Kidde Fire Suppression Systems Engineered with 3M™ Novec 1230™ Fire Protection Fluid
3M™ Novec 1230™ Fire Protection Fluid
• Manufactured by 3M
• Introduced by 3M in 2003, at NFPA
• Fluorinated Ketone
• CF3CF2C(O)CF(CF3)2
3M™ Novec 1230™ Fire Protection Fluid
• Used in Total Flooding Applications– Class A - (Ordinary combustible
materials)– Class B - (Flammable Liquids)– Class C - (Energized electrical
equipment)
• Design Concentrations
range from 4.2% to 10%
3M™ Novec 1230™ Fire Protection Fluid People Safety
• NOAEL = 10.0%
• LOAEL = >10.0%
• EPA listed as approved for use in occupied spaces
• Class A use concentration = 4.2%
3M™ Novec 1230™ Fire Protection Fluid - Environmental Factors
• 0 Ozone Depletion Potential
• 5 day Atmospheric Lifetime
• Novec 1230 has distinct environmental benefits
3M™ Novec 1230™ Fire Protection Fluid - Major Application Markets
• Data Processing Centers
• Telecommunications – Cell Sites, Switching Centers
• Industrial– Oil and Gas Industry
• Environmentally sensitive markets/end users
3M™ Novec 1230™ Fire Protection Fluid
• Environmentally more friendly than other clean agents
• Minimal Storage Space– Less Hardware over Inerts
• Lower Pressure during discharge than Inerts– Pressure relief venting
• Puts out fire by cooling rather than Oxygen depletion
3M™ Novec 1230™ Fire Protection Fluid - Kidde Offering
• 25 Bar system
• Engineered System Offering– Software– Optimal Design– Ambient Temp Range 0 C to 55 C
3M™ Novec 1230™ Fire Protection Fluid - Kidde Offering
• Cylinder Sizes to be offered– 10-lb. to 900-lb. Offering
• All the necessary accessories for Installation– Brackets, Nozzles,
• 10 Second Discharge Per NFPA 2001
• UL, ULC and FM approved at Market Launch
3M™ Novec 1230™ Fire Protection Fluid - Kidde Offering
• Class A Design Concentration - 4.2%
• Class B Design Concentration - 5.6%
• Nozzles - Both 360 and 180 deg Options
• Minimum Nozzle Pressure - 91 psig (6 bar)
• Area Coverage - 10.9m x 10.9m (35.6 ft. x 35.6 ft)
• Area height coverage - 4.87 m (16 ft.)
3M™ Novec 1230™ Fire Protection Fluid - Kidde Offering
• Status - To Date– Fire testing is complete– Hardware testing is complete– Software Development/Limit testing
and Agency Witnessed Testing
complete
• What's Left?– Agency review of documentation
3M™ Novec 1230™ Fire Protection Fluid - Kidde Offering
• Targeted Market Launch - Q4 2004
• 3M Asia Marketing Launch October 6
• Kidde technical certification school October 7