31
Large Tonnage Chiller WC Screw

Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Embed Size (px)

Citation preview

Page 1: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Large Tonnage ChillerWC Screw

Page 2: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Content• Mechanical System

• Key Components

• Control Logic

• Application

2

Page 3: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Mechanical System

3

Page 4: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Layout

4

Control PanelScrew Compressor

Shell & Tube Condenser Cooling water inlet/outlet conn. & Temp. sensor

Page 5: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Refrigerant System

5

DX PID

Page 6: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

6

Flooded PID

Page 7: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Key Components

7

Page 8: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Condenser

H2O

R134a

R134a

Tube

Page 9: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

High Efficiency Sub-cooler

• Compact and high-efficient sub-cooler • Low-liquid flash design requires less refrigerant• Control the liquid level accurately to ensure 4.5C sub-cooling

Cold liquid outSubcooler

High temperature gas in

Condenser

Page 10: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Condenser

Page 11: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Condenser

Oil Sep.

Page 12: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Evaporator

R134a

Water

Water

DX type

Page 13: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Evaporator

H2O

R134a

R134aFlooded type

Page 14: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Evaporator

H2O

R134a

R134aFull Falling Film type

Page 15: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Evaporator

Flooded Falling Film

40%

• Reduce 40% of refrigerant charge

• Improved performance of oil return and heat transfer

Full Falling Film

25%

Page 16: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Oil system

16

Gas jet

Page 17: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Oil System

The Venturi effect is the reduction in fluid pressure that results when a fluid flows through a constricted section of pipe, with the static pressure correspondingly decreasing .

Sound Velocity

Velocity

Pressure

Page 18: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Oil jet

Page 19: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Oil pump

Oil System

Page 20: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Gas jet Oil jet Oil pump

Features

Vacuum 50 ~ 80kPa;

Low gas pressure drop;

Low price; Piping design

complicated.

Vacuum 12 ~ 20kPa;

High oil pressure drop, up to 50%;

Low price; Piping design

complicated.

Best stability of oil return;

High price; Piping design

simply.

Oil System

Page 21: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Micro processer

MIC PLC

Price Cheap Expensive

Function The same

Failure rate 1/10 of PLC -

Maintenance Just replace it. Replace it. Not only it, but also the modular;

Page 22: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Control Logic

22

Page 23: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Start up

23

YES

Page 24: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Stop

24

Page 25: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Applications

25

Page 26: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Ice/Water storage

26

Series System

Parallel System

Storage

Storage

Page 27: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

EVA

HR

COND EEV

45℃40℃

35℃30℃

7℃12℃

Heat recovery

Note:The highest HR LWT is 60 ℃ , the higher EWT, the less HR.

Page 28: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Heat pump

28

Note:Cooling: A on, B off;Heating: A off, B on.

Comp

Flooded EVA

COND

Pump

Pump

Surface water system

FCU

Page 29: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

Heat pump

29

Note:Cooling: A on, B off;Heating: A off, B on.

Comp

Flooded EVA

CONDPump

Pump

Ground Source

FCU

Page 30: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

30

Page 31: Large Tonnage Chiller WC Screw. Content Mechanical System Key Components Control Logic Application 2

31

Thank You!