Underground Storage Tank Underground Storage Tank Operator Class A Operator Class A Training Course Training Course Presented By: Presented By: Doug Kassay Doug Kassay Module 1 Operator Requirements and Responsibilities

KPE - Class a&B Operator Training Presentation

Embed Size (px)

Citation preview

Page 1: KPE - Class a&B Operator Training Presentation

Underground Storage Tank Underground Storage Tank Operator Class AOperator Class ATraining CourseTraining Course

Presented By:Presented By:Doug KassayDoug Kassay

Module 1Operator

Requirements and Responsibilities

Page 2: KPE - Class a&B Operator Training Presentation

Operator Training Requirements

PA Code Title 25 Chapter 245.436 became effective December 26, 2009

Requires all facilities with regulated underground storage tanks to have at least one designated Class A, B, and C operators by August 8, 2012

Class A OperatorAssigned the primary responsibility of ensuring compliant operation of the underground storage tank system(s) at a facility. Makes sure UST systems are properly installed, repairs are made correctly and in atimely manner, and that documentation of repairs/modificationsis maintained.

Page 3: KPE - Class a&B Operator Training Presentation

Class A OperatorA class A operator must understand the different operator classifications along with the responsibilities and training requirements that accompany themA class A operator can train class C operatorsHe or she should prepare site maps, emergency procedures, and safety/maintenance checklists for the other designated operators.

Class B OperatorUnderstands day to day operations relating to compliance, monitoring, record keeping, maintenance, and spill prevention. Ensures equipment used on the UST system is operational, third party certified, and capable of functioning with the specific system. This includes overfill & spill prevention, corrosion protection, and release detection equipment.Must be familiar with their own duties and the duties of the Class C operators. Class B operators may also train Class C operators.

Page 4: KPE - Class a&B Operator Training Presentation

Class C OperatorsClass C operators are trained by the Class A or Class B operatorsThe main focus of a Class C operator is in emergency procedures, such as: – Spill response and general site

safety. (ie not allowing smoking at the pumps)

– Making appropriate notifications for spills, alarms, etc……

– Location and operation of the emergency stop

Multi-Class Operators

An ‘A’ operator is also a qualified ‘B’ and/or ‘C’ operator.

A ‘B’ operator is also a qualified ‘C’ operator.

For a small facility one person can fulfill all the required operator roles but….

Page 5: KPE - Class a&B Operator Training Presentation

Operator Response Requirements

A Class A or B operator must be available for immediate phone consultation during operating hours.A Class A or B operator must be able to be at the site within 24 hoursA Class C operator should always be at the site during operating hours.

What About Unmanned Facilities?Class A and B response times are the same. A Class C operator must be available immediately for phone consultation and be able to be onsite within 2 hours of being contacted Emergency contacts and procedures must be prominently displayed for all users of the site

Page 6: KPE - Class a&B Operator Training Presentation

Other Operator Options

Regulations do not specify that an operator must be a direct employee.Operator classes can be sub-contracted to a 3rd party that possess the appropriate certification. A contract must exist.Existing PADEP certified individuals in the IUM and/or UMX category are automatically certified as an ‘A’ operator.

Module 2Financial Responsibility

&Tank Notifications/Registration

Page 7: KPE - Class a&B Operator Training Presentation

Financial ResponsibilityUSTIF

All regulated USTs must be insured through the Pennsylvania Underground Storage Tank Indemnification Fund (USTIF).The fund is administered by ICF, Inc., a third party consulting firm.Heating oil tanks greater then 3,000 gallons can opt into the fund.

USTIF FeesAll regulated USTs storing gasoline, gasohol, aviation fuel, new motor oil, hazardous substances, mixture, other, and diesel fuel tanks at farms pay 1.1 cents per gallon which is charged by the distributor at the time of delivery.All regulated USTs storing heating oil, diesel fuel, kerosene, used motor oil and unknown products are charged a fee of 8.25 cents per gallon of UST capacity paid annually

Page 8: KPE - Class a&B Operator Training Presentation

Filing USTIF ClaimsCall (717) 787-0763 or (800) 595-9887 (IN PA) to report a claim. Claims must be submitted within 60 days of the discovery of the release or they will be denied!!!Just because a spill isn’t reportable to PA DEP does not mean it can’t be turned into a USTIF claim. Deductibles are $5,000 per tank per occurrenceCoverage is $1.5 million per occurrence.

PA DEP Forms30 Day Closure/Installation Form: Submitted 30 days before the installation or permanent closure of a UST system. This should be signed by the tank owner and lists the DEP certified individual to perform the work.

Page 9: KPE - Class a&B Operator Training Presentation

PA DEP FormsRegistration Form: This is used to register or remove tanks from PA DEP’s system. It must be signed by an individual certified in the activity being claimed on the form as well as the tank owner.

Page 10: KPE - Class a&B Operator Training Presentation
Page 11: KPE - Class a&B Operator Training Presentation
Page 12: KPE - Class a&B Operator Training Presentation
Page 13: KPE - Class a&B Operator Training Presentation
Page 14: KPE - Class a&B Operator Training Presentation
Page 15: KPE - Class a&B Operator Training Presentation

PA DEP FormsRegistration Amendment: Can be used to change facility or product information. It can also be used to register a facility as temporarily out of service (TOS). This only needs to be signed by the tank owner or owner representative.

Page 16: KPE - Class a&B Operator Training Presentation

PA DEP FormsModification Report: Completed by a DEP certified individual after a modification to the UST system is made. A copy should be retained by the owner/operator for all future inspections.Almost any work that involves your fuel system, including excavation work above your fuel system requires a DEP certified individual.The DEP charges the certified individual for filing major modification reports.

Replacing a drop tubeRepairing a line leak

Replacing a flex hoseAdding/replacing anodes on a tank

Replacing a leak detectorAdding a new form of line release detection (ie.. Install tank monitor)

Adding a spike anode to a flex lineAny work involving excavation

MinorMajor

Modification Types

Page 17: KPE - Class a&B Operator Training Presentation
Page 18: KPE - Class a&B Operator Training Presentation

PA DEP Forms

Facility Operations Inspection (FOI): Completed every three years by a PA DEP certified inspector. Copies should be retained by the owner/operator. DEP generally sends an inspection reminder letter. The due date of the next inspection is also on the annual registration certificate.This form is signed by both the inspector and the owner.

Page 19: KPE - Class a&B Operator Training Presentation
Page 20: KPE - Class a&B Operator Training Presentation

Notice of ContaminationNotice of ContaminationVerbal notification within 24 hours by Verbal notification within 24 hours by owner/operator or tank handler on their behalf (2 owner/operator or tank handler on their behalf (2 hours by certified individual when obvious hours by certified individual when obvious contamination is encountered)contamination is encountered)Written notification from the installer/inspector Written notification from the installer/inspector must be submitted within 48 hours of must be submitted within 48 hours of confirmation of the contamination (Notification of confirmation of the contamination (Notification of Contamination Form)Contamination Form)Written notification by owner/operator filed within Written notification by owner/operator filed within 15 days to the appropriate regional office and 15 days to the appropriate regional office and local municipality (Notification of Reportable local municipality (Notification of Reportable Release Form)Release Form)A certified individual may also call the notice in A certified individual may also call the notice in then submit a written notification jointly with the then submit a written notification jointly with the owner/operator within 15 days.owner/operator within 15 days.

Page 21: KPE - Class a&B Operator Training Presentation
Page 22: KPE - Class a&B Operator Training Presentation

What is a Reportable Spill?Any spill to soil or a waterway is reportableA spill to an impervious surface (concrete or asphalt) should only be reported to DEP in quantities greater than 25 gallonsAll spills can and should be reported to USTIF at the same time you report them to the DEP.

PA DEP Forms

All forms, instructions and regulations can be found at:

www.dep.state.pa.usKeyword: Storage Tanks

OrOn the USB drive provide to you as part of

this class.

Page 23: KPE - Class a&B Operator Training Presentation

Recordkeeping Requirements

Records are divided into two different types:– Permanent– Temporary

Permanent RecordsCorrosion expert’s design of your impressed current system, including the site assessment.Tank system installation, modification and upgrade documents.Tank system assessment records prior to an upgrade.Installation testing and commissioning reports required for corrosion protection systems.UST system repairs, including those in response to a release.Tank lining evaluation reports.Department approval for a variance or alternative leak detection method.

Page 24: KPE - Class a&B Operator Training Presentation

Temporary RecordsYour current tank registration certificate.Tank and pipe release detection records for the past 12 months.The last annual check/test/maintenance records of leak detection equipment which verify proper functionality.The last two impressed current system readings.The last CP survey for ICCP systems.The last 2 CP tests for galvanic systems.Properly completed closure report including site investigation. (must keep for 3 years)The last sump testing records. (installed or replaced after 11/10/2007)

Module 1 & 2 ReviewHow many of each operator class must each company have?

Who can train a companies Class C operator(s)?

One. A company is required to have at least one Cl ass A, B & C operator

The class A and B operators

What is the primary focus of the class C operators training?Emergency procedures

At a manned facility when should a class C operator be onsite?During operating hours

How many hours until a class A or B operator must be onsite after an emergency?Within 24 Hours

Page 25: KPE - Class a&B Operator Training Presentation

Module 1 & 2 ReviewUSTIF claims must be submitted within how many days of discovering the release?

How much is the USTIF deductible per tank, per occurance?

60 Days

$5,000.00

For record keeping purposes, records fall into two categories, what are they?Permanent & Temporary

How many hours until you must verbally notify DEP about a spill?24 hours

How many days are you afforded before you must submit a written notification of contamination form?15 Days

Module 3Module 3Site SafetySite Safety

& & Emergency ProceduresEmergency Procedures

Page 26: KPE - Class a&B Operator Training Presentation

Health and SafetyHealth and Safety

HazardsHazards

Safety EquipmentSafety Equipment

Safety Training Safety Training

Emergency Procedures/ContactsEmergency Procedures/Contacts

Safety Inspections and ChecklistsSafety Inspections and Checklists

HazardsHazards

TrafficTraffic

FireFire

ExplosionExplosion

Chemical Chemical ExposureExposure

WeatherWeather

AsphyxiationAsphyxiation

Other peopleOther people

Page 27: KPE - Class a&B Operator Training Presentation

The Fire TriangleThe Fire Triangle3 fire components:3 fire components:

1.1. Fuel Source Fuel Source

2.2. OxygenOxygen

3.3. Ignition SourceIgnition Source

A fire can A fire can notnot occur unless all three occur unless all three are present. The one most under are present. The one most under your control is the ignition source.your control is the ignition source.

Personal Safety EquipmentPersonal Safety EquipmentProper footwear Proper footwear Safety vest for doing work in the parking Safety vest for doing work in the parking lot and/or fueling arealot and/or fueling areaSafety conesSafety conesAll relevant safety contact All relevant safety contact information should be readily information should be readily availableavailable

Page 28: KPE - Class a&B Operator Training Presentation

Site Safety EquipmentSite Safety Equipment

Bollards & island forms Bollards & island forms –– Protection of the dispensers.Protection of the dispensers.

Swivels Swivels –– Protects the hose from twisting and kinking.Protects the hose from twisting and kinking.

BreakBreak--awaysaways and shear valves and shear valves –– Help to prevent Help to prevent spills/fire when a dispenser is hit or when a customer spills/fire when a dispenser is hit or when a customer drives off with the nozzle still in his tank.drives off with the nozzle still in his tank.

Nozzles Nozzles –– Help prevent spills.Help prevent spills.

EstopEstop –– Kills power to the fueling area to help prevent Kills power to the fueling area to help prevent fires.fires.

Intercom Intercom –– Used to communicate with the customer.Used to communicate with the customer.

Snuffer and fire extinguishers Snuffer and fire extinguishers –– Used to fight fires.Used to fight fires.

Safety Training and DocumentationSafety Training and Documentation

All employees who work at a facility utilizing a All employees who work at a facility utilizing a UST system should receive training on the UST system should receive training on the hazards that they will encounter, prevention hazards that they will encounter, prevention measures, and emergency proceduresmeasures, and emergency procedures

Training should cover necessary safety Training should cover necessary safety equipment and proper use of that equipmentequipment and proper use of that equipment

Emergency procedures and contacts Emergency procedures and contacts

Are weekly and daily safety checks being Are weekly and daily safety checks being performed? Documented?performed? Documented?

Page 29: KPE - Class a&B Operator Training Presentation

Emergency ProceduresEmergency Procedures must be posted at every regulated UST facility by June 28, 2010Where is the location of the Emergency Stop and how is it operated? Also include the location of exits, spill kits, and fire extinguishersEmergency proceduresshould include appropriate emergencycontacts and a list of what notifications need to be made

Safety Inspections & ChecklistsWhat site specific items are checked weekly and/or daily at your facility? What is required by regulations and what is a good idea for general safety?Who is performing the inspection? How are they being documented and how is this documentation being stored?

Page 30: KPE - Class a&B Operator Training Presentation

Workgroup DiscussionWorkgroup Discussion

Divide into groups based on facility types:– Attended self service (C-store/repair garage)– Unmanned sites (Retail/fleet/municipal)– Manned sites (Trucking terminal/municipal/fleet)

Pair up in groups of 5 or 6 with people from different companies. Discuss ideas for implementing Class C operator training in your organization.

Module 4Module 4Tank Components and Tank Components and Product CompatibilityProduct Compatibility

Page 31: KPE - Class a&B Operator Training Presentation

Components of a Fuel SystemComponents of a Fuel SystemA. Flow ChannelsB. Tank Bottom Deflector PlatesC. Primary Tank FittingsD. Monitoring Fitting1. Turbine Enclosure2. Fitting Kits for Turbine Enclosure3. Secondary Containment Collar4. Reservoir Sensor5. Fiberglass Reservoir (replaces monitoring fitting)6. Containment Collar Sensor7. Monitoring Fluid with Color Tracer8. Electronic Inventory Gauge9. Electronic Control Panel10. Split-Strap Anchor System11. Deadman Anchor12. Dispenser13. Dispenser Sump14. Double-Wall Pipe15. Submersible Pump16. Fill Tube with Overfill Shut-Off 17. Ball Float Valve18. Overfill Spill Container19. Primary Tank Vent

Venting & Vapor Recovery EquipmentVenting & Vapor Recovery EquipmentAll tanks must be vented. The vent riser should All tanks must be vented. The vent riser should be made of steel and extend 12be made of steel and extend 12’’ in the air (3in the air (3’’above rooflines)above rooflines)Stage I vapor recovery must be performed on Stage I vapor recovery must be performed on all gasoline tanks greater than 2,000gal and is all gasoline tanks greater than 2,000gal and is performed at the tank during deliveriesperformed at the tank during deliveries--Two point connectionTwo point connection--Coaxial connectionCoaxial connectionStage II vapor recovery is only required on Stage II vapor recovery is only required on gasoline dispensers in specific counties and is gasoline dispensers in specific counties and is performed at the dispenser while customers are performed at the dispenser while customers are fueling vehicles. fueling vehicles.

Page 32: KPE - Class a&B Operator Training Presentation

Spill and Overfill EquipmentSpill and overfill equipment is designed to catch small spills and prevent overfilling during deliveries.This equipment focuses on the delivery portion of the UST system. Equipment includes: spill buckets, drop-tube shutoff devices, ball floats, and alarms

Release Detection Equipment

Release detection equipment detects releases from various parts of the UST systemThis includes Automatic Tank Gauges (ATGs), probes, sensors, and leak detectors.

Page 33: KPE - Class a&B Operator Training Presentation

Secondary Containment SumpsSecondary Containment Sumps

Used to contain releases from doubleUsed to contain releases from double--wall piping wall piping and isolate piping componentsand isolate piping componentsNew DEP regulations now require containment New DEP regulations now require containment sumps to be tested upon installation or sumps to be tested upon installation or modification (including piping replacement)modification (including piping replacement)Testing is commonly performed by flooding the Testing is commonly performed by flooding the containment area with water and monitoring the containment area with water and monitoring the level for at least one hour. (called hydrostatic level for at least one hour. (called hydrostatic testing)testing)Water Level should be at least 4Water Level should be at least 4”” above highest above highest sump penetrationsump penetration

Sump TestingSump Testing

Page 34: KPE - Class a&B Operator Training Presentation

Tank Components & Product Compatibility

Product compatibility is becoming more and more of an issue with new fuels and blended fuels. Specifically ethanol blended gasoline and biodiesel. Ethanol is corrosive to softer metals.Every component in a UST system must be UL listed for the product that is being stored & dispensed in that system. UL ratings should be available through the manufacturer of the specific component.

Changing Product - TipsWhat if you want to change regulated products in a UST system?Ensure that the system is capable (UL listed) for the new product &HAVE THE TANK THROUGHLY CLEANED!!!!This is especially important when switching from conventional gas to an ethanol blend and from conventional diesel to biodiesel. Stickers are required on dispensers informing customers of the fuel and its contents Water should never be in a tank in the first place. Biodiesel and ethanol blended gasoline are more sensitive to water, possibly causing phase separation or bacterial/fungal growth.

Page 35: KPE - Class a&B Operator Training Presentation

Changing Product - Paperwork

Changing product grades does not require DEP notification. Ie… regular to super, or from conventional to ethanol or from diesel to bio-diesel.Changing regulated product types does require DEP notification using either the registration form or the registration amendment form. Ie…from gas to diesel or from kerosene to ethanol.Changing from a regulated product to an unregulated product requires a tank closure. Ie… from gas to heating oil.

Module 3 & 4 ReviewBy June 28th 2010, what must be posted at each facility with a regulated UST?

The fire triangle is composed of what 3 elements?

Emergency procedures

Fuel, oxygen and ignition source

What device helps prevent spills/fires if a dispenser is hit?Shear valve

What are the three main items that need to be on your emergency procedures?

Location and operation of the emergency stop

Notifications that need to be made

A list of emergency contacts

Page 36: KPE - Class a&B Operator Training Presentation

Module 3 & 4 ReviewWhat form is required to change regulated product types in a tank?

Stickers are required on dispensers to inform customers of fuel type and ____________.

Registration form or Registration amendment form

Blend ratio

DEP regulations of 11/10/2007 now require sump testing at what frequency?Upon installation, repair or replacement

All equipment in a UST system must be compatible and ______ listed for the product being store and dispensed.UL listed

Module 5Spill & Overfill Prevention

Page 37: KPE - Class a&B Operator Training Presentation

Spill ContainmentSpill ContainmentRequired on all UST systems filled in amounts greater than 25 gallons

Spill containment devices are often referred to as spill Spill containment devices are often referred to as spill buckets or catchment basinsbuckets or catchment basins

They should have a capacity of at least 5 gallons and They should have a capacity of at least 5 gallons and be placed around ports where product is transferred be placed around ports where product is transferred into the UST system (fill and vapor recovery ports)into the UST system (fill and vapor recovery ports)

Newly installed or modified spill buckets must be Newly installed or modified spill buckets must be tested (hydrostatic test) to show they are liquid tight. tested (hydrostatic test) to show they are liquid tight. The records should be retained until the unit is The records should be retained until the unit is replaced or modified. replaced or modified.

Spill Containment

Page 38: KPE - Class a&B Operator Training Presentation

Overfill PreventionOverfill PreventionThree main types: overfill drop tube, ball float and overfill alThree main types: overfill drop tube, ball float and overfill alarm.arm.

No matter which you have it must:No matter which you have it must:

Must automatically shutoff the flow of product to the tank at Must automatically shutoff the flow of product to the tank at 95% capacity or alert the driver at 90% capacity. 95% capacity or alert the driver at 90% capacity. There are two types of deliveries that UST systems receive. There are two types of deliveries that UST systems receive. 1. Pressurized1. Pressurized2. Gravity2. GravityTHE OVERFILL PREVENTION DEVICE / METHOD MUST BE THE OVERFILL PREVENTION DEVICE / METHOD MUST BE COMPATIBLE WITH THE DELIVERY METHOD!!!!COMPATIBLE WITH THE DELIVERY METHOD!!!!

Overfill PreventionOverfill Prevention --Drop tube shutoff devicesDrop tube shutoff devices

These are commonly referred to as These are commonly referred to as ““flappersflappers””

Action point should be 95% of the tanks Action point should be 95% of the tanks capacity at the highest. They can be set lower. capacity at the highest. They can be set lower.

Most dropMost drop--tube shutoff devices are only tube shutoff devices are only capable of stopping gravity deliveries.capable of stopping gravity deliveries.

Different devices must be used for pressurized Different devices must be used for pressurized deliveries. deliveries.

Page 39: KPE - Class a&B Operator Training Presentation

Overfill Prevention DropOverfill Prevention Drop --Tube Tube Shutoff DevicesShutoff Devices

AdvantagesAdvantages

Easily verifiedEasily verified

Hopefully an easy Hopefully an easy install (no power install (no power needed)needed)

DisadvantagesDisadvantages

Easily bypassed by Easily bypassed by delivery driverdelivery driver

Must be changed if Must be changed if the customer the customer switches delivery switches delivery methodsmethods

Ball Float ValvesBall Float Valves

Works on the theory Works on the theory that if air canthat if air can’’t exit the t exit the tank, fuel cantank, fuel can’’t go in.t go in.

Action point must be Action point must be set at 95% or less of set at 95% or less of the tankthe tank’’s capacity.s capacity.

Page 40: KPE - Class a&B Operator Training Presentation

Ball Float ValveBall Float ValveOPEN CLOSED

Ball Float ValvesBall Float ValvesAdvantagesAdvantages

Low costDisadvantagesDisadvantages

Not easily verified.No one knows if/when it breaksTank can be damaged if it receives a pressurized deliveryCan be very difficult to removeCannot not be used on systems with remote fills, coaxial vapor recovery, and suction systems with an air eliminator.

Page 41: KPE - Class a&B Operator Training Presentation

External Overfill AlarmsExternal Overfill AlarmsAudible and/or Audible and/or visual alarm that visual alarm that notifies the driver notifies the driver when the tank is when the tank is 90% full. 90% full.

It must be audible It must be audible and/or visible to and/or visible to the driver while he the driver while he or she is making or she is making the delivery.the delivery.

External Overfill AlarmsExternal Overfill Alarms

AdvantagesAdvantages

Can be used in most Can be used in most applicationsapplications

Easily testedEasily tested

DisadvantagesDisadvantages

ExpensiveExpensive

May need to run May need to run additional conduit at additional conduit at an existing sitean existing site

Does not physically Does not physically restrict the deliveryrestrict the delivery

Page 42: KPE - Class a&B Operator Training Presentation

Module 6Release Detection

Release Detection Release Detection Regulation RequirementsRegulation Requirements

TankTank

0.2gal/hr monthly test0.2gal/hr monthly test

or Interstitial or Interstitial monitoringmonitoring

Interstitial monitoring Interstitial monitoring is required on all is required on all USTsUSTs installed after installed after November 10, 2007. November 10, 2007.

Pressurized PipingPressurized Piping

0.2gal/hr monthly test or 0.2gal/hr monthly test or 0.1gal/hr annual test0.1gal/hr annual test

3.0gal/hr continuous form of 3.0gal/hr continuous form of release detection which must release detection which must be tested annually unless it be tested annually unless it is a self diagnostic ELLDis a self diagnostic ELLD

Pressurized piping installed Pressurized piping installed after Nov 10, 2007 must after Nov 10, 2007 must have positive shutdown on have positive shutdown on the 3.0gal/hr method & the 3.0gal/hr method & interstitial monitoring.interstitial monitoring.

Page 43: KPE - Class a&B Operator Training Presentation

Release Detection Release Detection Regulation RequirementsRegulation Requirements

American Suction Style American Suction Style Piping (check valve at Piping (check valve at

both ends)both ends)

Tightness test every Tightness test every three yearsthree years

oror

Monthly monitoring of Monthly monitoring of containment sumps at containment sumps at both endsboth ends

European or Safe European or Safe Suction Style (check Suction Style (check valve at dispenser valve at dispenser

end only)end only)

None currently None currently requiredrequired

Release Detection Release Detection Regulation RequirementsRegulation Requirements

If a release is ever suspected, an If a release is ever suspected, an investigation should be completed as investigation should be completed as

soon as possible but no later than soon as possible but no later than 7 days!!!7 days!!!

Page 44: KPE - Class a&B Operator Training Presentation

Tank Interstitial Monitoring Interstitial monitoring is monitoring the space between the two walls of double wall tanks for signs of a release (liquid). Must performed at least once a month. This can be done by manually sticking the interstice and logging the results or…With a sensor between the two walls where a status report is printed or the alarm status is manually loggedInterstitial monitoring has two main benefits:– It is not affected by manifolded systems– It is not affected by inventory levels

Automatic Tank GaugingAutomatic tank gauging uses the probe in the tank to perform a 0.2gal/hr test. This can be done in two ways– Static testing is when the fuel is monitored for one period of

time over a 2-5 hour period. The tank must not be in operation during this time and this method can not be used on manifolded systems.

– Continuous monitoring is when the probe tests for smaller amounts of time, while the system is not operating. It compiles the data over time gives a test results. This is a software upgrade for most ATGs (SCALD- Incon; CSLD-Veeder Root). The upgrade makes the ATG able to test manifolded systems. It performs better for sites that operate 24 hours a day and sites that frequently have low volumes in their tanks.

Page 45: KPE - Class a&B Operator Training Presentation

Statistical Inventory Reconciliation(SIR)

This must be done through an approved third party vendor. Daily stick readings, sales volumes, and delivery receipts must be very well kept and submitted to the vendor every month. They compile the data and send a test result. In addition to providing a monthly 0.2gal/hr tank test, SIR also provides a monthly 0.2gal/hr piping test. The tanks must be stuck every day!

Pressurized Piping Release Detection

UST systems utilizing pressurized piping are required to have two forms of piping release detection. The first is a continuous 3.0gal/hr form. A 3.0gal/hr leak would need to be picked up within one hour. This is the “big leak” form. The second is a monthly 0.2gal/hr form. A 0.2gal/hr leak must be picked up within a month. This is the “small leak” form. A 0.1gal/hr annual test can be substituted for 0.2gal/hr monthly testing.

Page 46: KPE - Class a&B Operator Training Presentation

Continuous 3.0gal/hr Piping Release Detection

Leak Detectors: Leak detectors are installed in the submersible pump and monitor fuel inside the line to check for leaks. In the event a leak is detected, they can restrict or shut off the flow of product. There are mechanical and electronic leak detectors. Mechanical leak detectors must be tested annually.Electronic leak detectors should be tested per the manufacturer’s recommendations, which is usually an annual functionality test.

Continuous 3.0gal/hr Piping Release Detection

Compliance via sensor: This can only be performed at facilities with double wall piping and containment sumps at both ends. A monthly sensor status report must be printed and kept for at least a year. When using sensors for continuous 3.0gal/hr piping release detection, THE SENSORS MUST BE TESTED ANNUALLY!!!Facilities with double-wall piping and sumps must also perform a visual check of the sumps and document it monthly even if not using sensors as the 3.0gal/hr form of line release detection.

Page 47: KPE - Class a&B Operator Training Presentation

Monthly 0.2gal/hr piping release detection

This can be done with electronic line leak detectors or SIR. SIR follows the same procedures as tank release detection

0.1gal/hr Annual Piping Release Detection

A 0.1gal/hr annual test can be substituted for monthly 0.2 gal/hr testing. There are two ways of achieving this. Most electronic line leak detectors can perform this. A passing test print out must be retained. The manufacturer’s recommendations for testing of the leak detector should be followed. An annual line test meets the 0.1gal/hr requirement. This must be performed by a PA DEP UTT certified individual.

Page 48: KPE - Class a&B Operator Training Presentation

Piping Release DetectionAs of November 2009, all facilities with pressurized double-wall piping and containment sumps must do a monthly sump check. This can be done visually or with a liquid sensor. The results must be documented. All unmanned facilities with pressurized piping must have a continuous 3.0gal/hr form of piping release detection that automatically shuts off or restricts the flow of product in the event of a release.

Release Detection Record KeepingRelease detection records must be maintained for at least one year. The most recent twelve months of records should be readily available for inspection.

Page 49: KPE - Class a&B Operator Training Presentation

Module 5 & 6 ReviewUST’s filled in increments of _____ gallons or less are exempt from _____ & _____?

Why can’t a ball float be used with pressurized deliveries?

25 gallons are exempt from spill and overfill preve ntion

When the ball closes, the pressurized delivery can rupture the tank.

How can a delivery driver bypass an overfill drop tube?By breaking off the tank stick in order to block th e flapper valve from closing.

What are the three types of overfill prevention equipment?

Drop tube shut off devices

Ball floats

Overfill alarms

What can’t an overfill alarm do?Restrict the delivery

Module 5 & 6 ReviewRelease detection records must be maintained for how long?

For your small form of line release detection your monthly leak test should be at a leak rate of ______ gallons per hour ?

12 months – one pass per tank/line per month for the last 12 months

.2gph (or one annual test at .1gph)

Your large form of line release detection is a continuous method able to detect a leak rate of _____ gallons per hour?3gph

Owners with complete secondary line containment must perform what monthly?Interstitial monitoring (visual sump inspections or sump sensors)

Within 7 days of a failed release detection test an owner must do what?Investigate

Page 50: KPE - Class a&B Operator Training Presentation

Module 7Module 7Cathodic Protection SystemsCathodic Protection Systems

Cathodic Protection Cathodic Protection –– What is it?What is it?Any one of several methods for protecting underground tanks and pipelines from corrosion.Corrosion results from an electric current which is caused by contact between metal surfaces, water, and the chemicals present in soils and water; cathodic protection counteracts this current.

Other common names: CP, corrosion protection, STIP-3 or STIP-3 Testing.

What DEP says:What DEP says:Any component of a UST system that is in contact with soil and/or back fill must be protected from corrosion.

Page 51: KPE - Class a&B Operator Training Presentation

Possible Petroleum Equipment Possible Petroleum Equipment Requiring Cathodic ProtectionRequiring Cathodic Protection

TanksLinesFlex hosesTank top fittings

Cathodic Protection Cathodic Protection –– How it WorksHow it Works

Regardless of the type of CP system you have, it Regardless of the type of CP system you have, it works by managing the flow and direction of the works by managing the flow and direction of the current which controls corrosioncurrent which controls corrosionMust be tested every 3 years Must be tested every 3 years New installations and repaired/upgraded New installations and repaired/upgraded systems need tested within 6 months of the systems need tested within 6 months of the installation and every 3 years thereafter installation and every 3 years thereafter Rectifiers on impressed current systems must be Rectifiers on impressed current systems must be monitored and logged every 60 daysmonitored and logged every 60 days

Page 52: KPE - Class a&B Operator Training Presentation

Cathodic Protection Cathodic Protection –– How it WorksHow it WorksRegardless of the type of CP system you have, it Regardless of the type of CP system you have, it works by managing the flow and direction of the works by managing the flow and direction of the current which controls corrosion.current which controls corrosion.

Uses an outside power source Uses an outside power source called a rectifier to create called a rectifier to create current flow. These systems current flow. These systems are designed by a corrosion are designed by a corrosion engineer/expert and are engineer/expert and are typically used to protect large typically used to protect large quantities of metal or added to quantities of metal or added to tanks/lines that were not tanks/lines that were not factory protected with galvanic.factory protected with galvanic.

Uses the difference in energy Uses the difference in energy levels between the steel tank levels between the steel tank (hard metal) and zinc or (hard metal) and zinc or magnesium anodes (soft metal) magnesium anodes (soft metal) to create current flow. This to create current flow. This causes corrosion to occur on causes corrosion to occur on the softer metal. This is the softer metal. This is typically a factory installed typically a factory installed option.option.

Impressed Current (ICCP)Galvanic (Sacrificial)

Two types of cathodic protection systems

Alternative to CP systems

In addition to the two types of CP systems used to prevent corrosion there is another way to meet DEP’s requirement for corrosion protection and that is:

– Isolating the component from the soil and/or back fill.

Page 53: KPE - Class a&B Operator Training Presentation

Galvanic ProtectionSacrificial System

A sacrificial anode protects steel by managing the flow of electrical currents from the equipment.The sacrificial anode(s) are attached to the component that is to be protected.The anodes are a softer metal then what is being protected, typically they are made of zinc or magnesium.Electrons exit the system through the anode. The anode corrodes instead of the tank.

Galvanic SystemGalvanic System

Page 54: KPE - Class a&B Operator Training Presentation

Impressed Current SystemThis type of system uses anodes attached to a rectifier to introduce a negative DC current to the soils around the objects to be protected. It is through the current introduction that corrosive forces are transferred to the anode.ICCP systems typically protect large steel structures or are used at facilities that did not come with factory installed galvanic CP systems.These systems are designed by a corrosion expert, typically someone holding NACE certification, and require a site survey be completed prior to installation.

Schematic & Components of an Schematic & Components of an ICCP SystemICCP System

AnodesAnodes

RectifierRectifier

Page 55: KPE - Class a&B Operator Training Presentation

Cathodic Protection Upgrades/Repairs

Anodes can be added to equipment if needed, but:An approved method must be followed when adding supplemental protection to a UST, this will involve a NACE certified corrosion expert to size the anode properly.A spike anode may be added to a flex hose to properly protect them from corrosion. This does not require a NACE certified individual.Adding anodes to soil safe brand flex connectors does not make them compliant.

Page 56: KPE - Class a&B Operator Training Presentation

CP Testing and Record Keeping Requirements

Must be third party tested upon installation or repair.Must be third party tested 6 months after installation or repair.Must be third party tested every 3 years thereafter.

Galvanic Systems:

Same as above, plus:Must record rectifier volt & amp readings every 60 days.

Impressed Current Systems:

Must keep last 12 months of rectifier readings for ICCP systems. (temp. record)Must keep last the last two sets of CP test results (temp record)Must keep the initial site survey for ICCP systems (permanent record)

Records:

Module 8Module 8Temporary and Permanent Temporary and Permanent Closure of Regulated UST Closure of Regulated UST

systemssystems

Page 57: KPE - Class a&B Operator Training Presentation

Temporarily Out of Service T.O.S.Temporarily Out of Service T.O.S.

Makes facilities that are not being used Makes facilities that are not being used safer safer Useful for facilities awaiting sale or saving Useful for facilities awaiting sale or saving for permanent closurefor permanent closure

Requirements for Temporary Requirements for Temporary ClosureClosure

Tanks must be emptied (less than 1Tanks must be emptied (less than 1”” of of substance) substance)

Lines must be emptied and capped or blindedLines must be emptied and capped or blinded

Secure tank against unauthorized entrySecure tank against unauthorized entry

Submit a registration amendment to DEPSubmit a registration amendment to DEP

Page 58: KPE - Class a&B Operator Training Presentation

Temporary Closure ResultsTemporary Closure ResultsUSTsUSTs in temporary closure are exempt from in temporary closure are exempt from release detection and inspection requirements release detection and inspection requirements If a UST inspection is missed during the TOS If a UST inspection is missed during the TOS period one should be performed prior to period one should be performed prior to resuming operationresuming operationAnnual registration and insurance fees must still Annual registration and insurance fees must still be paidbe paidCorrosion protection must be maintainedCorrosion protection must be maintainedTank must be ventedTank must be vented

Temporary Closure Time LimitsTemporary Closure Time Limits

A noncompliant UST has a 12 month (1 A noncompliant UST has a 12 month (1 year) temporary closure time period.year) temporary closure time period.

A compliant UST has a 36 month (3 year) A compliant UST has a 36 month (3 year) temporary closure time period.temporary closure time period.

Time limits can be shortened at the Time limits can be shortened at the discretion of DEP.discretion of DEP.

At the end of a temporary closure time At the end of a temporary closure time limit the tank must be permanently closed limit the tank must be permanently closed or returned to service operating, fully or returned to service operating, fully compliant.compliant.

Page 59: KPE - Class a&B Operator Training Presentation

Permanent UST Closure

A PA DEP Certified individual/company must be used to

permanently close a UST system

Closure in PlaceClosure in PlaceRemoval is always preferred though Removal is always preferred though circumstances can sometimes make removal circumstances can sometimes make removal impossibleimpossible

Sampling is still requiredSampling is still required

Closure in place is almost always more Closure in place is almost always more expensive then removal.expensive then removal.

Page 60: KPE - Class a&B Operator Training Presentation

Closure In PlaceClosure In PlaceAll product must be removed and the tank must be All product must be removed and the tank must be thoroughly cleaned before a solid, inert material can thoroughly cleaned before a solid, inert material can be added to fill the tank as much as possiblebe added to fill the tank as much as possible

Closure In Place DisadvantagesClosure In Place Disadvantages

More ExpensiveMore Expensive

More TimeMore Time

Difficult to SampleDifficult to Sample

The The tank(stank(s) may cause issues with the ) may cause issues with the property in the future. property in the future.

Page 61: KPE - Class a&B Operator Training Presentation

Tank RemovalTank Removal

Tank RemovalTank RemovalThe tank is removed from the ground and The tank is removed from the ground and dismantled safely. dismantled safely.

Samples can easily be taken from under Samples can easily be taken from under the tank. the tank.

Page 62: KPE - Class a&B Operator Training Presentation

UST Closure ReportUST Closure ReportA closure report must be created after the A closure report must be created after the permanent closure of any regulated UST. permanent closure of any regulated UST.

Closure reports should include: site information, tank Closure reports should include: site information, tank information, sampling maps, sample results, the information, sampling maps, sample results, the name of the certified individual/company performing name of the certified individual/company performing the closure, and all waste manifests (tanks, piping, the closure, and all waste manifests (tanks, piping, product, etc.product, etc.

If contamination is suspected or confirmed, the If contamination is suspected or confirmed, the closure report must be submitted to PA DEP. closure report must be submitted to PA DEP.

If contamination is not confirmed or suspected, the If contamination is not confirmed or suspected, the closure report must be kept by the owner for 3 years. closure report must be kept by the owner for 3 years.

Module 7 & 8 ReviewA rectifier must have its readings logged every how many days?

Cathodic protection must be tested within _____ months of installation/repair and every _____ years after?

60 days

6 months & 3 years

Any component of a UST system the come in contact with soil/back fill must be protected from what?Corrosion

What brand of flex hose does not have continuity between both metallic ends?

Soilsafe

In addition to CP systems, what is another method of protecting metallic components from corrosion?

Physically isolate the component from soil and/or b ackfill.

Page 63: KPE - Class a&B Operator Training Presentation

Module 7 & 8 ReviewA tank is considered empty if it has _______?

A UST in temporary closure is exempt from what? And not exempt from what?

Less then 1” of product

Tank and line release detection

Cathodic protection testing

How long can a compliant tank system be in TOS? How long can a non-compliant tank system be in TOS?

1 year

How long must a tank owner keep a tank closure report if no contamination was encountered?3 years

3 years