Upload
fredyno-azapa
View
213
Download
0
Embed Size (px)
Citation preview
8/18/2019 K122-C2-DS-65-290_A.pdf
1/5
A 2013-08-23 C.C.N R.A.Z. C.Q.S
C0 2013-08-13 C.C.N R.A.Z. C.Q.S
B0 2013-07-05 C.C.N R.A.Z. C.Q.S
A0 2012-11-17 V.B.C. R.A.Z. P.L.CH.
Rev Date Prepared by Checked by Approved by
Review
A
Technical person incharge:
Issued for ReviewDescription
OHV Power Lines and Substations for CVPUE
Issued for Review
ABENGOA PERU
Document name:
Data Sheet
Guy Wires and Accessories
Document N°:
K122-C2-DS-65-290
Issued for Review
Issued for Review
8/18/2019 K122-C2-DS-65-290_A.pdf
2/5
Rev: A
Item Unit Required Offered
A
1 Guy wires
1.1 Manufacturer - Report
1.2 Breaking load kN (pounds) 120 (26,977)
1.3 Nominal diameter mm (inch) 12.9 (0.509)
1.4 Number and size of wires - 19 N0. 10
1.5 Mass kg (pounds) Report
2 Thimble clevis
2.1 Manufacturer - Report
2.2 Material Forged steel hot dip
galvanised
2.3 gr/m2 >= 600
2.4 Breaking load kN (pounds) 120 (26,977)
2.5 mm (inch) 20.64 (13/16")
2.6 Mass kg (pounds) Report
2.7 Dimensions mm Attach drawings
3 Preformed dead-ends
3.1 Manufacturer -
3.2 Material Forged steel hot dip
galvanised
3.3 gr/m2 >= 600
3.4 Minimum breaking load kN (pounds) 120 (26,977)
3.5 Nominal diameter of guy wire mm (inch) 12.9 (0.509)
3.6 Number of threads - Report
3.7 Mass kg (pounds) Report
3.8 Dimensions mm Attach drawings
4 Anchor rod
4.1 Manufacturer - Report
4.2 Length mm (feet) 2438 (8')
4.3 Diameter mm (inch) 25.4 (1")
4.4 Mass kg (pounds) Report
4.5 Minimum breaking load kN (pounds) 120 (26,977)
4.6 Material Forged steel hot dipgalvanised
4.7 Dimensions mm Attach drawings4.8 Nut - Report
5 Square washer 4" x 4"5.1 Manufacturer Report
5.2 Material Forged steel hot dip
galvanised
5.3 Wide mm (inch) 102 (4")
5.4 Thickness mm (inch) 9.5 (3/8")
5.5 Central hole mm (inch.) 28.6 (1 1/8")
5.6 Dimensions mm Attach drawings
6 Connecting link6.1 Manufacturer
6.2 Material Forged steel hot dip
galvanised6.3 gr/m2 >= 6006.4 Wide mm (inch) 7.94 (5/16")
6.5 Length mm (inch) 76.20 (3")
6.6 Thickness mm (inch) 304 (12")
6.7 Central hole mm (inch.) 26.9 (1 1/16")6.8 Dimensions mm Attach drawings
6.9 Breaking load kN (pounds) 120 (26,977)
7 Guy Protector steel6.1 Manufacturer - Report
6.2 Material Forged steel hot dip
galvanised
6.3 Length mm (feet) 2438.4 (8')
6.4 Mass kg (pounds) Report
Notes:
1.-2.-
Page
Document code:
Description
Data sheet
Guy Wires and Accessories for Task 6 TransmissionLine 69kV from CV Substation to Congata
Bolt diameter (To be coordinated with connectinglink)
The term"report" in the column "required", indicates that the bidder must inform the resquested feature.
The term "Attach drawings" in the column "required", indicates that the dimensions of the accessoriesare obtained from the structures drawings.
For phase conductor
Galvanization according to ASTM 153/153M
K122-C2-DS-65-290 (1 de 4)
Galvanization according to ASTM 153/153M
Galvanization according to ASTM 153/153M
K122-C2-DS-65-290_A
8/18/2019 K122-C2-DS-65-290_A.pdf
3/5
Rev: A
Page
Document code:
Data sheet
Guy Wires and Accessories for Task 6 TransmissionLine 69kV from CV Substation to Congata
B1 Guy wires
1.1 Manufacturer - Report
1.2 Breaking load kN (pounds) 90 (20,233)
1.3 Nominal diameter mm (inch) 11.28 (0.444)
1.4 Number of individual wires - 71.5 Mass kg (pounds) Report
2 Thimble clevis2.1 Manufacturer - Report
2.2 Material Forged steel hot dip
galvanised
2.3 gr/m2 >= 600
2.4 Breaking load kN (pounds) 90 (20,233)
2.5 mm (inch) 18 (11/16")
2.6 Mass kg (pounds) Report2.7 Dimensions mm Attach drawings
3 Preformed dead-ends3.1 Manufacturer -
3.2 Material Forged steel hot dip
galvanised3.3 gr/m2 >= 600
3.4 Minimum breaking load kN (pounds) 90 (20,233)3.5 Nominal diameter of guy wire mm (inch) 11.28 (0.444)3.6 Number of threads - Report
3.7 Mass kg (pounds) Report3,8 Dimensions mm Attach drawings
4 Anchor rod
4.1 Manufacturer - Report
4.4 Length mm (feet) 2438 (8')
4.5 Diameter mm (inch) 19 (3/4")
4.6 Mass kg (pounds) Report4.7 Minimum breaking load kN (pounds) 90 (20,233)
4.8 Material Forged steel hot dip
galvanised
4.9 Dimensions mm Attach drawings4.1 Nut - Report
5 Square washer 4" x 4"5.1 Manufacturer Report
5.2 Material Forged steel hot dip
galvanised
5.4 Wide mm (inch) 102 (4")
5.5 Thickness mm (inch) 9.5 (3/8")
5.6 Central hole mm (inch.) 21 (13/16")
5.7 Dimensions mm Attach drawings
6 Connecting link6.1 Manufacturer
6.2 Material Forged steel hot dip
galvanised
6.3 gr/m2 >= 600
6.4 Wide mm (inch) 6.35 (1/4")
6.5 Length mm (inch) 76.20 (3")
6.6 Thickness mm (inch) 241.3 (9 1/2")6.7 Central hole mm (inch.) 24 (15/16")
6.8 Dimensions mm Attach drawings
6.9 Breaking load kN (pounds) 90 (20,233)
7 Guy Protector steel6.1 Manufacturer - Report
6.2 Material Forged steel hot dip
galvanised6.3 Length mm (feet) 2438.4 (8')
6.4 Mass kg (pounds) Report
Notes:1.-
2.-
are obtained from the structures drawings.
Galvanization according to ASTM 153/153M
The term "Attach drawings" in the column "required", indicates that the dimensions of the accessories
Galvanization according to ASTM 153/153M
Galvanization according to ASTM 153/153M
The term"report" in the column "required", indicates that the bidder must inform the resquested feature.
K122-C2-DS-65-290 (2 de 4)
For OPGW optical fiber
Bolt diameter (To be coordinated with connectinglink)
K122-C2-DS-65-290_A
8/18/2019 K122-C2-DS-65-290_A.pdf
4/5
Rev: A
Item Unit Required Offered
A
1 Guy wires
1.1 Manufacturer - Report
1.2 Breaking load kN (pounds) 70 (15,737)1.3 Nominal diameter mm (inch) 8,71 (0.343)
1.4 Number and size of wires - 7 N0. 7
1.5 Mass kg (pounds) Report
2 Thimble clevis
2.1 Manufacturer - Report
2.2 Material Forged steel hot dip
galvanised
2.3 gr/m2 >= 600
2.4 Breaking load kN (pounds) 70 (15737)
2.5 mm (inch) 18(11/16")
2.6 Mass kg (pounds) Report
2.7 Dimensions mm Attach drawings
3 Preformed dead-ends
3.1 Manufacturer -
3.2 Material Forged steel hot dip
galvanised
3.3 gr/m2 >= 600
3.4 Minimum breaking load kN (pounds) 70 (15,737)
3.5 Nominal diameter of guy wire mm (inch) 8,71 (0.343)
3.6 Number of threads - Report
3.7 Mass kg (pounds) Report
3.8 Dimensions mm Attach drawings
4 Anchor rod
4.1 Manufacturer - Report
4.2 Length mm (feet) 2438 (8')
4.3 Diameter mm (inch) 16 (5/8")
4.4 Mass kg (pounds) Report4.5 Minimum breaking load kN (pounds) 70 (15,737)
4.6 Material Forged steel hot dip
galvanised
4.7 Dimensions mm Attach drawings
4.8 Nut Report
5 Square washer 4" x 4"
5.1 Manufacturer Report
5.2 Material Forged steel hot dip
galvanised
5.3 Wide mm (inch) 102 (4")
5.4 Thickness mm (inch) 9,5 (3/8")
5.5 Central hole mm (inch.) 17.5 (11/16")
5.6 Dimensions mm Attach drawings
6 Connecting link
6.1 Manufacturer
6.2 Material Forged steel hot dip
galvanised
6.3 gr/m2 >= 6006.4 Wide mm (inch) 6.35 (1/4")
6.5 Length mm (inch) 76.20 (3")
6.6 Thickness mm (inch) 241.3 (9 1/2")
6.7 Central hole mm (inch.) 24 (15/16")6.8 Dimensions mm Attach drawings
6.9 Breaking load kN (pounds) 70 (15,737)
7 Guy Protector steel6.1 Manufacturer - Report
6.2 Material Forged steel hot dip
galvanised
6.3 Length mm (feet) 2438.4 (8')
6.4 Mass kg (pounds) Report
Notes:
1.-
2.-
Technical Specifications
Guy Wires and Accessories for Task 7.1 DistributionLine 34.5kV from M.H Substation to Primary Crushers
Page
Document code:
K122-C2-DS-65-290 (3 de 4)
Galvanization according to ASTM 153/153M
Galvanization according to ASTM 153/153M
Galvanization according to ASTM 153/153M
The term"report" in the column "required", indicates that the bidder must inform the resquested feature.
The term "Attach drawings" in the column "required", indicates that the dimensions of the accessoriesare obtained from the structures drawings.
Bolt diameter (To be coordinated with connectinglink)
Description
For phase conductor
K122-C2-DS-65-290_A
8/18/2019 K122-C2-DS-65-290_A.pdf
5/5
Rev: A
Technical Specifications
Guy Wires and Accessories for Task 7.1 DistributionLine 34.5kV from M.H Substation to Primary Crushers
Page
Document code:
B
1 Guy wires1.1 Manufacturer - Report
1.2 Breaking load kN (pounds) 90 (20,233)1.3 Nominal diameter mm (inch) 11.28 (0.444)
1.4 Number of individual wires - 7
1.5 Mass kg (pounds) Report
2 Thimble clevis
2.1 Manufacturer - Report
2.2 Material Forged steel hot dip
galvanised
2.3 gr/m2 >= 600
2.4 Breaking load kN (pounds) 90 (20,233)
2.5 mm (inch) 18(11/16")
2.6 Mass kg (pounds) Report
2.7 Dimensions mm Attach drawings
3 Preformed dead-ends3.1 Manufacturer -
3.2 Materia l Forged steel hot dip
galvanised
3.3 gr/m2 >= 6003.4 Minimum breaking load kN (pounds) 90 (20,233)
3.5 Nominal diameter of guy wire mm (inch) 11.28 (0.444)
3.6 Number of threads - Report
3.7 Mass kg (pounds) Report3,8 Dimensions mm Attach drawings
4 Anchor rod4.1 Manufacturer - Report
4.4 Length mm (feet) 2438 (8')
4.5 Diameter mm (inch) 19 (3/4")
4.6 Mass kg (pounds) Report4.7 Minimum breaking load kN (pounds) 90 (20,233)
4.8 Material Forged steel hot dip
galvanised
4.9 Dimensions mm Attach drawings4.1 Nut Report
5 Square washer 4" x 4"5.1 Manufacturer Report
5.2 Material Forged steel hot dip
galvanised
5.4 Wide mm (inch) 102 (4")
5.5 Thickness mm (inch) 9.5 (3/8")
5.6 Central hole mm (inch.) 21 (13/16")
5.7 Dimensions mm Attach drawings
6 Connecting link6.1 Manufacturer
6.2 Material Forged steel hot dip
galvanised
6.3 gr/m2 >= 600
6.4 Wide mm (inch) 6.35 (1/4")6.5 Length mm (inch) 76.20 (3")
6.6 Thickness mm (inch) 241.3 (9 1/2")
6.7 Central hole mm (inch.) 24 (15/16")6.8 Dimensions mm Attach drawings
6.9 Breaking load kN (pounds) 90 (20,233)
7 Guy Protector steel6.1 Manufacturer - Report
6.2 Material Forged steel hot dip
galvanised
6.3 Length mm (feet) 2438.4 (8')
6.4 Mass kg (pounds) Report
Notes:
1.-
2.-
Galvanization according to ASTM 153/153M
K122-C2-DS-65-290 (4 de 4)
are obtained from the structures drawings.
The term "Attach drawings" in the column "required", indicates that the dimensions of the accessories
For OPGW optical fiber
Galvanization according to ASTM 153/153M
The term"report" in the column "required", indicates that the bidder must inform the resquested feature.
Galvanization according to ASTM 153/153M
Bolt diameter (To be coordinated with connectinglink)
K122-C2-DS-65-290_A