ML= LINEAR METERS Item Descripcion Description UOM Cant Net Price (Price without IVA) IVA Full Price (IVA Included) 1 Zanjeo y relleno de ruta subterranea para tuberia electrica de 0.5m de profundidad x 0.4 metros de ancho. Dig of a ditch and refill the underground router for electrical tubien of 0.5 m deep and 0.4 m wide ML SEE DRAWINGS 2 Cajas de registro tipo H con drenaje frances de 0.8x0.8x0.8m. Registry Boxes with french drain of 0.8x0.8x0.8m. ea SEE DRAWINGS 3 Generador 1 a Tablero Colectora, suministro e instalacion de acometida con 6 Cables THHN 4/0 para lineas + 2 cables 4/0 THHN para neutro + 1 cable #2 AWG THHN para tierra, en tuberia PVC de 125PSI de 4". Generator 1 to Collector Board, supply and installation of connection with 6 THHN 4/0 cables for lines + 2 wires 4/0 THHN for neutral + 1 wire # 2 AWG THHN for ground, in PVC pipe of 125PSI of 4 ". ML SEE DRAWINGS 4 Generador 2 a Tablero Colectora, suministro e instalacion de acometida con 6 Cables THHN 4/0 para lineas + 2 cables 4/0 THHN para neutro + 1 cable #2 AWG THHN para tierra, en tuberia PVC de 125PSI de 4". Generator 2 a Collector Board, supply and installation of connection with 6 THHN 4/0 cables for lines + 2 wires 4/0 THHN for neutral + 1 wire # 2 AWG THHN for ground, in PVC pipe of 125PSI of 4 ". ML SEE DRAWINGS 5 Tablero de barra Colectora a Tablero TDP, suministro e instalacion de acometida con 6 Cables THHN 4/0 para lineas + 2 cables 4/0 THHN para neutro + 1 cable #2 AWG THHN para tierra, en tuberia PVC de 125PSI de 4". TDP Board, supply and installation of connection with 6 THHN 4/0 cables for lines + 2 wires 4/0 THHN for neutral + 1 wire # 2 AWG THHN for ground, in PVC pipe of 125PSI of 4 ". ML SEE DRAWINGS 6 Tablero TDP a T1 de 20KVA , suministro e instalacion de acometida con 3 Cables #6 AWG THHN para lineas + 1 cables #6 AWG THHN para neutro + 1 cable #10 AWG THHN para tierra, en tuberia PVC de 125PSI de 2" 20KVA TDP to T1 board, power supply and installation with 3 # 6 AWG THHN cables for lines + 1 wires # 6 AWG THHN for neutral + 1 # 10 AWG THHN ground wire in 125psi 2 ML SEE DRAWINGS 7 T1 de 20KVA a TD1, suministro e instalacion de acometida con 2 Cables #6 AWG THHN para lineas + 1 cables #6 AWG THHN para neutro + 1 cable #10 AWG THHN para tierra, en tuberia PVC de 125PSI de 2". T1 from 20 KVA to TD1, supply and installation of connection with 2 wires # 6 AWG THHN for lines + 1 wires # 6 AWG THHN for neutral + 1 wire # 10 AWG THHN for ground, in PVC pipe of 125PSI of 2 " . ML SEE DRAWINGS 8 TD1 a TD6, suministro e instalacion de acometida con 2 Cables #6 AWG THHN para lineas + 1 cables #6 AWG THHN para neutro + 1 cable #10 AWG THHN para tierra, en tuberia PVC de 125PSI de 1 1/2". TD1 to TD6, supply and installation of connection with 2 wires # 6 AWG THHN for lines + 1 wires # 6 AWG THHN for neutral + 1 wire # 10 AWG THHN for ground, in PVC pipe of 125PSI of 1 1 / 2". ML SEE DRAWINGS 9 Tablero TDP a T2 de 100KVA , suministro e instalacion de acometida con 3 Cables 4/0 THHN para lineas + 1 cables 4/0 THHN para neutro + 1 cable #4 AWG THHN para tierra, en tuberia PVC de 125PSI de 3" Panel TDP to T2 of 100KVA, supply and installation of connection with 3 Cables 4/0 THHN for lines + 1 wires 4/0 THHN for neutral + 1 cable # 4 AWG THHN for ground, in PVC pipe of 125PSI of 3 " ML SEE DRAWINGS 10 T2 de 100KVA a TSG, suministro e instalacion de acometida con 3 Cables 350MCM THHN para lineas + 1 cables 350MCM THHN para neutro + 1 cable #4 AWG THHN para tierra, en tuberia PVC de 125PSI de 4" T2 from 100KVA to TSG, supply and installation of connection with 3 Cables 350MCM THHN for lines + 1 cables 350MCM THHN for neutral + 1 cable # 4 AWG THHN for ground, in PVC pipe of 125PSI of 4 " ML SEE DRAWINGS 11 TSG a TD2, suministro e instalacion de acometida con 3 Cables #4 AWG THHN para lineas + 1 cables #4 AWG THHN para neutro + 1 cable #10 AWG THHN para tierra, en tuberia PVC de 125PSI de 3" TSG to TD2, supply and installation of connection with 3 wires # 4 AWG THHN for lines + 1 wires # 4 AWG THHN for neutral + 1 wire # 10 AWG THHN for ground, in PVC pipe of 125PSI of 3 " ML SEE DRAWINGS 12 TSG a TD3, suministro e instalacion de acometida con 2 Cables #2 AWG THHN para lineas + 1 cables #2 AWG THHN para neutro + 1 cable #8 AWG THHN para tierra, en tuberia PVC de 125PSI de 1 1/2" TSG to TD3, supply and installation of connection with 2 wires # 2 AWG THHN for lines + 1 wires # 2 AWG THHN for neutral + 1 wire # 8 AWG THHN for ground, in 1 1/2 " ML SEE DRAWINGS 13 TSG a TD4, suministro e instalacion de acometida con 2 Cables #4 AWG THHN para lineas + 1 cables #4 AWG THHN para neutro + 1 cable #10 AWG THHN para tierra, en tuberia PVC de 125PSI de 1 1/2" TSG to TD4, supply and installation of connection with 2 wires # 4 AWG THHN for lines + 1 wires # 4 AWG THHN for neutral + 1 wire # 10 AWG THHN for ground, in 1 1/2 " ML SEE DRAWINGS ACOMETIDAS A TABLEROS/SWITCHBOARD CONNECTION OBRA CIVIL/ CIVIL ELECTRICAL LABOR LABOR, MATERIALS AND EQUIPMENT REQUEST SEE EXHIBIT B AND EXHIBIT C FOR REFERENCE

LABOR, MATERIALS AND EQUIPMENT REQUEST ML ......Suministro e instalacion de Tablero de Barra Colectora de sincronismo y modulo de sincronismo marca ComAP IG‐NT‐GC. proteccion NEMA

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

  • ML=  LINEAR METERS

    Item Descripcion Description  UOM Cant Net Price (Price without IVA) IVAFull Price (IVA Included)

    1Zanjeo y relleno de ruta subterranea para tuberia electrica de 0.5m de profundidad x 0.4 metros de ancho.

    Dig of a ditch and refill the underground router for electrical tubien of 0.5 m deep and 0.4 m wide 

    ML SEE DRAWINGS

    2 Cajas de registro tipo H con drenaje frances  de 0.8x0.8x0.8m. Registry Boxes with french drain of  0.8x0.8x0.8m. ea SEE DRAWINGS

    3Generador 1 a Tablero Colectora, suministro e instalacion de acometida con 6 Cables THHN 4/0 para lineas + 2 cables 4/0 THHN para neutro + 1 cable  #2 AWG THHN para tierra, en tuberia PVC de 125PSI de 4".

    Generator 1 to Collector Board, supply and installation of connection with 6 THHN 4/0 cables for lines + 2 wires 4/0 THHN for neutral + 1 wire # 2 AWG THHN for ground, in PVC pipe of 125PSI of 4 ".

    ML SEE DRAWINGS

    4Generador 2 a Tablero Colectora, suministro e instalacion de acometida con 6 Cables THHN 4/0 para lineas + 2 cables 4/0 THHN para neutro + 1 cable  #2 AWG THHN para tierra, en tuberia PVC de 125PSI de 4".

    Generator 2 a Collector Board, supply and installation of connection with 6 THHN 4/0 cables for lines + 2 wires 4/0 THHN for neutral + 1 wire # 2 AWG THHN for ground, in PVC pipe of 125PSI of 4 ".

    ML SEE DRAWINGS

    5Tablero de barra Colectora a Tablero TDP, suministro e instalacion de acometida con 6 Cables THHN 4/0 para lineas + 2 cables 4/0 THHN para neutro + 1 cable  #2 AWG THHN para tierra, en tuberia PVC de 125PSI de 4".

    TDP Board, supply and installation of connection with 6 THHN 4/0 cables for lines + 2 wires 4/0 THHN for neutral + 1 wire # 2 AWG THHN for ground, in PVC pipe of 125PSI of 4 ".

    ML SEE DRAWINGS

    6Tablero TDP a T1 de 20KVA , suministro e instalacion de acometida con 3 Cables #6 AWG THHN  para lineas + 1 cables #6 AWG THHN para neutro + 1 cable  #10 AWG THHN para tierra, en tuberia PVC de 125PSI de 2"

    20KVA TDP to T1 board, power supply and installation with 3 # 6 AWG THHN cables for lines + 1 wires # 6 AWG THHN for neutral + 1 # 10 AWG THHN ground wire in 125psi 2 

    ML SEE DRAWINGS

    7T1 de 20KVA a TD‐1, suministro e instalacion de acometida con 2 Cables #6 AWG THHN  para lineas + 1 cables #6 AWG THHN para neutro + 1 cable  #10 AWG THHN para tierra, en tuberia PVC de 125PSI de 2".

    T1 from 20 KVA to TD‐1, supply and installation of connection with 2 wires # 6 AWG THHN for lines + 1 wires # 6 AWG THHN for neutral + 1 wire # 10 AWG THHN for ground, in PVC pipe of 125PSI of 2 " .

    ML SEE DRAWINGS

    8TD‐1 a TD‐6, suministro e instalacion de acometida con 2 Cables #6 AWG THHN  para lineas + 1 cables #6 AWG THHN para neutro + 1 cable  #10 AWG THHN para tierra, en tuberia PVC de 125PSI de 1 1/2".

    TD‐1 to TD‐6, supply and installation of connection with 2 wires # 6 AWG THHN for lines + 1 wires # 6 AWG THHN for neutral + 1 wire # 10 AWG THHN for ground, in PVC pipe of 125PSI of 1 1 / 2".

    ML SEE DRAWINGS

    9Tablero TDP a T2 de 100KVA , suministro e instalacion de acometida con 3 Cables 4/0 THHN  para lineas + 1 cables 4/0 THHN para neutro + 1 cable  #4 AWG THHN para tierra, en tuberia PVC de 125PSI de 3"

    Panel TDP to T2 of 100KVA, supply and installation of connection with 3 Cables 4/0 THHN for lines + 1 wires 4/0 THHN for neutral + 1 cable # 4 AWG THHN for ground, in PVC pipe of 125PSI of 3 "

    ML SEE DRAWINGS

    10T2 de 100KVA a TSG, suministro e instalacion de acometida con 3 Cables 350MCM THHN  para lineas + 1 cables 350MCM THHN para neutro + 1 cable  #4 AWG THHN para tierra, en tuberia PVC de 125PSI de 4"

    T2 from 100KVA to TSG, supply and installation of connection with 3 Cables 350MCM THHN for lines + 1 cables 350MCM THHN for neutral + 1 cable # 4 AWG THHN for ground, in PVC pipe of 125PSI of 4 "

    ML SEE DRAWINGS

    11TSG a TD‐2, suministro e instalacion de acometida con 3 Cables #4 AWG THHN  para lineas + 1 cables #4 AWG THHN para neutro + 1 cable  #10 AWG THHN para tierra, en tuberia PVC de 125PSI de 3"

    TSG to TD‐2, supply and installation of connection with 3 wires # 4 AWG THHN for lines + 1 wires # 4 AWG THHN for neutral + 1 wire # 10 AWG THHN for ground, in PVC pipe of 125PSI of 3 "

    ML SEE DRAWINGS

    12TSG a TD‐3, suministro e instalacion de acometida con 2 Cables #2 AWG THHN  para lineas + 1 cables #2 AWG THHN para neutro + 1 cable  #8 AWG THHN para tierra, en tuberia PVC de 125PSI de 1 1/2"

    TSG to TD‐3, supply and installation of connection with 2 wires # 2 AWG THHN for lines + 1 wires # 2 AWG THHN for neutral + 1 wire # 8 AWG THHN for ground, in 1 1/2 "

    ML SEE DRAWINGS

    13TSG a TD‐4, suministro e instalacion de acometida con 2 Cables #4 AWG THHN  para lineas + 1 cables #4 AWG THHN para neutro + 1 cable  #10 AWG THHN para tierra, en tuberia PVC de 125PSI de 1 1/2"

    TSG to TD‐4, supply and installation of connection with 2 wires # 4 AWG THHN for lines + 1 wires # 4 AWG THHN for neutral + 1 wire # 10 AWG THHN for ground, in 1 1/2 "

    ML SEE DRAWINGS

    ACOMETIDAS A TABLEROS/SWITCHBOARD CONNECTION 

    OBRA CIVIL/ CIVIL ELECTRICAL LABOR

    LABOR, MATERIALS AND EQUIPMENT REQUESTSEE EXHIBIT B AND EXHIBIT C FOR REFERENCE

  • 14Tablero TDP a TD‐5, suministro e instalacion de acometida con 3 Cables #10 AWG THHN  para lineas + 1 cables #10 AWG THHN para neutro + 1 cable  #14 AWG THHN para tierra, en tuberia PVC de 125PSI de 3"

    TDP board to TD‐5, supply and installation of connection with 3 wires # 10 AWG THHN for lines + 1 wires # 10 AWG THHN for neutral + 1 wire # 14 AWG THHN for ground, in PVC pipe of 125PSI of 3 "

    ML SEE DRAWINGS

    15Tablero TDP a T‐INCINERADOR, suministro e instalacion de acometida con 3 Cables 4/0 THHN  para lineas + 1 cables 4/0 THHN para neutro + 1 cable  #6 AWG THHN para tierra, en tuberia PVC de 125PSI de 3"

    TDP board to T‐INCINERATOR, supply and installation of connection with 3 wires 4/0 THHN for lines + 1 wires 4/0 THHN for neutral + 1 wire # 6 AWG THHN for ground, in PVC pipe of 125PSI of 3 "

    ML SEE DRAWINGS

    16Suministro e instalacion de Gerador 1 de 250KVA,  BP2500C Spec Sheet proteccion NEMA 3R

    Supply and installation of Generator 1 of 250KVA, BP2500C Spec Sheet protection NEMA 3R

    ea SEE DRAWINGS

    17Suministro e instalacion de Gerador 2 de 100KVA, BP100C Spec Sheet proteccion NEMA 3R

    Supply and installation of Generator 2 of 100KVA, BP100C Spec Sheet protection NEMA 3R

    ea SEE DRAWINGS

    18Suministro e instalacion de Tablero de Barra Colectora de sincronismo  y modulo de sincronismo marca ComAP IG‐NT‐GC. proteccion NEMA 3R

    Supply and installation of Comap IG‐NT‐GC timing collector bar and timing module. NEMA 3R protection

    ea SEE DRAWINGS

    19Suministro e instalacion de TDP, QD TABLERO I‐LINE UL 400A 30P 3F 4H N/S 600VAC 10 ESPACIOS DIMENSIONES 74H"X32W"X8.5D" BARRA DE TIERRA PARA TABLERO I‐LINE PK32DGTA, proteccion NEMA 3R

    Supply and installation of TDP, QD TABLE I‐LINE UL 400A 30P 3F 4H N / S 600VAC 10 SPACES DIMENSIONS 74H "X32W" X8.5D "GROUND BAR FOR I‐LINE PK32DGTA BOARD, NEMA 3R protection

    ea SEE DRAWINGS

    20Suministro e instalacion de T1 de 20KVA, 480V/120‐208V DELTA‐ESTRELLA, EATON DT‐3, proteccion NEMA 3R

    Supply and installation of T1 of 20KVA, 480V / 120‐208V DELTA‐STAR, EATON DT‐3, protection NEMA 3R

    ea SEE DRAWINGS

    21Suministro e instalacion de T2 de 100KVA, 480V/120‐208V DELTA‐ESTRELLA, EATON DT‐3, proteccion NEMA 3R

    Supply and installation of T2 of 100KVA, 480V / 120‐208V DELTA‐STAR, EATON DT‐3,protection NEMA 3R

    ea SEE DRAWINGS

    22Suministro e instalacion de TD‐1, SQ‐D Tablero I‐LINE Listado UL, 225A 30P, 3F ‐ 4H, N/S, 600VAC, 10 Espacios, dimensiones 65H'' x 26W'' x 6.5D'', barra de tierra PK32DGTA, proteccion NEMA 3R

    Supply and installation of TD‐1, SQ‐D Board I‐LINE UL listed, 225A 30P, 3F ‐ 4H, N / S, 600VAC, 10 Spaces, dimensions 65H '' x 26W '' x 6.5D '', Ground Bar PK32DGTA, protection NEMA 3R

    ea SEE DRAWINGS

    23Suministro e instalacion de TD‐2, SQ‐D Tablero I‐LINE Listado UL, 225A 30P, 3F ‐ 4H, N/S, 600VAC, 10 Espacios, dimensiones 65H'' x 26W'' x 6.5D'', barra de tierra PK32DGTA, proteccion NEMA 3R

    Supply and installation of TD‐2, SQ‐D Board I‐LINE List UL, 225A 30P, 3F‐4H, N / S, 600VAC, 10 Spaces, Dimensions 65H '' x 26W '' x 6.5D '', Ground Bar PK32DGTA, protection NEMA 3R

    ea SEE DRAWINGS

    24Suministro e instalacion de TD‐3, SQ‐D Tablero I‐LINE Listado UL, 225A 30P, 3F ‐ 4H, N/S, 600VAC, 10 Espacios, dimensiones 65H'' x 26W'' x 6.5D'', barra de tierra PK32DGTA, proteccion NEMA 3R

    Supply and installation of TD‐3, SQ‐D Board I‐LINE UL listed, 225A 30P, 3F ‐ 4H, N / S, 600VAC, 10 Spaces, dimensions 65H '' x 26W '' x 6.5D '', Ground Bar PK32DGTA, protection NEMA 3R

    ea SEE DRAWINGS

    25Suministro e instalacion de TD‐4, SQ‐D Tablero I‐LINE Listado UL, 225A 30P, 3F ‐ 4H, N/S, 600VAC, 10 Espacios, dimensiones 65H'' x 26W'' x 6.5D'', barra de tierra PK32DGTA, proteccion NEMA 3R

    Supply and installation of TD‐4, SQ‐D Board I‐LINE UL listed, 225A 30P, 3F ‐ 4H, N / S, 600VAC, 10 Spaces, dimensions 65H '' x 26W '' x 6.5D '', Ground Bar PK32DGTA, protection NEMA 3R

    ea SEE DRAWINGS

    26Suministro e instalacion de TD‐5, SQ‐D Tablero I‐LINE Listado UL, 225A 30P, 3F ‐ 4H, N/S, 600VAC, 10 Espacios, dimensiones 65H'' x 26W'' x 6.5D'', barra de tierra PK32DGTA, proteccion NEMA 3R

    Supply and installation of TD‐5, SQ‐D Board I‐LINE UL listed, 225A 30P, 3F ‐ 4H, N / S, 600VAC, 10 Spaces, dimensions 65H '' x 26W '' x 6.5D '', Ground Bar PK32DGTA, protection NEMA 3R

    ea SEE DRAWINGS

    27Suministro e instalacion de TD‐6, SQ‐D Tablero I‐LINE Listado UL, 225A 30P, 3F ‐ 4H, N/S, 600VAC, 10 Espacios, dimensiones 65H'' x 26W'' x 6.5D'', barra de tierra PK32DGTA, proteccion NEMA 3R

    Supply and installation of TD‐6, SQ‐D Board I‐LINE UL listed, 225A 30P, 3F ‐ 4H, N / S, 600VAC, 10 Spaces, dimensions 65H '' x 26W '' x 6.5D '', Ground Bar PK32DGTA, protection NEMA 3R

    ea SEE DRAWINGS

    28Suministro e instalacion de T‐INCINERADOR, SQ‐D Tablero I‐LINE Listado UL, 225A 30P, 3F ‐ 4H, N/S, 600VAC, 10 Espacios, dimensiones 65H'' x 26W'' x 6.5D'', barra de tierra PK32DGTA, proteccion NEMA 3R

    Supply and installation of T‐INCINERATOR, SQ‐D Board I‐LINE List UL, 225A 30P, 3F ‐ 4H, N / S, 600VAC, 10 Spaces, dimensions 65H '' x 26W '' x 6.5D '', Ground Bar PK32DGTA, protection NEMA 3R

    ea SEE DRAWINGS

    29Suministro e instalacion de TSG, QD TABLERO I‐LINE UL 400A 30P 3F 4H N/S 600VAC 10 ESPACIOS DIMENSIONES 74H"X32W"X8.5D" BARRA DE TIERRA PARA TABLERO I‐LINE PK32DGTA, proteccion NEMA 3R

    "Supply and installation of TSG, QD TABLE I‐LINE UL 400A 30P 3F 4H N / S 600VAC 10 SPACES DIMENSIONS 74H" "X32W" "X8.5D" "  GROUND BAR FOR I‐LINE PK32DGTA, NEMA 3R PROTECTION "

    ea SEE DRAWINGS

    30Unidad de Iluminacion con tuberia Hg de 3/4" 2 cables # 12 THHN para lineas + 1 cable #12 THHN para neutro + 1 cable #14 para tierra

    Lighting unit with 3/4 "Hg tubing 2 cables # 12 THHN for lines + 1 wire # 12 THHN for neutral + 1 wire # 14 for ground

    ea 11

    31 Instalacion de Lamparas Lighting installation  ea 11

    32Suministro de lampara Albeo LED Luminaire – ABV1 120/240V, de 9,000‐24,000 lm lumenes de salida. Ver anexo de Equipos y lamparas

    Lamp supply Albeo LED Luminaire ‐ ABV1 120 / 240V, from 9,000‐24,000 lm output lumens. See Equipment and lamp annex

    ea 11

    TABLEROS, TRANSFORMADORES Y GENERADORES/  SWITCHBOARDS, TRANSFORMERS AND GENERATORS

    ILUMINACION BODEGA Y OFICINA INCINERADOR/ SHED AND INCINERATOR OFFICE LIGHTING 

  • 33Unidad de fuerza 120V con tuberia Hg de 3/4" 1 cables # 12 THHN para lineas + 1 cable #12 THHN para neutro + 1 cable #14 para tierra

    Power unit 120V with 3/4 "Hg tubing 1 wires # 12 THHN for lines + 1 wire # 12 THHN for neutral + 1 wire # 14 for ground

    ea 7

    34 Instalacion de tomacorrientes Outlets installation  ea 735 Suministro de tomacorrientes similar o igual a  Bticino linea magic. Outlet supply similar or equal to Bticino linea magic. ea 7

    36Unidad de fuerza 240V con tuberia HG de 1 1/2" 2 cables calibre 8 para linesa + 1 cable calibre 8 para neutro + 1 cable calibre 10 para tierra

    240V force unit with 1 1/2 "HG tubing 2 linesa caliber 8 + 1 gauge wire for neutral + 1 gauge 10 wire for ground

    ea 2

    37Unidad de Iluminacion con tuberia Hg de 3/4" 2 cables # 12 THHN para lineas + 1 cable #12 THHN para neutro + 1 cable #14 para tierra

    Lighting unit with 3/4 "Hg tubing 2 cables # 12 THHN for lines + 1 wire # 12 THHN for neutral + 1 wire # 14 for ground

    ea 13

    38 Instalacion de Lamparas Lighting installation  ea 13

    39Suministro de lampara igual o similar a  marca Light Tec, tipo gasolinera explosion proof de 90W. Ver anexo Equipos y lamparas.

    Similar or equal to Light Tec brand lamp, explosion proof type 90W gas station. See annex Equipment and lamps.

    ea 13

    40Unidad de fuerza 120V con tuberia Hg de 3/4" 1 cables # 12 THHN para lineas + 1 cable #12 THHN para neutro + 1 cable #14 para tierra

    Power unit 120V with 3/4 "Hg tubing 1 wires # 12 THHN for lines + 1 wire # 12 THHN for neutral + 1 wire # 14 for ground

    ea 7

    41 Instalacion de tomacorrientes Outlets installation  ea 742 Suministro de tomacorrientes  Bticino linea magic. Outlet supply similar or equal to Bticino linea magic. ea 7

    43Unidad de fuerza 240V con tuberia HG de 1 1/2" 2 cables calibre 8 para linesa + 1 cable calibre 8 para neutro + 1 cable calibre 10 para tierra

    240V force unit with 1 1/2 "HG tubing 2 linesa caliber 8 + 1 gauge wire for neutral + 1 gauge 10 wire for ground

    ea 3

    44Unidad de Iluminacion con tuberia Hg de 3/4" 2 cables # 12 THHN para lineas + 1 cable #12 THHN para neutro + 1 cable #14 para tierra, areas externas

    Lighting unit with 3/4 "Hg tubing 2 cables # 12 THHN for lines + 1 wire # 12 THHN for neutral + 1 wire # 14 for ground, external areas

    ea 18

    45 Instalacion de Lamparas tipo reflector Installation of reflector lamps ea 18

    46Suministro de lampara tipo Reflector Led de 150 W Marca Light Tech, Tecnolite o similar. Ver anexo de Equipos y lamparas

    Supply of lamp type Led reflector of 150 W Brand Light Tech, Tecnolite or similar. See Equipment Attachments and Lamps

    ea 18

    47

    Suministro e instalacion de Parrrayos  similar o igual a marca ABB OPR 45, con bajante de conductor Thompson 28R calibre 4/0 o conductor plano de cobre estañado de 30x2mm, contador electronico de impactos de rayo marca ABB, sistema de puesta a tierra tipo estrella (pata de gallo), varilla de cobre de 5/8 UL, soldadura exotermica y accesorios, registro con pletina de comprobacion. Ver detalle en  plano IE‐05. Ver anexo de Lamps and Grounding System

    Supply and installation of similar or equal to ABB OPR 45 lightning rods, with Thompson 28R 4/0 gauge conductor downpipe or 30x2mm tinned copper flat conductor, ABB electronic lightning strike counter, starter system (crow's feet) , 5/8 UL copper rod, exothermic welding and accessories, registration with test plate. Seedetail in plan IE‐05. See Annex for Lamps and Grounding System

    ea 1

    48

    Suministro e instalacion de Parrrayos  similar o igual a marca ABB OPR 30, con bajante de conductor Thompson 28R calibre 4/0 o conductor plano de cobre estañado de 30x2mm, contador electronico de impactos de rayo marca ABB, sistema de puesta a tierra tipo estrella (pata de gallo), varilla de cobre de 5/8 UL, soldadura exotermica y accesorios, registro con pletina de comprobacion. Ver detalle en plano IE‐05. Ver anexo de Lamps and Grounding System

    Supply and installation of similar or  equal to ABB brand OPR 30, with downpipe driver Thompson 28R 4/0 caliber or 30x2mm tinned copper flat conductor, ABB electronic lightning strike counter, starter system (crow's feet) , 5/8 UL copper rod, exothermic welding and accessories, registration with test plate. See detail in plan IE‐05. See Annex for Lamps and Grounding System

    ea 1

    49

    Suministro e instalacion de sistema de puesta a tierra tipo delta, incluye cable Thompson 28R calibre 4/0, soldaduras exotermicas, registros y pletina de comprobacion, aterrizamiento de equipos con cable calibre 2/0. Ver detalle en plano IE‐04.

    Supply and installation of delta grounding system, includes Thompson 28R 4/0 caliber cable, exothermic welding, logs and test plate, grounding of equipment with 2/0 gauge wire. See detail in plan IE‐04.

    ea 2

    50Suministro e instalacion de tanque de combustible tipo DIESEL de 500 Galones, tuberia de llenado de tanque con tubos HG, tuberia de alimentacion a generadores 1 y 2 con tuberia HG. 

    Supply and installation of 500 gallon DIESEL fuel tank, tank filling pipe with HG pipes, supply line to generators 1 and 2 with HG piping.

    ea 1

    TOTALS

    SISTEMA DE TIERRAS Y PARARRAYOS/ GROUNDING AND LIGHTING ROD SYSTEM

    TANQUE DE DIESEL / DIESEL RESERVOIR

    ILUMINACION EXTERIOR/ OUTDOOR LIGHTING

    ILUMINACION BODEGA 1 EXISTENTE/ EXISTING SHED 1 LIGHTING 

  • Generator shall be prime power rated at 250kVA. Standby rated units are notacceptable .6LTAA8.9G23 cyl in Line Turbo/Aftercooled Mechanical Gov. 12vdc  3PH WYE/Delta 12 Lead4 pole, 1 Bearing SX460 Auto Start7 inputs/7 outputs 3 analog inputs RS232 InterfaceStandby Rating:Liters Gallons66 17.4 59.0 15.6 44.0 11.6 30.0 7.9 400 105.6According to ISO 8528‐1:2005, standby power is the maximum power available during variable electrical power sequence, under the stated operational conditions for which a generating set is capable of delivering in the event of a utility power outage for up to 200 hrs. per year while meeting manufacturers recommended operation and maintenance requirements. The permissible average power output over a 24 hr. period shall not exceed 70% of this rating. gensets are compliant with EC mark which include the following directives: * 2006/42/EC Machinery Safety.* 2006/95/EC Low Voltage.* EN 60204‐1 2006+A1:2009, EN ISO 12100: 2010, EN ISO 13849‐1: EN 12601: 2010

    GENERATOR 1  250 KVA SIMILAR OR EQUAL TO :

  • Generator shall be prime power rated at 100kVA. Standby rated units are notacceptable  4BTA3.9G114 cyl in Line Turbo‐Charged Elect Speed Gov. 12vdc, UCI 224G3PH WYE/Delta 12 Lead4 pole, 1 Bearing SX460 AVR, InteliLite AMF20Auto Start7 inputs/7 outputs 3 analog inputs RS232 Interface66 17.4 59.0 15.6 44.0 11.6 30.0 7.9 400 105.6According to ISO 8528‐1:2005, standby power is the maximum power available during variable electrical power sequence, under the stated operational conditions for which a generating set is capable of delivering in the event of a utility power outage for up to 200 hrs. per year while meeting manufacturers recommended operation and maintenance requirements. The permissible average power output over a 24 hr. period shall not exceed 70% of this rating. gensets are compliant with EC mark which include the following directives: * 2006/42/EC Machinery Safety.* 2006/95/EC Low Voltage.* EN 60204‐1 2006+A1:2009, EN ISO 12100: 2010, EN ISO 13849‐1: EN 12601: 2010

    GENERATOR 2  100 KVA SIMILAR OR EQUAL TO :

  • SINC MODULE AND COUPLING BAR  SIMILAR OR EQUAL TO :

    Modulo de sincronizacion COMAP IG‐NT‐GC, Gen‐set controller for single or multiple generating sets operating in standby or parallel modesSupport of engines with ECU (Electronic Control Unit)Many communication options – easy remote supervising and servicingGen‐set performance log for easy problem tracingAutomatic synchronizing and power control (via speed governor or ECU)AMF function, Baseload, Import / Export, Peak shaving, Voltage and PF control (AVR)Generator measurement, Mains measurementInputs and outputs configurable for various customer needsController redundancyEvent‐based history (up to 500 records) with customer‐selectable list of stored values; RTC; statistic valuesIntegrated PLC programmable functionsIntegrated fixed and configurable protection

  • TRANSFORMADORES TRANSFORMERS

    Transformador 20 KVA 480V/120‐208V DELTA‐ESTRELLA, EATON DT‐3 T1 Transformer 20 KVA 480V/120‐208V DELTA‐ESTRELLA, EATON DT‐3 T1

    Transformador 100KVA 480V/120‐208V DELTA‐ESTRELLA, EATON DT‐3 T2 Transformer 100KVA 480V/120‐208V DELTA‐ESTRELLA, EATON DT‐3 T2

    TABLEROS DE DISTRIBUCIÓN DISTRIBUTION SWITCHBOARDS

    QD TABLERO I‐LINE UL 400A 30P 3F 4H N/S 600VAC 10 ESPACIOS DIMENSIONES 74H"X32W"X8.5D"   BARRA DE TIERRA PARA TABLERO I‐LINE PK32DGTA TDP

    SQD TABLE I‐LINE UL 400A 30P 3F 4H N / S 600VAC 10 SPACES DIMENSIONS 74H" "X32W" "X8.5D" " GROUND BAR FOR I‐LINE PK32DGTA BOARD  TDP

    SQ‐D Tablero I‐LINE Listado UL, 225A 30P, 3F ‐ 4H, N/S, 600VAC, 10 Espacios, dimensiones 65H'' x 26W'' x 6.5D'', barra de tierra PK32DGTA  T‐INCINERADOR

    SQ‐D Board I‐LINE UL listed, 225A 30P, 3F‐4H, N / S, 600VAC, 10 Spaces, dimensions 65H '' x 26W '' x 6.5D '', ground bar PK32DGTA T‐INCINERATOR

    QD TABLERO I‐LINE UL 400A 30P 3F 4H N/S 600VAC 10 ESPACIOS DIMENSIONES 74H"X32W"X8.5D"   BARRA DE TIERRA PARA TABLERO I‐LINE PK32DGTA TSG

    SQD TABLE I‐LINE UL 400A 30P 3F 4H N / S 600VAC 10 SPACES DIMENSIONS 74H" "X32W" "X8.5D" " GROUND BAR FOR BOARD I‐LINE PK32DGTA TSG

    SQ‐D Tablero I‐LINE Listado UL, 225A 30P, 3F ‐ 4H, N/S, 600VAC, 10 Espacios, dimensiones 65H'' x 26W'' x 6.5D'', barra de tierra PK32DGTA  TD‐1

    SQ‐D Table I‐LINE UL Listed, 225A 30P, 3F ‐ 4H, N/S, 600VAC, 10 spaces, dimensions 65H'' x 26W'' x 6.5D'', ground bar PK32DGTA  TD‐1

    SQ‐D Tablero I‐LINE Listado UL, 225A 30P, 3F ‐ 4H, N/S, 600VAC, 10 Espacios, dimensiones 65H'' x 26W'' x 6.5D'', barra de tierra PK32DGTA  TD‐2

    SQ‐D Table I‐LINE UL Listed, 225A 30P, 3F ‐ 4H, N/S, 600VAC, 10 spaces, dimensions 65H'' x 26W'' x 6.5D'', ground bar PK32DGTA  TD‐2

    SQ‐D Tablero I‐LINE Listado UL, 225A 30P, 3F ‐ 4H, N/S, 600VAC, 10 Espacios, dimensiones 65H'' x 26W'' x 6.5D'', barra de tierra PK32DGTA TD‐3, TD‐4

    SQ‐D Table I‐LINE UL Listed, 225A 30P, 3F ‐ 4H, N/S, 600VAC, 10 spaces, dimensions 65H'' x 26W'' x 6.5D'', ground bar PK32DGTA TD‐3, TD‐4

    SQ‐D Tablero I‐LINE Listado UL, 225A 30P, 3F ‐ 4H, N/S, 600VAC, 10 Espacios, dimensiones 65H'' x 26W'' x 6.5D'', barra de tierra PK32DGTA  TD‐5, TD‐6

    SQ‐D Table I‐LINE UL Listed, 225A 30P, 3F ‐ 4H, N/S, 600VAC, 10 spaces, dimensions 65H'' x 26W'' x 6.5D'', ground bar PK32DGTA  TD‐5, TD‐6

    TVSS TVSSTVSS made in US   Categoria C  240KA 480V/277 UL 1449 SURGELOGIC  Square D

    TVSS made in US   Category C  240KA 480V/277 UL 1449 SURGELOGIC  Square D

    TRANSFORMERS AND DISTRIBUTION SWITCHBOARD SIMILAR OR EQUAL TO 

  • SWITCHBOARDS SIMILAR OR EQUAL TO 

  • SUPRESOR , SIMILAR OR EQUAL TO

  • SWITCHBOARDS SIMILAR OR EQUAL TO 

  • LAMPS FOR INCINERATOR SHED, SIMILAR OR EQUAL TO 

  • Grounding System & Lighting Rod Similar or Equal to  OPR 45 y OPR 30 marca ABB

  • * Grounding system shallbe in accordance with NEC Art.250, andGrounding electrodes shall be one of the permitted by NEC 250.52

    * Resistance to ground shall be not bigger than 10 ohms

    * Main Bonding Jumper shall be installed only in Main Breaker panel 480V and Main Breaker panel 208V and Sized regarding NEC Table 250.102

    * Grounded conductor for generators shall be equal or bigger than Cooper AWG 2 or Aluminum AWG 1/0, and for Dry Transformer shall be equal

    or bigger than copper AWG 8 or Aluminum AWG 6

    * Grounding wires for equipment shall be in accordance with NEC Table 250.122

    Grounding System

  • REFLECTOR LAMP FOR OUTDOOR LIGHTING SIMILAR OR EQUAL TO 

  • EXPLOSION PROOF LAMP FOR EXISTING SHED SIMILAR OR EQUAL TO  