K122-C2-DS-65-290_A.pdf

Embed Size (px)

Citation preview

  • 8/18/2019 K122-C2-DS-65-290_A.pdf

    1/5

    A 2013-08-23 C.C.N R.A.Z. C.Q.S

    C0 2013-08-13 C.C.N R.A.Z. C.Q.S

    B0 2013-07-05 C.C.N R.A.Z. C.Q.S

    A0 2012-11-17 V.B.C. R.A.Z. P.L.CH.

    Rev Date Prepared by Checked by Approved by

    Review

    A

    Technical person incharge:

    Issued for ReviewDescription

    OHV Power Lines and Substations for CVPUE

    Issued for Review

     ABENGOA PERU

    Document name:

    Data Sheet

    Guy Wires and Accessories

    Document N°:

    K122-C2-DS-65-290

    Issued for Review

    Issued for Review

  • 8/18/2019 K122-C2-DS-65-290_A.pdf

    2/5

    Rev: A

    Item Unit Required Offered

    A

    1 Guy wires

    1.1 Manufacturer - Report

    1.2 Breaking load kN (pounds) 120 (26,977)

    1.3 Nominal diameter mm (inch) 12.9 (0.509)

    1.4 Number and size of wires - 19 N0. 10

    1.5 Mass kg (pounds) Report

    2 Thimble clevis

    2.1 Manufacturer - Report

    2.2 Material Forged steel hot dip

    galvanised

    2.3 gr/m2 >= 600

    2.4 Breaking load kN (pounds) 120 (26,977)

    2.5 mm (inch) 20.64 (13/16")

    2.6 Mass kg (pounds) Report

    2.7 Dimensions mm Attach drawings

    3 Preformed dead-ends

    3.1 Manufacturer -

    3.2 Material Forged steel hot dip

    galvanised

    3.3 gr/m2 >= 600

    3.4 Minimum breaking load kN (pounds) 120 (26,977)

    3.5 Nominal diameter of guy wire mm (inch) 12.9 (0.509)

    3.6 Number of threads - Report

    3.7 Mass kg (pounds) Report

    3.8 Dimensions mm Attach drawings

    4 Anchor rod

    4.1 Manufacturer - Report

    4.2 Length mm (feet) 2438 (8')

    4.3 Diameter mm (inch) 25.4 (1")

    4.4 Mass kg (pounds) Report

    4.5 Minimum breaking load kN (pounds) 120 (26,977)

    4.6 Material  Forged steel hot dipgalvanised

    4.7 Dimensions mm Attach drawings4.8 Nut - Report

    5 Square washer 4" x 4"5.1 Manufacturer Report

    5.2 Material Forged steel hot dip

    galvanised

    5.3 Wide mm (inch) 102 (4")

    5.4 Thickness mm (inch) 9.5 (3/8")

    5.5 Central hole mm (inch.) 28.6 (1 1/8")

    5.6 Dimensions mm Attach drawings

    6 Connecting link6.1 Manufacturer

    6.2 Material Forged steel hot dip

    galvanised6.3 gr/m2 >= 6006.4 Wide mm (inch) 7.94 (5/16")

    6.5 Length mm (inch) 76.20 (3")

    6.6 Thickness mm (inch) 304 (12")

    6.7 Central hole mm (inch.) 26.9 (1 1/16")6.8 Dimensions mm Attach drawings

    6.9 Breaking load kN (pounds) 120 (26,977)

    7 Guy Protector steel6.1 Manufacturer - Report

    6.2 Material Forged steel hot dip

    galvanised

    6.3 Length mm (feet) 2438.4 (8')

    6.4 Mass kg (pounds) Report

    Notes:

    1.-2.-

    Page

    Document code:

    Description

    Data sheet

    Guy Wires and Accessories for Task 6 TransmissionLine 69kV from CV Substation to Congata

    Bolt diameter (To be coordinated with connectinglink)

    The term"report" in the column "required", indicates that the bidder must inform the resquested feature.

    The term "Attach drawings" in the column "required", indicates that the dimensions of the accessoriesare obtained from the structures drawings.

    For phase conductor

    Galvanization according to ASTM 153/153M

    K122-C2-DS-65-290 (1 de 4)

    Galvanization according to ASTM 153/153M

    Galvanization according to ASTM 153/153M

    K122-C2-DS-65-290_A

  • 8/18/2019 K122-C2-DS-65-290_A.pdf

    3/5

    Rev: A

    Page

    Document code:

    Data sheet

    Guy Wires and Accessories for Task 6 TransmissionLine 69kV from CV Substation to Congata

    B1 Guy wires

    1.1 Manufacturer - Report

    1.2 Breaking load kN (pounds) 90 (20,233)

    1.3 Nominal diameter mm (inch) 11.28 (0.444)

    1.4 Number of individual wires - 71.5 Mass kg (pounds) Report

    2 Thimble clevis2.1 Manufacturer - Report

    2.2 Material Forged steel hot dip

    galvanised

    2.3 gr/m2 >= 600

    2.4 Breaking load kN (pounds) 90 (20,233)

    2.5 mm (inch) 18 (11/16")

    2.6 Mass kg (pounds) Report2.7 Dimensions mm Attach drawings

    3 Preformed dead-ends3.1 Manufacturer -

    3.2 Material Forged steel hot dip

    galvanised3.3 gr/m2 >= 600

    3.4 Minimum breaking load kN (pounds) 90 (20,233)3.5 Nominal diameter of guy wire mm (inch) 11.28 (0.444)3.6 Number of threads - Report

    3.7 Mass kg (pounds) Report3,8 Dimensions mm Attach drawings

    4 Anchor rod

    4.1 Manufacturer - Report

    4.4 Length mm (feet) 2438 (8')

    4.5 Diameter mm (inch) 19 (3/4")

    4.6 Mass kg (pounds) Report4.7 Minimum breaking load kN (pounds) 90 (20,233)

    4.8 Material Forged steel hot dip

    galvanised

    4.9 Dimensions mm Attach drawings4.1 Nut - Report

    5 Square washer 4" x 4"5.1 Manufacturer Report

    5.2 Material Forged steel hot dip

    galvanised

    5.4 Wide mm (inch) 102 (4")

    5.5 Thickness mm (inch) 9.5 (3/8")

    5.6 Central hole mm (inch.) 21 (13/16")

    5.7 Dimensions mm Attach drawings

    6 Connecting link6.1 Manufacturer

    6.2 Material Forged steel hot dip

    galvanised

    6.3 gr/m2 >= 600

    6.4 Wide mm (inch) 6.35 (1/4")

    6.5 Length mm (inch) 76.20 (3")

    6.6 Thickness mm (inch) 241.3 (9 1/2")6.7 Central hole mm (inch.) 24 (15/16")

    6.8 Dimensions mm Attach drawings

    6.9 Breaking load kN (pounds) 90 (20,233)

    7 Guy Protector steel6.1 Manufacturer - Report

    6.2 Material Forged steel hot dip

    galvanised6.3 Length mm (feet) 2438.4 (8')

    6.4 Mass kg (pounds) Report

    Notes:1.-

    2.-

    are obtained from the structures drawings.

    Galvanization according to ASTM 153/153M

    The term "Attach drawings" in the column "required", indicates that the dimensions of the accessories

    Galvanization according to ASTM 153/153M

    Galvanization according to ASTM 153/153M

    The term"report" in the column "required", indicates that the bidder must inform the resquested feature.

    K122-C2-DS-65-290 (2 de 4)

    For OPGW optical fiber

    Bolt diameter (To be coordinated with connectinglink)

    K122-C2-DS-65-290_A

  • 8/18/2019 K122-C2-DS-65-290_A.pdf

    4/5

    Rev: A

    Item Unit Required Offered

    A

    1 Guy wires

    1.1 Manufacturer - Report

    1.2 Breaking load kN (pounds) 70 (15,737)1.3 Nominal diameter mm (inch) 8,71 (0.343)

    1.4 Number and size of wires - 7 N0. 7

    1.5 Mass kg (pounds) Report

    2 Thimble clevis

    2.1 Manufacturer - Report

    2.2 Material Forged steel hot dip

    galvanised

    2.3 gr/m2 >= 600

    2.4 Breaking load kN (pounds) 70 (15737)

    2.5 mm (inch) 18(11/16")

    2.6 Mass kg (pounds) Report

    2.7 Dimensions mm Attach drawings

    3 Preformed dead-ends

    3.1 Manufacturer -

    3.2 Material Forged steel hot dip

    galvanised

    3.3 gr/m2 >= 600

    3.4 Minimum breaking load kN (pounds) 70 (15,737)

    3.5 Nominal diameter of guy wire mm (inch) 8,71 (0.343)

    3.6 Number of threads - Report

    3.7 Mass kg (pounds) Report

    3.8 Dimensions mm Attach drawings

    4 Anchor rod

    4.1 Manufacturer - Report

    4.2 Length mm (feet) 2438 (8')

    4.3 Diameter mm (inch) 16 (5/8")

    4.4 Mass kg (pounds) Report4.5 Minimum breaking load kN (pounds) 70 (15,737)

    4.6 Material Forged steel hot dip

    galvanised

    4.7 Dimensions mm Attach drawings

    4.8 Nut Report

    5 Square washer 4" x 4"

    5.1 Manufacturer Report

    5.2 Material Forged steel hot dip

    galvanised

    5.3 Wide mm (inch) 102 (4")

    5.4 Thickness mm (inch) 9,5 (3/8")

    5.5 Central hole mm (inch.) 17.5 (11/16")

    5.6 Dimensions mm Attach drawings

    6 Connecting link

    6.1 Manufacturer

    6.2 Material Forged steel hot dip

    galvanised

    6.3 gr/m2 >= 6006.4 Wide mm (inch) 6.35 (1/4")

    6.5 Length mm (inch) 76.20 (3")

    6.6 Thickness mm (inch) 241.3 (9 1/2")

    6.7 Central hole mm (inch.) 24 (15/16")6.8 Dimensions mm Attach drawings

    6.9 Breaking load kN (pounds) 70 (15,737)

    7 Guy Protector steel6.1 Manufacturer - Report

    6.2 Material Forged steel hot dip

    galvanised

    6.3 Length mm (feet) 2438.4 (8')

    6.4 Mass kg (pounds) Report

    Notes:

    1.-

    2.-

    Technical Specifications

    Guy Wires and Accessories for Task 7.1 DistributionLine 34.5kV from M.H Substation to Primary Crushers

    Page

    Document code:

    K122-C2-DS-65-290 (3 de 4)

    Galvanization according to ASTM 153/153M

    Galvanization according to ASTM 153/153M

    Galvanization according to ASTM 153/153M

    The term"report" in the column "required", indicates that the bidder must inform the resquested feature.

    The term "Attach drawings" in the column "required", indicates that the dimensions of the accessoriesare obtained from the structures drawings.

    Bolt diameter (To be coordinated with connectinglink)

    Description

    For phase conductor

    K122-C2-DS-65-290_A

  • 8/18/2019 K122-C2-DS-65-290_A.pdf

    5/5

    Rev: A

    Technical Specifications

    Guy Wires and Accessories for Task 7.1 DistributionLine 34.5kV from M.H Substation to Primary Crushers

    Page

    Document code:

    B

    1 Guy wires1.1 Manufacturer - Report

    1.2 Breaking load kN (pounds) 90 (20,233)1.3 Nominal diameter mm (inch) 11.28 (0.444)

    1.4 Number of individual wires - 7

    1.5 Mass kg (pounds) Report

    2 Thimble clevis

    2.1 Manufacturer - Report

    2.2 Material Forged steel hot dip

    galvanised

    2.3 gr/m2 >= 600

    2.4 Breaking load kN (pounds) 90 (20,233)

    2.5 mm (inch) 18(11/16")

    2.6 Mass kg (pounds) Report

    2.7 Dimensions mm Attach drawings

    3 Preformed dead-ends3.1 Manufacturer -

    3.2 Materia l Forged steel hot dip

    galvanised

    3.3 gr/m2 >= 6003.4 Minimum breaking load kN (pounds) 90 (20,233)

    3.5 Nominal diameter of guy wire mm (inch) 11.28 (0.444)

    3.6 Number of threads - Report

    3.7 Mass kg (pounds) Report3,8 Dimensions mm Attach drawings

    4 Anchor rod4.1 Manufacturer - Report

    4.4 Length mm (feet) 2438 (8')

    4.5 Diameter mm (inch) 19 (3/4")

    4.6 Mass kg (pounds) Report4.7 Minimum breaking load kN (pounds) 90 (20,233)

    4.8 Material Forged steel hot dip

    galvanised

    4.9 Dimensions mm Attach drawings4.1 Nut Report

    5 Square washer 4" x 4"5.1 Manufacturer Report

    5.2 Material Forged steel hot dip

    galvanised

    5.4 Wide mm (inch) 102 (4")

    5.5 Thickness mm (inch) 9.5 (3/8")

    5.6 Central hole mm (inch.) 21 (13/16")

    5.7 Dimensions mm Attach drawings

    6 Connecting link6.1 Manufacturer

    6.2 Material Forged steel hot dip

    galvanised

    6.3 gr/m2 >= 600

    6.4 Wide mm (inch) 6.35 (1/4")6.5 Length mm (inch) 76.20 (3")

    6.6 Thickness mm (inch) 241.3 (9 1/2")

    6.7 Central hole mm (inch.) 24 (15/16")6.8 Dimensions mm Attach drawings

    6.9 Breaking load kN (pounds) 90 (20,233)

    7 Guy Protector steel6.1 Manufacturer - Report

    6.2 Material Forged steel hot dip

    galvanised

    6.3 Length mm (feet) 2438.4 (8')

    6.4 Mass kg (pounds) Report

    Notes:

    1.-

    2.-

    Galvanization according to ASTM 153/153M

    K122-C2-DS-65-290 (4 de 4)

    are obtained from the structures drawings.

    The term "Attach drawings" in the column "required", indicates that the dimensions of the accessories

    For OPGW optical fiber

    Galvanization according to ASTM 153/153M

    The term"report" in the column "required", indicates that the bidder must inform the resquested feature.

    Galvanization according to ASTM 153/153M

    Bolt diameter (To be coordinated with connectinglink)

    K122-C2-DS-65-290_A