Kenneth Moore
Architectural Engineering – Lighting/Electrical
September 8, 2014
University of Maryland – Baltimore
Health Sciences Facility III
Tech Report 1, Part 1 Lighting Proposal Memo
Circulation Space - Atrium Refer to A121E LEVEL ONE FLOOR PLAN EAST and A121W LEVEL ONE FLOOR PLAN WEST
Room 1001: Lobby/Gathering Space
The main atrium will be a suitable space to implement the psychological counterpart system of
Spaciousness versus Closure. Since the atrium is 7 stories in height, it will be an interesting
challenge to make such a large space seem a pleasing, ambient space. The seventh floor has a
series of coves, which will need to be adequately lit to be visible from the ground floor, while not
visible from an angle outside of the building .
Outdoor Space + Building Façade Refer to L101 LANDSCAPE PLAN, L201 PLANTING DETAILS & NOTES, L202 GREEN ROOF PLANTING PLAN, L203
GREEN ROOF PLANTING PLAN
I plan to use the majority of the outdoor space in my lighting design. There are multiple green
roofs that can be seen in the planting plans. The majority of the site lighting will have to be
integrated into the landscaping, some of which will need to showcase the façade of the building.
There is also a large overhang space under the dry lab tower. This will require recessed outdoor
lighting fixtures to be integrated into the first story ceiling.
Large Work Space Refer to A121E LEVEL ONE FLOOR PLAN EAST and A121W LEVEL ONE FLOOR PLAN WEST
Rooms 1140 and 1130: Nanomedicine PDoc/GS/TECH Workstation
The large work space on the first floor is predominantly a workstation space. I will conduct
lighting studies of the most appropriate design applicable to the desk height and intended layout.
This will most likely result in evenly spaced recessed troffers or equally spaced pendant fixtures.
Special Purpose Space – Large Conference Room Refer to A121E LEVEL ONE FLOOR PLAN EAST
Room 1010: Meeting Room
There are many conference rooms in this section of the building, however this one is located on
the first floor with the majority of the room consisting of curtain walls. This means that the
lighting design of the outdoor space must not interfere with the conference room lighting, and
vice versa. This will be an important study in reducing glare and maximizing daylighting
potential. The large conference room will be a suitable space for the three schematic design
concepts. I would like to integrate this room into the surrounding landscape of the outdoor space
which can be seen upon entering the space from the elevator lobby. My initial thoughts include
cove lighting in the conference room ceiling and around the north wall of the room.
UPUP
REF
.
UPUP
UPUP
1
H
G
B
C
E
F
A
1A301
1A305
2
B1
D
7643 54.5 5.5
E.5
21' - 0"
H.2
7A442
1A446
4A317
1A320
A207
1
2
3 4
1.5
4A405
3A401
CL103
1S01B
1S01
SH103
/MA TCHLINE SEE:
1A12 1E
2J6
2A6A
2A6A
2J6
2J6
2J6
0A6
0H6
0H6
1A6
0H6
1A6
1A6
2J6
2J6
2J6
2J6
5A207
6A207
3' - 11 5/8" 5' - 10 3/8" 5' - 3 5/8" 15' - 8 3/8" 5' - 3 5/8" 15' - 8 3/8" 5' - 3 5/8" 15' - 8 3/8" 5' - 3 5/8" 15' - 8 3/8" 5' - 3 5/8" 15' - 8 3/8"
2' - 0"
7' - 2
"5'
- 4 3/
8"22
' - 7 5
/8"5'
- 4 3/
8"15
' - 11
5/8"
5' - 4
3/8"
20' -
0 3/4"
6' - 2
7/8"
5' - 4
3/8"
20' -
0"
2A356
4A356
6A356
1A356
2A359
1A357
EL. 70' - 0"
CL104
2.5
31' -
6"
5A356
2A357
3A356
1A359
1101A1 1101A2 1101A3
1101A4 1101A5 1101A6
TW1 EW1
1A502
1A503
1175A
1101B4 1101B3
1101B2
1A336
1A337
10'-6" 2'-9" 5'-0" 2'-9" 21'-0" 2'-9" 5'-0" 2'-9" 10'-6" 21'-0" 2'-9" 5'-0" 2'-9"
3'-7" 6'-5 1/4" 14'-7 1/8" 25'-0" 17'-0 1/8" 10'-5 1/2" 10'-6 1/2" 10'-6" 10'-6"
10'-6" 10'-6" 10'-6" 10'-6" 10'-6" 10'-6" 10'-6" 10'-6" 10'-6" 10'-6"
9'-3"
10'-6
1/8"
10'-6
1/8"
9'-5 1
/2"2'-
5 7/8"
15'-3
1/2"
5'-11
5/8"
7'-11
5/8"
1'-3 3
/4"7'-
3 3/4"
2'-1 1
/4"
6'-4 1
/4"5'-
7 1/8"
4'-0 3
/4"21
'-10 1
/8"11
'-11 3
/8"10
'-0 1/
8"
21'-1
0 1/8"
2'-6 1
/8"8'-
6 3/8"
9'-1 1
/4"12
'-5"
1'-11
1/8"
18'-2
5/8"
11'-5
1/2"
11 1/
2"
3'-9 3/8" 7'-10 3/8" 8'-7 7/8" 3'-7 3/4" 6'-10 1/4" 10'-6"
Stair 11S01 Shaft
SH101IT Room
TW1Electrical Room
EW1
ShaftSH103
Vestibule1101B
Vestibule1101A
Lobby/GatheringSpace
1001
Lobby1001
Stair 41S04
BAS ClosetCL103
SCCL104
2J6
2J6
2J6
2J6
2A6A
2A6A
2A6AA
2J6
2A6A
1A6
2J6
2J6
1A6
2J6
0H2
0A3
0A30G2
0A3
0H2 0H2
0H2
3'-2 3/4" 7'-9 1/4" 9'-5 1/4"
2J6
0D3 0D
3
0D3
0D3
0D3
0D3
0D3
0D6
0D3
2J6
0D6
0D6
0D60D6
0D3
0G3
0D6
1A3B
0D3B
0D3B
0D3B
0D3B
0D3B
0D3B
0D3B
0D3B
0D3A
1A3A 1A3A
0H8
0D3
0D6
0D3
0D3
0H2
0H2
1A6
0H2
0D6 0D6
0H80H80H80H8
0G6
WLA1165
Office1181
Office1180
Office1177
Office1176
LER1160
Fire CommandCenter
1171
Lab Support1142
CorridorC112
Microscopy1141
Lab Support1131
Office1173
ShaftSH109
Clean Room1164
Lab Support1161
Lounge/StaffLunch Rm
1175
Lab Support1151
Lab Support1152
Lab Support1150
Lab Support1144
PhysiochemicalCharacterization
1145
NanomedicinePDoc/GS/Tech
Wkst1140
SAIR Suite1132
CTR1167
Autoclave1166
Clean Room1162
Clean Room1163
CTR1143
1151
1152
1176 1177 1178 1179
1145 1142
1132
1165
1141B
1175
1180 1181
1161
117411731172
1141A
1134A
11621162A
1163
2'-9" 5'-0" 2'-9"2'-9" 5'-0" 2'-9" 2'-9" 5'-0" 2'-9"
8A405
1S04A
1S04B
Office1172
Office1174
Office1178
Office1179
2J6
NanomedicinePDoc/GS/Tech
Wkst1130
1171A
1171B
3
3
3
3A343
1A729
5A343
1A343
A207A
1
FEC FEC FEC
FECFECFEC
FEC FEC
FEC
0D3
?
1S01A
1. WHERE INDICATED ON THESE PLANS,LABORATORY CASEWORK AND FURNITURE ARESHOWN FOR REFERENCE ONLY. SEE THE LABFURNISHING PLANS AND FURNITURE PLANS FORLAYOUTS, DIMENSIONS, DETAIL KEYS AND OTHERINFORMATION.
2. REFER TO SHEET A519 FOR DETAILS AT TYPICALINTERIOR COLUMNS NOT INCLUDED IN ENLARGEDPLAN DETAILS.
3. REFER TO SHEET A540 FOR DETAILS AT WALLBASES AND THRESHOLDS.
4. REFER TO ENLARGED FURNITURE PLANS A800LBATO A816 FOR LOCATIONS OF FLOOR BOXES.
5. REFER TO SHEETS A160LB THROUGH A171 FORFINISH PLANS THAT COORDINATE WITH FINISHSCHEDULE.
6. PROVIDE ELECTROMAGNETIC AND/OR LEADSHIELDING AS REQUIRED BY THE PROJECTSPECIFICATIONS.
7. REFER TO THE SPECIFICATIONS FOR FIREEXTINGUISHER REQUIREMENTS IN BACK OF HOUSEAREAS.
EAST/WEST FLOOR PLAN NOTES
ADMINISTRATION & FINANCE
FACILITIES MANAGMENTARCHITECTURE, ENGINEERING &CONSTRUCTION DIVISION220 ARCH STREET, OFFICE LEVEL 3BALTIMORE, MARYLAND 21201
PHONE NO. (410) 706-7740FAX NO. (410) 706-8547
UMB EMERGENCY PHONE NUMBERS
UMB POLICE (410)706-6882UMB WORK CONTROL (410)706-7570
KEY PLAN
A/E CONSULTANTS
PROFESSIONAL CERTIFICATION. I HERE BY CERTIFY THAT THESEDOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THATI AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THELAWS OF THE STATE OF MARYLAND,
LICENSE No.
EXPIRATION DATE: .
,
REGISTRATION / STAMP
PROJECT TITLE:
SHEET TITLE:
SHEET NO.
DATE:
CAD FILE NO.:
A/E PROJECT NO.:UMB PROJECT NO.:
UMB BUILDING NO.:
HOKArchitect3223 Grace Street, NWWashington, DC 20007
Design CollectiveAssociate Architect601 East Pratt Street, Suite 300Baltimore, MD 21202
AEI EngineersME Engineers401 N. Washington St, Suite 400Rockville, MD 20850
WFT EngineersPlumbing/FA/FP Engineers9737 Washingtonian Blvd. Suite 588Gaithersburg, MD 20878
Cagley & AssociatesStructural Engineer6141 Executive Blvd,Rockville, MD 20852
Site ResourcesCivil Engineer / Landscape Architect14315 Jarrettsville Pike,Phoenix, MD 21131-0249
Jacobs ConsultancyLab Planning303 South Broadway, Suite G20Tarrytown, NY 10591
Melville Thomas Architects, IncInterior Architects600 Wyndhurst Ave. Suite 315Baltimore, MD 21210
EASTWEST
HSF III
11-38512.14006.00
HEALTHSCIENCESFACILITY III
DONOR NAME.:
A121W
LEVEL ONEFLOOR PLAN -WEST
07/25/2014
1/8" = 1'-0"1 FLOOR PLAN - LEVEL 01 WEST
Revisions
No. Date Item1 05/08/14 Addendum 42 6/13/14 Bulletin 93 7/25/14 Bulletin 10
B CA B CA B CA B CA
Main Index
Arch Index
Curb per 1/A365RFI 24 Item 13j
GO TO ARCH GO TO HVAC GO TO HVAC PIPING GO TO PLUMB GO TO ELEC FP SUBMITTALS
UPUP
UP
UP
UPUP
DN
H
G
B
C
E
F
A
7.5
1A305
B1
2A202
1A306
D
76 12111098 11.5
1A302
1A303
EE
E.5
105
104
103
101
102
AA
BB
CC
DD
2' - 8 5/8"
17' - 7 1/4"
17' - 3"
16' - 11 1/2"
11' - 5 3/4"
2' - 8 5/8"
9' - 3"
10' - 11"
12' - 6 1/8"
1A202
3A202
H.2
1A431
10A431
7A431
1A446
A440
2
A440
6
A440
3
2A443
A444 3
A447 11A44712
1A550
7A447
1A447
1A310
1A311
1A313
1A315
1A316
3A316
1A318
2A328
3A328
4A328
5A328
1A331
2A333
2A208
1A410
1A408
3A405
3A403
12A405
103.1
104.8
BB.1
COMPACTOR
DOCK LIFTC104
1115
1154
1S03
EE1
1164
TE1
1105
1104
1154A
1S02A
C103
1S03A
CL103
SH103
/MATCHLINE SEE:
1A121W
2J6
2J6
1A6AP
1M8
1A6
0M8U
0M8
0M8U
1M8R
0M8R
2M8R
2M6
0M6
1M8
1M6
2M6
1A208
WHEELCHAIRLIFT
15' - 8 3/8" 16' - 6" 30' - 1" 15' - 4" 16' - 0 3/8" 9' - 11 5/8" 22' - 0 3/8" 2' - 11 5/8" 2' - 0" 13' - 9"
21' - 0" 15' - 8 3/8" 2' - 8"1' - 8" 14' - 1" 44' - 10" 15' - 8 3/8" 5' - 3 5/8" 5' - 4 3/8" 4' - 3 5/8"
7' - 1 1/2"
17' - 2 3/8"
5' - 3
5/8"
21' -
0 3/8"
5' - 4
"0"
5' - 3
5/8"
16' -
0 3/8"
5' - 3
5/8"
19' -
4 3/8"
3' - 4
"5'
- 3 5/
8"7'
- 2 3/
4"
4A358
3A358
SLOPE 1/8" PER FT. SLOPE 1/8" PER FT.
SLO
PE
1/8"
PER
FT.
SLO
PE
1/8"
PER
FT.
SLOPE 1/8"PER FT.
SLOPE 1/8"PER FT.
SLO
PE
1/8"
PER
FT.
SLO
PE
1/8"
PER
FT.
SLO
PE
1/8"
PER
FT.
SLO
PE
1/8"
PER
FT.
SLOPE 1/8"PER FT.
SLOPE 1/8"PER FT.
SLO
PE
1/8"
PER
FT.
SLO
PE
1/8"
PER
FT.
SLOPE 1/8"PER FT. FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
4A357
2A358
6A357
5A357
EL. 70' - 0"
EL. 69' - 10"
EL. 69' - 10"
EL. 65' - 6"
EL. 65' - 6"
EL. 65' - 6"
EL. 65' - 6"
EL. 69' - 10"
EL. 70' - 0"
EL. 70' - 0"
EL. 70' - 0"
EL. 70' - 0"
BOLLARD, TYP.
8' - 6
"
7' - 5" 2' - 1"
1' - 6
"1'
- 6"
1' - 8 5/8"
1' - 0"
2' - 0"
61' - 5 7/8"
61' - 5 3/8"
61' - 6"
61' - 4 3/4"
61' - 3 3/4"
61' - 6"
61' - 3 3/4"
61' - 5 7/8"
PAPE
R / P
LAST
IC+G
LASS
/ CAR
DBOA
RD / C
OMPO
ST
1A352
2A352
1A730
2A357
3A357
1A358
5A358
6A358
1A359
1120
1A731
3A731
C102
1154B
1117
1S02
4A731
6A731
1M8U
R
1M8U
1M8U
0M8U
1M8U
3'-8 1/2"
3'-8 1
/8"
3'-6 7/8"
3'-6 7/8"
5A726
7'-5 5/8" 5'-1 5/8" 9'-0 1/8" 18'-1 5/8" 2'-11" 30'-10"
2'-9" 5'-0" 2'-9" 32'-5 1/2" 8'-7 1/4"
10'-6" 10'-6" 17'-11 1/2"
10'-6" 29'-3 1/4" 2'-2 3/4"
17'-0 1/8"
5'-10"
5'-7 5/8"
3'-7 1/2"
7'-3 3/4"
2'-5 3/8"
31'-7 7/8"
2'-1 1/4"7'-10 3/4"
2'-7 1/4"
11'-7
"8'-
7"10
"31
'-6"
13'-8
3/8"
3'-7 5
/8"17
'-4 3/
8"11
1/2"
20'-2
1/4"
9'-7 1
/4"
2'-6 1
/8"12
'-5"
1'-11
1/8"
18'-2
5/8"
11'-5
1/2"
11 1/
2"
6'-1 3
/4"1'-
2"3'-
3 5/8"
29'-7
3/8"
7'-2 7
/8"2'-
4"10
'-0 1/
8"9'-
5 5/8"
4'-4 1
/4"
9'-10
"
5'-5 1/4"
8'-10 3/4" 6'-7" 20'-4" 5'-5 3/8"
3'-2"
ShaftSH107
ShaftSH108
Loading/Staging/Recycling1111
Biohazard WasteStorage
1104
Animal Receiving1115
Water Pump1120
CorridorC104
CorridorC105
Stair 31S03
Lobby/GatheringSpace
1001
ElevatorPE107
ElevatorSE101
Elevator LobbyC106
IT RoomTE1
Electrical RoomEE1
JC1117
CorridorC103
BAS ClosetCL103
Cylinder Stor1106
Chemical WasteStorage
1105
Stair 51S05
2J6
2J6
2J6
2J6
2A6A
2A6A
2A6A
2A6A
2J6A
2J6
ElevatorPE103
ElevatorPE104
ElevatorPE105
ElevatorPE106
ElevatorSE102
2J6
2J6
2J6
2J6
0A6A
P
0A3AP
2J6
2J6
1M8
0M6
0A6
0A6AP
0A6AP
1A6
0A6
2A6A 0H2
0H2
1M6
0M6
2J6
2J6
0H2
0G3P
0H3
0H21M
8
0H3
2A6A
0A3
0H2
0H2
2J6A
2J6A0H
3
2M8
3'-11 1/4" 1'-9 3/8"
2A6A
0A6A
P
0A6AP
1A6A
1182
0M8U
0M8
0M8U
0M8
Stair 21S02
0A3
0G20A3
9'-5 1/4"
11' - 1 3/4"
7' - 7 1/4"
24' - 7 1/4"
10' - 8 1/8"
2J6
0H3
0H3
0G3P
2J6
TRUCK RESTRAINT
TRUCK BUMPERS
TRUCK RESTRAINT
TRUCK BUMPERS
1A732
2A6A
1M8U
1A6
0D60D6
1A6A
0D6
0D3B
0D3B
0D3A
0H8
0D3A
0D3
1A6
0A6A
0H2
0H2
10' -
8 3/4"
DIRTY BEDDINGDUMPSTER
DIRTY BEDDINGVACUUMSYSTEM
EQUIPMENT
6' - 0"
CYLINDER STOR.
CorridorC102
Vestibule1125
Office1181
Office1180
Meeting Rm1010
Bioinformatics1134
CorridorC110
CorridorC111
Microscopy1141
Lab Support1131
(Wet Lab) LargeConference Rm
1182
SAIR Suite1132
CTR1167
Storage1010A
ShaftSH110
MenLocker/Shower
1118
WomenLocker/Shower
1119
Men1101
Women1100
Restroom1102
Wellness Rm1103
Elevator Lobby1003
ShaftSH113
CorridorC109
CorridorC101
EMR1164
C110
1104
1179
1132
1180
1133
1181
C111
1010A1
1010A2
1134A
1134
1104A
1119A
1118A
1119
1118
1101
1100
1103 1102
1125
C101
1105A 1105C1105B
SS STANCHION
3
7' - 6
"31
' - 6"
31' -
6"11
' - 7"
9' - 5
"31
' - 6"
21' -
0"20
' - 3"
8' - 2
"11
' - 7"
2'-9" 5'-0" 2'-9" 28'-5 1/2" 4'-1 1/2"
1A6A
0H2
2J6
1154D1154C
NanomedicinePDoc/GS/Tech
Wkst1130
4'-5 5
/8"5'-
6 7/8"
1'-2" 2'-0"MANF.PER 2'-0"
24" WIDE EMBEDDEDSTEEL SKID PLATES
5
1A411
1A729
5A343
1A343
FEC
FEC
FEC
FEC
FEC
FEC
1M6 2M8U
1120A
23'-6 1/2" 3'-5 5/8" 6'-7"9'-1 3
/4"
CLR.8'-0"
1. WHERE INDICATED ON THESE PLANS,LABORATORY CASEWORK AND FURNITURE ARESHOWN FOR REFERENCE ONLY. SEE THE LABFURNISHING PLANS AND FURNITURE PLANS FORLAYOUTS, DIMENSIONS, DETAIL KEYS AND OTHERINFORMATION.
2. REFER TO SHEET A519 FOR DETAILS AT TYPICALINTERIOR COLUMNS NOT INCLUDED IN ENLARGEDPLAN DETAILS.
3. REFER TO SHEET A540 FOR DETAILS AT WALLBASES AND THRESHOLDS.
4. REFER TO ENLARGED FURNITURE PLANS A800LBATO A816 FOR LOCATIONS OF FLOOR BOXES.
5. REFER TO SHEETS A160LB THROUGH A171 FORFINISH PLANS THAT COORDINATE WITH FINISHSCHEDULE.
6. PROVIDE ELECTROMAGNETIC AND/OR LEADSHIELDING AS REQUIRED BY THE PROJECTSPECIFICATIONS.
7. REFER TO THE SPECIFICATIONS FOR FIREEXTINGUISHER REQUIREMENTS IN BACK OF HOUSEAREAS.
EAST/WEST FLOOR PLAN NOTES
ADMINISTRATION & FINANCE
FACILITIES MANAGMENTARCHITECTURE, ENGINEERING &CONSTRUCTION DIVISION220 ARCH STREET, OFFICE LEVEL 3BALTIMORE, MARYLAND 21201
PHONE NO. (410) 706-7740FAX NO. (410) 706-8547
UMB EMERGENCY PHONE NUMBERS
UMB POLICE (410)706-6882UMB WORK CONTROL (410)706-7570
KEY PLAN
A/E CONSULTANTS
PROFESSIONAL CERTIFICATION. I HERE BY CERTIFY THAT THESEDOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THATI AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THELAWS OF THE STATE OF MARYLAND,
LICENSE No.
EXPIRATION DATE: .
,
REGISTRATION / STAMP
PROJECT TITLE:
SHEET TITLE:
SHEET NO.
DATE:
CAD FILE NO.:
A/E PROJECT NO.:UMB PROJECT NO.:
UMB BUILDING NO.:
HOKArchitect3223 Grace Street, NWWashington, DC 20007
Design CollectiveAssociate Architect601 East Pratt Street, Suite 300Baltimore, MD 21202
AEI EngineersME Engineers401 N. Washington St, Suite 400Rockville, MD 20850
WFT EngineersPlumbing/FA/FP Engineers9737 Washingtonian Blvd. Suite 588Gaithersburg, MD 20878
Cagley & AssociatesStructural Engineer6141 Executive Blvd,Rockville, MD 20852
Site ResourcesCivil Engineer / Landscape Architect14315 Jarrettsville Pike,Phoenix, MD 21131-0249
Jacobs ConsultancyLab Planning303 South Broadway, Suite G20Tarrytown, NY 10591
Melville Thomas Architects, IncInterior Architects600 Wyndhurst Ave. Suite 315Baltimore, MD 21210
EASTWEST
HSF III
11-38512.14006.00
HEALTHSCIENCESFACILITY III
DONOR NAME.:
A121E
LEVEL ONEFLOOR PLAN -EAST
07/25/2014
1/8" = 1'-0"1 FLOOR PLAN - LEVEL 01 EAST
Revisions
No. Date Item1 04/18/14 Addendum 32 05/08/14 Addendum 43 6/13/14 Bulletin 94 6/13/14 Addendum 55 7/25/14 Bulletin 10
B CAB CAB CAB CA
Main Index
Arch Index
GO TO ARCH GO TO HVAC GO TO HVAC PIPING GO TO PLUMB GO TO ELEC FP SUBMITTALS
Bollards are 8" dia., expansionanchor, concrete filledBP5 Pre-Bid Structure RFI 2
CIP Stair- see 2/S306BP5 Pre-Bid Structure RFI 3
HOKArchitect3223 Grace Street, NWWashington, DC 20007
Design CollectiveAssociate Architect601 East Pratt Street, Suite 300Baltimore, MD 21202
AEI EngineersME Engineers401 N. Washington St, Suite 400Rockville, MD 20852
WFT EngineersPlumbing/FA/FP Engineers9737 Washingtonian Blvd. Suite 588Gaithersburg, MD 20878
Cagley & AssociatesStructural Engineer6141 Executive Blvd,Rockville, MD 20852
Site ResourcesCivil Engineer / Landscape Architect14315 Jarrettsville Pike,Phoenix, MD 21131-0249
Jacobs ConsultancyLab Planning303 South Broadway, Suite G20Tarrytown, NY 10591
Melville Thomas Architects, IncInterior Architects600 Wyndhurst Ave. Suite 315Baltimore, MD 21210
HEALTH
SCIENCES
FACILITY III
SHEET TITLE :
PROJECT TITLE :
REVISIONSITEMDATENO
REGISTRATION / STAMP
A/E CONSULTANTS
UMB PROJECT NO. :
DATE :
SRI PROJECT NO. :
UMB BUILDING NO. :
SHEET NO.
CAD FILE NO. :
ADMINISTRATION & FINANCE
220 ARCH STREET, OFFICE LEVEL 3
PHONE NO. (410) 706-7740
BALTIMORE, MARYLAND 21201
FAX NO. (410) 706-8547
FACILITIES MANAGEMENT
CONSTRUCTION DIVISIONARCHITECTURE, ENGINEERING &
KEY PLAN
UMB EMERGENCY PHONE NUMBERS
UMB POLICE (410) 706-6882UMB WORK CONTROL (410) 706-7570
DONOR NAME :
LANDSCAPE
PLAN
L101
Main Index
Land Index
HOKArchitect3223 Grace Street, NWWashington, DC 20007
Design CollectiveAssociate Architect601 East Pratt Street, Suite 300Baltimore, MD 21202
AEI EngineersME Engineers401 N. Washington St, Suite 400Rockville, MD 20852
WFT EngineersPlumbing/FA/FP Engineers9737 Washingtonian Blvd. Suite 588Gaithersburg, MD 20878
Cagley & AssociatesStructural Engineer6141 Executive Blvd,Rockville, MD 20852
Site ResourcesCivil Engineer / Landscape Architect14315 Jarrettsville Pike,Phoenix, MD 21131-0249
Jacobs ConsultancyLab Planning303 South Broadway, Suite G20Tarrytown, NY 10591
Melville Thomas Architects, IncInterior Architects600 Wyndhurst Ave. Suite 315Baltimore, MD 21210
HEALTH
SCIENCES
FACILITY III
SHEET TITLE :
PROJECT TITLE :
REVISIONSITEMDATENO
REGISTRATION / STAMP
A/E CONSULTANTS
UMB PROJECT NO. :
DATE :
SRI PROJECT NO. :
UMB BUILDING NO. :
SHEET NO.
CAD FILE NO. :
ADMINISTRATION & FINANCE
220 ARCH STREET, OFFICE LEVEL 3
PHONE NO. (410) 706-7740
BALTIMORE, MARYLAND 21201
FAX NO. (410) 706-8547
FACILITIES MANAGEMENT
CONSTRUCTION DIVISIONARCHITECTURE, ENGINEERING &
KEY PLAN
UMB EMERGENCY PHONE NUMBERS
UMB POLICE (410) 706-6882UMB WORK CONTROL (410) 706-7570
DONOR NAME :
PLANTING
DETAILS &
NOTES
L201
Main Index
Land Index
HOKArchitect3223 Grace Street, NWWashington, DC 20007
Design CollectiveAssociate Architect601 East Pratt Street, Suite 300Baltimore, MD 21202
AEI EngineersME Engineers401 N. Washington St, Suite 400Rockville, MD 20852
WFT EngineersPlumbing/FA/FP Engineers9737 Washingtonian Blvd. Suite 588Gaithersburg, MD 20878
Cagley & AssociatesStructural Engineer6141 Executive Blvd,Rockville, MD 20852
Site ResourcesCivil Engineer / Landscape Architect14315 Jarrettsville Pike,Phoenix, MD 21131-0249
Jacobs ConsultancyLab Planning303 South Broadway, Suite G20Tarrytown, NY 10591
Melville Thomas Architects, IncInterior Architects600 Wyndhurst Ave. Suite 315Baltimore, MD 21210
HEALTH
SCIENCES
FACILITY III
SHEET TITLE :
PROJECT TITLE :
REVISIONSITEMDATENO
REGISTRATION / STAMP
A/E CONSULTANTS
UMB PROJECT NO. :
DATE :
SRI PROJECT NO. :
UMB BUILDING NO. :
SHEET NO.
CAD FILE NO. :
ADMINISTRATION & FINANCE
220 ARCH STREET, OFFICE LEVEL 3
PHONE NO. (410) 706-7740
BALTIMORE, MARYLAND 21201
FAX NO. (410) 706-8547
FACILITIES MANAGEMENT
CONSTRUCTION DIVISIONARCHITECTURE, ENGINEERING &
KEY PLAN
UMB EMERGENCY PHONE NUMBERS
UMB POLICE (410) 706-6882UMB WORK CONTROL (410) 706-7570
DONOR NAME :
GREEN ROOF
PLANTING
PLAN
L202
Main Index
Land Index
HOKArchitect3223 Grace Street, NWWashington, DC 20007
Design CollectiveAssociate Architect601 East Pratt Street, Suite 300Baltimore, MD 21202
AEI EngineersME Engineers401 N. Washington St, Suite 400Rockville, MD 20852
WFT EngineersPlumbing/FA/FP Engineers9737 Washingtonian Blvd. Suite 588Gaithersburg, MD 20878
Cagley & AssociatesStructural Engineer6141 Executive Blvd,Rockville, MD 20852
Site ResourcesCivil Engineer / Landscape Architect14315 Jarrettsville Pike,Phoenix, MD 21131-0249
Jacobs ConsultancyLab Planning303 South Broadway, Suite G20Tarrytown, NY 10591
Melville Thomas Architects, IncInterior Architects600 Wyndhurst Ave. Suite 315Baltimore, MD 21210
HEALTH
SCIENCES
FACILITY III
SHEET TITLE :
PROJECT TITLE :
REVISIONSITEMDATENO
REGISTRATION / STAMP
A/E CONSULTANTS
UMB PROJECT NO. :
DATE :
SRI PROJECT NO. :
UMB BUILDING NO. :
SHEET NO.
CAD FILE NO. :
ADMINISTRATION & FINANCE
220 ARCH STREET, OFFICE LEVEL 3
PHONE NO. (410) 706-7740
BALTIMORE, MARYLAND 21201
FAX NO. (410) 706-8547
FACILITIES MANAGEMENT
CONSTRUCTION DIVISIONARCHITECTURE, ENGINEERING &
KEY PLAN
UMB EMERGENCY PHONE NUMBERS
UMB POLICE (410) 706-6882UMB WORK CONTROL (410) 706-7570
DONOR NAME :
GREEN ROOF
PLANTING
PLAN & NOTES
L203
Main Index
Land Index