Upload
salman-zaheer
View
38
Download
3
Tags:
Embed Size (px)
DESCRIPTION
lac
Citation preview
1
Location Area Dimensioning Audit in Central Region (Week 20)
Alcatel-Lucent Optimization Service Team Central
Prepared By: Muhammad Nouman Afzal
2
Table Of Contents
1. Introduction: .................................................................................................................. 3
1.1 Location Area Dimensioning: ............................................................................... 3 1.2 Paging Limitations ................................................................................................ 4
1.2.1 Um interface Limit with Uncombined cells .................................................. 4 1.2.2 BSC Limit...................................................................................................... 5
2. Area definition, Analysis & recommendations: ............................................................ 5 2.1 LAC 448 ................................................................................................................ 7
2.1.1 Recommendations ......................................................................................... 9 2.2 LAC 827 ................................................................................................................ 9
2.2.1 Recommendations ....................................................................................... 11 2.3 LAC 831 .............................................................................................................. 11
2.3.1 Recommendations ....................................................................................... 13 2.4 LAC 836 .............................................................................................................. 13
2.4.1 Recommendations ....................................................................................... 15 2.5 LAC 838 .............................................................................................................. 15
2.5.1 Recommendations ....................................................................................... 17 2.6 LAC 853 .............................................................................................................. 17
2.6.1 Recommendations ....................................................................................... 19 2.7 LAC 855 .............................................................................................................. 19
2.7.1 Recommendations ....................................................................................... 21 3. Discrepancies Found ................................................................................................... 21 4. Conclusion................................................................................................................... 21
3
1. INTRODUCTION:
The location area is defined by a Set of cells which are paged each time one Mobile Terminating Call or SMS is initiated in a defined area called Location Area LA . It has a unique Location Area Code (LAC), & the position of each MS on a Location Area level is stored in HLR / VLR.
The MS updates the mobile network with its latest LA using SDCCH resources in the following two cases
. When it moves from one LAC to another (Location Update)
. Periodically its current LAC position (Periodical LU).
1.1 Location Area Dimensioning:
The Location Area Size is based on a Trade off between the three following criteria s which according to their values the Location Area is decided.
Signalling load in cells located at LAC border -SDCCH resources in each cell has to be sized accordingly
Number of simultaneous paging in each cell of the LAC -All MS in LAC and in MT call are paged simultaneously
The load on the Access grant channel, which in turn limits the number of blocks used for Paging
The maximum size of a Location Area is mainly driven by the max number of paging it can handle, i.e. by the traffic seen on this Location Area. Paging messages are transmitted within CCCH blocks contained within each 51 multiframe.
There are 9 CCCH blocks per M51 frame (duration of one M51 is 235 ms) for non-combined cells. Among those 9 blocks, 9 minus BS_AG_BLK_RES are reserved for paging (BS_AG_BLK_RES=4 as a usual default value for non-combined cells giving the number of Blocks reserved for Access Grant Channel).
4
There are 3 CCCH blocks per M51 frame for combined cells. Among those 3 blocks, 3 minus BS_AG_BLK_RES are reserved for paging (BS_AG_BLK_RES=1 as an usual default value for combined cells).
All cells in Mobilink Network are operating in the Non combined Mode.
Depending of the usage of IMSI or TMSI, from 1 to 4 mobiles can be paged simultaneously.
The maximum number of paging per Location Area is derived from the paging limitations at Um interface and at the BSC side
1.2 Paging Limitations
1.2.1 Um interface Limit with Uncombined cells
A 2 Paging/PCH value has been used to derive the maximum paging load per Location Area while only one user can be given an Access grant block at a time (1 AG/Block). A value of 3 paging or even 4 paging per block can be reached if and only if:
high PCH load (> 80%). The (safe) engineering limit taken later makes likely that this load is not reached. Indeed the CCCH capacity is not a linear function because of the paging request encoding method. Real time simulations performed internally show that when the 3 Paging/PCH ratio is reached we usually have a high blocking rate on PCH (about 5%), which will induce repetition by the MSC.
very good distribution of MS among all paging groups. This depends on the IMSI distribution.
Finally, we obtain the following values.
Available blocks for paging per hour:
Taking BS_AG_BLK_RES=2
7 PCH/Multiframe * (3600s / 235 ms) = 107234 PCH / hour
Paging per hour: 2 paging / Block x 107234 Blocks=214468paging/hour at 100% load. When the 70% engineering limit is applied, we obtain 150127 paging/hour, giving a 41 paging/ second value.
In turn giving an AGCH limit = 2*1*3600*(0.7)/235ms= 21447 access grant/hour, giving a 5.9 access grant/second value.
5
1.2.2 BSC Limit
The BSC limit is 70 Paging/ s, i.e. 252 000 paging/hour on the A interface (Alcatel traffic model). The paging on the A interface is the sum of the paging on all Location Area which are configured on a BSC. So it depends on the Paging rate on Location Area and on the number of Location Areas in a BSC.
2. AREA DEFINITION, ANALYSIS & RECOMMENDATIONS:
The Location Area audit report Part 1 will be carried out on the Area shown below in Figure 1.
Figure 1. Area being Audit
6
The Area includes the following BSCs mentioned in Table 1 below, an Audit shall be submitted for each Location Area which shall include Auditing on the Paging Load on the UM interface, Paging load on the BSS side & AGCH load.
BSC Name Location Area Code
MGH481A__Muzaffar_3 448 MGH480A__Muzaffar_1 448
BKR471A__Nazirtwn 827 BKR472A__Godala 827
BKR469A__MasjidUmer 827 KNL462A__Gnawaz_1 831 KNL463A__Gnawaz_2 831
KNL450A__Shabnamcine
836 KNL449A_Civillines 836
KNL561A__Kachakhu 838 KNL562A__Civillines_2 838 MLS508A__VehariRd_1 853
MLS510A__Mozadin 853 VHR511A__RailwaySt_1 855 VHR564A__RailwaySt_2 855
Table 1. Area Definition
7
2.1 LAC 448
Figure 2.1 LAC 448
BSC Name Location Area Code
MGH481A__Muzaffar_3
448 MGH480A__Muzaffar_1
448 Table 2.1 LAC 448
Since BS_AG_BLK_RES = 2 on all cells of these 2 BSCs Then AGCH limitation at 70% engineering limit = 21447 access grant/hour & Paging limitation at 70% engineering limit = 150127 paging/hour
8
Figure 2.1.1 AGCH Load
As per figure 2.1.1, all cells belonging to LAC 448 have an AGCH load below the threshold defined according to the value of the parameter BS_AG_BLK_RES.
010000
200003000040000
500006000070000
8000090000
12/0
5/20
07 12h
13/0
5/20
07 12h
14/0
5/20
07 12h
15/0
5/20
07 12h
16/0
5/20
07 12h
HWY3959A__S_MNKQaziabad (LAC =448, CI = 13959) (notplanned) 448 13959MGH481A__Muzaffar_3
HWY3959B__S_MNKQaziabad (LAC =448, CI = 23959) (notplanned) 448 23959MGH481A__Muzaffar_3
HWY3959C__S_MNKQaziabad (LAC =448, CI = 33959) (notplanned) 448 33959MGH481A__Muzaffar
Figure 2.1.2 Paging Load
As per figure 2.1.2, all cells belonging to LAC 448 have a Paging load well below the threshold defined according to the value of the parameter BS_AG_BLK_RES. Also all cells are having the same exact Paging, showing that there is no error in their creation from the NSS end except one or two hours
02000400060008000
100001200014000160001800020000
12/0
5/20
07 12h
13/0
5/20
07 12h
14/0
5/20
07 12h
15/0
5/20
07 12h
16/0
5/20
07 12h
HWY3959A__S_MNKQaziabad (LAC =448, CI = 13959) (notplanned) 448 13959MGH481A__Muzaffar_3
HWY3959B__S_MNKQaziabad (LAC =448, CI = 23959) (notplanned) 448 23959MGH481A__Muzaffar_3
HWY3959C__S_MNKQaziabad (LAC =448, CI = 33959) (notplanned) 448 33959MGH481A__Muzaffar
9
2.1.1 Recommendations
No Change in design for LAC 448 is needed as both the Paging load (on Um & BSS sides) & AGCH load are well below threshold.
2.2 LAC 827
Figure 2.2 LAC 827
BSC Name Location Area Code
BKR471A__Nazirtwn 827 BKR472A__Godala 827
BKR469A__MasjidUmer
827 Table 2.2 LAC 827
Since BS_AG_BLK_RES = 2 on all cells of these 3 BSCs Then AGCH limitation at 70% engineering limit = 21447 access grant/hour & Paging limitation at 70% engineering limit = 150127 paging/hour
10
0
10000
20000
30000
40000
50000
60000
12/0
5/20
07 12h
13/0
5/20
07 12h
14/0
5/20
07 12h
15/0
5/20
07 12h
16/0
5/20
07 12h
BHL4879A__S_MCBBehal (LAC = 827, CI= 14879) (notplanned) 827 14879BKR471A__Nazirtwn
BHL4879B__S_MCBBehal (LAC = 827, CI= 24879) (notplanned) 827 24879BKR471A__Nazirtwn
BHL4879C__S_MCBBehal (LAC = 827, CI= 34879) (notplanned) 827 34879BKR471A__Nazirtwn
Figure 2.2.1 AGCH Load
As per figure 2.2.1, all cells belonging to LAC 827 have an AGCH load below the threshold defined according to the value of the parameter BS_AG_BLK_RES.Only one cell did the violation for few hours,but it seems unreal stats as the trend has been quite normal throughout the week.
0
20000
40000
60000
80000
100000
120000
140000
160000
12/0
5/20
07 12h
13/0
5/20
07 12h
14/0
5/20
07 12h
15/0
5/20
07 12h
16/0
5/20
07 12h
BHL4879A__S_MCBBehal (LAC = 827, CI= 14879) (notplanned) 827 14879BKR471A__Nazirtwn
BHL4879B__S_MCBBehal (LAC = 827, CI= 24879) (notplanned) 827 24879BKR471A__Nazirtwn
BHL4879C__S_MCBBehal (LAC = 827, CI= 34879) (notplanned) 827 34879BKR471A__Nazirtwn
Figure 2.2.2 Paging Load
As per figure 2.1.2, all cells belonging to LAC 827 have a Paging load below the threshold defined according to the value of the parameter BS_AG_BLK_RES.
11
However the cell DRK4983C_S_Yarasula had the highest paging of 143,803 which is quite close to the threshold of 70%.This LAC might need a review in the near future because of this cell. All cells are having the same exact Paging, showing that there is no error in their creation from the NSS end.However some cells had different values due to stuck stats and sometimes Abis fluctuations
2.2.1 Recommendations
No Change in design for LAC 827 is needed as both the Paging load (on Um & BSS sides) & AGCH load are well below threshold. .
2.3 LAC 831
Figure 2.3 LAC 831
BSC Name Location Area Code
KNL462A__Gnawaz_1
831 KNL463A__Gnawaz_2
831 Table 2.3 LAC 831
12
Since BS_AG_BLK_RES = 2 on all cells of these 2 BSCs Then AGCH limitation at 70% engineering limit = 21447 access grant/hour & Paging limitation at 70% engineering limit = 150127 paging/hour
0
5000
10000
15000
20000
25000
30000
3500012
/05/
2007 12h
13/0
5/20
07 12h
14/0
5/20
07 12h
15/0
5/20
07 12h
16/0
5/20
07 12h
HWY3217A__H_JHNChowkMetla (LAC =831, CI = 13217) (notplanned) 831 13217KNL462A__Gnawaz_1
HWY3217B__H_JHNChowkMetla (LAC =831, CI = 23217) (notplanned) 831 23217KNL462A__Gnawaz_1
HWY3217C__H_JHNChowkMetla (LAC =831, CI = 33217) (notplanned) 831 33217KNL462A__Gnawaz_
Figure 2.3.1 AGCH Load
As per figure 2.3.1, all cells belonging to LAC 831 have an AGCH load below the threshold defined according to the value of the parameter BS_AG_BLK_RES except one cell HWY8547A__S_BastiTaraggar which sometimes crosses the threshold.So please change its Cell_reselect_hysteresis from 0 to 5.
0100002000030000400005000060000700008000090000
100000
12/0
5/20
07 12h
13/0
5/20
07 12h
14/0
5/20
07 12h
15/0
5/20
07 12h
16/0
5/20
07 12h
HWY3217A__H_JHNChowkMetla (LAC =831, CI = 13217) (notplanned) 831 13217KNL462A__Gnawaz_1
HWY3217B__H_JHNChowkMetla (LAC =831, CI = 23217) (notplanned) 831 23217KNL462A__Gnawaz_1
HWY3217C__H_JHNChowkMetla (LAC =831, CI = 33217) (notplanned) 831 33217KNL462A__Gnawaz_
Figure 2.3.2 Paging Load
13
As per figure 2.3.2, all cells belonging to LAC 831 have a Paging load below the threshold defined according to the value of the parameter BS_AG_BLK_RES. Also all cells are having the same exact Paging, showing that there is no error in their creation from the NSS end.However for some cells stats showed some errors
2.3.1 Recommendations
No Change in design for LAC 831 is needed as both the Paging load (on Um & BSS sides) & AGCH load are well below threshold.
2.4 LAC 836
Figure 2.4 LAC 836
BSC Name Location Area Code
KNL450A__Shabnamcine
836 KNL449A_Civillines 836
Table 2.4 LAC 836
Since BS_AG_BLK_RES = 2 on all cells of this BSC Then AGCH limitation at 70% engineering limit = 21447 access grant/hour & Paging limitation at 70% engineering limit = 150127 paging/hour
14
02000
400060008000
100001200014000
1600018000
12/0
5/20
07 12h
13/0
5/20
07 12h
14/0
5/20
07 12h
15/0
5/20
07 12h
16/0
5/20
07 12h
HWY4028A__S_asitDingaPul (LAC =836, CI = 14028) (notplanned) 836 14028KNL449A_Civillines
HWY4028B__S_asitDingaPul (LAC =836, CI = 24028) (notplanned) 836 24028KNL449A_Civillines
HWY4028C__S_asitDingaPul (LAC =836, CI = 34028) (notplanned) 836 34028KNL449A_Civillines
Figure 2.4.1 AGCH Load
As per figure 2.4.1, all cells belonging to LAC 836 have an AGCH load below the threshold defined according to the value of the parameter BS_AG_BLK_RES.
010000
200003000040000
500006000070000
8000090000
12/0
5/20
07 12h
13/0
5/20
07 12h
14/0
5/20
07 12h
15/0
5/20
07 12h
16/0
5/20
07 12h
HWY4028A__S_asitDingaPul (LAC =836, CI = 14028) (notplanned) 836 14028KNL449A_Civillines
HWY4028B__S_asitDingaPul (LAC =836, CI = 24028) (notplanned) 836 24028KNL449A_Civillines
HWY4028C__S_asitDingaPul (LAC =836, CI = 34028) (notplanned) 836 34028KNL449A_Civillines
Figure 2.4.2 Paging Load
As per figure 2.4.2, all cells belonging to LAC 836 have a Paging load below the threshold defined according to the value of the parameter BS_AG_BLK_RES. Also all cells are having the same exact Paging, showing that there is no error in their creation from the NSS end.
15
2.4.1 Recommendations
No Change in design for LAC 836 is needed as both the Paging load (on Um & BSS sides) & AGCH load are well below threshold.
2.5 LAC 838
Figure 2.5 LAC 838
BSC Name Location Area Code
KNL561A__Kachakhu 838 KNL562A__Civillines_2
838
Table 2.5 LAC 838
Since BS_AG_BLK_RES = 2 on all cells of this BSC Then AGCH limitation at 70% engineering limit = 21447 access grant/hour & Paging limitation at 70% engineering limit = 150127 paging/hour
16
0
5000
10000
15000
20000
25000
12/0
5/20
07 12h
13/0
5/20
07 12h
14/0
5/20
07 12h
15/0
5/20
07 12h
16/0
5/20
07 12h
ABH4291A__H_KBRAbdulHakeem (LAC= 838, CI = 14291)(not planned) 83814291KNL562A__Civillines
ABH4291B__H_KBRAbdulHakeem (LAC= 838, CI = 24291)(not planned) 83824291KNL562A__Civillines
ABH4291C__H_KBRAbdulHakeem (LAC= 838, CI = 34291)(not planned) 83834291
Figure 2.5.1 AGCH Load
As per figure 2.5.1, all cells belonging to LAC 838 have an AGCH load below the threshold defined according to the value of the parameter BS_AG_BLK_RES.Only one cell crossed the 70% value however it was only for one hour, otherwise the trend is quite normal.
010000
200003000040000
500006000070000
8000090000
12/0
5/20
07 12h
13/0
5/20
07 12h
14/0
5/20
07 12h
15/0
5/20
07 12h
16/0
5/20
07 12h
ABH4291A__H_KBRAbdulHakeem (LAC= 838, CI = 14291)(not planned) 83814291KNL562A__Civillines
ABH4291B__H_KBRAbdulHakeem (LAC= 838, CI = 24291)(not planned) 83824291KNL562A__Civillines
ABH4291C__H_KBRAbdulHakeem (LAC= 838, CI = 34291)(not planned) 83834291
Figure 2.5.2 Paging Load
As per figure 2.5.2, all cells belonging to LAC 838 has a Paging load below the threshold defined according to the value of the parameter BS_AG_BLK_RES. Also all cells are having the same exact Paging, showing that there is no error in their creation from the NSS end, the value has fluctuated on some cells over the last day of the analysis due to some Abis Fluctuations.
17
2.5.1 Recommendations
No Change in design for LAC 838 is needed as both the Paging load (on Um & BSS sides) & AGCH load are well below threshold.
2.6 LAC 853
Figure 2.6 LAC 853
BSC Name Location Area Code
MLS508A__VehariRd_1
853 MLS510A__Mozadin 853
Table 2.6 LAC 853
Since BS_AG_BLK_RES = 2 on all cells of these 2 BSCs Then AGCH limitation at 70% engineering limit = 21447 access grant/hour & Paging limitation at 70% engineering limit = 150127 paging/hour
18
02000
400060008000
100001200014000
1600018000
12/0
5/20
07 12h
13/0
5/20
07 12h
14/0
5/20
07 12h
15/0
5/20
07 12h
16/0
5/20
07 12h
FPR8453A__S_KarorPakkaRoad (LAC =853, CI = 18453) (notplanned) 853 18453MLS508A__VehariRd_1
FPR8453B__S_KarorPakkaRoad (LAC =853, CI = 28453) (notplanned) 853 28453MLS508A__VehariRd_1
FPR8453C__S_KarorPakkaRoad (LAC =853, CI = 38453) (notplanned) 853 38453MLS508A__VehariRd
Figure 2.6.1 AGCH Load
As per figure 2.6.1, all cells belonging to LAC 853 have an AGCH load below the threshold defined according to the value of the parameter BS_AG_BLK_RES.
010000
200003000040000
500006000070000
8000090000
12/0
5/20
07 12h
13/0
5/20
07 12h
14/0
5/20
07 12h
15/0
5/20
07 12h
16/0
5/20
07 12h
FPR8453A__S_KarorPakkaRoad (LAC =853, CI = 18453) (notplanned) 853 18453MLS508A__VehariRd_1
FPR8453B__S_KarorPakkaRoad (LAC =853, CI = 28453) (notplanned) 853 28453MLS508A__VehariRd_1
FPR8453C__S_KarorPakkaRoad (LAC =853, CI = 38453) (notplanned) 853 38453MLS508A__VehariRd
Figure 2.6.2 Paging Load
As per figure 2.6.2, all cells belonging to LAC 853 has a Paging load below the threshold defined according to the value of the parameter BS_AG_BLK_RES. Also all cells are having the same exact Paging, showing that there is no error in their creation from the NSS end.
19
2.6.1 Recommendations
No Change in design for LAC 853 is needed as both the Paging load (on Um & BSS sides) & AGCH load are well below threshold.
2.7 LAC 855
Figure 2.6 LAC 855
BSC Name Location Area Code
VHR511A__RailwaySt_1
855 VHR564A__RailwaySt_2
855 Table 2.6 LAC 855
Since BS_AG_BLK_RES = 2 on all cells of these 2 BSCs Then AGCH limitation at 70% engineering limit = 21447 access grant/hour & Paging limitation at 70% engineering limit = 150127 paging/hour
20
0
10000
20000
30000
40000
50000
60000
70000
12/0
5/20
07 12h
13/0
5/20
07 12h
14/0
5/20
07 12h
15/0
5/20
07 12h
16/0
5/20
07 12h
Bdw7506A__S_Chak216_E-B (LAC = 855,CI = 17506) (notplanned) 855 17506VHR511A__RailwaySt_1
Bdw7506B__S_Chak216_E-B (LAC = 855,CI = 27506) (notplanned) 855 27506VHR511A__RailwaySt_1
Bdw7506C__S_Chak216_E-B (LAC = 855,CI = 37506) (notplanned) 855 37506VHR511A__RailwayS
Figure 2.6.1 AGCH Load
As per figure 2.6.1, all cells belonging to LAC 855 have an AGCH load below the threshold defined according to the value of the parameter BS_AG_BLK_RES except PKM8469B__S_AddaPakhiMor which violated the threshold only for one hour but that seems unreal.
010000
200003000040000
500006000070000
8000090000
12/0
5/20
07 12h
13/0
5/20
07 12h
14/0
5/20
07 12h
15/0
5/20
07 12h
16/0
5/20
07 12h
Bdw7506A__S_Chak216_E-B (LAC = 855,CI = 17506) (notplanned) 855 17506VHR511A__RailwaySt_1
Bdw7506B__S_Chak216_E-B (LAC = 855,CI = 27506) (notplanned) 855 27506VHR511A__RailwaySt_1
Bdw7506C__S_Chak216_E-B (LAC = 855,CI = 37506) (notplanned) 855 37506VHR511A__RailwayS
Figure 2.6.2 Paging Load
As per figure 2.6.2, all cells belonging to LAC 855 has a Paging load below the threshold defined according to the value of the parameter BS_AG_BLK_RES. Also all cells are having the same exact Paging, showing that there is no error in their creation from the NSS end.
21
2.7.1 Recommendations
No Change in design for LAC 855 is needed as both the Paging load (on Um & BSS sides) & AGCH load are well below threshold.
3. DISCREPANCIES FOUND
No discrepancies were found during the Audit that need to be corrected.
.
4. CONCLUSION
Location Area dimensioning Audit was performed on 7 LACs in Alcatel-Lucent C2 region. No LACs violated the dimensioning rules on the CCCH (regarding the paging channel load.
However paging load was quite normal for all the LACs. So it was not possible to propose any LAC mergers.
This document was created with Win2PDF available at http://www.daneprairie.com.The unregistered version of Win2PDF is for evaluation or non-commercial use only.