high speed, and the reheat valve is de-energized
Heating mode: Thermostat or Zone Sensor (1 stage W1)
W1 demand:
1st: Electric Heat is energized and the supply fan operates at high speed
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 24
SEQUENCE OF OPERATION
SINGLE STAGE UNIT OPERATION (6 TON 072 MODELS)
Modulating Outdoor Air Damper:
Damper minimum positions are adjusted during unit setup to provide minimum fresh air requirements at the indicated supply fan speeds per ASHRAE 62.1.
1) Supply fan is off and the outdoor air damper is closed
2) Supply fan is on and the outdoor air damper is at minimum position
1 Unit Features an Economizer and Outdoor Air is Suitable
Cooling - Thermostat or Zone Sensor (Up to 2 stages Y1, Y2).
Y1 demand:
1st: Compressor is off, supply fan is on, economizer modulates (minimum to maximum open posi-tion) to maintain 55°F supply air temperature (default unit controller setting)
Y2 demand:
1st: Economizer goes to maximum open position and if the damper stays open for three minutes (default unit controller setting) the compressor is energized.
Unit Does Not Feature an Economizer (or outdoor air is not suitable)
Cooling - Thermostat or Zone Sensor (Up to 1 stage Y1).
Y1 demand:
1st: Compressor is operating and supply fan is on.
Dehumidification Mode (economizer free cooling is locked out):
Unit features the Humiditrol® dehumidification system
No Y1 demand but a call for dehumidification:
1st: Compressor is operating, supply fan is on, and the reheat valve is energized.
Y1 demand:
1st: Compressor is operating, supply fan is on, and the reheat valve is de-energized.
Y2 demand:
1st: Compressor is operating, supply fan is on, and the reheat valve is de-energized.
Heating mode: Thermostat or Zone Sensor (1 stage W1)
W1 demand:
1st: Electric Heat is energized and the supply fan operates at high speed
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 25
COOLING RATINGSNOTE - For Temperatures and Capacities not shown in tables, see bulletin - Cooling Unit Rating Table Correction Factor Data in Miscellaneous Product Data section.
3 TON STANDARD EFFICIENCY LCH036S4 (1ST STAGE)
Entering Wet Bulb
Temper-ature
Total Air
Volume
Outdoor Air Temperature Entering Outdoor Coil65°F 75°F 85°F 95°F
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F640 26.1 1.02 0.68 0.81 0.95 25.2 1.18 0.68 0.82 0.97 24.1 1.36 0.7 0.84 0.99 23 1.57 0.71 0.87 1800 27.6 1.01 0.72 0.88 1 26.6 1.17 0.73 0.91 1 25.4 1.35 0.75 0.93 1 24.2 1.56 0.77 0.96 1960 28.8 1 0.77 0.96 1 27.7 1.16 0.78 0.98 1 26.5 1.34 0.81 1 1 25.3 1.54 0.83 1 1
67°F640 27.7 1.01 0.54 0.65 0.76 26.7 1.17 0.54 0.66 0.78 25.6 1.35 0.55 0.67 0.8 24.3 1.55 0.56 0.69 0.82800 29.2 1 0.56 0.7 0.84 28.1 1.16 0.57 0.71 0.86 26.9 1.34 0.58 0.72 0.89 25.6 1.54 0.59 0.74 0.92960 30.3 0.99 0.59 0.74 0.92 29.2 1.15 0.6 0.76 0.94 27.8 1.33 0.61 0.78 0.97 26.4 1.53 0.62 0.81 1
71°F640 29.2 1 0.42 0.52 0.63 28.1 1.16 0.42 0.53 0.64 27 1.34 0.42 0.53 0.65 25.7 1.54 0.42 0.55 0.66800 30.8 0.98 0.43 0.55 0.67 29.7 1.14 0.43 0.55 0.68 28.4 1.32 0.43 0.57 0.7 27 1.53 0.44 0.58 0.72960 32.1 0.97 0.44 0.58 0.72 30.8 1.13 0.44 0.59 0.73 29.4 1.31 0.44 0.6 0.75 28 1.51 0.45 0.61 0.78
3 TON HIGH EFFICIENCY LCH036H4 (1ST STAGE)
Entering Wet Bulb
Temper-ature
Total Air
Volume
Outdoor Air Temperature Entering Outdoor Coil65°F 75°F 85°F 95°F
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F640 25.5 1.06 0.69 0.81 0.95 24.6 1.22 0.69 0.83 0.97 23.7 1.41 0.7 0.85 0.99 22.5 1.63 0.72 0.87 1800 27 1.05 0.73 0.88 1 26 1.21 0.74 0.91 1 24.9 1.4 0.76 0.93 1 23.7 1.61 0.78 0.96 1960 28.2 1.03 0.78 0.96 1 27.1 1.2 0.79 0.98 1 26 1.39 0.81 1 1 24.8 1.6 0.84 1 1
67°F640 27.1 1.05 0.55 0.66 0.77 26.1 1.21 0.55 0.67 0.79 25.1 1.4 0.55 0.68 0.81 23.9 1.61 0.57 0.7 0.83800 28.6 1.03 0.57 0.71 0.85 27.6 1.2 0.58 0.72 0.87 26.4 1.38 0.59 0.73 0.89 25.1 1.6 0.6 0.75 0.92960 29.7 1.02 0.6 0.75 0.92 28.6 1.19 0.61 0.77 0.94 27.3 1.37 0.61 0.78 0.97 25.9 1.59 0.64 0.81 1
71°F640 28.6 1.03 0.42 0.53 0.64 27.6 1.2 0.42 0.54 0.65 26.4 1.38 0.43 0.54 0.65 25.2 1.6 0.43 0.55 0.67800 30.2 1.01 0.43 0.56 0.68 29.1 1.18 0.43 0.56 0.69 27.8 1.37 0.44 0.58 0.71 26.5 1.58 0.44 0.59 0.73960 31.4 1 0.45 0.59 0.73 30.3 1.17 0.44 0.6 0.74 28.9 1.35 0.45 0.61 0.76 27.4 1.57 0.45 0.62 0.79
3 TON HIGH EFFICIENCY LCH036H4 (2ND STAGE)
Entering Wet Bulb
Temper-ature
Total Air
Volume
Outdoor Air Temperature Entering Outdoor Coil85°F 95°F 105°F 115°F
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F960 34 2.15 0.71 0.85 0.99 32.4 2.41 0.72 0.87 1 30.8 2.72 0.74 0.9 1 29 3.08 0.76 0.93 1
1200 35.7 2.17 0.77 0.93 1 34.1 2.44 0.78 0.96 1 32.3 2.74 0.81 0.99 1 30.4 3.1 0.83 1 11440 37 2.19 0.82 1 1 35.4 2.45 0.84 1 1 33.8 2.76 0.87 1 1 32 3.12 0.9 1 1
67°F960 35.9 2.17 0.57 0.69 0.82 34.3 2.44 0.57 0.7 0.84 32.5 2.74 0.58 0.72 0.86 30.6 3.1 0.6 0.74 0.9
1200 37.6 2.19 0.6 0.74 0.9 35.8 2.46 0.61 0.76 0.92 34 2.76 0.62 0.78 0.96 31.8 3.11 0.63 0.81 0.991440 38.8 2.21 0.63 0.8 0.97 36.9 2.47 0.64 0.82 1 34.9 2.77 0.66 0.84 1 32.7 3.13 0.67 0.88 1
71°F960 37.7 2.19 0.43 0.55 0.67 36 2.46 0.43 0.56 0.68 34.2 2.76 0.44 0.57 0.7 32.2 3.12 0.44 0.58 0.72
1200 39.6 2.22 0.44 0.58 0.72 37.7 2.48 0.44 0.59 0.74 35.7 2.79 0.46 0.61 0.76 33.6 3.14 0.46 0.62 0.791440 40.9 2.23 0.46 0.62 0.78 38.9 2.49 0.46 0.63 0.8 36.8 2.8 0.47 0.65 0.82 34.5 3.15 0.48 0.67 0.85
3 TON STANDARD EFFICIENCY LCH036S4 (2ND STAGE)
Entering Wet Bulb
Temper-ature
Total Air
Volume
Outdoor Air Temperature Entering Outdoor Coil85°F 95°F 105°F 115°F
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F960 34.1 2.21 0.71 0.85 0.99 32.4 2.48 0.73 0.87 1 30.8 2.79 0.74 0.9 1 28.9 3.15 0.76 0.94 1
1200 35.7 2.23 0.77 0.94 1 34.1 2.5 0.78 0.96 1 32.3 2.82 0.81 0.99 1 30.4 3.18 0.83 1 11440 37 2.25 0.82 1 1 35.5 2.52 0.84 1 1 33.8 2.84 0.87 1 1 31.9 3.2 0.91 1 1
67°F960 35.9 2.24 0.56 0.69 0.82 34.3 2.51 0.57 0.7 0.84 32.5 2.82 0.58 0.72 0.87 30.5 3.18 0.59 0.74 0.9
1200 37.6 2.26 0.6 0.74 0.9 35.8 2.53 0.61 0.76 0.93 33.9 2.84 0.62 0.78 0.96 31.7 3.2 0.63 0.81 11440 38.7 2.27 0.63 0.8 0.98 36.9 2.54 0.63 0.82 1 34.9 2.86 0.66 0.85 1 32.7 3.22 0.67 0.89 1
71°F960 37.8 2.26 0.43 0.55 0.66 36 2.53 0.43 0.56 0.68 34.1 2.84 0.44 0.57 0.7 32.1 3.21 0.44 0.58 0.72
1200 39.5 2.29 0.44 0.58 0.72 37.7 2.56 0.45 0.59 0.74 35.6 2.87 0.45 0.61 0.76 33.5 3.23 0.46 0.63 0.791440 40.9 2.3 0.46 0.62 0.77 38.8 2.57 0.46 0.63 0.8 36.7 2.89 0.47 0.65 0.83 34.3 3.24 0.48 0.67 0.86
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 26
4 TON HIGH EFFICIENCY LCH048H4 (1ST STAGE)
Entering Wet Bulb
Temper-ature
Total Air
Volume
Outdoor Air Temperature Entering Outdoor Coil65°F 75°F 85°F 95°F
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F850 37.1 1.54 0.67 0.79 0.93 35.9 1.78 0.67 0.81 0.95 34.4 2.05 0.69 0.83 0.97 32.7 2.35 0.7 0.85 1
1065 39.2 1.53 0.71 0.87 1 37.8 1.77 0.72 0.89 1 36.2 2.03 0.74 0.91 1 34.4 2.34 0.75 0.94 11280 40.9 1.52 0.76 0.94 1 39.4 1.76 0.77 0.97 1 37.6 2.02 0.79 0.99 1 36 2.32 0.82 1 1
67°F850 39.5 1.53 0.53 0.64 0.75 38.1 1.76 0.54 0.65 0.77 36.6 2.03 0.55 0.66 0.79 34.8 2.34 0.56 0.68 0.81
1065 41.7 1.51 0.56 0.69 0.83 40.1 1.75 0.57 0.7 0.85 38.4 2.02 0.57 0.72 0.88 36.5 2.32 0.58 0.73 0.91280 43.2 1.5 0.58 0.73 0.9 41.7 1.74 0.58 0.75 0.93 39.7 2 0.59 0.77 0.96 37.7 2.31 0.62 0.79 0.99
71°F850 41.9 1.51 0.41 0.51 0.62 40.4 1.75 0.41 0.52 0.62 38.7 2.01 0.42 0.53 0.63 36.9 2.32 0.43 0.54 0.65
1065 44.2 1.49 0.42 0.55 0.67 42.5 1.73 0.42 0.56 0.68 40.6 1.99 0.43 0.56 0.69 38.5 2.3 0.43 0.57 0.71280 45.8 1.48 0.43 0.57 0.71 43.9 1.71 0.42 0.58 0.72 41.9 1.98 0.45 0.58 0.74 39.8 2.28 0.43 0.6 0.77
4 TON HIGH EFFICIENCY LCH048H4 (2ND STAGE)
Entering Wet Bulb
Temper-ature
Total Air
Volume
Outdoor Air Temperature Entering Outdoor Coil85°F 95°F 105°F 115°F
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F1280 47.6 2.92 0.7 0.84 0.99 45.2 3.24 0.71 0.87 1 43 3.62 0.73 0.9 1 40.3 4.06 0.75 0.94 11600 49.9 2.95 0.76 0.94 1 47.4 3.27 0.77 0.96 1 44.9 3.64 0.8 0.99 1 42.3 4.09 0.83 1 11920 51.6 2.97 0.82 1 1 49.6 3.29 0.84 1 1 47.1 3.68 0.87 1 1 44.4 4.12 0.9 1 1
67°F1280 50.4 2.95 0.55 0.67 0.81 48 3.28 0.57 0.7 0.83 45.5 3.66 0.57 0.71 0.86 42.7 4.1 0.59 0.73 0.91600 52.7 2.98 0.59 0.73 0.9 50.1 3.3 0.6 0.75 0.92 47.3 3.68 0.6 0.77 0.96 44.3 4.12 0.62 0.8 11920 54.3 3 0.62 0.79 0.98 51.6 3.32 0.62 0.81 1 48.7 3.7 0.65 0.85 1 45.5 4.14 0.67 0.88 1
71°F1280 53.2 2.98 0.43 0.54 0.65 50.7 3.31 0.42 0.55 0.66 48 3.69 0.43 0.56 0.69 45.1 4.14 0.44 0.58 0.711600 55.6 3.01 0.44 0.58 0.71 52.8 3.33 0.44 0.59 0.73 49.9 3.71 0.44 0.6 0.75 46.8 4.16 0.45 0.62 0.781920 57.2 3.03 0.44 0.6 0.77 54.2 3.35 0.46 0.62 0.8 51.2 3.73 0.46 0.64 0.82 47.9 4.17 0.47 0.66 0.86
COOLING RATINGSNOTE - For Temperatures and Capacities not shown in tables, see bulletin - Cooling Unit Rating Table Correction Factor Data in Miscellaneous Product Data section.
4 TON STANDARD EFFICIENCY LCH048S4 (1ST STAGE)
Entering Wet Bulb
Temper-ature
Total Air
Volume
Outdoor Air Temperature Entering Outdoor Coil65°F 75°F 85°F 95°F
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F850 37.2 1.49 0.65 0.78 0.92 36.1 1.72 0.66 0.8 0.95 34.6 1.98 0.68 0.82 0.97 32.9 2.27 0.69 0.84 1
1065 39.4 1.47 0.7 0.86 1 38 1.7 0.71 0.88 1 36.4 1.96 0.72 0.91 1 34.6 2.26 0.74 0.93 11280 41 1.46 0.74 0.94 1 39.5 1.69 0.76 0.97 1 37.8 1.95 0.78 0.99 1 36.2 2.24 0.81 1 1
67°F850 39.7 1.47 0.52 0.63 0.74 38.2 1.7 0.53 0.64 0.75 36.7 1.96 0.54 0.64 0.77 35 2.25 0.55 0.67 0.8
1065 41.9 1.45 0.55 0.67 0.82 40.3 1.68 0.55 0.69 0.84 38.7 1.94 0.56 0.7 0.87 36.7 2.24 0.57 0.71 0.891280 43.5 1.44 0.57 0.72 0.9 41.9 1.67 0.57 0.74 0.92 39.9 1.93 0.58 0.75 0.95 38 2.23 0.6 0.78 0.99
71°F850 42.1 1.45 0.4 0.5 0.61 40.6 1.68 0.41 0.51 0.61 38.9 1.94 0.41 0.51 0.62 37.1 2.23 0.42 0.53 0.64
1065 44.4 1.43 0.41 0.54 0.65 42.7 1.66 0.42 0.55 0.66 40.9 1.92 0.42 0.55 0.66 38.8 2.22 0.42 0.56 0.691280 46 1.42 0.43 0.56 0.7 44.1 1.65 0.42 0.56 0.71 42.1 1.91 0.44 0.58 0.73 40 2.2 0.42 0.59 0.76
4 TON STANDARD EFFICIENCY LCH048S4 (2ND STAGE)
Entering Wet Bulb
Temper-ature
Total Air
Volume
Outdoor Air Temperature Entering Outdoor Coil85°F 95°F 105°F 115°F
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F1280 47.8 2.83 0.7 0.85 1 45.4 3.15 0.72 0.87 1 43 3.51 0.73 0.91 1 40.3 3.93 0.75 0.94 11600 50 2.86 0.76 0.94 1 47.5 3.17 0.78 0.97 1 44.9 3.54 0.8 1 1 42.5 3.97 0.83 1 11920 51.8 2.88 0.82 1 1 49.7 3.2 0.85 1 1 47.2 3.57 0.87 1 1 44.4 4 0.91 1 1
67°F1280 50.6 2.87 0.55 0.68 0.81 48.2 3.18 0.57 0.7 0.83 45.5 3.55 0.57 0.71 0.87 42.7 3.97 0.59 0.73 0.91600 52.9 2.9 0.59 0.73 0.9 50.1 3.21 0.6 0.75 0.93 47.3 3.57 0.6 0.77 0.97 44.2 4 0.62 0.81 11920 54.5 2.91 0.6 0.79 0.99 51.6 3.23 0.63 0.82 1 48.7 3.59 0.65 0.85 1 45.4 4.02 0.67 0.89 1
71°F1280 53.4 2.9 0.42 0.53 0.65 50.9 3.22 0.42 0.56 0.67 48 3.58 0.43 0.56 0.69 45.1 4.01 0.44 0.58 0.711600 55.8 2.93 0.43 0.58 0.71 52.8 3.24 0.44 0.58 0.73 49.9 3.61 0.44 0.6 0.75 46.7 4.04 0.45 0.62 0.791920 57.3 2.95 0.44 0.6 0.77 54.3 3.26 0.46 0.62 0.8 51.3 3.63 0.45 0.64 0.83 47.8 4.05 0.47 0.66 0.87
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 27
COOLING RATINGSNOTE - For Temperatures and Capacities not shown in tables, see bulletin - Cooling Unit Rating Table Correction Factor Data in Miscellaneous Product Data section.
5 TON HIGH EFFICIENCY LCH060H4 (1ST STAGE)
Entering Wet Bulb
Temper-ature
Total Air
Volume
Outdoor Air Temperature Entering Outdoor Coil65°F 75°F 85°F 95°F
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F1070 47.4 1.82 0.66 0.79 0.92 45.5 2.14 0.67 0.8 0.94 43.5 2.49 0.68 0.82 0.97 41.5 2.87 0.7 0.85 0.991335 50.1 1.81 0.71 0.85 1 48.2 2.13 0.72 0.88 1 46 2.48 0.73 0.91 1 43.7 2.86 0.75 0.93 11600 52.3 1.8 0.75 0.93 1 50 2.13 0.77 0.95 1 47.9 2.48 0.79 0.98 1 45.5 2.86 0.8 1 1
67°F1070 50.4 1.81 0.53 0.64 0.75 48.5 2.13 0.53 0.65 0.76 46.2 2.48 0.53 0.65 0.78 44.2 2.86 0.55 0.67 0.81335 53.3 1.8 0.55 0.68 0.82 51.2 2.13 0.57 0.69 0.84 49 2.48 0.57 0.71 0.86 46.7 2.86 0.58 0.72 0.891600 55.6 1.79 0.58 0.72 0.89 53.2 2.12 0.59 0.73 0.91 50.8 2.48 0.57 0.76 0.94 48.2 2.86 0.61 0.78 0.97
71°F1070 53.6 1.8 0.41 0.51 0.62 51.5 2.12 0.41 0.52 0.62 49.3 2.47 0.41 0.52 0.63 47 2.86 0.42 0.53 0.651335 56.7 1.79 0.42 0.54 0.66 54.4 2.12 0.43 0.55 0.67 51.9 2.47 0.43 0.56 0.68 49.5 2.86 0.43 0.57 0.71600 58.9 1.78 0.43 0.57 0.7 56.5 2.12 0.44 0.58 0.71 53.9 2.47 0.44 0.58 0.72 51.2 2.86 0.45 0.6 0.75
5 TON HIGH EFFICIENCY LCH060H4 (2ND STAGE)
Entering Wet Bulb
Temper-ature
Total Air
Volume
Outdoor Air Temperature Entering Outdoor Coil85°F 95°F 105°F 115°F
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F1600 59.5 3.5 0.69 0.84 0.99 56.9 3.93 0.71 0.86 1 54 4.42 0.73 0.89 1 50.9 4.99 0.75 0.93 12000 62.6 3.54 0.75 0.93 1 59.7 3.96 0.77 0.95 1 56.5 4.45 0.79 0.98 1 53.3 5.02 0.82 1 12400 64.9 3.56 0.8 1 1 62.2 3.99 0.83 1 1 59.4 4.49 0.85 1 1 56.3 5.07 0.9 1 1
67°F1600 63 3.54 0.54 0.67 0.8 60.2 3.97 0.56 0.68 0.82 57.3 4.46 0.57 0.7 0.85 53.9 5.03 0.58 0.72 0.882000 66.4 3.58 0.59 0.73 0.89 63.2 4.01 0.59 0.74 0.92 59.7 4.5 0.6 0.76 0.94 56.4 5.07 0.62 0.79 0.982400 68.4 3.61 0.61 0.78 0.97 65.2 4.03 0.63 0.8 0.99 61.6 4.52 0.64 0.83 1 58 5.09 0.65 0.87 1
71°F1600 66.8 3.59 0.42 0.53 0.64 63.9 4.01 0.42 0.54 0.66 60.8 4.51 0.43 0.56 0.68 57.3 5.08 0.44 0.57 0.72000 70.1 3.63 0.43 0.57 0.7 66.8 4.05 0.44 0.58 0.72 63.2 4.54 0.44 0.58 0.74 59.6 5.12 0.44 0.6 0.762400 72.3 3.65 0.45 0.6 0.76 68.8 4.08 0.45 0.61 0.77 65.2 4.57 0.46 0.63 0.8 61.4 5.14 0.46 0.65 0.84
5 TON STANDARD EFFICIENCY LCH060S4 (1ST STAGE)
Entering Wet Bulb
Temper-ature
Total Air
Volume
Outdoor Air Temperature Entering Outdoor Coil65°F 75°F 85°F 95°F
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F1070 48 1.76 0.66 0.78 0.92 46.1 2.08 0.66 0.8 0.94 44.1 2.42 0.68 0.81 0.96 42.1 2.79 0.69 0.84 0.991335 50.8 1.75 0.7 0.85 1 48.8 2.07 0.71 0.88 1 46.7 2.41 0.73 0.9 1 44.4 2.78 0.74 0.93 11600 53 1.74 0.75 0.93 1 50.8 2.06 0.76 0.95 1 48.6 2.4 0.78 0.97 1 46.1 2.77 0.8 1 1
67°F1070 51.2 1.75 0.53 0.64 0.74 49 2.06 0.53 0.64 0.76 46.9 2.41 0.53 0.65 0.78 45.1 2.78 0.54 0.67 0.791335 54.1 1.73 0.55 0.67 0.81 52 2.06 0.56 0.69 0.83 49.7 2.4 0.57 0.7 0.86 47.4 2.78 0.58 0.72 0.881600 56.4 1.72 0.58 0.72 0.89 54 2.05 0.58 0.73 0.91 51.6 2.39 0.57 0.75 0.93 49 2.77 0.6 0.78 0.97
71°F1070 54.4 1.73 0.41 0.51 0.61 52.3 2.05 0.41 0.51 0.62 50 2.4 0.4 0.51 0.62 47.7 2.77 0.41 0.52 0.641335 57.5 1.72 0.41 0.54 0.65 55.2 2.05 0.42 0.55 0.67 52.7 2.39 0.42 0.55 0.68 50.2 2.77 0.43 0.56 0.691600 59.8 1.71 0.43 0.56 0.69 57.4 2.04 0.43 0.57 0.71 54.6 2.39 0.42 0.57 0.72 51.9 2.76 0.44 0.59 0.75
5 TON STANDARD EFFICIENCY LCH060S4 (2ND STAGE)
Entering Wet Bulb
Temper-ature
Total Air
Volume
Outdoor Air Temperature Entering Outdoor Coil85°F 95°F 105°F 115°F
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F1600 59.5 3.42 0.69 0.84 0.98 56.9 3.84 0.71 0.86 1 54.1 4.33 0.73 0.89 1 51 4.89 0.75 0.92 12000 62.6 3.46 0.75 0.93 1 59.7 3.87 0.77 0.95 1 56.6 4.36 0.78 0.98 1 53.3 4.92 0.82 1 12400 64.9 3.48 0.8 0.99 1 62.1 3.9 0.83 1 1 59.5 4.39 0.85 1 1 56.4 4.97 0.89 1 1
67°F1600 62.9 3.46 0.55 0.67 0.8 60.3 3.88 0.56 0.69 0.82 57.4 4.37 0.57 0.7 0.85 54 4.93 0.58 0.72 0.882000 66.3 3.5 0.59 0.73 0.88 63.3 3.92 0.6 0.74 0.91 60 4.4 0.6 0.76 0.94 56.6 4.97 0.62 0.79 0.982400 68.4 3.52 0.61 0.77 0.96 65.3 3.94 0.63 0.8 0.99 61.8 4.42 0.64 0.82 1 58.1 4.98 0.65 0.86 1
71°F1600 66.9 3.5 0.42 0.53 0.65 63.9 3.92 0.43 0.54 0.66 60.8 4.41 0.43 0.56 0.68 57.4 4.98 0.43 0.57 0.72000 70 3.54 0.44 0.57 0.7 66.8 3.96 0.44 0.58 0.72 63.4 4.44 0.44 0.59 0.73 59.7 5.01 0.45 0.6 0.762400 72.2 3.57 0.44 0.6 0.75 69 3.99 0.44 0.61 0.78 65.2 4.47 0.47 0.63 0.8 61.5 5.03 0.46 0.64 0.83
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 28
COOLING RATINGSNOTE - For Temperatures and Capacities not shown in tables, see bulletin - Cooling Unit Rating Table Correction Factor Data in Miscellaneous Product Data section.
6 TON HIGH EFFICIENCY LCH072H4
Entering Wet Bulb
Temper-ature
Total Air
Volume
Outdoor Air Temperature Entering Outdoor Coil85°F 95°F 105°F 115°F
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F1920 72.3 4.53 0.71 0.85 0.99 69.1 5.05 0.73 0.87 1 65.7 5.63 0.74 0.9 1 61.8 6.28 0.76 0.93 12400 76.2 4.55 0.76 0.93 1 72.8 5.06 0.78 0.96 1 69 5.63 0.8 0.98 1 64.9 6.28 0.82 1 12880 79 4.56 0.82 1 1 75.6 5.06 0.84 1 1 72.5 5.64 0.86 1 1 68.8 6.31 0.9 1 1
67°F1920 76.7 4.55 0.56 0.68 0.81 73.3 5.05 0.57 0.69 0.83 69.9 5.64 0.58 0.72 0.86 66 6.29 0.59 0.73 0.892400 80.8 4.56 0.59 0.74 0.89 77.2 5.07 0.6 0.75 0.92 73.2 5.65 0.62 0.77 0.95 68.9 6.3 0.63 0.8 0.982880 83.6 4.57 0.63 0.79 0.97 79.7 5.07 0.63 0.81 0.99 75.8 5.65 0.65 0.84 1 71 6.3 0.66 0.87 1
71°F1920 81.6 4.56 0.43 0.55 0.66 78.1 5.07 0.43 0.55 0.67 74.4 5.65 0.43 0.56 0.69 70.1 6.3 0.44 0.58 0.712400 85.7 4.58 0.44 0.58 0.71 81.8 5.08 0.45 0.59 0.73 77.7 5.66 0.45 0.6 0.75 73.1 6.31 0.46 0.62 0.772880 88.4 4.59 0.46 0.61 0.77 84.4 5.09 0.46 0.62 0.79 80 5.67 0.46 0.63 0.8 75.5 6.32 0.47 0.65 0.84
6 TON HIGH EFFICIENCY LCH074H4 (1ST STAGE)
Entering Wet Bulb
Temper-ature
Total Air
Volume
Outdoor Air Temperature Entering Outdoor Coil65°F 75°F 85°F 95°F
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F1200 53.3 2.27 0.68 0.81 0.92 51 2.59 0.69 0.82 0.94 48.3 2.95 0.7 0.83 0.96 45.6 3.36 0.71 0.85 0.981600 57.8 2.26 0.74 0.88 1 55.2 2.58 0.75 0.9 1 52.5 2.94 0.77 0.92 1 49.3 3.36 0.78 0.95 12000 61.2 2.25 0.8 0.96 1 58.2 2.57 0.81 0.98 1 55.3 2.94 0.83 1 1 52.5 3.35 0.84 1 1
67°F1200 57.2 2.26 0.55 0.66 0.77 54.7 2.58 0.55 0.67 0.78 51.9 2.94 0.55 0.67 0.79 48.9 3.36 0.55 0.68 0.811600 61.9 2.25 0.58 0.72 0.85 59.2 2.57 0.59 0.73 0.86 56.3 2.93 0.59 0.74 0.88 53 3.35 0.6 0.76 0.912000 65.4 2.24 0.62 0.78 0.93 62.3 2.56 0.62 0.78 0.94 59.2 2.93 0.63 0.8 0.97 55.6 3.34 0.64 0.82 0.99
71°F1200 61.2 2.25 0.43 0.53 0.63 58.6 2.57 0.42 0.53 0.64 55.8 2.93 0.42 0.53 0.64 52.6 3.35 0.41 0.53 0.651600 66.3 2.23 0.44 0.57 0.69 63.3 2.56 0.44 0.57 0.7 60.2 2.92 0.44 0.58 0.71 56.7 3.34 0.44 0.59 0.732000 69.6 2.22 0.45 0.61 0.75 66.5 2.54 0.46 0.61 0.76 63.1 2.91 0.45 0.62 0.77 59.6 3.33 0.46 0.63 0.8
6 TON HIGH EFFICIENCY LCH074H4 (2ND STAGE)
Entering Wet Bulb
Temper-ature
Total Air
Volume
Outdoor Air Temperature Entering Outdoor Coil85°F 95°F 105°F 115°F
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F1920 68.6 4.12 0.73 0.88 1 64.9 4.65 0.75 0.9 1 60.9 5.25 0.77 0.93 1 56.6 5.94 0.79 0.96 12400 72.2 4.16 0.79 0.96 1 68.1 4.68 0.81 0.99 1 63.9 5.28 0.83 1 1 60 5.97 0.86 1 12880 75.2 4.18 0.85 1 1 71.6 4.72 0.87 1 1 67.6 5.32 0.9 1 1 63.4 6.01 0.94 1 1
67°F1920 73 4.16 0.57 0.71 0.85 69 4.69 0.59 0.73 0.87 64.8 5.29 0.59 0.74 0.89 60.4 5.97 0.6 0.77 0.932400 76.7 4.2 0.62 0.77 0.93 72.4 4.73 0.62 0.79 0.95 67.9 5.32 0.63 0.81 0.98 63 6 0.64 0.84 12880 79.1 4.22 0.64 0.83 0.99 74.8 4.75 0.66 0.85 1 69.9 5.34 0.67 0.88 1 65 6.02 0.69 0.91 1
71°F1920 77.6 4.21 0.44 0.56 0.69 73.5 4.74 0.43 0.57 0.7 69.1 5.34 0.43 0.58 0.72 64.2 6.02 0.43 0.59 0.742400 81.1 4.24 0.45 0.6 0.75 76.8 4.77 0.45 0.61 0.77 72 5.37 0.45 0.62 0.79 67.1 6.05 0.44 0.64 0.812880 83.7 4.27 0.47 0.64 0.8 79.3 4.8 0.46 0.65 0.83 74.2 5.4 0.48 0.66 0.85 69.2 6.07 0.48 0.68 0.89
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 29
HUMIDITROL® DEHUMIDIFICATION SYSTEM RATINGS
3 TON HIGH EFFICIENCY LCH036H4 WITH HUMIDITROL OPERATINGEntering
WetBulb
Temper-ature
Total Air Vol-
ume
Outdoor Air Temperature Entering Outdoor Coil65°F 75°F 85°F 95°F
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F640 22.8 1.66 .46 .61 .76 19.7 1.86 .40 .57 .75 16.3 2.07 .33 .53 .74 12.9 2.32 .23 .47 .73800 24.3 1.69 .50 .67 .85 20.6 1.88 .44 .64 .85 16.7 2.10 .37 .61 .87 12.7 2.35 .25 .57 .91960 25.2 1.71 .53 .74 .94 21.0 1.90 .48 .72 .97 16.6 2.12 .41 .71 1.00 12.2 2.37 .29 .69 1.00
67°F640 25.5 1.69 .32 .45 .58 22.2 1.88 .26 .40 .55 18.9 2.10 .18 .34 .51 15.3 2.35 .07 .26 .46800 27.1 1.71 .34 .48 .63 23.4 1.91 .27 .44 .61 19.5 2.12 .19 .38 .59 15.4 2.37 .05 .29 .55960 28.3 1.73 .35 .52 .70 24.0 1.93 .29 .48 .68 19.7 2.14 .19 .42 .68 15.1 2.39 .05 .34 .65
71°F640 28.2 1.71 .21 .32 .44 24.9 1.90 .16 .27 .40 21.4 2.12 .07 .21 .35 17.9 2.37 -.05 .12 .28800 30.0 1.73 .22 .34 .47 26.2 1.93 .15 .29 .44 22.2 2.15 .05 .22 .38 18.1 2.39 -.09 .12 .32960 31.3 1.75 .22 .36 .51 27.0 1.95 .15 .31 .48 22.6 2.17 .04 .23 .43 18.2 2.41 -.13 .12 .36
4 TON STANDARD EFFICIENCY LCH048S4 WITH HUMIDITROL OPERATINGEntering
WetBulb
Temper-ature
Total Air Vol-
ume
Outdoor Air Temperature Entering Outdoor Coil65°F 75°F 85°F 95°F
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F890 30.8 2.24 .47 .62 .77 26.8 2.48 .42 .60 .77 22.7 2.75 .36 .56 .76 18.2 3.05 .27 .52 .761115 32.6 2.28 .51 .68 .86 27.9 2.52 .47 .67 .87 23.2 2.78 .41 .65 .89 18.3 3.08 .31 .61 .921340 33.7 2.31 .55 .76 .96 28.6 2.55 .51 .75 .98 23.3 2.81 .45 .73 1.00 17.8 3.11 .35 .73 .99
67°F890 34.5 2.28 .33 .46 .59 30.4 2.52 .28 .42 .56 26.1 2.78 .20 .37 .54 21.7 3.08 .10 .30 .501115 36.4 2.31 .35 .50 .66 31.8 2.55 .29 .45 .63 26.8 2.82 .21 .41 .61 21.7 3.11 .09 .34 .591340 37.7 2.34 .37 .54 .72 33.0 2.58 .31 .48 .71 27.0 2.84 .21 .45 .70 21.4 3.14 .09 .39 .69
71°F890 38.1 2.31 .22 .33 .44 34.0 2.55 .16 .29 .41 29.6 2.81 .08 .22 .36 25.2 3.12 -.03 .14 .311115 40.3 2.35 .22 .35 .48 35.5 2.58 .15 .30 .45 30.5 2.85 .06 .24 .41 25.4 3.15 -.07 .15 .351340 41.6 2.37 .22 .38 .53 36.8 2.61 .15 .31 .50 31.0 2.87 .05 .25 .46 25.2 3.17 -.10 .15 .40
3 TON STANDARD EFFICIENCY LCH036S4 WITH HUMIDITROL OPERATINGEntering
WetBulb
Temper-ature
Total Air Vol-
ume
Outdoor Air Temperature Entering Outdoor Coil65°F 75°F 85°F 95°F
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F640 22.5 1.69 .46 .60 .76 19.3 1.88 .40 .57 .75 16.0 2.10 .32 .53 .74 12.5 2.35 .21 .46 .73800 23.9 1.71 .49 .67 .84 20.1 1.91 .44 .64 .86 16.2 2.13 .36 .61 .88 12.3 2.38 .24 .56 .90960 24.7 1.73 .53 .74 .95 20.5 1.93 .48 .73 .97 16.1 2.15 .39 .71 1.00 12.3 2.40 .27 .62 1.00
67°F640 25.1 1.71 .32 .44 .57 21.9 1.90 .26 .40 .54 18.5 2.13 .18 .34 .51 15.0 2.37 .05 .25 .45800 26.7 1.74 .33 .48 .26 22.9 1.93 .27 .44 .61 19.1 2.15 .18 .37 .58 15.0 2.40 .03 .28 .54960 27.8 1.76 .35 .52 .70 23.5 1.95 .28 .48 .69 19.2 2.17 .18 .41 .68 14.6 2.42 .02 .32 .66
71°F640 28.0 1.73 .20 .31 .43 24.5 1.93 .15 .27 .39 21.0 2.15 .06 .20 .34 17.5 2.40 -.07 .10 .27800 29.6 1.76 .21 .34 .47 25.7 1.96 .14 .28 .43 21.7 2.18 .04 .21 .38 17.6 2.43 -.11 .10 .31960 30.7 1.78 .21 .36 .51 26.5 1.98 .13 .30 .47 22.0 2.20 .02 .22 .42 17.4 2.45 -.15 .11 .35
4 TON HIGH EFFICIENCY LCH048H4 WITH HUMIDITROL OPERATINGEntering
WetBulb
Temper-ature
Total Air Vol-
ume
Outdoor Air Temperature Entering Outdoor Coil65°F 75°F 85°F 95°F
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F890 30.1 2.28 .46 .62 .77 26.1 2.52 .41 .59 .76 22.0 2.79 .35 .56 .76 17.6 3.09 .26 .51 .761115 31.8 2.32 .51 .68 .86 27.2 2.56 .46 .66 .87 22.4 2.83 .40 .64 .89 17.5 3.13 .29 .60 .921340 32.8 2.35 .55 .76 .96 27.7 2.59 .50 .74 .98 22.3 2.85 .44 .74 1.00 17.0 3.16 .33 .72 1.00
67°F890 33.8 2.32 .32 .46 .59 29.7 2.56 .27 .41 .56 25.5 2.83 .19 .36 .53 21.1 3.13 .08 .28 .491115 35.7 2.36 .34 .49 .65 30.8 2.59 .28 .46 .63 26.0 2.86 .19 .40 .61 20.9 3.16 .05 .33 .581340 36.7 2.38 .36 .54 .72 32.1 2.62 .30 .47 .67 26.1 2.89 .19 .45 .70 20.5 3.19 .06 .37 .69
71°F890 37.4 2.35 .21 .32 .44 33.3 2.59 .15 .27 .40 28.9 2.86 .07 .21 .36 24.5 3.17 -.05 .12 .291115 39.4 2.39 .21 .34 .48 34.6 2.63 .14 .29 .45 29.8 2.90 .04 .22 .40 24.5 3.20 -.09 .13 .341340 40.5 2.42 .21 .37 .53 35.9 2.65 .13 .30 .49 30.0 2.92 .02 .24 .45 24.2 3.23 -.14 .13 .39
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 30
HUMIDITROL® DEHUMIDIFICATION SYSTEM RATINGS
5 TON HIGH EFFICIENCY LCH060H4 WITH HUMIDITROL OPERATINGEntering
WetBulb
Temper-ature
Total Air Vol-
ume
Outdoor Air Temperature Entering Outdoor Coil65°F 75°F 85°F 95°F
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F1080 38.7 2.98 .41 .57 .73 32.6 3.31 .34 .52 .71 26.2 3.69 .23 .45 .69 19.4 4.12 .06 .35 .661350 40.8 3.03 .45 .64 .82 33.7 3.35 .38 .60 .83 26.4 3.73 .26 .54 .84 18.6 4.16 .06 .45 .861620 42.3 3.07 .49 .71 .93 34.8 3.39 .42 .66 .96 27.2 3.77 .30 .59 1.00 17.5 4.20 .07 .57 1.00
67°F1080 44.0 3.02 .27 .41 .55 37.8 3.35 .19 .35 .51 31.4 3.73 .08 .26 .45 24.6 4.17 -.10 .13 .361350 46.6 3.08 .29 .45 .61 39.2 3.40 .20 .39 .57 31.9 3.78 .08 .30 .52 23.9 4.21 -.14 .16 .451620 48.2 3.12 .30 .49 .67 40.3 3.45 .22 .43 .65 32.8 3.82 .05 .31 .62 23.1 4.25 -.18 .19 .55
71°F1080 49.6 3.08 .17 .28 .40 43.3 3.40 .08 .21 .35 36.5 3.78 -.03 .13 .28 29.6 4.22 -.20 .00 .181350 52.4 3.13 .16 .30 .44 45.1 3.46 .08 .23 .39 37.4 3.83 -.06 .13 .32 29.6 4.27 -.26 -.02 .211620 54.3 3.18 .16 .32 .48 46.1 3.50 .06 .25 .43 38.0 3.87 -.08 .13 .36 29.4 4.30 -.33 -.04 .25
5 TON STANDARD EFFICIENCY LCH060S4 WITH HUMIDITROL OPERATINGEntering
WetBulb
Temper-ature
Total Air Vol-
ume
Outdoor Air Temperature Entering Outdoor Coil65°F 75°F 85°F 95°F
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F1080 39.4 2.94 .42 .58 .73 33.2 3.27 .35 .53 .71 26.8 3.64 .25 .46 .69 20.0 4.07 .08 .36 .661350 41.7 2.99 .47 .64 .82 34.7 3.31 .39 .60 .83 27.2 3.69 .28 .55 .83 19.4 4.12 .09 .46 .851620 43.3 3.03 .50 .71 .92 35.1 3.35 .43 .69 .96 28.2 3.72 .31 .59 .99 18.4 4.15 .10 .58 1.00
67°F1080 44.8 2.99 .28 .41 .55 38.6 3.31 .21 .35 .51 32.1 3.69 .10 .27 .45 25.1 4.12 -.08 .15 .381350 47.4 3.04 .30 .46 .61 40.3 3.36 .21 .39 .58 32.8 3.73 .09 .31 .53 24.9 4.16 -.11 .18 .461620 49.3 3.08 .31 .49 .67 41.3 3.40 .24 .44 .66 32.7 3.77 .07 .36 .62 24.2 4.20 -.14 .21 .56
71°F1080 50.5 3.04 .17 .29 .40 44.1 3.36 .09 .22 .35 37.4 3.73 -.01 .14 .29 30.5 4.16 -.18 .01 .191350 53.4 3.09 .17 .31 .45 46.0 3.41 .09 .24 .40 38.4 3.78 -.04 .14 .33 30.7 4.22 -.23 .00 .221620 55.3 3.14 .17 .33 .48 47.2 3.45 .08 .26 .44 39.0 3.82 -.06 .15 .37 30.6 4.25 -.29 -.02 .26
6 TON HIGH EFFICIENCY LCH072H4 WITH HUMIDITROL OPERATINGEntering
WetBulb
Temper-ature
Total Air Vol-
ume
Outdoor Air Temperature Entering Outdoor Coil65°F 75°F 85°F 95°F
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F1920 49.0 3.62 .52 .73 .94 41.2 3.99 .44 .70 .98 32.1 4.40 .36 .69 1.00 23.0 4.85 .18 .65 1.002400 50.4 3.65 .57 .84 1.00 41.0 4.01 .52 .84 1.00 31.0 4.41 .42 .86 1.00 20.8 4.86 .26 .88 .892880 51.1 3.66 .65 .95 .95 40.7 4.03 .61 .98 1.00 29.8 4.43 .52 1.00 .99 19.6 4.87 .34 1.00 1.00
67°F1920 55.5 3.65 .32 .51 .69 47.2 4.02 .24 .46 .67 39.1 4.42 .10 .36 .65 29.2 4.87 -.09 .27 .612400 57.4 3.68 .35 .57 .79 47.6 4.04 .26 .53 .79 37.9 4.44 .11 .45 .79 27.6 4.88 -.14 .33 .792880 58.4 3.70 .37 .63 .89 47.6 4.05 .28 .60 .92 36.4 4.45 .13 .55 .96 25.3 4.89 -.17 .44 1.00
71°F1920 62.1 3.68 .17 .33 .49 53.6 4.04 .07 .27 .45 44.6 4.44 -.07 .17 .40 35.4 4.89 -.28 .02 .312400 64.2 3.71 .17 .36 .56 54.5 4.06 .06 .29 .52 44.5 4.46 -.10 .19 .46 34.2 4.91 -.38 .02 .382880 65.2 3.73 .17 .40 .62 54.7 4.08 .05 .32 .59 43.6 4.48 -.14 .22 .56 32.1 4.92 -.49 .03 .48
6 TON HIGH EFFICIENCY LCH074H4 WITH HUMIDITROL OPERATINGEntering
WetBulb
Temper-ature
Total Air Vol-
ume
Outdoor Air Temperature Entering Outdoor Coil65°F 75°F 85°F 95°F
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp. Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F1200 41.7 3.21 0.43 0.59 0.74 33.4 3.61 0.33 0.53 0.72 25.3 4.06 0.16 0.42 0.67 16.7 4.57 -0.19 0.22 0.591600 44.9 3.26 0.49 0.68 0.86 35.5 3.66 0.4 0.63 0.87 25.8 4.11 0.22 0.55 0.87 16 4.61 -0.17 0.38 0.892000 46.8 3.3 0.56 0.77 0.98 36.1 3.7 0.46 0.75 1 25.4 4.15 0.28 0.71 1 14.3 4.65 -0.16 0.6 0.95
67°F1200 48.1 3.25 0.31 0.44 0.57 40 3.65 0.19 0.36 0.52 31.8 4.1 0.03 0.23 0.43 23.1 4.61 -0.28 0.01 0.291600 52 3.31 0.33 0.49 0.65 42.3 3.71 0.21 0.42 0.61 32.5 4.15 0.02 0.3 0.55 22.7 4.66 -0.33 0.06 0.432000 54.2 3.35 0.35 0.55 0.73 43.3 3.75 0.23 0.48 0.72 33.9 4.2 0.03 0.32 0.62 21.4 4.7 -0.4 0.11 0.6
71°F1200 54.9 3.29 0.2 0.32 0.44 46.6 3.69 0.09 0.23 0.37 38.2 4.14 -0.07 0.1 0.27 29.6 4.65 -0.33 -0.1 0.121600 59.4 3.36 0.2 0.35 0.49 49.7 3.76 0.08 0.26 0.42 39.6 4.2 -0.11 0.12 0.33 29.6 4.71 -0.42 -0.12 0.182000 62.1 3.41 0.2 0.37 0.55 51 3.81 0.07 0.28 0.5 39.9 4.25 -0.14 0.14 0.4 28.6 4.75 -0.52 -0.13 0.24
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 31
BL
OW
ER
DA
TA
- D
IRE
CT
DR
IVE
- 3
TO
NB
LOW
ER T
AB
LE IN
CLU
DES
RES
ISTA
NC
E FO
R B
ASE
UN
IT O
NLY
WIT
H D
RY IN
DO
OR
CO
IL A
ND
AIR
FIL
TER
S IN
PLA
CE.
FOR
ALL
UN
ITS
AD
D:
1 - A
ny fa
ctor
y in
stal
led
optio
ns a
ir re
sist
ance
(hea
t sec
tion,
eco
nom
izer
, etc
.).
2 - A
ny fi
eld
inst
alle
d ac
cess
orie
s ai
r res
ista
nce
(duc
t res
ista
nce,
diff
user
, etc
.).S
ee P
age
42 fo
r blo
wer
mot
ors
and
driv
es a
nd w
et c
oil a
nd o
ptio
ns/a
cces
sory
air
resi
stan
ce d
ata.
DO
WN
FLO
WEx
tern
al
Stat
ic
Pres
s.
in. w
.g.
Perc
enta
ge o
f Tot
al M
otor
Tor
que
20%
30%
40%
50%
60%
70%
80%
90%
100%
Cfm
Wat
tsR
PMC
fmW
atts
RPM
Cfm
Wat
tsR
PMC
fmW
atts
RPM
Cfm
Wat
tsR
PMC
fmW
atts
RPM
Cfm
Wat
tsR
PMC
fmW
atts
RPM
Cfm
Wat
tsR
PM0
785
3840
796
968
468
1152
9852
913
0114
058
114
4918
263
415
7123
668
316
9329
073
217
9935
277
019
0441
480
90.
172
044
475
919
7452
211
1710
456
912
6415
062
614
1119
568
415
3924
872
416
6730
176
517
7236
680
518
7743
184
40.
264
550
550
851
8359
310
5611
663
712
1816
168
013
8020
572
215
0925
976
216
3831
380
217
4438
084
018
4944
687
90.
357
056
620
793
9065
110
1612
468
111
7517
273
013
3422
077
914
6827
481
316
0132
884
617
0839
688
318
1546
492
00.
450
560
678
731
9771
295
613
574
611
3018
278
113
0322
981
514
3428
685
215
6434
288
916
7641
092
017
8747
795
10.
543
265
740
663
105
775
895
145
810
1076
194
839
1257
243
867
1396
298
895
1534
353
923
1647
421
952
1759
489
981
0.6
- - -
- - -
- - -
- - -
- - -
- - -
855
152
852
1033
204
884
1211
256
917
1351
312
944
1490
369
971
1604
437
997
1718
505
1024
0.7
- - -
- - -
- - -
- - -
- - -
- - -
792
163
916
986
213
933
1180
264
949
1320
321
975
1460
379
1002
1575
447
1026
1690
515
1050
0.8
- - -
- - -
- - -
- - -
- - -
- - -
734
173
975
934
224
985
1134
275
995
1275
334
1021
1416
393
1046
1533
460
1067
1649
527
1088
0.9
- - -
- - -
- - -
- - -
- - -
- - -
674
183
1034
881
234
1037
1088
286
1039
1230
346
1064
1371
406
1088
1490
471
1106
1608
537
1123
1.0
- - -
- - -
- - -
- - -
- - -
- - -
613
193
1095
820
246
1094
1026
300
1093
1184
357
1104
1342
414
1115
1448
480
1140
1553
547
1165
1.1
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
980
309
1131
1139
367
1142
1297
425
1154
1404
488
1173
1511
551
1192
1.2
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
1253
436
1190
1355
495
1207
1456
554
1225
HO
RIZ
ON
TAL
Exte
rnal
St
atic
Pr
ess.
in
. w.g
.
Perc
enta
ge o
f Tot
al M
otor
Tor
que
20%
30%
40%
50%
60%
70%
80%
90%
100%
Cfm
Wat
tsR
PMC
fmW
atts
RPM
Cfm
Wat
tsR
PMC
fmW
atts
RPM
Cfm
Wat
tsR
PMC
fmW
atts
RPM
Cfm
Wat
tsR
PMC
fmW
atts
RPM
Cfm
Wat
tsR
PM0
796
4337
297
564
447
1155
8552
413
0212
656
014
4816
859
715
6621
463
916
8426
068
017
8632
372
018
8838
676
10.
170
950
461
909
7551
211
1010
156
412
5414
361
313
9818
566
215
2323
169
516
4927
772
917
5434
476
918
5841
181
00.
261
757
553
828
8859
110
4011
862
912
0415
666
413
6819
469
814
9224
373
416
1629
177
117
2135
880
818
2642
484
50.
350
364
662
747
9766
899
213
167
611
5117
272
213
1021
276
814
4226
079
415
7430
882
016
8137
485
317
8744
088
70.
441
969
747
671
107
746
924
146
747
1095
185
782
1266
225
818
1398
275
844
1530
325
870
1640
389
899
1749
454
927
0.5
323
7584
358
911
783
285
715
982
110
3919
884
412
2123
786
713
5928
788
814
9633
790
915
9840
394
117
0147
097
30.
6- -
-- -
-- -
-- -
-- -
-- -
-81
716
587
199
020
890
011
6225
292
912
9630
695
414
3136
097
915
4642
199
516
6248
110
100.
7- -
-- -
-- -
-- -
-- -
-- -
-74
717
695
793
321
996
611
1826
297
412
6431
498
714
1036
710
0015
2342
710
1616
3648
710
320.
8- -
-- -
-- -
-- -
-- -
-- -
-70
018
110
2688
622
610
2210
7327
110
1812
1632
710
3513
5938
310
5114
6944
210
6615
7950
110
810.
9- -
-- -
-- -
-- -
-- -
-- -
-64
318
711
1082
923
510
9110
1528
310
7311
6134
110
8713
0739
911
0114
0945
611
1815
1051
311
361.
0- -
-- -
-- -
-- -
-- -
-- -
-59
219
011
9778
124
111
5497
029
111
1311
1435
211
3012
5841
311
4713
5546
711
6114
5252
011
761.
1- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-91
530
011
6210
6736
211
7112
1942
411
8013
1247
311
9214
0552
212
041.
2- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-11
6843
712
2312
4848
012
3513
2952
312
46
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 32
BL
OW
ER
DA
TA
- D
IRE
CT
DR
IVE
- 4
TO
NB
LOW
ER T
AB
LE IN
CLU
DES
RES
ISTA
NC
E FO
R B
ASE
UN
IT O
NLY
WIT
H D
RY IN
DO
OR
CO
IL A
ND
AIR
FIL
TER
S IN
PLA
CE.
FOR
ALL
UN
ITS
AD
D:
1 - A
ny fa
ctor
y in
stal
led
optio
ns a
ir re
sist
ance
(hea
t sec
tion,
eco
nom
izer
, etc
.).
2 - A
ny fi
eld
inst
alle
d ac
cess
orie
s ai
r res
ista
nce
(duc
t res
ista
nce,
diff
user
, etc
.).S
ee P
age
42 fo
r blo
wer
mot
ors
and
driv
es a
nd w
et c
oil a
nd o
ptio
ns/a
cces
sory
air
resi
stan
ce d
ata.
DO
WN
FLO
WEx
tern
al
Stat
ic
Pres
s.
in. w
.g.
Perc
enta
ge o
f Tot
al M
otor
Tor
que
20%
30%
40%
50%
60%
70%
80%
90%
100%
Cfm
Wat
tsR
PMC
fmW
atts
RPM
Cfm
Wat
tsR
PMC
fmW
atts
RPM
Cfm
Wat
tsR
PMC
fmW
atts
RPM
Cfm
Wat
tsR
PMC
fmW
atts
RPM
Cfm
Wat
tsR
PM
010
4677
485
1257
134
565
1468
191
646
1639
271
715
1810
351
784
1960
445
837
2109
539
890
2251
674
947
2393
810
1004
0.1
992
8554
312
1114
561
914
3020
569
516
0928
575
517
8836
581
419
3746
387
020
8656
192
522
2769
197
723
6782
210
290.
292
695
612
1166
154
669
1405
214
727
1580
299
793
1755
384
859
1909
482
909
2063
581
959
2200
708
1008
2336
835
1056
0.3
883
101
657
1125
164
715
1367
227
774
1551
311
831
1734
396
888
1891
495
934
2048
593
980
2181
719
1028
2314
844
1076
0.4
818
111
724
1074
175
772
1329
240
820
1515
327
875
1701
414
930
1859
515
975
2017
617
1021
2147
737
1064
2276
857
1107
0.5
752
121
791
1022
187
828
1291
253
865
1485
339
911
1679
425
957
1837
529
1003
1994
632
1049
2120
749
1090
2245
866
1131
0.6
- - -
- - -
- - -
- - -
- - -
- - -
1253
265
908
1450
354
952
1646
442
996
1809
544
1036
1972
646
1076
2094
760
1114
2215
873
1153
0.7
- - -
- - -
- - -
- - -
- - -
- - -
1202
282
965
1408
370
999
1613
458
1034
1777
560
1071
1941
662
1109
2063
771
1141
2185
879
1174
0.8
- - -
- - -
- - -
- - -
- - -
- - -
1164
294
1006
1372
383
1038
1580
473
1070
1745
574
1104
1910
676
1138
2025
781
1171
2139
886
1204
0.9
- - -
- - -
- - -
- - -
- - -
- - -
1126
306
1046
1337
396
1075
1548
487
1105
1714
587
1135
1880
687
1165
1987
788
1198
2094
889
1230
1.0
- - -
- - -
- - -
- - -
- - -
- - -
1081
320
1092
1298
410
1115
1515
500
1138
1675
599
1169
1834
699
1200
1941
794
1227
2048
889
1254
1.1
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
1476
514
1174
1632
609
1201
1788
704
1229
1896
795
1251
2003
886
1274
1.2
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
1728
702
1256
1835
790
1277
1942
878
1298
HO
RIZ
ON
TAL
Exte
rnal
St
atic
Pr
ess.
in
. w.g
.
Perc
enta
ge o
f Tot
al M
otor
Tor
que
20%
30%
40%
50%
60%
70%
80%
90%
100%
Cfm
Wat
tsR
PMC
fmW
atts
RPM
Cfm
Wat
tsR
PMC
fmW
atts
RPM
Cfm
Wat
tsR
PMC
fmW
atts
RPM
Cfm
Wat
tsR
PMC
fmW
atts
RPM
Cfm
Wat
tsR
PM
010
2378
452
1234
131
536
1445
183
621
1611
251
688
1776
319
754
1910
400
800
2043
480
846
2192
613
904
2340
746
963
0.1
970
8252
911
9213
759
614
1419
266
415
8626
172
217
5733
078
019
0242
783
720
4852
389
321
8964
094
223
3075
899
10.
290
986
590
1146
144
647
1383
201
705
1553
275
764
1723
349
824
1876
444
873
2028
540
923
2170
659
970
2312
779
1018
0.3
829
9567
510
8415
471
813
3921
376
115
2028
780
717
0136
185
318
5345
990
320
0555
795
321
3867
310
0122
7178
910
490.
477
210
473
410
3216
577
412
9322
681
414
7730
485
916
6138
290
418
1848
094
919
7557
999
320
9869
010
3922
2280
210
840.
568
811
881
896
717
884
112
4723
886
414
3931
790
216
3139
694
017
8749
898
619
4359
910
3220
6670
410
6921
8980
911
060.
6- -
-- -
-- -
-- -
-- -
-- -
-12
0224
991
014
0033
094
415
9741
197
817
5851
210
1819
2061
310
5920
3571
510
9521
5081
711
320.
7- -
-- -
-- -
-- -
-- -
-- -
-11
4626
596
713
5534
599
015
6542
610
1417
2752
710
5318
8962
910
9219
9772
611
2521
0582
211
580.
8- -
-- -
-- -
-- -
-- -
-- -
-10
8528
010
2113
0236
210
4015
2044
310
6016
8554
410
9518
4964
611
3019
5073
711
6020
5182
811
910.
9- -
-- -
-- -
-- -
-- -
-- -
-10
2929
210
6412
5537
610
8514
8146
011
0616
4356
011
3718
0566
011
6718
9874
511
9419
9183
012
221.
0- -
-- -
-- -
-- -
-- -
-- -
-96
130
811
1412
0738
911
2614
5647
111
3716
0157
111
7317
4667
212
0918
3675
112
3019
2682
912
511.
1- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-14
1648
811
8515
4958
112
1316
8267
512
4117
7475
012
5818
6782
412
761.
2- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-- -
-15
7065
212
6816
7573
212
8617
8081
213
05
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 33
BL
OW
ER
DA
TA
- D
IRE
CT
DR
IVE
- 5
TO
NB
LOW
ER T
AB
LE IN
CLU
DES
RES
ISTA
NC
E FO
R B
ASE
UN
IT O
NLY
WIT
H D
RY IN
DO
OR
CO
IL A
ND
AIR
FIL
TER
S IN
PLA
CE.
FOR
ALL
UN
ITS
AD
D:
1 - A
ny fa
ctor
y in
stal
led
optio
ns a
ir re
sist
ance
(hea
t sec
tion,
eco
nom
izer
, etc
.).
2 - A
ny fi
eld
inst
alle
d ac
cess
orie
s ai
r res
ista
nce
(duc
t res
ista
nce,
diff
user
, etc
.).S
ee P
age
42 fo
r blo
wer
mot
ors
and
driv
es a
nd w
et c
oil a
nd o
ptio
ns/a
cces
sory
air
resi
stan
ce d
ata.
DO
WN
FLO
WEx
tern
al
Stat
ic
Pres
s.
in. w
.g.
Perc
enta
ge o
f Tot
al M
otor
Tor
que
20%
30%
40%
50%
60%
70%
80%
90%
100%
Cfm
Wat
tsR
PMC
fmW
atts
RPM
Cfm
Wat
tsR
PMC
fmW
atts
RPM
Cfm
Wat
tsR
PMC
fmW
atts
RPM
Cfm
Wat
tsR
PMC
fmW
atts
RPM
Cfm
Wat
tsR
PM
011
0276
420
1324
143
510
1545
211
601
1740
302
667
1934
393
734
2096
519
797
2258
645
860
2396
791
910
2534
938
959
0.1
1038
8548
412
8415
355
915
2922
163
317
2231
569
819
1441
076
320
7853
582
322
4266
088
223
7881
093
425
1496
098
60.
297
594
546
1235
165
611
1495
236
677
1692
332
737
1888
429
798
2057
553
851
2225
677
905
2363
825
954
2501
973
1003
0.3
911
104
603
1192
175
654
1473
245
706
1672
343
763
1871
441
820
2040
566
874
2208
692
928
2348
839
974
2488
987
1020
0.4
847
114
657
1143
187
702
1439
259
747
1642
359
800
1845
458
852
2015
585
904
2185
712
956
2327
858
1000
2469
1005
1044
0.5
784
124
708
1095
198
747
1406
273
785
1613
374
835
1819
475
884
1994
600
931
2168
726
977
2309
874
1022
2450
1022
1066
0.6
- - -
- - -
- - -
- - -
- - -
- - -
1372
285
822
1583
388
868
1793
490
915
1969
617
959
2145
743
1004
2288
890
1046
2431
1037
1087
0.7
- - -
- - -
- - -
- - -
- - -
- - -
1339
297
856
1553
401
900
1767
505
944
1945
633
987
2122
760
1029
2267
906
1068
2411
1051
1108
0.8
- - -
- - -
- - -
- - -
- - -
- - -
1294
313
899
1518
416
936
1741
519
973
1920
647
1013
2099
776
1054
2246
920
1090
2392
1064
1127
0.9
- - -
- - -
- - -
- - -
- - -
- - -
1249
327
937
1478
432
974
1706
537
1010
1891
663
1043
2076
790
1077
2221
934
1113
2366
1078
1150
1.0
- - -
- - -
- - -
- - -
- - -
- - -
1193
343
980
1437
446
1008
1680
549
1036
1867
676
1067
2053
803
1098
2200
945
1132
2347
1087
1166
1.1
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
1649
562
1066
1834
691
1097
2019
821
1129
2164
961
1162
2308
1100
1194
1.2
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
1984
836
1157
2133
971
1184
2282
1106
1211
HO
RIZ
ON
TAL
Exte
rnal
St
atic
Pr
ess.
in
. w.g
.
Perc
enta
ge o
f Tot
al M
otor
Tor
que
20%
30%
40%
50%
60%
70%
80%
90%
100%
Cfm
Wat
tsR
PMC
fmW
atts
RPM
Cfm
Wat
tsR
PMC
fmW
atts
RPM
Cfm
Wat
tsR
PMC
fmW
atts
RPM
Cfm
Wat
tsR
PMC
fmW
atts
RPM
Cfm
Wat
tsR
PM
011
2985
418
1343
146
512
1556
208
606
1740
306
679
1923
405
752
2084
530
812
2245
655
872
2377
807
927
2508
959
982
0.1
1063
8846
412
9515
455
015
2722
063
517
1531
870
519
0341
777
620
7054
683
522
3767
589
523
6882
394
824
9897
210
020.
298
495
534
1234
166
607
1483
237
680
1681
335
743
1878
432
807
2046
562
863
2214
691
920
2347
842
971
2479
993
1023
0.3
917
103
606
1178
179
665
1438
255
724
1645
351
780
1852
447
836
2018
580
894
2183
712
952
2321
862
997
2459
1012
1043
0.4
862
112
681
1128
192
725
1393
272
768
1604
370
823
1814
468
878
1987
598
927
2160
728
975
2298
881
1021
2435
1034
1067
0.5
818
124
760
1091
204
779
1364
283
798
1576
383
851
1788
482
905
1963
612
951
2137
742
997
2274
898
1044
2410
1055
1090
0.6
- - -
- - -
- - -
- - -
- - -
- - -
1319
300
842
1541
398
886
1762
495
931
1934
628
979
2106
761
1026
2244
919
1071
2381
1076
1115
0.7
- - -
- - -
- - -
- - -
- - -
- - -
1274
317
885
1499
415
926
1724
513
967
1900
646
1010
2075
779
1054
2219
934
1093
2362
1089
1131
0.8
- - -
- - -
- - -
- - -
- - -
- - -
1245
328
914
1466
429
957
1686
531
1001
1865
663
1040
2044
796
1080
2188
951
1117
2332
1106
1154
0.9
- - -
- - -
- - -
- - -
- - -
- - -
1200
344
957
1424
446
995
1647
547
1032
1830
679
1069
2013
812
1105
2154
968
1143
2294
1124
1181
1.0
- - -
- - -
- - -
- - -
- - -
- - -
1155
360
1000
1382
461
1030
1609
563
1061
1796
695
1095
1983
826
1129
2124
980
1164
2264
1134
1200
1.1
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
1570
577
1087
1753
712
1124
1936
847
1162
2086
994
1189
2235
1141
1216
1.2
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
1905
859
1182
2041
1003
1213
2176
1146
1244
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 34
BLOWER DATA - BELT DRIVE - 3 TON
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.FOR ALL UNITS ADD: 1 - Any factory installed options air resistance (heat section, economizer, etc.). 2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).See Page 42 for blower motors and drives and wet coil and options/accessory air resistance data.
DOWNFLOW
Air Volume (cfm)
External Static (in.w.g.)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.9 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
700 447 0.09 517 0.12 589 0.15 663 0.17 739 0.19 815 0.2 883 0.23 938 0.25 988 0.27 1039 0.29
800 465 0.1 534 0.14 605 0.17 678 0.19 753 0.21 825 0.23 890 0.25 946 0.27 996 0.3 1047 0.32
900 486 0.12 554 0.16 623 0.2 695 0.22 767 0.23 836 0.25 897 0.28 953 0.3 1004 0.33 1055 0.35
1000 508 0.15 576 0.19 643 0.22 713 0.24 783 0.26 848 0.28 907 0.3 961 0.33 1011 0.36 1062 0.38
1100 533 0.18 599 0.22 665 0.25 733 0.27 800 0.28 863 0.31 919 0.34 971 0.36 1020 0.39 1070 0.41
1200 560 0.21 625 0.25 689 0.28 755 0.3 820 0.32 879 0.34 932 0.37 983 0.4 1031 0.43 1079 0.45
1300 591 0.24 654 0.28 716 0.31 779 0.33 841 0.35 897 0.38 948 0.41 996 0.44 1044 0.47 1091 0.49
1400 631 0.26 690 0.3 748 0.34 807 0.36 864 0.39 916 0.42 964 0.46 1011 0.49 1058 0.51 1105 0.54
Air Volume (cfm)
External Static (in.w.g.)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
700 1088 0.31 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
800 1098 0.34 1144 0.36 1185 0.39 1224 0.42 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
900 1106 0.37 1152 0.4 1193 0.43 1232 0.46 1269 0.49 1305 0.52 1340 0.55 1376 0.59 - - - - - - - - - - - -
1000 1111 0.41 1157 0.43 1199 0.47 1238 0.5 1276 0.53 1311 0.56 1347 0.6 1382 0.63 1417 0.67 1452 0.7
1100 1118 0.44 1163 0.47 1206 0.51 1245 0.54 1282 0.58 1318 0.61 1353 0.65 1388 0.68 1423 0.72 1458 0.75
1200 1127 0.48 1171 0.52 1213 0.55 1252 0.59 1289 0.62 1324 0.66 1358 0.7 1393 0.73 1428 0.77 1463 0.81
1300 1137 0.53 1181 0.56 1221 0.6 1259 0.64 1296 0.68 1330 0.71 1364 0.75 1398 0.78 1432 0.82 1467 0.86
1400 1150 0.57 1191 0.61 1231 0.65 1268 0.69 1303 0.73 1337 0.77 1371 0.8 1404 0.84 1437 0.88 1473 0.91
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 35
BLOWER DATA - BELT DRIVE - 3 TON
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.FOR ALL UNITS ADD: 1 - Any factory installed options air resistance (heat section, economizer, etc.). 2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).See Page 42 for blower motors and drives and wet coil and options/accessory air resistance data.
HORIZONTAL
Air Volume (cfm)
External Static (in.w.g.)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.9 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
700 445 0.08 516 0.11 591 0.13 670 0.15 753 0.16 820 0.19 870 0.22 918 0.24 969 0.27 1021 0.29
800 463 0.09 534 0.12 608 0.14 685 0.16 766 0.18 830 0.21 878 0.24 926 0.27 977 0.29 1030 0.32
900 485 0.11 554 0.14 627 0.16 703 0.18 780 0.21 841 0.23 888 0.27 935 0.3 986 0.32 1039 0.35
1000 509 0.13 578 0.16 649 0.19 722 0.21 796 0.23 854 0.26 900 0.29 947 0.33 997 0.35 1048 0.38
1100 537 0.16 605 0.19 674 0.21 744 0.24 813 0.26 868 0.29 913 0.33 959 0.36 1008 0.39 1059 0.41
1200 567 0.19 633 0.22 700 0.24 768 0.27 833 0.3 884 0.33 928 0.37 974 0.4 1022 0.43 1071 0.45
1300 599 0.22 664 0.25 729 0.28 793 0.3 853 0.33 902 0.37 945 0.41 990 0.44 1037 0.47 1085 0.5
1400 634 0.26 697 0.29 758 0.31 819 0.34 875 0.38 921 0.42 964 0.46 1008 0.49 1054 0.52 1100 0.54
Air Volume (cfm)
External Static (in.w.g.)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
700 1071 0.32 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
800 1082 0.34 1128 0.37 1169 0.4 1205 0.42 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
900 1090 0.37 1137 0.4 1177 0.43 1214 0.46 1248 0.49 1280 0.51 1310 0.54 1340 0.57 - - - - - - - - - - - -
1000 1098 0.41 1143 0.44 1184 0.47 1221 0.5 1255 0.53 1287 0.56 1318 0.59 1347 0.61 1377 0.64 1406 0.67
1100 1107 0.44 1150 0.47 1191 0.51 1228 0.54 1263 0.57 1295 0.6 1325 0.63 1355 0.66 1384 0.69 1413 0.72
1200 1117 0.48 1160 0.52 1200 0.55 1237 0.59 1271 0.62 1303 0.66 1334 0.69 1363 0.72 1392 0.75 1420 0.78
1300 1130 0.53 1171 0.57 1210 0.6 1246 0.64 1280 0.68 1312 0.71 1342 0.74 1372 0.78 1400 0.81 1429 0.84
1400 1144 0.58 1183 0.62 1221 0.66 1256 0.7 1290 0.73 1321 0.77 1352 0.8 1381 0.84 1410 0.87 1439 0.9
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 36
BLOWER DATA - BELT DRIVE - 4 TONBLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.FOR ALL UNITS ADD: 1 - Any factory installed options air resistance (heat section, economizer, etc.). 2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).See Page 42 for blower motors and drives and wet coil and options/accessory air resistance data.
DOWNFLOW
Air Volume (cfm)
External Static (in.w.g.)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.9 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
900 496 0.13 568 0.16 640 0.18 711 0.2 779 0.22 844 0.25 905 0.28 960 0.3 1010 0.33 1061 0.35
1000 521 0.15 592 0.18 662 0.2 731 0.23 796 0.25 858 0.28 916 0.31 969 0.34 1019 0.36 1069 0.38
1100 548 0.18 618 0.21 686 0.23 752 0.25 814 0.28 873 0.31 929 0.34 980 0.37 1029 0.39 1078 0.42
1200 577 0.21 646 0.24 712 0.26 775 0.29 834 0.31 890 0.35 943 0.38 993 0.41 1041 0.43 1089 0.46
1300 611 0.24 677 0.27 740 0.3 800 0.32 856 0.35 909 0.39 959 0.42 1007 0.45 1055 0.47 1102 0.5
1400 654 0.26 713 0.29 771 0.33 826 0.36 878 0.39 928 0.43 976 0.47 1023 0.49 1070 0.52 1117 0.55
1500 698 0.28 751 0.32 802 0.36 852 0.4 901 0.44 948 0.48 995 0.51 1041 0.54 1088 0.57 1133 0.6
1600 738 0.32 785 0.36 831 0.41 878 0.45 923 0.49 969 0.53 1014 0.57 1061 0.59 1107 0.62 1151 0.66
1700 773 0.36 816 0.41 859 0.46 903 0.51 947 0.55 991 0.58 1036 0.62 1082 0.65 1128 0.68 1169 0.72
1800 803 0.42 844 0.47 886 0.52 929 0.57 972 0.61 1016 0.64 1060 0.68 1106 0.71 1150 0.74 1189 0.79
1900 831 0.48 872 0.54 915 0.59 957 0.63 1000 0.67 1043 0.71 1087 0.74 1131 0.78 1173 0.81 1208 0.86
Air Volume (cfm)
External Static (in.w.g.)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
900 1112 0.38 1157 0.4 1198 0.43 1236 0.46 1273 0.49 1309 0.52 1344 0.56 1380 0.59 - - - - - - - - - - - -
1000 1119 0.41 1164 0.44 1206 0.47 1244 0.5 1281 0.54 1317 0.57 1352 0.6 1387 0.64 1422 0.67 1458 0.71
1100 1126 0.45 1171 0.48 1213 0.51 1252 0.55 1288 0.58 1324 0.62 1359 0.65 1394 0.69 1429 0.72 1464 0.76
1200 1136 0.49 1180 0.52 1221 0.56 1259 0.6 1296 0.63 1331 0.67 1365 0.7 1400 0.74 1435 0.78 1471 0.81
1300 1148 0.53 1190 0.57 1230 0.61 1268 0.65 1304 0.68 1338 0.72 1372 0.76 1406 0.79 1440 0.83 1476 0.87
1400 1161 0.58 1202 0.62 1240 0.66 1277 0.7 1312 0.74 1346 0.78 1379 0.81 1412 0.85 1446 0.89 1482 0.92
1500 1175 0.64 1214 0.68 1252 0.72 1287 0.76 1321 0.8 1355 0.83 1387 0.87 1420 0.91 1454 0.95 1490 0.99
1600 1190 0.7 1228 0.74 1264 0.78 1298 0.82 1332 0.86 1364 0.9 1397 0.93 1430 0.97 1464 1.01 1499 1.06
1700 1206 0.76 1242 0.8 1277 0.84 1310 0.88 1343 0.92 1375 0.96 1407 1 1440 1.04 1475 1.09 1510 1.13
1800 1223 0.83 1257 0.87 1291 0.91 1324 0.95 1356 0.99 1388 1.03 1420 1.08 1453 1.12 1487 1.16 1523 1.21
1900 1240 0.91 1273 0.95 1306 0.99 1338 1.03 1369 1.07 1401 1.12 1433 1.16 1467 1.2 1501 1.25 1537 1.29
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 37
BLOWER DATA - BELT DRIVE - 4 TONBLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.FOR ALL UNITS ADD: 1 - Any factory installed options air resistance (heat section, economizer, etc.). 2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).See Page 42 for blower motors and drives and wet coil and options/accessory air resistance data.
HORIZONTAL
Air Volume (cfm)
External Static (in.w.g.)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.9 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
900 493 0.12 564 0.14 637 0.17 712 0.19 788 0.21 847 0.24 894 0.27 942 0.3 993 0.33 1046 0.35
1000 520 0.14 589 0.17 660 0.19 733 0.21 805 0.24 861 0.27 907 0.3 954 0.33 1004 0.36 1056 0.38
1100 549 0.16 617 0.19 686 0.22 756 0.24 823 0.27 876 0.3 921 0.33 968 0.37 1017 0.39 1067 0.42
1200 582 0.19 648 0.22 714 0.25 781 0.27 843 0.3 893 0.34 938 0.37 984 0.41 1032 0.43 1081 0.46
1300 624 0.22 686 0.25 747 0.28 808 0.31 865 0.34 912 0.38 956 0.42 1001 0.45 1048 0.48 1096 0.5
1400 670 0.24 726 0.27 782 0.31 837 0.35 887 0.39 932 0.43 975 0.47 1020 0.5 1066 0.52 1112 0.55
1500 714 0.26 765 0.31 814 0.35 863 0.39 910 0.44 953 0.48 996 0.52 1041 0.55 1086 0.58 1130 0.61
1600 752 0.3 798 0.35 844 0.4 889 0.45 933 0.49 975 0.53 1018 0.57 1062 0.6 1107 0.63 1149 0.67
1700 785 0.35 827 0.4 871 0.46 914 0.51 957 0.55 999 0.59 1042 0.63 1085 0.66 1129 0.69 1169 0.73
1800 813 0.42 855 0.47 898 0.52 940 0.57 983 0.62 1025 0.66 1067 0.69 1110 0.72 1152 0.76 1190 0.8
1900 841 0.49 883 0.54 926 0.6 969 0.65 1011 0.69 1052 0.72 1094 0.76 1136 0.79 1176 0.83 1212 0.89
Air Volume (cfm)
External Static (in.w.g.)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
900 1097 0.38 1142 0.41 1182 0.43 1218 0.46 1252 0.49 1284 0.52 1314 0.55 1344 0.57 - - - - - - - - - - - -
1000 1105 0.41 1149 0.44 1190 0.47 1226 0.5 1260 0.53 1292 0.56 1322 0.59 1352 0.62 1381 0.65 1410 0.68
1100 1115 0.45 1158 0.48 1198 0.51 1235 0.55 1269 0.58 1301 0.61 1331 0.64 1360 0.67 1389 0.7 1418 0.73
1200 1126 0.49 1168 0.53 1208 0.56 1244 0.6 1278 0.63 1309 0.66 1340 0.69 1369 0.72 1398 0.75 1426 0.78
1300 1140 0.54 1180 0.57 1218 0.61 1254 0.65 1287 0.68 1319 0.72 1349 0.75 1378 0.78 1407 0.81 1436 0.84
1400 1154 0.59 1193 0.63 1230 0.67 1265 0.7 1298 0.74 1330 0.78 1360 0.81 1389 0.85 1418 0.88 1447 0.91
1500 1170 0.65 1208 0.69 1244 0.73 1278 0.77 1310 0.8 1341 0.84 1371 0.88 1401 0.91 1430 0.95 1459 0.98
1600 1187 0.71 1223 0.75 1258 0.79 1291 0.83 1323 0.87 1354 0.91 1384 0.95 1414 0.99 1443 1.02 1474 1.06
1700 1204 0.78 1240 0.82 1274 0.86 1306 0.9 1338 0.95 1369 0.99 1399 1.03 1429 1.06 1459 1.1 1490 1.14
1800 1223 0.85 1258 0.9 1291 0.94 1323 0.99 1354 1.03 1385 1.07 1415 1.11 1445 1.15 1476 1.19 1507 1.23
1900 1243 0.94 1277 0.99 1309 1.03 1341 1.08 1372 1.12 1402 1.16 1433 1.2 1464 1.24 1495 1.28 1527 1.32
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 38
BLOWER DATA - BELT DRIVE - 5 TON
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.FOR ALL UNITS ADD: 1 - Any factory installed options air resistance (heat section, economizer, etc.). 2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).See Page 42 for blower motors and drives and wet coil and options/accessory air resistance data.
DOWNFLOW
Air Volume (cfm)
External Static (in.w.g.)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.9 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1100 512 0.15 571 0.19 630 0.23 690 0.26 770 0.26 854 0.26 922 0.27 970 0.30 1006 0.35 1045 0.39
1200 535 0.18 593 0.22 651 0.26 710 0.29 788 0.30 868 0.30 933 0.31 978 0.34 1013 0.38 1053 0.42
1300 559 0.22 616 0.26 674 0.29 732 0.32 807 0.34 883 0.34 944 0.35 987 0.38 1022 0.42 1062 0.46
1400 584 0.26 641 0.29 698 0.33 755 0.36 827 0.37 899 0.38 956 0.40 997 0.43 1033 0.47 1072 0.51
1500 615 0.29 671 0.33 726 0.36 782 0.39 850 0.41 917 0.42 970 0.44 1009 0.47 1045 0.52 1085 0.56
1600 665 0.30 716 0.34 768 0.38 819 0.41 879 0.44 937 0.46 985 0.49 1022 0.52 1059 0.57 1098 0.61
1700 723 0.31 768 0.35 814 0.39 860 0.43 910 0.47 959 0.50 1001 0.54 1037 0.58 1074 0.62 1113 0.66
1800 779 0.32 818 0.37 857 0.41 897 0.46 939 0.50 980 0.55 1018 0.59 1054 0.64 1091 0.68 1129 0.72
1900 826 0.36 859 0.41 894 0.45 928 0.50 964 0.56 1000 0.61 1036 0.66 1072 0.70 1109 0.75 1146 0.79
2000 857 0.42 889 0.47 920 0.52 952 0.57 986 0.62 1020 0.68 1055 0.73 1091 0.77 1128 0.82 1164 0.86
2100 878 0.49 909 0.54 940 0.59 973 0.64 1006 0.70 1041 0.75 1076 0.80 1112 0.85 1148 0.89 1185 0.93
2200 897 0.55 929 0.61 961 0.66 994 0.72 1028 0.78 1063 0.83 1099 0.89 1134 0.93 1170 0.97 1206 1.01
2300 918 0.62 950 0.68 983 0.74 1017 0.80 1052 0.86 1087 0.92 1122 0.97 1157 1.02 1193 1.06 1228 1.09
2400 941 0.70 974 0.77 1008 0.83 1042 0.90 1077 0.96 1111 1.01 1146 1.06 1181 1.11 1216 1.15 1250 1.19
Air Volume (cfm)
External Static (in.w.g.)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1100 1089 0.43 1134 0.46 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
1200 1095 0.46 1139 0.50 1186 0.53 1230 0.57 1266 0.60 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
1300 1104 0.50 1146 0.54 1192 0.57 1234 0.60 1269 0.64 1301 0.68 1334 0.71 1367 0.75 - - - - - - - - - - - -
1400 1114 0.55 1155 0.58 1199 0.61 1240 0.65 1275 0.68 1305 0.72 1338 0.76 1372 0.80 1406 0.83 1440 0.87
1500 1125 0.60 1165 0.63 1208 0.66 1248 0.69 1281 0.73 1311 0.77 1344 0.81 1378 0.85 1412 0.89 1446 0.92
1600 1138 0.65 1177 0.68 1218 0.71 1257 0.75 1290 0.79 1319 0.83 1352 0.87 1385 0.91 1418 0.95 1452 0.98
1700 1152 0.70 1190 0.74 1231 0.77 1268 0.80 1299 0.84 1328 0.89 1360 0.93 1393 0.97 1426 1.01 1459 1.05
1800 1167 0.76 1205 0.80 1244 0.83 1280 0.87 1310 0.91 1338 0.95 1370 0.99 1402 1.04 1434 1.08 1466 1.11
1900 1183 0.82 1221 0.86 1260 0.90 1294 0.94 1323 0.98 1349 1.02 1380 1.07 1412 1.11 1443 1.15 1475 1.19
2000 1201 0.89 1239 0.93 1276 0.97 1310 1.01 1336 1.06 1362 1.10 1392 1.15 1423 1.19 1454 1.23 1485 1.27
2100 1221 0.97 1258 1.01 1294 1.05 1325 1.09 1351 1.14 1376 1.19 1406 1.23 1436 1.27 1466 1.31 1497 1.35
2200 1242 1.05 1277 1.09 1311 1.14 1341 1.18 1365 1.23 1390 1.28 1420 1.32 1450 1.36 1480 1.41 1510 1.45
2300 1262 1.14 1295 1.19 1327 1.24 1355 1.29 1380 1.33 1406 1.37 1435 1.42 1465 1.46 1494 1.50 1524 1.54
2400 1282 1.24 1313 1.30 1343 1.36 1371 1.40 1396 1.44 1423 1.48 1452 1.52 1481 1.56 1510 1.60 1540 1.64
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 39
BLOWER DATA - BELT DRIVE - 5 TON
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.FOR ALL UNITS ADD: 1 - Any factory installed options air resistance (heat section, economizer, etc.). 2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).See Page 42 for blower motors and drives and wet coil and options/accessory air resistance data.
HORIZONTAL
Air Volume (cfm)
External Static (in.w.g.)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.9 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1100 509 0.15 562 0.18 624 0.20 691 0.22 771 0.24 852 0.25 919 0.28 970 0.31 1010 0.35 1049 0.38
1200 535 0.18 589 0.21 650 0.23 715 0.25 792 0.27 869 0.29 932 0.32 980 0.35 1019 0.38 1058 0.42
1300 564 0.21 618 0.24 678 0.27 741 0.29 815 0.31 887 0.33 946 0.36 991 0.39 1030 0.43 1068 0.47
1400 604 0.24 657 0.27 715 0.30 775 0.33 842 0.35 908 0.37 962 0.40 1004 0.43 1042 0.47 1080 0.51
1500 656 0.26 706 0.30 760 0.33 814 0.36 874 0.39 931 0.41 979 0.45 1019 0.48 1056 0.53 1094 0.57
1600 712 0.29 758 0.32 807 0.36 855 0.39 906 0.43 955 0.46 997 0.50 1035 0.54 1071 0.58 1109 0.62
1700 766 0.32 808 0.36 850 0.40 892 0.44 936 0.47 978 0.51 1016 0.56 1052 0.60 1088 0.64 1126 0.68
1800 814 0.36 851 0.40 888 0.44 925 0.49 963 0.53 1000 0.57 1035 0.62 1071 0.66 1107 0.70 1143 0.74
1900 853 0.41 886 0.46 919 0.50 952 0.55 986 0.60 1021 0.64 1056 0.69 1091 0.73 1126 0.77 1163 0.81
2000 883 0.48 913 0.53 944 0.57 976 0.62 1009 0.67 1043 0.71 1078 0.76 1112 0.80 1148 0.84 1183 0.88
2100 906 0.56 936 0.60 967 0.65 999 0.70 1033 0.75 1067 0.79 1101 0.84 1135 0.88 1170 0.92 1206 0.96
2200 930 0.64 960 0.68 991 0.73 1024 0.78 1058 0.83 1092 0.88 1126 0.92 1160 0.96 1195 1.00 1230 1.04
2300 954 0.72 985 0.77 1017 0.82 1051 0.87 1085 0.92 1119 0.96 1152 1.00 1186 1.04 1220 1.08 1254 1.13
2400 981 0.81 1013 0.86 1046 0.91 1079 0.96 1113 1.00 1146 1.05 1180 1.09 1213 1.13 1245 1.18 1278 1.22
Air Volume (cfm)
External Static (in.w.g.)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1100 1091 0.42 1134 0.45 1176 0.48 1218 0.51 1258 0.54 1297 0.57 1335 0.59 - - - - - - - - - - - - - - - - - -
1200 1099 0.46 1141 0.49 1182 0.52 1223 0.55 1263 0.58 1302 0.61 1339 0.64 1376 0.67 1410 0.70 1444 0.72
1300 1108 0.50 1149 0.53 1190 0.56 1230 0.59 1270 0.63 1308 0.66 1345 0.70 1381 0.73 1415 0.75 1449 0.78
1400 1120 0.55 1160 0.58 1200 0.61 1240 0.65 1278 0.68 1315 0.72 1352 0.75 1387 0.78 1421 0.81 1454 0.84
1500 1133 0.60 1172 0.63 1212 0.67 1250 0.70 1288 0.74 1324 0.77 1360 0.81 1394 0.84 1428 0.87 1460 0.90
1600 1147 0.66 1186 0.69 1225 0.72 1263 0.76 1299 0.80 1334 0.83 1369 0.87 1402 0.90 1435 0.94 1467 0.96
1700 1164 0.72 1202 0.75 1240 0.78 1276 0.82 1311 0.86 1345 0.90 1379 0.93 1411 0.97 1443 1.00 1475 1.03
1800 1181 0.78 1219 0.81 1256 0.85 1291 0.89 1324 0.93 1357 0.97 1390 1.00 1421 1.04 1453 1.07 1483 1.10
1900 1200 0.85 1237 0.88 1273 0.92 1306 0.96 1339 1.00 1371 1.04 1402 1.08 1433 1.11 1463 1.15 1493 1.18
2000 1220 0.92 1257 0.96 1291 1.00 1323 1.04 1354 1.08 1385 1.12 1416 1.16 1446 1.20 1476 1.23 1505 1.26
2100 1242 1.00 1277 1.04 1310 1.08 1340 1.13 1371 1.17 1401 1.21 1431 1.25 1460 1.29 1489 1.32 1519 1.36
2200 1265 1.08 1299 1.13 1330 1.18 1359 1.23 1388 1.27 1418 1.31 1447 1.35 1476 1.39 1504 1.42 1533 1.45
2300 1288 1.17 1320 1.23 1350 1.28 1378 1.34 1406 1.38 1435 1.42 1464 1.46 1492 1.50 1521 1.53 1549 1.56
2400 1311 1.28 1341 1.33 1370 1.40 1397 1.45 1425 1.50 1454 1.54 1482 1.57 1510 1.61 1538 1.64 1567 1.67
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 40
BLOWER DATA - BELT DRIVE - 6 TON
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.FOR ALL UNITS ADD: 1 - Any factory installed options air resistance (heat section, economizer, etc.). 2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).See Page 42 for blower motors and drives and wet coil and options/accessory air resistance data.
DOWNFLOW
Air Volume (cfm)
External Static (in.w.g.)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.9 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1900 480 0.38 512 0.44 545 0.51 579 0.57 614 0.63 648 0.7 683 0.76 719 0.83 752 0.89 781 0.95
2000 493 0.43 525 0.49 558 0.56 592 0.62 626 0.68 659 0.75 693 0.81 728 0.88 759 0.94 788 1
2100 507 0.48 539 0.54 572 0.61 605 0.67 639 0.74 671 0.8 704 0.86 737 0.93 768 0.99 795 1.04
2200 522 0.53 554 0.6 587 0.66 619 0.73 652 0.79 684 0.86 716 0.92 747 0.98 777 1.04 803 1.1
2300 537 0.59 569 0.65 602 0.72 634 0.79 666 0.85 697 0.91 728 0.98 758 1.04 786 1.1 812 1.15
2400 553 0.65 585 0.71 617 0.78 649 0.85 680 0.91 711 0.98 740 1.04 769 1.1 796 1.15 821 1.21
2500 570 0.71 602 0.78 633 0.84 665 0.91 695 0.97 725 1.04 753 1.1 781 1.16 807 1.22 832 1.27
2600 588 0.77 619 0.84 650 0.91 680 0.97 710 1.04 739 1.1 767 1.16 793 1.22 818 1.28 842 1.33
2700 607 0.84 637 0.91 667 0.97 697 1.04 726 1.11 753 1.17 780 1.23 806 1.29 830 1.35 854 1.4
2800 626 0.91 655 0.97 684 1.04 713 1.11 741 1.18 768 1.24 794 1.3 819 1.36 842 1.42 866 1.47
2900 646 0.98 674 1.05 702 1.11 730 1.18 757 1.25 783 1.32 808 1.38 832 1.44 855 1.49 878 1.54
Air Volume (cfm)
External Static (in.w.g.)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1900 807 1 832 1.04 857 1.07 883 1.11 912 1.14 941 1.17 968 1.21 993 1.25 1017 1.29 1039 1.34
2000 813 1.04 838 1.08 862 1.12 889 1.15 917 1.19 945 1.22 972 1.26 997 1.3 1020 1.35 1042 1.4
2100 820 1.09 844 1.13 869 1.17 895 1.21 923 1.24 951 1.28 977 1.32 1001 1.36 1024 1.41 1046 1.46
2200 828 1.14 852 1.18 877 1.22 903 1.26 930 1.3 957 1.33 983 1.37 1006 1.42 1028 1.47 1050 1.53
2300 836 1.2 861 1.24 885 1.28 911 1.31 938 1.35 964 1.39 989 1.43 1012 1.48 1033 1.54 1054 1.6
2400 846 1.25 870 1.29 895 1.33 920 1.37 947 1.41 972 1.45 996 1.5 1018 1.55 1039 1.61 1059 1.67
2500 856 1.31 880 1.35 905 1.39 930 1.43 956 1.47 980 1.52 1003 1.57 1024 1.63 1044 1.69 1064 1.76
2600 866 1.38 891 1.42 915 1.46 940 1.5 965 1.54 988 1.59 1010 1.65 1031 1.71 1050 1.78 1069 1.84
2700 878 1.44 902 1.48 926 1.52 950 1.57 974 1.61 997 1.67 1018 1.73 1037 1.8 1056 1.87 1075 1.93
2800 889 1.51 913 1.55 937 1.59 961 1.64 984 1.69 1006 1.75 1026 1.82 1044 1.89 1063 1.96 1081 2.03
2900 902 1.58 925 1.63 949 1.67 972 1.72 994 1.78 1015 1.84 1034 1.91 1052 1.99 1069 2.06 1087 2.13
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 41
BLOWER DATA - BELT DRIVE - 6 TON
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.FOR ALL UNITS ADD: 1 - Any factory installed options air resistance (heat section, economizer, etc.). 2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).See Page 42 for blower motors and drives and wet coil and options/accessory air resistance data.
HORIZONTAL
Air Volume (cfm)
External Static (in.w.g.)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.9 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1900 507 0.55 538 0.58 571 0.6 604 0.63 639 0.66 673 0.7 707 0.74 740 0.78 772 0.82 802 0.86
2000 522 0.59 554 0.62 586 0.64 620 0.67 653 0.71 687 0.74 720 0.78 752 0.82 783 0.87 812 0.91
2100 539 0.63 571 0.66 603 0.69 636 0.72 669 0.75 702 0.79 734 0.83 765 0.88 795 0.92 823 0.97
2200 557 0.68 588 0.71 620 0.74 652 0.77 685 0.81 717 0.84 748 0.89 778 0.93 807 0.98 834 1.03
2300 576 0.73 607 0.76 638 0.79 670 0.83 701 0.86 733 0.9 763 0.95 792 0.99 820 1.04 846 1.09
2400 596 0.79 626 0.82 657 0.85 688 0.89 718 0.92 749 0.96 778 1.01 806 1.06 833 1.11 858 1.16
2500 616 0.85 645 0.88 676 0.91 706 0.95 736 0.99 765 1.03 794 1.08 821 1.13 847 1.18 871 1.23
2600 636 0.91 665 0.94 695 0.98 724 1.02 754 1.06 782 1.1 809 1.15 836 1.2 861 1.25 885 1.3
2700 657 0.97 685 1.01 714 1.04 743 1.08 771 1.13 799 1.17 826 1.22 851 1.27 875 1.32 899 1.37
2800 677 1.03 706 1.07 734 1.11 762 1.16 790 1.2 816 1.25 842 1.3 867 1.35 890 1.4 913 1.45
2900 698 1.1 726 1.14 754 1.19 781 1.23 808 1.28 834 1.33 859 1.38 883 1.43 906 1.48 928 1.54
Air Volume (cfm)
External Static (in.w.g.)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1900 830 0.91 857 0.95 883 0.99 910 1.04 937 1.09 964 1.13 991 1.18 1017 1.23 1042 1.28 1067 1.34
2000 839 0.96 865 1 891 1.05 917 1.09 944 1.14 970 1.19 996 1.24 1022 1.29 1047 1.34 1071 1.4
2100 849 1.02 874 1.06 900 1.11 926 1.15 952 1.2 978 1.25 1003 1.3 1028 1.35 1052 1.41 1075 1.46
2200 860 1.08 885 1.12 910 1.17 935 1.21 960 1.26 986 1.31 1010 1.36 1034 1.42 1058 1.48 1081 1.53
2300 871 1.14 895 1.19 920 1.23 945 1.28 969 1.33 994 1.38 1018 1.43 1042 1.49 1065 1.55 1087 1.61
2400 883 1.21 907 1.25 931 1.3 955 1.35 979 1.4 1003 1.45 1027 1.51 1050 1.57 1072 1.63 1094 1.69
2500 895 1.28 919 1.32 942 1.37 966 1.42 990 1.48 1013 1.53 1036 1.59 1059 1.65 1081 1.71 1102 1.78
2600 908 1.35 931 1.4 955 1.45 978 1.5 1001 1.56 1024 1.62 1046 1.68 1068 1.74 1089 1.8 1110 1.87
2700 922 1.43 945 1.48 967 1.53 990 1.59 1013 1.65 1035 1.71 1056 1.77 1078 1.84 1099 1.9 1119 1.96
2800 936 1.51 958 1.56 980 1.62 1003 1.68 1025 1.74 1046 1.8 1067 1.87 1088 1.93 1109 2 1129 2.06
2900 950 1.6 972 1.66 994 1.72 1016 1.78 1037 1.84 1058 1.91 1079 1.97 1099 2.04 1119 2.11 1139 2.17
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 42
FACTORY INSTALLED OPTIONS/FIELD INSTALLED ACCESSORY AIR RESISTANCE - in. w.g.Air
Volume cfm
Wet Indoor Coil Humiditrol Dehumidification
Coil
Electric Heat Economizer
Filters
036 048 060, 072, 074 MERV 8 MERV 13
036-048 MODELS800 0.01 0.01 - - - 0.00 0.01 0.04 0.04 0.05
1000 0.02 0.02 - - - 0.00 0.03 0.04 0.04 0.071200 0.03 0.04 - - - 0.01 0.06 0.04 0.04 0.071400 0.04 0.05 - - - 0.02 0.09 0.04 0.04 0.071600 0.05 0.06 - - - 0.03 0.12 0.04 0.04 0.071800 0.06 0.07 - - - 0.04 0.15 0.05 0.04 0.072000 0.08 0.09 - - - 0.04 0.18 0.05 0.05 0.08
060, 072, 074 MODELS1000 - - - - - - 0.02 0.00 0.01 0.04 0.03 0.051200 - - - - - - 0.04 0.00 0.03 0.04 0.03 0.071400 - - - - - - 0.05 0.01 0.06 0.04 0.04 0.071600 - - - - - - 0.07 0.02 0.09 0.04 0.04 0.071800 - - - - - - 0.08 0.02 0.12 0.05 0.05 0.072000 - - - - - - 0.10 0.03 0.15 0.05 0.05 0.072200 - - - - - - 0.11 0.04 0.18 0.05 0.05 0.082400 - - - - - - 0.13 0.04 0.20 0.05 0.05 0.082600 - - - - - - 0.15 0.05 0.22 0.06 0.05 0.082800 - - - - - - 0.16 0.05 0.24 0.06 0.05 0.083000 - - - - - - 0.18 0.06 0.28 0.06 0.05 0.08
BLOWER DATABELT DRIVE KIT SPECIFICATIONS - 036-060
Model No.
Motor HP No. of Speeds
Drive Kits and RPM RangeNominal Maximum A01 A02 A03 A05 A06 A07
036 0.75 0.86 2 low 449-673 high 673-1010
- - - - - - - - - - - - - - -
1 1.15 2 - - - - - - - - - low 598-897 high 897-1346
- - - - - -
048 0.75 0.86 2 - - - low 497-673 high 745-1117
- - - - - - - - - - - -
2 2.3 2 - - - - - - - - - - - - low 714-953 high 1071-1429
- - -
060 1 1.15 2 - - - - - - low 555-833 high 833-1250
- - - - - - - - -
2 2.3 2 - - - - - - - - - - - - - - - low 808-1032 high 1212-1548
BELT DRIVE KIT SPECIFICATIONS - 072-074Model
No.Motor HP No. of
SpeedsDrive Kits and RPM Range
Nominal Maximum AA01 AA02 AA03072 1 1.15 1 522-784 - - - - - -
2 2.3 1 - - - 632-875 798-1105074 1 1.15 2 522-784 - - - - - -
2 2.3 2 - - - 632-875 798-1105
POWER EXHAUST FAN PERFORMANCE Return Air System Static
Pressure in. w.g.
Air Volume Exhausted cfm
0.00 20000.05 19900.10 19240.15 18100.20 16640.25 15070.30 13500.35 1210
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 43
BLOWER DATACEILING DIFFUSERS AIR RESISTANCE (in. w.g.)
Air Volume cfm
RTD9-65S Step-Down Diffuser FD9-65S Flush
Diffuser
RTD11-95S Step-Down Diffuser FD11-95S Flush
Diffuser2 Ends Open
1 Side & 2 Ends Open
All Ends & Sides Open
2 Ends Open
1 Side & 2 Ends Open
All Ends & Sides Open
800 0.15 0.13 0.11 0.11 - - - - - - - - - - - -
1000 0.19 0.16 0.14 0.14 - - - - - - - - - - - -
1200 0.25 0.20 0.17 0.17 - - - - - - - - - - - -
1400 0.33 0.26 0.20 0.20 - - - - - - - - - - - -
1600 0.43 0.32 0.20 0.24 - - - - - - - - - - - -
1800 0.56 0.40 0.30 0.30 0.13 0.11 0.09 0.09
2000 0.73 0.50 0.36 0.36 0.15 0.13 0.11 0.10
2200 0.95 0.63 0.44 0.44 0.18 0.15 0.12 0.12
2400 - - - - - - - - - - - - - 0.21 0.18 0.15 0.14
2600 - - - - - - - - - - - - - 0.24 0.21 0.18 0.17
2800 - - - - - - - - - - - - - 0.27 0.24 0.21 0.20
3000 - - - - - - - - - - - - - 0.32 0.29 0.25 0.25
CEILING DIFFUSER AIR THROW DATA
Air Volume - cfm 1 Effective Throw - ft.
Model No. RTD9-65S FD9-65S
800 10 - 17 14 - 18
1000 10 - 17 15 - 20
1200 11 - 18 16 - 22
1400 12 - 19 17 - 24
1600 12 - 20 18 - 25
1800 13 - 21 20 - 28
2000 14 - 23 21 - 29
2200 16 - 25 22 - 30
Model No. RTD11-95S FD11-95S
2600 24 - 29 19 - 24
2800 25 - 30 20 - 28
3000 27 - 33 21 - 291 Effective throw based on terminal velocities of 75 ft. per minute.
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 44
ELECTRICAL/ELECTRIC HEAT DATA 3 TON
3 TON HIGH EFFICIENCY (R-410A) LCH036H4
1 Voltage - 60hz 208/230V - 1 Ph 208/230V - 3 Ph 460V - 3 Ph 575V - 3 Ph
Compressor Rated Load Amps 15.3 11.6 5.7 4
Locked Rotor Amps 83 73 38 25.6
Outdoor Fan Motor
Full Load Amps 4.1 4.1 2.1 1.6
Power Exhaust (1) 0.33 HP
Full Load Amps 2.4 2.4 1.3 1
Service Outlet 115V GFI (amps) 15 15 15 20
Indoor Blower Motor
Horsepower 0.5 0.5 0.5 0.5
Full Load Amps 4.3 4.3 2.2 1.72 Maximum
Overcurrent Protection
Unit Only 40 30 15 15
With (1) 0.33 HPPower Exhaust
45 35 15 15
3 Minimum Circuit Ampacity
Unit Only 28 23 12 9
With (1) 0.33 HPPower Exhaust
30 26 13 10
ELECTRIC HEAT DATA
Electric Heat Voltage 208V 240V 208V 240V 480V 600V2 Maximum
Overcurrent Protection
Unit+Electric Heat
7.5 kW 4 40 45 30 30 15 15
15 kW 4 80 90 4 45 60 30 25
3 Minimum Circuit Ampacity
Unit+Electric Heat
7.5 kW 40 45 25 28 15 12
15 kW 74 84 45 51 26 21
2 Maximum Overcurrent Protection
Unit+Electric Heat
and (1) 0.33 HPPower Exhaust
7.5 kW 4 45 50 35 35 20 15
15 kW 4 80 90 4 50 60 30 25
3 Minimum Circuit Ampacity
Unit+Electric Heat
and (1) 0.33 HPPower Exhaust
7.5 kW 43 48 28 31 16 13
15 kW 77 87 48 54 27 22
ELECTRICAL ACCESSORIES
Disconnect 7.5 kW 20W21 20W21 20W21 20W21 20W21 20W21
15 kW 20W21 20W21 20W21 20W21 20W21 20W21NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1 Extremes of operating range are plus and minus 10% of line voltage. 2 HACR type breaker or fuse. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. 4 Factory installed circuit breaker not available.
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 45
ELECTRICAL/ELECTRIC HEAT DATA 3 TON
3 TON STANDARD EFFICIENCY (R-410A) LCH036S4
1 Voltage - 60hz 208/230V - 3 Ph 460V - 3 Ph 575V - 3 Ph
Compressor Rated Load Amps 11.6 5.7 4.0
Locked Rotor Amps 73 38 25.6
Outdoor Fan Motor
Full Load Amps 0.9 0.6 0.5
Power Exhaust (1) 0.33 HP
Full Load Amps 2.4 1.3 1
Service Outlet 115V GFI (amps) 15 15 20
Indoor Blower Motor
Horsepower 0.75 1 0.75 1 0.75 1
Full Load Amps 3.5 4.6 1.6 2.1 1.3 1.72 Maximum
Overcurrent Protection
Unit Only 30 30 15 15 15 15
With (1) 0.33 HPPower Exhaust
30 30 15 15 15 15
3 Minimum Circuit Ampacity
Unit Only 19 20 10 10 7 8
With (1) 0.33 HPPower Exhaust
22 23 11 12 8 9
ELECTRIC HEAT DATA
Electric Heat Voltage 208V 240V 208V 240V 480V 480V 600V 600V2 Maximum
Overcurrent Protection
Unit+Electric Heat
7.5 kW 30 30 30 30 15 15 15 15
15 kW 4 45 50 4 45 60 25 30 20 25
3 Minimum Circuit Ampacity
Unit+Electric Heat
7.5 kW 24 27 26 29 14 14 11 12
15 kW 44 50 45 51 25 26 20 21
2 Maximum Overcurrent Protection
Unit+Electric Heat
and (1) 0.33 HPPower Exhaust
7.5 kW 30 30 4 30 35 15 20 15 15
15 kW 4 50 60 4 50 60 30 30 25 25
3 Minimum Circuit Ampacity
Unit+Electric Heat
and (1) 0.33 HPPower Exhaust
7.5 kW 27 30 29 32 15 16 12 13
15 kW 47 53 48 54 27 27 21 22
ELECTRICAL ACCESSORIES
Disconnect 7.5 kW 20W21 20W21 20W21 20W21 20W21 20W21 20W21 20W21
15 kW 20W21 20W21 20W21 20W21 20W21 20W21 20W21 20W21NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1 Extremes of operating range are plus and minus 10% of line voltage. 2 HACR type breaker or fuse. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. 4 Factory installed circuit breaker not available.
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 46
ELECTRICAL/ELECTRIC HEAT DATA 4 TON
4 TON HIGH EFFICIENCY (R-410A) LCH048H4
1 Voltage - 60hz 208/230V - 1 Ph 208/230V - 3 Ph 460V - 3 Ph 575V - 3 Ph
Compressor Rated Load Amps 21.2 14 6.4 4.6
Locked Rotor Amps 104 83.1 41 33
Outdoor Fan Motor
Full Load Amps 4.1 4.1 2.1 1.6
Power Exhaust (1) 0.33 HP
Full Load Amps 2.4 2.4 1.3 1
Service Outlet 115V GFI (amps) 15 15 15 20
Indoor Blower Motor
Horsepower 0.75 0.75 0.75 0.75
Full Load Amps 6.1 6.1 3.1 2.42 Maximum
Overcurrent Protection
Unit Only 50 40 15 15
With (1) 0.33 HPPower Exhaust
60 40 20 15
3 Minimum Circuit Ampacity
Unit Only 37 28 14 10
With (1) 0.33 HPPower Exhaust
40 31 15 11
ELECTRIC HEAT DATA
Electric Heat Voltage 208V 240V 208V 240V 480V 600V2 Maximum
Overcurrent Protection
Unit+Electric Heat
7.5 kW 50 50 40 40 20 15
15 kW 4 80 90 4 50 60 30 25
3 Minimum Circuit Ampacity
Unit+Electric Heat
7.5 kW 42 47 28 31 16 13
15 kW 76 86 47 53 27 22
2 Maximum Overcurrent Protection
Unit+Electric Heat
and (1) 0.33 HPPower Exhaust
7.5 kW 60 60 40 40 20 15
15 kW 4 80 90 4 50 60 30 25
3 Minimum Circuit Ampacity
Unit+Electric Heat
and (1) 0.33 HPPower Exhaust
7.5 kW 45 50 31 34 17 14
15 kW 79 89 50 56 29 23
ELECTRICAL ACCESSORIES
Disconnect 7.5 kW 20W21 20W21 20W21 20W21 20W21 20W21
15 kW 20W22 20W22 20W21 20W21 20W21 20W21NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1 Extremes of operating range are plus and minus 10% of line voltage. 2 HACR type breaker or fuse. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. 4 Factory installed circuit breaker not available.
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 47
ELECTRICAL/ELECTRIC HEAT DATA 4 TON4 TON STANDARD EFFICIENCY (R-410A) LCH048S41 Voltage - 60hz 208/230V - 3 Ph 460V - 3 Ph 575V - 3 PhCompressor Rated Load Amps 14 6.4 4.6
Locked Rotor Amps 83.1 41 33Outdoor Fan Motor
Full Load Amps 1.7 1.1 0.7
Power Exhaust\ (1) 0.33 HP
Full Load Amps 2.4 1.3 1
Service Outlet 115V GFI (amps) 15 15 20Indoor Blower Motor
Horsepower 0.75 2 0.75 2 0.75 2Full Load Amps 3.5 7.5 1.6 3.4 1.3 2.7
2 Maximum Overcurrent Protection
Unit Only 35 40 15 15 15 15With (1) 0.33 HP
Power Exhaust35 40 15 20 15 15
3 Minimum Circuit Ampacity
Unit Only 23 27 11 13 8 10With (1) 0.33 HP
Power Exhaust26 30 12 14 9 11
ELECTRIC HEAT DATA
Electric Heat Voltage 208V 240V 208V 240V 480V 480V 600V 600V2 Maximum
Overcurrent Protection
Unit+Electric Heat
7.5 kW 35 35 40 40 15 20 15 1515 kW 4 45 50 4 50 60 25 30 20 25
3 Minimum Circuit Ampacity
Unit+Electric Heat
7.5 kW 24 27 29 32 14 16 11 1315 kW 44 50 49 55 25 27 20 22
2 Maximum Overcurrent Protection
Unit+Electric Heat
and (1) 0.33 HPPower Exhaust
7.5 kW 15 35 40 40 15 20 15 1515 kW 4 50 60 60 60 30 30 25 25
3 Minimum Circuit Ampacity
Unit+Electric Heat
and (1) 0.33 HPPower Exhaust
7.5 kW 27 30 32 35 15 18 12 1415 kW 47 53 52 58 27 29 21 23
ELECTRICAL ACCESSORIES
Disconnect 7.5 kW 20W21 20W21 20W21 20W21 20W21 20W21 20W21 20W21
15 kW 20W21 20W21 20W21 20W21 20W21 20W21 20W21 20W21NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1 Extremes of operating range are plus and minus 10% of line voltage. 2 HACR type breaker or fuse. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. 4 Factory installed circuit breaker not available.
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 48
ELECTRICAL/ELECTRIC HEAT DATA 5 TON
5 TON HIGH EFFICIENCY (R-410A) LCH060H4
1 Voltage - 60hz 208/230V - 1 Ph 208/230V - 3 Ph 460V - 3 Ph 575V - 3 Ph
Compressor Rated Load Amps 27.1 16.5 7.2 5.5
Locked Rotor Amps 152.9 110 52 38.9
Outdoor Fan Motor
Full Load Amps 4.1 4.1 2.1 1.6
Power Exhaust (1) 0.33 HP
Full Load Amps 2.4 2.4 1.3 1
Service Outlet 115V GFI (amps) 15 15 15 20
Indoor Blower Motor
Horsepower 1 1 1 1
Full Load Amps 7.4 7.4 3.7 32 Maximum
Overcurrent Protection
Unit Only 70 45 20 15
With (1) 0.33 HPPower Exhaust
70 50 20 15
3 Minimum Circuit Ampacity
Unit Only 46 33 15 12
With (1) 0.33 HPPower Exhaust
48 35 17 13
ELECTRIC HEAT DATA
Electric Heat Voltage 208V 240V 208V 240V 480V 600V2 Maximum
Overcurrent Protection
Unit+Electric Heat
7.5 kW 70 70 45 45 20 15
15 kW 4 80 90 4 50 60 30 25
22.5 kW 4 125 150 4 70 80 40 353 Minimum
Circuit Ampacity
Unit+Electric Heat
7.5 kW 46 49 33 33 16 13
15 kW 77 88 49 55 28 22
22.5 kW 111 127 68 77 39 312 Maximum
Overcurrent Protection
Unit+Electric Heat
and (1) 0.33 HPPower Exhaust
7.5 kW 70 70 50 50 20 15
15 kW 4 80 100 60 60 30 25
22.5 kW 4 125 150 80 80 45 35
3 Minimum Circuit Ampacity
Unit+Electric Heat
and (1) 0.33 HPPower Exhaust
7.5 kW 48 52 35 35 18 15
15 kW 80 91 52 58 29 24
22.5 kW 114 130 71 80 41 33
ELECTRICAL ACCESSORIES
Disconnect 7.5 kW 20W24 20W24 20W24 20W24 20W24 20W24
15 kW 20W25 20W25 20W24 20W24 20W24 20W24
22.5 kW 20W25 20W25 20W24 20W24 20W24 20W24NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1 Extremes of operating range are plus and minus 10% of line voltage. 2 HACR type breaker or fuse. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. 4 Factory installed circuit breaker not available.
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 49
ELECTRICAL/ELECTRIC HEAT DATA 5 TON
5 TON STANDARD EFFICIENCY (R-410A) LCH060S4
1 Voltage - 60hz 208/230V - 3 Ph 460V - 3 Ph 575V - 3 Ph
Compressor Rated Load Amps 16.5 7.2 5.5
Locked Rotor Amps 110 52 38.9
Outdoor Fan Motor
Full Load Amps 2.4 1.3 1
Power Exhaust (1) 0.33 HP
Full Load Amps 2.4 1.3 1
Service Outlet 115V GFI (amps) 15 15 20
Indoor Blower Motor
Horsepower 1 2 1 2 1 2
Full Load Amps 4.6 7.5 2.1 3.4 1.7 2.72 Maximum
Overcurrent Protection
Unit Only 40 45 15 20 15 15
With (1) 0.33 HPPower Exhaust
45 45 20 20 15 15
3 Minimum Circuit Ampacity
Unit Only 28 31 13 14 10 11
With (1) 0.33 HPPower Exhaust
31 33 14 16 11 12
ELECTRIC HEAT DATA
Electric Heat Voltage 208V 240V 208V 240V 480V 480V 600V 600V2 Maximum
Overcurrent Protection
Unit+Electric Heat
7.5 kW 40 40 45 45 15 20 15 15
15 kW 4 45 60 4 50 60 30 30 25 25
22.5 kW 4 70 80 4 70 80 40 40 30 353 Minimum
Circuit Ampacity
Unit+Electric Heat
7.5 kW 28 29 31 32 14 16 12 13
15 kW 45 51 49 55 26 27 21 22
22.5 kW 65 74 69 78 37 39 30 312 Maximum
Overcurrent Protection
Unit+Electric Heat
and (1) 0.33 HPPower Exhaust
7.5 kW 45 45 45 45 20 20 15 15
15 kW 4 50 60 60 60 30 30 25 25
22.5 kW 4 70 80 4 80 90 40 40 35 35
3 Minimum Circuit Ampacity
Unit+Electric Heat
and (1) 0.33 HPPower Exhaust
7.5 kW 31 32 33 35 16 18 13 14
15 kW 48 54 52 58 27 29 22 23
22.5 kW 68 77 72 81 39 40 31 32
ELECTRICAL ACCESSORIES
Disconnect 7.5 kW 20W24 20W24 20W24 20W24 20W24 20W24 20W24 20W24
15 kW 20W24 20W24 20W24 20W24 20W24 20W24 20W24 20W24
22.5 kW 20W24 20W24 20W24 20W24 20W24 20W24 20W24 20W24NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1 Extremes of operating range are plus and minus 10% of line voltage. 2 HACR type breaker or fuse. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. 4 Factory installed circuit breaker not available.
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 50
ELECTRICAL/ELECTRIC HEAT DATA 6 TON
6 TON HIGH EFFICIENCY (R-410A) LCH072H4
1 Voltage - 60hz 208/230V - 3 Ph 460V - 3 Ph 575V - 3 Ph
Compressor Rated Load Amps 19.6 8.2 6.6
Locked Rotor Amps 136 66.1 55.3
Outdoor Fan Motor
Full Load Amps 2.4 1.3 1
Power Exhaust (1) 0.33 HP
Full Load Amps 2.4 1.3 1
Service Outlet 115V GFI (amps) 15 15 20
Indoor Blower Motor
Horsepower 1 2 1 2 1 2
Full Load Amps 4.6 7.5 2.1 3.4 1.7 2.72 Maximum
Overcurrent Protection
Unit Only 50 50 20 20 15 15
With (1) 0.33 HPPower Exhaust
50 50 20 20 15 15
3 Minimum Circuit Ampacity
Unit Only 32 35 14 15 11 12
With (1) 0.33 HPPower Exhaust
34 37 15 17 12 13
ELECTRIC HEAT DATA
Electric Heat Voltage 208V 240V 208V 240V 480V 480V 600V 600V2 Maximum
Overcurrent Protection
Unit+Electric Heat
7.5 kW 50 50 50 50 20 20 15 15
15 kW 4 50 60 4 50 60 30 30 25 25
22.5 kW 4 70 80 4 70 80 40 40 30 35
30 kW 4 90 100 4 90 100 50 50 40 403 Minimum
Circuit Ampacity
Unit+Electric Heat
7.5 kW 32 32 35 35 14 16 12 13
15 kW 45 51 49 55 26 27 21 22
22.5 kW 65 74 69 78 37 39 30 31
30 kW 84 96 88 100 48 50 39 402 Maximum
Overcurrent Protection
Unit+Electric Heat
and (1) 0.33 HPPower Exhaust
7.5 kW 50 50 50 50 20 20 15 15
15 kW 4 50 60 60 60 30 30 25 25
22.5 kW 4 70 80 4 80 90 40 40 35 35
30 kW 4 90 100 4 100 110 50 60 40 453 Minimum
Circuit Ampacity
Unit+Electric Heat
and (1) 0.33 HPPower Exhaust
7.5 kW 34 34 37 37 16 18 13 14
15 kW 48 54 52 58 27 29 22 23
22.5 kW 68 77 72 81 39 40 31 32
30 kW 87 99 91 103 50 51 40 41
ELECTRICAL ACCESSORIES
Disconnect 7.5 kW 20W24 20W24 20W24 20W24 20W24 20W24 20W24 20W24
15 kW 20W24 20W24 20W24 20W24 20W24 20W24 20W24 20W24
22.5 kW 20W24 20W24 20W24 20W24 20W24 20W24 20W24 20W24
30 kW 20W25 20W25 20W25 20W24 20W24 20W24 20W24 20W24NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1 Extremes of operating range are plus and minus 10% of line voltage. 2 HACR type breaker or fuse. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. 4 Factory installed circuit breaker not available.
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 51
ELECTRICAL/ELECTRIC HEAT DATA 6 TON
6 TON HIGH EFFICIENCY (R-410A) LCH074H4
1 Voltage - 60hz 208/230V - 3 Ph 460V - 3 Ph 575V - 3 Ph
Compressor Rated Load Amps 17.6 8.5 6.3
Locked Rotor Amps 136 66.1 55.3
Outdoor FanMotor
Full Load Amps 2.4 1.3 1
Power Exhaust(1) 0.33 HP
Full Load Amps 2.4 1.3 1
Service Outlet 115V GFI (amps) 15 15 20
Indoor BlowerMotor
Horsepower 1 2 1 2 1 2
Full Load Amps 4.6 7.5 2.1 3.4 1.7 2.72 MaximumOvercurrentProtection
Unit Only 45 45 20 20 15 15
With (1) 0.33 HPPower Exhaust
45 50 20 25 15 15
3 MinimumCircuitAmpacity
Unit Only 29 32 15 16 11 12
With (1) 0.33 HPPower Exhaust
32 35 16 17 12 13
ELECTRIC HEAT DATA
Electric Heat Voltage 208V 240V 208V 240V 480V 480V 600V 600V2 MaximumOvercurrentProtection
Unit+Electric Heat
7.5 kW 45 45 45 45 20 20 15 15
15 kW 4 45 60 4 50 60 30 30 25 25
22.5 kW 4 70 80 4 70 80 40 40 30 35
30 kW 4 90 100 4 90 100 50 50 40 403 MinimumCircuitAmpacity
Unit+Electric Heat
7.5 kW 29 29 32 32 15 16 12 13
15 kW 45 51 49 55 26 27 21 22
22.5 kW 65 74 69 78 37 39 30 31
30 kW 84 96 88 100 48 50 39 402 MaximumOvercurrentProtection
Unit+Electric Heat
and (1) 0.33 HPPower Exhaust
7.5 kW 45 45 50 50 20 25 15 15
15 kW 4 50 60 60 60 30 30 25 25
22.5 kW 4 70 80 4 80 90 40 40 35 35
30 kW 4 90 100 4 100 110 50 60 40 453 MinimumCircuitAmpacity
Unit+Electric Heat
and (1) 0.33 HPPower Exhaust
7.5 kW 32 32 35 35 16 18 13 14
15 kW 48 54 52 58 27 29 22 23
22.5 kW 68 77 72 81 39 40 31 32
30 kW 87 99 91 103 50 51 40 41
ELECTRICAL ACCESSORIES
Disconnect 7.5 kW 20W24 20W24 20W24 20W24 20W24 20W24 20W24 20W24
15 kW 20W24 20W24 20W24 20W24 20W24 20W24 20W24 20W24
22.5 kW 20W24 20W24 20W24 20W24 20W24 20W24 20W24 20W24
30 kW 20W25 20W25 20W25 20W24 20W24 20W24 20W24 20W24NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.1 Extremes of operating range are plus and minus 10% of line voltage.2 HACR type breaker or fuse.3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.4 Factory installed circuit breaker not available.
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 52
B
D
C
A
OUTDOOR AIRHOOD
1 Unit ClearanceA B C D Top
Clearancein. mm in. mm in. mm in. mmService Clearance 36 914 36 914 36 934 36 914
UnobstructedMinimum Operation Clearance 36 914 36 914 36 914 36 914NOTE - Entire perimeter of unit base requires support when elevated above the mounting surface.1 Service Clearance - Required for removal of serviceable parts.
Minimum Operation Clearance - Required clearance for proper unit operation.
UNIT CLEARANCES - INCHES (MM)
ELECTRIC HEAT CAPACITIES
Input Voltage
7.5 kW 15 kW 22.5 kW 30 kWNo of
Stages kW
input Btuh
Output No of
Stages kW
input Btuh
Output No of
Stages kW
input Btuh
Output No of
Stages kW
input Btuh
Output 208 1 5.6 19,200 1 11.2 38,200 1 16.9 57,700 1 22.5 76,800220 1 6.3 21,500 1 12.6 43,000 1 18.9 64,500 1 25.2 86,000230 1 6.9 23,500 1 13.8 47,000 1 20.7 70,700 1 27.5 93,900240 1 7.5 25,600 1 15 51,200 1 22.5 76,800 1 30 102,400440 1 6.3 21,500 1 12.6 43,000 1 18.9 64,500 1 25.2 86,000460 1 6.9 23,500 1 13.8 47,000 1 20.7 70,700 1 27.5 93,900480 1 7.5 25,600 1 15 51,200 1 22.5 76,800 1 30 102,400550 1 6.3 21,500 1 12.6 43,000 1 18.9 64,500 1 25.2 86,000575 1 6.9 23,500 1 13.8 47,000 1 20.7 70,700 1 27.5 93,900600 1 7.5 25,600 1 15 51,200 1 22.5 76,800 1 30 102,400
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 53
OPTIONAL CONVENTIONAL TEMPERATURE CONTROL SYSTEMS
Item Model No. (Description)
Catalog No.
COMFORTSENSE® 8500 COMMERCIAL 7-DAY PROGRAMMABLE THERMOSTAT - ZONING/NON-ZONING
• Multi-Stage, Universal Thermostat• Zoning and Non-Zoning Models with or without CO2 Sensing• Intuitive Touchscreen Interface• Menu-driven Programming• Remote Indoor Temperature Sensing (up to nine averaging sensors)• Compressor Short-Cycle Protection• Relative Humidity Sensor• Occupancy Sensor• Outside Air Temperature Display• Scheduling - Two separate schedules for work days or non-work days• Four Time Periods Per Day (non-zoning models, standalone mode)• Scheduled Occupancy Control• Holiday Scheduling• Performance Reports (non-zoning models, standalone mode)• Reminders - Two Custom and Routine System Checkup (non-zoning models)• Dehumidification/Humiditrol® Control• Backlit Display• Wallplate Furnished
C0STAT04FF1L (Zoning)
14X57
C0STAT31FF1L (Zoning with Co2 Sensing)
14X58
C0STAT03FF1L (Non-Zoning)
14X55
C0STAT22FF1L (Non-Zoning
with Co2 Sensing)
14X56
Optional Accessories1 Remote non-adjustable wall mount 10k temperature sensor C0SNZN01AE2 47W371 Remote non-adjustable wall mount 11k temperature sensor C0SNZN08AE1 94L61Locking cover (clear) C0MISC15AE1- 39P211 Up to nine of the same type remote temperature sensors can be connected in parallel.
Zonebus Network Cable (Purple) - Zoning ModelsTwisted pair 100% shielded communication cable, Red and Black 22 AWG, purple jacket, rated at 75°C, 300V, Plenum rated Insulation - Low smoke PVC, NEC, CMP
500 ft. box - C0MISC05AE1- 23W991000 ft. box - C0MISC06AE1- 24W002500 ft. roll - C0MISC07AE1- 24W01
Sysbus Network Cable (Yellow) - Non-Zoning ModelsTwisted pair 100% shielded communication cable, Red and Black 22 AWG, yellow jacket, rated at 75°C, 300V, Plenum rated Insulation - Low smoke PVC, NEC, CMP
500 ft. box - C0MISC00AE1- 27M191000 ft. box - C0MISC04AE1- 94L632500 ft. roll - C0MISC01AE1- 68M25
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 54
OPTIONAL CONVENTIONAL TEMPERATURE CONTROL SYSTEMS
Item Model No.
Catalog No.
COMFORTSENSE® 7500 COMMERCIAL 7-DAY PROGRAMMABLE THERMOSTAT
• Four-Stage Heating / Two-Stage Cooling Universal Multi-Stage• Intuitive Touchscreen Interface• Remote Indoor Temperature Sensing with Averaging• Outside or Discharge Air Temperature Display• Full Seven-Day Programming• Four Time Periods Per Day• Occupancy Scheduling with Economizer Relay Control• Away Mode• Holiday Scheduling• Smooth Setback Recovery (SSR)• Performance Reports• Notifications/Reminders• Dehumidification/Humiditrol® Control for Split Systems and Rooftop Units• Economizer Relay Control• Backlit Display• Wallplate Furnished
C0STAT06FF1L 13H15
Optional Accessories1 Remote non-adjustable wall mount 20k temperature sensor C0SNZN01AE2- 47W361 Remote non-adjustable wall mount 10k temperature sensor C0SNZN73AE1- 47W37Remote non-adjustable discharge air (duct mount) temperature sensor C0SNDC00AE1- 19L22Outdoor temperature sensor C0SNSR03AE1- X2658Locking cover (clear) C0MISC15AE1- 39P211 R emote sensors can be applied in any of the following combinations:
One Sensor - (1) 47W36 Two Sensors - (2) 47W37 Three Sensors - (2) 47W36 and (1) 47W37 Four Sensors - (4) 47W36 Five Sensors - (3) 47W36 and (2) 47W37
COMFORTSENSE® 3000 COMMERCIAL 5-2 DAY PROGRAMMABLE THERMOSTAT
MAINT
Commercial
• Two-Stage Heating / Two-Stage Cooling Conventional Systems• Intuitive Interface• 5-2 Day Programming• Program Hold• Remote Indoor Temperature Sensing• Smooth Setback Recovery (SSR)• Economizer Relay Control• Maintenance/Filter/Service Reminders• Backlit Display• Wallplate Furnished• Simple Up and Down Temperature Control.
C0STAT05FF1L 11Y05
Optional AccessoriesRemote non-adjustable wall mount 10k averaging temperature sensor C0SNZN73AE1- 47W37Optional wall mounting plate C0MISC17AE1- X2659DIGITAL NON-PROGRAMMABLE THERMOSTAT
• One-Stage Heating / Cooling Conventional Systems• Intuitive Interface• Automatic Changeover• Backlit Display• Simple Up and Down Temperature Control.
C0STAT12AE1L 51M32
Optional AccessoriesOutdoor temperature sensor C0SNSR04AE1- X2658Optional wall mounting plate C0MISC17AE1- X2659
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 55
OUTDOOR SOUND DATA
1 Unit Model No.
Octave Band Linear Sound Power Levels dB, re 10-12 Watts Center Frequency - Hz 1 Sound Rating Number (SRN)
dBA125 250 500 1000 2000 4000 8000
036, 048 63 66 70 71 68 62 53 75060, 072, 074 67 72 77 76 73 68 61 82NOTE - The octave sound power data does not include tonal corrections.1 Sound Rating Number according to ARI Standard 270-95 (includes pure tone penalty). “SRN” is the overall A-Weighted Sound Power Level, (Lwa),
dB (100 Hz to 10,000 Hz).
OPTIONS / ACCESSORIESShipping Weight
lbs. kg.ECONOMIZER / OUTDOOR AIR / EXHAUSTEconomizerEconomizer, Includes Outdoor Air Hood and Barometric Relief Dampers with Hood
131 59
Outdoor Air DampersMotorized 40 18Manual 30 14Power ExhaustStandard Static 35 17ELECTRIC HEAT
7.5 kW 31 1415 kW 31 14
22.5 kW 35 1630 kW 35 16
PACKAGINGLTL Packaging (less than truck load) 60 27ROOF CURBSHybrid Roof Curbs, Downflow8 in. height C1CURB70A-1 50 2314 in. height C1CURB71A-1 70 3218 in. height C1CURB72A-1 80 3624 in. height C1CURB73A-1 100 45Adjustable Pitch Curb, Downflow14 in. height 113 51CEILING DIFFUSERSStep-Down RTD9-65S 80 36
RTD11-95S 118 54Flush FD9-65S 80 36
FD11-95S 118 54Transitions T1TRAN10AN1 22 10
T1TRAN20N-1 21 10HUMIDITROL® DEHUMIDIFICATION SYSTEMHumiditrol (net weight) 27 12
WEIGHT DATA
Model Number Outdoor Coil
Net Shipping Outdoor Coil
Net Shippinglbs. kg lbs. kg lbs. kg lbs. kg
036 Base Unit Environ 513 233 574 260 Fin/Tube 532 241 593 269036 Max. Unit Environ 723 328 784 356 Fin/Tube 742 337 803 364048 Base Unit Environ 529 240 590 268 Fin/Tube 562 255 623 283048 Max. Unit Environ 723 328 803 364 Fin/Tube 775 351 836 379060 Base Unit Environ 607 275 668 303 Fin/Tube 649 294 710 322060 Max. Unit Environ 844 383 905 410 Fin/Tube 886 402 947 430072 Base Unit Environ 684 310 745 338 Fin/Tube 726 329 787 357072 Max. Unit Environ 891 404 952 432 Fin/Tube 933 423 994 451074 Base Unit Environ 684 310 745 338 Fin/Tube 726 329 787 357074 Max. Unit Environ 891 404 952 432 Fin/Tube 933 423 994 451
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 56
45(1143)
END VIEW
1 (25)
47 (1194)BASE
38-7
/8 (9
87) 0
36 th
ru 0
4846
-7/8
(119
1) 0
60 th
ru 0
74
DD CC
BBAA
FF
EE
11(279)
16-1/4(413)
18(457)
20(508)
5 (127)
47 (1194)BASE
BOTTOMSUPPLY
AIROPENING
TOP VIEW (Base)
CENTEROF
GRAVITY
9-1/2(241)6-5/8
(168)
26-1/2(673)
5-5/8(143)
29(737)
7 (178) BOTTOMRETURN
AIROPENING
BOTTOMCONDENSATE OUTLET
25-3/4(654)
BOTTOM POWER ENTRY3 X 8 (76 X 203)
18-3/8(467)
19-1/2(495)
5-1/2(140)
FORKLIFT SLOTS(Front, Back and
Blower End)
HORIZONTALRETURN AIR
OPENING(Without Economizer)
HORIZONTALSUPPLY AIR
OPENING
2 (51)11(279)
29(737)
20(508)
5-1/2(140)
BACK VIEW
CONDENSATEOUTLET
(EITHER SIDE)
3-1/2 (89)
83-1/4(2115)
85-1/4 (2165)BASE
26-1/2(673)
5-1/2(140)
LIFTING HOLES(For rigging)
SIDE VIEW
ELECTRICALINLET
1 (25)35-3
/8 (8
99) 0
36 th
ru 0
4843
-3/8
(110
2) 0
60 th
ru 0
74
DIMENSIONS - INCHES (MM)CORNER WEIGHTS CENTER OF GRAVITY
Model No. AA BB CC DD EE FFlbs. kg lbs. kg lbs. kg lbs. kg in. mm in. mm
LCH036 Base Unit 92 42 112 51 180 82 148 67 38.5 978 18 457LCH036 Max. Unit 133 61 151 69 243 110 215 98 40 1016 18 457LCH048 Base Unit 97 44 118 54 190 87 157 71 38.5 978 18 457LCH048 Max. Unit 139 63 158 72 254 115 224 102 40 1016 18 457LCH060 Base Unit 112 51 136 62 219 100 181 82 38.5 978 18 457LCH060 Max. Unit 159 72 180 82 290 132 257 117 40 1016 18 457LCH072 Base Unit 126 57 152 69 246 112 202 92 38.5 978 18 457LCH072 Max. Unit 168 76 190 86 306 139 270 123 40 1016 18 457LCH074 Base Unit 126 57 152 69 246 112 202 92 38.5 978 18 457LCH074 Max Unit 168 76 190 86 306 139 270 123 40 1016 18 457Base Unit - The unit with NO INTERNAL OPTIONS.Max. Unit - The unit with ALL INTERNAL OPTIONS Installed. (Economizer, Standard Static Power Exhaust Fans, Controls, etc.). Does not include accessories external to unit or high static power exhaust.
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 57
ACCESSORY DIMENSIONS - INCHES (MM)
OUTDOOR AIR HOOD DETAIL FOR OPTIONAL ECONOMIZER AND BAROMETRIC RELIEF DAMPERS(Downflow Applications)
OPTIONAL OUTDOORAIR HOOD
(Furnished with Economizer)
OPTIONAL BAROMETRICRELIEF HOOD
(Furnished with Economizer )
17-3/8 (441)
13 (330)
11-3/4(298)
35(889)
19-7/8 (505)
17-3/8 (441)
BAROMETRIC RELIEF HOOD FOR ECONOMIZER (Furnished)OUTDOOR AIR HOOD FOR ECONOMIZER (Furnished)
SIDE VIEW
11-3/4(324)
35(889)
OUTDOOR AIR DAMPER HOOD DETAIL (Downflow or Horizontal Applications)
16-1/2(419)
35 (889)036 thru 04843 (1092)060 / 072
35(889)
13-1/2(343)
10-1/2(267)
OUTDOOR AIRDAMPER HOOD
OPTIONALOUTDOOR
AIR DAMPERSAND PANEL
MANUAL OUTDOOR AIR HOOD
16-1/2(419)
35 (889)036 thru 04843 (1092)060 / 072
35(889)
13-1/2(343)
10-1/2(267)
OUTDOOR AIRDAMPER HOOD
OPTIONALOUTDOOR
AIR DAMPERSAND PANEL
MOTORIZED OUTDOOR AIR HOOD
10-1/2(267)
OUTDOOR AIRDAMPER HOOD
(Furnished)
SIDE VIEW
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 58
ACCESSORY DIMENSIONS - INCHES (MM)
2-1/4(57)
UNIT RETURN AIR DUCTOPENING WITH ECONOMIZER
INSTALLED
30-7/16(773)
7/8(22)
18-3/4 (476)
END VIEW
7/8(22)
2-1/4(57)
OUTDOOR AIR HOOD DETAIL WITH OPTIONAL ECONOMIZER AND BAROMETRIC RELIEF DAMPERS(Horizontal Applications)
NOTE - Return Air Duct and Transition must be supported.
BAROMETRIC RELIEF HOOD DIMENSIONSWidth - 35-1/2 in. (902 mm)Height -21 in. (533 mm)
See previous page for details.
and
Dam
pers
SUPPLY AIR DUCT(Field Provided)
RETURN AIR DUCT(Field Fabricated - Must be sized to
accommodate Barometric ReliefHood and Return Air Requirements)
TOP VIEW
Baro
met
ric R
elie
f Hoo
d
RETURN AIRDUCT TRANSITION(Field fabricated and
installed on unit)
ECONOMIZER DAMPERS
RETURNAIR
INLET
SUPPLYAIR
OUTLET
RETURN AIR DUCT INLET(Field Fabricated - Must be sized to
accommodate Barometric ReliefHood and Return Air Requirements)
5-1/2(140)
19-1/2(495)
BAROMETRIC RELIEF HOOD(Furnished with Economizer andField Installed on Field fabricated
Return Air Duct)
RETURN AIRDUCT TRANSITION(Field fabricated and
installed on unit)
31-3/8(797)
11-3/4 (298)
OUTDOOR AIR HOOD(Furnished with Economizer)
BACK VIEW
EXHAUSTAIR
OUTDOORAIR
HORIZONTALSUPPLY AIR
OPENING
HORIZONTALRETURN AIR
OPENING
This openingnot used inHorizontal
Applicationswith
Economizer20(508)
NOTE - Horizontal applications with Economizer require Horizontal Economizer Conversion Kit.See Options/Accessories table.
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 59
ACCESSORY DIMENSIONS - INCHES (MM)
NOTE - Roof deck may be omitted within confines of curb.
TYPICAL FLASHING DETAIL FOR ROOF CURB
ROOF CURB(Extends around entire
perimeter of unit)
FIBERGLASSINSULATION
(Furnished)COUNTER FLASHING(Field Supplied)
BASE BOTTOM
RIGID INSULATION(Field Supplied)
ROOFINGMATERIAL
CANT STRIP(Field Supplied)
PACKAGEDUNIT
NAILER STRIP(Furnished)
DETAIL ROOF CURB
FACTORY INSTALLEDPERIMETER WOODNAILER STRIP
RETURNOPENING
SUPPLYOPENING
HYBRID ROOF CURBS - DOUBLE DUCT OPENING
79-3/4(2026)
76-1/4(1937)
19-1/8(486)
15-1/8(384)
12-5/8(321)
1-3/4(44)
32(813)
21-1/8(537)
41-1/2(1054)
38(965)
8 (203)14 (356)18 (457)24 (610)
8 (203)14 (356)18 (457)24 (610)
1-3/4(44)
1/2 (13)
1-3/4(44)
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 60
ACCESSORY DIMENSIONS - INCHES (MM)
TYPICAL FLASHING DETAIL FOR ROOF CURB
ROOF CURB(Extends around entire
perimeter of unit)
FIBERGLASSINSULATION
(Furnished)COUNTER FLASHING(Field Supplied)
BASE BOTTOM
RIGID INSULATION(Field Supplied)
ROOFINGMATERIAL
CANT STRIP(Field Supplied)
PACKAGEDUNIT
NAILER STRIP(Furnished)
DETAIL ROOF CURB
FACTORY INSTALLEDPERIMETER WOODNAILER STRIP
RETURNOPENING
ADJUSTABLE PITCH CURBS - DOUBLE DUCT OPENING
SUPPLYOPENING
FACTORY INSTALLEDPERIMETER WOODNAILER STRIP
BOTTOM CURBASSEMBLY
NOTE - Maximum slope pitch is 3/4 in. per 1 foot (19 mm per 305 mm)in any one direction.
19-1/8(486)
15-1/8(384)
12-5/8(321)
32(813)
21-1/8(537)
41-1/2(1054)
38(965)
14 (356)
1-3/4(44)
1/2 (13)
1-3/4(44)
76-1/4(1937)79-3/4
(2026)
14 (356)
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 61
ACCESSORY DIMENSIONS - INCHES (MM)
TRANSITIONS
21-1/8(537)32
(813)
RE
TUR
NO
PE
NIN
G
SUPPLYOPENING
12-5/8(321)
19-1/8(486)
12(305) 31-1/2
(800)
8 (203)
RETURN TRANSITION
T1TRAN10AN-1 - FOR 18 INCH (457 MM) DUCTT1TRAN20N-1 - FOR 20 INCH (508 MM) DUCT
1-1/2 inch (38 mm) T1TRAN10AN-12 inch (51mm) T1TRAN20N-1
18-1/2(470)
20-1/2(521)
8 (203)
SUPPLY TRANSITION
T1TRAN10AN-1 - FOR 18 INCH (457 MM) DUCTT1TRAN20N-1 - FOR 20 INCH (508 MM) DUCT
1-1/2 inch (38 mm) T1TRAN10AN-12 inch (51mm) T1TRAN20N-1
Energence® Packaged Electric / Electric 3 to 6 Ton / Page 62
ACCESSORY DIMENSIONS - INCHES (MM)
COMBINATION CEILING SUPPLY AND RETURN DIFFUSERSSTEP-DOWN CEILING DIFFUSER FLUSH CEILING DIFFUSER
L A
J
C
HH
DG
G
FE
B
K
2 (51)
A
C
HH
DG
G
FE
B
2 (51)
Model Number RTD9-65S RTD11-95SA in. 47-5/8 47-5/8
mm 1159 1159B in. 23-5/8 29-5/8
mm 600 752C in. 11-3/8 14-3/8
mm 289 365D in. 21-1/2 27-1/2
mm 546 699E in. 45-1/2 45-1/2
mm 1156 1158F in. 22-1/2 22-1/2
mm 572 572G in. 11-1/2 11-1/2
mm 292 292H in. 10-3/4 13-3/4
mm 273 349J in. 45-1/2 45-1/2
mm 1156 1156K in. 21-1/2 27-1/2
mm 546 699L in. 7-1/8 8-1/8
mm 181 206Duct Size in. 18 round 20 round
mm 457 round 508 round
Model Number FD9-65S FD11-95SA in. 47-5/8 47-5/8
mm 1159 1159B in. 23-5/8 29-5/8
mm 600 752C in. 13-1/2 16-5/8
mm 343 422D in. 21 27
mm 533 686E in. 45 45
mm 1143 1143F in. 22-1/2 22-1/2
mm 572 572G in. 11-1/4 11-1/4
mm 286 286H in. 10-1/2 13-1/2
mm 267 343Duct Size in. 18 round 20 round
mm 457 round 508 round
NOTE - Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency. ©2017 Lennox Industries, Inc.
Visit us at www.lennox.com
For the latest technical information, www.lennoxcommercial.com
Contact us at 1-800-4-LENNOX
REVISIONS
REVISIONS
Section Description
Specifications - Belt DriveCooling Performance (Gross Cooling Capacity, Net Cooling Capacity, and EER updated for 4 ton unit. Cooling Performance (EER) updated for 5 ton unit.