ConventionalFire DetectionControl EquipmentPages 48-61

Page 2: Kentec Convetnional Control Panels Catalogue

EN54-4Conventional Sounder Controller UnitsPage 55

Sigma SounderSigma CP Conventional Sounder Controller UnitsPage 54

Sigma CPEN54 Range Conventional Fire Alarm C/P’sPage 48-49

Sigma CP-AAlarmsense Compatible Conventional Fire Alarm C/P’sPage 50-51

Sigma CP-RConventional Fire Alarm C/P RepeatersPage 52-53

K3000 SeriesConventional Fire Alarm C/P’sPage 56-57

K3200 SeriesConventional Fire Alarm C/P RepeatersPage 58

Sigma MatrixConventional Fire AlarmMimic SystemPage 60-61

LCMULine Continuity Monitoring UnitPage 59

ConventionalFire DetectionControl EquipmentPages 48-61

NEW!

Page 3: Kentec Convetnional Control Panels Catalogue

Page 48

Conventional Fire Alarm Control Panels

Features

Product OverviewThe Sigma CP range consists of a series of conventional fire alarm control panels designed in accordance with European standards BS EN54-2 and BS EN54-4 Fire Detection and Fire Alarm systems - Control and Indicating Equipment.

The range consists of 2, 4 and 8 zone control panels. All control panels are available in two versions:

Sigma K11 range in which detectors and call points are wired on separate circuits to sounders (two sounder circuits are provided).

Sigma T11 range in which detectors, call points and sounders are wired to the same pair of cables. Commonly referred to as a two-wire system.

Wiring sounders to the detection circuits eliminates the need to install sounder circuit cables and also offers the ability to provide zoned or two stage sounder operation. (T series only)

All control panels have an integral, mains powered battery charger and power supply designed in accordance with the requirements of BS EN54-4.

Fully certified to BS EN54-2 and BS EN54-4

2-wire and standard versions in 2, 4 or 8 zones

Compatible for use on BS5839: Part 1: 2002 installations

2-wire repeaters and ancillary boards

Fully programmable using simple menu options

Adjustable sounder delay time

Sounder configuration options

Zonal sounder delay detectors only

Zonal sounder delay call points only

Coincidence input selection I.S Barrier selection by zone

Short circuit fire by zone

Non latching zones

Silent zones

Zone input delay

General panel configuration

Simple, single board construction

Installer friendly

Compatible with wide range of detection devices

Two monitored sounder outputs

3 Amp power supply

Auxiliary power output

Model No. K11080M2

CPSigma

BS-EN54-2BS-EN54-4KM 73505

Note: For 2-wire T series panels, compatible detectors and call points must be used. All sounders must be polarised.

Note: Also available is the Sigma Ancillary Board (K580) which is compatible with all Sigma CP and CP-R panels which have operating software version V2.0 or above. See DS39 (pages 52-53) for more details.

Note: Also available is the Sigma Sounder Board (K461) which is compatible with all Sigma CP and CP-R panels which have operating software version V3.0 or above. See DS48 (page 54) for more details.

Part No. K580 Part No. K461

Page 4: Kentec Convetnional Control Panels Catalogue

Specification

The manufacturer reserves the right to amend specifications without prior notice Page 49

ConstructionIP RatingFinishColour - lid & boxColour - controls plate & labelsSupply voltageMains supply fusePower supply DC ratingMaximum battery sizeFault contact ratingLocal fire contact ratingFire contact ratingSounder output ratingDetection zone currentDetection zone EOL resistorActive EOLSounder output EOL resistorCable capacityOperating temperatureOperating humidity

1.2mm mild sheet steelIP30Epoxy powder coatedBS 00 A 05 grey - fine textureRAL 7047 light grey - satin230V AC (+10%/-15%)1.6 Amp 250V 24V 3 Amps7Ah 12V (2 per panel)30V DC 1 Amp30V DC 1 Amp30V DC 1 Amp0.5A per output (max 1.6A over all outputs)1.6 milliamps6k8 5%K14606K (optional)10k 5%2.5mm² per terminal-5°C to +50°C<95% (non condensing)

--------------------

PanelsProduct Code

K11020M2K11040M2K11080M2T11020M2T11040M2T11080M2K18002

Description

2 zone control panel4 zone control panel8 zone control panel2 zone, 2 wire panel4 zone, 2 wire panel8 zone, 2 wire panelTamper resistantVision Window *

Standby Current

0.065 Amps0.075 Amps0.093 Amps0.065 Amps0.075 Amps0.093 Amps

N/A

* Vision Window can be easily retrofitted to any Sigma CP panel

Alarm Current

0.1 Amps0.21 Amps0.55 Amps0.15 Amps0.3 Amps

0.63 AmpsN/A

Technical

DS37.09.2012

8

7

6

5

4

3

2

1

Model: K11080M 2

BS EN54-2 : 199 8BS EN54-4 : 199 8

Fire Alarm Contro l

KM 73505

Zone Chart General System Status

Disablemen tSounder Fault/

8765

4321

System Mode

(+1)(+10 )

Zone Fault/Test/Disablement

Zone Fault/Test/Disablement

Ente rSelec tModeRese t

Enable Contro l

Fire

Fire In Zone

Fire In Zone

Test Mode On

Delay On

Power On

Warning SilencedAlarm/Faul t

Power Fault

DisablementGenera l

System Fault

General Faul t

Tes tLamp

Alar mSilence/Sound Alarm/Fault

Warning Silenc e

310

38590

Size

385 x 310 x 90385 x 310 x 90385 x 310 x 90385 x 310 x 90385 x 310 x 90385 x 310 x 90385 x 310 x 90

Page 5: Kentec Convetnional Control Panels Catalogue

Page 50

CP-ASigma

AlarmSense compatible two–wire conventional fire alarm control and indicating panels

Features

Product OverviewThe new Sigma CP-A AlarmSense® range consists of a series of conventional, 2, 4 and 8 zone fire alarm control panels designed and approved in accordance with European standards BS EN54-2 and BS EN54-4 Fire Detection and Fire Alarm systems - Control and Indicating Equipment. The AlarmSense® system enables all devices in a given zone to be wired to the same pair of cables thus greatly reducing the cabling and installation requirements and hence costs. The AlarmSense® range of devices includes smoke and heat detectors, call points, base sounders, base sounder/beacons and relay units – all wired to the same pair of cables. Having sounders and sounder beacons installed on the same cabling as detectors and call points allows all systems to be configured for common, zonal or two stage alarm by simply setting one of the panels configuration options. Selection of the AlarmSense® local alarm feature at sounder or sounder beacon bases invokes the alarm verification feature. This is particularly useful in Houses of Multiple Occupation such as student accommodation or nursing homes. When sounder or sounder beacon bases are selected for local alarm mode, any alarm sounders are restricted such that only the sounder connected to the activated detector will operate initially. The panel will attempt to reset the activated detector after a time delay and if successful no further alarms are sounded. If the detector re-activates after being reset, a general alarm will sound throughout the premises.Activation of a second detector or a call point will sound the general alarm immediately All control panels have an integral, mains powered battery charger and power supply designed and approved in accordance with the requirements of BS EN54-4.

Fully compliant with BS EN54-2 and BS EN54-4 Allows systems to be installed in accordance with BS5838: Part 6 2 wire systems, reduces installation cabling 2-wire repeaters and ancillary boards via serial bus Fully programmable using simple menu options Adjustable sounder delay time Sounder configuration options Zonal sounder delay for detectors only Zonal sounder delay for call points only Coincidence output via ancillary board Short circuit fire selectable by zone Non latching selection by zone Silent zones (common sounder outputs) Zone input delay for sprinkler system connection AlarmSense® local alarm feature supported Simple, single board construction Installer friendly Compatible with all AlarmSense® devices Two conventional monitored sounder outputs 3 Amp power supply Auxiliary power output

Ancillary PCB Part No. K580 Model No. A11080M2Sounder PCB Part No. K461

NEW!

Page 6: Kentec Convetnional Control Panels Catalogue

Specification

The manufacturer reserves the right to amend specifications without prior notice Page 51

DS65.03.2012

ConstructionIP RatingFinishColour - lid & boxColour - controls plate & labelsSupply voltageMains supply fusePower supply DC ratingMaximum battery sizeFault contact ratingLocal fire contact ratingFire contact ratingCommon Sounder output ratingAlarmSense Sounder output ratingDetection zone currentDetection zone EOL resistorSounder output EOL resistorCable capacityOperating temperatureOperating humidity

--------------------

Technical1.2mm mild sheet steelIP30Epoxy powder coatedBS 00 A 05 grey - fine textureRAL 7047 light grey - satin230V AC (+10%/-15%)1.6 Amp 250V 24V 3 Amps7Ah 12V (2 per panel)30V DC 1 Amp30V DC 1 Amp30V DC 1 Amp0.5A per output 0.2A per output1.6 milliamps3K3 5%10k 5%2.5mm² per terminal-5°C to +50°C<95% (non condensing)

PanelsProduct Code

KA11020M2KA11040M2KA11080M2

Description

2 zone control panel4 zone control panel8 zone control panel

Standby Current

0.065 Amps0.075 Amps0.093 Amps

Alarm Current

0.1 Amps0.21 Amps0.55 Amps

OptionsProduct Code

K580K461M2FCLGTK02000M2K02750M2K18002

Description

Stand alone ancillary boardSounder PCBBezel for semi flushing panel to wallBoxed ancillary boardBoxed ancillary board with 0.75A PSUTamper resistant Vision Window *

* Vision Window can be easily retrofitted to any Sigma CP-A panel

8

7

6

5

4

3

2

1

Model: KA11080M2

Fire Alarm Control

Zone Chart General System Status

Disablemen tSounder Fault/

8765

4321

System Mode

(+1)(+10 )

Zone Fault/Test/Disablement

Zone Fault/Test/Disablement

Ente rSelec tModeRese t

Enable Contro l

Fire

Fire In Zone

Fire In Zone

Test Mode On

Delay On

Power On

Warning SilencedAlarm/Faul t

Power Fault

DisablementGenera l

System Fault

General Faul t

Tes tLamp

Alar mSilence/Sound Alarm/Fault

Warning Silenc e

310

38590

Size (mm)

385 x 310x 90385 x 310 x 90385 x 310 x 90

Page 7: Kentec Convetnional Control Panels Catalogue

Page 52

Conventional Fire Alarm Control Panel Repeaters

Sigma CP-R Features

Ancillary PCB Product OverviewThe Sigma Ancillary Board is compatible with all Sigma CP and CP-R panels which have operating software version V2.0 or above.

The board provides common fire, common fault, coincidence and zonal fire, volt free contacts allowing control of sub-systems, graphical mimics and plant, remotely from the main panel over a two wire data bus.

Mains powered Ancillary boards require only a two core data cable from the main control panel. 24V DC versions require an additional two cores for power either from the main panel or from another 24V DC source.

A mixture of Ancillary boards, Sounder boards or Repeaters up to a maximum of 7 of each type can be connected to a control panel and each is allocated an address from 1 to 7 using a binary coded DIL switch. The total length of the data cable from the main panel to the last repeater must not exceed 1200 metres.

Two wire serial connection

Up to 7 panels per system

230V AC or 24V DC powered versions

Full control over main panel

Volt free fire and fault contact outputs

Model No. E01080M2

Sigma CP-R Product OverviewThe Sigma CP-R Repeater is compatible with all Sigma CP control panels which have operating software version V2.0 or above.

Repeaters are available with 2, 4 or 8 zones and in mains powered (K versions) or 24V powered (E versions).

Mains powered repeaters require only a two core data cable from the main control panel. 24V DC versions require an additional two cores for power either from the main panel or from another 24V DC source.

A mixture of Repeaters, Ancillary boards or Sounder Boards up to a maximum of 7 of each type can be connected to a control panel and each is allocated an address from 1 to 7 using a binary coded DIL switch. The total length of the data cable from the main panel to the last repeater must not exceed 1200 metres.

Ancillary PCB FeaturesTwo wire serial connection

Up to 7 boards per system

230V AC or 24V DC powered versions

Open collector zonal fault outputs

Volt free fire, coincidence and common fault contact outputs

Part No. K580

CP-R& Ancillary PCB

Sigma

Note: Also available is the Sigma Sounder Board (K461) which is compatible with all Sigma CP and CP-R panels which have operating software version V3.0 or above. See DS48 (page 54) for more details.

Page 8: Kentec Convetnional Control Panels Catalogue

Specification

The manufacturer reserves the right to amend specifications without prior notice Page 53

Equipment

ConstructionIP RatingFinishColour - lid & boxColour - Controls plate & labelsSupply voltage (K models)Supply voltage (E models)Mains supply fusePower supply DC ratingMaximum battery sizeFault contact ratingFire contact ratingCable capacityOperating temperatureOperating humidity

1.2mm mild sheet steelIP30Epoxy powder coatedBS 00 A 05 grey - fine textureRAL 7047 light grey - satin

230V AC (+10%/-15%)20-30V DC 1.6A 250V24V 1 Amps7Ah 12V (2 per panel)30V DC 1 Amp30V DC 1 Amp2.5mm² per terminal-5°C to +50°C<95% (non condensing)

-----

----------

Sigma CP-RTechnical

Product Code

E01020L2E01040L2E01080L2K01020M2K01040M2K01080M2

K580K02000M2K02750M2K18002

Description

2 zone Sigma CP-R repeater panel4 zone Sigma CP-R repeater panel8 zone Sigma CP-R repeater panel2 zone Sigma CP-R repeater panel with PSU4 zone Sigma CP-R repeater panel with PSU8 zone Sigma CP-R repeater panel with PSU

Stand alone ancillary boardBoxed ancillary boardBoxed ancillary board with 0.75A PSUTamper resistant Vision Window *

Standby Current

0.075 Amps0.075 Amps0.075 Amps0.075 Amps0.075 Amps0.075 Amps

0.020 Amps0.020 Amps0.020 Amps

N/A* Vision Window can be easily retrofitted to any Sigma CP-R panel

Alarm Current

0.094 Amps0.098 Amps0.11 Amps

0.094 Amps0.098 Amps0.11 Amps

0.2 Amps0.2 Amps0.2 Amps

N/A

Supply Voltage

24V DC24V DC24V DC

230V AC230V AC230V AC

24V DC24V DC

230V ACN/A

Construction (boxed)IP Rating (boxed)FinishColour - lid & boxColour - controls plate & labelsSupply voltage (K02750M2)Supply voltage (K02000M2)Mains supply fusePower supply DC ratingMaximum battery sizeStandby currentFull alarm currentFault contact ratingFire contact ratingCoincidence contact ratingZonal contact ratingCable capacityOperating temperatureOperating humidity

1.2mm mild steelIP30Epoxy powder coatedBS 00 A 05 grey - fine textureRAL 7047 light grey - satin230V AC (+10%/-15%)20-30V DC 1.6A 250V24V 750mA2.6Ah 12V (2 per panel)20mA190mA30V DC 1 Amp30V DC 1 Amp30V DC 1 Amp30V DC 1 Amp2.5mm² per terminal-5°C to +50°C<95% (non condensing)

-------------------

Ancillary PCBTechnical

Processor Reset Switch

Data ConnectionZonal Volt Free ContactsPower Connection

Address Switch

ADDRESSPROCESSOR

RESETFUSEFAILOK COMMS

24VDC

-+-+ -+RS485OUT

RS485IN

NO NCC NO NCC NO NCCCOINCRELAY

FAULTRELAY

FIRERELAY

Z8FIRE

Z7FIRE

Z6FIRE

Z5FIRE

Z4FIRE

Z3FIRE

Z2FIRE

Z1FIRE

K580 Sigma CP Ancillary PCB

DS39.06.2012

Size (mm)

385 x 310 x 60385 x 310 x 60385 x 310 x 60385 x 310 x 90385 x 310 x 90385 x 310 x 90 155 x 136 385 x 310 x 90385 x 310 x 90

Page 9: Kentec Convetnional Control Panels Catalogue

Page 54

Sigma CP Conventional Sounder Controller Units

Features

Product OverviewThe Sigma CP Sounder Board is compatible with all Sigma CP control panels which have operating software version V3.0 or above.

The board provides 8 additional sounder outputs which can be configured as zoned, 2-stage or common alarm.

All sounder outputs are open and short circuit monitored and any faults on the sounder outputs will be announced at the main fire alarm panel as a sounder fault.

A class change input is provided which, when activated by a volt free contact closing, will switch all sounder outputs on.

Mains powered units require only a two core data cable from the main control panel. 24V DC versions require an additional two cores from another 24V DC source which is suitably rated to supply the total sounder current. 230V versions have their own power supply which is rated to supply sounder loads up to 5.25 Amps.

Up to 7 Sounder boards can be connected to a control panel and each is allocated an address from 1 to 7 using a binary coded DIL switch. Sounder boards may be connected to the Sigma CP serial bus in addition to Sigma CP ancillary boards and Sigma CP-R repeater panels.

The total length of the data cable from the main panel to the last repeater must not exceed 1200 metres. Once Sounder boards have been recognised by the main panel, a fault will be announced at the main panel if any become disconnected.

Two wire serial connection

Up to 7 sounder boards per system

230V AC or 24V DC powered versions

Zoned, 2-stage or common alarm

All outputs monitored for open and short circuit faults

Individual open and short circuit fault indicators

Fully monitored by main control panel

Class change input facility

Up to 8 outputs with 1A available from each

Can be connected to serial bus with Ancillary boards and repeaters

Boxed units in enclosure to match Sigma CP control panels

Power fault input for monitoring remote power supplies

Construction (Boxed)IP Rating (Boxed)FinishColour - lid & boxSupply Voltage (K04400M2)Supply Voltage (K04000M2)Mains supply fusePower supply DC ratingSounder output ratingClass change inputCable capacityOperating temperatureOperating humidity

1.2mm mild steelIP30Epoxy powder coatedBS 00 A 05 grey - fine texture230V AC (+10%/-15%)

20-30V DC

1.6A 250V24V 5.25 Amp1A per outputVolt free NOC2.5mm² per terminal-5°C to +50°C<95% (non condensing)

-----

-

-------

Technical

PanelsProduct Code

K461

K04000M2K04400M2

Description

Stand alone sounder PCBBoxed sounder PCBBoxed sounder PCB with 5.25 Amp PSU

PSU

24V DC

24V DC230V DC

Model No. K04400M2

SounderSigma

Size (mm)

155 x 136

385 x 310 x 90385 x 310 x 90

Page 10: Kentec Convetnional Control Panels Catalogue

The manufacturer reserves the right to amend specifications without prior notice Page 55

Conventional SounderController Units

Features

Product OverviewConventional Sounder controllers enable additional, distrib-uted power and control for sounder circuits in situations where there are insufficient circuits at the fire alarm control panel or where additional power is required to power heavily loaded sounder circuits.

The Sounder Controller Unit connects to conventional sounder circuits and any faults on its outputs are transmitted to the fire control panel via the incoming, triggering sounder circuit thus maintaining full fault monitoring.

All units contain a mains powered battery charger/power supply. There is space for up to 7 Ah batteries.

Indicators are provided for power healthy, power fault and sounder fault conditions and power fault conditions are signalled to the fire alarm control panel as a sounder fault.

Two four or six way units available

Integral power supply

Robust steel enclosure

Space for 7Ah batteries

Power Healthy, Power Fault and Sounder Fault indicators

Full fault monitoring and integrity maintained

DS48.06.2012

ConstructionIP RatingFinishColour - lid & boxSupply voltageMains fuseBattery charge fusePower outputBatteryOperating temperatureOperating humidity

1.2mm mild sheet steelIP30Epoxy powder coatedBS 00 A 05 grey - fine texture230V AC (+10%/-15%)3A, 1¼ inch20mm x 5mm, 500 milliamp24V at 2.5A7Ah-5°C to +50°CTo 95% (non condensing)

-----------

Technical

PanelsProduct Code

K1740203

K1740403

K1740603

Description

2 Way Sounder Controller Unit4 Way Sounder Controller Unit6 Way Sounder Controller Unit

PSU

5.25A

5.25A

5.25A

Model No. K1725203

SounderController

Size (mm)

500 x 355 x 108

500 x 355 x 108

500 x 355 x 108

Page 11: Kentec Convetnional Control Panels Catalogue

Page 56

Conventional Fire Alarm Control Panels

Features

Product OverviewThe K3000 Series exceeds the requirements of BS5839: Part 4: 1988 in several areas. Inclusion of zone isolate, zonal one man test, zonal contacts, shop unit interface and zoned or two stage alarm outputs are all standard features.

A wide range of detectors are supported by the equipment, ensuring that the K3000 Series control panels can be used with existing installations without the need to change the field devices. Front panel controls and indicators are kept to a minimum to simplify user operation and to maintain clarity of indication. High intensity, twin bar LED indicators are used on all front panels. All panels are supplied with suitable power supply and generous battery space to give extended battery standby if required.

Ample cable entries and removable chassis assist in ease of installation. All panels are available as true flush or surface mounting and in two tone grey or cream and brown.

Other colours are available to special order. Arrangements can be made for special badging or special finishes such as brass or stainless steel.

K3000 Series control panels allow continued operation of call points and detectors upon removal of a device from the detec-tion line. This can be achieved either by fitting an active end of line device or by using special line clamping bases.

Complies with BS5839: Part 4: 1988

Can be used on pre BS5839 type systems

12 - 48 zones as standard more available on request

Class change input

Common fire and fault contacts

Line continuity upon detector removal

Remote signal contact and isolate

Shop interface input

Zonal one man test

Zonal selection for operation with intrinsically safe barriers

Zonal volt free contacts

Zone isolate facility

Compatible with most popular detectors

Option for plug-in two stage sounder cards

Model No. K3024005

3000Series

Page 12: Kentec Convetnional Control Panels Catalogue

Specification

The manufacturer reserves the right to amend specifications without prior notice Page 57

Panels

ConstructionIP RatingFinishStandard colourSounder outputs Isolatable fire contactAuxiliary alarm contactFault contactZonal contactsAuxiliary DC outputDetection zone monitoring resistorSounder circuit monitoring resistorRemote control inputs Mains supply Call pointsAlarm thresholdShort circuit thresholdMaximum zone quiescent currentActive end of lineOperating temperatureOperating humidity

1.2mm mild sheet steelIP30Epoxy powder coatedBS 00 A 05 grey - fine texture2 outputs each fused at 1 amp each (0.5A E3002001)Volt free changeover 1A at 30V DCVolt free changeover 1A at 30V DCVolt free changeover 1A at 30V DCVolt free normally open 1A at 30V DCFused at 500mA6k8

10k

Alarm input, Silence input, Reset input(option for pulsed alarm input [Security Alert])230V AC (+10%/-15%) (other voltages upon request)Require 470 OHM series resistor100 to 900 Ohms0 to 100 Ohms1.6mA

K1406K (optional)-5°C to +40°CTo 95% (non condensing)

-----------

-

-

-

----

---

Technical

Product Code

E3012003K3016005E3016005K3024005E3024005K3032007E3032007K3040007K3048009

Zones

121616242432324048

Standby Current

0.2A0.22A0.22A0.31A0.31A0.38A0.38A0.45A0.52A

Flush mounting versions are available to order. All weights quoted are less standby batteries

Alarm Current

0.34A0.38A0.38A0.45A0.45A0.52A0.52A0.59A0.66A

Sounder Load per

Circuit

1.0A1.0A1.0A1.0A1.0A1.0A1.0A1.0A1.0A

Sounder Load total

1.5A1.5A1.0A1.5A1.0A1.5A1.0A1.5A1.5A

Minimum Battery(24h standby)

7.0Ah7.0Ah7.0Ah

12.0Ah12.0Ah12.0Ah12.0Ah15.0Ah17.0Ah

PSU

2.5A4.0A2.5A4.0A2.5A4.0A2.5A4.0A4.0A

Weight (approx)

8.6kg11.0kg11.0kg11.5kg11.5kg20.0kg20.0kg20.5kg24.0kg

Size (mm)

500 x 355 x 108570 x 420 x 110570 x 420 x 110570 x 420 x 110570 x 420 x 110600 x 700 x 140600 x 700 x 140600 x 700 x 140700 x 1000 x 145

ControlPanel

Wall

Flush mount cross section

DS01.12.2012

Page 13: Kentec Convetnional Control Panels Catalogue

Page 58

Conventional Fire Alarm Control Panel Repeaters

Model No. K3212001

3200Series

EquipmentProduct Code

K3212001K3216001K3224001K3232003K3240005K3248005

Weight

3.5kg6.0kg6.0kg8.0kg

10.5kg10.5kg

Size (mm)

365 x 290 x 88365 x 290 x 88365 x 290 x 88500 x 355 x 108570 x 420 x 110570 x 420 x 110

Flush mounting versions are available to order, see price guide

Zones

121624324048

ConstructionIP RatingFinishColourVoltagePower consumption Operating temperatureOperating humidity

1.2mm mild sheet steelIP30Epoxy powder coatedBS 00 A 05 grey - fine texture20V - 30V DC20mA per zone-5 to +50 deg. CTo 95% (non condensing)

--------

Technical

DS02.12.2012

Features

Product OverviewThe K3200 series repeater panel uses a similar layout to the main control panel and is fitted with the same high quality indicators. In their discrete enclosure, they are well suited to areas where space is limited and aesthetics are an important consideration.

As well as zonal fire indicators, system fault, system healthy and buzzer muted indicators are provided. Controls are kept to the practical minimum of lamp test and buzzer mute. Subsequent alarm or fault conditions whilst the buzzer is muted will resound the buzzer to alert personnel to changing conditions.

Repeat panels are available as true flush or surface mounting and in two tone grey or cream and brown as standard. Other colours are available to special order. Arrangements can be made for special badging or special finishes such as brass or stainless steel. Special repeater panels can be made to order.

Zonal fire indicators

Common fault and power on indicators

Lamp test push button

Internal buzzer with mute facility

Buzzer resound facility

Page 14: Kentec Convetnional Control Panels Catalogue

The manufacturer reserves the right to amend specifications without prior notice Page 59

DS20.10.2012

FinishColourNormal currentFault condition currentMax. zone cable resistancePanel capacitorOperating voltageTerminal connectionsMax. detectors supportedLead colours

Conformal powder coatingBlue5mA at 28V750uA 50V20 ohms 47uF 50V15V to 30VBootlace ferrules20 per zoneK1406K - pink/blackK1406C - orange/blackK1406N - red/black

----------

Technical

PanelsProduct Code

K14060

NF14060

KID14060

Description

Line Continuity Monitoring Unit 6k8Line Continuity Monitoring Unit 5k6 Line Continuity Monitoring Unit 3k9

47uF

Not required onK3000 series or

Sigma CP panels

470R

Z

Z

LCMU

DETECTOR

POINTSCALL

470R

DETECTOR

POINTSCALL

ON ZONELAST DEVICECONTROL

PANEL

LCMU

Size (m)

25 x 20 x 8

25 x 20 x 8

25 x 20 x 8

Line Continuity Monitoring UnitProduct Overview

To use this method of monitoring, the breaking connection of the detector base must be fitted with a diode. To ensure correct operation over a wide supply voltage range and with up to 20 detectors removed, a Schottky type BYV-1060 is recommended. These devices are, however, very sensitive to electrostatic discharge and extra care should be taken when handling or cable testing.

It is also necessary to fit a 47uF capacitor to the detection line terminals on some of the control panels (not K3000 series or Sigma CP). Extreme care should be taken when fitting the capacitor in the panel as they are polarity conscious. The LCMU itself is also polarity conscious and the polarity is indicated in the normal manner i.e. black wire is always negative. A wrongly connected LCMU will produce a short circuit fault condition.

Due to the use of surface mount technology components, the LCMU is probably the smallest device of its kind on the market. This enables the device to be fitted either within the last device on a zone or in the back box, eliminating the need for an additional wiring point.

FeaturesEasy to install

No additional wiring point

Low cost

Sub-miniature design

Environmentally sealed

Page 15: Kentec Convetnional Control Panels Catalogue

Page 60

Conventional Fire AlarmMimic System

Features

Product OverviewThe Sigma Matrix system uses flexible, fibre optic light guides to illuminate areas on a floor plan, laid over a high resolution grid. This unique system dispenses completely with wiring and ena-bles indicators to be moved, removed or added on site without the need for any wiring.

All indicators can be configured to operate via switched positive or negative inputs providing compatibility with a wide range of input/output boards. Sigma Matrix can be supplied with or without common LEDs and controls. Optional LEDs indicate Power on, Fire and Fault and optional controls are for Buzzer silence and Lamp test.

Housed in attractive, slimline enclosures to match Sigma fire alarm panels and with high quality, full colour or monochrome floor plans, Sigma Matrix provides a clear, geographical indication of fire alarm activation enabling speedy identification of the source of an alarm.

Up to 320 LED’s can be controlled

Full colour printing

Available in a range of standard enclosures to suit any application

Bespoke sized units can be made upon request

Choice of Red, Green or Yellow LED’s

Available with or without controls

Same look and feel as Sigma range

Sigma Matrix can easily be upgraded on site with minimal cost and effort

EN54-4 approved PSU (optional)

M3 size Sigma Matrix

View showing mimic mountedon inner door

View showing LED grid

View showing internal layout

MatrixSigma

PSU optional

Page 16: Kentec Convetnional Control Panels Catalogue

Specification

The manufacturer reserves the right to amend specifications without prior notice Page 61

ConstructionIP RatingFinishColour - lid & boxColour - controls plate & labelsMimicNumber of indicators (standard models)Mains supply* Mains supply fuse* Power supply rating* Maximum ripple current* Battery type* (Yuasa NP) Battery charge voltage* Battery charge current* Max. current draw from batteries* Supply voltage (24V versions)Terminal capacityCabinet locks Maximum distance from control panelOperating temperature

1.2mm mild steelIP30Epoxy powder coated BS 00 A 05 grey - fine textureRAL 7047 light grey - satin3mm Clear Anti-Glare AcrylicM2 size - up to 32, M3 and S3 size - up to 64,S4 size - up to 96230V AC +10% - 15% (100 Watts max.)T2A L250V Replace only with similar type5.25 Amps total including battery charge 28V +/ 2V200 millivoltsTwo 12 Volt sealed lead acid (7Ah maximum)27.6VDC nominal (temperature compensated)1.5A maximum3 Amps. With mains power source disconnected18 to 30V DC0.5mm2 to 2.5mm2 solid or stranded wireM2/M3 - standard 801 key, S3/S4 - standard KT3001 key1km with 1.5mm2 cable

-5°C to +50°C

-------

------------

-

Technical

Max. number ofLED’s = 64

Will house 1 x LEDdriver PCB and

1 x 32 LEDextension PCB’s

(Red, Green or Yellow)

Enclosure Size OptionsMax. number of

LED’s = 64

Will house 1 x 32 LEDdriver PCB and

1 x 32 LEDextension PCB’s

(Red, Green or Yellow)

Max. number ofLED’s = 96

Will house 1 x 32 LEDdriver PCB and

2 x 32 LEDextension PCB’s

(Red, Green or Yellow)

Max. number ofLED’s = 320

Will house 1 x 32 LEDdriver PCB and up to

9 x 32 LEDextension PCB’s

(Red, Green or Yellow)

Max. number ofLED’s = 32

Will house 1 x 32 LEDdriver PCB

(Red, Green or Yellow)

385mm x 310mm90mm Deep

500mm x 355mm117mm Deep

385mm x 520mm110mm Deep

500mm x 650mm137mm Deep

Colour/Finish & Sizeto suit your requirements

M2S3

M3

S4

Bespoke Size

303400

225

400303

515400

??

185

DS59.03.2012

* 230 V Versions only