18
Overcurrent Protection for the IEEE 34 Node Radial Test Feeder Hamed B. Funmilayo, James A. Silva and Dr. Karen L. Butler-Purry Texas A&M University Electrical and Computer Engineering Department 1 Power System Automation Lab

Lab IEEE 34 Node Radial Test Feeder Overcurrent Protection ... · PDF fileOvercurrent Protection for the IEEE 34 Node Radial Test Feeder Hamed B. Funmilayo, James A. Silva and Dr

  • Upload
    vudang

  • View
    228

  • Download
    2

Embed Size (px)

Citation preview

Page 1: Lab IEEE 34 Node Radial Test Feeder Overcurrent Protection ... · PDF fileOvercurrent Protection for the IEEE 34 Node Radial Test Feeder Hamed B. Funmilayo, James A. Silva and Dr

Overcurrent Protection for the IEEE 34 Node Radial Test Feeder

Hamed B. Funmilayo, James A. Silva and

Dr. Karen L. Butler-Purry Texas A&M University

Electrical and Computer Engineering Department

1

Po

wer

Syste

m A

uto

mati

on

Lab

Page 2: Lab IEEE 34 Node Radial Test Feeder Overcurrent Protection ... · PDF fileOvercurrent Protection for the IEEE 34 Node Radial Test Feeder Hamed B. Funmilayo, James A. Silva and Dr

Introduction

• Major use of the benchmark radial test feeders -- provide load-flow data for validating load-flow results from existing/novel load-flow algorithms

• Extend Current IEEE 34 node test feeder

– Provide overcurrent protection, considering off-the-shelf protective devices

– Make available for studies under new scenarios (such as DG impact)

2

Page 3: Lab IEEE 34 Node Radial Test Feeder Overcurrent Protection ... · PDF fileOvercurrent Protection for the IEEE 34 Node Radial Test Feeder Hamed B. Funmilayo, James A. Silva and Dr

Work Reported in This Paper

• Model of Test feeder in DIgSILENT

PowerFactory 13.1 and conduct LF and

SC studies

• Coordination studies for temporary and

permanent faults for various fault

situations

• Select OCP devices for the test feeder

3

Page 4: Lab IEEE 34 Node Radial Test Feeder Overcurrent Protection ... · PDF fileOvercurrent Protection for the IEEE 34 Node Radial Test Feeder Hamed B. Funmilayo, James A. Silva and Dr

IEEE 34 Node Radial Test Feeder

• Developed by DSA Subcommittee

• Majority at 24.9 kV (one 4.16kV lateral)

• Total load: 2060 kVA at 0.86 pf

• Long, unbalanced radial system

4

[1] Radial Test Feeders - IEEE Distribution System Analysis Subcommittee

IEEE 34-Node Test Feeder system (modified from [1])

Page 5: Lab IEEE 34 Node Radial Test Feeder Overcurrent Protection ... · PDF fileOvercurrent Protection for the IEEE 34 Node Radial Test Feeder Hamed B. Funmilayo, James A. Silva and Dr

Over Current Protective Devices

• Modeled in DIgSILENT

• 1 recloser, 12 fuses – Fuse saving for fuses 1, 2, 3, 4, 6, 7, 8, and 11

5

Page 6: Lab IEEE 34 Node Radial Test Feeder Overcurrent Protection ... · PDF fileOvercurrent Protection for the IEEE 34 Node Radial Test Feeder Hamed B. Funmilayo, James A. Silva and Dr

Maximum and Minimum Fault Currents

6

Comparison of Maximum Fault

Current to IEEE TF Results

Faulted IEEE* DIgSILENT DIgSILENT

Node (A) (A) % Error

800 718.60 678.60 5.57

808 526.50 510.20 3.10

816 335.40 329.94 1.63

824 313.00 310.50 0.80

854 272.90 276.40 1.28

832 223.10 217.70 2.42

858 217.70 213.30 2.02

834 211.30 208.40 1.37

836 206.90 204.40 1.21

840 206.10 203.61 1.21

890 406.50 440.10 8.27

Comparison of Minimum Fault

Current to IEEE TF Results

Faulted IEEE* DIgSILENT DIgSILENT

Node (A) (A) % Error

800 479.30 459.00 4.24

808 309.40 322.26 4.16

816 213.50 205.49 3.75

824 195.10 194.06 0.53

854 175.90 173.68 1.26

832 146.20 140.55 3.86

858 143.00 138.06 3.45

834 139.30 135.19 2.95

836 136.50 132.71 2.78

840 136.00 132.27 2.74

890 94.10 87.94 6.55

Page 7: Lab IEEE 34 Node Radial Test Feeder Overcurrent Protection ... · PDF fileOvercurrent Protection for the IEEE 34 Node Radial Test Feeder Hamed B. Funmilayo, James A. Silva and Dr

Recloser and Fuses Types

• Recloser

– Recloser's coordination range must provide adequate time to sense all downstream faults.

– Fuse Saving mode used

– A triple single-phase electronic recloser was used

• Load side fuses

– Similar types of fuse links were selected for all branches within the same nominal current range

– Voltage rating equal to or higher than the maximum bus voltage at the fuse location

– Interrupting current rating larger than the maximum symmetrical fault current at the fuse location

– Type K, T and X expulsion fuse links

7

Page 8: Lab IEEE 34 Node Radial Test Feeder Overcurrent Protection ... · PDF fileOvercurrent Protection for the IEEE 34 Node Radial Test Feeder Hamed B. Funmilayo, James A. Silva and Dr

Step Down Transformer (XMF-1) Fusing

• A type T external expulsion cutout on the primary side – The voltage rating equal to or greater than the voltage at transformer's

location

– The ampere rating equal to or greater than the anticipated normal loading level

– The symmetrical short-circuit interrupting rating equal to or greater than the maximum fault current

• Be able to withstand the inrush current generated when transformer is energized

• Be able to protect against transformer faults and secondary side faults (through faults)

• Serve as backup device by coordinating with the OCP device downstream of the lateral

8

Page 9: Lab IEEE 34 Node Radial Test Feeder Overcurrent Protection ... · PDF fileOvercurrent Protection for the IEEE 34 Node Radial Test Feeder Hamed B. Funmilayo, James A. Silva and Dr

Capacitor Bank Fusing

• Group fusing method is used. (One fuse protects the capacitor bank)

• Promptly isolate the failed capacitor unit on the line prior to any other protective device on the system

• 1-phase grounded fault current without fault impedance is assumed as the capacitor fault value.

9

Page 10: Lab IEEE 34 Node Radial Test Feeder Overcurrent Protection ... · PDF fileOvercurrent Protection for the IEEE 34 Node Radial Test Feeder Hamed B. Funmilayo, James A. Silva and Dr

Settings for Recloser and Load Side Fuses

10

Minimum Fault Current Observed at the Recloser

For The Minimum Fault At Each Lateral

Recloser Faulted Lateral If recloser (A)

Node Node number DIgSILENT

800 810 1 321.79

800 822 2 168.90

800 826 3 218.89

800 856 4 179.82

800 888 5 61.08

800 864 6 126.36

800 848 7 165.82

800 838 8 166.88

800 Cap- 844 7 167.93

800 Cap- 848 7 165.82

800 840 11 165.88

No. of Instantaneous Trips 1

No. of Delay Trips 2

Nominal Voltage 14.4 kV, L-N

Minimum trip rating 100 A

Instantaneous trip curve type 103

Delay trip curve type 134

Recloser Settings

Nominal Voltage Rating 24.9 kV, L-L or

4.16 kV, L-L

Nominal Current Rating of Each Fuse

Based on each branch’s current

Load Side Fuse Settings

Page 11: Lab IEEE 34 Node Radial Test Feeder Overcurrent Protection ... · PDF fileOvercurrent Protection for the IEEE 34 Node Radial Test Feeder Hamed B. Funmilayo, James A. Silva and Dr

Coordination Studies

• Two terms for OCP operation – Primary device

• Near to the fault and first to clear the fault

– Secondary (backup device)

• Backup of the primary device

• Coordination between recloser and fuse – For temporary fault, K factor is used

– For permanent fault, fuse operates prior to recloser’s delay trip

• Coordination between fuse and fuse – Max clearing time of primary fuse will not exceed 0.75 times the

minimum melting time of the secondary fuse

11

Page 12: Lab IEEE 34 Node Radial Test Feeder Overcurrent Protection ... · PDF fileOvercurrent Protection for the IEEE 34 Node Radial Test Feeder Hamed B. Funmilayo, James A. Silva and Dr

Fault Case Studies

• Fault on main feeder

• Fault on ordinary laterals

• Fault on laterals with reactive compensation

• Faults on laterals with step-down transformer

12

Page 13: Lab IEEE 34 Node Radial Test Feeder Overcurrent Protection ... · PDF fileOvercurrent Protection for the IEEE 34 Node Radial Test Feeder Hamed B. Funmilayo, James A. Silva and Dr

Fault on ordinary laterals

• Recloser operates on its instantaneous trip for temporary fault

• For permanent fault, fuse operates to clear the fault and isolates the lateral

13

Instantaneous trip of recloser

Fuse melting time

Delayed curve of recloser (backup)

Recloser-Fuse coordination for min fault at 810

Page 14: Lab IEEE 34 Node Radial Test Feeder Overcurrent Protection ... · PDF fileOvercurrent Protection for the IEEE 34 Node Radial Test Feeder Hamed B. Funmilayo, James A. Silva and Dr

Discussion of Results

– RECLOSER-FUSE COORDINATION TIME INTERVALS FROM DIGSILENT

14

Page 15: Lab IEEE 34 Node Radial Test Feeder Overcurrent Protection ... · PDF fileOvercurrent Protection for the IEEE 34 Node Radial Test Feeder Hamed B. Funmilayo, James A. Silva and Dr

OPD List for the Test Feeder

15

Page 16: Lab IEEE 34 Node Radial Test Feeder Overcurrent Protection ... · PDF fileOvercurrent Protection for the IEEE 34 Node Radial Test Feeder Hamed B. Funmilayo, James A. Silva and Dr

Summary/Conclusions

16

• A conventional overcurrent protection and coordination scheme was implemented on IEEE 34 Node Test Feeder computer model in DIgSILENT

• The final list of selected OCP was provided

• Coordination was achieved for different cases

• This may be used for easy comparison and assessment of future overcurrent protection studies regarding radial distribution system with or without additions such as DG

Page 17: Lab IEEE 34 Node Radial Test Feeder Overcurrent Protection ... · PDF fileOvercurrent Protection for the IEEE 34 Node Radial Test Feeder Hamed B. Funmilayo, James A. Silva and Dr

Acknowledgement

• The authors would like to thank F. J. Verdeja Perez, J. Mendoza, S. Duttagupta, M. Marotti, K. Mansfield, T. Djokic, and H. E. Leon for their contributions, along with the assistance of Prof. W. H. Kersting.

• This work was supported in part by the U.S. National Science Foundation under Grant ECS-02-18309.

• Paper no. TPWRD-00792-2007.

17

Page 18: Lab IEEE 34 Node Radial Test Feeder Overcurrent Protection ... · PDF fileOvercurrent Protection for the IEEE 34 Node Radial Test Feeder Hamed B. Funmilayo, James A. Silva and Dr

18

Contact information: Dr. Karen L. Butler-Purry

Email: [email protected]